Fire behaviour of hollow structural section steel columns filled with high
strength concrete
Peter Schaumann a , Venkatesh Kodur b , Oliver Bahr a,
a
Leibniz Universitaet Hannover, Institute for Steel Construction, Appelstr. 9a, 30167 Hannover, Germany
b
Michigan State University, Department of Civil and Environmental Engineering, East Lansing, MI 48824, USA
a b
Notations
EU European material properties
NA North American material properties
NSC Normal strength concrete
HSC High strength concrete
HSS Hollow structural section
Fig. 2. Comparison between EU and NA stressstrain relationship for siliceous HSC Fig. 4. Comparison between NA and EU material properties for thermal
with compressive strength of 60 MPa at elevated temperatures. conductivity.
Fig. 3 shows the variation of specific heat capacity as a The computed values for the variation of the thermal elongation
function of temperature, as obtained from North American = 1l/l are summarized in Fig. 5, where the influence of the
recommendation and European code provisions. According to type of aggregate becomes clear. Because of the transformation of
Eurocode 2 thermal properties of normal weight concrete may also quartz in the siliceous aggregates, thermal elongation increases for
be applied for HSC. Contrary to Eurocode 2, the North American temperatures about 450 C. For temperatures exceeding 650 C
recommendations differ between concrete with calcareous and thermal expansion remains constant. Thermal elongation for
siliceous aggregates. According to the latter code, the initially concrete with calcareous aggregates is considerably lower for
assumed specific heat capacity for siliceous aggregates is below temperatures less than 800 C.
the corresponding European values. However, the North American
formula results in a peak value at 500 C for concrete with siliceous 3.5. Mass loss
aggregates. This is due to the presence of quartz that transforms
at these temperatures [4]. For concrete with calcareous aggregates The results for the mass loss are presented in Fig. 6. According
two peaks occur. The small peak near 400 C is caused by the to the North American material properties, the overall mass loss
removal of crystal water from the cement paste. The higher peak for concrete with siliceous aggregates only amounts to about
at temperatures of about 700 C results from the dissociation 5%. Nevertheless, for temperatures exceeding 700 C the mass of
of dolomite. At temperatures exceeding 800 C, the different concrete with siliceous aggregates is sharply reduced to 70% of its
formulas converge to similar values. initial mass. The loss is caused by the dissociation of dolomite in
In general, the differences can be explained by the fact that concrete. In contrast to this, Eurocode 2 does not differ between
the North American provisions take physio-chemical processes concrete with siliceous and calcareous aggregates with respect to
into account. In contrast to this, the European approaches neglect mass loss.
such phenomena. However, Eurocode 2 allows considering the
beneficial effect of increased moisture content on the specific heat 4. Verification of HSC material properties
capacity in the temperature range from 115 C to 200 C, which is
not presented here. According to Eurocode 4 a moisture content of A review of the literature indicates that there is very limited
10% may occur for HSS filled with concrete. fire test data on HSC-filled HSS columns exposed to fire [12,13].
The main objective of the reported tests was to determine the
3.3. Thermal conductivity fire resistance of HSS steel columns filled with different types
of HSC. The tests, which have been reported on HSS columns,
The different approaches for thermal conductivity can be seen include plain HSC-filling (columns C-46 and C-47), HSC with steel
in Fig. 4. Eurocode 2 defines thermal conductivity by lower and fibres (columns C-36 and SQ-11) and HSC with 4 15 mm
upper limit. Highest values of the thermal conductivity result from reinforcement bars (column SQ-14). Investigated cross-section
the North American provisions, whereas the minimum is given by types are presented in Fig. 7. Full details of the fire tests are
the lower limit of Eurocode 2. documented in [12,13].
P. Schaumann et al. / Journal of Constructional Steel Research 65 (2009) 17941802 1797
Fig. 6. NA and EU material properties for mass loss. Fig. 8. Comparison between tested and calculated fire resistance.
The tested HSS columns were 3.81 m long with fixed end
conditions and filled with calcareous aggregate (limestone) HSC.
After the load was applied, the columns were exposed to
heating according to standard fire ULC-S101-M04 [14] until failure
occurred. This fire exposure is equivalent to ASTM E-119 or ISO-
834 standard fire. The fire resistance period of some of the tested
columns (selected from literature) is calculated with the computer
program BoFIRE. This allows verification of material properties
given by the North American and European codes. Moreover, it
facilitates to study the influence of different types of concrete
filling on fire resistance. The material properties of steel fibre
reinforced HSC-filling are taken according to the published data by
Kodur and Sultan [4], which is reproduced in the Appendix. The
test data of the different HSS columns, taken from references [12,
13,15,18], is summarized in Table 1, where C in the column
designation denotes circular cross-section and SQ denotes square Fig. 9. Elevation of the separating concrete crack of an HSS column filled with plain
cross-section. concrete [16].
