BACnet Controllers:
ECB-203 Series, ECB-300 Series, ECB-400 Series, and ECB-600 Series
1. Product Description
This document describes the hardware installation procedures for the
ECB series BACnet controllers.
The Distech Controls BACnet controllers are designed to control and
monitor various HVAC equipment such as roof top units, air handling
units as well as chillers, boilers, and central plant applications.
Moreover, these controllers are suitable for any lighting control and
power measurement applications. This product line includes the
following controllers: ECB-203, ECB-300, ECB-400 Series, ECB-600
Series.
For controllers equipped with an operator interface (ECB-x50 models),
refer to the ECL-x50 and ECB-x50 Series Controller User Guide for
how to use the this interface.
The ECB-600 Series are compatible with the IO Extension Module
product line, which includes the following modules: ECx-400, ECx-410,
and ECx-420 (refer to the ECx-400 series IO Extension Module
Hardware Installation Guide).
Each controller uses the BACnet MS/TP LAN communication
protocol.
This document describes the hardware installation procedures for the
following controllers: ECB-203 Series, ECB-300 Series, ECB-400
Series, and ECB-600 Series controllers only.
These controllers are all built on a similar platform, but
have different numbers of inputs and outputs.
Moreover, each individual model has different amounts
of digital and/or universal outputs. For more
information on the specific layout and functionality of
each controller, please refer to their individual
datasheets and user guides.
The following controllers are housed in small
enclosures: ECB-203 Series and ECB-300 Series.
The following controllers are housed in large
enclosures: ECB-400 Series and ECB-600 Series.
www.distech-controls.com 1/14
2. General Installation Requirements - Power type cables (i.e. for power, 3-wire voltage and current inputs
and outputs) should be kept apart from other types of wiring to
For proper installation and subsequent operation of each controller, avoid any ambient noise transmission to other wires.
pay special attention to the following recommendations: - The board connectors accept wires or flat cables ranging from 22 to
14AWG (0.644 to 1.630mm diameter) per pole. However, power
- It is recommended that the controller(s) be kept at room
cables must be between 18 and 14AWG (1.024 to 1.630mm
temperature for at least 24 hours before installation to allow any
diameter).
condensation that may have accumulated due to low temperature
during shipping/storage to evaporate. - Do not connect the universal inputs, analog/digital outputs or
common terminals to earth or chassis ground (unless stated
- Upon unpacking the product, inspect the contents of the carton for
otherwise).
shipping damages. Do not install damaged controllers.
- Avoid areas where corroding, deteriorating or explosive vapors,
- Keep all wires away from high speed data transmission cables (for
example, Ethernet, etc.).
fumes or gases may be present.
- Allow for proper clearance around the controllers enclosure, wiring
- Keep input and output wiring in conduits, trays or close to the
building frame if possible.
terminals, and MAC Addressing switches to provide easy access for
hardware configuration and maintenance, and to ventilate heat
generated by the controller. 4. Mounting Instructions
- Orient the controller with the ventilation slots and power
supply/output terminal block connectors towards the top to permit Each controller can be mounted on a DIN rail to speed up the
proper heat dissipation. When installed in an enclosure, select one installation procedure. They are also equipped with two mounting holes
that provides sufficient surface area to dissipate the heat generated 0.25 x 0.165 (6.35mm x 4.191mm). The controller can be mounted in
by the controller and by any other devices installed in the enclosure. a panel or on a wall by using appropriate screw types (use sheet
A metal enclosure is preferred. If necessary, provide active cooling metal, thread forming, or self-tapping screws accordingly).
for the enclosure.
DIN Rail-Mounted Installation
- The controllers datasheet specifies the power consumption
(amount of heat generated), the operating temperature range, and 1. Ensure the DIN rail is properly mounted on the wall.
other environmental conditions the controller is designed to operate 2. Simply clip controller onto the DIN rail.
under.
