Anda di halaman 1dari 698

HOME PRINT

HOME PRINT

SCHWING SERVICE DEPARTMENT


(651) 429-0999
jlkjlkjlkjlkjlkjkj

OR

1-888-292-0262
OR

FAX (651) 429-2112


8:00 A.M. TO 5:00 P.M. (Central Time)
(MONDAY THROUGH FRIDAY)

SCHWING PARTS DEPARTMENT


1-800-328-9635
OR

FAX (651) 429-2112


6:00 A.M. - 9:00 P.M. (Central Time)
(MONDAY THROUGH FRIDAY)

24 Hour Service Hotline


1-888-292-0262
(MONDAY THROUGH SATURDAY)

Branches
Florida............................................................. 1-813-985-8311
Northern California........................................ 1-925-371-8595
Southern California ....................................... 1-562-493-1012
Georgia ........................................................... 1-678-560-9801
Texas .............................................................. 1-972-245-5166
HOME PRINT
SERVICE TRAINING
Table of Contents

Table of Contents Hydraulic Pump Spline Lubrication .........................................23


Product Data .........................................................................23
Features .................................................................................23
Uses ......................................................................................23
Table of Contents Maintenance of Hydraulic Cylinders ........................................24
To check the piston side holding valves .......................24
To check the rod side holding valve .............................24
Maintenance Check Outrigger Cylinder for: ......................................25
Check the control block for: .........................................25
Maintenance Chart ...................................................................... 1
Lubrication Specs for Schwing Placing Booms .......................26
Operators Check list for Weekly Maintenance (Ex.) ............... 3
Boom Inspections ........................................................................27
Size Comparison of Particles ...................................................... 4
Filtration Ratings ......................................................................... 5
Nominal Rating ...................................................................... 5 Pumpkits
Absolute Rating ..................................................................... 5
Specifications ...............................................................................29
Filtration Ratio(bn) ................................................................ 5
2023-4 ...................................................................................29
Filter Facts ............................................................................. 5
2023-5 ...................................................................................29
Fluid Contamination and Control .............................................. 6 2023H-6 ................................................................................29
Primary sources of contamination ......................................... 6 2525H-5 ................................................................................29
Control Methods .................................................................... 6 2525H-6 ................................................................................29
Handling, Storing & Dispensing Lubricating fluids ................. 7 Change rams ...............................................................................30
Hydraulic Oils .............................................................................. 8 Remove the old rams. ...................................................31
General information ............................................................... 8 Material Cylinder Alignment ....................................................34
Specific information .............................................................. 8 Changing the Material Cylinders ..........................................34
Hydraulic Oils ........................................................................ 9
Pumping on piston side ..............................................................40
When to change your hydraulic oil ........................................ 9
Sealing Gland Replacement .......................................................41
Hydraulic Oil Viscosity Chart .................................................. 10
Shimming the Differential Cylinders ........................................42
Lubrication Prefix Codes .......................................................... 11
Determining the proper shim size .........................................42
Standard codes used ............................................................. 11
Dimension A .........................................................................42
Hydraulic oil codes .............................................................. 11
Dimension B .........................................................................42
Industrial gear lubricant codes ......................................... 11
Formula .................................................................................43
Lubrication Recomendations .................................................... 12
Motor Vehicle Gearbox Oil ................................................. 12
Compressor Oil .................................................................... 13 Hydraulic Pumps
Filling Capacities ........................................................................ 14 Hydraulic Pump Drive ...............................................................45
Hydraulic Reservoirs ........................................................... 14
Placing boom hydraulic pumps .................................................45
Transmissions ...................................................................... 15
Gear Boxes ........................................................................... 16 Concrete pump hydraulic pumps ..............................................45
Spicer Transmisions .................................................................. 17 Hydraulic Pump Locations ........................................................46
Lubrication Specs ................................................................ 17 Fixed Displacement Pump A2FO ..............................................47
Recommended Lubricants ................................................... 17 Rexroth/Hydromatik Model A7V Series 2 ...............................48
Oil Changes .......................................................................... 17 Constant Pressure Control DR ..............................................49
Over-Filling ......................................................................... 17 Constant Horsepower Control LV ........................................49
ZF Transmissions ....................................................................... 18 Commencement of control: 50 bar min. ...............................49
Lubrication Specs ................................................................ 18 Auxiliary Equipment: Stroke Limiter ...................................50
Steyr Gear Boxes ........................................................................ 19 Rexroth/Hydromatik Model A7V Series 6 ...............................51
Lubrication Specs ................................................................ 19 LR Constant Power Control .................................................52
Transfer Case Gear Oil Capacities are as Follows: ............. 19 LRH Constant Power Control With Hydraulic
Stiebel Gear Boxes ..................................................................... 20 Stroke Limiter .......................................................................52
Lubrication Specs ................................................................ 20 Variation: Hydraulic Stroke Limiter (H...) ...........................53
H1/H5 (Negative Control Function): Vg max to Vg min .....53
FABCO Gear Boxes ................................................................... 21
DR Constant Pressure Control ..............................................53
Lubrication Specs ................................................................ 21
Rexroth/Hydromatik Model A10VO ........................................55
ZF Torque Converters ............................................................... 22
Lubrication Specs ................................................................ 22 Rexroth/Hydromatik Model A11VO ........................................57
WSK Torque Converters ..................................................... 22 Linde Hydraulik BPR 105 .........................................................60
Constant Power Regulator (LR) ...........................................61

Service Manual
HOME PRINT
SERVICE TRAINING
Table of Contents
Power Regulator With Hydraulic Stroke Limiter (LRH) .... 61 Set the agitator pressure ......................................................123
Voac Variable Displacement Axial Piston Pump .................... 62 S 31 XT ......................................................................................125
Check all hydraulic pressures .............................................125
Preheat the hydraulic oil .....................................................125
Pressure Settings Check the concrete pump pressure -4 pumpkits .................126
General ........................................................................................ 63 To check or set the concrete pump pressure
Stroke Limiter Adjustment .................................................. 63 adjustments, follow these steps: .................................126
Check the accumulator Pre-Charge ..................................... 64 Setting the main relief valve ...............................................126
Setting the soft switch circuit relief pressure ......................128
To check or adjust the soft switch pressure setting,
Hydraulic Pump Adjustments proceed as follows: .....................................................128
Setting pressures on load-sensing booms ...........................128
Main System Pumps A11VO .................................................... 69
Preheat the oil .....................................................................128
Setting the Flow Rate ........................................................... 69
About proportional boom systems ......................................128
Horsepower Setting .............................................................. 70
Setting DP ...........................................................................129
Setting Stroke Limitation ..................................................... 70
Setting Q-min .....................................................................131
Q-min Output Flow .............................................................. 70
Setting boom pressures .......................................................131
Check all hydraulic pressures. ............................................. 71
There are several devices on the boom circuit which
Setting pressures on Hi-flo -6 pumpkits .............................. 71
control boom pressure (Figure 45): ............................131
Pressure setting procedure: .................................................. 72
Raise the pressure of the lowest circuit ..............................132
Setting the soft switch relief pressure .................................. 73
Setting the outrigger pressures ...........................................132
BPL 500 ....................................................................................... 75 To set the 280 bar relief valve for the outrigger
BPL 2000 ..................................................................................... 81 circuit: .........................................................................132
BPL 4000 ..................................................................................... 85 Setting 15 bar pretension ....................................................134
KVM 17M ................................................................................... 97 To check or set pretension, follow these steps: ..................134
Setting concrete pump pressure ........................................... 98 Setting the agitator circuit pressure ....................................135
Setting the soft switch circuit relief pressure ..................... 100 Setting accumulator circuit pressure ...................................136
Setting accumulator E-Stop manifold pressure 32XL Single Circuit ..................................................................139
(original production) .......................................................... 100 Check hydraulic pressures ..................................................139
Setting the accumulator unloading valve Preheat the hydraulic oil .....................................................139
(original production) .......................................................... 101 Check the concrete pump pressure (900 or 1200) ..............139
Setting accumulator E-Stop manifold pressure Setting boom pressures .......................................................140
(current production) ........................................................... 101 Preheat the oil .............................................................140
Setting the accumulator unloading valve About proportional boom systems ..............................141
(current production) ........................................................... 102 Setting DP ...........................................................................141
Setting the boom E-Stop manifold pressure ...................... 102 Setting Q-min .....................................................................142
Setting the boom/outrigger pressure .................................. 103 Setting boom pressures .......................................................143
Setting the outrigger pressure ............................................ 103 Setting the 140 bar down side relief valve pressure ...........144
Setting the boom pressures ................................................ 104 Setting the outrigger
Set boom section #1 down pressure ................................... 105 pressures (7 place boom valve systems) .............................146
Setting water pump pressure .............................................. 106 Setting 15 bar pretension ....................................................148
Setting the agitator pressure ............................................... 107 To set the agitator circuit pressure: .....................................148
KVM 28X .................................................................................. 109 32 XL Twin Circuit ...................................................................151
Check all hydraulic pressures ............................................ 109 Units up to 450 l/m .....................................................151
Set the concrete pump main relief valve ............................ 111 Check hydraulic pressures ..................................................151
Set the concrete pump main relief valve ............................ 112 Preheat the hydraulic oil .............................................151
Set the soft switch circuit relief pressure ....113 Check the concrete pump pressure
Set accumulator circuit hydraulic oil pressure ................... 113 (900-1200 - MPS pumpkits) ...............................................151
Setting the outrigger pressure ............................................ 115 Setting the soft switch circuit relief pressure ......................153
Pressure reducing valve ..................................................... 116 Setting the boom pressures .................................................153
Electric stroke limiter ......................................................... 116 Load-sensing boom pressures .............................................155
Load-sensing boom pressures ............................................ 116 Preheat the oil .............................................................155
Check or set P .................................................................. 118 About proportional boom systems ..............................155
Check or set Q-min ............................................................ 119 Setting DP ...........................................................................156
Set boom pressures ............................................................ 119 Setting Q-min .....................................................................158
Set the down side relief valve pressure .............................. 121 Setting boom pressures ...............................................158
Set 15 bar pretension .......................................................... 122 Setting the 140 bar down side relief valve pressure ...........160
Set water pump pressure .................................................... 122

Service Manual
HOME PRINT
SERVICE TRAINING
Table of Contents
Setting the outrigger Check the concrete pump pressure
pressures (7 place boom valve system) .............................. 160 (2020, 2023, 2525 pumpkits) ..............................................205
Setting the water pump hyd. pressure ................................ 162 Setting the main relief valve on -4 pumpkit .......................206
To set the agitator circuit pressure: .................................... 162 Setting the soft switch circuit relief pressure ......................208
32 XL Hi-Flow B&W ............................................................... 165 Setting boom pressures .......................................................209
Units up to 450 l/m ............................................................ 165 140 bar down side relief .....................................................209
Check hydraulic pressures ................................................. 165 Setting the outrigger pressures ...........................................209
Preheat the hydraulic oil ............................................ 165 Setting the water pump hydraulic pressure .........................210
Location of pressure setting/checking devices .......... 166 Setting 15 bar pretension ....................................................210
Check the concrete pump pressure Setting the agitator circuit pressure ....................................211
(2020, 2023, 2525 pumpkits) ............................................. 167 Setting accumulator circuit pressure ...................................213
Setting the main relief valve .............................................. 168 S 34 X .........................................................................................217
Setting the soft switch circuit relief pressure ..................... 169 Check hydraulic pressures ..................................................217
Setting the boom pressures ................................................ 169 Preheat the hydraulic oil .............................................217
Setting the 140 bar down side relief valve pressure .......... 172 Check the concrete pump pressure
Setting the outrigger pressures (2020, 2023, 2525 pumpkits) ......................................217
(7 place boom valve systems) ............................................ 173 Setting the main relief valve .......................................218
To set the agitator circuit pressure: .................................... 175 Setting the soft switch circuit relief pressure ..............220
32 XL High Flow Proportional ............................................... 177 Load-sensing boom pressures .....................................221
Units up to 450 l/m ............................................................ 177 Preheat the oil .............................................................221
Check hydraulic pressures ................................................. 177 About proportional boom systems ..............................221
Check the concrete pump pressure Setting DP ...................................................................221
(2020, 2023, 2525 pumpkits) ............................................. 177 Setting Q-min .............................................................223
Setting the main relief valve .............................................. 178 Setting boom pressures
Setting the soft switch circuit relief pressure ..................... 180 (Load sensing proportional booms.) ...........................223
Load-sensing boom pressures ............................................ 180 Setting the 140 bar down side relief valve pressure ...224
Preheat the oil ............................................................ 181 Setting the outrigger pressures ...................................225
About proportional boom systems ............................. 181 Setting the water pump hydraulic pressure .................226
Setting DP .......................................................................... 181 Setting 15 bar pretension ............................................226
Setting Q-min ..................................................................... 183 Setting the agitator circuit pressure ............................227
Setting boom pressures ...................................................... 183 Setting accumulator circuit pressure ...........................228
Setting the 140 bar down side relief valve pressure .......... 185 KVM 36X-42M (pre-1998) .......................................................231
Setting the outrigger pressures ........................................... 185 Pressure Settings for KVM 36X
Setting the water pump hyd. pressure ................................ 187 Proportional Load Sensing .................................................231
Setting 15 bar pretension ................................................... 187 Component Location Guide KVM 36 X
To set the agitator circuit pressure: .................................... 188 W/Rexroth Handvalves .......................................................232
32 XL Hi-Flow Prop, A11VO .................................................. 191 Pressure Settings for KVM 36X Proportional
Units above 450 l/m (-5 and -6 units) ................................ 191 Load Sensing ......................................................................233
Check hydraulic pressures ................................................. 191 Pressure Regulator Cutaway ...............................................234
Preheat the hydraulic oil .................................................... 191 Pressure Settings for Regulator and Releif Valves .............235
Check the concrete pump pressure KVM 36 LW & 36 X W/Rexroth Boom Handvalve ..........236
(2020, 2023, 2525 pumpkits) ............................................. 191 Pressure Settings for KVM 42
Setting the main relief valve .............................................. 193 (B&W Load sensing and Proportional Load Sensing ........237
Setting the soft switch circuit relief pressure ..................... 194 Component Location Guide KVM 42
Setting boom pressures ...................................................... 194 W/Rexroth Handvalves .......................................................238
Preheat the oil ............................................................ 195 Pressure Settings for KVM 42LW Proportional
About proportional boom systems ............................. 195 Load Sensing ......................................................................239
Setting DP .......................................................................... 195 Pressure Regulator Cutaway ...............................................240
Setting Q-min ..................................................................... 197 Pressure Settings for Regulator and Relief Valves
Setting boom pressures ...................................................... 197 KVM 42 ..............................................................................241
Setting the 140 bar down side relief valve pressure .......... 199 KVM 42 LW, W/Rexroth BoomHandvalve .......................242
Setting the outrigger KVM 36X ...................................................................................243
pressures (7 place boom valve systems) 200 Set the concrete pump main relief valve (single- circuit) ...244
Setting 15 bar pretension ........................................... 202 Setting the soft switch circuit relief pressure ......................247
To set the agitator circuit pressure: .................................... 202 Set accumulator circuit .......................................................248
KVM 32 XG .............................................................................. 205 Units with a pressure- compensated pump .................248
Check hydraulic pressures ...................................................... 205 Setting the outrigger pressure .............................................249
Preheat the hydraulic oil .................................................... 205 Check or set P ...................................................................252

Service Manual
HOME PRINT
SERVICE TRAINING
Table of Contents
Set boom pressures ............................................................ 253 Setting concrete pump pressure (single-circuit units) ........303
(load sensing proportional booms) ............................ 253 Setting boom circuit pressures ............................................306
Set 15 bar pretension .......................................................... 255 Load-sensing boom hydraulic controls ...............................306
Set water pump pressure .................................................... 255 Setting DP ...........................................................................306
Set the agitator pressure ..................................................... 255 Setting Q-min .....................................................................308
KVM 39X .................................................................................. 257 Setting boom pressure ........................................................309
Check all hydraulic pressures ............................................ 257 Set the #1 down side pressure .............................................310
Set the concrete pump main relief valve (twin circuit) ...... 259 Setting outrigger pressure ...................................................311
Setting the soft switch circuit relief pressure ..................... 260 Set accumulator circuit hydraulic oil pressure
Set accumulator circuit ...................................................... 261 (units with accumulator unloading valves) .........................314
(units with a pressure- compensated pump) .............. 261 S 45/47SX ...................................................................................317
Set the outrigger pressure .................................................. 262 Setting Pressures .......................................................................317
Check or set P .................................................................. 265 Check all hydraulic pressures. ............................................317
Check or set Q-min ............................................................ 265 Setting pressures on Hi-flo -6 pumpkits .............................317
Set boom pressures ............................................................ 266 Setting the soft switch relief pressure .................................320
(load sensing proportional booms) ............................ 266 Setting boom circuit pressures ............................................320
Boom holding valves ......................................................... 267 Load-sensing boom hydraulic controls ...............................320
Set 15 bar pretension .......................................................... 268 Setting delta P pressure .......................................................321
Set water pump pressure .................................................... 268 Setting Q-min .....................................................................323
Set the agitator pressure ..................................................... 268 Setting boom pressures .......................................................323
S 42SX ....................................................................................... 271 Setting outrigger pressure ...................................................324
Setting Pressures ................................................................ 271 Set the agitator pressure ......................................................325
Check all hydraulic pressures ............................................ 271 Set accumulator circuit pressure .........................................326
Preheat the hydraulic oil ............................................ 271 S 45SX Hi-Flow - 6 ....................................................................329
Setting pressures on Hi-flo -6 pumpkits ............................ 272 Setting Pressures .......................................................................329
Setting the soft switch relief pressure ................................ 274 Check all hydraulic pressures. ............................................329
Setting boom circuit pressures ........................................... 274 Setting the main relief pressure and pressure cutoff on
Load-sensing boom hydraulic controls .............................. 274 Hi-flo -6 pumpkits ..............................................................330
Setting delta P pressure ...................................................... 275 Setting the soft switch relief pressure .................................332
Setting Q-min ..................................................................... 277 Setting boom circuit pressures ............................................332
Setting boom pressures ...................................................... 277 Load-sensing boom hydraulic controls ...............................332
Setting outrigger pressure .................................................. 278
KVM 52M (pre-1998) ...............................................................333
Setting the agitator pressure ............................................... 279
Pressure Settings for KVM 52 Proportional
Setting accumulator circuit pressure .................................. 280
Load Sensing ......................................................................333
KVM 42M - Proportional (Apitech) Single Circuit .............. 283 Component Location Guide- KVM 52 ...............................334
Check hydraulic pressures ................................................. 283 Pressure Settings for KVM 52 Proportional
Preheat the hydraulic oil .................................................... 283 Load Sensing ......................................................................334
Setting concrete pump pressure (single-circuit units) ........ 283 Pressure Regulator Cutaway KVM 52 ...............................336
Setting boom circuit pressures ........................................... 286 Pressure Settings for Regulator and Releif Valves
Load-sensing boom hydraulic controls .............................. 286 KVM 52 ..............................................................................337
Setting DP .......................................................................... 286 Setting Pretension Pressure(Refer to Figure 5) ..................337
Setting Q-min ..................................................................... 288 Control Block 1 for KVM 52 Boom 3, Boom 4,
Setting boom pressure ........................................................ 288 & Slewing 338
Setting pretension .............................................................. 291 Control Block 2 for KVM 52 Boom 1, Boom 2,
KVM 42M - Proportional (Apitech) Twin Circuit ............... 293 & Outriggers .......................................................................339
Check hydraulic pressures ................................................. 293 Pre-Control Block 1-A for KVM 52 ..................................340
Preheat the hydraulic oil .................................................... 293 Pre-Control block 1-B for KVM 52 ..................................341
Setting concrete pump pressure (High-flow pumpkits) ..... 293 Pre-Control Block 1-C for KVM 52 ..................................342
Setting the soft switch circuit relief pressure ..................... 295 Pre-Control Block 2-A for KVM 52 ..................................343
reheat the oil to check pressures ........................................ 296 Pre-Control Block 2-B for KVM 52 ..................................344
Load-sensing boom hydraulic controls .............................. 296 Electric Bypass Valve for KVM 52 ....................................345
Setting DP .......................................................................... 297 S 52 SX .......................................................................................347
Setting Q-min ..................................................................... 299
Setting Pressures .......................................................................347
Setting boom pressure ........................................................ 299
Check and adjust all hydraulic pressures ............................347
Setting 15 bar pretension ................................................... 301
Preheat the hydraulic oil .............................................347
KVM 42M - Proportional (Rexroth) ...................................... 303 Setting pressures on Hi-flo -6 pumpkits .............................348
Check hydraulic pressures ................................................. 303 Pressure setting procedure: .........................................348
Preheat the hydraulic oil .................................................... 303

Service Manual
HOME PRINT
SERVICE TRAINING
Table of Contents
Setting the soft switch relief pressure ................................ 350 Electrical Information
Setting boom circuit pressures ........................................... 350
Load-sensing boom hydraulic controls .............................. 350 Boom Control Systems and the Advantages of Each ............397
Setting Delta P pressure ..................................................... 351 Boom Control Systems .............................................................399
Setting Q-min ..................................................................... 352 Introduction to Proportional Controls ...................................400
Setting boom pressures ...................................................... 353 The Joystick with Potentiometer ........................................400
Setting main pressure ................................................. 353 The Proportional Amplifier ................................................401
Setting boom pressure (redundant) relief ................... 353 The Solenoid Valves ...........................................................401
Setting pressure cut-off .............................................. 354 The Proportional Amplifier in Use with the Radio ...............402
Setting slewing pressure ............................................ 354
Motherboard for Proportional Units ......................................403
Setting outrigger pressure ................................................. 355
Setting the agitator pressure ............................................... 355 Power Supply - Slot 9 ...............................................................404
Setting accumulator circuit pressure .................................. 356 Proportional Amplifier - Slot 1,2,3 ..........................................405
KVM 52M ................................................................................. 359 Calibration of Proportional Amplifier Cards ........................406
Setting relief pressure and pressure cutoff on Linear Signal Diagram .............................................................407
Hi-flo -6 pumpkits ............................................................. 359 Decal of Proportional Motherboard .......................................408
Setting the soft switch circuit relief pressure ..................... 362 Wiring Diagram - DUVAC II 12V / 24V Transformer .........409
Set boom circuit pressures ................................................. 362
Wiring Diagram - DUVAC II 12V / 24V Transformer .........410
Checking and Setting DP pressure ..................................... 363
Set Q-min ........................................................................... 364 Digital Proportional - Overview (1 of 5) .................................411
Checking boom pressures .................................................. 365 Overview ............................................................................411
Setting main boom circuit pressures .................................. 366 M.A.T. ................................................................................412
Checking pretension pressure ............................................ 367 Processor Unit .....................................................................413
Set the outrigger pressure .................................................. 368 Card Functions ....................................................................414
Set the agitator pressure ..................................................... 369 Control System Arrangement .............................................415
KVM 55M ................................................................................. 371 Digital Proportional - Programming ......................................416
Check all hydraulic pressures ............................................ 371 Programming ......................................................................416
Preheat the hydraulic oil .................................................... 371 MAT Operation ..................................................................416
Setting relief pressure and pressure cutoff on Menu Structure ...................................................................417
Hi-flo -6 pumpkits ............................................................. 372 Moving Through The Menu Survey ...................................418
Setting the soft switch circuit relief pressure ..................... 375 Access The Service Menu ..................................................419
Setting boom circuit pressures ........................................... 375 Identifying the Entries and Parameters ...............................420
Checking and setting DP pressure ..................................... 375 SCV Card Main Menus ...................................................420
Setting Q-min ..................................................................... 377 ?PAR Main Menu ...........................................................420
Checking boom pressures .................................................. 377 Submenus Functions and Parameters .................................421
Setting main boom circuit pressures .................................. 378 ?SELECT
Checking pretension pressure ............................................ 379 Submenu Functions and Parameters
Setting the outrigger pressure ............................................ 380 (In Service Menu Only!) .....................................................422
Set the agitator pressure ..................................................... 381 ?V24 Submenu Functions and Parameters ......................423
Set accumulator circuit pressure ........................................ 382 ?DIN Main Menu ............................................................423
?RACK Submenu Functions and Parameters ................424
S 58/61SX .................................................................................. 385
?BDI A Submenu Functions and Parameters .................425
Check all hydraulic pressures ............................................ 385
?BDI F Submenu Functions and Parameters .................426
Preheat the hydraulic oil ............................................ 385
?SOUT" Main Menu .........................................................427
Setting pressures on Hi-flo -6 pumpkits ............................ 385
?POUT Main Menu .........................................................428
Pressure setting procedure: ........................................ 385
?DIAG Main Menu .........................................................429
Setting the soft switch relief pressure ................................ 388
?SYSTEM Main Menu ..................................................429
Setting boom circuit pressures ........................................... 388
?GERAET Main Menu (In Service Menu Only!) ...........430
Load-sensing boom hydraulic controls .............................. 388
V2.4 Menus ........................................................................430
Setting Delta P pressure ..................................................... 389
Software Versions ...............................................................431
Setting Q-min ..................................................................... 390
Setting boom pressures ...................................................... 391 Digital Proportional - Balancing Valve Currents ..................453
Setting main pressure ................................................. 391 Hysteresis ............................................................................455
Setting boom pressure (redundant) relief ................... 391 Diagnostic Signal ................................................................455
Setting pressure cut-off .............................................. 392 Setting Valve Currents ........................................................455
Setting slewing pressure ............................................ 392 Digital Proportional - Troubleshooting ..................................457
Setting outrigger pressure ................................................. 393 Troubleshooting procedure 1 ..............................................459
Setting the agitator pressure ............................................... 393 Troubleshooting procedure 2 ..............................................459
Setting accumulator circuit pressure .................................. 394 Troubleshooting procedure 3 ..............................................459

Service Manual
HOME PRINT
SERVICE TRAINING
Table of Contents
Troubleshooting procedure 4 ............................................. 459 Bypass mode ...............................................................518
Troubleshooting The Radio ............................................... 460 Options box .........................................................................519
Operation ........................................................................... 461 Night light switch .......................................................519
Emergency Stop ................................................................. 462 Concrete shut-off valve switch ...................................519
Automatic Shut down ........................................................ 462 Control and monitoring components ..................................520
Trouble-shooting ................................................................ 463 Controller cabinet (Figure 13) ....................................520
Troubleshooting tables ....................................................... 464 Display window (Figure 14) .......................................520
Control status indications ...........................................520
Operating mode display ..............................................520
Comfort Control Manual Menu control .......................................................................521
1.0 Working with the info & diagnosis system ................. 468 Basic functions of the keys (Figure 15) ......................521
1.1 Introduction into the info & diagnosis system ..... 468 Fast selection/abbreviated function keys (shortcuts): .521
1.2 Menu structure info & diagnosis system / Local control .......................................................................522
Operation data display ....................................................... 470 Remote control ...................................................................523
1.2.1 Standard display & malfunction messages ....... 470 Menu overview - Main menu .............................................524
1.2.2 Main menu ........................................................ 471 Menu overview - Main menu (continued) ..........................525
1.2.3 "PUMP VPUME" sub-menu ............................. 472 Menu overview - submenus ................................................528
1.2.4 "OPERATION DATA" sub-menu .................... 472 Menu operation - Example: ................................................529
1.2.5 "MALFUNCTION LIST" sub-menu ................ 473 Diagnostic system/Fault handling ...................................530
1.2.6 "LUBRICATION-UNIT" sub-menu ................ 473 Display language ........................................................531
1.2.7 "I/O DISPLAY" sub-menu ............................... 473 Acknowledging messages ...........................................532
1.2.8 SCROLLING" sub-menu .................................. 474 Acknowledging faults .........................................................532
2.0 Concrete pump efficiency parameter setting / Fault definition ...................................................................532
Central lubrication / Prop characteristics ........................... 475 Low level fault ............................................................532
2.1 Password entry and parameter selection menu .... 475 High level faults ..........................................................532
2.2 Setting the concrete pump efficiency for Silent diagnostic .........................................................533
pumped volume determination .................................. 476 Reporting and acknowledging of faults ......................534
2.3 Adjusting the central lubrication .................................. 477 Acknowledging of several faults ................................539
2.4 Adjusting the proportional parameters for boom Switching off the control system ................................539
functions ............................................................................. 478 Summary of messages ........................................................540
Proportional characteristics adjustment for the Heat the oil first ..................................................................552
BOOM SLEW function with PROP valve types : ............. 479 Restore original factory settings .................................552
Proportional characteristics adjustment for the Setting parameters ......................................................553
BOOM 1 function with PULSAR valve types : ................ 480
3.0 I/O status display - signals & references ..................... 481
3.1 Machine control ................................................... 481 Radio Remotes
3.2 Concrete pump control ......................................... 483 Cross Reference Wiring Chart ................................................559
3.3 Boom control ....................................................... 484
3.4 Rear panel ............................................................ 486
3.5 Extension module ................................................ 487 Radio Control FW 18
4.0 Fault messages and fault causes ................................... 488
Table of Contents ......................................................................561
4.1Introduction ........................................................... 488
4.2 Control diagnosis electronic modules 1. Safety and Accident Prevention Regulations .....................561
Fault code S !) ............................................................ 489 Safety Regulations - Concrete Pumps with
4.3 Remote-control system diagnosis (fault code F!) 490 placing booms .....................................................................562
4.5 Engine/PTO Diagnosis (fault code D!) ................ 493 Traveling .............................................................................562
4.6 Concrete pump diagnosis (fault code B!) ............ 494 Jacking ................................................................................562
4.7 Boom control diagnosis (fault code M!) .............. 495 Concrete Pump ...................................................................562
4.8 Central lubrication/extension diagnosis (fault code Z/ Placing Boom .....................................................................562
E!) 497 Pipelines ..............................................................................563
5.0 Output signal interdependence list ............................... 498 Remote Controls .................................................................563
Electrical Connections .........................................................563
Part 1 Operation ...................................................................... 514
Commissioning .................................................................. 514 2. Short Instructions .................................................................564
Selecting local control ....................................................... 515 Preparing the Commissioning ............................................564
Selecting remote control .................................................... 516 Making Ready for Operation ..............................................564
Ram change mode: ............................................................. 517 Operating Mode ..................................................................564
Emergency stop buttons ..................................................... 518 Reasons for Automatic Switch-off .....................................564
Override of the E-stop manifold ........................................ 518 3. Preface ...................................................................................564

Service Manual
HOME PRINT
SERVICE TRAINING
Table of Contents
4. Extract from the Terms of Warranty ................................ 565 Troubleshooting: Receiver LEDs .......................................598
5. Model Plates ......................................................................... 566 Troubleshooting Controller (MC1) ....................................600
6. Technical Data ...................................................................... 566 Troubleshooting Table: Transmitter LEDs ......................601
7. Brief Description .................................................................. 566 16. Maintenance ........................................................................602
Transmitter ......................................................................... 566 Replacing of Fuses ..............................................................602
Receiver ............................................................................. 567 17. Repair ..................................................................................603
8. Control and Monitoring Equipment .................................. 568
Radio Remote .................................................................... 568
Receiver ............................................................................. 569
Radio Control FW 24
9. Commissioning ..................................................................... 570 Table of Contents ......................................................................605
Preparations ....................................................................... 570 Safety Instructions ....................................................................606
Ready for operation ........................................................... 570 Scope of Application .................................................................607
10. Operating the Radio Remote Control .............................. 571 Start-Up .....................................................................................608
Transmitter mode ............................................................... 571 Operation ...................................................................................611
Transmitter range ............................................................... 572
Charging the Battery ................................................................612
Putting out of Operation .................................................... 573
Changeover to Cable Remote Control ............................... 573 Maintenance ..............................................................................613
12. Safety Facilities .................................................................. 574 Operation Fault Indicators ......................................................614
Fuses .................................................................................. 574
13. Maintenance Works and Checks ...................................... 575 C32/CPC Radio Remote
Changing the transmitter battery ........................................ 575
Charging the transmitter battery ........................................ 575 Spread Spectrum Technology ..................................................617
Mounting the Receiver Antenna: ............................................618
Transmitter Operation .............................................................619
Radio Control FW 20 Remote Radio Controller .........................................................622
Table of Contents ..................................................................... 577
2. Short Operating Instructions .............................................. 578
Preparations ....................................................................... 578 Omnex Radio Control System
Ready-for-Operation State ................................................. 578 1. Introduction ..........................................................................627
Emergency Shut-Off .......................................................... 578 2. Physical Mounting ................................................................628
Automatic Shut-Off ........................................................... 578
3. Considerations for Electrowelding ......................................628
Interruptions of Work ........................................................ 578
4. Receiver Connector Assignments ........................................629
3. Foreward ............................................................................... 579
5. Cable Unit Connector Assignments ....................................630
4. Designated Use ..................................................................... 579
6. Fuses .......................................................................................630
Non Designated Use ................................................................. 579
7. Operations .............................................................................631
Extract from Terms of Warranty ........................................... 580
7.1 Receiver ........................................................................631
5. Safety Rules and Accident Prevention Regulations .......... 581 7.1.1 Receiver Lights - General Function ...................631
7. Short Description ................................................................. 582 7.1.2 Receiver Lights - Error Conditions ...................631
8. Technical Data: .................................................................... 583 7.1.3 Operator Adjustments: .......................................632
Transmitter ......................................................................... 583 7.2 Transmitter ....................................................................633
Receiver ............................................................................. 584 7.2.1 Transmitter Lights .............................................633
9. Monitoring-, Warning-, and Control Elements ................ 585 7.2.2 Operator Controls: .............................................634
7.3 Cable Unit .....................................................................634
10. Pre-Operational Instructions ............................................ 588
7.3.1 Cable Unit Lights ...............................................634
11. Operation ............................................................................ 592 7.3.2 Operator Controls: .............................................635
Battery Capacity ................................................................ 592
8. Troubleshooting Information ..............................................635
Disturbances ....................................................................... 593
8.1 I24-MC Board ...............................................................635
Frequency Change ............................................................. 593
8.2 Receiver TPCB-1527-01 Board ....................................635
12. Emergency Shut-Off .......................................................... 593
13. Interruptions of Work/End of Operation ........................ 594
14. Replacing the Battery ........................................................ 595 Conversion Charts
Recharging of Battery ........................................................ 595 Fluid Power Formulas ..............................................................642
15. Malfunctions ....................................................................... 596 Torque Specifications ...............................................................644
Message Interference ......................................................... 597
Torque Specification: Slewing Roller Bearing Bolts .............647
Trouble Shooting ...................................................................... 598
WP Number Codes ...................................................................652

Service Manual
HOME PRINT
SERVICE TRAINING
Table of Contents
BP Model Number Codes ........................................................ 653
Outrigger Spreads and Loads ................................................. 654
Boom Pin Clearances ............................................................... 655
Nozzle Chart ............................................................................. 665
Boom Times/Without Weights ................................................ 666
Boom Pressures & Nozzle Chart Size .................................... 667
Boom Pressures & Nozzle Chart Size .................................... 668
Rotek Bearing Clearance Instructions - SAIE - 5114 ........... 669

Special Tools
Hydraulic Trouble Shooting Kits ........................................... 679
Hydraulic Oil Filter Cart ........................................................ 679
Flow Meters and Accesories .................................................... 680
Flow Meter Y223 Model HT200 ............................... 680
Specifications: ............................................................ 680
Accessories: ............................................................... 680
Material Cylinder Alignment Tool ......................................... 681
Piston Installation Tools for Differential Cylinders ............. 682
Gland Packing Installation Tools ........................................... 683
Seal Replacement Tools ........................................................... 684
Piston Seal Guide Tool ...................................................... 684
Piston Seal Form Tool ....................................................... 684
Bushing Installation Tool ........................................................ 684
Rock Shaft Bushing Installation Tool ................................ 684
Accumulator Charging Kit ..................................................... 685
Adjustment Meters for Analog Proportional Cards ............. 685
Analog Adjustment Meter ................................................. 685
Technition Support Kit ........................................................... 685
Electrical Tools and Accessories ............................................. 686
Spanner Socket Tools for Boom Pins ..................................... 687
Truck Engine Tools ................................................................. 688
Pro-Link 9000 .................................................................... 688
Micellaneous Tools ................................................................... 688
Whip Hose and Fittings ..................................................... 688
Rock Valve Cover Alignment ............................................ 688

Service Manual
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Maintenance Maintenance Chart

Semi-annually

As Indicated
Quarterly

Annually
Monthly
Weekly
Daily
Task

Check hydraulic pressures


Check truck fluid levels
Bleed moisture from air tank
Check tires
Check hydraulic oil
Bleed moisture from hydraulic tank
Check differential cylinder rod packings
Inspect bolts on Rock Valve and rams
Grease Rock Valve and agitator bearings
Grease Rollix bearing and hollow pin
Check optional auto greaser reservoir
Fill optional auto greaser reservoir
Inspect for damage and leaks
Check if maintenance is due
Grease boom zerks
Check pipewall thickness
Check oil in optional air compressor
Check Rock Valve tension nut
Inspect cutting ring/rotate if needed
Lubricate mechanical moving parts
Check tapered bend wedge bolt

Service Manual 1
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Semi-annually

As Indicated
Quarterly

Annually
Monthly
Weekly
Daily
Task

Check boom slewing gearcase oil level


Clean slewing gearcase breather cap
Check function of mechanical boom brake
Clean and repack rollix gear
Inspect the turret bolts for tightness
Check fluid in distribution gearcase
Check unit mounting hardware
Check and adjust hydraulic pressures
Check hydraulic oil cooler fins
Check drive pinion mounting screw
Change oil in optional air compressor
Change hydraulic oil for temp. reasons
Check the accumulator pre-charge
Change oil in distribution gearcase -
Change oil in boom slewing gearcase
Test dirty filter lamp circuit
Change hydraulic oil for age reasons
Clean optional compressor
Change corrosion inhibitors
Periodic - structural inspection
Change main return oil filter
Change high pressure oil filter
Change water system inline filter

2 Service Manual
HOME
PRINT

Operators Checklist for Unit#_________________________ Week Ending_________________________


Task Mon Tues Wed Thurs Friday Comments
Perform DOT pre-trip inspection
Check hydraulic pressures
Check truck fluid levels
Bleed moisture from air tank
Check tires
Check hydraulic oil
Bleed moisture from hydraulic tank
Check differential cylinder rod packings
Inspect bolts on rock valve and rams
Grease rock valve and agitator bearings
Grease boom bearings and hollow pin
Fill optional auto greaser reservoir
Inspect for damage and leaks

Service Manual
Check if maintenance is due
Perform post-trip inspection
SERVICE TRAINING

Operators Check list for Weekly Maintenance (Ex.)

S0167.eps

3
Maintenance, Lubrication Schedules, etc.
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Size Comparison of Particles

SCREEN SIZES
U.S. SIEVE NUMBER OPENING (micro-meters) OPENING (inches)
50 297 0.0117
60 238 0.009
70 210 0.0083
100 149 0.0059
140 105 0.0041
200 74 0.0029
270 53 0.0021
325 44 0.0017
PAPER 10 0.00039
PAPER 5 0.00019

SIZES OF FAMILIAR OBJECTS


SUBSTANCE MICRO-METERS INCHES
Grain of Table Salt 100 0.004
Human Hair 70 0.0027
Lower Limit of Visibility 40 0.00158
White Blood Cell 25 0.001
Talcum Powder 10 0.0004
Red Blood Cell 8 0.0003
Bacteria (average) 2 0.00008

149 mm
(100 Mesh)

SIZES IN MICRO-METERS
(Magnification 500x) 74 mm
(200 Mesh)

44 mm
(325 Mesh)

25 mm

10 mm
5 mm
2 mm
S0022.eps

4 Service Manual
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Filtration Ratings Filter Facts


Fine Filters have P
Nominal Rating Fine filters have long life
An arbitrary micrometer value indicated by the filter Harmful particles cannot be seen
manufacturer. Due to lack of reproducibility, this rating 1 micron nominal filters pass 10 micron particles
is deprecated. Fine filters remove silt, not additives
Metal mesh breathers allow airborne ingression
Absolute Rating New oil can be very dirty
The diameter of the largest hard spherical particle that
will pass through a filter under specified test
BETA RATINGS
conditions. This is an indication of the largest opening
in the filter element. Particles in this range (and smaller) should {
pass through the filter.
Filtration Ratio(n)
The ratio of the number of particles greater than a
given size (n) in the influent fluid to the number of
particles greater than the same size (n) in the effluent
fluid.
Particles in this range (and larger) should
be removed by the filter.

X = 200
{
example: 12 = 200.
This means that for every 200 particles of
HOW BETA WORKS 12 microns or larger that hit the
media, 1 will make it through.

IN OUT = IN
OUT

PARTICLES > 5 m UPSTREAM DOWNSTREAM

FILTER IN OUT 5 FLOW

FILTER A 10,000 5000 2 X = 75


example: 12 = 75.
FILTER B 10,000 100 100 This means that for every 75 particles of
12 microns or larger that hit the
FILTER C 10,000 1 10,000
media, 1 will make it through.
S0023.eps (225 particles shown entering, 3 coming out)

The filtration ratio or Beta is calculated by dividing the


number of particles entering the filter by the number of
particles exiting the filter. 5 represents the filtration
ratio at 5 micrometers or the ratio of upstream to the
downstream particles larger than 5 micrometers. UPSTREAM DOWNSTREAM

FLOW S0024.eps

Service Manual 5
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Fluid Contamination and


Control Control Methods
Built in
The sources of contamination in hydraulic and
a. Clean all components before installation
lubricating systems are divided into three general
categories. The degree of importance of each source b. Use only straight thread fittings or flange fit-
depends on: system design, operating environment, and tings
maintenance practices c. Flush new systems with high efficiency filters
Ingressed
Primary sources of contamination a. Use reservoir breather filters that are as fine as
Bulit-In Contamination (dirt, shavings, slag, and the system filters
etc. that may be present during assembly). b. Use high quality seals in all system compo-
nents
Ingressed Contamination (is an environmental c. Always keep maintenance environment clean
type which happens during routine servicing or d. Pre-filter the new oil prior to dispensing to tank
from lack of maintenance). Internally Generated
a. Always use fine "silt control" filters
Internally Generated Contamination (occurs b. Use specified lubricants for components
from the rubbing and grinding of all moving parts c. Eliminate water from the system to reduce rust
inside each and every component of the system).

