providing insights for todays hvac system designer

Engineers Newsletter volume 454

AHRI 920
Rating Standard for DX Dedicated Outdoor-Air Units
Dedicated outdoor-air units are typically standard applies to DX "products which
used to dehumidify 100-percent outdoor air dehumidify 100-percent outdoor air to a Minimum equipment efficiencies
to a low dew point, and then deliver this low dew point," and are equipped with required by ASHRAE Standard 90.1. In
either an air-cooled or water-cooled order for the Standard 90.1 committee
conditioned air (CA) to each occupied
to include a certain class of equipment
space, either directly or in conjunction with condenser (including air-, water-, or
in the minimum equipment efficiency
local HVAC equipment serving those same ground-source heat pumps). tables in Section 6.4.1 of the standard,
spaces (Figure 1). This local (zone-level) there must be an industry standard that
HVAC equipment is then used to provide With this industry rating standard in place, defines how to uniformly rate the
the ASHRAE Standard 90.1 committee efficiency of that class of equipment.
cooling or heating to maintain space
temperature. proposed and published an addendum to
"Equipment efficiency levels defined in
prescribe minimum efficiency this section [Section 6.4.1] and Tables
Until recently, an industry rating standard requirements for DX dedicated OA units 6.8.1-1 through 6.8.1-13 are based on
for direct-expansion (DX) dedicated (more on this later). industry rating standards, such as those
of the Air-Conditioning, Heating, and
outdoor-air units didnt exist. And without a
However, because this rating standard is Refrigeration Institute (AHRI)."1
rating standard to cite, ASHRAE Standard
90.1 has not prescribed a minimum relatively new, there is still confusion in
The User's Manual that accompanies
efficiency requirement for this class of the industry when specifying the Standard 90.1 clarifies that HVAC
equipment (see sidebar). efficiency of this class of equipment. The equipment that is not included in the
purpose of this EN is to introduce the minimum equipment efficiency tables
reader to AHRI Standard 920 and help can still be used; it's just that Standard
In June 2013 ANSI/AHRI Standard 920, 90.1 does not prescribe a minimum
Performance Rating of DX Dedicated specifying engineers cite this as the efficiency requirement for that class of
Outdoor Air System Units, was approved appropriate rating standard for DX equipment.
by ANSI and published by AHRI. This dedicated OA units.
"Although Sections 6.4.1.1 and 6.4.1.2
include many types of HVACR
Figure 1. Example of a dedicated outdoor-air system equipment, not every type of HVACR
equipment that might be used in a
project is covered. This section [Section
dedicated 6.4.1.3] clarifies that the use of HVACR
OA unit equipment not covered by these
OA sections does not prohibit compliance
with the Standard. Equipment not
covered by these sections is not
relief air CA
regulated by this standard, but may be
CA regulated by other standards, codes, or
federal regulations."2

CA SA RA

zone-level [1] Standard 90.1-2013 User's Manual,


SA cooling/heating page 6-14
equipment
[2] Standard 90.1-2013 User's Manual,
page 6-18
RA CA

2016 Trane, a business of Ingersoll Rand. All rights reserved. 1


efficiency (MRE) by dividing the ISMRE = ( 0.12 A ) + ( 0.28 B ) +
AHRI Standard 920 or dehumidification capacity (lbs of water ( 0.36 C ) + ( 0.24 D )

