Anda di halaman 1dari 4

Short-Circuit Tests

on Bundle Conductors
A. L. M A L M S T R O M L. G. G I F F O R D J. O. S M I T H
MEMBER AIEE ASSOCIATE MEMBER AIEE

Corona losses in transmission lines may be re A n o t h e r m e t h o d by w h i c h c o r o n a losses c a n b e re


duced by the use of two or more conductors per d u c e d is to use m o r e t h a n o n e c o n d u c t o r per p h a s e .
phase, an arrangement often referred to as bun T h i s a r r a n g e m e n t , referred to as a b u n d l e c o n d u c t o r ,
dle conductors. Tests made to determine stresses u s u a l l y consists of t w o , three, or f o u r cables, w i t h the
on spacers between these conductors are de t w i n type m o s t p r e v a l e n t . F o r a g i v e n v o l t a g e the in
scribed. d i v i d u a l c o n d u c t o r s i n a b u n d l e are smaller as the
n u m b e r of c o n d u c t o r s is increased. T h e y are electri
cally c o n n e c t e d to o n e a n o t h e r a n d are u s u a l l y spaced

L
O N G D I S T A N C E S a n d ever-increasing difficulties f r o m 14 t o 18 inches.
i n securing rights of w a y for t r a n s m i s s i o n lines A d v a n t a g e s of a b u n d l e c o n d u c t o r o v e r a s i n g l e con
J h a v e m a d e it necessary to resort to h i g h e r operat d u c t o r of the s a m e total cross s e c t i o n are
i n g v o l t a g e s . T h e D e t r o i t E d i s o n C o m p a n y is presently
1. R e d u c e d c o r o n a losses a n d , therefore, less r a d i o
c o n s t r u c t i n g a n e x t r a h i g h - v o l t a g e l i n e . S u c h l i n e s pre
influence.
sent a p r o b l e m of c o n d u c t o r d e s i g n b e c a u s e of corona
2. Greatly r e d u c e d r e a c t a n c e a n d increased system
losses a n d r a d i o interferences. T h e s e losses can b e re
stability.
d u c e d by increasing the c o n d u c t o r d i a m e t e r , thereby
3. R e d u c e d i n d u c t a n c e a n d i n c r e a s e d c a p a c i t a n c e , re
l o w e r i n g the dielectric stress at the c o n d u c t o r surface.
s u l t i n g i n a n increase i n the p o w e r transfer capacity of
the line.

Electrical forces o n t h e b u n d l e consist of electro


m a g n e t i c a t t r a c t i o n , w h i c h is p r o p o r t i o n a l to t h e s q u a r e
of the current, a n d electrostatic r e p u l s i o n , w h i c h is
p r o p o r t i o n a l to t h e s q u a r e of t h e v o l t a g e . T h e electro
m a g n e t i c force p r e d o m i n a t e s at h e a v y current, a n d w h e n
large e n o u g h (short-circuit c o n d i t i o n s ) t h e c o n d u c t o r s
w i l l c o n t a c t e a c h o t h e r . Spacers b e t w e e n t h e c o n d u c t o r s ,
i n s t a l l e d a p p r o x i m a t e l y 2 0 0 feet apart i n t h e s p a n , are
l e q u i r e d t o m a i n t a i n b u n d l e s p a c i n g . T h e s e spacers are
expected to prevent the conductors from wrapping
a r o u n d e a c h o t h e r u n d e r fault c o n d i t i o n s a n d a l s o w h e n
there is i n t e r m i t t e n t d r o p p i n g of ice. H o w e v e r , the c o n
d u c t o r s m a y c o n t a c t e a c h o t h e r b e t w e e n spacers u n l e s s
they are i n s t a l l e d at closer intervals.
I t is difficult, if n o t i m p o s s i b l e , t o c a l c u l a t e t h e forces
resisted by the spacers u n d e r short-circuit c o n d i t i o n s .
Fig. 1 . Preformed type of spacer mounted on test s p a n . B e c a u s e n o satisfactory test d a t a w e r e a v a i l a b l e o n these
spacers a n d the forces to w h i c h they are s u b j e c t e d u n d e r
faults, it was d e c i d e d to set u p a test s p a n t o m e a s u r e
V a r i o u s m e t h o d s h a v e b e e n u s e d for i n c r e a s i n g t h e
t h e m . S p e c i a l i n s t r u m e n t s w e r e d e s i g n e d to m e a s u r e
d i a m e t e r w i t h o u t i n c r e a s i n g the a m o u n t of m e t a l ; for
these forces. I n a d d i t i o n , t h e a c t i o n a n d p e r f o r m a n c e of
e x a m p l e , t h e use of h o l l o w c o n d u c t o r s a n d e x p a n d e d
v a r i o u s types of spacers u n d e r short-circuit c o n d i t i o n s
c o n d u c t o r s . O n e type of the latter has a filler, s u c h as
w e r e w i t n e s s e d a n d r e c o r d e d o n film w i t h m o t i o n pic
p a p e r or h e m p , b e t w e e n t h e steel core a n d t h e o u t e r
t u r e cameras.
layers of a l u m i n u m .
TEST EQUIPMENT AND PROCEDURE