S0025.eps

6 Service Manual
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Handling, Storing & Dispensing and snow. The proper storing position of an oil drum
is: drum should be laid on its side with the bungs
Lubricating fluids approximately horizontal and at the lowest point. In
To obtain optimum performance from oil, proper this position, water and moisture cannot collect in the
handling, storing and dispensing is required. These chime and because the bungs are below the level of the
steps are necessary to preserve the integrity of the drums contents, the incidence of water being drawn
product. It is uneconomic to buy a high quality into the drum from normal breathing is greatly
lubricant and then permit degradation through reduced. For maximum protection, drums should be
contamination. stood on end with bungs down on a well-drained
surface. In circumstances when all the aforementioned
Unless simple precautions are observed, contamination
storing methods are impractical, drum covers should be
of lubricants can occur during storage; or during
used. Covers are available in both metal and plastic.
transfer of oil from the original container to the
Drums with a bung on the side should be stored either
dispensing equipment; or during dispensing of oils to
on their end, or on their side with the bung facing
the equipment to be lubricated. Pumps, oil cans,
down. Regardless of the position, drums should
measures, funnels and other dispensing equipment
always be placed on blocks or racks several inches
must be kept clean at all times and covered when not in
from the ground to avoid contact with moisture or
use.
standing water.
Storing oil drums, fill carts, or other containers outside
When drums must be stored outside with the bung end
of climate controlled areas is a poor practice. Water
upward, they should be blocked up in a manner that
and moisture may get into the drum around the bungs
will keep the drum teetered to provide sufficient
and contaminate or destroy the drums contents. A
draining of water. The drum should be rotated on the
drum standing on end with the bungs facing up can
blocks so that any water collecting on the top of the
collect rain water or condensation inside the chime.
drum surface does not come in contact with or
This water can gradually be drawn in around the bungs
submerge the bung openings.
by the breathing of the drum as the ambient
temperature rises and falls. This can occur even with Before opening a drum that has been stored outside, the
bungs drawn tight and the tamper-proof seals in place. bung and chime areas should be cleaned thoroughly to
In addition, the dirt and rust that can accumulate inside eliminate the hazard of collected rust, scale and dirt
the chime and around the bungs may contaminate the from falling into the drum.
drums contents when the drum is opened for use. Always use the oldest oil first. The probability of
As a general rule, lubricants in drums smaller than 16 oxidation, contamination and attack by heat and cold,
gallon capacity should never be stored outside. increase with age. If the oil quality is suspect due to
However if drums must be stored outside, a temporary long periods of storage, have the oil analyzed before
shelter or lean-to, and/or a waterproof tarpaulin is using it.
highly recommended for protecting the drum from rain

SUN
standing
RAIN
water
chime bungs

COOL air space WARM powerful COOLING


air space
reduced suction
created
Contaminating
Clean oil in sealed Oil and air in drum water is drawn into
drum as delivered expand from heat drum through the
and then stored exposure forcing bungs when oil
outside standing air out through top water and air cools and
on end contracts
S0026.eps

Service Manual 7
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Hydraulic Oils gets. The lower the ISO VG number the thinner the oil
and the lower the pour point of the oil. On the other
General information relates to all hydraulic oils. hand, the thinner the oil, the lower the temperature will
Specific information contains hydraulic oil have to be before it breaks down the lubricating film
recommendations for Schwing concrete pumps. that protects your components.
The quality of the oil needed for use in a Schwing
General information concrete pump is rated in the DIN system. The ratings
Hydraulic oils are rated for viscosity, heat dissipation, have to do with the chemical additive package that is
foaming characteristics, pour point, antiwear additives, introduced into the oil. Both the DIN rating HLP and
anticorrosive additives, lubricating qualities, HV qualities are approved for use in our concrete
compressibility, temperature range, temperature pumps.
stability, and other functions. Although many different
brands of oil meet these specifications, they may use Specific information
different chemical additive packages to achieve the end All concrete pumps leave the Schwing factory filled
result. For this reason, you should not mix two with Texaco Rando HD 46 hydraulic oil, which has an
different brands of oil. The additive package from one ISO viscosity rating of VG 46. Rando HDZ 46, an
brand may be incompatible with the additive package extended-viscosity oil designed for use under severe
from the other, rendering both packages useless. conditions, is available on request. If you want your
Recently a few manufacturers have introduced new concrete pump filled with a different brand or
biodegradable hydraulic oils onto the market. These different viscosity oil, you should specify it when
oils are based on vegetable extracts instead of mineral ordering.
extracts. They are considered safer for the environment Many other brands of oil have been approved for use in
in the event of a spill, although the additive packages Schwing concrete pumps, including:
are not inert. One brand, Mobil EAL 224-H, has been
accepted for use in Schwing pumps, and other brands Mobil DTE
are under consideration and testing. These oils must Shell Tellus oil
not be mixed with mineral-based hydraulic oils, even in BP Energol
very small amounts. If you will be pumping a job in an
Aral Vitam
environmentally sensitive location and want to use this
type of hydraulic oil, please contact the Schwing Esso Nuto
Service Department at (651) 429-0999 for instructions Esso Univis
on making the change from mineral oil.
Total Azolla
Viscosity of hydraulic oil is similar in concept to the
Wintershall Wiolan
different weights of motor oil. For example, in the
winter you may run 5W-30 in your car, while in the The order of the brands listed is not significant. Any oil
summer you run 10W-40. The same is true for that meets the quality and viscosity standards described
hydraulic systems. If you live in a climate where the above can be used.
weather is changing from extremely hot conditions to
extremely cold conditions, you should consider
changing the weight of the hydraulic oil that you use
by the season. The International Standards
Organization (ISO) has developed a method of grading
hydraulic oils for viscosity. For summer in northern
North America, we recommend ISO VG 46 weight oil,
while in the winter we recommend ISO VG 32 or even
VG 22, depending on how cold it gets in your area. For
southern North America and Central America, we
recommend ISO VG 46 for the winter and ISO VG 68
or VG 100 for the summer, depending on how hot it

8 Service Manual
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.
Hydraulic Oils When to change your hydraulic oil
VG 32 = Winter application conditions in Central Change your hydraulic oil at least once a year. If you
Europe. use good filters, and change them when they are dirty,
VG 46 = Summer application conditions in Central the oil will be clean even after a year. The chemical
Europe. additive packages that give the oil its properties will
break down with time, however and no amount of
VG 68 = Excessive heat indoors application or in the
filtration will bring them back.
Tropics.

ISO viscosity / DIN quality VG 32 / HLP VG 46 / HLP VG 68 / HLP


ARAL - VITAM GF 32 GF 46 GF 68
BP - ENERGOL HLP 32 HLP 46 HLP 68
ESSO - NUTO H 32 H 46 H 68
MOBIL - DTE 24 25 26
SHELL - TELLUS OIL 32 46 68
TOTAL - AZOLLA ZS 32 ZS 46 ZS 68
TEXACO - RANDO OIL HD* A-32 B-46 C-68
WINTERSHALL - WIOLAN HS 32 HS 46 HS 68

* Factory Fill oil at Schwing America Inc.

Service Manual 9
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Hydraulic Oil Viscosity Chart The minimum permissible viscosity represents the
warmest temperature at which the oil will still be
The illustration below shows the relationship between thick enough to provide lubrication and sealing.
the oil temperature and its viscosity. As you can see, Anything warmer, and the components will have
the oil gets thicker when the temperature is low and metal-to-metal contact (thermal breakdown).
thinner as the temperature rises. The optimum operating viscosity is the range of oil
The cold start limit represents the coldest thickness at which the oil works best (thin enough
temperature at which the oil is thin enough to flow to flow easily yet thick enough to protect the
into the hydraulic pumps. Anything colder, and system components).
the pumps would not be able to suck in the oil An example of how to read a chart for VG-46 oil is
(cavitation). given in the chart below. The chart shows the cold start
limit as -8C (18F) and the minimum permissible
viscosity as 90C (194F). The optimum range is 50-
76C.

Temperature of Hydraulic Oil


(C)
Cold Start Limit
(very thick oil)
Water freezes

Water boils
VG
VG 2
VG 2
VG 6
VG 8
2
3
4
6
10
0

Optimum
Operating
Viscosity
temp chart.eps

Minimum permissible
viscosity
(C)
(F)
C = degrees Celsius
F = degrees Fahrenheit S0027.eps

10 Service Manual
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Lubrication Prefix Codes Industrial gear lubricant codes


CLP An "industrial" gear lubricant oil with
Standard codes used additives to improve corrosion protection,
API American Petroleum Institute aging stability, and protection against wear in
areas with many types of friction, and to
BI Main Association of the German increase gear stability under load. Meets
Construction Industry. As an alternative to DIN 51517.
the recommended lubricants and operating
agents, the standard lubricants with this Vehicle gear box oil codes
prefix may be substituted. GO 90 BI standard lubricant, a gear box oil that
DIN Deutche Industrie Norm (German Industry meets API-GL 5.
Norm) MIL-L-2105B Motor vehicle gear lubricant oil for
ISO International Standardization Organization hypoid bevel gear lubrication under
highest demands in gears and axles.
MIL-L American Military Standard for Lubricants Roughly corresponds to API-GL 5.
SAE Society of Automotive Engineers Compressor oil codes
VG Viscosity in millimeters 3/s @ 10 F (40 C) VDL Mineral oil for air compressors with additives
to improve corrosion protection and aging
Hydraulic oil codes stability. Coke residue after aging is no more
API-CD Engine oil for heavily loaded diesel engines than 3%. Meets DIN 51532.
with or without superchargers. Grease codes
EO BI standard lubricant, a quality engine oil. KP 2 K Grease for high pressure load; in working
HLP Hydraulic oils with additives to improve temperature range from -20 C to 140 C;
corrosion protection, aging stability, and worked penetration from 265 to 295; and
protection against wear in areas with many minor or no changes due to presence of water.
types of friction. Meets DIN 51524. MPG-A BI standard lubricant, a grease in accordance
Temperature Range: 0 F up to 180 F. to KP 2 N. Meeting more requirements than
HV Hydraulic oils with low viscosity- KP 2 K and K 2 K.
temperature dependance, otherwise like If hydraulic oil of another manufacturer is to be used,
HLP. Meets DIN 51524. Temperature or oil of a different type; e.g. HP instead of HLP, a
Range: -30 F (-34 C) up to 180 F (82 C). complete oil change is necessary.
VG 32 Oil viscosity for winter application Mixing different viscosities of oil of the same
conditions in Northern USA or Central manufacturer is permissible in some cases. Consult the
Europe. oil manufacturer to be sure, and take into account that
VG 46 Oil viscosity for summer application the new viscosity is dependent on the ratio of the
conditions in Northern USA or Central mixture.
Europe. All hydraulic oil should be filtered from the storage
VG 68 Oil viscosity for extremely high temperatures container to the concrete pump hydraulic system. This
such as in the tropics, or within very hot filtering must be performed with a filter rated at 10
enclosed rooms. micron.
VG 220 Corresponds approximately to SAE 90 for For additional information on oil and specific
Industrial Gear Lubrication. viscosities, refer to Service Bulletin G112/84 and 103/
97.

Service Manual 11
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Lubrication Recomendations
Industrial Gear Lubricant Oil

ISO viscosity / DIN quality VG 220 / CLP


ARAL DEGOL BG 220, DEGOL BMB 220

BP ENERGOL GR-XP 220

ESSO SPARTAN - EP 220

MOBIL MOBILGEAR 630

SHELL OMALA OIL 220

TEXACO MEROPA 220

WINTERSHALL WIOLAN - IT 220

BI -

Motor Vehicle Gearbox Oil

ISO viscosity / MIL-L quality 90 (85w-90) / 2105 B


ARAL GEARBOX OIL HYP

BP ENERGEAR HYPO 90, HYPOGEAR 90

ESSO GEAR OIL GX-D, GEAR OIL GX

MOBIL MOBILUBE HD

SHELL SPIRAX HD, SPIRAX MB

TEXACO GEARTEX EP-C

WINTERSHALL WIOLAN HYPOID GEARBOX OIL 90


BI GO 90

The gear lubricant oils Industrial and Motor Vehicle are Under extreme conditions, please inquire as to
suitable for continuous ambient temperatures of suitability. The viscosity class ISO-VG 220 roughly
approximately -10 C to approximately +40 C. corresponds to SAE 90.

12 Service Manual
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.
Compressor Oil
VG 100 = AMBIENT TEMPERATURE 0 C to +10 C
VG 150 = AMBIENT TEMPERATURE ABOVE +10 C

ISO viscosity / DIN quality VG 100 / VDL VG 150 / VDL


ARAL MOTANOL - HE 100 MOTANOL - HE 150

BP ENERGOL - RC 100 ENERGOL - RC 150

MOBIL RARUS 427 RARUS 429

SHELL CORENA - H 100 CORENA - H 150

TEXACO COMP. OIL - EP 100 COMP. OIL - EP 150

WINTERSHALL WIOLAN - CD 100 WIOLAN - CD 150

Operating the compressor below 0 C may only be For an explanation of the various lubricant prefix codes
done according to manufacturers specifications. for determining suitable lubricant substitutes, refer to
page 11 of this section in this Service Manual.

Service Manual 13
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Filling Capacities
Hydraulic Reservoirs

Model System 1 & 2 System 3


BPL 500 66 gallons

BPA 750 37 gallons

BPA 750-18/1000 75 gallons

BPL 750/1000 66 gallons

BPA 2000 100 gallons

BPL 2000 120 gallons

BP 3000/3001 126 gallons

BP 4000 126 gallons

BPL 4000

BP 5000 126 gallons


BP 8000 126 gallons

KVM 17M 102 gallons

S 17 130 gallons

KVM 23M

KVM 23-4H 102 gallons 26.5 gallons

KVM 24-4 102 gallons 26.5 gallons

KVM 25
KVM 26M

KVM 26-4

KVM 28M 102 gallons 26.5 gallons

KVM 28 XL 125 gallons

S 28 X 98 gallons

S 31 XT 127 gallons

KVM 32M 132 gallons

KVM 32 XL 127 gallons

S 34 X 127 gallons

KVM 36M 147 gallons

KVM 36XL 127 gallons

14 Service Manual
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Model System 1 & 2 System 3


KVM 39X 127 gallons

S 39/41 SX 110 gallons

KVM 42M 147 gallons

S 42 SX 169 gallons

S 45/47 SX 169 gallons

S 52 SX 153 gallons

KVM 52/55 M 206 gallons

S 58/61 SX 153/180 gallons

SPB Power Pack 30 gallons

Slew Drives

Schwing Model Model Part Number Liters


S 17 NA NA NA

KVM 32 XL ZHP 10072000 2.25 liters

KVM 36M ZHP 3.19 10150116 3.0 liters

S 34X/KVM 36X ZHP 3.19 10117070 3.0 liters

KVM 39X ZHP 3.20 10174652 5.0 liters

KVM 42M ZHP 3.20 10150115 4.5 liters

DVM 42M ZHP 3.21L 10013890 5.0 liters

S 45/47 SX ZHP 3.20 10174104 4.0 liters


KVM 52 M ZHP 3.25 10154423 3.7 liters

S 52 SX ZHP 3.25 10188099 9.2 liters

S 58/61 SX ZHP 3.25 10188099 9 liters

Transmissions

Model Number Quarts/Liters


ZF Model WSK 400 21.5 quarts

ZF Model 4-S-150 GPA 20 quarts

ZF Model 16-S-190 A 20 quarts

Service Manual 15
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.
Gear Boxes

Model Number Quarts/Liters


STEYR Model VG2000 9 quarts

STEYR VG2000 w/cooler 10 quarts

STIEBEL Model 4190 NA

STIEBEL Model 4193 4.5 Liters

STIEBEL Model 4194 5.5 Liters

STIEBEL Model 4195 3.0 Liters

STIEBEL Model 4196 3.8 Liters

STIEBEL Model 4252 NA

STIEBEL Model 4400 NA

FABCO Transfer Case NA

16 Service Manual
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Spicer Transmisions of over-the-road service, but not exceeding 4000 miles.


In off-highway use, the oil change should be made
after 24 elapsed hours, but not exceeding 100 elapsed
Lubrication Specs
hours of service.
To ensure proper lubrication and operating
There are many factors that influence the following oil
temperatures in these units, it is important that the
change periods and we have not specified a definite
proper lubricants be used and that correct oil levels be
mileage interval.
maintained.
In general, it is suggested that a drain and flush period
Recommended Lubricants be scheduled every 20,000 miles for normal over-the-
road service. Off-highway service usually requires an
The following lubricants are recommended for use in
oil change every 30 days. The oil level in the
all SPICER Unit Power Transmissions, Auxiliary
transmission should be checked every 2000 miles (on-
Transmissions, and Transfer Cases.
highway), or every 24 hours (off-highway). The
1. Above 0 F, use SAE 50, 40, or 30 heavy duty correct oil level in all SPICER transmissions is
engine oil, API service classification MS, DG, DM, established by the filler plug opening.
or DS.
TO REFILL: Remove all dirt around the filler plug
2. Below 0 F, use SAE 30 heavy duty engine oil, before unscrewing plug; then refill with new oil of a
API service classification MS, DG, DM, or DS. grade recommended for the present season and
DO NOT USE EXTREME PRESSURE prevailing service. Fill to the bottom of the level-
ADDITIVES - such as found in multi-purpose or rear testing plug positioned on the side of the transmission.
axle type lubricants. These additives are not required
in SPICER transmissions, and may in some cases Over-Filling
create transmission problems. Multi-purpose oils as a Do not over-fill the transmission. Over-filling usually
group have; relatively poor oxidation stability, a high results in oil breakdown due to excessive heat and
rate of sludge formation, and a greater tendency to aeration from the churning action of the gears.
react on or corrode the steel or bronze parts within the Breakdown of the oil will result in heavy varnish and
unit. sludge deposits that plug up oil ports and build up on
splines and bearings. Also, overflow from overfilling
Oil Changes of oil usually escapes onto clutch or parking brake
SPICER recommends an initial oil change and flush area, causing additional trouble.
after the transmission is placed in actual service. This
oil change can be made any time following 1000 miles

TRANSMISSION CAPACITY MODEL (PINTS) TRANSMISSION CAPACITY MODEL (PINTS)

UNIT POWER TRANSMISSIONS UNIT POWER TRANSMISSIONS (cont)

3152, 3153 10 8251, 8255, 8753, 8755 24


5652 13 1062, 1262, 1263, 1010 28
5662 17 *1211 10
5752, 5753 15 Auxiliary Unit 10
5852, 5853 15 *1020 28
6352, 6354 17 Auxiliary Unit 10
6452, 6453, 6454, 6455, 6456 17 8440, 8445, 8842, 8844 16
6852, 6853, 6854, 6855 17 * These transmissions have separate oil suppliers. Each pod must be selected and filled separately.
7016, 7216 (4x4) 28 AUXILIARY TRANSMISSIONS
7352 18
7452, 7453 18 5831 4
8012, 8212, 8512 (4x3) 36 6041 8
8016, 8216, 8516, 8716 (4x4), P8516, P8716 36 7041 11
8041, 8045, 8542, 8544 16 7231 8
8051, 8055, 8553, 8555 24 8031, 8035 12
8052, 8054, 8552, 8554 24 8431, 8345, P8341, P8345 12
8241, 8245, 8742, 8744 16 9341 18
9441 12
S0028.eps

Service Manual 17
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

ZF Transmissions oil. (Please ask the oil supplier to certify fulfillment of


these conditions).
Lubrication Specs In torrid zones, oil grades SAE 85 W/90 or SAE 90
ZF-Synchromesh gearboxes can be used if the grades 80 W, 80 W/85 W or 80 W/90
are not available.
ZF-Constant mesh gearboxes W/splitter group &
range change gearboxes If these gear oils cannot be obtained, engine oils SAE-
ZF-Gearboxes with disc-clutch operated NMV 30 or SAE-40 in accordance with specification API-
CC, CD, SE, SF, or MIL-L-2104 C, MIL-L-2104 D,
ZF-Transfer gearboxes
MIL-L-46152 A & B should be used as a substitute. In
The oil grades listed on the following page are in this case, intervals between oil changes are to be
accordance with specification MIL-L-2105 and API reduced by half. NOTE! Multi-grade engine oils ARE
classification GL-4. Gear oils of viscosity group SAE NOT approved.
80 W, must be used.
THE SELECTOR TRANSMISSION MUST BE
These oils are partly available in viscosity grades SAE FILLED WITH OIL WHICH CONFORMS TO THE
80 W/85 and SAE 80 W/90. These multi-grade gear FOLLOWING LUBRICANT LIST: TE-ML 02 (API
oils can be used instead of SAE 80 W, under the GL-4, SAE 80W) UNIT CAPACITY =
condition that in addition to the EP additives, (the type APPROXIMATELY 20 QUARTS
and concentration of which are specified by ZF), any
other dissolved components (VI-Improver, Pour point
depressant) DO NOT exceed 2% (weight) of the basic

TE-ML 10
APPROVED LUBRICANTS
TRANSMISSION FOR SERVICE FILL
16 S 151 +WSK 4 S 120 GP +WSK Engine oils
16 S 160 (A) +WSK 4 S 150 GP (A) +WSK - API CD / CE / CF / SF / SG
16 S 190 (A) +WSK S 6-65 +WSK - MIL-L-2104C / -D / -E
16 S 220 (A) +WSK S 6-90 +WSK - MIL-L-46152C / -D / -E
16 S 221 +WSK 9 S 75 +WSK -SAE 20W-20
16 S 251 +WSK 9 S 109 +WSK
16 S 150 +WSK

3 DS 18 +WSK 244 Engine oils


- API CD / CE / CF / SF / SG
- MIL-L-2104C / -D / -E
- MIL-L-46152C / -D / -E
- SAE 10W for ambient temperatures above-10C, (14F)
- SAE 30 for ambient temperatures above-10C, (14F)

Add Add

Dip Stick
Oil Level
Indicator Plug

Drain Drain

Drain Drain
16 S 190 A 4 S-150 GPA S0029.eps

18 Service Manual
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Steyr Gear Boxes Remove the level checking plug at position #3, if
no oil comes from the port, start to dispense new
oil into the filling port until oil starts to over-flow
Lubrication Specs
out the checking port, then replace all plugs and
1. Steyr specifies 85-140 weight gear oil and strongly tighten.
advises a change of gear oil on all their transfer
5. With this method, proper oil filling is achieved
cases every 3300 hours or once per year.
without over-filling.
2. Whenever leakage of gear oil is discovered,
preventative measures must be taken. Transfer Case Gear Oil Capacities are as
3. Operating the transfer case with too low an oil Follows:
level WILL result in severe damage to the unit. Model VG2000 w/o cooler ...........2.25gal/8.5 liters
4. IMPORTANT! A proper oil level check can only Model VG2000 w/cooler ..............2.50gal/9.5 liters
be done by dispensing new oil into the filling port
at position #1, be sure that vehicle is on level
surface before removing any port plugs.

4 - Breather

1 - Oil Filler Plug

2 - Oil Drain Plug

3 - Oil Level Plug


2 - Oil Drain Plug
(only for models with oil cooler)
S0031.eps

Service Manual 19
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Stiebel Gear Boxes 5. Subsequent oil changes should occur every 2000
operating hours or at least, every 12 months.
Lubrication Specs 6. The oil type and quality approved by Stiebel is
determined by the following index. In situations
1. Reducers are supplied without oil. For filling
when an oil from this index cannot be acquired, use
capacity, please see data on the gear plate.
EP SAE 90 with viscosity 220 cST at 40 C.
2. Refilling is only necessary in case of oil leakage
7. Special conditions and applications will require
due to defective seals or defective gear case
special lubricants. Consult the gear manufacturer
gaskets. Such defects should be repaired
for special recommendations.
immediately.
GEAR OIL SAE 90 (or as we call it: 90W) IS A
3. First change of oil should be after 200 operating
SINGLE RANGE OIL.
hours.
GEAR OIL SAE 85-90 IS A MULTIGRADE OIL.
4. Drain the old oil immediately after the stopping of
EITHER OF THESE OILS MAY BE USED
reducer operation, while oil is still warm. Prior to
refilling the gear case, dispense some new oil into
the top of case to flush remaining old oil out.

ARAL Aral Degol BG 220, or Aral Degol BMB 220, or Aral Getriebeol EP 90

BP BP Energol GR-XP 220, or BP Getriebeoel EP SAE 90, or BP Gear Oil 90 EP

COLYPSOL UK-ECUBSOL OL 8050, or UK-ECUBSOL OL DB 90

CHEVRON Universal Gear Lubricant E SAE 85W-90, or Non-Leaded Gear Compound 220

ESSO SPARTAN EP 220, or ESSO GETRIEBEOEL GP-D 90, or ESSO GEAR OIL GP 90

MOBIL Mobilgear 630, or Mobil SHC 630, or Mobilube GX 85W-90-A

SHELL Shell Spirax EP 90, or Shell Omala Ol 220

TEXACO Meropa 220, or Geartex EP-D SAE 85W/90, or Geartex EP-A SAE 85W/90

20 Service Manual
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

FABCO Gear Boxes


Lubrication Specs

Lubricating Oil for Fabco TC-143 Transfer Case


LUBRICATION OIL CHANGE
The transfer case lubricant should be changed on all
RECOMMENDED LUBRICANTS new transfer cases after the first 3,000 to 5,000 miles
(on-highway), or the first 40 hours (off-highway):
On Highway Vehicles thereafter, oil changes should be done at the following
intervals:
1. Heavy-Duty Engine Oil:
Temperature Grade On Highway Service...........10,000-15,000 miles
Above + 10 F SAE 50 Off-Highway Service (Logging, dirt moving, mining,
Below + 10 F SAE 30 and associated operations)..500-750 hr.
Be sure to specify heavy-duty type MIL-L-2104B
specifications. The recommended oil change and inspection periods
are based on the average use and operating
2. Mineral Gear Oil: conditions that the unit may encounter. It is suggested
that the individual owner make a periodic lab analysis
Temperature Grade
of the lubricant to determine contamination based on
Above + 10 F SAE 90 the units specific operating conditions. With this data,
Below + 10 F SAE 80 the oil change and inspection periods can be better
Must be inhibited against corrosion, oxidation, and determined.
foam.
DRAINING THE OIL
3. MIL-L-2105B E.P. Oil, except sulfer-chlorine-lead
type: Draining is best accomplished after the vehicle has
Temperature Grade been operated briefly, allowing the oil to become warm
Above + 10 F SAE 90 and flow more freely. Remove both drain and fill plugs.
Below + 10 F SAE 80 Allow the housing to empty completely. Before the unit
is refilled, it should be thoroughly flushed with clean
Extreme pressure oils under some conditions might flushing oil or kerosene.
form carbon deposits on gears, shafts, and bearings,
which will result in transfer case malfunctions and If the unit is equipped with an oil pump, the lube oil
premature failure. It is suggested that if these filter should be replaced whenever the oil is changed.
conditions exsist, and E.P. oil is being used, a change The element is of the spin-on type. A film of clean oil
should be made to mineral gear oil or heavy-duty should be applied to the rubber gasket of the new
engine oil as recommended. element before installing. Do not overtighten.

Off Highway & Mining Equipment


REFILLING THE OIL
1. Heavy-Duty Engine Oil:
If the transfer case has been removed from the vehicle
Temperature Grade for service, it is best to refill the oil after the unit has
Above + 10 F SAE 50 been reinstalled into the vehicle.
Below + 10 F SAE 30
Be sure to specify heavy-duty type MIL-L-2104B Clean and replace the drain plug and fill the transfer
specifications. case with the appropriate oil with the vehicle on level
ground. Fill the transfer case to the level of the fill plug.
2. Special Recommendation: For extreme cold On transfer cases equipped with a proprtional
weather where temperature is consistently below 0F, differential, it may take some time for the oil to flow into
use SAE 20W heavy-duty engine oil meeting MIL-L- the main housing; therefore, it is necessary to fill the
2104B specifications unit to the level of the fill plug, wait a few minutes, and
top off the oil level. It may be necessary to do this
several times. The plug should be installed only after
the oil level has stabilized.
S0035.ai

Service Manual 21
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

ZF Torque Converters WSK Torque Converters


Independent oil circuit in convertor and clutch unit and
Lubrication Specs selector transmission systems.
HE TORQUE CONVERTOR and CLUTCH SYSTEM The ATF (Automatic Transmission Fluid) oil grades on
MUST BE filled with the SPECIFIED ENGINE OILS the following list may be used with all the WSK
or with AUTOMATIC TRANSMISSION FLUIDS Transmissions.
which conform to the following lubricant list; TE-ML NOTE! When using Dexron II products, particular
14. UNIT CAPACITY= APPROXIMATELY 21.5 care must be taken to ensure that the trade name and
QUARTS. the "D" number on the oil barrel correspond.
If ATF is not available, SAE 10W mono-grade engine
ADD oils conforming to the following specifications may
also be used: MIL-L-2104 C, or MIL-L-2104 D, or
MIL-L-46152 A, or
MIL-L-46152 B, or API-CC, CD, SC, SD, SE, or
OIL LEVEL
INDICATOR SF.
PLUG NOTE! When engine oils are used in place of ATF,
there may be a loss in shifting comfort because the
DRAIN
DRAIN shifting elements and friction are adapted to ATF.
S0032.eps A range of suitable engine oils are also included in the
following list.

TE-ML 09
APPROVED LUBRICANTS
VERSION FOR SERVICE FILL

Hydraulic power-assisted steering systems Automatic Transmission Fluid (ATF)


Hydrostatic steering systems - Dexron - IID / -IIE / -III
In-line boosters - Mercon -M
Oil pumps
Intermediate drives

TE-ML 14
APPROVED LUBRICANTS RECOMMENDED
VERSION ALTERNATIVES
FOR SERVICE FILL

Automatic Transmission Fluid (ATF) Engine oils


Ecomat 1. Base oil: mineral - API CD / CE / CF / SF / SG
1.1 - Dexron - IID - MIL-L-2104C / -D / -E
- MIL-L46152C / -D / -E
- Mercon - M -SAE 10W
1.2 - Dexron - III
- Mercon - M The shift elements and friction linings
are designed for use with ATFs. Using
engine oils may result in reduced shift
2. Base oil semi-synthetic/hydrocracked comfort.
- Dexron - IID
- Mercon - M

3. Base oil synthetic


3.1 - Dexron - IID / -IIE
- Mercon - M
(Not approved for transmissions with ratio 5.6-0.83/ 1.0)

3.2 - Dexron -III


- Mercon -M

22 Service Manual
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Hydraulic Pump Spline Product Data


Lubrication Optimoly Paste White T - white paste for clean
assembly work, prevents fretting corrosion (false
It is highly recommended prior to the installation of brinelling). Tight fitting components may be
any model/manufacture of hydraulic pump(s) that the disassembled without any difficulties even after many
drive spline be lubricated with a special pre-assembly years of operation.
grease. Schwing America recommends Optimoly Paste
Optimoly Paste White T - is excellently suited for all
White T. Following this procedure will add extended
assembly work and for base thin-film lubrication in all
life to the spline and related parts.
engineering areas.
Optimoly Paste White T is available in cartridge (p/n
Optimoly Paste White T - is also available as a spray.
30346107) or aerosol (p/n 30346108) from, and can
also be used in other pre-assembly work.

Typical Hydraulic Pump Spline


S0036.eps

Features Uses
inhibits fretting corrosion and false brinelling Assembly paste with universal application range
clean handling due to its clean handling and long-term separating
facilitates assembly and disassembly and lubrication effect. Superior to lack assembly
lubricants in performance test for a variety of
good separating effect for all types of contact
applications.
resistant to cold and hot water
Prevents fretting corrosion on bearing seals, spline
excellent rust protection even in salt water shafts, torque loaded connections.
white, almost colorless in thin layer
easy application (spray-without CFC)
temperature application range: -30C/-22F to
+250C/+482F
USDA-H2 approval

Service Manual 23
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Maintenance of Hydraulic side have internal leakage.


a. Remove the hose connections at the holding
Cylinders valve on the piston side.
b. If no oil runs out of the hose connections at the
holding valve, then that means the piston seal
WARNING is leaking, allowing oil to by-pass from the pis-

READ FIRST! S0101.ai


ton side of the cylinder to the rod side of the
cylinder.
c. If oil runs out of the hose connected to the
holding valve, then the holding valve on the
Warning! Danger of crushing! Before removing any
piston side is defective.
holding valve, the boom MUST be completely
supported so that removal of the valve will not cause To check the rod side holding valve
the boom to fall. If an extended boom is unsupported
Set the boom section to be checked in the retracted
when a holding valve is removed, oil will escape under
position, but do not completely retract. Make a mark on
high pressure, and can cause serious injury.
the piston side rod (with a felt tip pen) and observe if
Warning! Before removing any holding valve, hoses, there is any movement indicating leakage.
tubes or fittings, the engine or motor MUST be shut 1. If there is no movement of the cylinder rod,
off; the key removed; and a "DO NOT OPERATE" tag then piston sealing and holding valve are free from
attached to the door of the truck or in case of an electric internal leakage.
motor as the units prime mover, the electrical panel
MUST be "locked out" and "tagged out", preventing 2. If there is movement of the cylinder rod, then
any accidental power up. piston sealing and/or holding valve on the rod side
have internal leakage.
To check the piston side holding valves a. Remove the hose connecting at the holding
Set the boom into a horizontal position, but do not valve on the piston side.
completely extend the boom cylinder. Make a mark on b. If no oil runs out of the hose connections at the
the piston rod (with a felt pen) and observe if there is holding valve, then that means the piston seal
any movement indicating leakage. is leaking, allowing oil to by-pass from the rod
1. If there is no movement of the cylinder rod, side of the cylinder to the piston side of the
then piston sealing and holding valve are free from cylinder.
internal leakage. c. If oil runs out of the hose connections at the
2. If there is movement of the cylinder rod, then holding valve, then the holding valve on the
piston sealing and/or holding valve on the piston rod side is defective.

Holding valves mounted on a hydraulic cylinder (H.E.R. Valves)

S0100.ai

24 Service Manual
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.
Check Outrigger Cylinder for: 2. Check the lever position with the respective
1. Any missing or damaged parts, then check for cylinder movements. Test is to be carried out while
leakage of shut-off valves or cylinder seals. you have an operating oil temperature of
2. With no load applied to the outrigger cylinder, approximately 30 to 50 (86 to 122 F.)
close the shut-off valve and remove the hydraulic 3. Check the #1 boom down relief - Refer to Service
line between this valve, and the outrigger cylinder. Bulletin G-103-89 for checking this function.
Engage control valve for the outrigger cylinder to 4. Check boom slewing cylinders for:
level position, front to extend the outrigger a. Exterior damage of cylinders tubes and mount-
cylinder. If the valve is leaking, oil will run out of ing flanges.
the shut-off valve. b. Leakage and correct movement.
3. Slew the extended boom over the outrigger 5. Check the hydraulic tank for:
cylinder which is to be checked. Close the shut-off
a. Proper oil level and leakage
valve and remove the hydraulic line between this
valve and the boom control block. Mark the b. Contamination and oil purity. (if necessary,
cylinder rod (with a felt tip pen) and observe. If the take an oil sample for evaluation).
cylinder retracts and no oil runs out of the shut-off 6. Check boom operation speed (too fast / too slow),
valve, then the piston sealing is leaking. with unstressed boom as per Boom Time Chart.
7. Check remote control motions with all switch
Check the control block for:
functions and operation symbols.
1. Any missing parts (knobs, symbol of switching
8. Check remote control safety switch (emergency
levers, etc.), damaged or leaking parts, and
stop button) for proper operation.
cleanliness.

S0099.eps

Service Manual 25
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Lubrication Specs for Schwing equivalent with the below listed minimum
characteristics:
Placing Booms Base Type....................................................Lithium
Maintenance of the collar bearing, step bearing on NLG1 No. ..............................................................2
the shorter booms and rollix bearing for the slew- cSt @ 40 C (104 F) ........320 summer, 150 winter
ing gear of longer booms should be lubricated
Molybdenum disulfide.......................3% minimum
daily.
ASTM dropping point (degrees F..... 350 degrees F
The boom should be rotated while grease is applied
minimum
to achieve adequate lubrication.
The outriggers and boom should be greased
monthly. 2. All other bearings must be greased with a lithium
The grease recommendations are as follows: grease such as Mobil Grease HP, CM-S, or an
equivalent.
1. The bronze tower or column bushings must be
greased with a moly additive which has a minimum In order to ensure that the grease is uniformly
of 3% molybdenum disulfide. distributed on the bearing surface, you must lubricate
while slowly rotating the boom.
Greases such as Lubriplate Mo-Lith No. 2, Texaco
Molytex EP2, Mobil Grease CM-P may be used or an
Greasing zerks.eps L

32XLZerks above stack.eps L

S102.eps

26 Service Manual
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

Boom Inspections It is the concrete pump owner who is responsible for


completing scheduled inspections, either by himself or
The recommended CPMA (Concrete Pump whomever he authorizes to do so. Upon request
Manufactures Association) Safety Standard boom however, Schwing America will provide a qualified
inspection intervals are as follows: service person to aid pump owners in doing boom
First 5 years; every 2000 working hours, or at least inspections. To request a service person to do your
once per year. inspections, or to request guidebooks and inspection
Five to ten years; every 1000 working hours, or at forms for doing your own inspections, make a copy of
least once per year. the Inspection Request Form printed on the reverse
side of this page, complete the form and mail to
Ten years and older, every 500 working hours, or at Schwing America Inc. Attn.: Service Dept. Manager.
least once per year, whichever occurs first.
This schedule must be a planned schedule based on the
age of the unit.

S0162.eps

Service Manual 27
HOME PRINT
SERVICE TRAINING
Maintenance, Lubrication Schedules, etc.

BOOM INSPECTION REQUEST FORM

TODAY S DATE: / /

COMPANY:

STREET ADDRESS:

CITY: STATE: ZIP:

CONTACT: PHONE: ( )

LIST ALL MACHINES REQUIRING INSPECTION(S)/REPAIR(S) BELOW:

MODEL SERIAL NO. LOCATION

PLEASE FILL OUT AND FAX OR MAIL THIS FORM TO:

SERVICE DEPARTMENT
SCHWING AMERICA INC.
5900 CENTERVILLE ROAD
WHITE BEAR, MN 55127

FAX: 651/429-2112

SAISVC 018REV05/03/00

28 Service Manual
HOME PRINT
SERVICE TRAINING
Pumpkits

Pumpkits A11VO 60 Boom Pump with A10VO 28 Accumu-


lator Pump with Through Drive Tandem Mounted
4400 Stiebel Gearbox
Specifications Separate Cooling System(Standard on the S 45
SX)
2023-4 High Flow DN 30 S1-S2 Control Block
130/80 x 2000 Pump Kit
2525H-5
A7VO 107 Hydraulic Pumps
120/85 x 2500 Pump Kit
A10VO 28 Accumulator Pump with Through Drive
Two Tandem Mounted A11VO 130 Hydraulic
Standard 4194 Stiebel Gearbox
Pumps
Separate Cooling System
A11VO 60 Boom Pump with A10VO 28 Accumu-
High Flow DN 30 S1-S2 Control Block. lator Pump with Through Drive Tandem Mounted
4400 Stiebel Gearbox
2023-5
Separate Cooling System(Standard on S 45 SX)
130/80 x 2000 Pump Kit
High Flow DN 30 S1-S2 Control Block
Two tandem mounted A11VO 130 Hydraulic
Pumps
2525H-6
A11VO 60 Boom Pump with A10VO 28 Accumu-
120/85 x 2500 Pump Kit, A11VO 190 with A11VO
lator Pump with Through Drive tandem mounted
130 Hydraulic Pumps Tandem Mounted
4400 Stiebel Gearbox
A11VO 60 Boom Pump with A10VO 28 Accumu-
Separate Cooling System (Standard on S 45 SX) lator Pump with Through Drive Tandem Mounted
High Flow DN 30 S1-S2 Control Block 4400 Stiebel Gearbox
Separate Cooling System(Standard on S 45 SX)
2023H-6
High Flow DN 30 S1-S2 Control Block
120/80 x 2000 Pump Kit
A11VO 190 with A11VO 130 Hydraulic Pumps
Tandem Mounted

PUMPK I T PUMP DIFFERENTAL MAX. CONCRETE MAX. PRESS. MAX. THEORY STROKE
CYL. CYLINDER OUTPUT ON CONCRETE STROKES/MIN LENGTH
(Dia) (Diameter) ROD PISTON ROD PISTON ROD PISTON (IN.)
(cu. Yd/hr) (cu. Yd/hr) (psi) (psi)
500-18x 7 3.1 - 75 - 870 - 27 55
900 HDR 8 4.7 (120mm) 117 67 870 1565 30 17 63
1250 7 3.14 - 95 - 942 - 34 55
1200 HDR-20 8
1200 HDR-23 9
2023-4 9 5.1 (130mm) 170 - 1007 - 26 - 79
2023-5 9 5.1 (130mm) 209 - 1007 - 32 - 79
2023H-6 9 4.7 (120mm) 182 - 1233 - 28 - 79
2525H-5 10 4.7 (120mm) 181 - 1169 - 18 - 98
2525H-6 10 4.7 (120mm) 213 - 1169 - 22 - 98
750-18R 7 3.1 - 69 - 870 - 34 39

Service Manual 29
HOME PRINT
SERVICE TRAINING
Pumpkits

Change rams The stroke limiter is set to minimum output.


