Anda di halaman 1dari 20

Volume Control Dampers

DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

VOLUME CONTROL DAMPERS


Volume Control Dampers

DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

DVAC, One Of The Premium Workshops Specialized in Duct Fabrication


has Executed Several Projects
(Residential, Governmental, Commercial, Industrial & Institutional).

2
Table of Contents

DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Volume Control Dampers


Page
Introduction 4

Rectangular Volume Control Dampers 5

Flat Oval Volume Control Dampers 12

Circular Volume Control Dampers 13

Test Reports 16

3
Volume Control Dampers
Rectangular
Types : VCD-FC / VCD-SC / VCD-RSC
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.) As per: - SMACNA (2nd Edition-1995) See Pages 2.16/2.17

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Rectangular Volume Control Dampers

TYPES: - VCD-FC Flange Case


- VCD-SC (VCD-FC)
- VCD-RSC

Multi-leaf Volume Control Dampers Have Been Specifically


Designed to be Used in Ventilation Systems to Control Flow
and Pressure.

Volume Control Dampers are Applicable for the Rectangular,


Circular and Flat Oval Ducts.

Sleeve Case
The Casing is a Rigid and Robust Assembly formed from Either
(VCD-SC)
Channel Frame for Flanged Connection to Duct Work,
Top Hat Section for Spigot Style Connection or Top Hat Sleeve
to Side in Ducting.

The Blades Are Formed Single Skin with Grooved Blade Tips
to Provide Interlocking Closure, or Airfoil Double Skin for Superior
Rigidity and Deflection Resistance with Low Pressure Drop.
Blade Action is as Standard, Parallel or Opposed (Optional).
The Dampers Can be Fitted with Hand Locking Quadrant
or Can be Power Operated by Electric or Pneumatic Actuators.

Rectangular Spigot Case


Volume Control Dampers Have Been Designed and Tested (VCD-RSC)
to Provide a Reliable Cost Effective Control .

Volume Control Dampers Have Rigid Frame and Integrally


Braced Corners Providing True Damper Alignment that
Greatly Resists Being Installed Indoor or Outdoor.

* Materials Used for VCD :


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.
- Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L.

* All VCDs Are Available With Actuators.

4
Volume Control Dampers
Rectangular
Type : VCD-FC
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.) As per: - SMACNA (2nd Edition-1995) See Pages 2.16/2.17

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Rectangular Volume Control Damper

TYPE: Flange Case (VCD-FC) is Fabricated of One Piece


Roll-Formed Channel.
VCD-FC is to be Installed Between Two Pieces
of Ducts By Flanges.

H
RATINGS:
- Pressure : Up to 4'w.g. (Up to 1000 Pa)
- Velocity : Up to 3000 fpm (Up to 15.2 m/s)
- Temperature : 176F (80C)

FEATURES: W

Casing : - 16 Gage Galvanized Steel.


Blades : - Triple-vee Profile 16 Gage Galvanized Steel.
Axles : - Zinc Plated Square Mild Steel, 12x12mm.
Linkage : - 14 Gage Galvanized Steel.
Bearings : - Synthetic (acetal) Sleeve Type.
Quadrant: - Galvanized Hand Locking Quadrant.
Height Number of Position of
Blades Drive Arm X
(mm) (mm)

100 1 50
150 1 75
1 Casing 4 Axle 200 1 100
250 1 125
2 Blade 5 Side Linkage 300 1 150
350 2 240
3 Drive Spindle 400 2 275
450 2 300
500 3 240
600 3 300
Parallel Blades 700 4 425
800 5 400
900 5 450
1000 6 575
1100 7 540
1
1200 7 600
X 1300 8 725
2 5 1400 9 600
1500 9 750
4 3 1600 10 875
1700 11 840
H 1800 11 900

30 Minimum / Maximum Sizes:


- 100x100mm Minimum Size
30 W 30 120 - 1200x1800mm Maximum Size

* Materials Used for VCD :


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.
- Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L.