The test and calculated fire resistance period of the different
HSS columns is summarized in Fig. 8. A moisture content of 10% 15 to 20 min the load has to be transferred from the steel section
was considered in the computer program BoFIRE, which may occur to the concrete core. This is because the steel section yields due
for HSS filled with concrete according to Eurocode 4, part 12. to attaining critical temperature, which is linked with significant
Regarding the numerical results for HSS columns filled with plain reduction of its strength.
HSC it is obvious that the fire resistance is overestimated to a great In case of load eccentricities, which can hardly be avoided,
extent. This is true for both the North American and European HSC the gap between the concrete cross-sections cannot be closed;
material properties. With respect to the circular HSS columns C- this leads to local failure of the column [16]. An example of local
46 and C-47 the gap between tested and calculated fire resistance buckling of a concrete-filled HSS column is shown in Fig. 10. The
increases for higher concrete compressive strength. However, concrete prevents the steel tube from inward buckling. However,
the results of both numerical models are conservative for HSC- after exposure to fire, outer buckling could be noticed which means
filling with additional steel fibres (columns C-36 and SQ-11) and that the tube and concrete were locally separated. As the program
reinforcing bars (column SQ-14). BoFIRE does not take such local effects into account, it might
The divergence between computed and test fire resistance be worthwhile to establish a three-dimensional model for this
period for plain HSC-filling can be explained from the test problem. This is outside the scope of this paper. Nevertheless,
experience gained in [16]. The steel HSS column expands faster by comparison to test data it is examined if the distribution of
than the concrete core under fire load, initiating cracks in the temperatures derived from this computer program is adequate.
concrete. This effect can be considerable due to lack of any For this purpose, the points at which temperatures are
reinforcement. evaluated in BoFIRE (MP1 and MP2) are arranged according to
In the worst case scenario, the cracks magnify and might the location of thermocouples in test columns. As an example, in
separate the concrete cross-section into two halves as shown in the column C-46 with plain HSC-filling, the measured and calculated
elevation in Fig. 9. In the initial stage of fire exposure, the load is temperatures according to the HSC material properties defined
mainly carried by the steel section. However, after approximately in Eurocode 2, part 12 [6] are presented in Fig. 11. A moisture
1798 P. Schaumann et al. / Journal of Constructional Steel Research 65 (2009) 17941802
Table 1
Summary of fire resistance test data on HSC-filled HSS columns [12,13,15].
Tube filling Column Cross-section Test load (kN) Concrete strength (MPa) Fire resistance (min)
Fig. 12. Recorded and calculated temperatures for column C-46 with varying
moisture content (u) (calculated with EU material properties).
Fig. 13. Recorded and calculated temperatures for column SQ-14 according to EU
material properties.
Fig. 11. Recorded and calculated temperatures for column C-46 according to EU
material properties.
Fig. 15. Axial deformations recorded in test for specimens C-46, SQ-11 and SQ-14. Fig. 16. Effect of varying A/V -ratio on fire resistance period of circular HSS columns
with HSC-filling.
Table 2 eccentricity. Thus, a numerical study was carried out to set a rea-
Results from parametric studies on the effect of cross-sectional shape. sonable limitation on eccentricity for the use of HSC as HSS-filling.
Cross-section A/V -ratio (1/m) Load for C90/105 (kN) The parametric study was performed with a circular cross-section
Circular Square Circular Square C219.1 6 mm and hinged end conditions. A HSS column was filled
CS1 C610 16 SQ610 12.5 7 15,316 20,628 with calcareous aggregate concrete with compressive strength of
CS2 C273 8 SQ273 6.2 15 3,117 4,214 40, 60, 80 or 100 MPa based on cylinder strength. This corresponds
CS3 C139.7 4 SQ139.7 3.1 29 813 1,103 to compressive strength of 50, 75, 95 and 115 MPa based on cube
strength.
With regard to the tube, conventional yield strength of 235 MPa
and improved yield strength of 355 MPa were chosen for the first
two cross-sections. The third cross-section consisted of a tube with
yield strength of 235 MPa and 4 25 mm reinforcement bars.
The influence of slenderness was examined by varying the column
length from 0.1 to 6 m with an assumed imperfection of L/1000.