The operation stations (the rear control panel, the
When you begin to see not just cement dust in your cable remote box, the radio remote box) are
waterbox at the end of the day, but also small bits of disabled.
sand or even pebbles, it is time to change the rams. Three LEDs (oil cooler status, oil filter status, and
When changing rams, you will have to put your hands E-Stop status) on the rear control panel will be
in the waterbox on several occasions. In the past, we flashing. These LEDs will continue to flash as
instructed you to stop the engine each and every time long as the O I switch is in the I position.
before putting your hands into the waterbox, and we
Three LEDs (rear control, cable control, radio
still highly recommend this practice.
control) on the CPC will be OFF.
The local control on-off switch for the concrete pump
The concrete pump can only be actuated with the
and the manual handle for activating the concrete pump
Forward/Reverse switch to the right of the O I
are located in positions that make them impossible for
selector switch. This momentary switch is spring
you to activate while your hands are in the waterbox. If
loaded to the center position and activates only while it
however, another person has access to these devices, or
is being held in a forward or reverse position.
the ram change operation panel, the danger of
accidental activation increases. While operating in ram change mode the pistons will
move at the slowest possible speed.

ramctrl.eps

If you insist on changing rams with the


motor running, you must take the following
precautions to avoid amputation of hands,
arms, and fingers:
Do not use the remote controller for this
procedure! Unplug it, and store it.
Do not allow anyone else at the rear control panel
or the forward/reverse hand valve when you are
rd
changing rams. The chances of accidental
s e Forwa
r
amputation are greatly increased if more than one Reve
person is around. You will have fewer distractions
when you are alone. If someone approaches you
when you are changing rams, stop working until
the person leaves.
ps
tch.e
Select the ram change mode OIsw

Select local control on the rear control panel and then I = On


O = Off
select I (ON = ram change mode) with the O I selector
switch located on the ram change station (Figure 1). Figure 1
When I (ram change mode) is selected the following Ram change station on rear boom
things happen automatically: cradle A frame (current
The diesel engine R.P.M. will return to idle production)

30 Service Manual
HOME PRINT
SERVICE TRAINING
Pumpkits

Remove the old rams.


Use the following procedure to remove the old rams. dogbone1.eps

1. Close the shutoff valve (also known as the ball


cock and quarter turn valve). The shut-off valve is
located on the concrete pump control block (Figure
2). This gives you control over the direction of
travel of the differential cylinders.

Soft switch
shutoff valve

Figure 3
Retract the drivers side rod into the
waterbox all but about an inch and a half
5. A 55mm open end wrench and a 24 - 30 mm box
end wrench were supplied with the unit; you will
need them for this step. Locate the 55mm wrench
Concrete pump on the dog bone to hold the assembly from turning.
39
shutoff valve hif
low
.ep You can rest the handle against the side of the
s
waterbox (Figure 4). Unscrew the 4 M20 bolts that
hold the assembly together.
Figure 2
Concrete pump shutoff valve
dogbone2.eps

2. Drain the waterbox. Remove the waterbox cover


and the bolt down grate.
3. Retract the driver side differential rod almost all
the way into the waterbox (Figure 3). Leave about
1.5 inches of travel, which will allow you to
remove the spacer coupling (dogbone).
4. Push the emergency stop button on the operators
panel. Stop the engine, and put the key in your
pocket. (Stopping the engine before putting your
hands in the waterbox is mentioned at every appro-
priate spot.)

Figure 4
Remove the bolts from the dogbone

6. Be sure all personnel and tools are out of the water-


box, then start the engine. Release the emergency
stop button. Finish retracting the driver side rod
into the waterbox. The dogbone will fall out.
7. Push the emergency stop button on the operators

Service Manual 31
HOME PRINT
SERVICE TRAINING
Pumpkits

panel. Stop the engine, and put the key in your


pocket. ramflang.eps

8. Remove the dogbone from the waterbox (Figure


5).
.

dogbone3.eps

Figure 6
Removal bolt grooves on flanges

11. Start the engine. Release the emergency stop but-


ton, and slowly retract the cylinder rod until the
ram is clear of the material cylinder (Figure 7).
Figure 5
Remove the dogbone ram install fig 3

9. Start the engine. Release the emergency stop but-


ton. Slowly extend the cylinder rod until it just
contacts the rubber ram flange.
NOTE!
Be careful not to drive the rubber ram into
the material cylinder. If it happens that you
accidentally knock the ram into the material
cylinder so far that you cant reach it, you
Figure 7
will have to remove it by knocking it out
Slowly bring the ram into the
from the Rock Valve end of the unit. Call the
waterbox
Schwing America Service Department at
(651) 429-0999 for instructions on this pro- 12. Push the emergency stop button on the operators
cedure. panel. Stop the engine, and put the key in your
10. Push the emergency stop button on the operators pocket. Remove the nut and bolt, and the ram will
panel. Stop the engine, and put the key in your be free to come out of the waterbox.
pocket. There is a groove in the ram flange that will 13. Clean and inspect the bolts and cone washers, the
line up with a groove in the cylinder flange. An dogbone, and the cylinder flange. Replace any
M12 x 45 bolt with nut will drop into this groove damaged or worn parts with new ones.
and allow you to pull the ram out. The fit should be Install the new rams.
snug, but there is no need to tighten the nut with
tools (Figure 6). (Note that the ram flange and cyl- Use the following procedure to install the new rams.
inder flange are shown outside of the waterbox for 1. Apply Loc-tite primer (or equivalent) to the M20
clarity of the illustration.) bolts. Allow the primer to dry.
2. While the primer is drying, apply a liberal coat of
clean grease to the new rams. There is no such
thing as too much grease here, because the excess

32 Service Manual
HOME PRINT
SERVICE TRAINING
Pumpkits

will be wiped off by the material cylinders during 8. Start the engine. Release the emergency stop
installation. button. Slowly move the cylinder down to where
3. With the engine still stopped, hold the new ram up the flange butts up to the dogbone. Be careful not
to the cylinder flange. Line up the grooves, and to go too far! (Figure 9).
drop your nut and bolt into place to hold the assem-
bly together. Again, you should only tighten the nut
finger tight. ram install fig 3

4. Start the engine. Release the emergency stop but-


ton. Slowly extend the cylinder until the ram is
installed in the material cylinder but the mounting
flange is still exposed enough to remove the nut
and bolt (Figure 8).

ram install fig 2

Figure 9
Slowly move the cylinder to meet
the dogbone

9. Push the emergency stop button on the operators


panel. Stop the engine, and put the key in your
pocket. You may have to slightly rotate the
Figure 8 dogbone to align the bolt holes with the cylinder
Slowly push the new ram into the flange. When aligned, coat the two remaining M20
material cylinder bolts with Loc-tite and install, including the cone
washer sets. Once all four bolts are started, you
5. Push the emergency stop button on the operators may tighten the bolts to the torque specification for
panel. Stop the engine, and put the key in your M20 10.9 bolts (420 ft/lbs).
pocket. Remove the nut and bolt.
10. Repeat all steps in the Remove the old rams
6. Start the engine. Release the emergency stop but-
procedure and Install the new rams procedure for
ton. Slowly retract the rod again until there is room
the passenger side ram.
to install the dogbone.
7. Push the emergency stop button on the operators 11. Open the shutoff valve. Note that the unit will not
panel. Stop the engine, and put the key in your cycle with this valve closed.
pocket. Apply Loc-tite 242 or equivalent to two of
the M20 bolts. Place the dogbone up against the
flange of the new ram. Install two of the M20 bolts
(with Loc-tite) and the cone washer sets. At this
time finger tighten only.
NOTE!
It is important to install the dogbone against
the new ram first, not the cylinder flange.
This gives you an extra 6 to 8 inches of
safety margin when you extend the cylinder
to meet the dogbone. If you attach to the cyl-
inder flange first, chances are good that you
will accidentally knock the new ram into the
material cylinder so far that you wont be
able to reach it.

Service Manual 33
HOME PRINT
SERVICE TRAINING
Pumpkits

Material Cylinder Alignment


The material cylinders are considered worn out when
the inside diameter has grown 3 millimeters beyond the
specification for new. For example, a 2023 has 230 mm
material cylinders. When the inside diameter reaches
233 mm, they are worn out. With 150s they are worn
out at 153, etc. Normally, it is the end attached to the
rock valve that wears out first, because it sees the most
concrete. The waterbox end may show little or no wear,
because that end never experiences concrete. For this
reason, the material cylinders were designed to be able
to rotate end for end. That way you can move the worn
out end to the waterbox and the little-worn end to the
concrete valve for double the life. If you notice
excessive amounts of grout in the waterbox or
accelerated wear on the rams, it may be time to rotate
the material cylinders. Concrete Pump forward Concrete Pump reverse
For units without the Ram Change Station, please S0169.eps

reference Schwing Service Bulletin #G-102/88.


Contact the Schwing America Service Department at Figure 12
(651) 429-0999 if you need a copy of the bulletin. Ram Change Mode switch
b. Place the Concrete Pump Forward/Reverse
Changing the Material Cylinders switch in the forward position. The pistons
1. Extend and jack the outriggers. will move at the slowest possible speed. Hold
the switch until the piston reaches bottom dead
2. Lift the placing boom enough to clear an
center (B.D.C.) position.
obstructions and slew it off to the side.
3. Remove both rubber rams from the differential
cylinders in the normal manner. See Remove the
old rams on page 31.
4. Retract the first differential cylinder rod
completely:
a. Select local control on the rear control panel
and then select I (ON = ram change mode)
with the O I selector switch located on the ram
change station
NOTE!
The concrete pump can only be actuated
with the Forward/reverse switch to the right Figure 13
of the I O selector switch. For more infor- B.D.C. position
mation see Select the Ram Change Mode
on page 30. c. The rod will move into the end position and
stop. Immediately release the Pump Forward/
reverse switch on the Ram Change mode sta-
tion. This will place the S1 spool into the neu-
tral position. (otherwise the machine will go
into a high pressure situation)
d. Stop the engine. Put the key in your pocket.

34 Service Manual
HOME PRINT
SERVICE TRAINING
Pumpkits

5. In order to move the second piston to the bottom Rock Valve section of this book for rebuilding
dead center position without re-extending the first instructions.
cylinder, we must drain out the rocking oil. 12. Support each material cylinder with the lifting
NOTE! device. Remove the bolts at the waterbox. If an
When opening the hydraulic system, which impact wrench is used, you must use an impact
we have to do to drain the rocking oil, make socket and wear eye protection.
certain of absolutely clean conditions. 13. Detach the material cylinders and remove in a
6. To drain the rocking oil rod side: downward direction.
a. Disconnect one end of the rocking oil hose and
NOTE!
hold the hose into a clean container.
Take care not to damage hoses and tubes
b. Start the engine. that may be positioned under the material
c. Select I (ON = ram change mode). Put the S1 cylinders
in reverse mode by holding the Pump Forward/
Reverse switch in the reverse position. When
the piston reaches bottom dead center (B.D.C.)
position. The rocking oil will be expelled,
through the hose.
\

S0168.eps
Figure 14
Draining the rocking oil
7. Stop the engine Figure 15
8. Remove the hopper and outlet piping from the Removing bolts at the waterbox
concrete valve 14. Remove the split rings and mounting flanges. If
9. Carefully support the differential cylinders spacing rings are used on the unit, remove them at
cylinders to avoid unintentional movement of the this time.
pumpkit after the material cylinders have been
removed. for example, wedge wooden blocks
between the cylinders and across of the subframes.
10. Mark for identification, then remove the hydraulic
hoses from the rock slewing cylinder.
NOTE!
Plug the open hydraulic lines with dead
plugs.

11. Remove the entire rock valve assembly. See the

Service Manual 35
HOME PRINT
SERVICE TRAINING
Pumpkits

S0171 S0172.eps
Figure 16
Removing the Split Rings Figure 17
15. Clean, check and grease the mounting parts and all Grease new o-rings
mounting surfaces at the waterbox and rock 19. Carefully slide a pre-completed material cylinder
housing. into the waterbox, and give a ballpark alignment.
16. Clean the mounting surfaces of the new material 20. Screw in the mounting bolts and washers and
cylinders thoroughly, remove primer, and grease. tighten crosswise, using the torques specified in the
17. Install mounting flanges and split rings. At this table.
time mount spacing rings removed in step 12, if
any
NOTE!
Please remember not to interchange the
flanges and split rings, and spacing rings
from the waterbox to concrete valve end.
The cylinder themselves can go either way.

18. Grease the new o-rings and insert into the lead in
rings of the waterbox

S0168.eps

Figure 18
Tightening bolts at the waterbox

36 Service Manual
HOME PRINT
SERVICE TRAINING
Pumpkits

25. To visually inspect the alignment, put a trouble


light in the waterbox, at the opening to the cylinder
being aligned. Be careful with fingers and hands in
Bolt Step 1 Step 2
the waterbox. Put the trouble light in the waterbox,
M16 8.8 75 ft/lbs 155 ft/lbs then remove your hand BEFORE proceeding to the
next step.
M16 10.8 110 ft/lbs 220 ft/lbs

M24 8.8 260 ft/lbs 525 ft/lbs

21. After both material cylinders have been installed,


the alignment must be checked.
22. Re-attach the rocking oil hose that you removed in
step 6. After the rocking oil loop is in place, start
the engine. Pump Forward/Reverse switch in the
reverse position. The passenger side differential
cylinder rod should extend as the rocking oil loop
is refilled. When the rod stops moving, the loop is
filled. Release the Pump Forward/Reverse switch
23. Stop the engine. Put the key in your pocket.
24. Mount alignment tool on a differential cylinder
rod. See chart on page 39 for the proper material
cylinder alignment tool part number and size.
Figure 20
Putting trouble light in waterbox
26. Put the Pump Forward/Reverse switch in the
forward position. Look into the material cylinder
from the valve end. The gap between the alignment
tool and the cylinder wall should be seen as even
rays of light. When the cylinder gets fully
extended, the alignment tool may drop a small
amount or even barely touch the material cylinder
wall

S0174.eps

Figure 19
Mount the alignment tool, to the differential
cylinder rod.

Service Manual 37
HOME PRINT
SERVICE TRAINING
Pumpkits

Even rays around alignment tool


MOUNTING
BOLTS

Figure 22
Mounting bolts on waterbox
28. Grease new o-rings and insert in the valve housing.
29. Carefully slide the valve housing onto the material
cylinders, and rest the valve housing on the
Uneven rays around alignment tool machine frame.
30. Bolt the valve housing and material cylinder
flanges together making sure that the alignment is
Figure 21
being maintained.
NOTE! 31. Bolt the valve housing to the machine frame.
If the alignment tool should contact the cyl-
inder wall at any time, release the Concrete 32. Check alignment with the tool once more, by using
Pump Forward/Reverse switch immedi- the Ram Change Mode switch.
ately! Damage may occur to cylinder wall. NOTE!
If a squeaking sound indicates the align-
27. If, for example, the alignment tool contacts the ment tool is dragging on the material cylin-
cylinder on the lower side, loosen the mounting der, turn off the pump IMMEDIATELY!
bolts at the waterbox a little bit, then tighten the
LOWER bolts first. This will lower the bottom of 33. If there is no dragging, you may proceed to step 36.
the material cylinder. When the alignment is close, If dragging does happen, repeat the visual checks.
tighten the top bolts and recheck the alignment. 34. Loosen the bolts on the material cylinders and
When the alignment is within specification, the valve housing, and at the machine frame, and
alignment tool will travel the entire length of the repeat the alignment procedure.
cylinder without touching the cylinder wall. If the 35. Check the mounting and shimming of the pump kit
alignment tool is not always located exactly in the and its mounting to the pump kit frame.
middle of the cylinder during the travel, but DOES
NOT TOUCH, then realignment is not necessary. 36. Tighten all bolts.
Minor misalignments are compensated for with the 37. Complete the reassembly of valves, and install the
rubber ram. Repeat procedure for the other rubber rams.
cylinder. 38. Reopen the 1/4 turn valve.
NOTE!
If proper alignment cannot be achieved oth-
erwise, tightening torques may be exceeded
by 10% over the charts specs. If further
alignment problems persist, please contact
the Schwing Service Department.

38 Service Manual
HOME PRINT
SERVICE TRAINING
Pumpkits

Rod Diameter

Material Cylinder Diameter

Ordering Chart
Rod Cylinder Item
Diameter Diameter Number Pumpkit Model Number

50 mm 150 mm 30379547 450, 500, BP 750-15


50 mm 180 mm 30339165 WP 750-18, WP 1000-18, BP 1000-18
55 mm 150 mm 30379532 250-15
55 mm 180 mm 30379533 350-18, 500-18, 650-18
63 mm 150 mm 30379534 650-15
63 mm 180 mm 30379535 580-18, 600-18, 650-18, 601-18, 900-18, 901D-18
63 mm 200 mm 30379536 800-20, 801-20, 901-20
80 mm 150 mm 30379541 3000-15, 3001-15, 5000-15
80 mm 150 mm 30379544 5000-15
80 mm 180 mm 30379548 900-18, 2000-18, 3000-18, 3001-18, 4000-18, 5000-18,
80 mm 200 mm 30379542 900-20, 1200-20, 1201-20, 2000-20, 3000-20, 3001-20, 4000-20,
5000-20, 8000-20, 2020
80 mm 230 mm 30379543 1200-23, 1201-23,2000-23, 4000-23, 5000-23, 8000-23, 2023
85 mm 180 mm 30379538 4000-18
90 mm 180 mm 30379549 8000-18HPR, 4000-18
85 mm 200 mm 30379540 1001-20
90 mm 200 mm 30379550 4000-20
85 mm 230 mm 30379539 1001-23, 4000-23
85 mm 250 mm 30364756 2525 S0044.eps

Figure 23
Alignment Tool Chart

Service Manual 39
HOME PRINT
SERVICE TRAINING
Pumpkits

Pumping on piston side When changing the hoses from the rod side port to the
piston side port, you must cross them. This keeps the
Piston side pumping changes your concrete pump from machine in the same sequence of events as when it is
a low-pressure, high-volume machine into a high hooked up for rod side pumping. Failure to cross the
pressure, low-volume machine. This would be handy, hoses will result in pumping in reverse whenever you
for example, to pump long distances horizontally or select forward.
vertically.
When you have finished with the need for piston side
Piston side operation dramatically raises the maximum operation, change it back to rod side immediately.
pressure on the concrete. For this reason, it is crucial
When you are configured on the piston side, the safety
that your entire material delivery system be rated to
rules for the following topics become even more
handle the available pressure and be maintained in like-
important:
new condition. Remember that pipe wall thickness
wears with each yard of concrete pumped. Inspect the Opening lines under pressure
wall thickness regularly. The maximum material Sucking back plugged lines before opening
pressure available on the piston side depends on which Pressure-handling capacity of pipes, hoses, and
differential and material cylinders you purchased with clamps in your delivery system
your unit. The maximum material pressure is recorded The dangers of blockages
on the main ID tag.
All of these items are covered in the Safety Manual.
To convert your machine to piston side operation, you Understand the rules and live by them.
must have some additional hoses and fittings, plus the
tools to install them.
Loosen for Add dead
rotation plugs
(1200s only)
This hose
1200s only

Add hose
and fittings
to each side

Loosen for Loosen for


rotation rotation
rod/piston change.eps

Loosen for
rotation

Rod Side Changes Piston Side


Configuration Configuration

40 Service Manual
HOME
PRINT

ASSEMBLY INSTRUCTIONS FOR SEALING GLAND IN THE DIFFERENTIAL CYLINDERS

The following steps must be followed to ensure proper installation of the sealing glands (rod packings) on
differential cylinders:

1. Measure the distance from the bottom of the


bore on the guide bushing to the outside
machine surface of the cylinder housing where CYLINDER BARREL

the tension ring bolts to it (Figure 1, Dimension A


A). TENSION RING
SPACING DISK

GUIDE BUSHING

SCRAPER
PISTON ROD
SEALING GLAND SET
Sealing Gland Replacement

FIGURE 1

2. Set the packing set (unwrapped) on a at


Product: THE DIFFERENTIAL CYLINDERS

surface and set the tension ring on top of the


packing set. Measure the distance from the SCRAPER

at surf ace to the bottom side of the tension


TENSION RING
ring that mates to the cylinder housing when SPACING DISKS
AS REQUIRED

Service Manual
assembled (Figure 2, Dimension B).
SAIE STANDARD

B SEALING GLAND SET


3. Subtract Dimension A from Dimension B. The
SERVICE TRAINING

difference is the amount of thickness in


Subject: ASSEMBLY INSTRUCTIONS FOR SEALING GLAND IN

spacing disks required between the cylinder


housing and tension ring for assembly. FIGURE 2
Sheet
By: T.A.

The packings must never be under compression from the tension ring. If the packings are under
compression from the tension ring, it is possible that the cylinder rod may become scored after a short
1

period of time during operation. Therefore when Dimension A is subtracted from Dimension B, the
Date: 12-19-95

dimension of the spacing disks must equal the difference with a tolerance of minus nothing, plus 1 mm or
No.: SAIE - 5221

of 1

.039 inch.
Rev.: D

41
Pumpkits
HOME PRINT
SERVICE TRAINING
Pumpkits

Shimming the Differential Tension Ring


Cylinders
Determining the proper shim size
When ever you rebuild differential cylinders, it may be
necessary to add shims to the tension ring. Adding
shims protects the cylinder rod from the cheveron seals
in the event the cheveron seals expand. Use the
following procedure to determine the proper amount of
shimming necessary. Cheveron Seal Set

Dimension A
Using a caliper measure the distance from the top of Tape
the bushing down to the bushing seal recess.
Figure 25
See Figure 1.
Compacting the Cherevon seals
Use the caliper to measure the distance between the top
and the bottom of the compacted cheveron seals.
See Figure 3.

Dimension A = 57.12 mm

57.12 mm is the depth of the guide Dimension B = 57.4 mm


bushing seal recess.

Tension Ring
Bushing Seal Recess

Bushing
Dimension B

Cheveron Seal Set

Dimension B

Figure 24
Measuring for dimension A
Figure 26
Dimension B Measuring for dimension B
Leave the tape around the cheveron seals to hold them
into place. On a solid flat surface place the Tension ring
on top of the cheveron seals. This will compact the
cheveron seals to the proper size. See Figure 2.

42 Service Manual
HOME PRINT
SERVICE TRAINING
Pumpkits

Formula

A should equal B
B - A = shims required

In this example:
57.40
- 57.12
.28 mm (.011")

Refer to SAIE 5221

Figure 27
Formula for determining shim size
In this example, we would need to add 1 - 0.5mm shim
to the Tension ring. This will ensure that the cheveron
seals will not expand, thus preventing wear on the
cylinder rod. See Figure 4
NOTE!
A maximum of 5 shims can be used.
NOTE!
Dimension B can never be greater than
dimension A or cylinder rod damage can
occur.

Service Manual 43
HOME PRINT
SERVICE TRAINING
Pumpkits

44 Service Manual
HOME PRINT
SERVICE TRAINING
Hydraulic Pumps

Hydraulic Pumps Schwing, we route signals to the pump from the


hydraulic stroke limiter and on single circuit units with
the dampener. The effect of these devices is to tell the
pump to put out a different amount of hydraulic oil per
Hydraulic Pump Drive revolution, to accommodate the pump operator. Your
All hydraulic pumps, such as the one for the concrete unit may be equipped with an A7VO pump or an
pump, placing boom, and agitator, are mounted on the A11VO pump.
distribution gearcase. When you are driving the truck,
the power of the truck engine is transmitted through the
truck transmission, through a propeller shaft, through
the bottom of the distribution gearcase, through another
propeller shaft, and into the rear end of the truck. When
you are operating the unit, the distribution gearcase
interrupts the power to the rear end of the truck and
transmits it to internal gears that turn the hydraulic
pumps. Changing between travel and pumping modes
is accomplished by means of a power takeoff (PTO)
switch in the truck cab

Placing boom hydraulic pumps A7VO

The hydraulic pumps for the placing boom is a variable


displacement pump, either a swash plate (A11VO), or
an axial piston (A7VO). Both have load sensing control
and feed all of the following components:
the hydraulic cylinders on the boom sections
the hydraulic cylinders on the outriggers
the hydraulic motor for the boom slewing gear
the hydraulic motor for the water pump
the hydraulic motor of the compressor (optional
equipment)
The directional control valves for each of the afore
mentioned circuits are incorporated into control blocks
and equipped with hand levers. In addition, the control
block for the boom functions have electric over oil
piloting for operation via remote control.
A11VO
S103.eps
Concrete pump hydraulic
pumps
The hydraulic pumps for the concrete pump circuit are
bent axis, variable displacement piston pumps (A7VO)
or a swash plate pumps (A11VO). They are horsepower
controlled, which means that as pressure rises, the flow
decreases, so the power consumption remains constant.
We use this type of pump so the truck engine will not
bog down under hard pumping conditions. The pumps
also accept external signals for control of the output. At

Service Manual 45
HOME PRINT
SERVICE TRAINING
Hydraulic Pumps

Hydraulic Pump Locations

PumpKit Pumps

Proportional Boom Pump

Accumulator Pump
Agitator Pump
Oil Cooler Pump Stiebel 4194

PumpKit Pumps

Proportional Boom Pump

Accumulator Pump

Oil Cooler Pump

Agitator Pump

Stiebel 4400
S0064.eps

46 Service Manual
HOME PRINT
SERVICE TRAINING
Hydraulic Pumps

Fixed Displacement Pump the fixed displacement of the pump. The pump is
suitable for use in mobile and industrial applications.
A2FO
Fixed displacement axial piston pumps of bent axis
design for use in hydrostatic drives in open circuits.
The output flow is proportional to the input speed and

Service Manual 47
HOME PRINT
SERVICE TRAINING
Hydraulic Pumps

Rexroth/Hydromatik Model A7V


Series 2 The flow is proportional to the drive speed and the
displacement and is steplessly variable at constant
Note: After replacing any A7VO hydraulic pump, the drive speed.
unit must be bled before start-up. Comprehensive program of control devices for every
If there is a U-Port on the pump, this is the control and regulating function.
bearing flush and that is where the pump should be
bled from.
High performance rotary group with well-proven
If there is not a U-Port, the pump should be spherical control area offering the following
bled from the highest case drain. advantages: self-centering, low peripheral speed, high
Variable displacement pump, axial piston, bent axis efficiency.
design, fir hydraulic transmissions in open circuits.

48 Service Manual
HOME PRINT
SERVICE TRAINING
Hydraulic Pumps

Constant Pressure Control DR Constant Horsepower Control LV


The constant pressure control maintains the pressure in The constant HP control flow in relation to pressure,
thereby maintaining hydraulic power constant.
a hydraulic system constant within its control range in
spite of changing pump flow requirements. The
variable pump supplies only the volume of fluid
required by the services. Should operating pressure P = Power [kW]
pQ
exceed the set pressure, the pump is automatically P= = constant p = Pressure [bar]
600
swivelled back to a smaller angle and the deviation in
control corrected. Q = Flow [l/min]
The required pressure is set either direct at the pump
(valve built-in, standard model) or at the separate (Provided that the drive speed is constant)
sequence valve for the model with remote control.
Setting range from 50 to 350 bar.
Setting range for remote control 50 to 315 bar. Operating pressure acts on a pilot piston, causing it to
press on a set of springs. If the hydraulic force exceeds
the spring force, pilot oil is fed to the adjusting piston,
which swivels the pump back to a smaller angle and
Setting range from 50 to 350 bar. Setting range for remote control 50 to 315 bar
therefore a smaller flow.
max. 10 bar

P max
350

315 Commencement of control: 50 bar min.


300
150

A (B) R
Operating pressure PB (bar)
setting range

200
G

100

50

0
Flow Q (L/min.)

S
Figure 28 - Pressure Setting Ranges Figure 30 - Schematic of a A7V Variable
Displacement Pump
Summation HP control is made possible by means of
throttles via port G.
A (B) R
T

X3 A

S T

Figure 29 - Schematic of a A7V Variable


Displacement Pump With Remote Control

Service Manual 49
HOME PRINT
SERVICE TRAINING
Hydraulic Pumps

Auxiliary Equipment: Stroke Limiter

A (B) R

X2
G

X1
S

Figure 31 - Schematic of a A7V Variable


Displacement Pump With Hydraulic Stroke Limiter
By Means of a mechanical or hydraulic stroke limiter,
the maximum displacement can be infinitely varied or
limited. Adjusting range from Vg max to Vg min.
A pilot pressure (port X1) of at least 10% of the
operating pressure is required for the hydraulic stroke
limiter. Maximum permissible pressure at port X1 =
200 bar (for all sizes).
If it is required to limit the flow at an operating
pressure < 50 bar, then a boost pressure of minimum 50
bar must be applied at port X2 (at port X1 then,
minimum 10% = 5 bar)

Q min

Q max
S0098.eps

Figure 32 - Q Min and Q Max Locations on a A7V


Variable Displacement Pump

50 Service Manual
HOME PRINT
SERVICE TRAINING
Hydraulic Pumps

Rexroth/Hydromatik Model A7V Comprehensive programming of control devices is


available. The robust taper roller drive shaft bearings
Series 6 are designed to give long service life. Output flow is
Variable pump with axial tapered piston rotary group of proportional to drive speed and pump displacement is
bent axis design, for open circuit hydraulic drives. This steplessly variable between maximum and zero.
pump is suitable for mobile applications.

0
25 -

Service Manual 51
HOME PRINT
SERVICE TRAINING
Hydraulic Pumps

LR Constant Power Control


The constant power control controls the output volume
of the pump in relation to the operating pressure so
that, at a constant drive speed, the preset drive power is
not exceeded.

V = constant
p B = operating pressure
pB g
V = pump displacement
g

Optimum power usage is obtained by accurately following the


power hyberbola

350
Operating pressure p B (bar)

300
A (B) R
250
220 bar
200
Adjust. range
G
150
Start of control
100
50 50 bar
0
0 0.2 0.4 0.6 0.8 1.0
V Displacement V
g min g max

Figure 33 - A7VO Variable Displacement Output


Chart S
Operating pressure applies a force on a piston within Figure 34 - Schematic of a A7VO Variable
the control piston on to a rocker arm. An externally Displacement Pump
adjustable spring force is applied to the other side of
the rocker arm to determine the power setting. LRH Constant Power Control With
Should the operating pressure exceed the set spring Hydraulic Stroke Limiter
force, the pilot control valve is operated via the rocker
arm, allowing the pump to swivel towards zero output.
This in turn reduces the effective moment on the arm of X1
the rocker, thus allowing the operating pressure to rise
in the same ratio by which the output flow is reduced Y3
(Vg = constant). A
When the pump is bypassing at zero pressure, a spring A1
ensures that the pump is swivelled to max. displace-
ment (Vg max).l

S A7VO-107 LR

Figure 35 - Schematic of a A7VO Variable


Displacement Pump With Hydraulic Stroke Limiter

52 Service Manual
HOME PRINT
SERVICE TRAINING
Hydraulic Pumps

Variation: Hydraulic Stroke Limiter (H...)


The hydraulic stroke limiter allows the maximum
displacement to be infinitely varied or limited as
required. Control range Vg max to Vg min. The
displacement is set by means of the pilot pressure
applied at port X1. The hydraulic stroke limiter is
overridden by the constant power control, i.e. below the
power curve (power hyperbola), displacement is
adjusted in relation to pilot pressure. If the set flow or
the operating pressure is such that the power curve is
exceeded, the constant power control overrides the
stroke limiter and reduces displacement until the power
hyperbola is restored.

H1/H5 (Negative Control Function): Vg max


to Vg min
As pilot pressure increases the pump swivels towards Horsepower
lower displacement. (Starting position at zero pressure: Adjustment
Screw
Vg max).
Figure 37 - Horsepower Adjusting Screw on a A7VO
Start of control: adjustable between 4 and 15 bar. Variable Displacement Pump
H1 pilot pressure increase (Vg max - Vg min) _____ p = Q min
25 bar.

40
35

0
30

25 -
25
pilot press. PSt in bar

20
setting range

15
Q max
10

4 Figure 38 - Q Min and Q Max on a A7VO Variable


Displacement Pump
0 0,2 0,4 0,6 0,8 1,0
Vg min Vg Vg max
Displacement Vg max DR Constant Pressure Control
The constant pressure control maintains the pressure in
Figure 36 - Displacement Output Chart a hydraulic system constant within its control range in
spite of changing pump flow requirements. The
variable pump supplies only the volume of fluid
required by the consumer. Should operating pressure
exceed the set pressure, the pump is automatically
swivelled back to a smaller angle and the deviation in
control corrected.
In un-operated (zero pressure) condition, the pump is
swivelled to its starting position (Vg max) by means of
a control spring.
Setting range from 50 to 350 bar.

Service Manual 53
HOME PRINT
SERVICE TRAINING
Hydraulic Pumps

Setting range from 50 to 350 bar. Setting range for remote control 50 to 315 bar

max. 10 bar
P max
350

315
300
150
Operating pressure PB (bar)
setting range

200

100

50

0
Flow Q (L/min.)

Figure 39 - Pressure Setting Ranges

Variation: Remote constant pressure


control (G)
A sequence valve with subplate takes over the pressure
control function. The valve is mounted separate from
the pump, and the piping length should not exceed 5 m.
High pressure is supplied from the pump to the valve
via part A1, and the valve control oil is fed back to the
pump via Port X, causing the pump to swivel back
towards Vg min. Port T of the sequence valve and T1,
the pilot drain from the pump must be connected back
to tank (cooler). Pressure may be set between 50 and
315 bar.
Sequence valve: DZ5DP2-1X/315 Y SO21 (Id.-Nr. 154
869)
Subplate: G 115/1 (Id.-Nr. 153 138)

P regulator
High pressure filters
X
20
A bar P
A1
290
bar

P
A T

X3

Boom hydraulic pump

Figure 40 - Schematic of a A7VO Variable


Displacement Pump

54 Service Manual
HOME PRINT
SERVICE TRAINING
Hydraulic Pumps

Rexroth/Hydromatik Model transmissions in open loop circuits. Flow is


proportional to the drive speed and the displacement.
A10VO By adjusting th position of the swashplate it is possible
Variable displacement axial piston A10VO of to smoothly vary the flow.
swashplate design is designed for hydrostatic

Pressure Cut-off Screw S0081.eps

Service Manual 55
HOME PRINT
SERVICE TRAINING
Hydraulic Pumps

DR Pressure Control
The pressure control serves to maintain a constant
pressure in the hydraulic system, within the control
range of the oump. The pump therefore supplies only
the amount of hydraulic fluid required by the actuators.
Pressure may be smoothly set at the pilot valve.

Figure 41 - Static Operating Curve

Figure 42 - Schematic of A10V0 Variable


Displacement Pump

56 Service Manual
HOME PRINT
SERVICE TRAINING
Hydraulic Pumps

Rexroth/Hydromatik Model pump is available with a through drive to accept a gear


pump or a second axial piston pump up to the same size
A11VO (100% through drive).
The A11VO is a variable displacement pump of axial
piston swashplate design for use in open circuit Output flow is proportional to drive speed and pump
hydrostatic drives. displacement and is steplessly variable between
Designed principally for use in mobile applications. A maximum and zero.
wide variety of controls are available. Setting of the
constant power control is possible via external
adjustments, even when the unit is operating. The

Service Manual 57
HOME PRINT
SERVICE TRAINING
Hydraulic Pumps

p B = operating pressure
pB V = constant
g
V = pump displacement
M A G T1 R T2
g

Optimum power usage is obtained by accurately following the


power hyberbola

350
Operating pressure p B (bar)

300 320 bar

250
220 bar
200 Setting range
150 Start of control
100 Vg max Vg min
50 50 bar
0
0 0.2 0.4 0.6 0.8 1.0
V Displacement V
g min g max

Figure 43 - A11VO Variable Displacement Output


Chart s M1
The constant power control controls the output volume
of the pump in relation to the operating pressure so Figure 44 - Schematic of a A11VO Variable
that, at a constant drive speed, the preset drive power is Displacement Pump
not exceeded.
35
30
Operating pressure applies a force on a piston within
25
the control piston on to a rocker arm. An externally
20
adjustable spring force is applied to the other side of
pilot press. PSt in bar

15
the rocker arm to determine the power setting.
setting range

10

4
Should the operating pressure exceed the set spring
force, the pilot control valve is operated via the rocker 0 0,5 1,0
Vg min Vg Vg max
arm, allowing the pump to swivel towards zero output. Displacement Vg max
This in turn reduces the effective moment on the arm of
the rocker, thus allowing the operating pressure to rise Figure 45 - A11VO Variable Displacement Output
in the same ratio by which the output flow is reduced Chart
(pB Vg = constant).
Variation: Hydraulic Stroke Limiter (LRH...)
The hydraulic stroke limiter allows the maximum
displacement to be infinitely varied or limited as
required.

Control range Vg max to Vg min.


The displacement is set by means of the pilot pressure
applied at port Y (max. 40 bar).

The hydraulic stroke limiter is overridden by the


constant power control, i.e. below the power curve
(power hyperbola), displacement is adjusted in relation

58 Service Manual
HOME PRINT
SERVICE TRAINING
Hydraulic Pumps

to pilot pressure. If the set flow or the operating


pressure is such that the power curve is exceeded, the Pressure Cut-Off
constant power control overrides the stroke limiter and Delta P
reduces displacement until the power hyperbola is Q min
restored. Load Sense Port

H1 bzw. H5 > function: Vg max to Vg min


(negative control)
As pilot pressure increases the pump swivels towards
lower displacement. (starting position at zero pressure:
Q max
vg max). Start of control, (at Vg max), settable _______ 4
- 10 bar.
H1 > pilot pressure increase (Vg max - Vg min), A11VO Boom Pump
________ p = 25 bar.

M A G T1 R T2 Y
Stroke Regulation
Horsepower Control

Pressure Cut-Off

Stroke Regulation
Pressure Cut-Off

Horsepower
Control
Q min

Vg max Vg min
Q min

A11VO 130/190 Main Pumps

s M1

Schematic of a A11VO Variable Displacement Pump


With Stroke Limiter

Service Manual 59
HOME PRINT
SERVICE TRAINING
Hydraulic Pumps

Linde Hydraulik BPR 105 from 3.06 to 15.86 cid. Pressure ratings are 5000 psi
intermittent and 3000 psi continuous duty.
Our BPR, bent-axis, variable displacement pumps are
self-priming units primarily for use in open circuit
applications. Six sizes are available with displacement

60 Service Manual
HOME PRINT
SERVICE TRAINING
Hydraulic Pumps

Power Regulator With Hydraulic Stroke


Limiter (LRH)
P RE The LRH is similar to the constant power regulator but
has a second sensor which responds to a low-pressure
pilot signal allowing the pump to be de-stroked on
demand. The pump's reduced displacement is
PC proportional to the signal and gives overriding control
within the set power band. This control is useful where
it is necessary to alter maximum flow to accommodate
certain conditions.
RB

Q L P P Y X

Figure 46 - BPR 105 Variable Displacement Output


Chart

Constant Power Regulator (LR)


This regulator is designed so that an exact hyperbola
curve of pressure/flow is realized. Therefore, the pump
makes maximum use of available power.
Setting the required power output simply involves
setting the pressure at which the regulator begins to de-
stroke the pump. The pump then follows a constant
power curve throughout the regulated range.
It is also possible to adjust the regulator to compensate
U T
for altitude changes, prime engine options or usage
changes. Figure 48 - Schematic of a BPR 105 Variable
Displacement Pump With Stroke Limiter

L P P Y

U T
Figure 47 - Schematic of a BPR 105 Variable
Displacement Pump With Stroke Limiter

Service Manual 61
HOME PRINT
SERVICE TRAINING
Hydraulic Pumps

Voac Variable Displacement desired displacement flow. The setting range can be
mechanically limited by setting screws. The position of
Axial Piston Pump the swash plate can be controlled via a visual
Variable displacement pumps work according to the mechanical indicator. The latest knowledge and
swash plate pricipal: 9 pistons operate in a rotating experience with regard to noise reduction has been
cylinder barrel where they fulfill one suction and one used in the development of V30D. All components
presssure stroke per rotaiton. The axial movement of used in the V30D are manufactured from high grade
the pistons is provided by an adjustable swash plate. he materials and machined with close tolerances.
setting angle (0-17) is varied in proportion to the

Horsepower Control

Q min Q min Q max


Q max

Pressure Cut-off (200bar) Pressure Cut-off

VOAC Accumulator Pump VOAC Main Pump

Delta P Adjustment Screw

Q min Q max

Pressure Cut-off
VOAC Boom Pump

62 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Pressure Settings
General
Stroke Limiter Adjustment

Override
Button

Pressure Reducing Valve


Pressure Adjustment

B P A
Remote controlled
stroke limiter

P
Output to hydraulic pumps 70
A

via dampner shuttle valve B bar

A
B
C

Line from manual


A

stroke limit valve


B
C

Adjustment Procedure

1. Disconnect line at A port of shuttle valve and install a 0-200 bar gauge in the end of the hose.
2. Push override button in all the way.
3. Pressure out pumpkit.
4. Set relief valve to 70 bar.
5. Set max. pressure on computer card for 35-40 bar with override button de-activated and the stroke limit
knob on remote box at min. strokes.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 63
HOME PRINT

Pressure Settings
Check the accumulator Pre-Charge
After charging an accumulator that has had no initial
gas pre-charge, allow 20 to 30 minutes for the gas
temperature and pressure to stabilize. Recheck the gas
WARNING
pre-charge pressure and adjust if necessary.
EXPLOSION CAUSED BY
After the accumulator has been put in service it is
important that the pre-charge pressure is checked at
IMPROPER ACCUMULATOR
least once in the first week to verify the initial pre- CHARGING CAN RESULT IN
charge has not changed due to temperature and DEATH OR SERIOUS INJURY!
pressure stabilization. If the check reveals no loss in
pressure, the pre-charge should be checked on the * Follow the charging instructions exactly!
following schedule: * Use ONLY dry nitrogen to charge the
1st Check - 1 week accumulator!
* NEVER use oxygen or compressed air to
2nd Check - 3 months
charge the accumulator!
3rd Check - 1 year
4th Check and continued - yearly
Read all instructions for charging accumulators before
beginning the charging procedure. Accumulators must
be charged only with dry nitrogen. Compressed air and
oxygen must never be used, because oxygen molecules
combine with hydraulic oil, lower the flash point of the
oil to less than room temperature, and cause an
explosion. Workers have died using compressed air or
oxygen to charge accumulators (Figure 49). Use only
dry nitrogen, never liquid nitrogen.
explwarn.eps

Figure 49
Charging accumulators
improperly can cause injury or
death

The procedure for checking the accumulator charge


pressure and the procedure for charging the
accumulator are described in the following steps:
1. Before you begin, you will need a charging kit
(Figure 50). Do not attempt to charge the
accumulators without one. Order the charge valve
assembly from Schwing America using part
number 30355436.
2. You must use a high-pressure regulator with the
nitrogen bottle. If it was not supplied with the
bottle, order one before proceeding with this job.
Before beginning the charging procedure, stop the
engine, remove the key, and put a Do Not Operate
tag over the key switch. Put the key in your pocket, so
no one can start the engine

revDate
64 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Tank Regulated High pressure gas 45s3blck.epsL

Pressure Pressure regulator is not


included with the
kit. These are
available from the
nitrogen supplier.

