Rev-01
Prepared By
Gulf Consulting Group
Eng. Ahmed M. Sami
###
Plumbing Calculation
Rev-01
1- Building specification :
so get total building height (static head) 135 m
2- For residential :
No. of bed room in the building : 288 Bed room
No. of person in the room : 2 Person
No of person 576 Person
Assume daily water consumption in L/s/person 180 L/day
Then the total water consumption of building 103.68 m3
13-For School :-
NO. of Student 0 Student
Assume daily water consumption in L/student 75 L/student/day
Daily water consumption 0 m3
14-For Airport :-
NO. of Passenger Per Day 0 Passenger
Assume daily water consumption in L/passenger 20 L/passenger/day
Daily water consumption 0 m3
17-For Camps :-
NO. of person 0 Person
Assume daily water consumption in L/person 75 L/person/day
Daily water consumption 0 m3
19-For Mosque :-
NO. of person 0 Person
Assume daily water consumption in L/person 30 L/person/day
Daily water consumption 0 m3
26-For Farms :-
No. of Caws 0 caw
No. of Calf 0 calf
No. of goats & sheep 0 goat & sheep
No. of horses 0 horses
No. of egg Chicken 0 Chicken
No. of turkey Chicken 0 Chicken
No. of ducks 0 duck
No. of camel 0 Camel
Daily water consumption 0 m3
Septic Tank
the storage will be fo3 day 458 m3
Table of total fixtures
Total
FIXTURES / POINT NO. B3 B2 B1 G.F. F.F 2nd.F 3rd F 4th F. 5th F 6th F TYP. F
fixtures
Water closet (flush valve) 1 1 1 1 1 1 1 1 1 1 26 426
Water closet (flush tank) 0 0 0 0 0 0 0 0 0 0 0
Water Bidet 0 1 0 0 0 0 0 0 0 0 16 257
Hose for W.C 0 1 0 0 0 0 0 0 0 0 1
Lavatory (& H.B.) 0 0 0 0 0 0 0 0 0 0 26 416
Kitchen sink 0 1 0 0 0 0 0 0 0 0 16 257
Service sink office,ect 0 0 0 0 0 0 0 0 0 0 0
Shower 1 1 1 1 1 1 1 1 1 1 10 170
Bath tub 0 0 0 0 0 0 0 0 0 0 6 96
Dishwashing machine 0 0 0 0 0 0 0 0 0 0 10 160
Laundry 8 Ib 6 0 0 0 0 0 0 0 0 0 10 166
Laundry 16 Ib 0 1 0 0 0 0 0 0 0 0 1
Ablution (Public) 0 0 0 0 0 0 0 0 0 0 0
Urinal (1" flush valve) 0 0 0 0 0 0 0 0 0 0 0
Urinal (3/4" flush valve) 0 1 0 0 0 0 0 0 0 0 1
Urinal (flush tank) 0 0 0 0 0 0 0 0 0 0 0
Drinking fountain 3/8 in 0 0 0 0 0 0 0 0 0 0 0
SUM 1951
Total
FIXTURES / POINT NO. B3 B2 B1 G.F. F.F 2nd.F 3rd F 4th F. 5th F 6th F TYP. F
fixtures
Water closet (flush valve) 1 0 0 0 0 0 0 0 0 0 0 1
Water closet (flush tank) 1 0 0 0 0 0 0 0 0 0 0 1
Water Bidet 1 0 0 0 0 0 0 0 0 0 0 1
Hose for W.C 1 3 0 0 0 0 0 0 0 0 0 4
Lavatory (& H.B.) 1 0 0 0 0 0 0 0 0 0 0 1
Kitchen sink 1 0 3 0 0 0 0 0 0 0 0 4
Service sink office,ect 1 0 3 0 0 0 0 0 0 0 0 4
Shower 1 0 0 3 0 0 0 0 0 0 0 4
Bath tub 1 3 0 0 0 0 0 0 0 0 0 4
Dishwashing machine 1 0 0 0 0 0 0 0 0 0 0 1
Laundry 8 Ib 1 0 0 0 0 0 0 0 0 0 0 1
Laundry 16 Ib 1 0 0 0 0 0 0 0 0 0 0 1
Ablution (Public) 1 3 0 0 0 0 0 0 0 0 0 4
Urinal (1" flush valve) 1 0 0 0 0 0 0 0 0 0 0 1
Urinal (3/4" flush valve) 1 0 0 0 0 0 0 0 0 0 0 1
Urinal (flush tank) 1 2 2 0 0 0 0 0 0 0 0 5
Drinking fountain 3/8 in 1 0 0 0 0 0 0 0 0 0 0 1
SUM 39
A B C D E F G H I J
1 Pump will Calculated according to the type of project
2
3 Put ( X ) Beside The Type of Project
4
5 Appartemen x Hotels & Club Hospital
6
7 School Office Industerial
8
9 Put ( X ) Beside The Type of Heater Used
10
11 Individual Heaters Don`t Mark 2 Point
12
13 x Centeral Heater
14
15 Total length of water pipe for lift pump from ground to roof water tank 176 m
30 No. of Lift Pump To be Used = 3 Duty + 1 StandBy
31 No. of Boster Pump To be Used = 5 Duty + 1 StandBy
32
33 Lift Pump Selection
34 Pump Flow 160 GPM
35 Pump Head 283 PSI
36 Pump HP 45 HP
37 No. of Pumps 3 Duty + 1 StandBy
38
39 Boster Pump Selection
43 Pump Flow 81 GPM
44 Pump Head 35 PSI
45 Pump HP 3 HP
46 No. of Pumps 5 Duty + 1 StandBy
47
48 Pressure Vessel
49 Volume of Vessel 568 Liters
50
51
Filter will Calculated According to it's Location :-
Filter Selection
Filter Capacity 58 GPM
Filter Working Pressure 22 Psi
No. of Filters 3 Unit
Maximum Losses in Filter 15 Psi
Filteration Pump Capcity 88 GPM
Filteration Pump Head 26.4 Psi
Irrigation Pump Selection
Calculation Will be According to Type of The Building & Fixture Unit Methods:-
GYM
Calculation Will be According to Type of The Building & Fixture Unit Methods:-
GYM
Insert Pipe Length For Supply Network as We Don`t Know the Return Pipe Size