Both the North American and European material properties for
HSC were used. The cross-sections were heated 30 min according
to the ISO time-temperature curve. This standard curve according
to the European code Eurocode 1, part 12 [17] is very similar
to the North American standard time-temperature curve, which
is defined by the code ULC-S101 [14]. The short heating period
of 30 min already showed the unfavorable fire endurance of
Fig. 18. Comparison between circular and square cross-sections with same A/V - slender HSC-filled HSS columns. For longer fire exposure times,
ratio. the reduction in ultimate load would be even more rapid. After
the heating process, the load was gradually increased until failure
were taken as the basis of comparison. Since it was shown that occured.
the A/V -ratio has crucial influence on the fire endurance, the
square HSS columns selected for the comparison had the same 7.1. Calculation with tube yield strength of 235 MPa
A/V -ratio as the circular HSS columns. In addition, the wall
thickness of the square HSS columns was calculated such that
Results from the analysis are plotted in Fig. 20, which presents
the resulting steel area for the square section was the same as
the ultimate load-bearing capacity (at 30 min) as function of
for circular cross-section. This was necessary to account for the
column length. The HSC-filled HSS column with tube yield strength
decreasing material properties of steel at elevated temperatures.
of 235 MPa was concentrically loaded. Using the NA and EU
The examined columns can be found in Table 2. The HSS columns,
material properties, the ultimate load after fire exposure of 30 min
which had a load level of 50% at room temperature, were filled with
to ISO standard fire was determined.
calcareous aggregate C90/105 concrete. The first value denotes the
As expected, load carrying capacity decreased with increased
compressive strength of the concrete in MPa based on cylinder
column length. The North American code provisions were more
strength, whereas the second value is based on cube strength.
conservative for both NSC and HSC under concentric load, which
Second-order effects were excluded with a chosen column length
is also illustrated in Fig. 20. This is in particular true for the HSC
of only 0.50 m (short columns) with fixed end conditions.
class C100/115 as the European results for non-slender columns
The fire endurance for the different steel HSS columns with
exceeded the North American predictions about 25%.
HSC-filling is presented in Fig. 18. It is apparent that the circular
For column lengths exceeding 2 m similar ultimate loads were
cross-sections showed slightly better fire resistance period than
obtained using both approaches. This can be attributed to the
the square cross-sections with same A/V -ratio. Whereas the differ-
fact that these columns fail by global buckling, which is largely
ence in fire resistance between the massive circular C610 16 mm
influenced by the elastic modulus. The latter is very similar for both
and square SQ610 12.5 mm cross-sections is only 6% (CS1), it
approaches. Thus, no great differences with respect to buckling
amounts to about 11% for two other examples (CS2 and CS3).
could be expected.
The lower fire resistance in square columns can be explained
The results for moderate eccentric loads with e/h = 0.25
by the fact that square cross-section corners were heated from
two sides, which led to an increased supply of heat, higher loss are given in Fig. 21. The tube yield strength was 235 MPa.
of strength and thus earlier failure. This is illustrated in Fig. 19. In The North American code provisions still calculated the more
the case of square columns, the temperature at a given distance conservative results. Nevertheless, the difference between the
from the edge was higher at the corner than that along the approaches was insignificant for column lengths exceeding 2 m.
sides caused by the heat transfer from two sides. In contrast to Due to its low tensile strength, the beneficial effect of concrete
this, the circular cross-section showed a uniform temperature with high compressive strength was sharply reduced for slender
distribution along the radial lines. However, the investigation columns and load eccentricities causing bending moments. Thus,
illustrates that the difference between the two cross-sections the use of HSC as filling for HSS columns should be limited to non-
concerning fire resistance period is moderate. Therefore, mostly slender columns with only moderate load eccentricity.
circular cross-sections are considered in the later on carried out
studies. Considering that square cross-sections show lower fire 7.2. Calculation with tube yield strength of 355 MPa
endurance about 10%, the numerical results for the circular HSS
columns in general allow fire resistance assessment of square The average steel temperature of the tube was 860 C for a
cross-sections with comparable A/V -ratio. fire exposure of 30 min. Due to its reduced strength and elastic
modulus, the load share of the steel tube was negligible. Thus, the
7. Effect of slenderness HSS column with the improved tube yield strength of 355 MPa
carried only slightly higher loads than the cross-section with a steel
Columns are mainly compression members and hence suscep- tube having yield strength of only 235 MPa. Therefore the results
tible to bending with respect to column slenderness and load are not presented in detail.