Nitrogen Bottle

charge valve assy


100 150

1500 2000
1000 2500
50 200
3000
500
3500
hose
0 250
30355456
accuman1.eps

BPL
ACCUMULATOR CHARGING KIT
HYDAC bladder (Includes hose and charge valve assy)
Accumulator
SCHWING PART NUMBER:
30355436
chargkit.eps

Figure 50
Accumulator charge kit for HYDAC
       
bladder accumulators    
 
 
.

3. The accumulators should dump pressure when the


  
    
  
engine is stopped, but you must still verify zero
accumulator pressure. Dump the accumulator
pressure using the manual bleed valve on the

acc
um
ma

accumulator unloading valve (Figure 51). Verify nifo


ld.e


ps

zero accumulator pressure on the concrete pumps


accumulator pressure gauge..

 
  

  
  S0106.eps
Figure 51
Accumulator manual bleed valves

4. Refer to Figure 13 for component location on the


charge valve assembly while performing the
following steps.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 65
HOME PRINT

Pressure Settings

Tank Regulated
Pressure Pressure
Nitrogen Supply Valve

Regulator Adjustment
Handle
Nitrogen Bottle

Push Button

Pressure Gauge
100 150
Charge Valve Stem
1500 2000
1000 2500
50 200
3000
500
3500

0 250

Bleed Swivel Nut


Valve

HYDAC bladder
Accumulator

chgvalve.eps

Figure 52
Charge valve assembly

revDate
66 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
5. Remove the valve protection cap and the valve seal 9. Be sure that the nitrogen bottle supply valve is
cap from the accumulator (Figure 53). Leave the firmly closed. Attach the high-pressure regulator to
valve protection cap on the accumulator until you the nitrogen bottle, then attach the hose to the high-
actually begin the procedure. pressure regulator. Finally, attach the other end of
the hose to the charge valve stem on the charge
valve assembly (Figure 52.
10. Do not open the nitrogen bottle supply valve yet.
Valve Protection Cap Turn the regulator adjustment handle on the high-
pressure regulator (Figure 52) counter clockwise to
its minimum setting (closed).
11. Slowly open the nitrogen bottle supply valve
(Figure 52). You will get a reading on the tank
Valve Seal Cap pressure gauge side of the regulator. If there is
enough pressure in the nitrogen bottle to do the
job, proceed to Step 13.
Valve Stem NOTE!
O-ring
If there is not at least 1450 PSI in the
nitrogen bottle (as shown on the regulator
gauge at this time), you will not be able to
charge the accumulator nitrogen to the 1450
PSI specification. If that is the case, you will
need a new bottle of nitrogen before
HYDAC bladder proceeding.
Accumulator 12. Adjust the regulator adjustment handle clockwise,
accum closeup
raising the regulated pressure. The accumulator
will begin to fill. Continue filling until the charge
Figure 53 valve assembly pressure gauge (Figure 52) reads
Detail of accumulator the desired pressure of 1450 PSI. Close the
gas valve area nitrogen bottle supply valve.
13. If you overcharge the nitrogen pressure, refer to
(Figure 52) and proceed as follows:
6. On the charge valve assembly (Figure 52, close the
bleed valve (turn it clockwise all the way in). If a Close the nitrogen bottle supply valve.
hose is connected to the charge valve stem, Depress the push button on the top of the charge
disconnect the hose from the charge valve stem. valve assembly.
This step closes the charge valve stem to prevent Slowly open the bleed valve on the charge kit.
the gas pressure from escaping out of the hose. It Close the bleed valve when the correct pressure is
ensures that the initial pressure reading is accurate. reached on the charge valve pressure gauge.
7. Find the swivel nut on the charge valve assembly NOTE!
(Figure 52). Screw the swivel nut onto the Never let nitrogen out of the accumulator by
accumulator gas valve. Tighten to 1015 in./lb. pressing the gas valve pin with a foreign
8. After the swivel nut is attached, depress the push object. The high pressure may rupture the
button on the top of the charge valve assembly valve seal!
(Figure 52). This presses a pin into the accumulator 14. Let the nitrogen sit in the accumulator for 10 to 15
gas valve and opens it. Read the pressure on the minutes. This allows the gas temperature to
charge valve assembly pressure gauge. The stabilize. Depress the push button on top of the
pressure should read 100 bar (1450 PSI). charge valve assembly. Recheck the pressure on
If pressure must be added, proceed to Step 10. the charge valve assembly pressure gauge.
If pressure is too high, skip to Step 14.
If no adjustment is necessary, skip to Step 17.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 67
HOME PRINT

Pressure Settings
15. Add or release nitrogen until the pressure is
correct. Be sure that the bleed valve is closed
before adding pressure and that the nitrogen bottle
supply valve is closed before releasing pressure.
16. When the correct pressure is reached, refer to
(Figure 52) and proceed as follows:
Close the nitrogen bottle supply valve.
Open the charge valve assembly bleed valve.
This releases the pressure in the hose, charge
valve assembly, and regulator.
While holding the charge valve assembly on
the accumulator, unscrew the charge valve
swivel nut.
Remove the charge valve assembly.
If you are finished with the charge valve
assembly, remove the hose and regulator.
54. Make a bubbly mixture from soap and water.
Spread the mixture around the accumulator gas
valve to check for gas leaks. Gas leaks will push
the bubbles away from the area of the leak. If you
find a leak, replace the accumulator or have it
repaired by qualified personnel. Never repair an
accumulator yourself.
55. Replace the gas valve seal cap (tighten to 22 ft/lb),
and hand-tighten the valve protection cap.
56. If your concrete pump has two accumulators,
repeat this procedure for each accumulator.

revDate
68 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Hydraulic Pump
Adjustments Adjustment Knob

Main System Pumps A11VO


To perform the proper adjustments of flow, horsepower,
beginning of stroke limitation and the pressure cut-off T

P
to the tandem A11VO main system hydraulic pumps, T
MG
P
the following steps must be done in order that they are MY Y
G

listed;

Setting the Flow Rate Adjustment Knob Adjustment Knob


Before flow metering the pumps, ensure that the
Figure 57
maximum engine Rpms are set to the proper
Electric Stroke Limiters
specifications. All Schwing units have a metal ID tag
located inside the cab displaying the specific RPM Install the flow meter. (Consult the operation manual
settings for that particular unit. Set the supplement for proper installation and use of the flow meter). Set
system pressure to 0 bar by turning the adjustment the engine Rpms at maximum and set the maximum
knob all the way out on the electric stroke limiter. This flow at the Q max screw to the proper specifications per
will avoid false readings of the flow rate until the the output chart. (Check your operators manual for the
maximum flow rate and horsepower break points are proper output chart for your specific unit).
set.
A11VO130 / A11VO130

Q-max Screws

A11VO130 / A11VO190

Q-max Screws

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 69
HOME PRINT

Pressure Settings
Horsepower Setting
Adjustment Knob
After the flow rate is set, the horsepower setting then
must be done. The horsepower break point must be set
to the proper specifications per the output chart.
CONCRETE
BPL 2023-5 PRESSURE
350 or 400 HP truck PSI Bar
2000 138

PERFORMANCE CHARACTERISTICS OF 1900 131


Piston Side

Piston Side

THE AXIAL PISTON HYDRAULIC PUMP T


1800 124
PSI

Bar

PUMP SPEED

E
2100 RPM 1700 117 P
T
HYDRAULIC RELIEF VALVE IS SET AT 1600 110
350 BAR MAX. PRESSURE (5075 PSI). MG
1500 103 P
G
PL
1400 97
MY Y
1300 90

ROD SIDE 1200 83

5500 180 Kw 200 Kw 1100 76

5000 350 1000 1007 69

900 62 Adjustment Knob Adjustment Knob


M

4500
300
OIL PRESSURE

4000 800 55
250 700 48
3500

3000 200
600 41
Figure 60
SA

2500 500 34
150
2000

1500 100
400

300
27

21
Stroke Limiters (two generations)
1000

500
50
200

100
14

7
3. Increase the engine Rpm's to the maximum setting
Break Point
180 Kw = 182 bar
200 KW = 202 bar
0
10 20 30 40 50 60 70 80
208
90 100 110 120 130 140 150 160 170 180 190 200 210 220 cu yd / h
and while watching the flow meter scale, slowly
At 350 bar
180 Kw = 278 l/m
200 Kw = 309 l/m
7.5 15 23 30.5 38 46 53.5 61 69 76.5 84 92 99 107 114 122 130 137 145 153 160 168

CONCRETE OUTPUT
cu meters/ h
turn the stroke limit potentiometer to the minimum
5 10 15 20 25 30
32
Number of strokes
(stroke / min.)
material output until the maximum flow rate begins
100 200 300 400 500 535
Oil volume
(liter / min.) to drop.
Break Points
4. When the flow rate begins to drop, stop turning the
Figure 58 potentiometer and read the pressure on the 0 to 40
Sample output chart bar gauge. The reading that is seen is the
beginning of stroke limitation. The reading should
Setting Stroke Limitation be between 5 to 7 bar. If it is not, then adjust the
beginning of stroke limitation screw accordingly to
Now that the maximum flow rate and horsepower
achieve the proper pressure reading.
settings have been made, the beginning of stroke
limitation can be set. Adjust the supplement system a. If the pressure is too high, then turn the screw
pressure to the maximum pressure of 50 bar. counter-clockwise (out) to reduce the pressure.
1. Make sure the stroke limit potentiometer at the rear b. If the pressure is too low, then turn the screw
operation panel or remote box is at the maximum clockwise (in) to increase the pressure.
material output setting.
Q-min Output Flow
Once the beginning of stroke limitation is set, the next
step is to check the Q min output flow.
1. With the 0 to 40 bar gauge still in the electric
stroke limit line going to the Y port of the hydraulic
pumps. Increase the engine Rpm's to the
maximum setting and while watching the flow
meter scale, turn the stroke limit potentiometer to
the minimum material output. The 0 to 40 bar
gauge should be reading approximately 25 bar
Figure 59
more than the beginning of stroke limitation setting
Stroke Limiter Potentiometer
to ensure the hydraulic pumps are all the way to the
2. Install a 0 to 40 bar gauge in the electric stroke minimum against the Q min stop. The Q min
limit line going to the Y port of the hydraulic reading should be between 15 to 25 liters per
pumps, at this time the reading on the gauge should minute. If it is too high, turn the Q min screw out
be 0. until the reading is correct or if it is to low, turn the

revDate
70 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Q min screw in until the reading is correct. When Parts Department using part number 10004680
the Q min has been set, the flow meter can now be (valve), and number 30303432 (tube). Contact the
removed. Service Department for installation instructions.
2. Activate the agitator. With the valve closed the
A11VO190
agitator will not be able to turn and the oil will be
forced over the relief valve. At an idle (about 600
RPM), 4.5 horsepower is being converted to heat.
A11VO130


  
 agitoff2.eps


     

Q min Screw

Q min Screw

Figure 61 
Q-min screw locations Figure 62
2. Repeat steps 2 through 6 on the second main Agitator shutoff valve
system pump before attempting to set the pressure 3. When the oil temperature gauge shows 50C, open
cut-off on both pumps. the shutoff valve.
NOTE!
All screw adjustments with the system Setting pressures on Hi-flo -6 pumpkits
reliefs and pressure cut-off must be done a. To set the pressure of the main relief valve on
while the unit (pumpkit) is in the neutral Hi-flo pumpkits, you must first disable the soft
position. switch circuit. Simply locate the ball cock for
the soft switch circuit (Figure 63) and close it
Check all hydraulic pressures.
by rotating the handle 90 degrees.
Changes in pressures can indicate trouble in one or b. The quarter turn shutoff valve for the concrete
more components. The specifications for each circuit pump will also need to be closed during this
are shown on the hydraulic schematics found in the procedure.
Appendix of this manual. The hydraulic schematics are
the only documents in this manual that have been NOTE!
updated specifically for your unit, by the serial number, Main system adjustments are preset at the
so in each of the following procedures you will be told factory. The following procedure begins
with adjustment of the main relief cartridge
to refer to the schematic for the pressure required. and pressure cutoff. If proper pressures can
Preheat the hydraulic oil not be obtained through these steps, refer to
Pressure settings must be made with the oil at normal the beginning of this procedure for specific
instructions on the adjustment of flow,
operating temperatures (40 60 C). In the past we horsepower, beginning of stroke regulation
could pressure out a function in the boom or outrigger and Q-min.
system to create heat, but load sensing systems no
longer allow maximum oil flow to be forced over relief.
Because of this the agitator circuit must be used to heat
the hydraulic oil.
To preheat the hydraulic oil:
1. Locate the agitator shutoff valve (Figure 62) and
close it. NOTE! If your unit does not have a
shutoff valve, order one from the Schwing Spare

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 71
HOME PRINT

Pressure Settings
Pressure setting procedure: 7. Stop the truck engine and put the key in your
pocket. Adjust the pressure cutoff screw (Figure
Soft switch 64) on each pump, by backing off the jam nut with
shutoff valve a 13mm wrench. Using a 4mm allen wrench, turn
the adjustment screw in (clockwise) one full turn
Main Pressure and tighten the jam nut. Restart the truck engine.
Gauge port
8. Adjust the engine RPM to maximum specification.
(See decal in truck cab)
9. Pressure out the system by activating the concrete
pump forward switch on the rear panel. Using the
Concrete pump
shutoff valve hif
lob
rn.
rear panel controls will allow you to read the
ep
s concrete pump main system pressure gauge, near
Figure 63 the e-stop manifold, from a safe distance.
Concrete pump and Soft switch shutoff valves NOTE!
1. Be sure that the waterbox covers and guards are in Because you turned out the pressure relief
place any time you will be working in the area cartridge in step 7, the system pressure
around the main control block. should read low at this time. If it does not
and the gauge spikes to 320 bar or more,
2. Wear safety glasses when working around a disengage the pump immediately. Turn the
concrete pump. relief cartridge out (counterclockwise)
more. For safety, it is important to adjust
NOTE! the pressure up from below the specified
It is vital that each adjustment screw be target pressure rather than down from a
properly identified prior to making any pressure which exceeds the target. Continue
adjustment. All screw adjustments for the this procedure until the main system pres-
system relief must be made with the pump- sure gauge reads lower than the specified
kit in the neutral position and adjustments target.
for pressure cutoff must be made with the 1. To increase the pressure put the pump in the
engine shut off.
neutral position and adjust the relief cartridge by
1. Start the truck engine, and put the PTO in gear just
turning it in (clockwise). When increasing the
as you would to pump a job.
pressure, the adjustments should be made in
2. If you have not already closed the soft switch quarter turn increments. If you make adjustments
shutoff valve and the concrete pump shutoff valve to increase the pressure but the pressure does not
(Figure 63) do so at this time. come up, you are probably reading the pressure
3. At the rear panel, select local control with the cutoff of the pumps, if so proceed to the next step
local/remote switch and turn the electric stroke otherwise skip to step 15.Turn the relief cartridge
limiter knob clockwise to maximum strokes per adjustment screw back out (counterclockwise)
minute. until you can no longer see a pressure drop and
4. The main system control block pressure must be tighten the jam nut.
set first to properly set the pressure cutoff on both 2. Stop the truck engine, put the key in your pocket.
pumps. Begin by backing off the jam nut of the 3. Go to the pressure cutoff screw on both hydraulic
main relief cartridge (Figure 65) with a 9/16 inch pumps (Figure 64) and back off the jam nut with a
wrench. 13mm wrench. Turn the adjustment screws in with
5. Using a 5/32 inch allen wrench, turn the a 4mm allen wrench one or two more turns, restart
adjustment screw out (counterclockwise) until you the engine and check the pressure again. Repeat
can feel no spring tension on the adjustment screw. this procedure until the main system relief can be
6. Now, turn the screw back in (clockwise) two or set to the target pressure.
three full turns to give you a proper starting point 4. When the proper main relief pressure is achieved,
and tighten the jam nut. pressure cutoff can be set. Shut off the engine, put
the key in your pocket and install 0-600 bar gauges
with whip hoses to the M1 gauge ports on the
bottom of the two hydraulic pumps (Figure 64).
revDate
72 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
You must be able to read both gauges
simultaneously to ensure that one pump is not  
      
more dominant than the other.      
NOTE!  
The gauges in the M1 ports will read consid-
 
erably less than the cutoff pressure of the 
pump. On a -6 (190/130 pump combination) 
the 190 will usually read 85 to 90 bar while
the 130 reads about 110 bar. They could
read the same however, at approximately
110 bar, but the 190 must never read higher  
 
than the 130. The actual cutoff pressure will   
 
130ajst.eps
be read on the concrete pump main system
pressure gauge near the e-stop manifold. Figure 64
1. Activate concrete pump forward to pressure out the Adjustment screw locations
pump and read the pressure on the two gauges in
the M1 ports. Soft switch
shutoff valve
2. Always stop the truck engine and put the key in
your pocket before making any adjustment on the Main Pressure
hydraulic pump. If the cutoff on one pump is set Gauge port
higher than the other, that pump will be more
dominant. The pressure gauge in the M1 port of the
dominant pump will however, read lower than the
other. To equalize the two pumps you must either
Concrete pump
adjust the cutoff screw in (clockwise) to increase shutoff valve hif
lob
rn.
ep
the pressure of the pump showing the higher s

reading or adjust the cutoff screw of the dominant


pump showing the lower reading out
(counterclockwise) to reduce the pressure. These Closed Open
adjustments must be made until the two gauges in
soft switch
the M1 ports are reading approximately the same.
relief valve
3. When you have achieved the same pressure on the
M1 port gauges, you can begin to adjust the
openclsd.eps

pressure cutoff screws in or out simultaneously


until you achieve the desired pressure setting of
350 bar (again, confirm the pressure specification
with the hydraulic schematic). Main relief valve
After pressure cutoff is set, return the pump to neutral, 5/32" Allen head
bring engine RPM to idle, open the soft switch quarter 9/16" jam nut
turn valve, and either proceed to other pressure settings Figure 65
or take the transmission and PTO out of gear and shut Soft switch circuit/Main relief valve
off the truck.
Setting the soft switch relief pressure
First, open the soft switch quarter turn valve (Figure
65) that you closed in the previous procedure. The rest
of the unit should still be set up as if you were going to
check the main relief valve pressure (concrete pump
shutoff valve still closed).
When you put the pump in forward now, the main
concrete pump pressure gauge should read the pressure
shown on the schematic for soft switch. If adjustment
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 73
HOME PRINT

Pressure Settings
is needed, loosen soft switch relief valve jam nut
(Figure 65) with a 9/16 open end wrench, and use a 5/
32 allen wrench to adjust the pressure. Turn the
adjustment screw in (clockwise) to raise the pressure or
out (counter clockwise), to lower the pressure. When
you attain the required pressure, tighten the jam nut
while holding the allen wrench to keep the pressure
from rising. Be sure to open the concrete pump shutoff
valve on the side of the brain (Figure 65) when you are
finished. The unit will not stroke with this valve closed

revDate
74 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
BPL 500

E-Stop Manifold Valves


Concrete Pump and Gauge Ports
Shutoff Valve
Water Pump Hand

Concrete Pump Valves and Gauge Port

Soft Switch

Accumulator Unload-
ing Manifold Valve
Concrete Pump
and Gauge Port
Pressure Gauge

Main Relief Valve

Manual (forward/reverse)
Agitator Hand Valve Control Lever.
and Gauge Port
Main Control Panel
Agitator Shutoff Valve

Figure 66
General location of components used
to set hydraulic pressures

Heating hydraulic oil. Pressure settings must be horsepower is being converted to heat. Shut off the
made with the oil at normal operating temperatures concrete pump when the temperature gauge on the
(40 60C). The agitator circuit must be used to operators panel shows 50C.
heat the hydraulic oil. Do not jam the paddles to 3. Open the agitator shutoff valve or remove plug and
force the oil over the relief valve by stopping the reconnect hose to agitator motor.
movement of the agitator. To preheat the
hydraulic oil using the agitator circuit, follow these NOTE!
instructions. If your unit does not have a shutoff valve,
order one, using part #10004680 (valve),
1. Locate the agitator shutoff valve and close it
and #30303432 (tube). Contact the Schwing
(Figure 67). The general location of the agitator
Service Department for installation instruc-
shutoff valve is shown in Figure 66.
tions. If you cant wait for a shutoff valve,
2. Position the agitator hand valve in the forward or you will need to remove one of the hoses
reverse position. The agitator will not be able to from the agitator motor and plug the hose
turn, and the oil will be forced over the relief valve. and open fitting with approved hydraulic
At idle speed (about 600 RPM), about 4.5
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 75
HOME PRINT

Pressure Settings
dead plugs. Do not substitute other plugs, 6. Using the concrete pump forward/neutral/
such as a steel bearing inside a cap fitting. reverse control lever, put the concrete pump into
You will need: the forward position. The unit will cycle one
- Qty 2 VS-16S locking plugs, part number stroke, then the rock valve cylinder will retract. Oil
10016803 will have nowhere to go except over the main relief
- Qty 1 GS-16S straight fitting, part number valve.
10008088 7. Read the pressure on the concrete pump gauge,
- Qty 2 16S capnuts, part number 10001743. located on the main control block. It should read
300 bar. If no adjustment is needed, skip to Step
12.
agit.shutoff.eps

CLOSED
8. If adjustment is required, loosen the jam nut on the
main relief valve adjusting screw (requires a 13-
mm spanner wrench).
9. Turn the knob on the relief valve to adjust the
pressure. Screw the handle in to raise pressure, out
to lower the pressure.
10. Retighten the jam nut. (Tightening the jam nut
tends to raise the pressure. If it becomes a problem,
Valve is shown in the hold the knob while tightening the jam nut)
OPEN position .
17mainreliefvalv

Figure 67
Agitator shut off valve

NOTE!
Pressure setting shown in these procedures
are for the BPL 500 HDR-18. Pressure set-
ting will be different for each type of pump
kit. Refer to the hydraulic schematic in the
Appendix of your Operation manual for the
correct pressure settings.
Set the concrete pump pressure. The Schwing
concrete pump circuit on the BPL 500 is designed Jam nut
to be operated at a maximum pressure of 300 bar
(4350 PSI). It is controlled by the main relief Relief Valve
valve, which is located at the rear of the main
control block (Figure 68).
To check or set the main relief pressure:
1. Be sure that the waterbox covers are installed on
the waterbox. We do not recommend using the
remote control box for the following procedure. Figure 68
2. Wear safety glasses when setting pressures.
3. Close the concrete pump shutoff valve and the soft 11. Put the concrete pump into the forward position
switch shutoff valve (Figure 6-77). again. The machine will not stroke this time, but
will again develop maximum pressure. Read the
4. Put the operators panel remote/local switch into pressure on the gauge. If more adjustment is
the local position. needed, return the pump to neutral, then repeat
5. Using the switch on the operators panel, rev the steps 9. thru 11. until the pressure is at 300 bar.
engine up to full RPM. Return the pump to the neutral position.
revDate
76 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
2. High-pressure the concrete pump. The control
block pressure gauge should read 100-bar (1450
17valves.epsL
Concrete pump
PSI) instead of 300 bar. If adjustment is needed,
shutoff valve loosen the 2.5-mm allen screw on the face of the
soft switch relief valve cartridge (Figure 69). Using
a screwdriver, adjust the pressure up or down as
needed, and lock into place with the 2.5-mm allen
screw. Use a screwdriver, if necessary, to prevent
the cartridge from turning while tightening the
allen screw. Be sure to open the concrete pump
shutoff valve when you are finished. The unit will
not stroke with this valve close
Setting accumulator E-Stop manifold pressure.
The accumulator E-Stop manifold pressure circuit

;@;@ @


; @


; @


; @


; ;@;@;@;@;@;@;@;@;@;@ is set to a maximum of 260-bar (3771 PSI) by its

;@ @


; @; @


@; @


@; @

 @


; ;@ ;@@


; @
@;

 @;@;@;@;@;@
@;
Soft switch relief valve on the emergency stop manifold. To

;@;@
;
Q

@


@


;
Q @;
;
Q

@




;
Q


;
Q 

;
Q

@
@;
;
Q

@




;
Q


;
Q

@
@;
;
Q

@




;
Q
@


;
Q

@
@;
@


;
Q



;
Q
@


;
Q
 @


; @


;
Q
@;@;@ 
@


;
Q
 @


;
Q
 @


; @


;
Q
@


;
Q@


;@


;
Q

@


;
Q


;
Q

@


;
@ ;
@


;
Q



;
Q


;
Q

@


; @;@;@;@;@
shutoff valve check the setting of the valve with the highest
pressure, you must first raise the pressure of the
lower three:
Soft Switch closed
1. Locate the accumulator unloading valve and its
Relief Valve relief valves (Figure 70).
Blckgrvs.eps

open
Figure 69
Concrete pump shut off valves 170-bar

138-bar
NOTE!
If you cannot adjust the pressure up to 300
bar, you have a problem. To ensure that the
pressure will not be to high when the prob-
230-bar
lem is found, turn the main relief knob OUT
several turns to lower the pressure. Contact
Schwing Americas service department for 17accum.eps

advice on how to continue.


Figure 70
12. If you will not be setting the soft switch pressure, Accumulator unloading valve
open both shutoff valves. The unit will not stroke
with closed shutoff valves.
2. Loosen the jam nut of the high pressure valve
13. Return the RPM to an idle and go on to the other (230-bar) adjustment screw. With an allen wrench
pressure settings, as required. turn the adjustment screw in one-and-a-half turns.
Setting the soft switch circuit relief pressure. To This will raise the pressure on the valve above 260-
check or adjust the soft switch pressure setting, bar.
perform the following steps:
1. Close the concrete pump shutoff valve. Open the
soft switch shutoff valve.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 77
HOME PRINT

Pressure Settings
3. Loosen the jam nut of the open valve (170-bar) and 3. Turn the open valve (170-bar) adjustment screw
the close valve (138-bar) pressure adjustment out two-and-a-half turns or until the gauge on the
screws. With an allen wrench turn both adjustment accumulator unloading valve reads 170-bar
screws in two-and-a-half turns. This will raise the (Figure 70).
pressure on both valves above 260-bar. 4. Turn the close valve (138-bar) adjustment screw
4. Connect the whip hose of a 0400 or 0600 bar out two-and-a-half turns or until the gauge on the
gauge into the gauge port of the E-Stop manifold accumulator unloading valve reads 138-bar
(Figure 71). (Figure 70
5. Tighten the jam nuts on all three adjustment
17estopman.eps
screws.
Set the water pump/agitator pressures. You will
need an assistant to perform this procedure. The
location of all the components needed for this
procedure are shown in (Figure 66). This hydraulic
circuit has a maximum pressure of 200 bar (2900
PSI), limited by the relief valve on the water pump
handvalve.
To set the water pump/agitator hydraulic circuit
pressures perform the following steps.
Relief valve
1. Stop the unit, and put the key in your pocket.
Gauge port 2. Install the whip hose of a 0400 or 0600 bar
gauge on to the gauge port located on the
waterpump handvalve. The location of the water
pump hand valve if shown in Figure 66. Make sure
the whip hose connection is tight.
3. To check or set the highest pressure of this circuit,
you must first raise the pressure of the agitator
Figure 71 relief valve. Turn the body of the relief valve in
E-Stop manifold accumulator relief valve (clockwise) one and one half turns on the agitator
hand valve. (The location of the water pump and
5. High-pressure the concrete pump. The pressure the agitator hand valve are shown in Figure 66.)
gauge should read 260-bar (3771 PSI) This will increase the circuit pressure over the 200
6. If adjustment is needed, loosen the jam nut and bars needed to set the water pump relief valve.
with a allen wrench turn the adjustment screw on 4. Start the unit engine and set the transmission and
the relief valve (Figure 71). Turn in to raise PTO as you would to pump concrete.
pressure, turn out to lower pressure. 5. Locate the relief valve on the water pump hand
7. Repeat steps (5) and (6) until the gauge reads 260- valve. It will be on the bottom, passenger side, of
bar. the water pump handvalve.
8. Tighten the jam nut on the adjustment screw, 6. Be sure that all personnel are clear.
remove the whip hose and gauge from the gauge 7. Bring the engine to full RPM.
port, and replace the cap on the gauge port. 8. Locate the agitator shutoff valve and close it
Setting the accumulator unloading valve. Use an (Figure 67) The general location of the agitator
allen wrench to make these adjustments shutoff valve is shown in Figure 66.
1. High-pressure the concrete pump. 9. Position the agitator hand valve in the forward or
2. Turn the high pressure (230-bar) adjustment screw reverse position. The agitator will not be able to
out one-and-a-half turns or until the gauge on the turn, and the oil will be forced over the water pump
accumulator unloading valve reads 230-bar relief valve.
(Figure 70).

revDate
78 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
10. The gauge attached to the water pump hand valve pressure at which the valve relieves can be seen on
should read 200 bar. the pressure gauge attached to the agitator hand
11. To adjust the pressure, turn the outside body of the valve. It should read 150 bar (2175 PSI).
water pump pressure relief valve (shown in Figure 20. To adjust the pressure, turn the outside body of the
58) clockwise to increase, or counterclockwise to agitator pressure relief valve, located on the bottom
decrease until 200 bar is showing the pressure of the agitator hand valve. It is the smaller of the
gauge. two cartridges extending from the bottom of the
valve (Figure 72). Turn the body of the relief valve
clockwise to increase or counter clockwise to
Turn body of valve decrease until 150 bar is showing the pressure
200 bar to adjust. gauge.
Higher
Relief Valve Lower

PS
7.E
lv1
m pv
p/c
pm
wtr

Figure 72
Water pump relief valve

12. Return the agitator handvalve to the neutral


position.
13. Turn the body of the agitator relief valves out
(counter clockwise) one and one half turns. This
will return the agitator relief valve to its original
settings.
14. Remove the pressure gauge from the water pump
hand valve and replace the cap nut on the gauge
port.
15. Install the whip hose of a 0400 or 0600 bar
gauge on to the gauge port located on the
passenger side agitator hand valve. Make sure the
whip hose connection is tight.
16. Close the agitator shutoff valve (Figure 67)
17. Be sure that all personnel are clear.
18. Bring the engine to full RPM.
19. Hold the agitator lever in the forward or reverse
position. This will send the oil against the high-
pressure plug. The oil will return to the tank over
the relief valve in the agitator hand valve. The
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 79
HOME PRINT

Pressure Settings

revDate
80 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
BPL 2000 4. Wear safety glasses when setting pressures.
5. Start the engine.
NOTE!
6. Close the concrete pump shut-off valve (also
Pressure settings must be made with the
known as the ballcock or quarter-turn valve). (See
hydraulic oil at normal operating tempera-
Figure 74.)
tures (4060C).
7. Put the operators panel remote / local switch
To heat the oil to operating temperature use one of the into the local position.
following procedures:
8. Using the switch on the operators panel, rev the
1. When the oil is very cold (at or below the pour engine up to full RPM.
point of your hydraulic oil), bring engine RPM to
an idle. Let the engine idle until the temp. gauge on 9. Using the concrete pump forward / neutral /
the operators panel reads 40C. reverse handle, put the concrete pump into the
forward position. The unit will stroke no more
2. If your concrete pump unit has an agitator shutoff than once, then the rock cylinder will retract. Oil
valve, refer to Preheating the hydraulic oil in the will have nowhere to go except over the main relief
Operation section of this manual. valve.
Set the concrete pump pressure. The Schwing
10. Read the pressure on the concrete pump gauge,
concrete pump circuit on the BPL 2000 is designed
located on the main control panel. It should read
to be operated at a maximum pressure of 300 bar
300 bar. Return the pump to neutral whether in
(4350 PSI). It is controlled by the main relief
needs adjustment or not. If no adjustment is
valve, which is located on the top of the main
needed, skip to Step 13.
control block (Figure 73). To check or set the main
relief pressure: 11. If adjustment is required, loosen the jam nut on the
relief valve adjusting screw (requires a 13 mm
spanner wrench).
12.
13. Turn the knob on the relief valve to adjust the
pressure. Screw the handle in to raise pressure, out
to lower the pressure.
14. Retighten the jam nut. (This step is necessary
because tightening the nut tends to raise the
pressure. If it becomes a problem, hold the knob
while tightening the jam nut).
15. Put the concrete pump into the forward position
again. The machine will not stroke this time, but
will again develop maximum pressure. Read the
pressure on the gauge. If more adjustment is
needed, return the pump to neutral, then repeat
steps i. thru l. until the pressure is at 300 bar.
Lower Raise Return the pump to the neutral position.
pressure pressure 16. Open the quarter turn valve.
17. Return the RPM to an idle and go on to the other
gray valve.eps L pressure settings, as required.
Figure 73
Concrete pump circuit
main relief valve

3. Be sure that the waterbox covers are installed on


the waterbox. We do not recommend using the
remote control box for the following procedure.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 81
HOME PRINT

Pressure Settings

Closed

Ball cock grooves.eps


Open

Figure 74
Concrete pump shutoff valve

NOTE! Set the agitator/water pump/outrigger pressure.


If you cannot adjust the pressure up to 300 The hydraulic circuit has a maximum pressure of
bar, you have a problem. In this case, 200 bar (2900 PSI), limited by the relief valve
unscrew the adjustment knob by several located on the outrigger handvalve (Figure 75).
turns so that your pressure isnt too high
once the problem is found. Contact Schwing
Americas service department for advice on
how to continue.

Relief Valve

OU
TR
IG
GE
R
R
ET
RA
CT
E
XT
EN
D

Figure 75
Outrigger handvalve

To set the agitator/water pump/outrigger hydraulic


circuit pressure use the following steps:
1. Stop the unit, and put the key in your pocket.
2. Install the whip hose of a 0400 or 0600 bar
gauge on to the gauge port located below the
outrigger handvalve. Make sure the whip hose
connection is tight.
revDate
82 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
3. Start the unit engine and set the transmission and
PTO as you would to pump concrete.
4. Locate the relief valve on the outrigger handvalve.
It will be on back left side of the outrigger
handvalve.
5. Be sure that all personnel are clear.
6. Restart the engine and bring it to full RPM.
7. Activate the outrigger handvalve in the retract
position. Hold the handvalve in retract position to
cause the outrigger (left or right) to bottom out in
the retract position. This will send the oil against
the high-pressure plug. The oil will return to the
tank over the relief valve in the handvalve. The
pressure at which valve relieves can be seen on the
attached pressure gauge. It should read 200 bar.
8. To adjust the pressure, turn the pressure relief valve
(location shown in Figure 75) clockwise to
increase, or counterclockwise to decrease until 200
bar is showing the pressure gauge.
9. Return the outrigger handvalve to the neutral
position.
10. Stop the engine and put the key in your pocket.
11. Remove the pressure gauge and replace the cap nut
on the gauge port.
12. The unit can now be restarted, if necessary.
Remember to put the key back in the engine before
you go home.
NOTE!
If your unit is equipped with an agitator
pressure gauge on the panel below the main
control panel, you only need to perform
Steps 6, 7, and 8 of the previous procedure.
The circuit pressure can be set to 200 bar on
the agitator pressure gauge.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 83
HOME PRINT

Pressure Settings

revDate
84 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
BPL 4000

E-Stop Manifold Valves


Concrete Pump and Gauge Ports
Shutoff Valve
Water Pump Hand

Concrete Pump Soft Valves and Gauge Port


Switch and Relief Valve
Main Relief Valve

Accumulator Unload-
ing Manifold Valve
Concrete Pump
and Gauge Port
Pressure Gauge

Outrigger Hand Valve Outrigger Hand Valve


and Gauge Port and Gauge Port

Main Control Panel


Agitator Hand Valve
and Gauge Port

Agitator Shutoff Valve

Figure 76
General location of components used
to set hydraulic pressures (original
production)

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 85
HOME PRINT

Pressure Settings

E-Stop Manifold Valves


and Gauge Ports
Concrete Pump Soft
Switch
Water Pump Hand
Valves and Gauge Port
Concrete Pump
Shutoff Valve Main Relief Valve and
Soft Switch Relief Valve
Accumulator Unload-
ing Manifold Valve
Concrete Pump
and Gauge Port
Pressure Gauge

Outrigger Hand Valve Outrigger Hand Valve


and Gauge Port and Gauge Port

Main Control Panel


Agitator Hand Valve
and Gauge Port

Agitator Shutoff Valve

Figure 77
General location of components used
to set hydraulic pressures (current
production)

Pressure settings must be made with the oil at normal NOTE!


operating temperatures (40 60C). The agitator If your unit does not have a shutoff valve,
circuit is used to heat the hydraulic oil. Do not jam the order one, using part #10004680 (valve),
paddles to force the oil over the relief valve by and #30303432 (tube). Contact the Schwing
stopping the movement of the agitator. To preheat Service Department for installation instruc-
the hydraulic oil using the agitator circuit, follow these tions. If you cant wait for a shutoff valve,
instructions: you will need to remove one of the hoses
1. Locate the agitator shutoff valve and close it from the agitator motor and plug the hose
(Figure Figure 77). and open fitting with approved hydraulic
2. Position the agitator hand valve in the forward or dead plugs. Do not substitute other plugs,
reverse position. The agitator will not be able to such as a steel bearing inside a cap fitting.
turn, and the oil will be forced over the relief valve. You will need:
At idle speed (about 600 RPM), about 4.5 - Qty 2 VS-16S locking plugs, part number
horsepower is being converted to heat. Shut off the 10016803
concrete pump when the temperature gauge on the - Qty 1 GS-16S straight fitting, part number
operators panel shows 50C. 10008088
3. Open the agitator shutoff valve or remove plug and - Qty 2 16S capnuts, part number 10001743.
reconnect hose to agitator motor.
revDate
86 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

agit.shutoff.eps
CLOSED

Valve is shown in
the OPEN
position

Figure 78
Agitator shut off valve

Set the concrete pump pressure (original located at the front of the main control block
production) - The concrete pump circuit on the (Figure 79). To check or set the main relief
BPL 4000 is designed to be operated at a pressure perform the following steps.
maximum pressure of 320 bar (4640 PSI). It is
controlled by the main relief valve, which is

relieflocMPS.eps

Main relief valve

Lower Raise
pressure pressure

Concrete pump
shutoff valve gray valve.eps L

Figure 79
Concrete pump shutoff valve
and main relief valve

1. Be sure that the waterbox covers are installed on 2. Wear safety glasses when setting pressures.
the waterbox. We do not recommend using the
remote control box for the following procedure.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 87
HOME PRINT

Pressure Settings
3. Close the concrete pump shutoff valve (Figure 6-
88) and the soft switch shutoff valve (FigureFigure
81).

