Anda di halaman 1dari 5

cooling prize paper

The uplift capacity of transmission


pylon foundations
Frederick Levy, University of Southampton and National Grid UK

Abstract
The National Grid high Table 1: Foundation design parameters
voltage network requires urgent Soil strength Type Measurement Frustrum angle (o)
refurbishment to accommodate
the demands of the 21st century. Cohesionless Strong SPT N 15 (N<20)
However, there is significant Weak 25
uncertainty surrounding the
in-service uplift performance Cohesive Strong Undrained shear 15 (su<49)
of transmission pylon shallow Weak strength (su) 25
foundations under dynamic
(wind) loading. This uncertainty Source: National Grid, 2004
has been driven by the apparent
understrength of foundations when
tested using current industry testing Table 2: The design test from BS EN61773:1996
practice.
Test type Load steps of design Increment time (minutes)
A suite of full-scale tests on
capacity (%)
transmission pylon foundations
was commissioned at a London Design test 25, 50, 70, 80, 90 and 10
clay site in Kent. The tests aimed to 100 30 at 100%
mimic in-service dynamic loading
to reveal the mechanisms associated Source: BSI, 1996
with rapid foundation uplift. It was
shown that foundations founded on
London clay mobilised significantly the foundation system being loaded The high voltage network pylon foundation system behaviour
greater uplift capacities at smaller in tension (uplift) or compression with incremental upgrades and is therefore required to facilitate
displacements compared with (bearing) (Figure 1). refurbishments has been able to this upgrade in a cost-effective and
current industry practice. To prevent excessive buckling weather nearly half a century of timely manner.
The results also suggested that stresses, differential movement changing demand and generation Recent studies undertaken by
aspects of current uplift design, of the foundation system needs patterns. The recent 2020 University of Southampton and
namely failure mechanism geometry to be limited. During loading renewable targets (BERR, 2008) field tests by National Grid have
and ultimate limit state criterion, the compression foundations in combination with saturation of demonstrated that the design
may also require revision. displacement will be limited due to capacity has necessitated a major basis for transmission pylon
soil beneath it, whereas as uplifted program of restringing and uprating foundations may not be reliable.
1. Introduction foundation is pulled out of the old cables (Clark et al., 2006). This It has been statistically shown that
In the UK there are approximately ground it accumulates resistance program will result in significant when subject to testing, half of the
22,000 high voltage (275/400kV) before eventually shedding all load increases of loading on transmission foundations tested did not reach
transmission pylons supported carrying capacity. The performance pylon foundations systems due to their uplift design capacity (Figure
by a shallow foundation under of the system therefore relies on a larger cable sizes. 2). Yet the present failure rate of
each pylon leg. The loading of a sound understanding of foundation The need for a better pylon foundations is extremely low,
transmission pylon will result in uplift performance. understanding of transmission suggesting that there are additional

100
Percentage of sample (%)

Vertical loads
Horizontal loads
(tranverse and
longitudinal components) 80

60

40

20

0
0 20 40 60 80 100 120 140 160
Uplift resistance/design capacity (%)

Figure 1: Transmission pylon foundation system and loading Figure 2: Sample of field tests (n=45)