* All VCDs Are Available With Actuators.

5
Volume Control Dampers
Rectangular
Type : VCD-FC-AGI
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Rectangular Volume Control Damper

TYPE: Flange Case (VCD-FC-AGI) is Fabricated of One


Piece Roll-Formed Channel.
VCD-FC-AGI is to be Installed Between Two
Pieces of Ducts By Flanges.

H
RATINGS:
- Pressure : Up to 4'w.g. (Up to 1000 Pa)
- Velocity : Up to 3000 fpm (Up to 15.2 m/s)
- Temperature : 176F (80C)

FEATURES:
W
Casing : - 16 Gage Galvanized Steel.
Blades : - Airfoil Double Skin 22 Gage Galvanized Steel.
Axles : - Zinc Plated Square Mild Steel, 12x12mm.
Linkage : - 14 Gage Galvanized Steel (Alternative Plastic Gear).
Bearings : - Synthetic (acetal) Sleeve Type.
Quadrant: - Galvanized Hand Locking Quadrant.
Height Number of Position of
Blades Drive Arm X
(mm) (mm)

100 1 50
150 1 75
1 Casing 200 2 100
250 2 125
2 Blade 300 3 100
350 3 125
3 Drive Spindle 400 4 200
450 4 225
500 5 200
600 6 200
Opposed Blades Parallel Blades 700 7 300
800 8 300
900 9 400
1000 10 400
1100 11 500
1 1200 12 500
1300 13 500
X 1400 14 600
2 1500 15 600
3 1600 16 700
1700 17 800
H H 1800 18 900

30 30 Minimum / Maximum Sizes:


- 100x100mm Minimum Size
25 W 25 120 120 - 1200x1800mm Maximum Size

* Materials Used for VCD :


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.
- Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L.

* All VCDs Are Available With Actuators.

6
Volume Control Dampers
Rectangular
Type : VCD-FC-AA
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Rectangular Volume Control Damper

TYPE: Flange Case (VCD-FC-AA) is Fabricated of One


Piece Roll-Formed Channel.
VCD-FC-AA is to be Installed Between Two
Pieces of Ducts By Flanges.

H
RATINGS:
- Pressure : Up to 4'w.g. (Up to 1000 Pa)
- Velocity : Up to 3000 fpm (Up to 15.2 m/s)
- Temperature : 176F (80C)

FEATURES:
W
Casing : - 16 Gage Galvanized Steel.
Blades : - Airfoil Double Skin Heavy Gauge Extruded Aluminum.
Axles : - Zinc Plated Square Mild Steel, 12x12mm.
Linkage : - 14 Gage Galvanized Steel (Alternative Plastic Gear).
Bearings : - Synthetic (acetal) Sleeve Type.
Quadrant: - Galvanized Hand Locking Quadrant.
Height Number of Position of
Blades Drive Arm X
(mm) (mm)

100 1 50
150 1 75
1 Casing 200 2 100
250 2 125
2 Blade 300 3 100
350 3 125
3 Drive Spindle 400 4 200
450 4 225
500 5 200
600 6 200
Opposed Blades Parallel Blades 700 7 300
800 8 300
900 9 400
1000 10 400
1100 11 500
1 1200 12 500
1300 13 500
X 1400 14 600
2 1500 15 600
3 1600 16 700
1700 17 800
H H 1800 18 900

30 30 Minimum / Maximum Sizes:


- 100x100mm Minimum Size
25 W 25 120 120 - 1200x1800mm Maximum Size

* Materials Used for VCD :


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.
- Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L.

* All VCDs Are Available With Actuators.

7
Volume Control Dampers
Rectangular
Type : VCD-SC
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.) As per: - SMACNA (2nd Edition-1995) See Pages 2.16/2.17

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Rectangular Volume Control Damper

TYPE: Sleeve Case (VCD-SC) is Fabricated of One


Piece Roll-Formed Hat Channel.
VCD-SC Installation Shall be Easy and Inside
The Ducts.