Closed

Ball cock grooves.eps


Open

Figure 80
Concrete pump shutoff valve

7. Read the pressure on the concrete pump pressure


4Ksoft switch.epsL gauge, located on the main control block (Figure
79.) It should read 320 bar. Position the throttle
switch to the neutral position. If no adjustment is
needed, skip to Step 12.
8. If adjustment is required, loosen the jam nut on the
relief valve adjusting screw with a 13-mm spanner
wrench (Figure 79).
9. Turn the adjustment knob on the relief valve to
adjust the pressure. Turn the adjustment knob in to
raise pressure, out to lower the pressure.
Relief valve 10. Retighten the jam nut. (tightening the jam nut
tends to raise the pressure. If this happens, hold the
adjustment knob while tightening the jam nut).
Figure 81 11. Put the concrete pump into the forward position
Soft switch shutoff valve and relief again. The machine will not stroke this time, but
valve will develop maximum pressure. Read the pressure
on the gauge. If more adjustment is needed, return
4. Position the remote / local switch, on the main the pump to neutral, then repeat Steps 8. through
control panel, to the local position. 11. until the pressure is at 320 bar. Position the
5. Use the throttle switch, on the main control panel, throttle switch to the neutral position.
to rev the engine up to full RPM. NOTE!
6. Use the concrete pump forward / neutral / If you cannot adjust the pressure up to 320
reverse switch to put the pump into the forward bar, you have a problem. In this case, turn
position. The unit will stroke only once, then the the adjustment knob out by several turns so
rock cylinder will retract. Oil will have nowhere to that your pressure isnt too high once the
go except over the concrete pump main relief problem is found. Contact Schwing Amer-
valve. icas service department for advice on how
to continue.
revDate
88 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
12. If you are not setting the soft switch pressure, open
both shutoff valves. The unit will not stroke with
the shutoff valves closed.
Setting the soft switch circuit relief pressure
(original production) - To check or adjust the soft
switch pressure setting, perform the following
steps:
1. Open the soft switch shutoff valve. Close the
concrete pump shutoff value.
2. Rev the engine to full RPM. The control block
pressure gauge should read 80-bar (1160 PSI)
instead of 320 bar. If adjustment is needed, loosen
the 2.5-mm allen screw on the face of the soft
switch relief valve cartridge (Figure 81). Using a
screwdriver, adjust the pressure up or down as
needed, and lock into place with the 2.5-mm allen
screw. Use a screwdriver, if necessary, to prevent
the cartridge from turning while tightening the
allen screw. Be sure to open the concrete pump
shutoff valve when you are finished. The unit will
not stroke with the shutoff valve closed.
Set the concrete pump pressure (current
production) - The concrete pump circuit on the
BPL 4000 is designed to be operated at a
maximum pressure of 320 bar (4640 PSI). It is
controlled by the main relief valve, which is
located at the front of the main control block
(Figure 79). To check or set the main relief
pressure perform the following steps.
1. Be sure that the waterbox covers are installed on
the waterbox. We do not recommend using the
remote control box for the following procedure.
2. Wear safety glasses when setting pressures.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 89
HOME PRINT

Pressure Settings

Soft switch
shutoff valve

Gauge or gauge port

Pressure
Concrete pump control
hif
shutoff valve low
brn
.ep
s
position
(closed)

Groove lined
up with ports - open
grooves.eps

Groove at 90
to ports - closed

Main relief valve Jam nut


4K
op
n-c
lsd
.ep
s
Soft switch relief valve
Operating
Allen adjustment screw position
(open)

Figure 82
Concrete pump shutoff valve and soft switch shutoff valve

3. Close the concrete pump shutoff valve and the soft 7. Read the pressure on the concrete pump pressure
switch shutoff valve (Figure 82). gauge, located on the main control block (Figure
4. Position the remote / local switch, on the main 82.) It should read 320 bar. Position the throttle
control panel, to the local position. switch to the neutral position. If no adjustment is
needed, skip to Step 12.
5. Use the throttle switch, on the main control panel,
to rev the engine up to full RPM. 8. If adjustment is required, loosen the 9/16 inch jam
nut on the main relief valve (Figure 82).
6. Use the concrete pump forward / neutral /
reverse switch to put the pump into the forward 9. Use a 5/32 inch allen wrench to adjust the pressure
position. The unit will stroke only once, then the to 320 bar. Turn the adjustment screw in to raise
rock cylinder will retract. Oil will have nowhere to pressure, out to lower the pressure.
go except over the concrete pump main relief
valve.
revDate
90 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
10. Retighten the jam nut. (tightening the jam nut the pump to neutral, then repeat Steps 1. through
tends to raise the pressure. If this happens, hold the 6. until the pressure is at 80 bar. Position the
allen wrench in position while tightening the jan throttle switch to the neutral position.
nut). 8. Be sure to open the concrete pump shutoff valve
11. Put the concrete pump into the forward position when you are finished. The unit will not stroke
again. The machine will not stroke this time, but with the shutoff valve closed.
will develop maximum pressure. Read the pressure Set accumulator circuit hydraulic oil pressure
on the gauge. If more adjustment is needed, return (units with pressure- compensated pumps) - You
the pump to neutral, then repeat Steps 8. through will need an assistant for parts of this procedure.
11. until the pressure is at 320 bar. Position the To check or adjust the hydraulic pressure in the
throttle switch to the neutral position. accumulator circuit, perform the following steps:
NOTE! 1. Stop the truck, put the key in your pocket, and
If you cannot adjust the pressure up to 320 place a Do Not Operate sign on the windshield.
bar, you have a problem. In this case, turn 2. Loosen the jam nut on the pressure regulator of the
the adjustment knob out by several turns so accumulator hydraulic pump. Turn the screw in
that your pressure isnt too high once the two-and-a-half turns. This will raise the regulator
problem is found. Contact Schwing Amer- pressure above 300 bar (Figure 83).
icas service department for advice on how .
to continue.
12. If you are not setting the soft switch pressure, open
both shutoff valves. The unit will not stroke with
the shutoff valves closed.
Setting the soft switch circuit relief pressure
(current production) - To check or adjust the soft
switch pressure setting, perform the following Accumreg.eps

steps:
1. Open the soft switch shutoff valve. Close the
concrete pump shutoff value (Figure 82.)
2. Use the throttle switch, on the main control panel,
to rev the engine up to full RPM.
Accumulator pump
3. Use the concrete pump forward / neutral / pressure regulator
reverse switch to put the pump into the forward
position. The control block pressure gauge should
read 80-bar (1160 PSI) instead of 320 bar.
Figure 83
4. If adjustment is required, loosen the 9/16 inch jam
Accumulator pump pressure regulator
nut on the soft switch relief valve (Figure 82).
5. Use a 5/32 inch allen wrench to adjust the pressure
to 80 bar. Turn the adjustment screw in to raise 3. Connect the whip hose of a 0-600 bar gauge into
pressure, out to lower the pressure. the gauge port of the E-Stop manifold (Figure 84).
6. Retighten the jam nut. (tightening the jam nut 4. Loosen the jam nut on the accumulator relief valve,
tends to raise the pressure. If this happens, hold the located on the E-Stop manifold. Turn the screw in
allen wrench in position while tightening the jan two turns. This will raise the relief setting above
nut). 300 bar (Figure 84).
7. Put the concrete pump into the forward position
again. The machine will not stroke this time, but
will develop maximum pressure. Read the pressure
on the gauge. If more adjustment is needed, return

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 91
HOME PRINT

Pressure Settings

e-stop/left.epsL 45s3blck.epsL

Relief Valve and


Gauge Port

Relief Valve

Figure 84
Figure 85
E-Stop manifold accumulator relief valve
Accumulator manifold pressure relief
valve
5. Clear all personnel away from the drive lines, start
the truck engine, engage the pumps, and bring 8. You will need an assistant for this step. With the
engine RPM to maximum. engine still running, adjust the relief valve of the E-
6. Read the pressure on the accumulator circuit gauge Stop manifold. Back out the adjustment screw
located just between the hopper and the A-frame. until pressure reads 260 bar (3770 PSI) on the
Pressure should read 300 bar (4350 PSI). If no gauge connected to the E-Stop manifold.
adjustment is needed, skip to (Step 8).
7. If additional pressure adjustment is needed, locate
the accumulator manifold pressure relief valve
(Figure 85). Loosen the jam nut, and turn the screw WARNING
in to increase pressure, or out to decrease pressure.
Tighten the jam nut when pressure is at 300 bar. Stop the truck engine before proceed-
ing to the next Step. Entanglement
hazard

9. After the truck engine is stopped, back out the


accumulator circuit hydraulic pump pressure
regulator two-and-a-half-turns. This restores the
pressure regulator to its original setting (Figure
83).
10. Clear all personnel from the drive line area, start
the truck, and rev the engine RPM to maximum.
11. Read the pressure on the accumulator gauge. It
should read 260 bar (3770 PSI).
12. If additional adjustment is needed, you must stop
the truck engine, each time you approach the
accumulator circuit hydraulic pump (Figure 83).
Adjust the accumulator pump pressure regulator

revDate
92 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
screw in to increase pressure, or out to decrease
pressure. Lock the jam nut when pressure is e-stop/left.epsL

correct.
Set accumulator circuit hydraulic oil pressure Relief Valve
(units with accumulator unloading valves) - You and Gauge Port
will need an assistant for parts of this procedure.
To check or adjust the hydraulic pressure in the
accumulator circuit, follow these steps:
1. Stop the truck, put the key in your pocket, and
place a Do Not Operate sign on the windshield.
2. Connect the whip hose of a 0-600 bar gauge into
the gauge port of the E-Stop manifold (Figure 87).
3. Locate the accumulator unloading valve. The
location of this valve on the pump unit may vary.
Loosen the jam nut on the accumulator unloading
valve. Turn the screw in two-and-a-half turns. This
will raise the pressure above 300 bar (Figure 86). Figure 87
E-Stop manifold accumulator
relief valve
Adjustment Screw

5. Clear all personnel away from the drive lines, start


the truck engine, engage the pumps, and bring
engine RPM to maximum.
6. Read the pressure on the accumulator circuit gauge
located just between the hopper and the A-frame.
Pressure should read 300 bar (4350 PSI). If no
adjustment is needed, skip to (Step 8).
7. If additional pressure adjustment is needed locate
the accumulator manifold pressure relief valve
(Figure 88). Loosen the jam nut, and turn the screw
s
in to increase pressure, or out to decrease pressure.
.ep
un
lvlv
Tighten the jam nut when pressure is at 300 bar.

Figure 86
Accumulator unloading valve

4. Loosen the jam nut on the accumulator relief valve,


located on the E-Stop manifold. Turn the screw in
two turns. This will raise the relief setting above
300 bar (Figure 87).

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 93
HOME PRINT

Pressure Settings
. 2. Install the whip hose of a 0400 or 0600 bar
gauge on to the gauge port located on the
45s3blck.epsL

waterpump handvalve. The location of the water


pump hand valve if shown in Figure 66. Make sure
the whip hose connection is tight.
3. To check or set the highest pressure of this circuit,
you must first raise the pressure of the lower two
relief valves. Turn the body of the relief valves in
(clockwise) one and one half turns on the agitator
hand valve and the passenger side outrigger hand
valve. (The location of the water pump and the
agitator hand valve are shown in Figure 66.) This
will increase the circuit pressure over the 210 bars
needed to set the water pump relief valve.
Relief Valve 4. Start the unit engine and set the transmission and
PTO as you would to pump concrete.
5. Locate the relief valve on the water pump hand
Figure 88 valve. It will be on the bottom, passenger side, of
Accumulator manifold pressure relief valve the water pump handvalve.
6. Be sure that all personnel are clear.
7. Bring the engine to full RPM.
8. You will need an assistant for this step. With the
engine still running, adjust the accumulator relief 8. Push the outrigger enable push button, located next
valve on the E-Stop manifold (Figure 87). Back to the outrigger control lever. Hold the outrigger
out the adjustment screw until pressure reads 260 control lever in the retract position to cause the
bar (3770 PSI) on the gauge connected to the E- outrigger to bottom out in the retract position. This
Stop manifold. will send the oil against the high-pressure plug.
The oil will return to the tank over the relief valve
9. Back out the accumulator unloading valve
in the water pump hand valve. The pressure at
adjustment screw two-and-a-half-turns. This
which the valve relieves can be seen on the
restores it to its original setting.
pressure gauge attached to the water pump hand
10. Read the pressure on the accumulator gauge. It valve. It should read 210 bar.
should read 260 bar (3770 PSI).
11. If additional adjustment is needed, adjust the screw NOTE!
on the accumulator relief valve (Figure 63) in to You cannot use the extend position for this
increase pressure, out to decrease pressure. Lock adjustment because extend position has a
the jam nut when pressure is correct. non-adjustable, secondary relief functions
built into the valve.
12. Remove the pressure gauge from the outrigger
hand valve and replace the cap nut on the gauge 9. To adjust the pressure, turn the outside body of the
port. water pump pressure relief valve (shown in Figure
Set the water pump/outrigger/agitator 89) clockwise to increase, or counterclockwise to
pressures - You will need an assistant to perform decrease until 210 bar is showing the pressure
this procedure. The location of all the components gauge.
needed for this procedure are shown in (Figure 66).
This hydraulic circuit has a maximum pressure of
210 bar (3045 PSI), limited by the relief valve on
the water pump handvalve.
To set the water pump/outrigger/agitator hydraulic
circuit pressures, perform the following steps:
1. Stop the unit, and put the key in your pocket.
revDate
94 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
17. To adjust the pressure, turn the outside body of the
outrigger pressure relief valve, located on the back
of the outrigger hand valve (Figure 90), clockwise
Turn body of valve to increase or counter clockwise to decrease until
210 bar to adjust. 200 bar is showing the pressure gauge.

;;;;;;;; 
@@@@@@@@

 ;;;
@@@

Higher
Relief Valve Lower

@@@@@@@@ ;;;


;;;;;;;;
4Kpsoutr.eps

@@@


@@@@@@@@ ;;;


;;;;;;;; @@@

 WARNING
IN Clear area
RETRACT
before activating
OUTRIGGER
outriggers
OUT
EXTEND

S
.EP
4K
vlv
/cmp
p mp
wtr

Outrigger
Figure 89 Relief Valve
Water pump relief valve and Gauge
Port
10. Return the outrigger handvalve to the neutral
position.
Figure 90
11. Turn the body of the relief valves out (counter Outrigger relief valve
clockwise) one and one half turns on the agitator
hand valve and the passenger side outrigger hand
valve. This will return the these relief valves to 18. Return the outrigger handvalve to the neutral
their original settings. position.
12. Remove the pressure gauge from the water pump 19. Remove the pressure gauge from the passenger
hand valve and replace the cap nut on the gauge side outrigger hand valve and replace the cap nut
port. on the gauge port.
13. Install the whip hose of a 0400 or 0600 bar 20. Close the agitator shutoff valve (Figure 91).
gauge on to the gauge port located on the 21. Install the whip hose of a 0400 or 0600 bar
passenger side outrigger hand valve. Make sure the gauge on to the gauge port located on the drivers
whip hose connection is tight.(Figure 65). side agitator hand valve (Figure 92). Make sure the
14. Be sure that all personnel are clear. whip hose connection is tight.
15. Rev the engine to full RPM.
16. Activate the passenger side outrigger handvalve in
the retract position. Hold the handvalve in retract
position to cause the outrigger to bottom out in the
retract position. This will send the oil against the
high-pressure plug. The oil will return to the tank
over the relief valve in the outrigger hand valve.
The pressure at which the valve relieves can be
seen on the pressure gauge attached to the
outrigger pump hand valve. It should read 200 bar
(2900 PSI).

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 95
HOME PRINT

Pressure Settings

WARNING 4Kdshppr.epsL
agit.shutoff.eps

CLOSED
Do not stand on
hopper grates.

SAFETY INSTRUCTIONS
HOPPER GRATE OR
BEFORE REMOVING
SERVICE:
PERFORMING ANY
Engines Electric Motors
Gasoline or Diesel motor.
1. Stop the electric
1. Stop the engine.
place it 2. Lock out the power an
2. Remove the key, source according to
put
in your pocket, and approved lockout-tagout
a "DO NOT OPERATE" program.
tag on the switch.
3. Check accumulator
3. Check accumulator circuit pressure gauge
circuit pressure gauge (if so equipped) to
verify
verify
(if so equipped) to zero system pressure.
zero system pressure.

Gauge Port

@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;
QQQQQQQQQQQQQQQQQQQQ
@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;
QQQQQQQQQQQQQQQQQQQQ

@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;
QQQQQQQQQQQQQQQQQQQQ

Valve shown in the @@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;
QQQQQQQQQQQQQQQQQQQQ

@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;
QQQQQQQQQQQQQQQQQQQQ

SUBSIDIARY OF F. W. GMBH.
AMERICA INC.
HERNE 2/ GERMANY
AGITATOR
WHITE BEAR, MINNESOTA

OPEN position
PHONE (02325)7871
PHONE 612-429-0999 TELEX 820 348
TWX: 910-563-3539
4.373.875
U. S. PATENTS: 3.146.721; 3.640.303; 3.409.334; REVERSE - FORWARD

SERIAL NO. YEAR


MODEL
MATERIAL
STROKES PER MINUTE MAX.
WEIGHT LBS. PRESSURE

SYSTEM SYSTEM SYSTEM


MAXIMUM HYDRAULIC PRESSURE 1 1
1

WARNING This product is covered by one or more of the following


3,409,334 4,057,373 4,392,510 4,708,288 5,257,912
U.S. patents:
Re. 32,041
4,437,817 4,852,467 5,263,828 Re. 32,657
3,580,696 4,178,142
Clear area 3,640,303
3,685,543
4,191,513
4,260,338
4,465,441
4,472,118
4,978,073
5,066,203
5,281,113
5,332,366
Re. 32,719

5,346,368
before activating 3,741,691
3,829,251
4,343,598
4,373,225
4,556,370
4,621,375
4,681,022
5,106,225
5,106,272
5,224,654
5,401,140
4,019,839 4,373,875
outriggers

Figure 91 IN
RETRACT

OUTRIGGER
OUT

EXTEND

Close agitator shutoff valve

Agitator Relief
22. Be sure that all personnel are clear. Valve
23. Rev the engine to full RPM.
24. Hold the agitator lever in the forward or reverse Figure 92
position. This will send the oil against the high- Agitator relief valve
pressure plug. The oil will return to the tank over
the relief valve in the agitator hand valve. The 26. Return the agitator handvalve to the neutral
pressure at which the valve relieves can be seen on position.
the pressure gauge attached to the agitator hand 27. Remove the pressure gauge from the outrigger
valve. It should read 200 bar (2900 PSI). hand valve and replace the cap nut on the gauge
25. To adjust the pressure, turn the outside body of the port.
agitator pressure relief valve, located on the bottom
of the agitator hand valve. It is the smaller of the
two cartridges extending from the bottom of the
valve (Figure 92). Turn the body of the relief valve
clockwise to increase or counter clockwise to
decrease until 200 bar is showing the pressure
gauge.

revDate
96 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
KVM 17M
Check hydraulic pressures. Check all hydraulic
pressures. Changes in pressures can indicate
trouble in one or more components. The
specifications for all circuits are shown on the
Hydraulic Schematics in the Appendix of this
manual.
Pressure settings must be made with the oil at normal
operating temperatures (40C 60C). The agitator
circuit must be used to heat the hydraulic oil. Do not
jam the paddles to force the oil over relief by stopping
the movement of the agitator. To preheat the hydraulic
oil using the agitator circuit, follow these instructions.
1. Locate the agitator shutoff valve and close it
(Figure 107). The general location of the agitator
shutoff valve is shown in Figure 93.
NOTE!
If your unit does not have a shutoff valve,
order one, using part #10004680 (valve),
and #30303432 (tube). Contact the Schwing
Service Department for installation instruc-
tions. If you cant wait for a shutoff valve,
you will need to remove one of the hoses
from the agitator motor and plug the hose
and open fitting with approved hydraulic
dead plugs. Do not substitute other plugs,
such as a steel bearing inside a cap fitting.
2. Position the agitator lever in the forward or reverse
position (Figure 107). The agitator will not be able
to turn, and the oil will be forced over the relief
valve.
3. At idle speed (about 600 RPM), about 4.5
horsepower is being converted to heat. Shut off the
concrete pump when the temperature gauge on the
operators panel shows 50C.
4. Open the agitator shutoff valve or remove plug and
reconnect hose to agitator motor.
The general location of the components used to check
or set hydraulic pressures in shown in Figure 93.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 97
HOME PRINT

Pressure Settings

Boom (Section #1)


Down Pressure Relief Boom Hand Valves and
Valve and Gauge Gauge Port

Boon/Outrigger
Hand Valve and Gauge E- Stop Manifold Valves
Port and Gauge Ports

Concrete Pump Shutoff


Valve
Water-Pump/Compressor
Soft Switch Shutoff Hand Valve and Gauge
Valve Port
AGITATOR
CONCRETE PUMP

30347529 A

Accumulator Unload- Main Relief Valve


ing Manifold Valve and
Gauge Concrete Pump Pressure
EMERGENCY STOP
PARO DE EMERGENCIA
ARRT D'URGENCE

Gauge

Outrigger Hand Valve Main Control Panel


and Gauge Port

Agitator Hand Valve


and Gauge Port
Outrigger Hand Valve
Agitator Shutoff Valve

Figure 93
General location of components
used to set hydraulic pressures

Setting concrete pump pressure


The MPS pumpkits used on the KVM 17 are designed
to be operated at a maximum pressure of 300-bar (4350
PSI). The pressure in the system is limited by the relief
valve located on the rear (toward the hopper) of the
main control block (Figure 94).

revDate
98 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
8. Read the pressure on the control block pressure
17mainreliefvalve.eps
gauge, shown in Figure 68. It should read 300-bar.
Return the pump control to neutral, whether it
needs adjustment or not. If no adjustment is
needed, skip to Step 13.
17valves.eps

Shutoff valve

Jam nut

Relief Valve

Figure 94
Concrete pump main relief valve

To check or set concrete pump circuit pressures, closed


perform the following steps.
1. Wear safety glasses when setting pressures.
2. Be sure that the waterbox covers and guards are Blckgrvs.eps

installed on the waterbox. Schwing does not


recommend using the remote control box when
setting the main relief pressure.
3. Start the truck engine, and put the PTO and open
transmission into gear, just as you would to pump a
job.
Figure 95
4. Locate and close the concrete pump shutoff valve Concrete pump shut off valves
(quarter-turn valve), and the soft switch shutoff
valve (quarter-turn valve) (Figure 95).
5. Put the operators panel remote / local switch 9. Using a 13-mm spanner wrench, loosen the jam
into the local position. nut on the relief valve adjusting screw (Figure 95).
6. Using the switch on the operators panel, rev the 10. Turn the knob on the relief valve to adjust the
truck engine up to full RPM. pressure. Screw the handle in to raise pressure, out
to lower pressure.
7. Put the operators panel forward / neutral /
reverse switch into the forward position. The 11. Retighten the jam nut. Tightening the nut tends to
unit will stroke only once, then the rock cylinder raise the pressure. If the rise in pressure becomes a
will retract. The oil leaving the hydraulic pumps problem, hold the knob while tightening the jam
will be forced over the main relief valve. This nut.
procedure is called high-pressuring the concrete
pump.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 99
HOME PRINT

Pressure Settings
12. High-pressure the concrete pump again. Read the
pressure on the control block pressure gauge. If
more adjustment is needed, return the concrete
pump switch to neutral, then repeat Steps (5)
through (8) until the pressure is correct.
NOTE!
If you cannot adjust the pressure up to spec- 170-bar
ification, you have a problem. In this case,
unscrew the adjustment knob several turns 138-bar
so that your pressure is not too high when
you find the problem. Contact Schwing
Americas Service Department at (651) 429-
0999 for advice on how to continue. 230-bar
13. If you will not be setting the soft switch pressure,
open the shutoff valves. The unit will not stroke
17accum.eps
with closed shutoff valves.
Figure 96
Setting the soft switch circuit relief Accumulator unloading valve
pressure (original production)
To check or adjust the soft switch pressure setting,
1. Locate the accumulator unloading valve (Figure
perform the following steps.
96).
1. Open the soft switch shutoff valve. The rest of the
2. Loosen the jam nut of the high pressure valve
unit should still be set up as if you were going to
(230-bar) adjustment screw. With an allen wrench
check or set concrete pump pressure.
turn the adjustment screw in one-and-a-half turns.
2. High-pressure the concrete pump. The control This will raise the pressure on the valve above 260-
block pressure gauge should read 100-bar (1450 bar.
PSI) instead of 300 bar. If adjustment is needed,
3. Loosen the jam nut of the open relief valve (170-
loosen the 2.5-mm allen screw on the face of the
bar) and on the close valve (138-bar) pressure
soft switch relief valve cartridge (Figure 95). Using
adjustment screws. With an allen wrench turn both
a screwdriver, adjust the pressure up or down as
adjustment screws in two-and-a-half turns. This
needed, and lock into place with the 2.5-mm allen
will raise the pressure on the valve above 260-bar.
screw. Recheck. Use a screwdriver, if necessary, to
prevent the cartridge from turning while tightening 4. Connect the whip hose of a 0400 or 0600 bar
the allen screw. Be sure to open the concrete pump gauge into the gauge port of the E-Stop manifold
shutoff valve when you are finished. The unit will (Figure 97).
not stroke with this valve close

Setting accumulator E-Stop manifold


pressure (original production)
The accumulator E-Stop manifold pressure circuit is
set to a maximum of 260-bar (3771 PSI) by its relief
valve on the emergency stop manifold. To check or
adjust this setting, you must first raise the pressure of
the accumulator unloading valves to 260-barr or
higher.

revDate
100 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
4. Turn the close valve (138-bar) adjustment screw
17estopman.eps out two-and-a-half turns or until the gauge on the
accumulator unloading valve reads 138-bar (Figure
96).
5. Tighten the jam nuts on all three adjustment
screws.

Setting accumulator E-Stop manifold


pressure (current production)
The accumulator E-Stop manifold pressure circuit is
Relief valve set to a maximum of 260-bar (3771 PSI) by its relief
valve on the emergency stop manifold. To check or
Gauge port adjust this setting, you must first raise the pressure of
the accumulator unloading valves to 260-barr or
higher.

17accum2.eps
@@@@@@@@@@@@@@@@@@@@@@@@

;;;;;;;;;;;;;;;;;;;;;;;;
 ;@Q ;@Q ;@Q;@Q ;@Q;@Q ;@Q;@Q ;@Q;@Q ;@Q
;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q
@@@@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;;; 
Q


@ 
Q


@
; 
Q


@
; 
Q


@
;
;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q
;
@@@@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;;; ;@Q ;@Q ;@Q ;@Q ;@Q
;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q
@@@@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;;;
Figure 97 @@@@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;;; 
Q


@
; 
Q


@
; 
Q


@
; 
Q


@
; 
Q


@
; 
Q


@
; 
Q


@
; 
Q


@
; 
Q


@
; 
Q


@
; ;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q
@@@@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;;;

Q


@
; 
Q


@
; 
Q


@
; 
Q


@
; 
Q


@
; 
Q


@
; 
Q


@
; 
Q


@
; 
Q


@
; 
Q


@
; 
Q


@
; 
Q


@
;
E-Stop manifold accumulator relief valve ;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q;@Q
@@@@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;;; ;@Q;@Q;@Q ;@Q;@Q;@Q ;@Q;@Q;@Q ;@Q;@Q ;@Q;@Q ;@Q;@Q ;@Q
;@Q;@Q;@Q ;@Q;@Q;@Q ;@Q;@Q;@Q ;@Q;@Q;@Q;@Q ;@Q;@Q;@Q;@Q ;@Q;@Q;@Q ;@Q;@Q;@Q
@@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;
5. High-pressure the concrete pump. The pressure @@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;
gauge should read 260-bar (3771 PSI). @@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;; Gauge
@@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;
6. If adjustment is needed, loosen the jam nut and @@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;
230-bar relief
@@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;
with a allen wrench turn the adjustment screw on @@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;
170-bar relief
@@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;
the relief valve (Figure 97). Turn in to raise @@@@@@@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;;;;;;;
pressure, turn out to lower pressure. Figure 98
7. Repeat steps (5) and (6) until the gauge reads 260- Accumulator unloading valve
bar. (current production
8. Tighten the jam nut on the adjustment screw,
1. Locate the accumulator unloading valve (Figure
remove the whip hose and gauge from the gauge
98).
port, and replace the cap on the gauge port
2. Loosen the jam nut of the high pressure valve
Setting the accumulator unloading valve (230-bar) adjustment screw. With an allen wrench
(original production) turn the adjustment screw in one-and-a-half turns.
This will raise the pressure on the valve above 260-
Use an allen wrench to make these adjustments bar.
1. High-pressure the concrete pump. 3. Loosen the jam nut of the open relief valve (170-
2. Turn the high pressure (230-bar) adjustment screw bar.) With an allen wrench turn the adjustment
out one-and-a-half turns or until the gauge on the screw in two-and-a-half turns. This will raise the
accumulator unloading valve reads 230-bar (Figure pressure on the valve above 260-bar.
96). 4. Connect the whip hose of a 0400 or 0600 bar
3. Turn the open valve (170-bar) adjustment screw gauge into the gauge port of the E-Stop manifold
out two-and-a-half turns or until the gauge on the (Figure 99.)
accumulator unloading valve reads 170-bar (Figure
96).

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 101
HOME PRINT

Pressure Settings
Setting the boom E-Stop manifold
17estopman.eps
pressure
The boom E-Stop manifold pressure circuit is set to a
maximum of 350-bar (5076 PSI) by its relief valve on
the emergency stop manifold. To check the setting of
the valve with the highest pressure, you must first raise
the pressure of the lower two:
1. Locate the boom/outrigger hand valve (Figure
101).
Relief valve 2. Turn the outside body of the 300-bar relief valve
that is located at the bottom of the boom/outrigger
Gauge port hand valve in two-and-one-half turns. This will
raise the pressure on the valve above 350-bar.
3. Locate the boom hand valves (Figure 101).
4. Turn the outside body of the (280-bar) relief valve
that is located at the back of the boom hand valve
in two-and-one-half turns. This will raise the
pressure on the valve above 350-bar.
Figure 99 5. Connect the whip hose of a 0400 or 0600 bar
E-Stop manifold accumulator relief valve gauge into the gauge port of the boom E-Stop
manifold valve (Figure 100).
5. High-pressure the concrete pump. The pressure
gauge should read 260-bar (3771 PSI)
6. If adjustment is needed, loosen the jam nut and 17e-stop.eps
GREASE TOWER BEARINGS
GREASE TOWER BEARINGS ONLY GREASE WHICH HAS
THE FOLLOWING CHARACTERISTICS. USE LUBRIPLATE

Gauge port and


MO-LITH NO 2, TEXACO MOLYTEX EP 2 OR EQUAL.
BASE TYPE LITHIUM
NLGI NO 2
WORKING PENETRATION RANGE AT 77F 265/295
MOLYBDENUM DISULPHIDE 3% MINIMUM
ASTM DROPPING POINT F 350 MINIMUM

with a allen wrench turn the adjustment screw on


the relief valve (Figure 99). Turn in to raise relief valve on
pressure, turn out to lower pressure. SAFETY INSTRUCTIONS
cab side of
WARNING
= STOP

7. Repeat steps (5) and (6) until the gauge reads 260- manifold block.
Emergency stop
switches do NOT
function when
= manual bypass is
depressed.

bar.
8. Tighten the jam nut on the adjustment screw,
remove the whip hose and gauge from the gauge
port, and replace the cap on the gauge port.
cato E!
r light
temp hydr whe POS GE."
erat aulic n indi SIBL

g
CAR pped

atin
TRID
N!

es not repl oper

is cold if
LAC AND PAP is equi

.
n oil ace
IO

GE NOT

flash Do is at
NT

ER
r

TRID SE IS
ANIN E-W oil filte

light ure. oil

whe
TE

flash E CAR RE-U


AY
aulic
AT
with hydr
CLE a "ON

and
G
The

es
REP

WARNING
Do not operate at
pressures exceeding
the rating of the
entire material
delivery system.

Setting the accumulator unloading valve


(current production)
Use an allen wrench to make these adjustments
1. High-pressure the concrete pump. Figure 100
E-Stop manifold boom relief valve
2. Turn the high pressure (230-bar) adjustment screw
out one-and-a-half turns or until the gauge on the
6. Pressure out any boom cylinder except #1 in a
accumulator unloading valve reads 230-bar (Figure
retract position. You can pressure out a cylinder by
98.)
retracting a fully retracted cylinder or extending a
3. Turn the open valve (170-bar) adjustment screw fully extended cylinder. The oil will have nowhere
out two-and-a-half turns or until the gauge on the to go but over the relief valve.
accumulator unloading valve reads 170-bar (Figure
7. The pressure gauge on the boom E-Stop manifold
98.)
should read 350-bar.
4. Tighten the jam nuts on all adjustment screws.

revDate
102 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
8. If adjustment is needed, loosen the jam nut and 1. Connect the whip hose of a 0400 or 0600 bar to
turn the adjustment screw on the relief valve that is the gauge port of the boom/outrigger hand valve.
located on the boom E-Stop manifold valve (Figure 2. If this is not already done, start the truck engine
100). Turn in to raise pressure, turn out to lower and set the transmission and PTO as you would for
pressure. a pumping job.
9. Repeat steps (4) thorough (6) until the gauge reads 3. Locate the 300-bar relief valve on the bottom of
350-bar. the boom/outrigger hand valve.
10. Tighten the jam nut on the boom E-Stop manifold 4. Set the engine RPM to maximum.
adjustment screw, remove the whip hose and gauge
5. Push the outrigger enable pushbutton located next
from the gauge port, and replace the cap on the
to the outrigger hand valves. Hold the outrigger
gauge port.
hand valve lever in the retract position. The oil
11. Turn the outside body of the 300-bar relief valve coming from the pump has nowhere to go but over
that is located at the bottom of the boom/outrigger the relief valve on the boom/outrigger hand valve.
hand valve out two-and-one-half turns.
NOTE!
12. Turn the outside body of the (280-bar) relief valve
You cannot use the outrigger extend posi-
that is located at the back of the boom hand valve
tion for this adjustment because extend has
out two-and-one-half turns.
nonadjustable secondary relief functions
13. Set or reset the boom and the outrigger hydraulic built into the valve.
pressures.
6. The pressure on the pressure gauge should read
300-bar.
Setting the boom/outrigger pressure
7. If adjustment is needed, turn the outside body of
The outrigger circuit is set to a maximum of 300-bar
the relief valve that is located at the bottom of the
(4350 PSI) by the relief valve on the boom/outrigger
boom/outrigger hand valve. Turn in to raise
hand valve. This handvalve is located on the drivers
pressure, turn out to lower pressure.
side of the turret (Figure 101). Due to the location of
the boom/outrigger handvalve and the outrigger control 8. Activate the enable pushbutton and the hand valve
lever used in this procedure, you will need an assistant and read the pressure on the gauge again. Repeat
to make the adjustments and read the gauge. steps (7) and (8) until the gauge reads 300-bar.
9. When the pressure is 300-bar, release the enable
pushbutton and the outrigger hand valve.
Turn body of valve 10. Remove the whip gauge from the boom/outrigger
to adjust. hand valve, and replace the cap on the gauge port.
300 bar Higher
Relief Valve Lower Setting the outrigger pressure
The outrigger circuit is set to a maximum of 280-bar
(4060 PSI) by the relief valve located on the drivers
side outrigger hand valve assembly (Figure 102). The
valve routes the oil to the two outrigger hand valve
banks, one on each side of the unit. A relief valve
inside the drivers side bank limits the entire outrigger
circuit to 280-bar.
PS
X.E
-28
lve
va
oom
tr ig/b
ou

Figure 101
Boom/outrigger hand valve

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 103
HOME PRINT

Pressure Settings
8. Activate the enable pushbutton and the hand valve
;;;;;;;;;;;;;
@@@@@@@@@@@@@

 and read the pressure on the gauge again. Repeat
@@@@@@@@@@@@@


;;;;;;;;;;;;; WARNING 17dshopper.epsL

@@@@@@@@@@@@@


;;;;;;;;;;;;; steps (7) and (8) until the gauge reads 280-bar.
@@@@@@@@@@@@@


;;;;;;;;;;;;;
@@@@@@@@@@@@@


;;;;;;;;;;;;; 9. When the pressure is 280-bar, release the enable
@@@@@@@@@@@@@


;;;;;;;;;;;;;
Do not stand on
hopper grates.

@@@@@@@@@@@@@


;;;;;;;;;;;;; SAFETY INSTR
UCTIONS pushbutton and the outrigger hand valve.
@@@@@@@@@@@@@


;;;;;;;;;;;;;
OR
HOPPER GRATE
BEFORE REMOVING
ANY SERVICE:
PERFORMING
Electric Motors
Engines
Gasoline or Diesel 1. Stop the electric
motor.

@@@@@@@@@@@@@


;;;;;;;;;;;;;
1. Stop the engine. power
2. Lock out the

10. Remove the whip hose and gauge from the boom
key, place it to an
2. Remove the and put
source according t
in your pocket, approved lockout-tagou
a "DO NOT OPERATE" program.
tag on the switch.

@@@@@@@@@@@@@


;;;;;;;;;;;;;
3. Check accumulatorgauge
3. Check accumulator circuit pressure
gauge to verify
circuit pressure (if so equipped)
to verify
(if so equipped) zero system pressure.
zero system pressure.

WARNING
Stored hydraulic energy.
Release all hydraulic
pressure and verify zero
pressure on gauge
@@@@@@@@@@@@@


;;;;;;;;;;;;; hand valve, and replace the cap on the gauge port.
before servicing.

Setting the boom pressures


@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@@


;;;;;;;;;;;;;;;; This product is covered by one or more of the following U.S. patents:
WARNING
Stored hydraulic energy.
The boom circuit is set to a maximum of 280-bar (4060
3,409,334
3,580,696
3,640,303
3,685,543
3,741,691
3,829,251
4,019,839
4,057,373
4,178,142
4,191,513
4,260,338
4,343,598
4,373,225
4,373,875
4,392,510
4,437,817
4,465,441
4,472,118
4,556,370
4,621,375
4,681,022
4,708,288
4,852,467
4,978,073
5,066,203
5,106,225
5,106,272
5,224,654
5,257,912
5,263,828
5,281,113
5,332,366
5,346,368
5,401,140
Re. 32,041
Re. 32,657
Re. 32,719

30308020 C
Release all hydraulic
pressure and verify zero
pressure on gauge
before servicing. PSI) by the relief valve on the boom hand valve
WARNING
Clear area
before activating
assembly (Figure 103).
outriggers

FRONT FOOT REAR FOOT

17bmcntl.epsL

Relief Valve

Figure 102
Outrigger hand valve
1. Connect the whip hose of a 0400 or 0600 bar
gauge into the gauge port on the drivers side
outrigger hand valve.
2. If this is not already done, start the truck engine
and set the transmission and PTO as you would for
a pumping job.
3. Locate the 280-bar relief valve on the back of the ;;;;;;;;;;;


@@@@@@@@@@@
;;;;;;;;;;;


@@@@@@@@@@@
Ele DA
Sta ctro
vo y ba cu
NG
ER

;;;;;;;;;;;


@@@@@@@@@@@
17 ltage ck tion
fe
et wir fromhaza

drivers side boom/outrigger hand valve, as shown


(5 es hi rd
m
et at le gh .
er
s) ast
.

;;;;;;;;;;;


@@@@@@@@@@@
W
Do
m not
AR
ac
tra hi oper NIN

in Figure 102.
;;;;;;;;;;;


@@@@@@@@@@@
ne
th inin w ate G
e
m warg. Unithou this
an
ua ning ders t
ls
an s in tand
d
on safe
de ty

;;;;;;;;;;;


@@@@@@@@@@@
ca
ls.

4. Set the engine RPM to maximum.


5. Push the outrigger enable pushbutton located next
;;;;;;;;;;;


@@@@@@@@@@@
Figure 103
to the outrigger hand valves. Hold the outrigger Boom hand valves
hand valve lever in the retract position. The oil
coming from the pump has nowhere to go but over 1. Connect the whip hose of a 0400 or 0600 bar
the relief valve. gauge to the gauge port on the back of the boom
hand valve.
NOTE!
2. If this is not already done, start the truck engine
You cannot use the extend position for this
and set the transmission and PTO as you would for
adjustment because extend has a nonadjust-
a pumping job.
able secondary relief functions built into the
valve. 3. Locate the 280-bar relief valve on the back of the
boom hand valve, as shown in Figure 104.
6. The pressure on the pressure gauge should read
280-bar.
7. If adjustment is needed, turn the outside body of
the relief valve that is located at the back of the
drivers side outrigger hand valve. Turn in to raise
pressure, turn out to lower pressure.

revDate
104 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Turn body of valve


Higher to adjust.

280 bar Lower


Relief Valve

s
.ep
17
lblk
ntr
omc
bo

Figure 104
Boom control relief valve

4. Pressure out any boom cylinder except #1 in a possibility of an inattentive operators causing damage
retract position. You can pressure out a cylinder by to the boom or the A frame when folding into the
retracting a fully retracted cylinder or extending a transport position. To prevent this, there is a secondary
fully extended cylinder. The oil will have nowhere relief valve that regulates only the pressure on the #1
to go but over the relief valve. retract function. The #1 boom down pressure should be
5. Have your assistant read the pressure on the gauge 170-bar (2465 PSI). To check or adjust the down side
at the boom hand valve. It should read 280-bar. If relief valve:
no adjustment is needed, skip to Step 8. You have to raise the boom and rotate it for this
6. To adjust the boom pressure, locate the relief valve procedure, so you must set the outriggers as you would
on the back of the boom control block (Figure to pump a job. Release the boom strap. To adjust the
104). valve, you will need a 2.5 mm allen wrench and a
7. If adjustment is needed, turn the outside body of standard screwdriver.
the relief valve that is located at the back of the 1. Connect the whip hose of a 0-400 or 0600-bar
boom hand valve. Turn in to raise pressure, turn gauge into the gauge port shown in Figure 105.
out to lower pressure.
8. When the pressure is 280-bar, release the boom
hand valve.
9. Remove the whip hose and gauge from the boom
hand valve, and replace the cap on the gauge port.

