Cable Selected
In/(Ca*Cg*Ci)
Rated/ Input
Voltage drop
Voltage drop
Adjustment
Earth cable
Earth cable
I2=In*1.45
Intallation
Length
Power
length
Equipment
1.45Iz
Cable type
I2 <1.45Iz
4%*400V
In
Ib
Iz
kW A A condition method Ca Cg Ci A A A A m mV/A/m % mm2 Nos mm2 m
Chiller Room
Ta=35C, 1 X-88, 1 core
Chiller 1 314.70 567.77 800 D 0.96 0.77 1 1082.25 1268 1160 1839 OK 31.50 0.24 1.07 OK 240 2 240 31.5
core Unarmoured
Ta=35C, 1 X-88, 1 core
Chiller 2 314.70 567.77 800 D 0.96 0.77 1 1082.25 1268 1160 1839 OK 37.00 0.24 1.26 OK 240 2 240 37.0
core Unarmoured
Ta=35C, 1 X-88, 1 core
Chiller 3 314.70 567.77 800 D 0.96 0.77 1 1082.25 1268 1160 1839 OK 42.50 0.24 1.45 OK 240 2 240 42.5
core Unarmoured
Ta=35C, 1 X-88, 1 core
Chiller 4 314.70 567.77 800 D 0.96 0.77 1 1082.25 1268 1160 1839 OK 48.00 0.24 1.64 OK 240 2 240 48.0
core Unarmoured
Primary pump Ta=35C, 3 X-98, 3 core
22.00 39.69 63 D 0.96 0.77 1 85.23 100 91.4 145 OK 29.00 2.50 0.72 OK 16 1 16 29.0
1 core Unarmoured
Primary pump Ta=35C, 3 X-98, 3 core
22.00 39.69 63 D 0.96 0.77 1 85.23 100 91.4 145 OK 37.50 2.50 0.93 OK 16 1 16 37.5
2 core Unarmoured
Primary pump Ta=35C, 3 X-98, 3 core
22.00 39.69 63 D 0.96 0.77 1 85.23 100 91.4 145 OK 46.00 2.50 1.14 OK 16 1 16 46.0
3 core Unarmoured
Primary pump Ta=35C, 3 X-98, 3 core
22.00 39.69 63 D 0.96 0.77 1 85.23 100 91.4 145 OK 54.50 2.50 1.35 OK 16 1 16 54.5
4 core Unarmoured
Cable Selected
In/(Ca*Cg*Ci)
Rated/ Input
Voltage drop
Voltage drop
Adjustment
Earth cable
Earth cable
I2=In*1.45
Intallation
Length
Power
length
Equipment
1.45Iz
Cable type
I2 <1.45Iz
4%*400V
In
Ib
Iz
kW A A condition method Ca Cg Ci A A A A m mV/A/m % mm2 Nos mm2 m
Cooling tower
Cable Selected
In/(Ca*Cg*Ci)
Rated/ Input
Voltage drop
Voltage drop
Adjustment
Earth cable
Earth cable
I2=In*1.45
Intallation
Length
Power
length
Equipment
1.45Iz
Cable type
I2 <1.45Iz
4%*400V
In
Ib
Iz
kW A A condition method Ca Cg Ci A A A A m mV/A/m % mm2 Nos mm2 m
Cooling tower
Ta=35C, 3 3 core
makeup pump 1.14 2.06 6 B 0.96 0.7 1 8.93 23 8.7 33.35 OK 30 27.00 0.42 OK 1.5 1 1.5 1.5
core Unarmoured
01
Cooling tower
Ta=35C, 3 3 core
makeup pump 1.14 2.06 6 B 0.96 0.7 1 8.93 23 8.7 33.35 OK 30 27.00 0.42 OK 1.5 1 1.5 1.5
core Unarmoured
02
Notes:
Equipment
kW
Rated/ Input
Power
A
Ib
A
condition In
Intallation
method
Ca
Cg
Adjustment
Ci
factors
A
In/(Ca*Cg*Ci)
1. The cable that comes upto the isolator will be continued upto the cooling tower power panel
A
Iz
A
I2=In*1.45
A
1.45Iz
I2 <1.45Iz
m
Length
mV/A/m
Voltage drop
%
Voltage drop
Cable Selected
Cable type
mm2
Earth cable
m
Earth cable
length