Full text of District paper 58-508, presented at the AIEE Great Lakes Dis Test Equipment. I n o r d e r t o test t h e l i n e spacers
trict Meeting, East Lansing, Mich., May 5-7, 1958. u n d e r s i m u l a t e d field c o n d i t i o n s , a special 4 0 0 - f o o t
A. L. Malmstrom, L. G. Gifford, and J. O. Smith are with The Detroit
Edison Company, Detroit, Mich. single-phase b u n d l e s p a n w a s e r e c t e d of t w o 9 5 4 - M C M
The authors wish to acknowledge the valuable assistance of A. E. Featham, ( t h o u s a n d circular m i l ) 4 5 / 7 A C S R ( a l u m i n u m c a b l e ,
R. W. Burke, and J. Howe of The Detroit Edison Company in the pre
paration of the field setup and instrumentation for the tests described. steel r e i n f o r c e d ) c o n d u c t o r s s p a c e d 16 i n c h e s apart. T h e

724 Malmstrom, Gifford, SmithShort-Circuit Tests ELECTRICAL ENGINEERING


return l i n e was offset h o r i z o n t a l l y 6 feet a n d vertically
13 feet a n d was of t h e s a m e c o n s t r u c t i o n T h e tension
in each c o n d u c t o r at the t i m e of testing v a r i e d f r o m
6,500 p o u n d s t o 7,000 p o u n d s b e c a u s e of c h a n g i n g tem
peratures d u r i n g the day of the test. T o approximate
actual c o n d i t i o n s , a spacer was p l a c e d i n t h e center of
the 400-foot span w i t h t h e e n d s of t h e s p a n rigidly
a n c h o r e d a n d c o n s i d e r e d as spacers. T h i s w a s e q u i v a
lent to the spacer a r r a n g e m e n t b e i n g c o n s i d e r e d for
future l i n e c o n s t r u c t i o n . I n Fig. 1, o n e t y p e of spacer
that was tested is s h o w n m o u n t e d o n the test l i n e .
T e s t current was o b t a i n e d by u s i n g a spare 24-kv
p o s i t i o n at W a r r e n S t a t i o n ( o n e of t h e h i g h e r sources
of fault current) to feed four 3,333-kva, 2 4 / 4 . 8 - k v single-
p h a s e transformers c o n n e c t e d i n parallel. T h e trans
formers were fed from t h e 24-kv p o s i t i o n by m e a n s of
3 0 0 feet of 3 5 0 - M C M cable. T h e s e c o n d a r y of t h e bank Fig. 3 . Spacer incorporating s t r a i n - g a u g e dynamometer.

