List of Nomenclature

Iz - current carrying capacity of the cable in thesituation where it is installed


It - tabulated current for a single circuit at an ambient temperature of 30C
Ib - design current, the actual current to be carried by the cable
In - rating of the protecting fuse or circuit breaker
I2 - operating current for the fuse or circuit breaker (the current at which the fuse blows or the circuit breaker opens)
Ca - correction factor for ambient temperature
Cg - correction factor for grouping
Ci - correction factor for thermal insulation.
Ta - Ambient temperature

Cable Selected
In/(Ca*Cg*Ci)
Rated/ Input

Voltage drop

Voltage drop
Adjustment

Earth cable

Earth cable
I2=In*1.45
Intallation

Voltage drop <


factors

Length
Power

length
Equipment

1.45Iz

Cable type
I2 <1.45Iz

4%*400V
In
Ib

Iz
kW A A condition method Ca Cg Ci A A A A m mV/A/m % mm2 Nos mm2 m

Chiller Room
Ta=35C, 1 X-88, 1 core
Chiller 1 314.70 567.77 800 D 0.96 0.77 1 1082.25 1268 1160 1839 OK 31.50 0.24 1.07 OK 240 2 240 31.5
core Unarmoured
Ta=35C, 1 X-88, 1 core
Chiller 2 314.70 567.77 800 D 0.96 0.77 1 1082.25 1268 1160 1839 OK 37.00 0.24 1.26 OK 240 2 240 37.0
core Unarmoured
Ta=35C, 1 X-88, 1 core
Chiller 3 314.70 567.77 800 D 0.96 0.77 1 1082.25 1268 1160 1839 OK 42.50 0.24 1.45 OK 240 2 240 42.5
core Unarmoured
Ta=35C, 1 X-88, 1 core
Chiller 4 314.70 567.77 800 D 0.96 0.77 1 1082.25 1268 1160 1839 OK 48.00 0.24 1.64 OK 240 2 240 48.0
core Unarmoured
Primary pump Ta=35C, 3 X-98, 3 core
22.00 39.69 63 D 0.96 0.77 1 85.23 100 91.4 145 OK 29.00 2.50 0.72 OK 16 1 16 29.0
1 core Unarmoured
Primary pump Ta=35C, 3 X-98, 3 core
22.00 39.69 63 D 0.96 0.77 1 85.23 100 91.4 145 OK 37.50 2.50 0.93 OK 16 1 16 37.5
2 core Unarmoured
Primary pump Ta=35C, 3 X-98, 3 core
22.00 39.69 63 D 0.96 0.77 1 85.23 100 91.4 145 OK 46.00 2.50 1.14 OK 16 1 16 46.0
3 core Unarmoured
Primary pump Ta=35C, 3 X-98, 3 core
22.00 39.69 63 D 0.96 0.77 1 85.23 100 91.4 145 OK 54.50 2.50 1.35 OK 16 1 16 54.5
4 core Unarmoured
Cable Selected
In/(Ca*Cg*Ci)
Rated/ Input

Voltage drop

Voltage drop
Adjustment

Earth cable

Earth cable
I2=In*1.45
Intallation

Voltage drop <


factors

Length
Power

length
Equipment

1.45Iz

Cable type
I2 <1.45Iz

4%*400V
In
Ib

Iz
kW A A condition method Ca Cg Ci A A A A m mV/A/m % mm2 Nos mm2 m

Secondry Ta=35C, 3 X-117, 3 core


30.00 54.13 125 D 0.96 0.77 1 169.10 192 181 278.4 OK 38.00 0.87 0.45 OK 50 1 25 38.0
pump 1 core Unarmoured
Secondry Ta=35C, 3 X-117, 3 core
30.00 54.13 125 D 0.96 0.77 1 169.10 192 181 278.4 OK 46.50 0.87 0.55 OK 50 1 25 46.5
pump 2 core Unarmoured
Secondry Ta=35C, 3 X-117, 3 core
30.00 54.13 125 D 0.96 0.77 1 169.10 192 181 278.4 OK 55.00 0.87 0.65 OK 50 1 25 55.0
pump 3 core Unarmoured
Secondry Ta=35C, 3 X-117, 3 core
30.00 54.13 125 D 0.96 0.77 1 169.10 192 181 278.4 OK 63.50 0.87 0.75 OK 50 1 25 63.5
pump 4 core Unarmoured
Secondry Ta=35C, 3 X-117, 3 core
30.00 54.13 125 D 0.96 0.77 1 169.10 192 181 278.4 OK 72.00 0.87 0.85 OK 50 1 25 72.0
pump 5 core Unarmoured
Condensor Ta=35C, 3 X-118, 3 core
55.00 99.23 160 D 0.96 0.77 1 216.45 246 232 356.7 OK 43.50 0.60 0.65 OK 70 1 35 43.5
pump 1 core Unarmoured
Condensor Ta=35C, 3 X-118, 3 core
55.00 99.23 160 D 0.96 0.77 1 216.45 246 232 356.7 OK 52.00 0.60 0.77 OK 70 1 35 52.0
pump 2 core Unarmoured
Condensor Ta=35C, 3 X-118, 3 core
55.00 99.23 160 D 0.96 0.77 1 216.45 246 232 356.7 OK 60.50 0.60 0.90 OK 70 1 35 60.5
pump 3 core Unarmoured
Condensor Ta=35C, 3 X-118, 3 core
55.00 99.23 160 D 0.96 0.77 1 216.45 246 232 356.7 OK 69.00 0.60 1.03 OK 70 1 35 69.0
pump 4 core Unarmoured
Chilled water
Ta=35C, 3 X-112, 3 core
make-up 2.20 3.97 10 D 0.96 0.77 1 13.53 23 14.5 33.35 OK 40 27.00 1.07 OK 1.5 1 1.5 40.0
core Unarmoured
pump 01
Chilled water
Ta=35C, 3 X-112, 3 core
make-up 2.20 3.97 10 D 0.96 0.77 1 13.53 23 14.5 33.35 OK 40 27.00 1.07 OK 1.5 1 1.5 40.0
core Unarmoured
pump 02