24 ground engineering october 2013


Load

Backfill
H=3m

25 25

London
Clay

B=1.45m

2.5m
Figure 3: L4M foundation Figure 4: Construction of an L4M foundation

factors contributing to uplift centrifuge modelling from being


resistance. made.
Centrifuge model tests on This paper aims to investigate
transmission pylon foundations has pylon foundation capacity by
shown that uplift resistance under conducting a set of full-scale
rapid loading may be enhanced due rapid foundation uplift testing to
to the development of negative pore compare the dynamic response to
water pressures (suctions) across the standard static testing practise. The
foundation base. It was shown that purpose of the field tests was to
this increase in uplift resistance had introduce the effects of construction
a log linear relationship with the practices, tolerances and defects
uplift velocity (Lehane et al., 2008). typical of those encountered in the
These model tests were conducted field that are likely to influence the
using kaolin clay the preferred performance of a foundation subject
soil for centrifuge modelling work to uplift.
due to its uniformity and drainage Figure 5: Load application
characteristics. However, it exhibits 2. Design and construction
a soft response in comparison to practice (National Grid, 2004) that extends The ultimate limit state (ULS)
clays encountered in the field. Uplift resistance (specified by to the surface from the base of the displacement criterion of shallow
Similarly, the close control in model National Grid in TS 3.04.15) foundation (Figure 3). The frustum foundations is considered to be
tests may not be replicated in the is derived from weight of the angle, and therefore the geometry of approximately 10% of foundation
field. These limitations prevent foundation and soil, contained the failure mechanism, is governed width (B) (BSI, 2004). However,
confident extrapolations from within an inverted frustum by the insitu soil properties (Table 1). the ULS displacement (w) criterion
of specified in TS 3.04.15 for all
Table 3: Load schedule foundations is w = 10mm. This
value is based on the assumption
Foundation Test Backfill Base Uplift velocity (mm/s) Displacement w (mm)
that it represents the elastic limit of
1 1-A Loose London London clay 35 150 the backfill in uplift (CIGRE, 1998).
clay A truncated mass concrete
pyramid base with a reinforced
2 2-A Dense London London clay 5 15 concrete inclined chimney is the
clay 15 most common foundation type for
2-B 150
transmission pylons in the UK. The
3 3-A Type 2 Type 2 15 15 foundation is cast inside a large
3-B 10 150 excavation typically backfilled using
excavated or imported material
4 4-A Type 2 London clay Design test - compacted in 300mm layers.
4-B 15 150 Foundation testing practice in the
5 5-A Type 2 London clay 35 150 UK is codified by EN 61773:1996
(BSI, 1996). A summary of

ground engineering october 2013 25


cooling prize paper
Corrected cone resistance, qt (MPa) Sleeve friction (kPa)
0 1 2 3 4 5 0 50 100 150 200
0 0
Depth (m)

Depth (m)
0-3m = Type 2
-2 3-10m+ = London clay -2

0-10m = London clay


-4 -4

-6 -6

0-3m = Type 2
-8 -8
3-10m+ = London clay
0-10m = London clay
-10 -10

Figure 6: Cone resistance profiles (Foundation 5) Figure 7: Sleeve friction profiles (Foundation 5)

the incremental design test is the isolation of each resistance


presented in Table 2. This type mechanism. The performance Pore water pressure (kPa)
of test has been routinely used to of footings subjected to dynamic -100 0 100 200 300 400 500 600
assess foundation capacity since loading was scrutinised by using 0
Depth (m)

the 1960s (Parr and Vanner, 1962) varying uplift velocities and Foundation 1
and is the source of the uncertainty displacements. A design test to BS Foundation 2
surrounding the in service uplift EN61773:1996 (BSI, 1996) was also -2
performance of transmission pylon carried out to provide design test
foundations. results for the L4M foundation type.
Load was applied to each -4
3. Field tests foundation stubs using an inclined
3.1 Site layout and load schedule hydraulic jack (Figure 4). The load-
Five foundations were constructed at displacement behaviour of the -6
the Building Research Establishment foundations was measured using
London clay test site at Lodge Hill a load cell mounted above the
Camp in Chattenden during August hydraulic jack and linear voltage
-8
2009. The foundations were designed displacement transducers (LVDTs)
and constructed to TS 3.04.15 on a reference beam.
(National Grid, 2004) with uplift
capacities of 420kN. 3.2 Ground conditions -10
To determine whether suctions Chattenden has been used
occurred at field scale the extensively for foundation testing Figure 8: Pore water pressure through backfills and in situ clay
foundations were installed with due to its deep (~30m) and uniform
different base contact conditions, London clay strata. Testing was water at the base of the excavations the same loss in strength was not
backfill material and uplifted at conducted over two weeks in July in combination with the rapid uplift experienced in the London clay
different velocities to w/B = 10% 2012. Due to wet weather in the velocities was expected to result in backfills.
(150mm). Two foundations were weeks prior to testing the top layer the development of an undrained The inferred values of undrained
backfilled with compacted or loose of weathered clay became soft condition (suctions) on the base of shear strength (su) and density ()
London clay representing early requiring remediation with 40t of the foundations. of the London clay corroborated
construction practices (Parr and stone. The inundation of water in the with previous observations (Butcher
Vanner, 1962). The remaining Five 10m deep cone penetration compacted Type 2 granular backfills et al., 2008). A summary of the
foundations used compacted Type tests (CPTs) were used to appears to have caused a significant in situ values from the CPTs at
2 a coarse granular material from characterise the site and backfills. loss in strength resulting in very low Footing 5 is presented in Table 4.
recycled aggregate (Department of The measurements of pore water penetration resistances (Figures These values were used for a set of
Transport, 2009) and represented pressure from the CPTs through the 6 and 7). The low strength of the effective and total numerical back-
current practice. backfills confirmed that water had granular backfill contrasts with the analysis studies.
The load schedule in Table 3, significantly infiltrated the voids relatively stiff and homogeneous in Table 5 presents a summary of the
in combination with the different in the London clay and Type 2 situ London clay. The CPT results record uplift resistances (Q). Only
forms of construction, allowed backfills (Figure 8). The pooling of from Foundations 1 suggested the rapidly loaded foundations on