- Ensure that all equipment is installed according to local, regional,
and national regulations.
- The controllers plastic enclosure has a back plate that is separable
from the front plate allowing the back plates (with the connectors) to
be shipped directly to the installation site while all the engineering is
done in the office.
- Do not drop the controller or subject it to physical shock.
- If the controller is used and/or installed in a manner not specified by
Distech Controls, the functionality and the protection provided by
Figure 4-1: DIN rail-mounted controller
the controller may be impaired.
Wall-Mounted Installation
Any type of modification to any Distech Controls product 1. Open the controller by separating the front and back plate while
will void the products warranty. pressing on the side clips.
2. Use the back plates mounting holes to mark the location of any
holes that need to be drilled.
Take special care to keep the front and back plate 3. Drill the holes.
aligned when separating and joining them. 4. Clean the surface and mount the controller using the appropriate
Before installation of the Wireless Receiver, verify that screw types.
local communication regulations allow the installation
of wireless devices and available frequencies to be
supported in your area. Refer to the Open-to-
Wireless Solution Guide for more information.
- All wiring must comply with electrical wiring diagrams as well as Figure 4-2: Wall-mounted controller
national and local electrical codes.
- To connect the wiring to a controller, use the terminal connectors. It
is recommended to remove the front plate from the back plate to
facilitate the wiring process, however it is possible to do all wiring
with the front and back plates together. Use a small flat screwdriver
to tighten the terminal connector screws once the wires have been
inserted.
- Comply with all BACnet network and power supply guidelines
outlined in the Network Guide.
2/14
5. Controller Dimensions 6. Power Wiring
Voltage: 24VAC/DC; 15%, Class 2
This is a Class 2 Product. Use a Class 2 transformer only
(rated at 100VA or less at 24VAC) to power the
controller(s).
Fuse: 4 A Max.
Controller 1 Fast Acting
24V AC
24V COM 24 VAC AC
Transformer
Controller 2
24V AC Electrical System Ground
24V COM - At Transformer Only
Controller 2
24V AC/DC Electrical System Ground
24V COM - At Power Supply Only
Figure 5-1: (From top to bottom) rear view of the large enclosure,
rear view of the small enclosure and side view of the Figure 6-2: Power wiring DC
large and small enclosure
3/14
7. Configuration Jumper Location and Table 8-1: Controller Input Support
Identification Controller Fast and Slow Pulse Inputs Current Input
support Jumper
Controllers have the following onsite configurable jumpers. 50Hz: 10ms 1Hz: 500ms support:
minimum minimum 0 to 10VDC /
Wireless
Port
ON/OFF (Fast ON/OFF (Slow 0 to 20mA
Pulse) Pulse)
ECB-203 None UI1 to UI6 None
ECB-300 UI1 to UI4 UI5 to UI10 Yes; see
BACnet MS/TP Network EOL
EOL Off
Termination
EOL On
ECB-400 Series UI1 to UI4 UI5 to UI12 Figure 8-8 and
(Disabled)* (Enabled)
ECB-600 Series UI1 to UI4 UI5 to UI16 Section 7.
Net Port
Subnet
Port
For a wire length less than 75 (23m), either a shielded
* Factory-default positions
or unshielded 18AWG wire may be used.
For a wire up to 200 (61m) long, a shielded 18AWG
Figure 7-1: ECB-203 Controller Jumper Locations wire is recommended.
Wireless
The shield of the wire should be grounded on the
Port
controller side and the shield length should be kept as
short as possible.
Universal Outputs (UO)
0-10V / 0-20mA Select
Wiring Digital Inputs
This input configuration is used to monitor digital dry contacts, as well
0-10V 0-20mA
BACnet MS/TP Network Board
Figure 8-1: Digital input Digital dry contact (NO & NC)
Wiring Resistive Inputs
Subnet
* Factory-default positions
Detectors (RTD), thermistors such as 1000 RTDs to 10k type II and
Figure 7-2: ECB-300 Controller Jumper Locations III thermistors, as well as 10k and 100k potentiometers.