Set boom section #1 down pressure


Because gravity wants to pull your boom down, high
pressure is not needed to bring section #1 down.
Allowing high pressure to be available leaves open the
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 105
HOME PRINT

Pressure Settings

170-bar gauge
port

170-bar relief
valve


;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@
 @;
@;
DA

@;@;@;@;@;@;@;@;@;@;@;@;
Ele
Sta ctr NG

@;
;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@

vo y oc
17 ltag bac utio ER
fe e w k fr n h
et o a
(5 ires m zard
m h
ete at le igh .
rs as
). t

@;@;@;@;@;@;@;@;@;@;@;@;
;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@


W
Do
m no
AR
a
tra chint op NIN
th inin e w erate
m e wa g. U ith
an o this
G
ua rnin nde ut
ls g rs
an s in tan

;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@


d
on safe d

@;@; @;@;@;@;@; @;@;


de ty
ca
ls.

;;;;;;;;;;;;;;;;
@@@@@@@@@@@@@@@@


@;@;@; @;(Hoses @;@;@; @; abbreviated for clarity)
Figure 105
Section #1 down relief valve

NOTE! screwdriver until the pressure reads just under 170-


For the following procedure, we must bring bar. Retightening the set screw will raise the
section #1 all the way down until the cylin- pressure slightly. (If it becomes a problem, hold the
der bottoms out. The cylinder does not bot- cartridge adjustment with the screwdriver while
tom out if you set the folded boom into the you tighten the set screw.) Recheck the pressure,
A-frame (travel position). Position the boom and readjust if needed.
so this can be done without hitting the 5. When the pressure is set at 170-bar, remove the
truck, electrical wires, or any other obsta- whip hose gauge and replace the cap on the gauge
cles. port.
2. Unfold section #2 from section #1 until it is 6. The boom pressure setting sequence is complete. If
straight. you are finished with the boom, slew it back into
3. Bring section #1 down until the cylinder is the transport position, and lower #1 into the A-
completely bottomed out. Activate the #1 down frame cradle. Reattach the boom strap.
(retract) hand valve. The boom will not be able to
move because the cylinder is already bottomed out. Setting water pump pressure
Read the pressure on the gauge that you just The agitator/water pump-compressor circuit has a
installed. It should read 170-bar. If no adjustment maximum pressure of 200-bar (2900 PSI), limited by
is necessary, skip to Step 7. the relief valve located in the water pump-compressor
4. If adjustment is needed, loosen the set screw with hand valve. There is a gauge port for checking or
the 2.5 mm allen wrench. While you activate #1 setting the pressure in this circuit. The port is located
down, adjust the relief cartridge with the on the water pump-compressor hand valve.

revDate
106 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
To set the water pump circuit pressure perform the
following steps: Turn body of valve
1. Stop the unit, and put the key in your pocket. to adjust.
200 bar Higher
2. Connect the whip hose of a 0-400 or 0-600 bar
gauge to the gauge port on the water pump hand
Relief Valve Lower
valve.
3. If your unit does not have a compressor, skip to
Step 6.
4. If your unit has a compressor remove one of the
hoses from the water pump motor and plug the
hose and the open fitting with approved hydraulic
dead plugs. Do not improvise on these plugs. If
you dont have any, contact Schwings Spare Parts
Department and order them before continuing with
this procedure. You will need: pv
lv1
7.E
PS

p/cm
Qty 2 VS-16S locking plugs, part number wtrpm

10016803
Qty 1 GS-16S straight fitting, part number Figure 106
10008088 Water pump relief valve
Qty 2 16S capnuts, part number 10001743 9. If adjustment is needed, turn the outside body of
All of these fittings and many, many more the relief valve that is located at the bottom of the
extremely useful items are included in the water pump/compressor hand valve. Turn in to
Troubleshooting Kit, part number 30308553. raise pressure, turn out to lower pressure.
We highly recommend purchase of this kit. It 10. When the pressure is set to 200-bar, stop the engine
will pay for itself many times over. and remove the key.
5. Be sure that one of the locking plugs and capnuts 11. Remove the dead plugs and store in a clean area or
are tightened on the straight fitting and that the in a plastic bag or something similar to keep dirt
dead plugs are securely tightened to the hose and from entering the fittings. Re-attach the hose to the
the open motor fitting. water pump motor fitting and tighten securely.
6. Locate the relief valve on the water pump hand (Torque is correct if you make one complete
valve. It comes out of the valve body toward the revolution after feeling initial resistance increase.)
ground, and it is the smaller of the two cartridges 12. Remove the whip hose and pressure gauge.
that youll see. Replace the gauge port cover.
7. Be sure that any personnel are clear, and restart the
engine. Setting the agitator pressure
8. Activate the water hand valve by pushing or The agitator circuit has a maximum pressure of 150-
pulling the handle. This will send the oil against bar (2175 PSI), limited by the relief valve located in
the high pressure plug. The oil will have nowhere the agitator hand valve (Figure 107). There is a gauge
to go, so it will return to the tank over the relief port for checking or setting the pressure. The port is
valve in the water pump hand valve. The pressure located on the agitator hand valve.
at which it relieves can be seen on the gauge. It 1. Stop the unit, and put the key in your pocket.
should read 200-bar. If no adjustment is needed,
2. Connect the whip hose of 0-400 or a 0600-bar
skip to Step 10.
gauge to the gauge port on the agitator hand valve.
3. If your unit is equipped with a agitator shut off
valve, close it (Figure 107). Skip to Step 6.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 107
HOME PRINT

Pressure Settings
valve in the agitator hand valve. The pressure at
which it relieves can be seen on the gauge. It
should read 150-bar.
agit.shutoff.eps

12. If adjustment is needed, turn the outside body of


the relief valve that is located at the back of the
agitator hand valve. Turn in to raise pressure, turn
out to lower pressure.
13. When the pressure is set at 150-bar, stop the engine
and remove the key. Open the shut off valve or
remove the dead plugs and store in a clean area or
in a plastic bag or something similar to keep dirt
from entering the fittings. Reattach the hose to the
agitator motor fitting and tighten securely. (Torque
is correct if you make one complete revolution
after feeling initial resistance increase.)
Figure 107
Agitator shutoff valve 14. Remove the whip hose and pressure gauge.
Replace the gauge port cover.

4. If your unit is not equipped with an agitator shut


off valve, remove one of the hoses from the
agitator motor and plug the hose and the open
fitting with approved hydraulic dead plugs. Do not
improvise on these plugs. If you dont have any,
contact the Schwings Spare Parts Department and
order them before continuing with this procedure.
All of these fittings and many, many more
extremely useful items are included in the
Troubleshooting Kit, part number 30308553. We
highly recommend purchase of this kit. It will pay
for itself many times over. You will need:
5. - Qty 2 VS-16S locking plugs, part number
10016803
6. - Qty 1 GS-16S straight fitting, part number
10008088
7. - Qty 2 16S capnuts, part number 10001743
8. Be sure that one of the locking plugs and capnuts
are tightened on the straight fitting and that the
dead plugs are securely tightened to the hose and
the open motor fitting.
9. Locate the relief valve on the agitator hand valve. It
comes out of the valve body toward the ground,
and it is the smaller of the two cartridges that
youll see.
10. Be sure that any personnel are clear, and restart the
engine.
11. Activate the agitator hand valve by pushing or
pulling the handle. This will send the oil against
the high pressure plug. The oil will have nowhere
to go, so it will return to the tank over the relief
revDate
108 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
KVM 28X 1. Locate the agitator shutoff valve, and close it
(Figure 1). The general location of the agitator
shutoff valve is shown in Figure 1.
Check all hydraulic pressures
Check all hydraulic pressures. Changes in pressures NOTE!
can indicate trouble in one or more components. If your unit does not have a shutoff valve,
order one using part #10004680 (valve) and
NOTE! #30303432 (tube). Contact the Schwing
Hydraulic pressure settings shown in the Service Department for installation
following procedures are for a 2023 twin instructions. If you cant wait for a shutoff
circuit pump kit. However, because valve, you will need to remove one of the
different pump kits may be used in this unit, hoses from the agitator motor, and plug the
all pressure settings should be verified with hose and the open fitting with approved
the pressure settings shown on the hydraulic dead plugs. Do not substitute
applicable hydraulic schematic. The other plugs, such as a steel bearing, inside a
hydraulic schematics for your pump kit are cap fitting.
in the Appendix of this manual. 2. Position the agitator lever in the forward or reverse
If you wish to order a CD ROM which explains the position. The agitator will not be able to turn, and
pressure setting procedure for a specific model (all the oil will be forced over the relief valve.
pumpkits), call SAI Spare Parts Department at (800) 3. At idle speed (about 600 RPM), about 4.5
328 - 9635 and request the CD using the following part horsepower is being converted to heat. Position the
numbers: agitator lever to the off (center) position when the
61/58 meter. . . . . . . . . . . . . . . . . . . . . . . 30365860 temperature gauge on the rear control panel
52 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30354732 indicates 50C.
45/47 meter. . . . . . . . . . . . . . . . . . . . . . . 30356770 4. Open the agitator shutoff valve or remove the plug,
42 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30355485 and reconnect the hose to the agitator motor.
39 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30365861 52qrttrn.epsL
Closed
34 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30356772
32 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30355486
31 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30365862
Read all of the instructions before beginning any
pressure settings. You will need an assistant for parts of
the procedure.
You and any assistants should wear eye protection Shown in the
when checking or setting pressures. open position
Be sure that the waterbox covers are installed on the
waterbox. Figure 1
We do not recommend using the remote control box for Agitator shutoff valve
the following procedures.
Wear safety glasses when setting pressures.
Position the remote/local switch on the rear control
panel to the local position.
Pressure settings must be made with the oil at normal
operating temperatures (40C 60C). The agitator
circuit must be used to heat the hydraulic oil. Do not
jam the paddles to force the oil over relief by stopping
the movement of the agitator. To preheat the hydraulic
oil using the agitator circuit, follow these instructions:

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 109
HOME PRINT

Pressure Settings
NOTE! The general location of the components used to check
Depending on the type of pumpkit and or set hydraulic pressures are shown in Figure 2.
original or current production, your
concrete pump unit may or may not have all
the components shown in Figure 2

Boom (Section #1) Down


Side Pressure Relief Valve Boom Hand Valves and Gauge
and Gauge Port Port
Water Pump/Compressor Hand
Valve and Gauge Port E-Stop Manifold Valves and
Gauge Ports
Electric Stroke Limiter and
Pressure Reducing Control Boom/Outrigger Hand Valve
Block(s) and Gauge Port plus Agitator
Soft Switch Shutoff Valve Hand Valve and Gauge Port
(twin circuit)
Concrete pump forward/reverse
Dampener Valve (single and Agitator Hand Valves
circuit)

Concrete Pump Shutoff Soft Switch and Concrete


Valve Pump Relief Valves
Outrigger Hand Valve
Outrigger Hand Valve and
Gauge Port
Concrete Pump Pressure Gauge
Accumulator Unloading
Manifold Valve and Gauge
(twin circuit)
Rear Control Panel
Electric Agitator Switch

Agitator Shutoff Valve Accumulator Pressure Gauge


(twin circuit)

Figure 2
General location of components
used to set hydraulic pressures

revDate
110 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Set the concrete pump main relief valve 8. Use the concrete pump forward/neutral/reverse
(single- circuit) switch to put the pump into the forward position.
The unit will stroke only once, then the rock
The BPL 1200 concrete pump is designed to operate at cylinder will retract. Oil will have nowhere to go
a maximum pressure of 300 bar (4350 PSI). It is except over the concrete pump main relief valve.
controlled by the main relief valve (Figure 3). The
9. Read the pressure on the concrete pump pressure
main relief valve is located at the front of the control
gauge, located on the main control block. It should
block (towards the truck cab). To check or set the main
read 300 bar. Position the throttle switch to the
relief pressure, perform the following steps:
neutral position. If no adjustment is needed, skip
to Step 12.

Mount bolt and washer


removed for illustration

grooves2.eps

Grooves in handle should


line up with grooves
in valve shaft
Lower Raise
pressure pressure

gray valve.eps

Figure 3
Main relief valve (single circuit)
1. Be sure that the waterbox covers are installed on
the waterbox. We do not recommend using the
remote control box for the following procedure.
2. Wear safety glasses when setting pressures.
3. Close the concrete pump shutoff valve (Figure 80).
quarter turn.eps

4. Position the remote/local switch, on the rear


control panel, to the local position. Figure 4
5. Use the throttle switch, on the rear control panel, to Concrete pump shutoff valve
rev the engine up to full RPM. (single circuit)
6. Make sure the manual stroke limiter valve and the
10. If adjustment is required, loosen the jam nut on the
dampener valve are turned, counterclockwise, all
relief valve adjusting screw with a 13-mm spanner
the way out.
wrench (Figure 3).
7. If the unit is equipped with an electric stroke
11. Turn the adjustment knob on the relief valve to
limiter, turn the control knob clockwise to the
adjust the pressure. Turn the adjustment knob in
maximum output (+) position.
(clockwise) to raise pressure and out (counter
clockwise) to lower the pressure.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 111
HOME PRINT

Pressure Settings
12. Retighten the jam nut. (Tightening the jam nut 3. Close the concrete pump shutoff and soft switch
tends to raise the pressure. If this happens, hold the shutoff valves (Figure 5).
adjustment knob while tightening the jam nut.) 4. Position the remote / local switch on the rear
13. Put the concrete pump into the forward position control panel to the local position.
again. The machine will not stroke this time, but 5. Use the throttle switch on the rear control panel to
will develop maximum pressure. Read the pressure rev the engine up to full RPM.
on the control block pressure gauge. If more
6. Use the concrete pump forward/neutral/reverse
adjustment is needed, return the pump to neutral;
switch to put the pump into the forward position.
then repeat Steps 8 through 11 until the pressure is
The unit will stroke only once, then the rock
at 300 bar. Position the throttle switch to the
cylinder will retract. Oil will have no where to go
neutral position.
except over the concrete pump main relief valve.
14. Open the shutoff valve. The unit will not stroke
7. Read the pressure on the concrete pump pressure
with the shutoff valve closed.
gauge located on the main control block. It should
NOTE! read 350 bar. Position the concrete pump switch to
If you cannot adjust the pressure up to 300 the off (neutral) position. If no adjustment is
bar, you have a problem. In this case, turn needed, skip to Step 11.
the adjustment knob out by several turns so
that your pressure isnt too high once the 8. If adjustment is needed, use a 9/16 inch spanner
problem is found. Contact Schwing wrench, to loosen the jam nut on the main relief
Americas Service Department for advice on valve adjusting screw (Figure 5).
how to continue. 9. Insert a 5/32 inch allen wrench in the adjustment
screw. Turn the screw in to raise pressure or out to
Set the concrete pump main relief valve
lower the pressure.
(twin circuit) 10. Once the pressure is correct (350 bar) retighten the
The main relief valve is the primary pressure control jam nut. Tightening the nut tends to raise the
device on units equipped with Rexroth A7VO pressure, so check pressure again after tightening.
hydraulic pumps. This pump is designed to operate at a Verify the correct pressure setting (350 bar).
maximum pressure of 350 bar (5075 PSI). 11. Open the concrete pump shutoff valve and soft
switch shutoff valves. The unit will not stroke with
these valves closed.
WARNING
Hot oil expulsion hazard. Stand away
from pumpkit when checking hydraulic
pressures.
W008.eps

NOTE!
The main relief valve is set to very high
pressure (at least 350 bar). Use the controls
on the rear control panel when checking the
pressure of the main relief valve, so you will
be out of the way if a hose or a fitting
malfunctions.
Refer to Figure 5 for the location of the components
used to set the concrete pump pressures. Use the
following steps to set the main relief valve pressure:
1. Be sure that the waterbox covers are installed on
the waterbox. We do not recommend using the
remote control box for the following procedure.
2. Wear safety glasses when setting pressures.
revDate
112 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
w

Gauge port

Hif
lrv
vw
.ep
s

Main relief valve

Soft switch
relief valve

Mount bolt and washer


Soft switch removed for illustration
shutoff valve

grooves2.eps

Concrete pump Grooves in handle should


hif
shutoff valve low
brn line up with grooves
.ep
s
in valve shaft

Figure 5
Location of the main relief valve

Set the soft switch circuit relief pressure 3. If adjustment is needed, loosen the jam nut on the
To check or adjust the soft switch pressure setting, soft switch relief valve with a 9/16 inch spanner
proceed as follows: wrench. Adjust the pressure up or down, as needed,
using a 5/32 inch Allen wrench. When the correct
1. Close the concrete pump shutoff valve. Open the pressure is achieved, re-lock the jam nut.
soft switch shutoff valve. The rest of the unit
should still be set up as though you were going to 4. Be sure to open the concrete pump shutoff valve
check concrete pump pressure. when you are finished. The unit cannot stroke with
this valve closed.
2. Increase the engine RPM to pressure out the
concrete pump. The pressure gauge should read 80 Set accumulator circuit hydraulic oil
bar (check your schematic). If no adjustment is
pressure
needed, skip to Step 4.
(units with a pressure- compensated pump)
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 113
HOME PRINT

Pressure Settings
You will need an assistant for parts of this procedure. .
To check or adjust the hydraulic pressure in the
accumulator circuit, perform the following steps:
1. Stop the truck, put the key in your pocket, and
place a Do Not Operate sign on the windshield.
2. Loosen the jam nut on the pressure regulator of the
accumulator hydraulic pump. Turn the screw in
Accumreg.eps
two-and-a-half turns. This will raise the regulator
pressure above 300 bar (Figure 83).
NOTE!
If your unit is a current production model
(Figure 6), skip Steps 3,4, and 8 of this
procedure.
Accumulator pump
pressure regulator

Figure 7
Accumulator pump pressure regulator

3. Connect the whip hose of a 0-600 bar gauge into


no
ca
rt.ep
s
the gauge port of the E-Stop manifold (Figure 84).
4. Loosen the jam nut on the accumulator circuit
relief valve, located on the E-Stop manifold. Turn
the screw in two turns. This will raise the relief
setting above 300 bar (Figure 84).

estopleft.epsL

Figure 6 Relief Valve and


E-Stop manifold Gauge Port
(current production)

Figure 8
E-Stop manifold relief valve
accumulator circuit (original
production)

5. Clear all personnel away from the drive lines, start


the truck engine, engage the pumps, and bring the
engine RPM to maximum.
revDate
114 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
6. Read the pressure on the accumulator circuit gauge 8. You will need an assistant for this step. With the
(Figure 9). Pressure should read 300 bar (4350 engine still running, adjust the relief valve on the
PSI). If no adjustment is needed, skip to Step 8. E-Stop manifold. Back out the adjustment screw
until pressure reads 260 bar (3771 PSI) on the
gauge connected to the E-Stop manifold.
accumgag.eps

WARNING
Entanglement hazard. Stop drive shafts
before adjusting the accumulator pump
pressure regulator.

W010.eps
9. After the truck engine is stopped, back out the
accumulator circuit hydraulic pump pressure
regulator two-and-a-half-turns. This restores the
pressure regulator to its original setting (Figure
83).
10. Clear all personnel from the drive line area, start
the truck, and rev the engine RPM to maximum.
11. Read the pressure on the accumulator gauge. It
Figure 9 should read 200 bar (2900 PSI).
Accumulator pressure gauge 12. If additional adjustment is needed, you must stop
the truck engine each time you approach the
accumulator circuit hydraulic pump (Figure 83).
7. If additional pressure adjustment is needed, locate
Adjust the accumulator pump pressure regulator
the accumulator manifold pressure relief valve
screw in to increase pressure or out to decrease
(Figure 85). Loosen the jam nut, and turn the screw
pressure. Lock the jam nut when pressure is correct
in to increase pressure or out to decrease pressure.
(200 bar).
Tighten the jam nut when pressure is at 300 bar.
Setting the outrigger pressure
45s3blck.eps

With a seven place hand valve, the boom/outrigger


selector valve is inside the boom control block. This
valve is activated when the outrigger enable push
button is pushed. There is not a separate relief for this
circuit and, therefore, nothing must be set.
The outrigger circuit is set to a maximum of 280-bar
(4060 PSI) by the relief valve located on the passenger
side outrigger hand valve assembly (Figure 11). The
valve routes the oil to the two outrigger hand valve
banks, one on each side of the unit. A relief valve
inside the passenger side bank limits the entire
Relief Valve outrigger circuit to 280-bar.
NOTE!
On some pump units the relief valve may be
Figure 10 in a slightly different location (opposite side)
Accumulator manifold pressure relief than shown in Figure 11.
valve

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 115
HOME PRINT

Pressure Settings
6. When the pressure on the gauge connected to the
outrigger hand valve is 280-bar, release the enable
280 bar push button and the outrigger hand valve.
Lower Relief Valve 7. Remove the whip hose and gauge from the
outrigger hand valve, and replace the cap on the
gauge port.
Higher Pressure reducing valve
This valve is preset at the factory. Contact Schwing
Turn body of valve Americas Service Department at (651) 429-0999 for
to adjust. information on checking or setting this valve.

Electric stroke limiter


Figure 11 This valve is preset at the factory. Contact Schwing
Outrigger hand valve Americas Service Department at (651) 429-0999 for
information on checking or setting this valve.
1. Connect the whip hose of a 0400 or 0600 bar
gauge to the gauge port on the back or side of the
Load-sensing boom pressures
passenger side outrigger hand valve (Figure 11).
(7 place proportional circuit)
2. If this is not already done, start the truck engine
and set the transmission and PTO as you would for If your unit has a load-sensing proportional system, it
a pumping job. will have different pressure adjustments than if it is
equipped with a black and white boom system. The
following instructions are for load-sensing proportional
WARNING systems. If you have a unit equipped with a black and
white boom system, contact Schwing America Service
Tipping hazard. Never set outrigger Department for the correct instruction pages.
pressures with the boom unfolded.
In a black and white boom system, the hydraulic pump
Pressure setting procedure requires
puts out an unchanging amount of oil, and speed
retraction of an outrigger jacking
control is done by restricting the oil to certain functions
W026.eps

cylinder.
with orifices. In a load-sensing system, the pump puts
out more or less oil to respond to the needs of the
3. Set the engine RPM to maximum.
system. Generally, the pump puts out enough oil to
4. Push the outrigger enable pushbutton located next maintain a 20 bar higher pressure at the pump than
to the outrigger hand valve (passenger side). Hold what the cylinders actually require. This 20 bar is
an outrigger hand valve lever in the jacking-retract called delta P (P). Additionally, we set the hydraulic
position. The oil coming from the pump has pump so that it always puts out a small amount of oil,
nowhere to go but over the outrigger relief valve. even if no oil is needed for the system. This oil is used
NOTE! to ensure that you have control when you need it. The
You cannot use the extend position for this setting to maintain this minimum amount of oil is
adjustment because extend has a called Q-min (pronounced cue min). To set the boom
nonadjustable secondary relief function or outrigger hydraulic pressures on a load-sensing
built into the valve. system, begin by setting Q-min and P.
5. Turn the outside body of the relief valve cartridge The general locations of the components used to set
that is located at the back of the passenger side boom hydraulic pressures is shown in Figure 12.
outrigger hand valve (Figure 11). Turn in
(clockwise) to raise pressure; turn out (counter NOTE!
clockwise) to lower pressure. Do not adjust P or Q-min if your boom is
operating as you like it. The pressure setting
procedure uses a standard starting point

revDate
116 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
and must be fine tuned from there. It was NOTE!
fine tuned at the factory and should not be Each time the Q-min screw must be
adjusted unless absolutely necessary. adjusted, the engine must be stopped, or at
least the transmission must be taken out of
gear so that the drive lines stop turning.

WARNING
Entanglement hazard. Stop drive shafts
before adjusting Q-min.

W009.eps

Boom Hand Valves E-Stop Manifold P Regulator Q-min Adjust Screw

Figure 12
Location of components used to
check or set boom pressures

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 117
HOME PRINT

Pressure Settings

140 bar gauge port (use 0-400


bar gauge when checking)

140 bar downside


relief cartridge
0-400 bar
gauge port
0-60 bar
gauge port

boom control
ps
block relief valve
v.e
itprd
ap

15 bar pretension
adjustment screw

Figure 13
Boom hand valves

Check or set Delta-P adjusted by a screw on the boom hydraulic pump


To check or set P, follow these steps: (Figure 14). Turn the Q-min adjustment screw out
(counterclockwise) three full turns.
1. Stop the truck engine, and place a Do Not
Operate sign on the truck windshield. 4. Check that all personnel are clear of the truck, then
restart the engine, engage the pumps, and leave the
NOTE! engine at an idle. Pressure should read 20 (1) bar.
When checking Delta-P, it is important to 5. Increase the throttle RPM, and the P pressure
note that you will be installing a low
pressure gauge into a high pressure port. should remain the same. If the pressure fluctuates
Any activation of a boom function or with a change in engine RPM, you are probably
activation of an E-stop button will damage still reading Q-min. The Q-min adjustment screw
the low pressure gauge. will need to be turned out more.
2. Install a 0-100 bar gauge in the 0-400 bar gauge 6. If no adjustment is needed, turn the Q-min
port of the manual boom handvalves. Take care not adjustment screw in (clockwise) three full turns or
to accidently install the gauge in the 0-60 bar port whatever amount it was turned out.
(Figure 13). 7. If adjustment is needed, continue to Step 8.

WARNING
Entanglement hazard. Stop drive shafts
before adjusting Q-min.
W009.eps

3. To ensure that the pump is putting out only enough


oil needed to maintain P, we need to change the
setting of the Q-min adjustment screw. Q-min is
revDate
118 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Check or set Q-min
Q-min
adjustment screw Q-min pressure is checked when the engine is at the
maximum specified RPM, but must be adjusted with
the engine stopped. To check or set the Q-min, follow
these steps:
1. Install a 0-600 bar gauge in the 0-400 bar gauge
port of the manual boom handvalves. Take care not
to accidently install the gauge in the 0-60 bar port.
Qminscrew.eps (Figure 13).
Q-max 2. Clear all personnel away from the drive lines, start
the truck engine, engage the pumps, and bring
Figure 14 engine RPM to max. All boom functions must be
Q-min adjust screw in neutral, and all emergency stop buttons
should be up (not engaged).
8. Delta P is adjusted by the P screw on the P
regulator (Figure 15). The location of the P
regulator valve is shown in Figure 12. Loosen the
jam nut, and adjust the screw in to increase WARNING
pressure or out to decrease pressure until it is set at
Entanglement hazard. Stop drive shafts
20 bar (1). Contact Schwing Americas Service
before adjusting Q-min.

W009.eps
Department if you are unable to adjust the pressure
to specification.
NOTE!
If the boom does not operate smoothly at 20
bar, you must fine tune the adjustment.
9. Remove the gauge, and adjust P until the boom is
responsive and smooth. When done, the gauge
3. Read the pressure on the 0 - 600 gauge. If the
(reinstalled) must read between 14 and 25 bar. The
pressure reads less than 100 bar, return the engine
electronics in the control system can also affect
RPM to idle speed and install a 0 -100 bar gauge. If
how the boom operates, so if P adjustment does
the pressure reads more than 100 bar, stop the drive
not seem to help, reset to 20 bar and check the
shafts from turning, and turn the Q-min adjustment
electrical settings. Once electrical settings are
screw in until the pressure is below 100 bar, then
verified, you could again refine the boom action
install the 0 - 100 bar gauge.
with the P adjustment. Caution! Do not operate
any functions while setting P. 4. Bring the engine RPM to maximum. Q-min
pressure should read 40 - 45 bar.
10. When P has been set, remove the 0-100 gauge.
5. If no adjustment is needed, stop the drive lines
from turning. Tighten the jam nut on the Q-min
adjustment screw. Remove the 0-100 gauge.
6. If adjustment is needed, continue to Step 7.
deltaPvlv.eps

7. Turn the Q-min screw in to raise the pressure


P adjust (Figure 14). Turn it out to lower the pressure. Be
T screw sure that you stop the drive shafts from turning
each time before making the adjustment. When
Figure 15 pressure is correct (40-45 bar), tighten the jam nut
P regulator valve on the Q-min adjustment screw. Remove the 0-100
bar gauge.

Set boom pressures


(load sensing proportional booms)
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 119
HOME PRINT

Pressure Settings
Now that P and Q-min are set, you can check or set 2. The redundant relief valve located in the
the boom valve pressures. There are three pressure emergency stop manifold, set at 320 bar (4640
settings on the boom circuit (Figure 16): PSI).
1. Pressure regulator (the high-pressure adjustment 3. The boom control block relief valve, set at 350 bar
screw on the P regulator valve), set at 290 bar (5075 PSI).
(4205 PSI).

P Regulator Valve
(high pressure
adjustment screw)

0-400 bar
gauge port
0-60 bar
gauge port

s deltaPvlv.eps
.ep
nly
ipo
ap
boom control T
block relief valve

estop/right.eps
E-Stop Manifold
Redundant Relief Valve

ps
rt.e
ca
no

Original Production
Current Production

Figure 16
Boom hydraulic pressure adjustment components

To check the setting of the valve with the highest two:


pressure, you must first raise the pressure of the lower
revDate
120 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
1. Loosen the jam nut of the high pressure adjustment specified after following the instructions, contact
screw on the P regulator. Turn the screw in two- Schwing Americas Service Department at (651)
and-a-half turns. This will raise the pressure on the 429-0999 for advice on how to continue.
P regulator above 350 bar.
2. Loosen the jam nut of the adjustment screw on the Set the down side relief valve pressure
E-stop manifold redundant relief valve. Turn the This valve is a secondary relief valve for the #1
screw in one-and-a-half turns. This will raise the cylinder retract function (Figure 17). Proper
pressure setting of the relief valve to above 350 bar. adjustment ensures that the #1 boom and the A-frame
3. Pressure out any boom cylinder except #1 down by wont be damaged by putting the boom in the cradle.
pushing or pulling the control handle. To pressure To adjust this valve requires a 2.5 mm Allen wrench
out a cylinder, retract a fully retracted cylinder or and a standard screwdriver. Set the pressure of the 140
extend a fully extended cylinder. The oil is forced bar down side relief valve using the following steps:
over the relief valve. 1. Install a 0 - 400 bar or 0 - 600 bar gauge into the
4. The tell tale hiss of an open relief valve should be 140 bar gauge port (Figure 17).
coming from the Apitech control block relief valve 2. Unfold the #2 section from #1 until it is straight.
now. If it isnt, raise the setting of the other For the following procedure, we must bring #1 all
pressure devices until the hiss originates at the the way down until the cylinder bottoms out.
Apitech control block relief valve. Read the Position the boom so this can be done without
pressure on the gauge connected to the 0-400 bar hitting the truck or any other obstacle.
gauge port on the boom hand valve block. It should 3. Bring #1 down until the cylinder is completely
read 350 bar. If pressure is correct, proceed to Step bottomed out. The cylinder does NOT bottom out
5. if you are setting the folded boom into the A-frame
NOTE! (travel position).
Although the pressure specification for the 4. Activate the #1 down (retract) hand valve. The
Apitech relief valve is 350 bar, you may boom will not be able to move because the cylinder
continue to use the relief valve as long as the is already bottomed out. Read the pressure on the
cartridge maintains at least 330 bar. If you gauge that you just installed. It should read 140 bar
must replace the valve, proceed to Step 5
before using the concrete pump again, and (2030 PSI). If no adjustment is necessary, skip to
re-do this entire procedure when you have Step 6.
installed the new valve. If pressure on the 5. If adjustment is needed, loosen the set screw of the
Apitech relief valve is below 290 bar, you 140 bar relief valve with the 2.5 mm allen wrench.
should not use the concrete pump until the
valve is replaced. While you activate #1 down, adjust the relief
cartridge with the screwdriver until the pressure
5. Screw out the E-Stop manifold redundant relief reads just under 140 bar. Retighten the set screw.
valve adjustment screw one-and-a-half turns. The pressure may raise slightly. Recheck the
Pressure out any boom cylinder except #1 down, pressure, and readjust if needed.
and read the gauge. Pressure should read 320 bar.
If it does not, turn the screw in to raise pressure or 6. When the pressure is set at 140 bar with the set
out to lower pressure until it is set at 320 bar. If the screw tight, you can remove the whip hose gauge
location of this valve causes you to be near the and replace the cap on the gauge port.
drive lines, be sure to stop them from turning 7. The boom pressure setting sequence is complete. If
before accessing the valve. you are done with the boom, slew it back into the
6. You will need a helper for this step. While transport position. Lower section #1 into the
pressuring out any boom cylinder except #1 down, cradle, and attach the boom transport strap.
have your helper adjust the high pressure screw of
the P regulator out (lowering the pressure) until
the gauge reads 290 bar. Release the pressurized
function, and lock the jam nut. The boom pressures
are now set. If you did not get the readings

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 121
HOME PRINT

Pressure Settings

140 bar
gauge port

140 bar relief valve

Figure 17 0.e
ps
it14
140 bar relief valve and gauge ap

port

Pretension
gauge port

Figure 18 .ep
s
rtn
itp
Pretension adjustment screw ap

and gauge port Pretension adjustment screw

Set 15 bar pretension 3. If adjustment is needed, loosen the jam nut on the
To check or set pretension, follow these steps: pretension valve (Figure 18). Turn the screw in to
raise pressure and out to lower pressure. When the
1. Stop the truck engine. Plug the 0 - 40 bar gauge pressure is correct, retighten the jam nut.
into the pretension check port of the Apitech
handvalve (Figure 18). 4. Stop the engine, and remove the 0 - 40 bar gauge.
Pretension setting is complete.
2. Start the truck engine, but leave it at an idle.
Pretension adjustment is made at an idle to Set water pump pressure
establish the minimum pressure setting. (Note: As
RPM is increased, pretension pressure will rise.) With a seven place hand valve, the water pump
Read the pressure on the gauge. If it reads 15 bar hydraulic control is inside the boom control block.
1 bar, the pressure is set correctly. There is not a separate relief valve for this circuit and,
therefore, nothing that must be set.

revDate
122 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Set the agitator pressure fittings and many, many more extremely useful
The agitator circuit has a maximum pressure of 200 bar items are included in the Troubleshooting Kit, part
(2900 PSI), limited by the relief valve located on the number 30308553. We highly recommend
passenger side of the main control block (Figure 19). purchase of this kit. It will pay for itself many
times over. You will need:
Agitator Relief Valve Turn body of valve - Qty 2 VS-16S locking plugs, part number
10016803
Gauge port to adjust
Higher - Qty 1 GS-16S straight fitting, part number
10008088
Lower - Qty 2 16S capnuts, part number 10001743
5. Be sure that one of the locking plugs and capnuts
are tightened on the straight fitting and that the
dead plugs are securely tightened to the hose and
the open motor fitting.
6. Locate the relief valve on the back of the agitator
hand valve.
itrlf
2.e
ps 7. Be sure that all personnel are clear, and restart the
ag
engine.
8. Activate the agitator hand valve by pushing or
Figure 19 pulling the handle. This will send the oil against
Agitator hand valve the high pressure plug. The oil will have nowhere
to go, so it will return to the tank over the relief
1. Stop the unit, and put the key in your pocket. valve in the agitator hand valve. The pressure at
2. Connect the whip hose of a 0-400 or a 0600-bar which it relieves can be seen on the gauge. It
gauge to the gauge port on the agitator hand valve should read 200-bar.
(Figure 19). 9. If adjustment is needed, turn the outside body of
3. If your unit is equipped with an agitator shutoff the relief valve that is located at the back of the
valve, close it (Figure 20). Skip to Step 5. agitator hand valve. Turn in to raise pressure or
52qrttrn.epsL
turn out to lower pressure.
Closed 10. When the pressure is set at 200-bar, stop the engine
and remove the key. Open the shutoff valve or
remove the dead plugs, and store them in a clean
area like a plastic bag or something similar in order
to keep dirt from entering the fittings. Reattach the
hose to the agitator motor fitting, and tighten
securely. (Torque is correct if you make one
Shown in the complete revolution after feeling initial resistance
open position increase.)
11. Remove the whip hose and pressure gauge.
Replace the gauge port cover.
Figure 20
Agitator shutoff valve

4. If your unit is not equipped with an agitator shutoff


valve, remove one of the hoses from the agitator
motor, and plug the hose and the open fitting with
approved hydraulic dead plugs. Do not improvise
on these plugs. If you dont have any, contact
Schwings Spare Parts Department and order them
before continuing with this procedure. All of these
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 123
HOME PRINT

Pressure Settings

revDate
124 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
S 31 XT handle as well as on the handle itself, which will
indicate the open or closed configuration of the
valve (Figure 108). If the handle is removed from
Check all hydraulic pressures
the agitator shutoff valve (Figure 108) or the
Changes in pressure can indicate trouble in one or concrete pump shutoff valve (Figure 110) and
more components and will serve as early warning replaced in a different configuration, the grooves in
indicators if you check them on a regular basis. The the handle may no longer indicate the proper open/
specifications for each circuit are shown on the closed orientation of the valve. The grooves in the
hydraulic schematics found in the Appendix section of shaft give the only true indication of the valves
this manual. The hydraulic schematics are the only position.
documents in this manual that have been updated
specifically for your unit, by the serial number, so in NOTE!
each of the following procedures you will be told to If your unit is an early production model
refer to the schematic for the pressure required. and does not have an agitator shutoff valve,
order one from the Schwing Spare Parts
Preheat the hydraulic oil Department, using part number 10004680
(valve) and number 30303432 (tube).
Pressure settings must be made with the oil at normal
Contact the Service Department for
operating temperatures (50 to 60 C). In the past we
installation instructions.
could pressure out a function in the boom or outrigger
system to create heat, but today, load sensing systems 2. Activate the agitator. With the valve closed, the
no longer allow maximum oil flow to be forced over agitator will not be able to turn and the oil will be
relief. Because of this, the agitator circuit must be used forced over the relief valve. At an idle (about 600
to heat the hydraulic oil. RPM) you will be converting 4.5 horsepower to
To heat the oil to operating temperature: heat.
1. Locate the agitator shutoff valve (Figure 108), and 3. When the oil temperature gauge shows 50 C, open
close it. The quarter turn shutoff valve has a the shutoff valve.
grooved line on the shaft or pivot point of the

Grooves in handle Closed


000174.eps
Agitator quarter turn
shutoff valve (open position)
Grooves in shaft 000273.eps

Motor Open
Mounting screw and washer
removed for illustration
Figure 108
Agitator shutoff valve (left) and Open/closed orientation of shutoff valve (right)

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 125
HOME PRINT

Pressure Settings
Check the concrete pump pressure -4 8. Place the concrete pump forward / neutral /
pumpkits reverse switch on the rear control panel into the
forward position. The unit will stroke no more
than once, then the rock cylinder will retract. Oil
leaving the hydraulic pumps will be blocked in the
WARNING brain. This is called high-pressuring the concrete
pump.
Wear safety glasses any time you check 9. Read the pressure on the gauge. The target pressure
or set pressures. Oil expulsion hazard!

000438.eps
for the concrete pump circuit main relief valve is
shown on the hydraulic schematic in the Appendix
section of this manual. Return the pump control to
neutral whether the pressure needs adjustment or
Because the Hi-flow pumpkits have the ability to create
not. If no adjustment is needed, skip to step 14. If
high pressure on the concrete, the pressure settings
adjustment is needed, proceed to next paragraph.
have to be tailored specifically for each model. This
means that we cannot simply list a pressure
Setting the main relief valve
specification for all units. The correct pressure
specifications for your unit are shown on the hydraulic The main relief valve is the primary pressure control
schematic in the Appendix, section of this manual. device on units equipped with Rexroth A7VO
hydraulic pumps.
NOTE!
If the main relief valve needs adjustment, proceed as
Do not use the remote control box for the
follows:
following pressure setting procedure.
1. Wear safety glasses when checking or adjusting
To check or set the concrete pump pressure pressures.
adjustments, follow these steps:
2. Using a 9/16 spanner wrench, loosen the jam nut
1. Be sure that the waterbox covers and guards are
on the main relief valve adjusting screw (Figure
installed on the waterbox.
111).
2. Start the truck engine, and put the PTO and
transmission into gear just as you would to pump a Gauge port
job.
3. Locate and close the concrete pump shutoff valve 00
02
97
.ep
and the soft switch shutoff valve (Figure 110). s

(These valves are also known as quarter turn


valves).
Main relief valve
4. If your concrete pump pressure gauge is not
already plumbed into the gauge port (Figure 37), Soft switch
install a 0 - 400 or 0 - 600 bar gauge in the gauge relief valve
port.
5. The remote / local switch located on the rear
control panel must be in the local position.
Figure 109
6. Be sure that all emergency stop switches are in the Location of the concrete pump circuit
up (not activated) position. Reset the E-stop circuit. main relief valve and soft switch relief
7. Using the throttle switch on the rear control panel, valve
bring the truck engine up to full RPM.
The main relief valve (Figure 111) is set to very high 3. Insert a 5/32 Allen wrench in the adjustment
pressure (at least 350 bar). Use the rear control panel screw. Turn the screw in to raise pressure and out
switch when checking the pressure of the main relief to lower the pressure. Always go back to the rear
valve, so you will be out of the way if a hose or fitting panel before checking the pressure.
blows.

revDate
126 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
4. Once the pressure is correct to the hydraulic 5. If you will not be setting the soft switch pressure,
schematic, retighten the jam nut. Tightening the open the shutoff valves. The unit will not stroke
nut tends to raise the pressure, so check pressure with closed shutoff valves.
again after tightening.