H
RATINGS:
- Pressure : Up to 4'w.g. (Up to 1000 Pa)
- Velocity : Up to 3000 fpm (Up to 15.2 m/s)
- Temperature : 176F (80C)

FEATURES:
W
Casing : - 16 Gage Galvanized Steel.
Blades : - Triple-vee Profile 16 Gage Galvanized Steel.
Axles : - Zinc Plated Square Mild Steel, 12x12mm. * W & H Dimension Furnished
Approximately 1/4"( 6mm)
Linkage : - 14 Gage Galvanized Steel. Undersize.
Bearings : - Synthetic (acetal) Sleeve Type.
Quadrant: - Galvanized Hand Locking Quadrant.
Height Number of Position of
Blades Drive Arm X
(mm) (mm)

150 1 75
1 Casing 4 Axle 200 1 100
250 1 125
2 Blade 5 Side Linkage 300 1 150
350 1 175
3 Drive Spindle 400 2 265
450 2 300
500 2 325
600 3 300
Parallel Blades 700 4 415
800 4 475
130 900 5 450
1000 6 565
1100 6 625
1 1200 7 600
1300 8 715
X 5
2 1400 8 775
1500 9 750
4 3 1600 10 865
1700 10 925
H 1800 11 900

Minimum / Maximum Sizes:


- 100x100mm Minimum Size
W 90 - 1200x1800mm Maximum Size

* Materials Used for VCD :


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.
- Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L.

* All VCDs Are Available With Actuators.

8
Volume Control Dampers
Rectangular
Type : VCD-RSC-AGI
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Rectangular Volume Control Damper

TYPE: Rectangular Spigot Case (VCD-RSC-AGI) is Fabricated


of Double Skin Steel (Internal Liner is Optional).
VCD-RSC-AGI is to be Flexible and Installed Between Two
Pieces of Ducts by Three Connection Types: - Slip & Drive
- Slide-on Flange
- Companion Angles H
RATINGS:
- Pressure : Up to 4'w.g. (Up to 1000 Pa)
- Velocity : Up to 3000 fpm (Up to 15.2 m/s)
- Temperature : 176F (80C)

FEATURES:
W
Casing : - Inner: 20 Gage Galvanized Steel
- Outer: 20 Gage Galvanized Steel

Blades : - Airfoil Double Skin 22 Gage Galvanized Steel.


Axles : - Zinc Plated Square Mild Steel, 12x12mm.
Linkage : - 14 Gage Galvanized Steel (Alternative Plastic Gear).
Bearings : - Synthetic (acetal) Sleeve Type.
Height Number of Position of
Quadrant: - Galvanized Hand Locking Quadrant. Blades Drive Arm X
(mm) (mm)

100 1 50
150 1 75
1 Casing 200 2 100
250 2 125
2 Blade 300 3 100
350 3 125
3 Drive Spindle 400 4 200
450 4 225
500 5 200
600 6 200
Opposed Blades Parallel Blades 700 7 300
800 8 300
180 180 900 9 400
1000 10 400
1100 11 500
1 1200 12 500
1300 13 500
X 1400 14 600
2 1500 15 600
3 1600 16 700
1700 17 800
H H 1800 18 900

25 25 Minimum / Maximum Sizes:


- 100x100mm Minimum Size
25 W 25 120 120 - 1200x1800mm Maximum Size

* Materials Used for VCD :


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.
- Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L.

* All VCDs Are Available With Actuators.