Standard 340/360? removed/hr) of the equipment by the


power input (kW). where,
Historically, some engineers have A = MRE at standard rating condition A
specified that DX dedicated OA units This highlights the difference in scope
should be rated in accordance with AHRI between these two standards. Standard B = MRE at standard rating condition B
Standard 340/360. Is this appropriate? 920 was specifically developed to rate the
performance of DX equipment that is C = MRE at standard rating condition C
How does this standard compare with
AHRI Standard 920? used to dehumidify 100-percent outdoor
D = MRE at standard rating condition D
air to a low dew point.
AHRI Standard 340/360, Performance Table 1 compares the rating conditions
Rating of Commercial and Industrial The second difference is in how the two used to determine both IEER and ISMRE
Unitary Air-conditioning and Heat Pump standards determine an integrated (or for equipment with an air-cooled
Equipment, is used to rate the weighted) efficiency rating: IEER by condenser. Notice that Standard 340/360
performance of DX air-conditioning Standard 340/360 and ISMRE by Standard requires the equipment to operate at four
equipment. This rated performance 920. While both standards use four different dry-bulb temperatures entering
includes the total cooling capacity operating conditions to perform a the air-cooled condenser: 95F, 81.5F,
(Btu/hr), full-load Energy Efficiency Ratio weighted calculation of full-load and part- 68F, and 65F. This is intended to depict
(EER, Btu/W-hr), and an Integrated Energy load efficiencies, the operating conditions the equipment operating during different
Efficiency Ratio (IEER, Btu/W-hr). IEER is and method of testing differ greatly. times of the year. However, the air
a weighted calculation of cooling IEER = ( 0.020 A ) + ( 0.617 B ) +
entering the evaporator coil remains the
efficiencies at full-load and part-load ( 0.238 C ) + ( 0.125 D ) same (80F DBT, 67F WBT) for all four
conditions. This standard also rates conditions, which essentially depicts how
heating capacity and efficiency where, a unit would operate with a constant
(Coefficient of Performance, or COP). return-air condition and no outdoor air.
A = EER at 100% capacity and standard
rating conditions
AHRI Standard 920, Performance Rating This is because Standard 340/360 is
of DX Dedicated Outdoor Air System B = EER at 75% capacity and reduced intended to rate the cooling capacity and
Units, is used to rate the performance of condenser temperature efficiency of an air-conditioner, it doesnt
DX equipment that is used to dehumidify address dehumidification. During testing
100-percent outdoor air to a low dew C = EER at 50% capacity and reduced there is no requirement that the
condenser temperature
point. This rated performance includes the evaporator achieve a dew point
Moisture Removal Capacity (MRC, lb/hr), D = EER at 25% capacity and reduced temperature low enough to ensure
full-load Moisture Removal Efficiency condenser temperature dehumidification.
(MRE, lb/kWh), and an Integrated
Seasonal Moisture Removal Efficiency
(ISMRE, lb/kWh). ISMRE is a weighted
calculation of dehumidification
efficiencies at full-load and part-load
conditions. The standard also rates
Table 1. Comparison of standard rating test conditions for packaged DX units with air-cooled condensers
heating capacity, efficiency (COP), and
condition A condition B condition C condition D
Integrated Seasonal Coefficient of
Performance (ISCOP, which is a weighted IEER rating conditions (per AHRI 340/360) IEER = ( 0.020 A ) + ( 0.617 B ) + ( 0.238 C ) + ( 0.125 D )

calculation of heating efficiencies at full- evaporator entering-air conditions 80F DBT 80F DBT 80F DBT 80F DBT
load and part-load conditions). 67F WBT 67F WBT 67F WBT 67F WBT
condenser entering-air conditions 95F DBT 81.5F DBT 68F DBT 65F DBT
The first obvious difference between
ISMRE rating conditions (per AHRI 920) ISMRE = ( 0.12 A ) + ( 0.28 B ) + ( 0.36 C ) + ( 0.24 D )
these two rating standards is that
evaporator entering-air conditions 95F DBT 80F DBT 68F DBT 60F DBT
Standard 340/360 rates efficiency (EER)
78F WBT 73F WBT 66F WBT 58F WBT
by dividing the total cooling capacity
(Btu/hr) of the equipment by the power condenser entering-air conditions 95F DBT 80F DBT 68F DBT 60F DBT
input (W), whereas Standard 920 rates