of transformers was c o n n e c t e d t o t h e test l i n e t h r o u g h a


special secondary s w i t c h . T h e c l o s i n g of t h e s e c o n d a r y
s w i t c h w a s c o n t r o l l e d by a s y n c h r o n o u s t i m e r which
A series of a d d i t i o n a l tests w e r e p e r f o r m e d i n w h i c h
closed t h e s w i t c h at v o l t a g e zero t o o b t a i n maximum
several spacers of v a r i o u s d e s i g n w e r e e a c h i n s t a l l e d at
t h e c e n t e r of t h e test s p a n a n d s u b j e c t e d t o f a u l t cur
rents of v a r i o u s m a g n i t u d e s . A t least o n e test was con
d u c t e d o n e a c h type of spacer at t h e m a x i m u m current
of 18,500 s y m m e t r i c a l a m p e r e s , w i t h m a x i m u m offset.
No force measurements were made in these tests.
M e a s u r e m e n t s w e r e m a d e of the d i m e n s i o n b e t w e e n t h e
c o n d u c t o r s at t h e spacer l o c a t i o n t o d e t e r m i n e w h e t h e r
p e r m a n e n t d e f o r m a t i o n o c c u r r e d i n t h e spacers. T h e s e
spacers, e x c e p t the p r e f o r m e d type, are s h o w n i n Fig. 2.
T w o o t h e r types of spacers w h i c h w e r e n o t tested are
also shown.

Force-Measuring Instrumentation, T w o types of force-


m e a s u r i n g d e v i c e s w e r e e m p l o y e d t o m e a s u r e the forces
i m p o s e d u p o n a spacer by short-circuit currents. O n e
Fig. 2 . Some of the difFerent types of spacers a v a i l a b l e .
was a strain-gauge t y p e d y n a m o m e t e r i n c o r p o r a t e d i n a

current offset. T h e 24-kv breaker was p r e t r i p p e d so that


the d u r a t i o n of t h e fault current w a s a p p r o x i m a t e l y five
cycles, w h i c h is t h e e x p e c t e d breaker t i m e p l u s relay
time o n the e x t r a h i g h - v o l t a g e l i n e . T h e m a g n i t u d e of
the test current was varied by c h a n g i n g t h e n u m b e r of
transformers c o n n e c t e d i n parallel. T h e p o i n t of volt
age at w h i c h the secondary s w i t c h was c l o s e d a n d t h e
fault current were recorded by m e a n s of a n o s c i l l o g r a p h .

Test Procedure, A total of s i x tests w e r e c o n d u c t e d , in


w h i c h m e a s u r e m e n t s were m a d e of force o n a n instru
m e n t e d spacer i n s t a l l e d at the center of the s p a n . I n all
b u t o n e of these tests, a strain-gauge d y n a m o m e t e r was
e m p l o y e d t o record t h e c o m p r e s s i v e force d u e t o electro
m a g n e t i c a t t r a c t i o n b e t w e e n the c o n d u c t o r s a n d t e n s i o n
due to conductor rebound. T h e s e measurements were
m a d e at four v a l u e s of current, a p p r o x i m a t e l y 8,000,
13,000, 15,500, a n d 18,500 s y m m e t r i c a l a m p e r e s , respec
tively. A n a d d i t i o n a l test was s u b s e q u e n t l y c o n d u c t e d ,
at a current of a p p r o x i m a t e l y 18,500 a m p e r e s , i n w h i c h
the m a x i m u m c o m p r e s s i v e force was m e a s u r e d by m e a n s Fig. 4 . V i e w of s t r a i n - g a u g e dynamometer s h o w i n g details
of a deflection g a u g e . of magnetic shielding.