P. Schaumann et al. / Journal of Constructional Steel Research 65 (2009) 17941802 1801
5 0 5
5 5
0 0
5 5
7
5 0 5 7 2 3
Fig. 19. Temperature field for square SQ139.7 3.1 mm and circular C139.7 4 mm cross-section (CS3) after fire exposure of 32 min.
Fig. 20. Ultimate load for concentrically loaded HSC-filled HSS column using NA Fig. 22. Comparison of ultimate loads between HSS column with tube yield
and EU HSC material properties at 30 min fire exposure. strength of 235 MPa and additional reinforcement bars and tube of improved yield
strength of 355 MPa both under eccentric load of e/h = 0.25 using European
material properties at 30 min fire exposure.
7.3. Calculation with tube yield strength of 235 MPa and reinforce- Based on the information presented, the following conclusions
ment bars concerning the fire resistance of high strength concrete-filled HSS
steel columns can be drawn.
The addition of reinforcement bars in concrete filling is helpful
in improving fire resistance. This can be seen in Fig. 22, where the - The computer code BoFIRE is capable of modelling the fire
HSS column with the tube of improved yield strength of 355 MPa is response of HSC-filled HSS columns with different types of
compared to the conventional tube with yield strength of 235 MPa reinforcement (steel fibres and bar reinforcement).
and 4 25 mm reinforcement bars. - Local effects like gaping cracks and local plastic buckling, which
With a concrete cover of 50 mm, the reinforcement bars were might occur in concrete-filled HSS columns without reinforce-
to some degree protected against heating. The outcome was an ment, are not covered by most conventional simulation tools.
average temperature of 500 C in reinforcement bars remarkably This might lead to exaggerated results.
reducing the elastic modulus to about 60% of its initial value - High strength concrete-filling is particularly beneficial for
according to Eurocode 4. Nevertheless, in comparison to the massive columns with low A/V -ratio as the material properties
directly fire-exposed steel tube with an average temperature of of high strength concrete at elevated temperatures do not play
about 860 C and corresponding reduction to only 8% of the initial crucial role as in the case of leaner columns.
1802 P. Schaumann et al. / Journal of Constructional Steel Research 65 (2009) 17941802
- Circular concrete-filled HSS steel columns provide higher fire c cp ( ) = 3.81 106 for 0 C 400 C
resistance than square concrete-filled HSS columns of similar c cp ( ) = (0.0165 + 10.41) 106 for 400 C < 475 C
cross-section area. c cp ( ) = (0.0079 1.182) 106 for 475 C < 625 C
- The use of HSC as filling in HSS columns is beneficial from c cp ( ) = (0.2333 142.06) 106 for 625 C < 700 C
fire resistance point of view for non-slender columns with c cp ( ) = (0.1800 + 147.25) 106 for 700 C < 800 C
only moderate load eccentricity. This recommendation is the c cp ( ) = 3.25 106 for 800 C < 1000 C .
result of an investigation on fire exposure of up to 30 min.
Since the disadvantageous load-bearing behaviour of HSC- A.3. Thermal conductivity
filling increases with rising temperatures, this trend is also valid
for higher fire resistance classes. c = 1.80 0.0016 c for 0 C 500 C
- The fire resistance of HSC-filled HSS columns can be signifi- c = 1.20 0.0004 c for 500 C < 1000 C .
cantly enhanced by using reinforcement in the concrete core.
This is true for both steel fibre and conventional bar reinforce- A.4. Thermal elongation
ment.
- There are variations between the considered European and
c ( ) = 2.00 104 + 9 106 for 0 C 700 C
North American material properties resulting in different
c ( ) = 3.45 102 + 58 106 for 700 C < 870 C
fire resistance times. Numerical studies showed that North
c ( ) = 1.60 102 for 870 C < 1000 C .
American results are more conservative for increasing concrete
strengths and decreasing cross-sectional parameter.
- In general, the results for HSS columns filled with normal A.5. Variation of density
strength concrete are in fair agreement using the European
and North American material properties. In contrast to this, ( )/(20 C ) = 1.003 6 105 for 0 C 700 C
significant differences could be noticed concerning the results ( )/(20 C ) = 2.214 1.79 103 for 700 C < 785 C
for HSC-filling. One of the primary factors that produce these ( )/(20 C ) = 0.817 1.00 105 for 785 C < 1000 C .
differences is the variation in high temperature material
properties of HSC. Hence the authors recommend further
References
research on the high temperature material properties of HSC.
[1] Kodur VKR, Lie TT. Fire performance of concrete-filled hollow steel columns.