2 Trane Engineers Newsletter volume 454 providing insights for todays HVAC system designer
Figure 2. Evaporator entering-air conditions for standard ratings
Cold versus neutral air? As
explained, AHRI Standard 920
requires the dehumidified outdoor air
to be reheated to a dry-bulb
temperature of at least 70F for the
evaporator entering-air purpose of rating this class of
equipment. However, reheating to a
conditions for ISMRE
"neutral" air temperature is not
rating (AHRI 920) necessarily the most efficient way to
operate the overall system.
B A
When a chilled-water or DX cooling coil
is used for dehumidification, a
C byproduct of that process is that the
dry-bulb temperature of the air leaving
A, B, C, D the coil is colder than the occupied
D
evaporator entering-air space. If the dehumidified outdoor air
conditions for IEER is reheated to a "neutral" dry-bulb
rating (AHRI 340/360) temperature, most (or all) of the
sensible cooling performed by the
dedicated OA unit is wasted.

The Standard 90.1 committee


recognizes this inefficiency and added
a new requirement to the 2016 version
that prevents reheating this air to any
warmer than 60F during the cooling
Standard 920 also requires the 70F at each of the four test conditions
season:
equipment to operate at four different (see sidebar). If the equipment's HGRH
dry-bulb temperatures entering the air- system is unable to achieve this minimum "Units that provide ventilation air to
cooled condenser: 95F, 80F, 68F, and leaving-air temperaturewhich is likely to multiple zones and operate in
occur at rating condition D, for example conjunction with zone heating and
60F. But the air entering the evaporator
cooling systems shall not use heating
coil matches the outdoor-air conditions, supplemental reheat energy must be or heat recovery to warm supply air
so it is different at each of these four accounted for when determining Moisture above 60F when representative
conditions. This depicts how a Removal Efficiency (MRE). building loads or outdoor air
100-percent outdoor-air unit would temperature indicate the majority of
DX dedicated OA units are more energy zones require cooling."3
operate during different times of the year
(see Figure 2). intense than conventional air conditioners
For more discussion of cold versus
for several reasons: neutral air in a dedicated OA system,
In addition, because Standard 920 is refer to the Trane application guide,
More compressor capacity (and power)
intended to rate the dehumidification Dedicated Outdoor Air Systems
per CFM due to the higher sensible (SYS-APG001-EN).
capacity and efficiency of a dedicated OA load of cooling 100-percent outdoor air
unit, the evaporator must dehumidify the (versus a mixture of outdoor and
air to a leaving-air dew point no higher recirculated air)
than 55F at each of the four test
More compressor capacity (and power) [3] ASHRAE Standard 90.1-2016,
conditions.
Section 6.5.2.6
per CFM due to the higher latent load
This emphasizes a third difference of dehumidifying 100-percent outdoor
between the standards. Whereas air to no higher than a 55F dew point
Standard 340/360 is a static test,
More fan power per CFM due to the
Standard 920 is a dynamic test that
need for deeper/denser evaporator
requires dehumidification capacity
coils and hot gas reheat coils
modulation via compressor staging,
variable-speed or variable-capacity Possible added power demand due to
compressors, or other methods of the need for compressor capacity
capacity modulation. modulation

And finally, Standard 920 also Therefore, DX dedicated OA units should


incorporates the impact of hot gas be specified using the rating standard
reheat (HGRH) on equipment efficiency, (AHRI 920) developed specifically to reflect
since the dry-bulb temperature of the air these differences.
leaving the unit must be no lower than

providing insights for todays HVAC system designer Trane Engineers Newsletter volume 454 3
New Efficiency Table 2. Minimum efficiency requirements for electrically-operated DX-DOAS units without energy recovery

Requirements Added to Equipment Type Subcategory Minimum efficiency Test procedure