AUGUST 1958 Malmstrom, Gifford, Smith-Short-Circuit Tests 725


m o d i f i e d spacer. B y r e c o r d i n g t h e o u t p u t of this 1.58 t i m e s t h e s y m m e t r i c a l v a l u e . M a x i m u m c u r r e n t o b
d y n a m o m e t e r o n a n o s c i l l o g r a p h , a c o m p l e t e record of t a i n e d i n this test w a s 18,500 s y m m e t r i c a l a m p e r e s w i t h
t h e force t h r o u g h o u t a g i v e n test c o u l d b e o b t a i n e d . T h e a v e r a g e offset of 1.4 t i m e s t h e s y m m e t r i c a l v a l u e .
s e c o n d type was a p r o v i n g - r i n g t y p e deflection g a u g e T h e results of t h e s i x tests i n w h i c h force w a s meas
that m e a s u r e d o n l y t h e m a x i m u m c o m p r e s s i v e force o n u r e d are s h o w n i n F i g . 6, s h o w i n g a p l o t of t h e c o m p r e s
the spacer. sive force o n t h e spacer a g a i n s t s y m m e t r i c a l current.
T h e m a x i m u m force r e c o r d e d was 4 8 5 p o u n d s , corres
p o n d i n g to a s y m m e t r i c a l c u r r e n t of 18,500 a m p e r e s .
A typical o s c i l l o g r a p h record of current, spacer force,
a n d t h e p o i n t o n t h e v o l t a g e w a v e at w h i c h t h e fault
was a p p l i e d is s h o w n i n F i g . 7. T h e s y m m e t r i c a l current
for this test w a s 15,500 a m p e r e s . T h e current w a s in
t e r r u p t e d after 4i/^ cycles. A p p r o x i m a t e l y 0.04 s e c o n d
after i n t e r r u p t i o n of t h e current, t h e c o n d u c t o r s con
tacted at l o c a t i o n s b e t w e e n t h e spacer a n d t h e e n d s of
the s p a n . T h i s e v e n t is characterized by h i g h - f r e q u e n c y
Fig. 5. Deflection g a u g e used for measurements of m a x i m u m o s c i l l a t i o n s of short d u r a t i o n o n t h e force trace. T h e
compressive force on spacer. m a x i m u m c o m p r e s s i v e force of 3 3 0 p o u n d s o c c u r r e d
0.07 s e c o n d later. T h e s u b s e q u e n t r e b o u n d of t h e con
d u c t o r s p r o d u c e d a m a x i m u m tensile force of 3 2 0
T h e m o d i f i e d spacer c o n t a i n i n g t h e strain-gauge
p o u n d s o n t h e spacer. I n all tests, t h e m a x i m u m t e n s i o n
d y n a m o m e t e r is s h o w n , as it w a s i n s t a l l e d b e t w e e n t h e
i m p o s e d b y r e b o u n d of t h e c o n d u c t o r s w a s a p p r o x i
c o n d u c t o r s , i n Fig. 3. A v i e w of t h e d y n a m o m e t e r w i t h
m a t e l y e q u a l t o t h e m a x i m u m c o m p r e s s i v e force o n t h e
t h e s h i e l d i n g partially r e m o v e d is s h o w n i n F i g . 4. T h e
spacer.
force-sensing e l e m e n t is a m a c h i n e d steel r i n g t o w h i c h
D u r i n g t h e p e r i o d of c u r r e n t flow, t h e c o m p r e s s i v e
four resistance type strain g a u g e s are b o n d e d . T h e strain
force o n t h e spacer increased at a n a p p r o x i m a t e l y u n i
g a u g e s are c o n n e c t e d t o g e t h e r i n a p u s h - p u l l type b r i d g e
f o r m rate. T h e 60-cycle v a r i a t i o n s v i s i b l e o n t h e force
circuit, such that t h e b r i d g e o u t p u t v o l t a g e is propor
trace of t h e o s c i l l o g r a p h record prior t o i n t e r r u p t i o n of
t i o n a l to e i t h e r tensile or c o m p r e s s i v e l o a d i n g o n t h e
t h e c u r r e n t represent s m a l l s p u r i o u s i n d u c e d currents i n
ring.
O n e p r o b l e m e n c o u n t e r e d w h e n strain g a u g e s are e m
p l o y e d i n t h e presence of e l e c t r o m a g n e t i c fields of in 600|
tensity is that of e l i m i n a t i n g large s p u r i o u s 60-cycle CD
currents i n t h e strain-gauge circuit. S u c h effects w e r e
m i n i m i z e d i n this case by t h e p r o v i s i o n of i/^-inch thick
steel s h i e l d i n g a r o u n d t h e strain g a u g e s a n d w i r i n g . T h e w A00[
d e t a i l s of t h e s h i e l d i n g c a n b e seen i n F i g . 4. T h e
d y n a m o m e t e r was c o n n e c t e d to t h e r e c o r d i n g e q u i p m e n t
Fig. 6. Compressive 300F
by m e a n s of 3 0 0 feet of s h i e l d e d m i c r o p h o n e cable. T h e force on spacer v s
cable was e n c l o s e d i n thin-wall c o n d u i t i n t h e p r o x i m i t y fault current.
g 2001
of the c o n d u c t o r s as a further p r e c a u t i o n against spuri