Table 4: CPT results


Depth (m) E backfill (kPa) E insitu (kPa) backfill insitu backfill (o) insitu (o) Su backfill (kPa) Su insitu
(kN/m3) (kN/m3) (kPa)
1.5 T2: 7,840 7,185 T2: 17.4 18.0 T2: 31 32 T2: n/a 31.8
LC: 11,600 LC: 17.6 LC: 32 LC: 50
3 T2: 1,770 12,300 T2: 15.3 18.3 T2: 31 31 T2: n/a 54.8
LC: 13,400 LC: 18.5 LC: 32 LC: 76

10 n/a 31,800 n/a 19.3 n/a 32 n/a 132.5

26 ground engineering october 2013


300 6

Suction factor
Normalised uplift resistance, Q/A (kN/m2)

Field test
Lehane et al (2008)
250 5

200 4

150 3

Test 1-A 2
100
Test 2-B
Test 5-A
50 vf=100mm/s, Lehane et al (2008) 1
vf=30mm/s, Lehane et al (2008)
0
0
0 1 2 3 4 5 6 7 8 9 10 100 101 102 103 104 105 106 107

Normalised displacement, w/B (%) Normalised uplift velocity, vfB/cv

Figure 9: Rapid load test results Figure 10: Suction factor

600 500
Uplift resistance (kN), applied load (KN)

Uplift resistance (kN)

500
400

400
300
300

200
200 Test 5-A
Test 3-B Eu /su=490
Test 4-A (design test) 100 Eu=184 MPa, Gasparre et al (2007)
100
Test 5-A Eu=122 MPa, Gasparre et al (2007)
0 0
0 10 20 30 40 50 60 70 80 90 100 0 5 10 15 20 25 30 35 40 45 50
Displacement, w (mm) Displacement, w (mm)

Figure 11: Design test results compared to pullout tests Figure 12 Total stress numerical results