Journal of Fire Protection Engineering 1995;7(3):8998.
Appendix [2] Canadian Standards Association. CSA A23.3-M04. Code for the design of
concrete structures for buildings. Rexdale, Ontario, Canada; 1994.
[3] Canadian Standards Association. CSA S16.1. Limit states design of steel
The following formulae describe the material behaviour of HSC structures. Rexdale (Ontario, Canada); 2001.
with steel fibres at elevated temperatures according to Kodur and [4] Kodur VKR, Sultan MA. Effect of temperature on thermal properties of high-
Sultan [4] and are referred to as North American material models, strength concrete. Journal of Materials in Civil Engineering 2003;15(2):1017.
[5] Cheng FP, Kodur VKR, Wang TC. Stressstrain curves for high strength concrete
for HSC, in the main text. These material properties are defined for
at elevated temperatures. Journal of Materials in Civil Engineering 2004;16(1):
concrete strengths between 55 and 110 MPa. 8494.
[6] European Committee for Standardization. EN 1992-1-2 (Eurocode 2). Design
of concrete structures, Part 1-2: General rulesStructural fire design. Brussels;
A.1. Stressstrain relationship 2004.
" [7] European Committee for Standardization. EN 1994-1-2 (Eurocode 4). Design
H # of composite steel and concrete structures, Part 1-2: General rulesStructural
max c
fc = fc0 1 for: c c ,max fire design. Brussels; 2005.
max [8] Schaumann P. Computation of steel members and frames exposed to fire (in
German: Zur Berechnung staehlerner Bauteile und Rahmentragwerke unter
!2 Brandbeanspruchung). Bochum: Technisch-wissenschaftliche Mitteilungen
30 (max c ) Nr. 84-4. Institut fr konstruktiven Ingenieurbau, Ruhr-Universitt; 1984.
fc = fc0 1 for: c > c ,max [9] Upmeyer J. Fire design of partially encased composite columns by ultimate
max
0
130 fc0 fire loads (in German: Nachweis der Brandsicherheit von kammerbetonierten
Verbundbauteilen ueber Grenzbrandlasten). Hannover: Institute for Steel
where: Construction, Leibniz Universitaet Hannover, Shaker Verlag; 2001.
[10] Schaumann P, Bahr O, Kodur VKR. Numerical studies on HSC-filled steel
H = 2.28 0.012 fc0
0 columns exposed to fire. In: Tubular structures XI. London: Taylor and Francis
Group; 2006.
max = 0.0018 + 6.7 fc00 + 6 + 0.03 2 106
[11] Schaumann P, Bahr O, Kodur VKR. Fire resistance of high strength concrete-
filled steel columns. SIF06 - 4th International Workshop Structures in Fire;
and: 2006.
[12] Kodur VKR. Performance of high strength concrete-filled steel columns
fc0 = fc0
0
(1.0625 0.003125 ( 20)) for: < 100 C exposed to fire. Canadian Journal of Civil Engineering 1998;25:97581.
[13] Kodur VKR. Solutions for enhancing the fire endurance of steel HSS columns
fc0 = 0.75 fc0
0
for: 100 < 400 C filled with high strength concrete. AISC Steel Construction Journal 2006;43(1):
fc0 = fc0
0
(1.33 0.00145 ) for: 400 C 17.
[14] Canadian Standards Association. CAN/ULC S101-4. Standard methods of fire
such that: endurance tests of building construction and materials. Rexdale (Ontario,
Canada); 2004.
0 fc0 fc0
0
[15] Lie TT, Kodur VKR. Fire resistance of steel columns filled with bar-reinforced
concrete. Journal of Structural Engineering 1996;122(1):306.
Unit: MPa. [16] Kordina K, Klingsch W. Fire resistance of composite columns and of solid
steel columns - part I (in German: Brandverhalten von Stahlstuetzen im
Verbund mit Beton und von massiven Stahlstuetzen ohne Beton). Duesseldorf:
A.2. Specific heat capacity Studiengesellschaft fr Anwendungstechnik von Eisen und Stahl e.V.; 1983.
[17] European Committee for Standardization. EN 1991-1-2 (Eurocode 1). Actions
on structures, Part 1-2: General actionsActions on structures exposed to fire.
The specific heat is the product of specific heat capacity and
Brussels; 2002.
density. A value of 2535 kg/m3 is assumed for the density of HSC [18] Kodur VKR, Wang TC, Cheng FP. Predicting the fire resistance behavior of high
with calcareous aggregates. strength concrete columns. Cement and Concrete Composites Journal 2004;
26(2):14155.