Air-cooled
ASHRAE Standard 90.1 4.0 ISMRE
(dehumidification mode)
Air-source heat pump
After AHRI Standard 920 was published, 4.0 ISMRE
(dehumidification mode)
the ASHRAE Standard 90.1 committee
Water-cooled cooling tower condenser water 4.9 ISMRE
drafted addendum CD to include minimum
(dehumidification mode) chilled water 6.0 ISMRE
efficiency requirements for DX dedicated
ground-source, closed loop 4.8 ISMRE AHRI Standard
OA units. Water-source heat pump
groundwater-source 5.0 ISMRE 920-2015
(dehumidification mode)
"Dedicated outdoor air systems (DOAS) ... water-source 4.0 ISMRE
are now used in many buildings covered by Air-source heat pump
2.7 ISCOP
ASHRAE 90.1. However, the current (heating mode)

ASHRAE 90.1 standard has no minimum ground-source, closed loop 2.0 ISCOP
Water-source heat pump
energy efficiency requirements for this groundwater-source 3.2 ISCOP
(heating mode)
equipment. Through AHRI, manufacturers of water-source 3.5 ISCOP

DOAS developed Standard 920 to establish


common rating conditions for these
products. This proposal establishes for the Table 3. Minimum efficiency requirements for electrically-operated DX-DOAS units with energy recovery
first time a product class for DOAS." 4
Equipment Type Subcategory Minimum efficiency Test procedure
Air-cooled
This addendum included minimum 5.2 ISMRE
(dehumidification mode)
efficiencies for this class of equipment,
Air-source heat pump
which are based on the Integrated 5.2 ISMRE
(dehumidification mode)
Seasonal Moisture Removal Efficiency
Water-cooled cooling tower condenser water 5.3 ISMRE
(ISMRE) and Integrated Seasonal
(dehumidification mode) chilled water 6.6 ISMRE
Coefficient of Performance (ISCOP)
ground-source, closed loop 5.2 ISMRE AHRI Standard
defined by AHRI Standard 920 (Table 2 and Water-source heat pump
groundwater-source 5.8 ISMRE 920-2015
Table 3). (dehumidification mode)
water-source 4.8 ISMRE
Addendum CD to ASHRAE 90.1-2013 went Air-source heat pump
3.3 ISCOP
(heating mode)
through two public reviews before being
ground-source, closed loop 3.8 ISCOP
approved by the ASHRAE Board of Water-source heat pump
groundwater-source 4.0 ISCOP
Directors on September 6, 2016. (heating mode)
water-source 4.8 ISCOP
The 2016 version of Standard 90.1 will
include these tables of minimum efficiency
requirements in Section 6.4.1.

Calculating Moisture Removal Capacity Note: In this equation, 4.5 is not a constant, but The required MRC of the dedicated OA unit in this
(MRC). The example in Figure 3 depicts a is derived from multiplying the density of air at example is 212 lb/hr (or about 25 gallons/hr):
dedicated OA unit that dehumidifies 4000 cfm "standard" conditions (69F dry air at sea level
of outdoor air from 84F dry bulb and 76F dew has a density of 0.075 lb/ft3) by the conversion MRC = 4.5 4000 cfm (135.9 - 53.4 gr/lb) /
point (which equates to a humidity ratio of of 60 minutes/hr. Air at other conditions and (7000 gr/lb) = 212 lb/hr
135.9 grwater/lbdry air) to a leaving-air dew point elevations will cause this factor to change.
of 50F (which equates to 53.4 grwater/lbdry air).
Figure 3.
Moisture Removal Capacity (MRC) = Example calculation of MRC
4.5 Vot (WOA - WCA) / (7000 gr/lb)
OA
where,
WOA = 135.9 gr/lb
m