9
Volume Control Dampers
Rectangular
Type : VCD-RSC-AA
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Rectangular Volume Control Damper

TYPE: Rectangular Spigot Case (VCD-RSC-AA) is Fabricated


of Double Skin Steel (Internal Liner is Optional).
VCD-RSC-AA is to be Flexible and Installed Between Two
Pieces of Ducts by Three Connection Types: - Slip & Drive
- Slide-on Flange
- Companion Angles H
RATINGS:
- Pressure : Up to 3'w.g. (Up to 750 Pa)
- Velocity : Up to 3000 fpm (Up to 15.2 m/s)
- Temperature : 176F (80C)

FEATURES:
W
Casing : - Inner: 20 Gage Galvanized Steel
- Outer: 20 Gage Galvanized Steel

Blades : - Airfoil Double Skin Heavy Gauge Extruded Aluminum.


Axles : - Zinc Plated Square Mild Steel, 12x12mm.
Linkage : - 14 Gage Galvanized Steel (Alternative Plastic Gear).
Bearings : - Synthetic (acetal) Sleeve Type.
Height Number of Position of
Quadrant: - Galvanized Hand Locking Quadrant. Blades Drive Arm X
(mm) (mm)

100 1 50
150 1 75
1 Casing 200 2 100
250 2 125
2 Blade 300 3 100
350 3 125
3 Drive Spindle 400 4 200
450 4 225
500 5 200
600 6 200
Opposed Blades Parallel Blades 700 7 300
800 8 300
180 180 900 9 400
1000 10 400
1100 11 500
1 1200 12 500
1300 13 500
X 1400 14 600
2 1500 15 600
3 1600 16 700
1700 17 800
H H 1800 18 900

25 25 Minimum / Maximum Sizes:


- 100x100mm Minimum Size
25 W 25 120 120 - 1200x1800mm Maximum Size

* Materials Used for VCD :


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.
- Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L.

* All VCDs Are Available With Actuators.

10
Volume Control Dampers
Rectangular
Type : VCD-RSC
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.) As per: - SMACNA (2nd Edition-1995) See Pages 2.16/2.17

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Rectangular Volume Control Damper

TYPE: Rectangular Spigot Case (VCD-RSC) is Fabricated


of Double Skin Steel (Internal Liner is Optional).
VCD-RSC is to be Flexible and Installed Between Two
Pieces of Ducts by Three Connection Types: - Slip & Drive
- Slide-on Flange
- Companion Angles H
RATINGS:
- Pressure : Up to 3'w.g. (Up to 750 Pa)
- Velocity : Up to 3000 fpm (Up to 15.2 m/s)
- Temperature : 176F (80C)

FEATURES:
W
Casing : - Inner: 20 Gage Galvanized Steel
- Outer: 20 Gage Galvanized Steel

Blades : - Triple-vee Profile 18-16 Gage Galvanized Steel.


Axles : - Zinc Plated Square Mild Steel, 12x12mm.
Linkage : - 14 Gage Galvanized Steel.
Bearings : - Synthetic (acetal) Sleeve Type.
Height Number of Position of
Quadrant: - Galvanized Hand Locking Quadrant. Blades Drive Arm X
(mm) (mm)

100 1 50
150 1 75
1 Casing 4 Axle 200 1 100
250 1 125
2 Blade 5 Side Linkage 300 3 100
350 3 125
3 Drive Spindle 400 4 200
450 4 225
500 5 200
600 6 200
Parallel Blades 700 7 300
800 8 300
180 900 9 400
1000 10 400
1100 11 500
1 1200 12 500
1300 13 500
2 X 5 1400 14 600
1500 15 600
4 3 1600 16 700
1700 17 800
H 1800 18 900

25 Minimum / Maximum Sizes:


- 100x100mm Minimum Size
25 W 25 120 - 1200x1800mm Maximum Size

* Materials Used for VCD :


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.
- Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L.

* All VCDs Are Available With Actuators.