Soft switch
shutoff valve

Main Pressure
Gauge port

Concrete pump
shutoff valve 00
02
74
.e
ps

Figure 110
Showing the concrete pump and soft switch shutoff
valves

Grooves in handle Closed


Closed Open
soft switch
relief cartridge
Grooves in shaft 000273.eps Main relief cartridge
000276.eps

9/16" jam nut

Open
5/32" Allen head
Mounting screw and washer
removed for illustration 9/16" jam nut
Figure 111
Shutoff valve open / closed orientation

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 127
HOME PRINT

Pressure Settings
Setting the soft switch circuit relief
pressure
Gauge port

00
04
32
.ep
s

Figure 112
Location of the Main relief valve
main relief valve
Soft switch
relief valve

To check or adjust the soft switch pressure setting, Preheat the oil
proceed as follows:
When you set pressures for any circuit on any unit, the
1. Open the soft switch shutoff valve (Figure 111). hydraulic oil should be at normal operating
The rest of the unit should still be set up as though temperature (40 - 60 C). Instructions for heating the
you were going to check concrete pump pressure. hydraulic oil are found on page 371.
2. High pressure the concrete pump. The pressure
gauge should read 60 or 80 bar (check your About proportional boom systems
schematic). If adjustment is needed, proceed to In a black and white boom system, the hydraulic pump
step (3). If no adjustment is needed, skip to step puts out an unchanging amount of oil, and speed
(4). control is done by restricting the oil to certain functions
3. Loosen the jam nut on the soft switch relief valve with orifices. In a load-sensing system, the pump puts
(Figure 5) with a 9/16 spanner wrench. Adjust the out more or less oil to respond to the needs of the
system. Generally, the pump puts out enough oil to
pressure up or down, as needed, using a 5/32 Allen
maintain a 20 bar higher pressure at the pump than
wrench. When the correct pressure is achieved, what the cylinders actually require. This 20 bar is
tighten the jam nut. called delta P (P). Additionally, we set the hydraulic
4. Be sure to open the concrete pump shutoff valve pump so that it always puts out a small amount of oil,
(Figure 111) on the side of the brain when you are even if no oil is needed for the system. This oil is used
finished. The unit cannot stroke with this valve to ensure that you have control when you need it. The
closed. setting to maintain this minimum amount of oil is
called Q-min (pronounced cue min). To set the boom
Setting pressures on load-sensing booms or outrigger hydraulic pressures on a load-sensing
If your unit has a load-sensing proportional system, it system, begin by setting Q-min and P.
will have different pressure adjustments than if it is Read all of the instructions before beginning any
equipped with a black and white boom system. The pressure settings. General locations of the components
following instructions are for seven place, load-sensing for the following procedures are shown in Figure 113.
proportional systems. If you have a unit equipped with You will need an assistant for parts of the procedure.
a black and white boom system, contact Schwing You and any assistants should wear eye protection
Service for the correct instruction pages. when checking or setting pressures.

revDate
128 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Manual boom hand valves,


Delta P adjustment
and E-Stop manifold

Figure 113
Locations of
components used to
check and set boom
pressures 000433.eps

Q-min adjustment screw

Setting P 1. Stop the truck engine and place a Do Not


Operate sign on the truck windshield.
NOTE!
Do not adjust P or Q-min if your boom is 2. Install a 0-40 or 0-60 bar gauge in the 0-400 bar
running as you like it. The pressure setting gauge port (Figure 114) of the manual boom
procedure uses a standard starting point handvalves. Take care not to accidently install the
and must be fine tuned from there. It was gauge in the 0-60 bar port.
fine tuned at the factory and should not be
adjusted unless absolutely necessary. If it CAUTION
becomes necessary, do not adjust Q-min
with the drive shafts turning! Do not operate any function during this

000442.eps
procedure. Gauge damage possible!
Each time the Q-min screw is adjusted, the engine must
be stopped, or at least the transmission must be taken
out of gear so that the drive lines stop turning. To check
or set P, follow these steps:

Boom control
block relief valve
0-400 bar (non-adjustable)
gauge port

0-60 bar 15 bar pretension


gauge port adjusment screw

30 bar
pilot pressure 448
.ep
s

000
relief cartridge
140 bar downside
relief cartridge (non-adjustable)

Figure 114
Location of the boom circuit pressure devices (Hoses removed for clarity.)
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 129
HOME PRINT

Pressure Settings

Q-min
adjustment screw

000434.eps

Q-max

Figure 115
Location of the Q-min adjustment screw on A11VO (left)
and A7VO (right)
3. To be sure that the pump is putting out only enough wrench) and adjusting the screw (3mm Allen
oil to maintain P, we need to change the setting of wrench) clockwise to increase pressure or counter
the Q-min screw. Q-min is adjusted by a screw on clockwise to decrease it.
the boom hydraulic pump (Figure 115). Unscrew 5. The delta P adjustment screw on the A11VO boom
the Q-min screw three full turns. Make sure that all pump, also shown in Figure 44 below, requires a
emergency stop switches are in the up (not 13mm open end wrench and a 4mm allen wrench.
activated) position. Check that all personnel are
clear of the truck; then restart the engine, engage NOTE!
the pumps, and leave the engine at an idle. Pressure If the boom is not smooth at 20 bar, you
can be read on the 0 - 40 bar gauge that you must fine tune the adjustment. In that case,
installed. Pressure should read 20 bar. If no REMOVE THE GAUGE and adjust P
adjustment is needed, simply reset the Q-min until the boom is responsive and smooth.
screw as described on page 223. If adjustment is The gauge (reinstalled) must now read
needed, continue to step (4). between 14 and 25 bar. The electronics in
the control system can also affect how the
4. Delta P is adjusted on the bottom (smaller) screw
boom operates, so if P adjustment does not
of the pressure regulator shown in Figure 44 below.
seem to help, reset to 20 bar and check the
If your unit has an A7VO boom pump, you can do
electrical settings. Once electrical settings
so by loosening the jam nut (10mm open end
are verified, you could again refine the boom
action with the P adjustment.

Delta-p
000435.eps

T
P adjustment screw

000281.eps

Figure 116
Location of the delta P adjustment screw for a unit
with A7VO pump (left) and A11VO pump (right)
revDate
130 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Setting Q-min each time before making the adjustment. When
Check Q-min pressure when the engine is at the pressure is correct, tighten the jam nut on the
maximum specified RPM, but the engine must be adjustment screw before continuing with the other
stopped to adjust the screw. procedures.
1. If you unscrewed the Q-min screw as the first step Setting boom pressures
of P adjustment, begin by returning the screw to
its original position (Figure 115). (Load sensing proportional booms)
2. Remove the 0 - 40 bar gauge from the 0 - 400 bar Now that P and Q-min are set, you can check or set
gauge port, and install the 0 - 600 bar gauge in its the boom valve pressures.
place.
There are several devices on the boom circuit
3. Clear all personnel away from the drive lines, start which control boom pressure (Figure 45):
the truck engine, engage the pumps, and bring 1. Pressure regulator (the high-pressure adjustment
engine RPM to max. All boom functions must be in
screw on the P regulator valve on units with
neutral, and all emergency stop buttons should be
A7VO boom pumps), set at 300 bar.
up (not engaged).
2. Pressure cut-off on units with A11VO pumps.
4. Read the pressure on the 0 - 600 bar gauge.
Pressure should be at 40 - 45 bar. If no adjustment 3. The boom control block relief valve, pre-set at 350
is needed, stop the drive lines from turning, be sure bar.
the jam nut on the Q-min screw is tight, and NOTE!
proceed to Setting boom pressures. If adjustment is This relief valve is nonadjustable. If
needed, continue to the next step. pressure is not maintained with the
5. Turn the Q-min screw in to raise the pressure specification limits, the valve must be
(Figure 115). Turn it out to lower the pressure. Be replaced.
sure that you stop the drive shafts from turning

Boom control
block relief valve
0-400 bar (non-adjustable)
000436.eps

gauge port

T High pressure
adjustment screw

0-60 bar 15 bar pretension


gauge port adjusment screw

30 bar
pilot pressure 448
.ep
s

000
relief cartridge
140 bar downside
relief cartridge (non-adjustable)

Figure 117
The boom pressure devices

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 131
HOME PRINT

Pressure Settings
Raise the pressure of the lowest circuit Setting the outrigger pressures
To check the setting of the valve with the highest After the boom pressures are set, you can set the
pressure, you must first raise the pressure of the lower: outrigger pressure.
1. Loosen the jam nut of the high pressure adjustment The boom, outriggers, water pump, and compressor
screw (Figure 117) of the P regulator. Turn the circuits have all been put together in the boom valve
screw in two-and-a-half turns. This will raise the manifold. When the outrigger selector push button is
pressure on the regulator above 350 bar. pushed, the boom/outrigger control handle is activated
2. Pressure out any boom cylinder except #1 down by (Figure 117), which routes oil to the two outrigger
activating the control handle. To pressure out a hand valve banks (one on each side of the unit). A
cylinder, retract a fully retracted cylinder or extend relief valve inside the passenger side bank limits the
a fully extended cylinder. The oil is then forced entire outrigger circuit to 280 bar (4060 PSI) instead of
over the relief valve. the 300 bar (4350 PSI) of the boom relief valve.
The telltale hiss of an open relief valve should be
To set the 280 bar relief valve for the outrigger
coming from the Apitech control block relief valve circuit:
now. If it isnt, raise the setting of the delta P
regulator a little more until the hiss originates at
the Apitech control block relief valve. Read the
pressure on the gauge. It should read 350 bar. If
pressure is correct, proceed to the next step.
WARNING
NOTE!
Although the pressure specification for the Wear safety glasses any time you check
Apitech relief valve is 350 bar, you may or set pressures. Oil expulsion hazard!

000438.eps
continue to use the relief valve as long as the
cartridge maintains at least 330 bar. If you
must replace the valve and dont have one
on hand, proceed to the next step before 1. Plug the whip hose of a 0-400 or 0-600 bar gauge
using the machine again. Redo this entire (Figure 46) into the gauge port.
procedure when you have installed the new 2. If not already done, start the truck engine and set
valve. If pressure on the Apitech relief valve the transmission and PTO as you would for a
is below 290 bar, you should not use the pumping job.
machine until the valve is replaced. 3. Locate the 280 bar relief valve (Figure 118) on the
back of the outrigger valve.
3. You will need a helper for this step. While
pressuring out any boom cylinder except #1 down, 4. Set the engine RPM to maximum.
have your helper adjust the high pressure screw of 5. Select outrigger with the outrigger push button.
the P regulator out (lowering the pressure) until This will route oil to the outrigger handvalves.
the gauge reads 300 bar. Release the pressurized 6. With the outriggers folded into the travel position,
function, and lock the jam nut. The boom pressures activate the passenger side hand valve jacking
are now set. If you did not get the readings cylinder retract for either the front or rear
specified after following the instructions, contact outrigger.
Schwing Americas Service Department at (651)
429-0999 for advice on how to continue.
NOTE!
You will get an incorrect reading if you select any
other outrigger function. The handles are spring
loaded and will return to neutral as soon as you let
go.

revDate
132 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

000452.eps
0-400 bar
gauge port

Boom/Outrigger
control handle

AGITATOR
CONCRETE PUMP

Boom 1
Boom 2
Boom 3
Boom 4
Boom 1 Telescope
Slewing
Boom / Outrigger
Water / Compressor

10189517

DANGER WARNING
s Electrocution hazard.

.ep
Do not operate this
Stay back from high machine without

451
voltage wires at least training. Understand
17 feet (5 meters).

000
the warnings in safety
manuals and on decals.

Figure 118
Position of the 0-400 bar gauge port and boom/outrigger control handle

7. Read the pressure on the gauge. It should read 280 10. When the pressure is correct, either go on to other
bar (4060 PSI). If no adjustment is needed, skip to pressure settings or remove the whip hose and
step 10. gauge, and cap the gauge port with the attached
8. If adjustment is needed, turn the outside body of cap.
the relief valve that is located at the back of the 11. Return the RPM of the truck to an idle, take the
outrigger valve. Turn in to raise pressure and out to transmission and PTO out of gear, and shut off the
lower pressure. There is no jam nut on this valve. truck, or go on to the other pressure settings as
9. Activate the outrigger jacking retract hand valve, required.
and read the pressure on the gauge again. Repeat
steps (8) and (9) until the gauge reads 280 bar.
000453.eps

280 bar
Relief valve

AGITATOR
CONCRETE PUMP

Boom 1
Boom 2
Boom 3
Boom 4
Boom 1 Telescope
Slewing
Boom / Outrigger
Water / Compressor

10189517

DANGER WARNING
Electrocution hazard.
4 Stay back from high
Do not operate this
machine without
voltage wires at least

Outrigger control block


training. Understand
17 feet (5 meters). the warnings in safety
3

manuals and on decals.

WARNING
Clear area
before activating
outriggers

REAR EXTEND REAR JACKING FRONT JACKING FRONT EXTEND

00
04
40
.ep
s

Figure 119
Location of the 280 bar outrigger pressure relief valve
(Hoses removed for clarity)

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 133
HOME PRINT

Pressure Settings
Setting 15 bar pretension 2. Start the truck engine, but leave it at an idle.
(Pretension adjustment is made at an idle to
establish the minimum pressure setting. As RPM is
CAUTION increased, pressure will rise. Damage to the 0 - 40
bar gauge is possible if RPM is raised while the
Truck engine must be at idle to set
gauge is connected.)

000439.eps
pretension. Gauge damage possible!
3. If the pressure reads 15 bar 1 bar, the pressure is
set correctly. If adjustment is needed, proceed to
To check or set pretension, follow these the next step.
steps: 4. Loosen the jam nut on the pretension valve. Turn
1. Stop the truck engine. Plug the 0 - 40 bar gauge the screw in to raise pressure and out to lower
into the 0-60 bar pretension check port of the pressure. When the pressure is correct, retighten
Apitech hand valve (Figure 118). the jam nut.
5. Stop the engine, and remove the 0 - 40 bar gauge.
Pretension setting is complete.

15 bar pretension
adjustment screw

0-60 bar
gauge port

s
.ep
450
000

Figure 120
Pretension adjustment screw
and gauge port

revDate
134 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Setting the agitator circuit pressure

000447.eps

Agitator Relief Valve


Turn body of valve
Gauge port Higher to adjust.

Lower
AGITATOR
CONCRETE PUMP

Agitatior Hand Valve Boom 1


Boom 2
Boom 3
Boom 4
Boom 1 Telescope
Slewing
Boom / Outrigger
Water / Compressor

10189517

DANGER WARNING
Electrocution hazard.
4 Stay back from high
Do not operate this
machine without
voltage wires at least training. Understand
17 feet (5 meters). the warnings in safety

3
Agitator

1
manuals and on decals.

Fwd/Reverse WARNING
Clear area
before activating
outriggers

Concrete pump REAR EXTEND REAR JACKING FRONT JACKING FRONT EXTEND

Fwd/Reverse 88
.ep
s
02
00

Figure 121
Agitator hand valve (location right, blowup left)

The agitator relief valve is located in the agitator


forward / neutral / reverse hand valve block. The Agitator quarter turn
000174.eps

agitator relief valve limits the pressure in the agitator shutoff valve (open position)
circuit to 200 bar (2900 PSI). There is a gauge port for
checking or setting the pressure in this circuit. The port
is located on the agitator hand valve block and shown
on top in Figure 49. The gauge port may be mounted
on the side of the block on some units. To check or set
the agitator pressure, follow these steps:
Motor
1. Unscrew the cover from the gauge port. Plug in the
0-600 bar gauge and whip hose that came in the Figure 122
toolbox. The agitator shutoff valve
2. Start the engine if its not already running. 4. Activate the agitator, and read the pressure on the
3. Close the agitator shutoff valve (Figure 62). gauge.
NOTE! 5. If adjustment is needed, put your wrench on the
body of the relief valve (Figure 49), which is
If your unit does not have a shutoff valve,
located on the back of the agitator hand valve.
you can order one using part number
While reading the gauge, turn the body in to raise
10004680 (valve) and part number
pressure or out to lower pressure until 200 bar is
30303432 (tube). Contact Schwing
achieved.
Americas Service Department at (651) 429-
0999 for installation instructions. 6. Put the agitator handle in neutral.
7. Remove the whip hose and pressure gauge.
Replace the gauge port cover.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 135
HOME PRINT

Pressure Settings
Setting accumulator circuit pressure 4. Read the pressure on the accumulator circuit
To check or adjust the hydraulic pressure in the pressure gauge (Figure 124). The pressure should
accumulator circuit: read the value shown on the hydraulic schematic. If
no adjustment is needed, skip to step (7). If
1. Stop the truck, put the key in your pocket, and additional pressure adjustment is needed, continue
place a Do Not Operate sign on the windshield. with step (5).
2. Loosen the jam nut on the pressure regulator of the
@@@@@@@@



;;;;;;;;
QQQQQQQQ
@@@@@@@@


;;;;;;;;
QQQQQQQQ

000292.eps

accumulator hydraulic pump (Figure 123). Turn


the screw in two-and-one-half turns. This will raise
@@@@@@@@


;;;;;;;;
QQQQQQQQ

@@@@@@@@


;;;;;;;;
QQQQQQQQ

the regulator pressure above 300 bar.

;;;;;;;;
@@@@@@@@


QQQQQQQQ

3. Clear all personnel away from the drive lines, start

@@@@@@@@


;;;;;;;;
QQQQQQQQ

the truck engine, engage the pumps, and bring the

;;;;;;;;
@@@@@@@@


QQQQQQQQ

engine RPM to maximum.

;;;;;;;;
@@@@@@@@


QQQQQQQQ

Figure 124
Accumulator circuit pressure gauge
000289.eps

5. Locate the accumulator manifold pressure relief


cartridge (Figure 125). Loosen the jam nut, and
turn the screw clockwise to increase the pressure or
counter clockwise to decrease the pressure. Tighten
Accumulator pump
pressure regulator
the jam nut when the pressure reaches the value
required, and shut off the truck engine.
000449.eps

Figure 123
Accumulator pump pressure regulator for
A7VO (above) and for A11VO (below) Manual bleed
valve

Boom Pump
Accumulator Pump

Pressure relief
cartridge

Accumulator Pump
Pressure Regulator Figure 125
Accumulator manifold pressure relief
Standby 000446.eps cartridge and manual bleed valve
Pressure Screw hgacugc.psd

revDate
136 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

WARNING
Entanglement hazard. Stop drive shafts
before adjusting the accumulator pump

000075.eps
pressure regulator.

6. After the truck engine is stopped, go back to the


accumulator circuit hydraulic pump pressure
regulator (Figure 124), and turn the screw back out
two-and-one-half turns. This restores it to its
original setting.
7. Clear all personnel from the drive line area, start
the truck, and bring the engine RPM up to
maximum.
8. Read the pressure on the accumulator gauge. It
should now read the proper accumulator system
pressure.
9. If adjustment is needed, you must stop the truck
engine, or a least stop the drive lines from turning,
each and every time you approach the accumulator
circuit hydraulic pump. Turn the screw in to
increase the pressure or out to decrease pressure.
Lock the jam nut when the pressure is correct.

NOTE!
The accumulator circuit hydraulic pump
pressure regulator is sometimes referred
to as the pressure cut-off.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 137
HOME PRINT

Pressure Settings

revDate
138 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
32XL Single Circuit 2. Turn on the agitator. The agitator will not be able
to turn, and the oil will be forced over the relief
valve.
Check hydraulic pressures
3. At an idle (approx. 600 rpm), about 5.4 horsepower
Check all hydraulic pressures. Changes in pressures
is being converted to heat. Shut off the concrete
can indicate trouble in one or more components.
pump when the temperature gauge on the rear
Pressure settings must be made with the oil at normal
control panel shows 40 C.
operating temperatures (40 to 60 C).The
specifications for all circuit pressures are found on the
Check the concrete pump pressure (900 or
hydraulic schematics in the appendix section of this
1200)
manual.
The Schwing concrete pump circuit on the BPL 900 or
Preheat the hydraulic oil 1200, KVM 32 XL is designed to be operated at a
maximum pressure of 300 bar (4350 PSI). Pressure is
Because of the new load sensing and pressure cutoff
limited by the main relief valve which is located on the
regulated hydraulic systems, you cant use the concrete
forward (towards the truck cab) end of the main control
pump or boom circuit to preheat the hydraulic oil (they
block. To check or set the main relief pressure: (See
stop putting out oil if you try). To heat the oil to
Figure 126).
operating temperature:
1. Locate the agitator shutoff valve and close it. Note!
If your unit does not have a shutoff valve, you can
order one using part number 10004680 (valve) and
part number 30303432 (tube). Install as shown in
figure 50 on page 6-228.
s
.ep
in2
Bra

Pressure gauge
Main relief valve

Jam nut

Lower Raise
pressure pressure

Adjustment
handle scmnrlf2.eps

Figure 126
The main relief valve, concrete pump

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 139
HOME PRINT

Pressure Settings
1. Be sure that the waterbox covers are installed on 3. Start the truck engine, and put the PTO and
the waterbox. Use of the remote control box for the transmission into gear just as you would to pump a
following procedure is NOT recommended. job.
2. Wear safety glasses when checking or setting 4. See figure 127. Close the shutoff valve (also known
pressures. as the ball cock or quarter turn valve).

Figure 127
Showing the concrete pump shutoff valve

5. Put the rear control panel switch remote / local bar, there is a hydraulic problem. In this case,
into the local position. unscrew the adjustment knob by several turns so
6. Using the switch on the rear control panel, rev the that your pressure isnt too high once the problem
truck engine up to full RPM. is found. Contact Schwing Americas Service
Department at (651) 429-0999 for advice on how
7. Using the concrete pump forward / neutral /
to continue.
reverse switch on the rear control panel, put the
concrete pump into the forward position. The 13. Return the pump to the neutral position.
unit will stroke no more than once, then the rock 14. Open the shutoff valve.
cylinder will retract. Oil will have nowhere to go 15. Return the RPM of the truck to an idle, take the
except over the main relief valve. transmission and PTO out of gear, and shut off the
8. Read the pressure on the gauge, as shown. It truck, or go on to the other pressure settings, as
should read 300 bar. Return the pump to neutral required.
whether in needs adjustment or not. If no
adjustment is needed, skip to step 14. Setting boom pressures
9. Loosen the jam nut on the relief valve adjusting (7 place proportional circuit) If your unit has a load-
screw (requires a 13 mm spanner wrench). sensing proportional system, it will have different
10. Turn the knob on the relief valve to adjust the pressure adjustments than if it is equipped with a black
pressure. Screw the handle in to raise pressure, out and white boom system. The following instructions are
to lower the pressure. for load-sensing proportional systems. If your unit is
11. Retighten the jam nut. (This step is necessary equipped with a black and white boom system, these
because tightening the nut tends to raise the instructions will be wrong. Contact Schwing Americas
pressure. If it becomes a problem, hold the knob Service Department to obtain correct instructions.
while tightening the jam nut). Preheat the oil
12. Put the concrete pump into the forward position
NOTE!
again. The machine will not stroke this time, but
will again develop maximum pressure. Read the Whenever you set pressures for any circuit
pressure on the gauge. If more adjustment is on any unit, the hydraulic oil should be at
needed, return the pump to neutral, then repeat normal operating temperature (40 - 60 C).
steps 8. thru 12. until the pressure is at 300 bar. Instructions for heating he hydraulic oil
NOTE! If you cannot adjust the pressure up to 300 are found in section on page 6-139.
revDate
140 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
About proportional boom systems called delta P (P). Additionally, we set the hydraulic
In a black and white boom system, the hydraulic pump pump so that it always puts out a small amount of oil,
puts out an unchanging amount of oil, and speed even if no oil is needed for the system. This oil is used
control is done by restricting the oil to certain functions to ensure that you have control when you need it. The
with orifices. In a load-sensing system, the pump puts setting to maintain this minimum amount of oil is
out more or less oil to respond to the needs of the called Q-min (pronounced cue min). To set the boom
system. Generally, the pump puts out enough oil to or outrigger hydraulic pressures on a load-sensing
maintain a 20 bar higher pressure at the pump than system, begin by setting Q-min and P. See figure 130.
what the cylinders actually require. This 20 bar is

Manual P regulator Q-min adjustment screw


boom handvalves

Figure 128
Locations of components
CONCRETE PUMP

REV FWD

s
.ep
used to check and set

loc
XL
32
boom pressures

E-Stop manifold

Check that all personnel are clear of the truck, then


Read all of the instructions before beginning any restart the engine, engage the pumps, and leave the
pressure settings. You will need an assistant for parts of engine at an idle. CAUTION! If you activate any
the procedure. You and any assistants should wear eye boom or outrigger functions, you will damage
protection when checking or setting pressures. the 0 - 40 bar gauge. Make sure that all
emergency stop switches are in the up (not
Setting P activated) position. Pressure can be read on the 0 -
Note! Do not adjust P or Q-min if your boom is 40 bar gauge that you installed. Pressure should
running as you like it. The pressure setting procedure read 20 bar. If no adjustment is needed, simply
uses a standard starting point and must be fine tuned reset the Q-min screw as described in . If
from there. It was fine tuned at the factory, and should adjustment is needed, continue to step (4.).
not be adjusted unless absolutely necessary. 4. Delta P is adjusted by the P screw on the P
You must not adjust Q-min with the drive shafts regulator (see Figure 131). Loosen the jam nut and
turning! Each time the Q-min screw must be adjusted, adjust the screw inward to increase pressure, or
the engine must be stopped, or at least the transmission outward to decrease pressure until it is set at 20 bar
must be taken out of gear so that the drivelines stop (1). Contact Schwing Americas Service
turning. To check or set P, follow these steps: Department at (651) 429-0999 if you are unable to
adjust the pressure to spec. NOTE! If the boom is
1. Stop the truck engine and place a Do Not not smooth at 20 bar, you must fine tune the
Operate sign on the truck windshield. adjustment. In that case, REMOVE THE GAUGE,
2. Install a 0 - 40 or 0 - 60 bar gauge in the 0 - 400 bar and adjust P until the boom is responsive and
gauge port of the manual boom handvalves. Take smooth. When done, the gauge (reinstalled) must
care not to accidently install the gauge in the 0 - 60 read between 14 and 25 bar. The electronics in the
bar port. (See Figure 129.) control system can also affect how the boom
3. To be sure that the pump is putting out only enough operates, so if P adjustment does not seem to
oil needed to maintain P, we need to change the help, reset to 20 bar and check the electrical
setting of the Q-min screw. Q-min is adjusted by a settings. Once electrical settings are verified, you
screw on the boom hydraulic pump (see Figure could again refine the boom action with the P
130). Unscrew the Q-min screw three full turns. adjustment.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 141
HOME PRINT

Pressure Settings

140 bar gauge port (use 0-400


bar gauge when checking)

140 bar downside


relief cartridge
0-400 bar
gauge port
0-60 bar
gauge port

boom control
ps
block relief valve
v.e
itprd
ap

15 bar pretension
adjustment screw

Figure 129
Showing the location of the boom circuit pressure devices
(Hoses removed for clarity.)

Q-min
adjustment screw

Qminscrew.eps

Q-max

Figure 130
Location of the Q-min adjustment screw

Setting Q-min 2. Clear all personnel away from the drive lines, start
You must check Q-min pressure when the engine is at the truck engine, engage the pumps, and bring
the maximum specified RPM, but you must adjust it engine RPM to max. All boom functions must be in
with the engine stopped. neutral, and all emergency stop buttons should be
up (not engaged).
1. If you unscrewed the Q-min screw as the first step
of P adjustment, begin by returning the screw to 3. Read the pressure on the 0 - 600 gauge. Pressure
its original position (see Figure 130).Remove the 0 should be at 40 - 45 bar. If no adjustment is needed,
- 40 bar gauge from the 0 - 400 bar gauge port, and stop the drivelines from turning, be sure the jam
install the 0 - 600 bar gauge in its place. nut on the Q-min screw is tight, then continue to
revDate
142 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

CAUTION
Do not operate any functions while setting P.

000435.eps

T Figure 131
P adjustment screw The P regulator valve

paragraph to check the rest of the boom and 5. Loosen the jam nut of the adjustment screw of the
outrigger pressures. If adjustment is needed, redundant relief valve in the emergency stop
continue to step (5.). manifold. Turn the screw in one-and-a-half turns.
4. Turn the Q-min screw in to raise the pressure This will raise the pressure setting of the relief
(Figure 130). Turn it out to lower the pressure. Be valve to above 350 bar.
sure that you stop the drive shafts from turning 6. Pressure out any boom cylinder except #1 down by
each time before making the adjustment. When pushing or pulling the control handle. To pressure
pressure is correct, tighten the jam nut on the out a cylinder, retract a fully retracted cylinder or
adjustment screw before continuing with the other extend a fully extended cylinder. The oil is forced
procedures. over the relief valve.

Setting boom pressures The telltale hiss of an open relief valve should be
(Load sensing proportional booms.) Now that P and coming from the Apitech control block relief valve
Q-min are set, you can check or set the boom valve now. If it isnt, raise the setting of the other
pressures. pressure devices until the hiss originates at the
Apitech control block relief valve. Read the
There are three pressure settings on the boom circuit: pressure on the gauge. It should read 350 bar. If
(see Figure 132) pressure is correct, proceed to step (4.).
1. Pressure regulator (the high-pressure adjustment
screw on the P regulator valve), set at 300 bar. NOTE! Although the pressure specification for the
2. The redundant relief valve located in the Apitech relief valve is 350 bar, you may continue
emergency stop manifold, set at 330 bar. to use the relief valve as long as the cartridge
3. The boom control block relief valve, set at 350 bar. maintains at least 330 bar. If you must replace the
NOTE! This relief valve is nonadjustable. If valve, proceed to step (4.) before using the
pressure is not maintained with the specification machine again, and redo this entire procedure
limits, the valve must be replaced. when you have installed the new valve. If pressure
on the Apitech relief valve is below 290 bar, you
To check the setting of the valve with the highest
should not use the machine until the valve is
pressure, you must first raise the pressure of the
replaced.
lower two:
7. Screw out the e-stop manifold redundant relief
4. Loosen the jam nut of the high pressure adjustment
valve adjustment screw one-and-a-half turns.
screw of the P regulator. Turn the screw in two- Pressure out any boom cylinder except #1 down,
and-a-half turns. This will raise the pressure on the and read the gauge. Pressure should read 330 bar.
regulator above 350 bar. If it does not, turn the screw in to raise pressure, or
out to lower pressure until it is set at 330 bar. If the
location of this valve causes you to be near the accessing the valve.
drivelines, be sure to stop them from turning before
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 143
HOME PRINT

Pressure Settings

Redundant
relief valve
000436.eps

T High pressure MP
1

adjustment screw
TT

M
10
16
78

P1
92
-7.
ep
s

P4
P2
P3
0-400 bar
gauge port
0-60 bar
gauge port

s
.ep
nly
ipo
ap
boom control Figure 132
block relief valve The three boom pressure

8. You will need a helper for this step. While again. Remember, the emergency stop switches do
pressuring out any boom cylinder except #1 down, nothing if the e-stop manifold is plumbed out of
have your helper adjust the high pressure screw of the system.
the P regulator out (lowering the pressure) until 9. Remove the whip hose from the 300 bar gauge
the gauge reads 300 bar. Release the pressurized port. Before folding up the boom, proceed to the
function and lock the jam nut. The boom pressures instructions for setting the 140 bar down side relief
are now set. If you did not get the readings valve.
specified after following the instructions it is
possible that there is a problem with the emergency Setting the 140 bar down side relief valve
stop manifold (see Figure 133). You can plumb the pressure
malfunctioning circuit out of the system to test it.
Set the pressure of the 140 bar down side relief valve.
Use only approved hydraulic dead plugs to plug
This valve is a secondary relief valve for #1 cylinder
the inlet hose to the malfunctioning circuit. If
retract function. Proper adjustment ensures that the #1
pressure can now be achieved, the e-stop manifold
boom and the A-frame wont be damaged by putting
is the source of the problem. If pressure still cannot
the boom in the cradle. (See figure 134.) To adjust this
be achieved, the problem is elsewhere. Contact
valve (requires a 2.5 mm Allen wrench and a standard
Schwing Americas Service Department for advice
screwdriver):
on how to continue. If the problem was found to be
the e-stop manifold, repair it before using the unit 1. Install a 0 - 400 bar or 0 - 600 bar gauge into the
140 bar gauge port (shown in Figure 134).
revDate
144 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Concrete pump Boom dump valve


dump valve

Outlet to tank

Boom /
Outriggers
Pilot drain

Concrete pump Accumulator

Water pump / compressor / agitator


estophartbm.eps

S
MP
Boom/outrigger
T circuit dump
valve
S
MP

P3
ps
s.e
oppre
est

P2
Boom
P4 P1
override
button

Boom/outrigger
inlet port

Figure 133
Emergency stop manifold
original production (top), current production

2. Unfold the #2 section from #1 until it is straight. 3. Bring #1 down until the cylinder is completely
For the following procedure we must bring #1 all bottomed out. The cylinder does NOT bottom out
the way down until the cylinder bottoms out. if you are setting the folded boom into the A-frame
Position the boom so this can be done without (travel position).
hitting the truck or any other obstacle.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 145
HOME PRINT

Pressure Settings
4. Activate the #1 down (retract) handvalve The reads just under 140 bar. Retightening the set screw
boom will not be able to move because the cylinder will raise the pressure slightly. Recheck the
is already bottomed out. Read the pressure on the pressure, and readjust if needed.
gauge that you just installed. It should read 140 6. When the pressure is set at 140 bar with the set
bar. If no adjustment is necessary, skip to step 6. screw tight, you can remove the whip hose gauge
5. If adjustment is needed, loosen the set screw of the and replace the cap on the gauge port.
140 bar relief valve with the 2.5 mm Allen wrench. 7. The boom pressure setting sequence is complete. If
While you activate #1 down, adjust the relief you are done with the boom, slew it back into the
cartridge with the screwdriver until the pressure transport position, and lower #1 into the cradle.
Reattach the boom strap.

140 bar
gauge port

140 bar relief valve

ps
0.e
it14
ap

Figure 134
location of the 140 bar relief
valve and gauge port

Setting the outrigger 1. Wear safety glasses whenever you check or set
pressures (7 place boom valve systems) pressures.
After the boom pressures are set, you can set the 2. Plug the whip hose of a 0 - 400 or 0 - 600 bar
outrigger pressure. gauge into the gauge port. Location is shown in
In this system, the boom, outriggers, water pump, figure 46.
and compressor circuits have all been put together 3. If not already done, start the truck engine and set
in the boom valve manifold. (See Figure 46). When the transmission and PTO as you would for a
the outrigger selector push-button is activated, the pumping job.
outrigger valve routes oil to the two outrigger 4. Locate the 280 bar relief valve on the back of the
handvalve banks, one on each side of the unit. A outrigger valve, as shown in Figure 47.
relief valve inside the passenger side bank limits 5. Set the engine RPM to maximum.
the entire outrigger circuit to 280 bar (4060 PSI)
6. Select outrigger with the outrigger pushbutton.
instead of the 300 bar (4350 PSI) of the boom
This will route oil to the outrigger handvalves.
relief valve.
To set the 280 bar relief valve for the outrigger
circuit: (See Figure 46 and Figure 47).
revDate
146 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Gauge port

Figure 135 hd
.ep
s
itor
ap
Position of the outrigger selector valve
Outrigger handle

32Porct5.eps

REAR EXTEND FRONT EXTEND REAR FOOT FRONT FOOT

Figure 136
Location of the passenger
side outrigger control block

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 147
HOME PRINT

Pressure Settings

280 bar
Lower Relief Valve

PS
oc
bb
ck.
Higher ep
s

Turn body of valve


to adjust. Figure 137
Location of the outrigger circuit relief valve

7. Assuming that the outriggers are folded into the 1. Stop the truck engine. Plug the 0 - 40 bar gauge
travel position, activate the passenger side into the pretension check port of the Apitech
handvalve jacking cylinder retract for either the handvalve (Figure 138).
front or rear outrigger. Note! You will get an 2. Start the truck engine, but leave it at an idle.
incorrect reading if you select extension cylinder (Pretension adjustment is made at an idle to
retract by mistake. If you select extend by establish the minimum pressure setting. As RPM is
mistake, the outriggers will extend instead of increased, pressure will rise. Damage to the 0 - 40
reading the relief valve setting. The handles are bar gauge is possible if RPM is raised while the
spring loaded and will return to neutral as soon as gauge is connected.)
you let go.
3. Read the pressure on the gauge. If it reads 15 bar
8. Read the pressure on the gauge. It should read 280 1 bar, the pressure is set correctly. If adjustment is
bar (4060 PSI). If no adjustment is needed, skip to needed, proceed to step (4.).
step 10.
4. Loosen the jam nut on the pretension valve. Turn
9. If adjustment is needed, turn the outside body of the screw in to raise pressure, and out to lower
the relief valve that is located at the back of the pressure. When the pressure is correct, retighten
outrigger valve. Turn in to raise pressure, turn out the jam nut.
to lower pressure. There is no jam nut on this
5. Stop the engine, and remove the 0 - 40 bar gauge.
valve.
Pretension setting is complete.
10. Activate the outrigger jacking retract handvalve
and read the pressure on the gauge again. Repeat To set the agitator circuit pressure:
steps 8. and 9. until the gauge reads 280 bar.
The agitator relief valve is located in the agitator
11. When the pressure is correct, either go on to other forward / neutral / reverse handvalve, at the rear of the
pressure settings, or remove the whip hose and unit on the drivers side. The relief valve limits the
gauge, and cap the gauge port with the attached pressure in the agitator circuit to 200 bar (2900 PSI).
cap. (See Figure 49). There is a gauge port for checking or
12. Return the RPM of the truck to an idle, take the setting the pressure in this circuit. The port is located
transmission and PTO out of gear, and shut off the on the agitator handvalve. To check or set the agitator
truck, or go on to the other pressure settings, as pressure, follow these steps:
required. 1. Remove the aluminum diamond plate cover from
over the agitator handvalve.
Setting 15 bar pretension
2. Unscrew the cover from the gauge port. Plug in the
To check or set pretension, follow these steps: 0 - 600 bar gauge and whip hose that came in the
toolbox.

revDate
148 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

CAUTION
Truck engine must be at an idle while setting pretension.

Pretension
gauge port

s
.ep
rtn
itp
ap

Pretension adjustment screw

Figure 138
Pretension adjustment screw and gauge
agitator pressure check.eps L

Relief valve on this


side (not visible from
this angle).
Gauge port

Figure 139
Showing the agitator handvalve
and gauge port
(Diamond plate removed
for this illustration.)