MRC = Moisture Removal Capacity, lb/hr


cf
00
40

Vot = design outdoor airflow, cfm


=
ot
V

WOA = humidity ratio of the entering outdoor


air, gr/lb CA WCA = 53.4 gr/lb

WCA = humidity ratio of the leaving


conditioned (dehumidified) air, gr/lb

[4] Excerpt from the "Foreword" to addendum


CD to ASHRAE Standard 90.1-2013

4 Trane Engineers Newsletter volume 454 providing insights for todays HVAC system designer
Further, Section 6.4.1.4 of Standard 90.1 By John Murphy, applications engineer, Trane. You
can find this and previous issues of the Engineers
requires verification of equipment How This Impacts Newsletter at www.trane.com/EN. To comment,
efficiency information provided by the Specifying Engineers send e-mail to ENL@trane.com.
manufacturer. If a certification program
exists for the product class, then the
Use MRC and ISMRE (tested in
selected product must be either listed in
accordance with AHRI Standard 920)
the directory of certified products
when specifying the required
(www.ahridirectory.org) or its efficiency
dehumidification performance of a
rating(s) must be verified by an References
DX dedicated OA unit; and not IEER
independent laboratory test report (per
based on AHRI Standard 340/360. ANSI/ASHRAE/IES, Standard 90.1-2016,
options B and C, listed below). However, if
Energy Standard for Buildings Except Low-
no certification program exists for the As explained in this EN, DX dedicated Rise Residential Buildings (I-P Edition),
product class, then the efficiency rating OA units are constructed differently, Atlanta: ASHRAE, 2016.
data furnished by the manufacturer is tested differently, and operated ANSI/ASHRAE/IES, Standard 90.1-2013,
considered sufficient for demonstrating differently than conventional DX air Energy Standard for Buildings Except Low-
compliance (per option D, listed below). Rise Residential Buildings (I-P Edition),
conditioners. Therefore, they should be
Atlanta: ASHRAE, 2013.
specified using AHRI Standard 920,
"Equipment efficiency information ANSI/AHRI Standard 920-2015,
which was developed to reflect these
supplied by manufacturers shall be Performance Rating of DX Dedicated Outdoor
differences. When specifying the Air System Units. Air-Conditioning, Heating
verified by one of the following:
required MRC for a specific application, and Refrigeration Institute. 2015.
(a) be sure to also specify the associated
AHRI Standard 340/360-2015, Performance
(b) If a certification program exists for a airflow and entering-air conditions (see Rating of Commercial and Industrial Unitary
covered product, and it includes sidebar). Air-Conditioning and Heat Pump Equipment,
Air-Conditioning, Heating and Refrigeration
provisions for verification and Institute, 2015.
challenge of equipment efficiency Help educate code officials that the
ratings, then the product shall be current version of ASHRAE Standard
listed in the certification program. 90.1 does not prescribe minimum
efficiency requirements for DX
(c) If a certification program exists for a
dedicated OA units by informing
covered product, and it includes
them about the new tables being
provisions for verification and
added to the 2016 version of the
challenge of equipment efficiency
standard.
ratings, but the product is not listed in
the existing certification program, the Since there was no industry standard to
ratings shall be verified by an uniformly rate the efficiency of this
independent laboratory test report. class of equipment, previous and
(d) If no certification program exists for a current versions of Standard 90.1 did
covered product, the equipment not prescribe a minimum equipment
efficiency ratings shall be supported efficiency for DX dedicated OA units.
by data furnished by the This will change with the publication of
manufacturer." 5 ASHRAE 90.1-2016 when minimum
efficiency requirements, tested in
AHRI is in the process of starting a accordance with AHRI Standard 920,
certification program for DX dedicated OA are added to the standard for the first
units, to accompany AHRI Standard 920. time.
Until that is in place, however, efficiency
rating data furnished by the manufacturer Until the corresponding certification
is sufficient for demonstrating compliance program is in place, efficiency rating
with Standard 90.1. data furnished by the manufacturer is
sufficient for demonstrating compliance
with Standard 90.1. However, once the
certification program is in place, the
product must be listed in AHRI's
directory of certified products
(www.ahridirectory.org) or the ratings
must be verified by an independent
[5] ASHRAE Standard 90.1-2016, laboratory test report.
Section 6.4.1.4

providing insights for todays HVAC system designer Trane Engineers Newsletter volume 454 5
www.Trane.com/bookstore
HVAC Educational Resources

On-demand continuing education credit for LEED and AIA.