UIx To Analog-
RTD/
Wireless To-Digital
Port Thermistor
COM Converter
Each controller has physical connections for inputs (marked as UIx) Figure 8-4: Current input 2-wire transducer powered by the
that are configured in EC-gfxProgram. Each input can be configured controller
for digital, resistive, current, voltage, or pulse signals. Input types must
be configured properly in software to ensure proper input readings. Use the following configuration for a 2-wire, 0 to 20mA transducer
powered by an external 24 AC/DC power supply.
249 W
UIx
0-20mA - To Analog-
Transducer + To-Digital
COM Converter
24VDC
4/14
Use the following configuration for a 3-wire, 0 to 20mA transducer When using a pulse meter that requires more than 5VDC to operate, a
powered by an external 24 AC/DC power supply. Fast Pulse Input type (see Figure 8-12) must be used. An external
249 W
power supply is required to operate the pulse meter. For this, the
controllers built-in power supply may be used as shown in Figure 8-12,
+
UIx or by using an external power source (from 6VDC to 27VDC
0-20mA
Transducer
Common
COM
To Analog- maximum) as shown in Figure 8-13.
24VAC To-Digital
AC Converter
Controller
Suitable current-limiting resistor as
15VDC
recommended by the pulse meters
Figure 8-6: Current input 3-wire transducer, externally powered manufacturer (field supplied) To Pulse Count Accumulator
Use the following configuration for a transducer powered by its own UI1 to UI4 Trigger Threshold: 2.5Volts
Pulse Meter +
power source. Output -
Figure 8-8: Equivalent circuit for 0 to 20mA current input showing 9. Allure EC-Smart-Vue Wiring
the jumper setting for ECB-300, ECB-400 Series, and
ECB-600 Series controllers The Allure EC-Smart-Vue sensor is a communicating room
temperature sensor with backlit display and graphical menus. Connect
Wiring Voltage Inputs the Allure EC-Smart-Vue sensor to the SUBNET PORT modular
Voltage inputs have a range of 0 to 10VDC or 0 to 5VDC. Connect the connector of the controller with a standard Category 5e Ethernet patch
voltage input according to the following figure if a 3-wire 0 to 10V or 0 cable fitted with RJ-45 connectors. The Network Guide provides
to 5V transducer is being used. extensive information and requirements for the connection of Allure
UIx
EC-Smart-Vue sensors. It contains information about network topology
0-10V
Common
+
To Analog-
and length, cable type, setting the Subnet ID, etc. It can be
Transducer
24VAC COM To-Digital downloaded from our website. See also the Hardware Installation
AC Converter Guide supplied with the Allure EC-Smart-Vue sensor.
If you make your own patch cable, use Category 5e cable crimped with
Figure 8-9: Voltage input 3-wire transducer RJ-45 connectors either as T568A or T568B.
Connect the voltage input according to the following figure if the Do not crimp one connector as T568A and crimp the other
transducer is powered by its own power source. connector as T568B on the same cable.
UIx To Analog-
0-10V +
Transducer - To-Digital
COM Converter
Table 9-1: T568A and T568B Terminations for an RJ-45
Connector
Figure 8-10: Voltage input Transducer with its own power source Pin T568A (at both cable ends) T568B (at both cable ends)
Pair Color Pair Color
Wiring Pulse Inputs 1 3 2
The input must be wired according to the requirements of the white/green stripe white/orange stripe
connected pulse meter (Fast Pulse or Slow Pulse and Internal or 2 3 2
External supply type). See Table 8-1. green solid orange solid
3 2 3
Pulse Input types must be configured properly in software according to
white/orange stripe white/green stripe
how the pulse meter is powered (set the Internal / External Supply 4 1 1
Type). blue solid blue solid
Connect the pulse input according to the following figure for a pulse 5 1 1
meter that can pull-down a +5VDC supply with a 10K pull-up resistor white/blue stripe white/blue stripe
(Internal supply type). 6 2 3
orange solid green solid
Controller 7 4 4
5VDC Pulse Input
Equivalent
white/brown stripe white/brown stripe
Circuit 8 4 4
10K
UIx brown solid brown solid
Pulse Meter +
5/14
T568A T568B Line Switching Neutral Switching
Fuse: 4A Max. Fuse: 4A Max.