ous pickup. LJ
lOOh
T h e deflection g a u g e is s h o w n i n Fig. 5. T h i s g a u g e
was constructed w i t h a shaft e x t e n d i n g i n w a r d f r o m o n e 8
side of a n 8-inch d i a m e t e r steel r i n g a n d c e n t e r e d i n a 12 16 20
h o l l o w t u b e a t t a c h e d to t h e o t h e r side of t h e ring. Prior FAULT C U R R E N T ,
SYMMETRICAL KtLOAMPERES
to a test, a s l i d i n g collar o n t h e shaft was p o s i t i o n e d i n
c o n t a c t w i t h the e n d of t h e h o l l o w tube. C o m p r e s s i v e
l o a d i n g o n t h e r i n g c a u s e d t h e s l i d i n g collar t o b e dis t h e strain-gauge circuit, t h e result of i m p e r f e c t m a g n e t i c
placed toward a fixed collar o n t h e shaft. T h e m a x i m u m s h i e l d i n g of t h e d y n a m o m e t e r .
d i s p l a c e m e n t was d e t e r m i n e d by i n s i d e m i c r o m e t e r W i t h t h e e x c e p t i o n of o n e type, all t h e spacers that
m e a s u r e m e n t s of t h e d i m e n s i o n b e t w e e n t h e s l i d i n g a n d w e r e tested w e r e f o u n d to h a v e n o n o t i c e a b l e d e f o r m a
fixed collars. T h e . m a x i m u m c o m p r e s s i v e l o a d w a s de t i o n from t h e forces i m p o s e d as t h e result of f a u l t cur
t e r m i n e d from a c a l i b r a t i o n r e l a t i n g l o a d a n d deflection rents. T h e spacer that w a s unsatisfactory c o n s i s t e d of a
of t h e s l i d i n g collar. l e n g t h of s t r a n d e d c a b l e b e t w e e n t w o c l a m p s . T h i s type
p e r m i t t e d t h e t w o c o n d u c t o r s t o c o n t a c t e a c h o t h e r at
TEST RESULTS t h e spacer c l a m p s w h e n s u b j e c t e d t o t h e c o m p r e s s i v e
T H E EXTRAHIGH-VOLTAGE L I N E is e x p e c t e d t o h a v e a force a c c o m p a n y i n g t h e h i g h c u r r e n t flow. A f t e r o n e
m a x i m u m f a u l t current of a p p r o x i m a t e l y 20,000 sym m a x i m u m current test, t h e s t r a n d e d c a b l e of this spacer
m e t r i c a l a m p e r e s w i t h a m a x i m u m m o m e n t a r y offset of was p e r m a n e n t l y d e f o r m e d .

726 Malmstrom, Gifford, SmithShort-Circuit Tests ELECTRICAL ENGINEERING


A n o t h e r spacer, o f t h e p r e f o r m e d type, w a s s u b j e c t e d f o r m e d s p a c e r of t h e s a m e t y p e w a s s u b j e c t e d t o t w o
to t h e forces r e s u l t i n g f r o m test currents of 13,000 a n d h i g h - c u r r e n t tests, w i t h n o n o t i c e a b l e d e f o r m a t i o n .
16,000 amperes, followed b y three tests at 18,500
CONCLUSIONS

1. T h e m a x i m u m c o m p r e s s i v e force e x e r t e d o n 16-
i n c h spacers i n s t a l l e d a t 200-foot i n t e r v a l s is of t h e o r d e r
of 5 0 0 p o u n d s for f a u l t currents of a p p r o x i m a t e l y 20,000
a m p e r e s . T h e force increased approximately at t h e
s q u a r e of current.
2. T h e t e n s i l e force e x e r t e d o n spacers as t h e result of
c o n d u c t o r r e b o u n d is a p p r o x i m a t e l y e q u a l t o t h e c o m
pressive force c a u s e d b y e l e c t r o m a g n e t i c attraction.
3. A l l e x c e p t o n e of t h e spacers that w e r e tested w e r e
Fig. 7. Typical oscillograph record of force variation.
f o u n d a d e q u a t e , f r o m a s t r e n g t h s t a n d p o i n t , t o resist t h e
forces i m p o s e d b y short-circuit currents of u p t o a p p r o x i
amperes each w i t h m a x i m u m offset. After these tests, mately 20,000 symmetrical amperes having maximum
the s p a c i n g of t h e c o n d u c t o r s at t h e s p a c e r l o c a t i o n w a s offset. T h e t y p e t h a t w a s n o t a d e q u a t e c o n s i s t e d of a
r e d u c e d f r o m 16 i n c h e s t o 15%6 i n c h e s . A n o t h e r pre p i e c e of s t r a n d e d c a b l e b e t w e e n t w o c l a m p s .