60 to 90-minute, on-demand programs available free of charge. Check
out the newest courses:
DIY Chiller Plant Performance Modeling: Easy and Easier
Delivering Performance from Airside Economizers

View a complete list of courses at www.trane.com/


continuingeducation.

Engineers Newsletters. Quarterly articles that cover timely topics


related to the design, application and operation of commercial HVAC
systems. Subscribe at trane.com/EN.

Air conditioning clinics. A series of educational presentations that


teach HVAC fundamentals, equipment and systems. The series
includes full-color student workbooks, which can be purchased
individually. Approved by the American Institute of Architects for 1.5
(Health, Safety and Welfare) learning units. Contact your local Trane
office to sign up for training in your area.

Engineers Newsletter Live. A series of 60 to 90-minute programs


that provide technical and educational information on specific aspects
of HVAC design and control. Topics range from water- and airside
system strategies to ASHRAE standards and industry codes. Contact
your local Trane office for a schedule of upcoming events or order
DVDs of past programs by visiting www.trane.com/ENL.

Application manuals. Comprehensive reference guides that can


increase your working knowledge of commercial HVAC systems.
Topics range from component combinations and innovative design
concepts to system control strategies, industry issues, and
fundamentals. View a complete list of manuals available to order at
www.trane.com/bookstore.

6 Trane Engineers Newsletter volume 454 providing insights for todays HVAC system designer
Mark your calendars
Plan to Attend These 2017 Programs!

2017 Engineers Newsletter Live programs


Energy-Saving Strategies for Small Rooftop
Systems discusses various design and control strategies that
can reduce energy use in these types of systems, and reviews new
requirements in ASHRAE Standard 90.1 related to these systems.

HVAC Myths and Realities addresses various myths,


claims, and misunderstandings in the HVAC & R market place then
follows with technically correct details, examples and situations to
help design teams evaluate the likelihood of actually realizing claimed
effectiveness, performance and savings.

High-Performance Air Systems examines the properties of


high-performance air systems and provides guidance on their design.
Topics include right-sizing and proper component selection, duct
design guidelines, system control strategies, selection for part-load
efficiency and much more.

Demand Response in Commercial Buildings discusses


the relevant improvements that load shifting and demand response
can provide, with examples of the types of utility and funding
programs that are available.

Contact your local Trane ofce for details or visit Trane.com/ENL.

2016 Trane a business of Ingersoll Rand. All rights reserved.


ENL-SLB001-EN October 2016

ENL-SLB001-EN_ENL2017Postcard.indd 2 10/7/2016 10:35:45 AM

providing insights for todays HVAC system designer Trane Engineers Newsletter volume 454 7
www.Trane.com/TRACE
Check Out the Latest TRACE 700 Release!
The latest release of TRACE 700 focuses on updating and adding
to the standard libraries included in the program. Check out the latest
release which features the following

ASHRAE Standard 90.1-2013 libraries. Previously the TRACE


library included equipment and constructions for 90.12004,
2007, and 2010. This has now been expanded to include 90.1-
2013 equipment and constructions to support the LEED v5.
CVHS Library Trane Series S CenTraVac chiller is now
available as cooling equipment library in the program. This
can be found in the water-cooled chiller category. Remember, you
can still import Trane equipment selections from TOPSS into
TRACE.

Visit www.Trane.com/TRACE to view version details or download a


free 30-day trial.

Trane, Trane believes the facts and suggestions presented here to be accurate. However, final design and
A business of Ingersoll Rand application decisions are your responsibility. Trane disclaims any responsibility for actions taken on
the material presented.
For more information, contact your local Trane
TM The following are registered trademarks of United States Green Building Council: LEED
office or e-mail us at comfort@trane.com
TM The following are registered trademarks of Trane: TRACE and CenTraVac

8 Trane Engineers Newsletter volume 454 ADM-APN060-EN (November 2016)