London clay mobilised resistances extremely stiff response, 90% peak was limited by operational value of When compared using a suction
that were within 10% of the design resistance before w/B = 1%. The su of the London clay underneath factor, where the capacity difference
capacity at ULS. The design test different uplift rates did not affect the foundations. between foundations with and
(Foundation 4 Test 4-A) only the load-displacement behaviour. Figure 9 compares the field tests without suction is normalised with
reached ~50% of its design capacity The measured differences in uplift with results from the aforementioned the foundation area and su on the
at w = 10mm, consistent with capacities between rapid tests was centrifuge tests (Lehane et al., 2008) base (Qsucton - Qno suction/suB2),
previous observations (Parr and <10% at w = 10mm with a maximal with uplift capacities normalised to the results from the Chattenden
Vanner, 1962, Clark et al., 2006). difference of 50kN at peak. From the foundation base areas. The peak field test closely match that from the
Lehane et al. (2008) it is inferred capacities of the centrifuge tests centrifuge model tests (Figure 10). It
4.1 Rapidly loaded foundations that the rate independence meant are within ~20% of the field tests, is proposed that the spline fit from
The rapidly loaded foundations that full suctions occurred on the which may be due to differences in Lehane et al. (2008) is replicated
on London clay exhibited an base and therefore peak capacity the values of su between tests. for different values of consolidation
coefficient (cv = khE/w).
Table 5: Summary of results
4.2 Static design tests results
Foundation Test Q10mm Q25mm Qpeak (kN) Design capacity A design test (BSI, 1996) was
(ULS) (kN) (kN) (kN) carried out on Foundation 4
(Figure 11). Under the applied
1 1-A 416 436 439 420
load increments the foundation
2 2-A 391 - 432 420 performed poorly, reaching only
2-B 367 440 471 420 50% of design capacity at ULS. The
difference between the rapid loading
3 3-A 332 - 350 420 methodology and the design test
3-B 162 247 571 420 was marked. It has previously been
shown that peak loads are applied
4 4-A 234 234 303 420 rapidly (Clark et al., 2006). It may
4-B 162 224 515 420 therefore be the case that the rapid
5 5-A 433 455 483 420 test is more applicable and the
design test is unduly conservative.