Fast Acting Fast Acting
Key:
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
24VAC 24VAC
24VAC AC 24VAC AC
24VCOM 24VCOM
Transformer Transformer
Controller Controller
Electrical Electrical
Stripe Solid System Ground System Ground
DOx A2 DOx A2
Load Load
Pair 3 Pair 1 Pair 2 Pair 4 Pair 2 Pair 1 Pair 3 Pair 4 Cx A1 Cx A1
24VAC AC 24VAC AC
Transformer Transformer
Figure 9-2: Pins on RJ-45 Jack Face Electrical Electrical System
System Ground Ground
Patch cables fitted with connectors supplied by Distech Controls are
wired as T568B. Figure 10-2: Digital triac output, line switching Relay using an
external power source
10. Output Wiring If a floating actuator is being controlled, connect the digital output
according to the following figure.
Each controller has physical connections for digital (triac) outputs External power supplies must be grounded as shown
and/or universal outputs, depending on the type and model. These below.
outputs are all software configurable.
Actuator
Cy
Table 10-1: Controller Output Support
DOy ~
Outputs
ECB-203 5 3
Figure 10-3: Digital triac output Floating actuator
ECB-300 0 8
ECB-4x0 Series 0 12 Wiring Universal Outputs (UOx)
ECB-4x3 Series 8 4 Universal outputs can be configured to provide either a discrete signal
ECB-600 Series 0 12 of 0 or 12VDC, a linear signal ranging from 0 to 10VDC or a 0 to 20mA
signal (ECB-300, ECB-400 Series, and ECB-600 Series only). The
For jumper location, see Section 7. discrete signal can be used to generate a pulse wave modulation
Before connecting an output device (actuator, relay, etc.) (PWM) signal or a simple two-state signal. These outputs are protected
to the controller, refer to the installation guide of the by an auto-reset fuse.
equipment manufacturer.
Wiring Discrete Outputs
If a 12VDC relay is being controlled, connect it to a universal output
For a wire length less than 75 (23m) long, either a according to the following figure.
shielded or unshielded 18AWG wire may be used.
For a wire length up to 200 (61m) long, a shielded From
Digital
UOx
A1
18AWG wire is recommended. Output
COM
A2
ON
actuator according to the following figure.
Actuator
From Digital- UOx
0-10V
To-Analog
Output ~ or +
COM 24VAC
or -
NET+
NET-
NET-
jumper internally
- AND add a 120 Ohm EOL
- + S
network will be made through the computer that will disrupt
resistor as shown here
The shield of the
BACnet network communications.
Data Bus Shields: Twist data bus must be
together and isolate connected to the
with electrical tape 12
0 electrical system
ground at only one
point usually at
LAN Access
Data Bus: Shielded Twisted Pair Cable Up to 50 Devices Total Connector Net BACnet MS/TP Adaptor
one end of the bus
Data Bus Shield:
: Isolate with Data Bus Shield: Connect as shown. Port with Isolated RS-485 Port
electrical tape to the S terminal NET+
NET-
Figure 11-1: Communications wiring Shield
If inserting multiple wires in the terminals, ensure to properly twist Cable Supplied with
BACnet MS/TP Adaptor
wires together prior to inserting them in the terminal connectors.