11
Volume Control Dampers
Flat Oval
Type : VCD-FOSC
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.) As per: - SMACNA (2nd Edition-1995) See Pages 2.16/2.17

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Flat Oval Volume Control Damper

TYPE: Flat Oval Spigot Case (VCD-FOSC) is Fabricated


of Double Skin Steel (Internal Liner is Optional).
VCD-FOSC is to be Installed Between Two Pieces
of Flat Oval Ducts.

H
RATINGS:
- Pressure : Up to 3'w.g. (Up to 750 Pa)
- Velocity : Up to 2000 fpm (Up to 10.2 m/s)
- Temperature : 176F (80C)

FEATURES:
W
Casing : - Inner: 20 Gage Galvanized Steel
- Outer: 20 Gage Galvanized Steel

Blades : - Triple-vee Profile 18-16 Gage Galvanized Steel.


Axles : - Zinc Plated Square Mild Steel, 12x12mm.
Linkage : - 14 Gage Galvanized Steel.
Bearings : - Synthetic (acetal) Sleeve Type.
Quadrant: - Galvanized Hand Locking Quadrant.

1 Casing 4 Axle Height Number of Position of


Blades Drive Arm X
2 Blade 5 Side Linkage (mm) (mm)

3 Drive Spindle 100 1 50


150 1 75
200 1 100
250 1 125
Parallel Blades 300 3 100
350 3 125
220
400 4 200
450 4 225
500 5 200
600 6 200
X 5 700 7 300
800 8 300
900 9 400
3 1000 10 400
H=d+105 d 1100 11 500
1200 12 500
4

1 Minimum / Maximum Sizes:


D - 100x100mm Minimum Size
W=D+105 120 - 1200x1800mm Maximum Size

* Materials Used for VCD :


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.
- Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L.

* All VCDs Are Available With Actuators.

12
Volume Control Dampers
Circular
Type : VCD-CSC
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.) As per: - SMACNA (2nd Edition-1995) See Pages 2.16/2.17

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Circular Volume Control Damper

TYPE: Circular Spigot Case (VCD-CSC) is Fabricated


of Double Skin Steel (Internal Liner is Optional).
VCD-CSC is to be Installed Between Two Pieces
of Circular Ducts.

H
RATINGS:
- Pressure : Up to 3'w.g. (Up to 750 Pa)
- Velocity : Up to 2000 fpm (Up to 10.2 m/s)
- Temperature : 176F (80C)

FEATURES:
W
Casing : - Inner: 20 Gage Galvanized Steel
- Outer: 20 Gage Galvanized Steel

Blades : - Triple-vee Profile 18-16 Gage Galvanized Steel.


Axles : - Zinc Plated Square Mild Steel, 12x12mm.
Linkage : - 14 Gage Galvanized Steel.
Bearings : - Synthetic (acetal) Sleeve Type.
Quadrant: - Galvanized Hand Locking Quadrant.

1 Casing 4 Axle Height Number of Position of


Drive Arm X
2 Blade 5 Side Linkage (mm) Blades (mm)

3 Drive Spindle 100 1 50


150 1 75
200 1 100
Parallel Blades 250 1 125
300 3 100
350 3 125
220 400 4 200
450 4 225
500 5 200
600 6 200
X 5 700 7 300
800 8 300
900 9 400
3 1000 10 400
H=Diam.+105 Diam. 1100 11 500
1200 12 500
4

1 Minimum / Maximum Sizes:


Diam. - 100x100mm Minimum Size
W=Diam.+105 120 - 1200x1800mm Maximum Size

* Materials Used for VCD :


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.
- Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L.

* All VCDs Are Available With Actuators.

13
Volume Control Dampers
Circular
Type : VCD
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.) As per: - SMACNA (2nd Edition-1995) See Pages 2.16/2.17

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Circular Volume Control Damper

TYPE: Circular (VCD) is Fabricated of Steel.


VCD shall be Installed Between Two Pieces of Circular Ducts or Plenum Box.
VCD with Nominal Sizes of 100 to 450mm, are Circular Control Dampers to Adjust
Air Volume Flow Rates in Air Conditioning and Ventilation Systems.
The Damper is Designed without a Seal (Approximately 3mm Clearance all Around).