Cooling tower
Cable Selected
In/(Ca*Cg*Ci)
Rated/ Input

Voltage drop

Voltage drop
Adjustment

Earth cable

Earth cable
I2=In*1.45
Intallation

Voltage drop <


factors

Length
Power

length
Equipment

1.45Iz

Cable type
I2 <1.45Iz

4%*400V
In
Ib

Iz
kW A A condition method Ca Cg Ci A A A A m mV/A/m % mm2 Nos mm2 m

Cooling tower Ta=35C, 3 3 core


7.50 13.53 32 B 0.96 0.7 1 47.62 54 46.4 78.3 OK 31 6.80 0.71 OK 6 1 6 6.0
fan 01 core Unarmoured

Cooling tower Ta=35C, 3 3 core


7.50 13.53 32 B 0.96 0.7 1 47.62 54 46.4 78.3 OK 35 6.80 0.81 OK 6 1 6 6.0
fan 02 core Unarmoured

Cooling tower Ta=35C, 3 3 core


7.50 13.53 32 B 0.96 0.7 1 47.62 54 46.4 78.3 OK 39 6.80 0.90 OK 6 1 6 6.0
fan 03 core Unarmoured

Cooling tower Ta=35C, 3 3 core


7.50 13.53 32 B 0.96 0.7 1 47.62 54 46.4 78.3 OK 43 6.80 0.99 OK 6 1 6 6.0
fan 04 core Unarmoured

Cooling tower Ta=35C, 3 3 core


7.50 13.53 32 B 0.96 0.7 1 47.62 54 46.4 78.3 OK 31 6.80 0.71 OK 6 1 6 6.0
fan 05 core Unarmoured

Cooling tower Ta=35C, 3 3 core


7.50 13.53 32 B 0.96 0.7 1 47.62 54 46.4 78.3 OK 35 6.80 0.81 OK 6 1 6 6.0
fan 06 core Unarmoured

Cooling tower Ta=35C, 3 3 core


7.50 13.53 32 B 0.96 0.7 1 47.62 54 46.4 78.3 OK 39 6.80 0.90 OK 6 1 6 6.0
fan 07 core Unarmoured

Cooling tower Ta=35C, 3 3 core


7.50 13.53 32 B 0.96 0.7 1 47.62 54 46.4 78.3 OK 43 6.80 0.99 OK 6 1 6 6.0
fan 08 core Unarmoured

Cooling tower
Ta=35C, 3 3 core
makeup pump 1.14 2.06 6 B 0.96 0.7 1 8.93 23 8.7 33.35 OK 30 27.00 0.42 OK 1.5 1 1.5 1.5
core Unarmoured
01

Cooling tower
Ta=35C, 3 3 core
makeup pump 1.14 2.06 6 B 0.96 0.7 1 8.93 23 8.7 33.35 OK 30 27.00 0.42 OK 1.5 1 1.5 1.5
core Unarmoured
02
Notes:
Equipment

kW
Rated/ Input
Power

A
Ib

A
condition In

Intallation
method
Ca
Cg

Adjustment
Ci

factors
A

In/(Ca*Cg*Ci)
1. The cable that comes upto the isolator will be continued upto the cooling tower power panel
A

Iz
A

I2=In*1.45
A

1.45Iz

I2 <1.45Iz
m

Length
mV/A/m

Voltage drop
%

Voltage drop

Voltage drop <


4%*400V
mm2 Nos

Cable Selected

Cable type
mm2

Earth cable
m

Earth cable
length