ground engineering october 2013 27


cooling prize paper
Figure 11 also shows the References
results from Test 3-B; rapid uplift
BERR (2008) UK Renewable Energy
excluding suction. It is evident
Strategy. Department for Business
that the performance of Type 2 Enterprise Regulatory Reform,
granular fill is extremely poor. Large London, UK.
displacements were required for BSI (1996) EN 61773:1996. Overhead
the backfill to compact sufficiently lines Testing of foundations for
to reach design capacity. Such a structures. BSI, London, UK.
poor performance will require a BSI (2004) EN 1997-1:2004.
re-evaluation of the use coarse Eurocode 7: Geotechnical design,
granular material, specifically Part 1: General rules. BSI, London,
Type 2, when used in excavations UK.
bounded by London clay. Butcher, A P; Powell, J M M;
Kightley, M; and Troughton, V (2008)
5. Numerical modelling Comparison of behaviour of CFA
A set of numerical back-analysis piles in London clay as determined
studies were conducted to by static, dynamic and rapid testing
reproduce the load-displacement methods. In 5th International
behaviour of the tested foundations. Symposium on Deep Foundations on
Bored and Auger Piles (BAP V) (Van
An axisymmetric foundation finite Impe, P & Van Impe, W F (eds)). CRC
element model was analysed using Figure 13: Granular backfill failure modes at w = 10mm and Press, Ghent, Belgium. pp. 205-212.
OASYS SAFE (Oasys, 2009) with w = 50mm
CIGRE, (1998) Probabilistic Design
total and effective stress soil models. of Transmission Line Structure
The total stress soil model was numerical back analysis that the (in general) before the specified Foundations. International Council
used to examine the mobilised failure mechanism may not occur ultimate limit state. This includes on Large Electronic Systems, Paris,
undrained shear strength and when granular backfill is used to the performance of footings where France, SC-22 WG07.
stiffness on the base of the fill an excavation in cohesive soil. suction developed. In the cases Clark, M; Richards, D J; and
foundation. The stiffness of the There therefore must be a careful where suctions did not develop, the Clutterbuck, D (2006) Measured
Chattenden field tests varied re-examination of the failure uplift performance of the footings dynamic performance of electricity
between Eu = 184MPa (w 2.5mm) mechanism used in design, with was extremely poor. transmission towers following
and Eu/su = 490 (w = 50mm) attention paid to combinations of Also demonstrated was that controlled broken-wire events.
(Figure 12). The former stiffness backfill and insitu material. current testing practice may have International Council on Large
Electronic Systems, Paris, France,
value corresponds to undrained The field tests showed that the led to an undue underestimation of
Paper B2-313.
triaxial tests on London clay expectation that full uplift capacity foundation uplift capacity due to the
samples from Heathrow Terminal 5 will be mobilised within the specified manner of test load application. Department of Transport (2009)
MCHW Volume 1 Series 800, Road
(Gasparre et al., 2007). ULS criterion of w = 10mm may be The differences in observed uplift
pavements Unbound Cement and
The large values of stiffness unreasonable. The field test results resistances due to rapid loading Other Hydraulically Bound Mixtures.
contrast starkly to the soft kaolin indicate that only those foundations requires further consideration DoT, London, UK.
clay (Eu/su = 50) used in previous that mobilised suctions had uplift of the in service applied loading Gasparre, A; Nishimura, S; Minh, N A;
centrifuge model tests (Rattley et al., capacities within 5% of design typically transmitted to foundation Coop, M R; and Jardine, R J (2007)
2008). The numerical back analysis capacity at w = 10mm. To develop systems. This can be achieved The stiffness of natural London Clay.
also suggested that the operational a more legitimate criterion a through careful instrumentation Gotechnique, 57(1): 3-18.
value of su on the foundation bases rigorous examination of foundation and monitoring through foundation Lehane, B M; Gaudin, C; Richards,
was on average 41kPa, close to system performance (differential systems from their base upwards D J; and Rattley, M J (2008) Rate
the CPTs values recorded on site movement) with relation to the using accelerometers together effects on the vertical uplift capacity
suggesting that there may be merit development of buckling stresses with instrumentation to determine of footings founded in clay.
in using such instrumentation to in the transmission pylon structure external loads and structural loads. Gotechnique, 58(1): 13-21.
predict uplift resistances. needs to be undertaken. With recent developments in National Grid (2004) TS 3.4.15.
The effective stress model aimed Finally, the design test according data logging and transmission it Overhead line support foundations.
to capture the development of the to BS EN61773:1996 (BSI, would be relatively straightforward NG, Warwick, UK.
granular backfill failure mechanism. 1996) appears to yield extremely to fully instrument a high voltage Oasys 2009. Safe: Version 19.
The displacement vector plots conservative results in comparison transmission pylon from the base London, UK.
of Figure 13 show that the uplift to the rapid uplift methodology. upwards. Through such endeavours Parr, R G; and Vanner, M J (1962)
resistance at w = 10mm is solely Both methods seek to apply the a better design and testing rationale Strength Tests on Overhead Line
due to the backfill overburden maximum design load arising may be developed, leading to more Tower Foundations. Electrical
immediately above the pyramid. from transmission pylon design. sustainable refurbishment solutions. Research Association, Leatherhead,
The failure mechanism at w = 50mm Crucially, the rapid methodology UK, Report O/T28.
reaches the excavation interface does so within 2s, which may better Acknowledgments Rattley, M J; Richards, D J; and Lehane,
but breakout was not observed on replicate the dynamic loading of The work presented forms part of B M (2008) Uplift performance
site. Both of these observations are transmission pylon compared to a wider examination of shallow of transmission tower foundations
embedded in clay. Journal of
contrary to the design methodology the static incremental loading of foundation performance, funded
Geotechnical and Geoenvironmental
of the frustum method (National the design test. Current statnamic and supported by the National Grid. Engineering, 134(4): 531-540.
Grid, 2004). testing of piles bears the closest The author is grateful for technical
relation to the dynamic testing used advice and support from David
6. Impact at Chattenden. Clutterbuck and Boud Boumeced
The finds of the field tests have of National Grid and University
highlighted significant limitations of 7. Conclusions of Southampton professor David
current design and testing practice. The series of field tests on a number Richards.
Current design practice makes use of full-scale L4M footings has The foundations were constructed
of the frustum mechanism, which confirmed that base suction may by Grid Line Foundations and
due the geometry of excavations is contribute significantly to footing testing was undertaken by ESG.
assumed to breakout of the backfill performance. The results have The support of Andrew
into the insitu soil. However, it also shown that the design uplift Hewitt of Lankelma is also
has been demonstrated through performance may be not reached gratefully acknowledged.

28 ground engineering october0 2013

Anda mungkin juga menyukai