For more information and detailed explanations on network topology NET+ (White) - Temporary
and wire length restrictions, refer to the Network Guide, which can be NET- (Red) Commissioning and
Maintenance
downloaded from our website. Shield (bare)
Connection
To BACnet MS/TP - No EOL Resistors are
Adaptor Necessary EC-Net Pro
7/14
Screen timeout: 15 sec
15. Setting the Allure EC-Smart-Vue Subnet ID PASSW
ECB Series controllers can be commissioned with an Allure
EC-Smart-Vue sensor by connecting it to the controller as shown in OR
Figure 23-1. The default Subnet ID for an Allure EC-Smart-Vue sensor
is 1. To commission an ECB Series controller, the Allure
EC-Smart-Vue sensors Subnet ID must be set to 1. If the Subnet ID
3. Use the down button to set the number to 9995 (this is the
has been set to another value (for example, the display flashes error
default password).
code 1 with the Bell icon when the sensor is connected to a controller
for commissioning), change the Subnet ID to 1 as follows: Screen timeout: 15 sec
PASSW
1. Connect an Allure EC-Smart-Vue sensor to the controller with a Cat
5e patch cable. Wait for the Bell icon and the number 1 to flash on
the display.
2. Press and hold the Menu button for 5 seconds to enter the
password menu. 10000 is shown on the display.
Screen timeout: 15 sec 4. Press the Menu button to submit the password. Upon
PASSW submitting the password, the GEN CFG menu appears on the
display.
OR 5. Press the down button once to enter the GEN CFG submenu.
The MAC ADDRESS menu is shown with the current controllers
BACnet MAC Address.
Screen timeout: 30 sec
3. Use the down button to set the number to 9995 (this is the MAC A
default password).
Screen timeout: 15 sec
PASSW
8/14
Screen timeout: 15 sec
PASSW 19. Strain Relief and Terminal Block Cover
In certain jurisdictions, terminal block covers are required to meet local
safety regulations. Strain reliefs and terminal block covers are
available for controllers housed in large enclosures and are used to
relieve tension on the wiring and conceal the controllers wire
terminals. Strain reliefs and terminal block covers are optional and are
sold as peripherals.
4. Press the Menu button to submit the password. Upon
submitting the password, the GEN CFG menu appears on the Prior to connecting all wires, it is recommended to install the strain
display. relief. Three screws are provided for its installation under the bottom
Screen timeout: 30 sec part of the enclosure. Tie wraps can then be used to group wires
GEN C together and attach them securely to the strain relief in an effort to
relieve undue tension. If necessary, the terminal block cover can then
OR
be clipped on to the strain relief as shown below.
5. Press the down button once to enter the GEN CFG submenu.
6. Press the Menu button several times until BAUD RATE
appears on the display. The current controllers baud rate is shown.
Screen timeout: 30 sec
BAUD
9/14
22. FCC Statement
Changes or modifications not expressly approved by
Distech Controls could void the user's authority to operate
the equipment.
10/14
23. Typical Roof Top Application Wiring Diagram
To To
Supply Return
Fan Fan Heat Cool Damper Humidifier
Starter Starter
A2
A1
A2
A1
Fuse: 4A Max. 0-10 + - 0-10 + - 0-10 + - 0-10 + -
Transformer Fast Acting
VDC ~ VDC ~ VDC ~ VDC ~
24VAC
Electrical
System
Ground
ECB-400
*
Data Bus Shields: Twist together
and Isolate with electrical tape
BACnet MS/TP Network
CT CT Back of an Allure
EC-Smart-Vue
* 249 ohm resistor built-in for inputs configured as 0-20mA
To Next Device
From Previous Device
Supply Air Temperature
10k type II
ON
EOL
OFF
EOL Enabled at
the last sensor
at the end of
the Bus
Allure EC-Smart-Vue
Figure 23-1: Typical Power and Network Connections with an Allure EC-Smart-Vue sensor
11/14
24. Troubleshooting Guide
Controller is powered but does not turn on
Fuse has blown Disconnect power from the controller. Check the fuse integrity. Reconnect power to the controller.