RATINGS:
- Pressure : Up to 2'w.g. (Up to 500 Pa)
- Velocity : Up to 2000 fpm (Up to 10.2 m/s)
- Temperature : 131F (55C)

FEATURES:
Casing & Blade : - Galvanized Steel
Axles : - Zinc Plated Square Mild Steel.
Bearings : - Synthetic (acetal) Sleeve Type.
Quadrant: - Galvanized Hand Locking Quadrant.

Sizes D Length Casing Thickness Blade Thickness Axle & Bearing


(mm) (mm) (mm) (mm) (mm)

100 170 0.6 1.0 6x6


125 170 0.6 1.0 6x6
150 170 0.6 1.0 6x6
200 220 0.6 1.0 8x8
250 270 0.8 1.2 8x8
300 320 0.8 1.2 10x10
350 400 1.0 1.5 10x10
400 450 1.0 1.5 10x10
450 500 1.0 1.5 10x10

25 L 25
3

1 Casing
2 Blade
D
3 Drive Spindle
4 Beaded

1 2 4

* Materials Used for VCD :


- Galvanized Steel: (Standard) L.F.Q. Complying with ASTM A653 and Having G90 Coating Designation.
- Stainless Steel : (Optional) Complying with ASTM A240M / A480M, Grade 304, 304L, 316, & 316L.

* All VCDs Are Available With Actuators.

14
Volume Control Dampers
Circular
Type : AL - VCD
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.) As per: - SMACNA (2nd Edition-1995) See Pages 2.16/2.17

DOHA- QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117

Circular Volume Control Damper

TYPE: Circular (AL-VCD) is Fabricated of Aluminum.


AL-VCD shall be Installed Between Two Pieces of Circular Ducts or Plenum Box.
AL-VCD with Nominal Sizes of 100 to 450mm are Circular Control Dampers to Adjust
Air Volume Flow Rates in Air Conditioning and Ventilation Systems.
The Damper is Designed without a Seal (Approximately 3mm Clearance all Around).

RATINGS:
- Pressure : Up to 4'w.g. (Up to 1000 Pa)
- Velocity : Up to 2000 fpm (Up to 10.2 m/s)
- Temperature : 131F (55C)

FEATURES:
Casing & Blade : - Aluminum
Axles : - Zinc Plated Square Mild Steel.
Bearings : - Synthetic (acetal) Sleeve Type.
Quadrant: - Galvanized Hand Locking Quadrant.

Sizes D Length Casing Thickness Blade Thickness Axle & Bearing


(mm) (mm) (mm) (mm) (mm)

100 170 1.0 1.0 6x6


125 170 1.0 1.0 6x6
150 170 1.0 1.0 6x6
200 220 1.0 1.0 8x8
250 270 2.0 2.0 8x8
300 320 2.0 2.0 12x12
350 400 2.0 2.0 12x12
400 450 2.0 2.0 12x12
450 500 2.0 2.0 12x12

25 L 25
3

1 Casing
2 Blade
D
3 Drive Spindle
4 Beaded

1 2 4

* Materials Used for AL-VCD :


- Aluminum Metal: Comply with ASTM B209, Alloy 3003 Temper 16

* All AL-VCDs Are Available With Actuators.

15
16
17
18
Remarks:

DOHA - QATAR - PHONE: +974-44500118 - +974-44500119 - FAX: +974-44500117


19
DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.)

Small Industries Zone - Pink Area


Zone 81 - Street 13 - Bldg. 57

Tel: +974 445 00 118 - 445 00 119


Fax: +974 445 00 117
P.O. Box: 55619 - Doha, State Of Qatar

Email: info@dvac-duct.com
Website: www.dvac-duct.com

Anda mungkin juga menyukai