Standard Basic Impulse


Insulation Levels
AIEE C O M M I T T E E REPORT

Since the issue of report on basic impulse in required. Also, the trend toward the use of higher
sulation levels in 1941, additional information transmission voltages makes it desirable to determine
regarding system grounding practices and maxi whether higher values should b e added.
mum operating voltages has been made avail SCOPE
able. This new report provides recommended
values applicable to equipment for use on THIS REPORT p r o v i d e s recommended standard BIL

grounded and ungrounded a-c supply systems. values applicable to e q u i p m e n t for use o n grounded
o r u n g r o u n d e d a-c s u p p l y systems. T h e s e basic i m p u l s e
i n s u l a t i o n levels are t h o s e w h i c h h a v e g e n e r a l applica

I N 1951, t h e A I E E - E E I - N E M A J o i n t C o m m i t t e e o n t i o n a n d are c o n s i d e r e d s u i t a b l e for a d o p t i o n as A m e r i


I n s u l a t i o n C o o r d i n a t i o n , after m o r e t h a n 10 years can Standard values.
of study, issued a r e p o r t ( E d i s o n Electric I n s t i t u t e OBJECTIVES
P u b l i c a t i o n N o . H - 8 ; N a t i o n a l Electrical M a n u f a c t u r e r s
A s s o c i a t i o n P u b l i c a t i o n 1 0 9 ; Electrical Engineering, INSULATION CO-ORDINATION has for its objectives the

vol. 6 0 , M a r c h 1 9 4 1 , p . 121) w h i c h r e c o m m e n d e d a e s t a b l i s h m e n t of s t a n d a r d B I L v a l u e s a n d t h e specifica


series of s t a n d a r d basic i m p u l s e i n s u l a t i o n levels ( B I L s ) , t i o n of i n s u l a t i o n s t r e n g t h s of electric e q u i p m e n t i n
30 k v t h r o u g h 1,550 k v , i n c l u s i v e . T h e s e r e c o m m e n d e d terms of s t a n d a r d i n s u l a t i o n levels, w h e n s u c h e q u i p
standard B I L s h a v e r e c e i v e d w i d e a c c e p t a n c e a n d are m e n t is a p p l i e d a m o n g t h e preferred n o m i n a l system
serving a very u s e f u l p u r p o s e . H o w e v e r , s i n c e t h e 1941 voltages (taking into consideration usual operating con
report w a s issued, a d d i t i o n a l d a t a h a v e b e e n m a d e d i t i o n s a n d v a r i a t i o n s i n system g r o u n d i n g practices).
available r e g a r d i n g system g r o u n d i n g practices a n d I t is e x p e c t e d t h a t t h e s t a n d a r d B I L v a l u e s w i l l c o n -
m a x i m u m o p e r a t i n g voltages. I n a d d i t i o n , there h a s
A report by the AIEE Standards Co-ordination Committee No. 8, recom-
been substantial operating experience w i t h e q u i p m e n t mended for publication by the AIEE Standards Committee.
h a v i n g r e d u c e d i n s u l a t i o n strengths. T h e s e d a t a a n d The personnel of the AIEE Standards Co-ordinating Committee No. 8
are: J. H. Foote (chairman), H. W. Collins, I. W. Gross, E. M. Hunter,
e x p e r i e n c e s w a r r a n t a r e - e x a m i n a t i o n o f these B I L T. G. A. Sillers, E. C. Starr, J. J. Taylor, C. F. Wagner, Byron Evans.
K. E. Hapgood, K. H. Kidd, S. C. Killian, J. R. Meador, C. W. MiUer,
values to determine whether changes o r additions are J. M. Towner, and F. J. Vogel.

A U G U S T 1958 AIEE Committee ReportStandard Basic Impulse Insulation Levels 727

Anda mungkin juga menyukai