Power supply polarity Verify that consistent polarity is maintained between all controllers and the transformer. Ensure that the 24VCOM terminal
of each controller is connected to the same terminal on the secondary side of the transformer. See Figure 6-1 and Figure
6-2.
Controller cannot communicate on an BACnet MS/TP network
Absent or incorrect supply voltage 1. Check power supply voltage between 24VAC 15% and 24VCOM pins and ensure that it is within acceptable limits.
2. Check for tripped fuse or circuit breaker.
Overloaded power transformer Verify that the transformer used is powerful enough to supply all controllers. See Power Wiring.
Network not wired properly Double check that the wire connections are correct.
Absent or incorrect network termination Check the network termination(s).
Max Master parameter Configure the maximum number of master device on the MS/TP network in all devices to the controllers highest MAC
address used on the MS/TP trunk.
There is another controller with the same MAC Each controller on a BACnet MS/TP data bus must have a unique MAC Address. Look at the MAC Address DIP switch on
Address on the BACnet MS/TP data bus the faceplate of each controller. If it is set to 0 (all off), use an Allure EC-Smart-Vue sensor to check the MAC Address.
There is another controller with the same Device Each controller on a BACnet intranetwork (the entire BACnet BAS network) must have a unique Device ID. Use an Allure
ID on the BACnet intranetwork EC-Smart-Vue sensor to check the Device ID of each controller.
Controller communicates well over a short network, but does not communicate on large network
Network length Check that the total wire length does not exceed the specifications of the Network Guide.
Wire type Check that the wire type agrees with the specification of the Network Guide.
Network wiring problem Double check that the wire connections are correct.
Absent or incorrect network termination Check the network termination(s). Incorrect or broken termination(s) will make the communication integrity dependent
upon a controllers position on the network.
Number of controllers on network segment The number of controllers on a channel should never exceed 50. Use a router or a repeater in accordance to the Network
exceeded Guide.
Max Master parameter Configure the maximum number of master device on the MS/TP network in all devices to the controllers highest MAC
address used on the MS/TP trunk.
IO Extension Module cannot communicate on the subnetwork
Absent or incorrect supply voltage 1. Check power supply voltage between 24VAC 15% and COM pins and ensure that it is within acceptable limits.
2. Check for tripped fuse or circuit breaker.
Overloaded power transformer Verify that the transformer used is powerful enough to supply all controllers. See Power Wiring.
Network not wired properly Double check that the wire connections are correct.
Absent or incorrect network termination Check the subnetwork termination(s). Only the last ECx-400 Series IO Extension module must have its EOL termination
set to ON. When one or more Allure EC-Smart-Vue sensors are connected to the controller, only the last Allure
EC-Smart-Vue sensor must have its EOL termination set to ON. See the Hardware Installation Guide supplied with either
the ECx-400 Series IO Extension Module or Allure EC-Smart-Vue sensor.
There is another controller with the same Each IO Extension Module on the subnetwork must have a unique Subnet ID. Look at the Subnet ID DIP switch on the
Subnet ID on the subnetwork faceplate of each IO Extension Module.
Network length Check that the total wire length does not exceed the specifications of the Network Guide.
Wire type Check that the wire type agrees with the specification of the Network Guide.
Hardware input is not reading the correct value
Input wiring problem Check that the wiring is correct according to this manual and according to the peripheral devices manufacturer.
Open circuit or short circuit Using a voltmeter, check the voltage on the input terminal. Short circuit (0V) and open circuit (5V).
Configuration problem Using the controller configuration wizard, check the configuration of the input. Refer to the controllers user guide for more
information.
Over-voltage or over-current at an input An over-voltage or over-current at one input can affect the reading of other inputs. Respect the allowed voltage / current
range limits of all inputs. Consult the appropriate datasheet for the input range limits of this controller.
Hardware output is not operating correctly
Fuse has blown (Auto reset fuse) Disconnect the power and outputs terminals. Then wait a few seconds to allow the auto-reset fuse to cool down. Check
the power supply and the output wiring. Reconnect the power.
Output wiring problem Check that the wiring is correct according to this manual and according to the peripheral devices manufacturer.
Configuration problem Using the controller configuration wizard, check the configuration of the output. Refer to the controllers programming user
guide for more information.
0 to 10V output, 24VAC powered actuator is not Check the polarity of the 24VAC power supply connected to the actuator while connected to the controller. Reverse the
moving. 24VAC wire if necessary.
Wireless devices not working correctly
Device not associated to controller Using the device configuration wizard, check the configuration of the input. Refer to the devices user guide for more
information.
Power discharge 1. Recharge device with light (if solar-powered) or replace battery (if battery-powered),
2. Ensure sufficient light intensity (200lx for 4 hours/day).
Device too far from the Wireless Receiver Reposition the device to be within the range of the Wireless Receiver. For information on typical transmission ranges,
refer to the Open-to-Wireless Solution Guide.
Configuration problem Using the device configuration plug-in or wizard, check the configuration of the input. Refer to the Wireless Battery-less
Sensors and Switches Solutions Guide for more information.
12/14
Rx/Tx LEDs
RX LED not blinking Data is not being received from the BACnet MS/TP data bus.
TX LED not blinking Data is not being transmitted onto the BACnet MS/TP data bus.
Fast blink continuous: Firmware upgrade in progress. Controller operation is temporarily unavailable. The new firmware is
being loaded into memory. This takes a few seconds. Do not interrupt power to the device during this
(150ms On, 150ms Off, continuous) time.
The Status LED is always OFF The controller is operating normally.
Status LED blink patterns Repeats every 2 seconds (highest priority shown first)
Long Long Long blink The device has not received a BACnet token, and therefore cannot communicate on the network: Verify
that the controllers MAC Address is unique on the BACnet MS/TP Data Bus see Section 12. Make
(800ms On, 300ms Off, 800ms On, 300ms Off, 800ms On)
sure the controllers BAUD rate is the same as the BACnet MS/TP Data Bus BAUD rate (see Section
17). Verify that the Max Master is set high enough to include this controllers MAC Address (See the
Network Guide).
Short Short Long blink Poor-quality power; The device has browned-out: The voltage at the 24VAC and 24VCOM terminals has
gone below the devices acceptable limit during power up.
(150ms On, 300ms Off, 150ms On, 300ms Off, 800 ms On)
Short Long blink Invalid MAC address: The devices MAC address is set to zero (0) or is set to an address higher than the
Max Master. See the Network Guide .
(150ms On, 300ms Off)
For issues with the Allure EC-Smart-Vue sensor, refer to the Allure EC-Smart-Vue Hardware Installation Guide. For issues with the ECx-400 Series
IO Extension Module, refer to the ECx-400 Series IO Extension Module Hardware Installation Guide.
13/14
Total Quality Commitment
All Distech Controls product lines are built to meet rigorous quality standards. Distech Controls is an ISO 9001
registered company.
Images are simulated. While all efforts have been made to verify the accuracy of information in this manual, Distech Controls is not responsible for damages or claims
arising from the use of this manual. Persons using this manual are assumed to be trained HVAC specialist / installers and are responsible for using the correct wiring
procedures and maintaining safe working conditions with fail-safe environments. Distech Controls reserves the right to change, delete or add to the information in this
manual at any time without notice.
Distech Controls, the Distech Controls logo, Open-to-Wireless, Innovative Solutions for Greener Buildings, and Allure are trademarks of Distech Controls Inc. BACnet is
a registered trademark of ASHRAE. NiagaraAX Framework is a registered trademark of Tridium, Inc.
14/14 *05DI-HIECBXX-19*