3. Start the engine, if not already running. 6. If adjustment is needed, put your wrench on the
4. Close the agitator shutoff valve. (See Figure 140.) body of the relief valve, which is located on the
Note! If your unit does not have a shutoff valve, back of the agitator handvalve. While reading the
you can order one using part number 10004680 gauge, turn the body in to raise pressure, or out to
(valve) and part number 30303432 (tube). Contact lower pressure until 200 bar is achieved.
Schwings Service Department at (651) 429-0999 7. Put the agitator handle in neutral.
for installation instructions. 8. Remove the whip hose and pressure gauge.
5. Activate the agitator in forward. Read the pressure Replace the gauge port cover.
on the gauge. 9. Replace the aluminum diamond plate over the
agitator handvalve.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 149
HOME PRINT

Pressure Settings

closed

s
ep
o.
its
ag
open
Figure 140
The agitator shutoff valve

revDate
150 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
32 XL Twin Circuit off, and the key in your pocket, remove the plug
(item 2). The oil should be at the level of the
Units up to 450 l/m bottom of the hole in the case. If oil is needed, add
Check the fluid level of the distribution gearcase. by removing the breather (item 1) and pouring in
(See Figure 141). Be sure the truck is on through the top. This gearcase uses 90W gearlube.
reasonably level ground. With the truck engine

2
4194.e
ps

Figure 141
Check, drain and fill ports of the Stiebel 4194

Check the mounting hardware of the subframe, the 1. Locate the agitator shutoff valve and close it. There
oil and water tanks, the delivery pipeline, the is a picture of the location on page 6-228. Note! If
pumpkit, the differential cylinders, the material your unit does not have a shutoff valve, you can
cylinders and the driveline hardware. Check for order one using part number 10004680 (valve) and
bolt tightness, cracks and other abnormalities. part number 30303432 (tube). Contact Schwings
Service Department at (651) 429-0999 for
Check hydraulic pressures installation instructions.
Check all hydraulic pressures. Changes in 2. Turn on the agitator. The agitator will not be able
pressures can indicate trouble in one or more to turn, and the oil will be forced over the relief
components. Pressure settings must be made with valve.
the oil at normal operating temperatures (40 to 3. At an idle (approx. 600 rpm), about 5.4 horsepower
60 C).The specifications for all circuit pressures is being converted to heat. Shut off the agitator
are found on the hydraulic schematics in the when the temperature gauge on the rear control
appendix section of this manual. panel shows 40 C. Dont forget to open the shutoff
Preheat the hydraulic oil
valve when the procedure is finished.
Because of the new load sensing and pressure cut-
Check the concrete pump pressure (900-
off regulated hydraulic systems, you cant use the
1200 - MPS pumpkits)
concrete pump or boom circuit to preheat the
hydraulic oil (they stop putting out oil if you try). Schwing concrete pumps with MPS pumpkits are
To heat the oil to operating temperature: designed to be operated at a maximum pressure of 320
bar (4640 PSI). Pressure is limited by the main relief
valve which is located on the forward end (towards the

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 151
HOME PRINT

Pressure Settings
truck cab) of the main control block. (See Figure 142). 9. Read the pressure on the gauge, located as shown
To check or set the concrete pump relief pressure, in figure 142. It should read 320 bar. Return the
follow these steps: pump control to neutral whether the pressure
needs adjustment or not. If no adjustment is
needed, skip to step 14.
1. Wear safety glasses when checking or setting
pressures. 10. Using a 13 mm spanner wrench, loosen the jam nut
on the relief valve adjusting screw (Figure 142).
2. Be sure that the waterbox covers and guards are
installed on the waterbox. Use of the remote 11. Turn the knob on the relief valve to adjust the
control box for the following pressure setting pressure. Screw the handle in to raise pressure, out
procedure is NOT recommended. to lower the pressure.
3. Start the truck engine, and put the PTO and 12. Retighten the jam nut. Tightening the nut tends to
transmission into gear just as you would to pump a raise the pressure. If the pressure rise becomes a
job. problem, hold the knob while tightening the jam
nut.
4. See Figure 127. Close the concrete pump shutoff
valve, and the soft switch shutoff valve. (These 13. High pressure the concrete pump again. Read the
valves are also known as quarter turn valves). pressure on the gauge. If more adjustment is
needed, return the pump control to neutral, then
5. Put the rear control panel switch remote / local
repeat steps (8.) thru (13.) until the pressure is
into the local position.
correct. NOTE! If you cannot adjust the pressure
6. Be sure that all emergency stop switches are in the up to specification, there is a hydraulic problem. In
up (not activated) position. Reset the e-stop circuit. this case, unscrew the adjustment knob several
7. Using the switch on the rear control panel, rev the turns so your pressure isnt too high when you find
truck engine up to full RPM. the problem. Contact Schwing Americas Service
8. Put the concrete pump forward / neutral / reverse Department for advice on how to continue.
switch on the rear control panel into the forward 14. If you will not be setting the soft switch pressure,
position. The unit will stroke no more than once, open the shutoff valves. The unit will not stroke
then the rock cylinder will retract. Oil leaving the with closed shutoff valves.
hydraulic pumps will be forced over the main relief
valve. This is called high-pressuring the concrete
pump.
relieflocMPS.eps

Main relief valve

Pressure
Gauge Jam Nut
Adjustment
Handle

Lower Raise
pressure pressure

gray valve.eps

Figure 142
The main relief valve, concrete pump circuit.

revDate
152 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

soft switch.epsL

Figure 143
Showing the concrete pump shut-off valve (left) and soft switch shutoff valve (right)

Groove lined up with ports


- open

grooves.eps

Groove at 90 to ports
- closed

Figure 144
Shutoff valve orientation

Setting the soft switch circuit relief 3. Be sure to open the concrete pump shutoff valve on
pressure the side of the brain (shown in Figure 143) when
To check or adjust the soft switch pressure setting, you are finished. The unit cannot stroke with this
proceed as follows: valve closed.
1. Open the soft switch shutoff valve, as shown in
Setting the boom pressures
figures 143 and 144. The rest of the unit should
still be set up as though you were going to check (7 place black and white circuit) If your unit has a
concrete pump pressure. black and white boom system, it will have different
pressure adjustments than if it is equipped with a load-
2. High pressure the concrete pump. The pressure
sensing proportional system. The following
gauge should read 80 bar (1160 PSI) instead of 320
instructions are for black and white systems. If you
bar. If adjustment is needed, loosen the set screw
have a proportional unit, skip to page 6- 221. To set the
on the face of the relief valve cartridge with a 2.5
300 bar boom circuit relief valve proceed as follows:
mm allen wrench. Using a screwdriver, adjust the
(See Figure 145)
pressure up or down as needed, and lock the set
screw into place with the 2.5 mm allen wrench. 1. We have to raise the boom and rotate it 180 for
Recheck. Use a screwdriver, if necessary, to this procedure, so you must set the outriggers as
prevent the cartridge from turning while tightening you would to pump a job. Be sure that you set up
the allen screw. well away from electrical wires and other
obstructions.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 153
HOME PRINT

Pressure Settings

7plcpres.eps

Use #2, 3, or 4
140 bar port

3
140 bar relief

300 bar port SECTION 1 SECTION 2 SECTION 3 SECTION 4 SLEWING AIR / WATER BOOM / OUTRIG.

Turn body of valve


DANGER WARNING
Do not operate this
Higher to adjust.
Electrocution hazard.
Stay back from high machine without
training. Understand
voltage wires at least SAFETY

the warnings in safety


17 feet (5 meters). MANUAL
manuals and on decals.

Lower
300 bar
Relief Valve

Figure 145
Showing the location of the boom ep
s
m.
oo
circuit pressure devices. 7p
lcb

(Hoses removed for clarity.)

2. Once the outriggers are set, unlock the boom strap, 6. If adjustment is needed, put your wrench on the
and raise the #1 boom far enough that you wont 300 bar relief valve at the back of the boom control
hit anything on the truck. Leave the rest of the valve bank. While you are holding the function in
boom folded. Rotate the boom so that you have retract mode, adjust the cartridge in or out until the
safe and easy access to the boom control valves. pressure reads 300 bar.
3. Remove the control block cover, held on by 2 M6 7. If you cannot achieve 300 bar, it is possible that
screws. there is a problem with the emergency stop
4. Install the whip hose of a 0-400 or 0-600 bar gauge manifold (see Figure 146). You can plumb the
in the 300 bar gauge port (Item 1 in Figure 145). malfunctioning circuit out of the system to test it.
Use only approved hydraulic dead plugs to plug
5. Assuming that your boom is completely folded up
the inlet hose to the malfunctioning circuit. If
(except for #1), select a handle, and retract #2, #3
pressure can now be achieved, the e-stop manifold
or #4 section. Do NOT use #1 retract, slewing left
is the source of the problem. Contact Schwing
right, outrigger, water pump, or any extend
Americas Service Department for advice on repair
function. (Again, when you try to retract a fully
of the e-stop manifold. Repair the e-stop manifold
retracted cylinder, the oil has no where to go except
before using the unit again. Remember, the
over the relief valve - this allows us to read the
emergency stop switches do nothing if the e-stop
relief valve setting on a gauge). Read the pressure
manifold is plumbed out of the system. Remove
on the whip gauge that you installed in step 4,
the whip hose from the 300 bar gauge port. Before
above. It should read 300 bar. If no adjustment is
folding up the boom, proceed to the instructions
necessary, skip to step 7.
for setting the 140 bar down side relief valve.
revDate
154 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Concrete pump Boom dump valve


dump valve

Outlet to tank

Boom /
Outriggers
Pilot drain

Concrete pump Accumulator

Water pump / compressor / agitator


estophartbm.eps

S
MP
Boom/outrigger
T circuit dump
valve
S
MP

P3
s
.ep
ppres
esto

P2
Boom
P4 P1
override
button
Figure 146
Emergency stop manifold
Boom/outrigger
original production (top),
inlet port
current production (bottom)

Load-sensing boom pressures Preheat the oil


(7 place proportional circuit) If your unit has a load- Note! Whenever you set pressures for any circuit on
sensing proportional system, it will have different any unit, the hydraulic oil should be at normal
pressure adjustments than if it is equipped with a black operating temperature (40 - 60 C). Instructions for
and white boom system. The following instructions are heating the hydraulic oil are found in section on
for load-sensing proportional systems. page 217.

About proportional boom systems


In a black and white boom system, the hydraulic pump
puts out an unchanging amount of oil, and speed
control is done by restricting the oil to certain functions
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 155
HOME PRINT

Pressure Settings
with orifices. In a load-sensing system, the pump puts even if no oil is needed for the system. This oil is used
out more or less oil to respond to the needs of the to ensure that you have control when you need it. The
system. Generally, the pump puts out enough oil to setting to maintain this minimum amount of oil is
maintain a 20 bar higher pressure at the pump than called Q-min (pronounced cue min). To set the boom
what the cylinders actually require. This 20 bar is or outrigger hydraulic pressures on a load-sensing
called delta P (P). Additionally, we set the hydraulic system, begin by setting Q-min and P. See figure 149.
pump so that it always puts out a small amount of oil,

Manual P regulator Q-min adjustment screw


boom handvalves

CONCRETE PUMP

REV FWD

sp
loc.e
XL
32

E-Stop manifold

Figure 147
Locations of components used to check and set boom pressures

Read all of the instructions before beginning any


pressure settings. You will need an assistant for parts of
the procedure. You and any assistants should wear eye
protection when checking or setting pressures.

Setting P
Note! Do not adjust P or Q-min if your boom is
running as you like it. The pressure setting procedure
uses a standard starting point and must be fine tuned
from there. It was fine tuned at the factory, and should
not be adjusted unless absolutely necessary.
You must not adjust Q-min with the drive shafts
turning! Each time the Q-min screw must be
adjusted, the engine must be stopped, or at least the
transmission must be taken out of gear so that the
drivelines stop turning. To check or set P, follow
these steps:
1. Stop the truck engine and place a Do Not
Operate sign on the truck windshield.

revDate
156 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
2. Install a 0-40 or 0-60 bar gauge in the 0-400 bar
gauge port of the manual boom handvalves. Take
care not to accidently install the gauge in the 0-60
bar port. (See Figure 145.)

140 bar gauge port (use 0-400


bar gauge when checking)

140 bar downside


relief cartridge
0-400 bar
gauge port
0-60 bar
gauge port

boom control
ps
block relief valve
v.e
itprd
ap

15 bar pretension
adjustment screw

Figure 148
Showing the location of the boom circuit pressure devices.
(Hoses removed for clarity.)
3. To be sure that the pump is putting out only enough boom or outrigger functions, you will damage
oil needed to maintain P, we need to change the the 0 - 40 bar gauge. Make sure that all
setting of the Q-min screw. Q-min is adjusted by a emergency stop switches are in the up (not
screw on the boom hydraulic pump (see Figure activated) position. Pressure can be read on the 0 -
149). Unscrew the Q-min screw three full turns. 40 bar gauge that you installed. Pressure should
Check that all personnel are clear of the truck, then read 20 bar. If no adjustment is needed, simply
restart the engine, engage the pumps, and leave the reset the Q-min screw as described in . If
engine at an idle. CAUTION! If you activate any adjustment is needed, continue to step (4.).

Q-min
adjustment screw

Qminscrew.eps

Q-max

Figure 149
Location of the Q-min adjustment screw

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 157
HOME PRINT

Pressure Settings
4. Delta P is adjusted by the P screw on the P boom is responsive and smooth. When done, the
regulator (see Figure 150). Loosen the jam nut and gauge (reinstalled) must read between 14 and 25
adjust the screw inward to increase pressure, or bar. The electronics in the control system can also
outward to decrease pressure until it is set at 20 bar affect how the boom operates, so if P adjustment
(1). Contact Schwing Americas Service does not seem to help, reset to 20 bar and check the
Department if you are unable to adjust the pressure electrical settings. Once electrical settings are
to spec. NOTE! If the boom is not smooth at 20 verified, you could again refine the boom action
bar, you must fine tune the adjustment. In that case, with the P adjustment.
REMOVE THE GAUGE, and adjust P until the

CAUTION
Do not operate any functions while setting P.
000435.eps

T
P adjustment screw

Figure 150
The P regulator valve

Setting Q-min 1. Turn the Q-min screw in to raise the pressure


You must check Q-min pressure when the engine (Figure 149). Turn it out to lower the pressure. Be
is at the maximum specified RPM, but you must sure that you stop the drive shafts from turning
adjust it with the engine stopped. each time before making the adjustment. When
pressure is correct, tighten the jam nut on the
1. If you unscrewed the Q-min screw as the first step
adjustment screw before continuing with the other
of P adjustment, begin by returning the screw to
procedures.
its original position (see Figure 149).
1. Remove the 0 - 40 bar gauge from the 0 - 400 bar Setting boom pressures
gauge port, and install the 0 - 600 bar gauge in its (Load sensing proportional booms.) Now that P
place. and Q-min are set, you can check or set the boom valve
1. Clear all personnel away from the drive lines, start pressures.
the truck engine, engage the pumps, and bring There are three pressure settings on the boom
engine RPM to max. All boom functions must be in circuit: (see Figure 151)
neutral, and all emergency stop buttons should be 1. Pressure regulator (the high-pressure adjustment
up (not engaged). screw on the P regulator valve), set at 300 bar.
1. Read the pressure on the 0 - 600 gauge. Pressure 2. The redundant relief valve located in the
should be at 40 - 45 bar. If no adjustment is needed, emergency stop manifold, set at 330 bar.
stop the drivelines from turning, be sure the jam
nut on the Q-min screw is tight, then continue to
paragraph to check the rest of the boom and
outrigger pressures. If adjustment is needed,
continue to step (5.).

revDate
158 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
3. The boom control block relief valve, set at 350 bar.
NOTE! This relief valve is nonadjustable. If
pressure is not maintained with the specification
limits, the valve must be replaced.

Redundant
relief valve
000436.eps

MP
1
T High pressure
adjustment screw TT

M
10
16
78

P1
92
-7.
ep
s

P4
P2
P3
0-400 bar
gauge port
0-60 bar
gauge port

Figure 151
s
.ep
a pip
o nly
The three boom pressure devices
boom control
block relief valve

To check the setting of the valve with the highest over the relief valve.
pressure, you must first raise the pressure of the
lower two: The telltale hiss of an open relief valve should be
1. Loosen the jam nut of the high pressure adjustment coming from the Apitech control block relief valve
screw of the P regulator. Turn the screw in two- now. If it isnt, raise the setting of the other
and-a-half turns. This will raise the pressure on the pressure devices until the hiss originates at the
regulator above 350 bar. Apitech control block relief valve. Read the
pressure on the gauge. It should read 350 bar. If
2. Loosen the jam nut of the adjustment screw of the
pressure is correct, proceed to step (4.).
redundant relief valve in the emergency stop
manifold. Turn the screw in one-and-a-half turns.
This will raise the pressure setting of the relief NOTE! Although the pressure specification for the
valve to above 350 bar. Apitech relief valve is 350 bar, you may continue to
use the relief valve as long as the cartridge maintains at
3. Pressure out any boom cylinder except #1 down by
least 330 bar. If you must replace the valve, proceed to
pushing or pulling the control handle. To pressure
step (4.) before using the machine again, and redo this
out a cylinder, retract a fully retracted cylinder or
entire procedure when you have installed the new
extend a fully extended cylinder. The oil is forced
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 159
HOME PRINT

Pressure Settings
valve. If pressure on the Apitech relief valve is below 5. If adjustment is needed, loosen the set screw of the
290 bar, you should not use the machine until the valve 140 bar relief valve with the 2.5 mm Allen wrench.
is replaced. While you activate #1 down, adjust the relief
4. Screw out the e-stop manifold redundant relief cartridge with the screwdriver until the pressure
valve adjustment screw one-and-a-half turns. reads just under 140 bar. Retightening the set screw
Pressure out any boom cylinder except #1 down, will raise the pressure slightly. Recheck the
and read the gauge. Pressure should read 330 bar. pressure, and readjust if needed.
If it does not, turn the screw in to raise pressure, or 6. When the pressure is set at 140 bar with the set
out to lower pressure until it is set at 330 bar. If the screw tight, you can remove the whip hose gauge
location of this valve causes you to be near the and replace the cap on the gauge port.
drivelines, be sure to stop them from turning before 7. The boom pressure setting sequence is complete. If
accessing the valve. you are done with the boom, slew it back into the
5. You will need a helper for this step. While transport position, and lower #1 into the cradle.
pressuring out any boom cylinder except #1 down, Reattach the boom strap.
have your helper adjust the high pressure screw of
the P regulator out (lowering the pressure) until Setting the outrigger
the gauge reads 300 bar. Release the pressurized pressures (7 place boom valve system)
function and lock the jam nut. The boom pressures After the boom pressures are set, you can set the
are now set. If you did not get the readings outrigger pressure.
specified after following the instructions, contact
In this system, the boom, outriggers, water pump,
Schwing Americas Service Department at (651)
and compressor circuits have all been put together
429-0999 for advice on how to continue.
in the boom valve manifold. (See Figure 46). When
the outrigger selector pushbutton is activated, the
Setting the 140 bar down side relief valve
outrigger valve routes oil to the two outrigger
pressure handvalve banks, one on each side of the unit. A
Set the pressure of the 140 bar down side relief valve. relief valve inside the passenger side bank limits
This valve is a secondary relief valve for #1 cylinder the entire outrigger circuit to 280 bar (4060 PSI)
retract function. Proper adjustment ensures that the #1 instead of the 300 bar (4350 PSI) of the boom
boom and the A-frame wont be damaged by putting relief valve.
the boom in the cradle. (See figure 134.) To adjust this To set the 280 bar relief valve for the outrigger
valve (requires a 2.5 mm Allen wrench and a standard circuit: (See Figure 154).
screwdriver):
1. Install a 0 - 400 bar or 0 - 600 bar gauge into the
140 bar gauge port (shown in Figure 152). 1. Wear safety glasses whenever you check or set
2. Unfold the #2 section from #1 until it is straight. pressures.
For the following procedure we must bring #1 all 2. Plug the whip hose of a 0-400 or 0-600 bar gauge
the way down until the cylinder bottoms out. into the gauge port. Location is shown as item 1 in
Position the boom so this can be done without figure 46.
hitting the truck or any other obstacle. 3. If not already done, start the truck engine and set
3. Bring #1 down until the cylinder is completely the transmission and PTO as you would for a
bottomed out. The cylinder does NOT bottom out pumping job.
if you are setting the folded boom into the A-frame 4. Locate the 280 bar relief valve on the back of the
(travel position). outrigger valve, as shown in Figure 154.
4. Activate the #1 down (retract) handvalve The 5. Set the engine RPM to maximum.
boom will not be able to move because the cylinder 6. Select outrigger with the outrigger pushbutton.
is already bottomed out. Read the pressure on the This will route oil to the outrigger handvalves.
gauge that you just installed. It should read 140
bar. If no adjustment is necessary, skip to step 6.

revDate
160 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

7plc140.eps

140 bar gauge port

140 bar relief valve

SECTION 1 SECTION 2 SECTION 3 SECTION 4 SLEWING AIR / WATER BOOM / OUTRIG.

DANGER WARNING
Electrocution hazard. Do not operate this
Stay back from high machine without
training. Understand
voltage wires at least SAFETY

the warnings in safety


17 feet (5 meters). MANUAL
manuals and on decals.

140 bar
gauge port

140 bar relief valve

ps
0.e
it14
ap

Figure 152
location of the 140 bar relief valves and gauge
ports. - B & W (top)
proportional (bottom)

7. Assuming that the outriggers are folded into the 8. Read the pressure on the gauge. It should read 280
travel position, activate the passenger side bar (4060 PSI). If no adjustment is needed, skip to
handvalve jacking cylinder retract for either the step 10.
front or rear outrigger. Note! You will get an 9. If adjustment is needed, turn the outside body of
incorrect reading if you select extension cylinder the relief valve that is located at the back of the
retract by mistake. If you select extend by outrigger valve. Turn in to raise pressure, turn out
mistake, the outriggers will extend instead of to lower pressure. There is no jam nut on this
reading the relief valve setting. The handles are valve.
spring loaded and will return to neutral as soon as
you let go.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 161
HOME PRINT

Pressure Settings

7plcORhndl.eps

Outrigger handle
1
Gauge port

SECTION 1 SECTION 2 SECTION 3 SECTION 4 SLEWING AIR / WATER BOOM / OUTRIG.

DANGER WARNING
Electrocution hazard. Do not operate this
Stay back from high machine without
training. Understand
voltage wires at least SAFETY

the warnings in safety


17 feet (5 meters). MANUAL
manuals and on decals.

1
Gauge port

Figure 153
.ep
s Position of the outrigger selector valve
hd
itor
ap Monsun-Tyson black & white (top right)
Outrigger handle Apitech proportional (bottom left)

10. Activate the outrigger jacking retract handvalve pressure in the agitator circuit to 200 bar (2900 PSI).
and read the pressure on the gauge again. Repeat (See Figure 155). There is a gauge port for checking or
steps 8. and 9. until the gauge reads 280 bar. setting the pressure in this circuit. The port is located
11. When the pressure is correct, either go on to other on the agitator handvalve. To check or set the agitator
pressure settings, or remove the whip hose and pressure, follow these steps:
gauge, and cap the gauge port with the attached 1. Remove the aluminum diamond plate cover from
cap. over the agitator handvalve.
12. Return the RPM of the truck to an idle, take the 2. Unscrew the cover from the gauge port. Plug in the
transmission and PTO out of gear, and shut off the 0-600 bar gauge and whip hose that came in the
truck, or go on to the other pressure settings, as toolbox.
required. 3. Start the engine, if not already running.
4. Close the agitator shutoff valve. (See Figure 156.)
Setting the water pump hyd. pressure
Note! If your unit does not have a shutoff valve,
With a seven place handvalve, the water pump you can order one using part number 10004680
hydraulic control is inside the boom control block. (valve) and part number 30303432 (tube). Contact
There is not a separate relief for this circuit. Schwings Service Dept. for installation
instructions.
To set the agitator circuit
5. Activate the agitator in forward. Read the pressure
pressure:
on the gauge.
The agitator relief valve is located in the agitator
forward / neutral / reverse handvalve, at the rear of the
unit on the drivers side. The relief valve limits the
revDate
162 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

32Porct5.eps

280 bar
Lower Relief Valve

PS
oc
bb
ck.
Higher ep
s

Turn body of valve


to adjust.
REAR EXTEND FRONT EXTEND REAR FOOT FRONT FOOT

Figure 154
Location of the 280 bar outrigger
pressure relief valve.
(Hoses removed for clarity).
agitator pressure check.eps L

Relief valve on this


side (not visible from
this angle).
Gauge port
Figure 155
Showing the agitator handvalve and
gauge port.
(Diamond plate removed
for this illustration.)

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 163
HOME PRINT

Pressure Settings

closed

s
ep
o.
its
ag
open
Figure 156
The agitator shutoff valve

6. If adjustment is needed, put your wrench on the


body of the relief valve, which is located on the
back of the agitator handvalve. While reading the
gauge, turn the body in to raise pressure, or out to
lower pressure until 200 bar is achieved.
7. Put the agitator handle in neutral.
8. Remove the whip hose and pressure gauge.
Replace the gauge port cover.
9. Replace the aluminum diamond plate over the
agitator handvalve.

revDate
164 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
32 XL Hi-Flow B&W off, and the key in your pocket, remove the plug
(item 2). The oil should be at the level of the
bottom of the hole in the case. If oil is needed, add
Units up to 450 l/m
by removing the breather (item 1) and pouring in
Check the fluid level of the distribution gearcase. through the top. This gearcase uses 90W gearlube.
(See Figure 141). Be sure the truck is on
reasonably level ground. With the truck engine

4194 gearcase scan.eps


2

Figure 157
Check, drain and fill ports of the Stiebel 4194 gearcase.

Check the mounting hardware of the subframe, the part number 30303432 (tube). Contact Schwings
oil and water tanks, the delivery pipeline, the Service Department at (651) 429-0999 for
pumpkit, the differential cylinders, the material installation instructions.
cylinders and the driveline hardware. Check for 2. Turn on the agitator. The agitator will not be able
bolt tightness, cracks and other abnormalities. to turn, and the oil will be forced over the relief
valve.
Check hydraulic pressures
3. At an idle (approx. 600 rpm), about 5.4 horsepower
Check all hydraulic pressures. Changes in is being converted to heat. Shut off the agitator
pressures can indicate trouble in one or more when the temperature gauge on the rear control
components. Pressure settings must be made with panel shows 40 C. Dont forget to open the shutoff
the oil at normal operating temperatures (40 to valve when the procedure is finished.
60 C).The specifications for all circuit pressures
are found on the hydraulic schematics in the
appendix section of this manual.

Preheat the hydraulic oil


To heat the oil to operating temperature:
1. Locate the agitator shutoff valve and close it. There
is a picture of the location on page 6-228. Note! If
your unit does not have a shutoff valve, you can
order one using part number 10004680 (valve) and

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 165
HOME PRINT

Pressure Settings
Location of pressure setting/checking devices eral location of the devices needed to check pressures
See Figure 158. The illustration below shows the gen- on the concrete pump, boom, and outriggers,

Boom control
block

32
prs
loc
.ep
s

E-Stop manifold

Soft Switch ball cock

Ball cock
CONCRETE PUMP
REV
FWD

(quarter-turn valve)

Outrigger pushbutton
Outrigger pushbutton
Passenger side
outrigger controls
Driver's side
outrigger controls

Agitator control Control panel


valve

Agitator shutoff valve

Figure 158
Location of the pressure setting devices

revDate
166 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Check the concrete pump pressure (2020, model. This means that we cannot simply list a
2023, 2525 pumpkits) pressure specification for all units. The correct
Because the Hi-flo pumpkits have the ability to pressure specifications for your unit are shown on
create high pressure on the concrete the pressure the hydraulic schematic in section 7 of this
settings have to be tailored specifically for each manual..

Gauge port

Hif
lrv
vw
.ep
s

Main relief valve

Soft switch
relief valve

Figure 159
Location of the concrete pump circuit main relief
valve and soft switch relief valve

To check or set the concrete pump pressure 5. Install a 0 - 400 or 0 - 600 bar gauge in the gauge
adjustments, follow these steps: port.
6. Put the rear control panel switch remote / local
1. Wear safety glasses when checking or setting into the local position.
pressures. 7. Be sure that all emergency stop switches are in the
2. Be sure that the waterbox covers and guards are up (not activated) position. Reset the e-stop circuit.
installed on the waterbox. Use of the remote 8. Using the switch on the rear control panel, rev the
control box for the following pressure setting truck engine up to full RPM.
procedure is NOT recommended. 9. Put the concrete pump forward / neutral / reverse
3. Start the truck engine, and put the PTO and switch on the rear control panel into the forward
transmission into gear just as you would to pump a position. The unit will stroke no more than once,
job. then the rock cylinder will retract. Oil leaving the
4. See figures 38, 161, and 162. Locate and close the hydraulic pumps will be blocked in the brain. This
concrete pump shutoff valve, and the soft switch is called high-pressuring the concrete pump.
shutoff valve. (These valves are also known as
quarter turn valves).
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 167
HOME PRINT

Pressure Settings

Soft switch
shutoff valve

Concrete pump
shutoff valve
hif
lob
r2.
ep
s

Figure 160
Showing the concrete pump and soft switch shutoff valves

Groove lined up with ports


- open

grooves.eps

Groove at 90 to ports
- closed

Figure 161
Orientation of the concrete pump shutoff valve open/closed positions

10. Read the pressure on the gauge. Pressure shown on valve so you will be out of the way if a hose or fitting
the gauge should be the same as the specification blows. See Figure 162. If the main relief valve needs
for the concrete pump circuit on the hydraulic adjustment, proceed as follows:
schematic. Return the pump control to neutral 1. Always wear eye protection when checking or
whether the pressure needs adjustment or not. If no setting pressures.
adjustment is needed, skip to step (14.) on page 6-
218. If adjustment is needed, proceed to step (1.). 2. Using a 9/16 spanner wrench, loosen the jam nut
on the main relief valve adjusting screw (Figure
Setting the main relief valve 162).
The main relief valve is the primary pressure control 3. Insert a 5/32 Allen wrench in the adjustment
device on units equipped with Rexroth A7VO screw. Turn the screw in to raise pressure, out to
hydraulic pumps. lower the pressure. Always go back to the rear
CAUTION! The main relief valve is set to very high panel before checking the pressure.
pressure (at least 350 bar). Use the rear control panel
switch when checking the pressure of the main relief
revDate
168 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

op
n-c
lsd
2.e
ps

closed

open

Main relief valve


Soft switch
relief valve

Figure 162
Orientation of the soft switch valve open/closed positions

4. Once the pressure is correct to the hydraulic 4. Be sure to open the concrete pump shutoff valve on
schematic, retighten the jam nut. Tightening the the side of the brain (shown in Figure 163) when
nut tends to raise the pressure, so check pressure you are finished. The unit cannot stroke with this
again after tightening. valve closed.
5. If you will not be setting the soft switch pressure,
open the shutoff valves. The unit will not stroke Setting the boom pressures
with closed shutoff valves. (7 place black and white circuit) If your unit has a
black and white boom system, it will have different
Setting the soft switch circuit relief pressure adjustments than if it is equipped with a load-
pressure sensing proportional system. The following
To check or adjust the soft switch pressure setting, instructions are for black and white systems. If you
proceed as follows: have a proportional unit, contact Schwing Americans
1. Open the soft switch shutoff valve, as shown in Service Department at (651) 429-0999 for correct
figure 162. The rest of the unit should still be set up instructions.
as though you were going to check concrete pump To set the 300 bar boom circuit relief valve proceed as
pressure. follows: (See Figure 164)
2. High pressure the concrete pump. The pressure 1. The boom must be raised and rotated 180 for this
gauge should read 60 or 80 bar (check your procedure, so you must set the outriggers as you
schematic). If adjustment is needed, proceed to would to pump a job. Be sure that you set up well
step (3), below. If no adjustment is needed, skip to away from electrical wires and other obstructions.
step (4.). 2. Once the outriggers are set, unlock the boom strap,
3. Loosen the jam nut on the soft switch relief valve and raise the #1 boom far enough that you wont
hit anything on the truck. Leave the rest of the
with a 9/16 spanner wrench. Adjust the pressure up boom folded. Rotate the boom so that you have
or down, as needed, using a 5/32 Allen wrench. safe and easy access to the boom control valves.
When the correct pressure is achieved, re-lock the 3. Remove the control block cover, held on by 2 M6
jam nut. screws.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 169
HOME PRINT

Pressure Settings

Gauge port

Hif
lrv
2.e
ps

Main relief valve

Soft switch
relief valve

Figure 163
Location of the main relief valve

4. Install the whip hose of a 0 - 400 or 0 - 600 bar 7. If you cannot achieve 300 bar, it is possible that
gauge in the 300 bar gauge port (see Figure 165). there is a problem with the emergency stop
5. Assuming that your boom is completely folded up manifold (see Figure 166). You can plumb the
(except for #1), select a handle, and retract #2, #3 malfunctioning circuit out of the system to test it.
or #4 section. Do NOT use #1 retract, slewing left Use only approved hydraulic dead plugs to plug
right, outrigger, water pump, or any extend the inlet hose to the malfunctioning circuit. If
function. (Again, when you try to retract a fully pressure can now be achieved, the e-stop manifold
retracted cylinder, the oil has no where to go except is the source of the problem. Contact Schwing
over the relief valve; this allows the relief valve Americas Service Department for advice on repair
setting to be read on a gauge). Read the pressure on of the e-stop manifold. Repair the e-stop manifold
the whip gauge that you installed in step 4, above. before using the unit again. Remember, the
It should read 300 bar. If no adjustment is emergency stop switches do nothing if the e-stop
necessary, skip to step 8. manifold is plumbed out of the system.
6. If adjustment is needed, put your wrench on the
300 bar relief valve at the back of the boom control
valve bank. While you are holding the function in
retract mode, adjust the cartridge in or out until the
pressure reads 300 bar.
revDate
170 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

7plcpres.eps

Use #2, 3, or 4
140 bar port

140 bar relief

300 bar port SECTION 1 SECTION 2 SECTION 3 SECTION 4 SLEWING AIR / WATER BOOM / OUTRIG.

DANGER WARNING
Electrocution hazard. Do not operate this
Stay back from high machine without
training. Understand
voltage wires at least SAFETY

the warnings in safety


17 feet (5 meters). MANUAL
manuals and on decals.

Figure 164
Showing the location of the boom circuit pressure devices.
(Hoses removed for clarity.)

Turn body of valve


Higher to adjust.

Lower
300 bar
Relief Valve

s
ep
m.
oo
lcb
7p

Figure 165
Location of the boom relief valve

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 171
HOME PRINT

Pressure Settings
8. Remove the whip hose from the 300 bar gauge
port. Before folding up the boom, proceed to the
instructions for setting the 140 bar down side relief
valve on page 172.

S
MP
Boom/outrigger
T circuit dump
valve
S
MP

P3
ps
res.e
opp
est

P2
Boom
P4 P1
override
button

Boom/outrigger
inlet port

Figure 166
Emergency stop manifold

Setting the 140 bar down side relief valve 3. Bring #1 down until the cylinder is completely
pressure bottomed out. The cylinder does NOT bottom out
if you are setting the folded boom into the A-frame
Set the pressure of the 140 bar down side relief valve.
(travel position).
This valve is a secondary relief valve for #1 cylinder
retract function. Proper adjustment ensures that the #1 4. Activate the #1 down (retract) handvalve The
boom and the A-frame wont be damaged by putting boom will not be able to move because the cylinder
the boom in the cradle. (See figure 167.) To adjust this is already bottomed out. Read the pressure on the
valve (requires a 2.5 mm Allen wrench and a standard gauge that you just installed. It should read 140
screwdriver): bar. If no adjustment is necessary, skip to step 6.
1. Install a 0 - 400 bar or 0 - 600 bar gauge into the 5. If adjustment is needed, loosen the set screw of the
140 bar gauge port (shown in Figure 134). 140 bar relief valve with the 2.5 mm Allen wrench.
While you activate #1 down, adjust the relief
2. Unfold the #2 section from #1 until it is straight.
cartridge with the screwdriver until the pressure
For the following procedure we must bring #1 all
reads just under 140 bar. Retightening the set screw
the way down until the cylinder bottoms out.
will raise the pressure slightly. Recheck the
Position the boom so this can be done without
pressure, and readjust if needed.
hitting the truck or any other obstacle.

revDate
172 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
6. When the pressure is set at 140 bar with the set 7. The boom pressure setting sequence is complete. If
screw tight, you can remove the whip hose gauge you are done with the boom, slew it back into the
and replace the cap on the gauge port. transport position, and lower #1 into the cradle.
Reattach the boom strap.

7plc140.eps

140 bar gauge port

140 bar relief valve

SECTION 1 SECTION 2 SECTION 3 SECTION 4 SLEWING AIR / WATER BOOM / OUTRIG.

DANGER WARNING
Electrocution hazard. Do not operate this
Stay back from high machine without
training. Understand
voltage wires at least SAFETY

the warnings in safety


17 feet (5 meters). MANUAL
manuals and on decals.

Figure 167
location of the 140 bar relief valve and gauge port

Setting the outrigger pressures (7 place 2. Plug the whip hose of a 0 - 400 or 0 - 600 bar
boom valve systems) gauge into the gauge port. Location is shown in
figure 46.
After the boom pressures are set, you can set the
outrigger pressure. 3. If not already done, start the truck engine and set
In this system, the boom, outriggers, water pump, the transmission and PTO as you would for a
and compressor circuits have all been put together pumping job.
in the boom valve manifold. (See Figure 46). When 4. Locate the 280 bar relief valve on the back of the
the outrigger selector pushbutton is activated, the outrigger valve, as shown in Figure 47.
outrigger valve routes oil to the two outrigger 5. Set the engine RPM to maximum.
handvalve banks, one on each side of the unit. A 6. Select outrigger with the outrigger pushbutton.
relief valve inside the passenger side bank limits This will route oil to the outrigger handvalves.
the entire outrigger circuit to 280 bar (4060 PSI)
7. Assuming that the outriggers are folded into the
instead of the 300 bar (4350 PSI) of the boom
travel position, activate the passenger side
relief valve.
handvalve jacking cylinder retract for either the
To set the 280 bar relief valve for the outrigger front or rear outrigger. Note! You will get an
circuit: (See Figure 170). incorrect reading if you select extension cylinder
retract by mistake. If you select extend by
mistake, the outriggers will extend instead of
1. Wear safety glasses whenever you check or set
reading the relief valve setting. The handles are
pressures.
spring loaded and will return to neutral as soon as
you let go.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 173
HOME PRINT

Pressure Settings

7plcORhndl.eps

Outrigger handle

Gauge port

SECTION 1 SECTION 2 SECTION 3 SECTION 4 SLEWING AIR / WATER BOOM / OUTRIG.

DANGER WARNING
Electrocution hazard. Do not operate this
Stay back from high machine without
training. Understand
voltage wires at least SAFETY

the warnings in safety


17 feet (5 meters). MANUAL
manuals and on decals.

Figure 168
Position of the outrigger selector valve

32Porct5.eps

REAR EXTEND FRONT EXTEND REAR FOOT FRONT FOOT

Figure 169
Location of the passenger side outrigger control block

revDate
174 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

280 bar
Lower Relief Valve

PS
oc
bb
ck.
Higher ep
s

Turn body of valve


to adjust.

Figure 170
Location of the outrigger relief valve

8. Read the pressure on the gauge. It should read 280 2. Unscrew the cover from the gauge port. Plug in the
bar (4060 PSI). If no adjustment is needed, skip to 0 - 600 bar gauge and whip hose that came in the
step 10. toolbox.
9. If adjustment is needed, turn the outside body of 3. Start the engine, if not already running.
the relief valve that is located at the back of the 4. Close the agitator shutoff valve. (See Figure 172.)
outrigger valve. Turn in to raise pressure, turn out Note! If your unit does not have a shutoff valve,
to lower pressure. There is no jam nut on this you can order one using part number 10004680
valve. (valve) and part number 30303432 (tube). Contact
10. Activate the outrigger jacking retract handvalve Schwings Service Dept. for installation
and read the pressure on the gauge again. Repeat instructions.
steps 8. and 9. until the gauge reads 280 bar. 5. Activate the agitator in forward. Read the pressure
11. When the pressure is correct, either go on to other on the gauge.
pressure settings, or remove the whip hose and 6. If adjustment is needed, put your wrench on the
gauge, and cap the gauge port with the attached body of the relief valve, which is located on the
cap. back of the agitator handvalve. While reading the
12. Return the RPM of the truck to an idle, take the gauge, turn the body in to raise pressure, or out to
transmission and PTO out of gear, and shut off the lower pressure until 200 bar is achieved.
truck, or go on to the other pressure settings, as 7. Put the agitator handle in neutral.
required.
8. Remove the whip hose and pressure gauge.
Replace the gauge port cover.
To set the agitator circuit pressure:
9. Replace the aluminum diamond plate over the
The agitator relief valve is located in the agitator agitator handvalve.
forward / neutral / reverse handvalve, at the rear of the
unit on the drivers side. The relief valve limits the
pressure in the agitator circuit to 200 bar (2900 PSI).
(See Figure 171). There is a gauge port for checking or
setting the pressure in this circuit. The port is located
on the agitator handvalve. To check or set the agitator
pressure, follow these steps:
1. Remove the aluminum diamond plate cover from
over the agitator handvalve.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 175
HOME PRINT

Pressure Settings

agitator pressure check.eps L


Relief valve on this
side (not visible from
this angle).
Gauge port

Figure 171
Showing the agitator handvalve and gauge port.
(Diamond plate removed for this illustration.)

closed
s
ep
o.
its
ag

open

Figure 172
The agitator shutoff valve

revDate
176 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
32 XL High Flow Proportional engine off, and the key in your pocket,
remove the plug (item 2). The oil should be at
the level of the bottom of the hole in the case.
Units up to 450 l/m If oil is needed, add by removing the breather
5.3-6 Check the fluid level of the distribution gear- (item 1) and pouring in through the top. This
case. (See Figure 173). Be sure the truck is on gearcase uses 90W gearlube.
reasonably level ground. With the truck

2
4194.e
ps

Figure 173
Check, drain and fill ports of the Stiebel 4194 gearcase

Check the mounting hardware of the subframe, the 1. Locate the agitator shutoff valve and close it. There
oil and water tanks, the delivery pipeline, the is a picture of the location on page 6-228. Note! If
pumpkit, the differential cylinders, the material your unit does not have a shutoff valve, you can
cylinders and the driveline hardware. Check for order one using part number 10004680 (valve) and
bolt tightness, cracks and other abnormalities. part number 30303432 (tube). Contact Schwings
Service Department at (651) 429-0999 for
Check hydraulic pressures installation instructions.
Check all hydraulic pressures. Changes in 2. Turn on the agitator. The agitator will not be able
pressures can indicate trouble in one or more to turn, and the oil will be forced over the relief
components. Pressure settings must be made with valve.
the oil at normal operating temperatures (40 to 3. At an idle (approx. 600 rpm), about 5.4 horsepower
60 C).The specifications for all circuit pressures is being converted to heat. Shut off the agitator
are found on the hydraulic schematics in the when the temperature gauge on the rear control
appendix section of this manual. panel shows 40 C. Dont forget to open the shutoff
Preheat the hydraulic oil
valve when the procedure is finished.
Because of the new load sensing and pressure cut-
Check the concrete pump pressure (2020,
off regulated hydraulic systems, you cant use the
2023, 2525 pumpkits)
concrete pump or boom circuit to preheat the
hydraulic oil (they stop putting out oil if you try). Because the Hi-flow pumpkits have the ability to
To heat the oil to operating temperature: create high pressure on the concrete the pressure
settings have to be tailored specifically for each
model. This means that we cannot simply list a
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 177
HOME PRINT

Pressure Settings
pressure specification for all units. The correct manual. (See Figure 37).
pressure specifications for your unit are shown on
the hydraulic schematic in Section 7 of this

Gauge port

Hif
lrv
vw
.ep
s

Main relief valve

Soft switch
relief valve

Figure 174
Location of the concrete pump circuit main
relief valve and soft switch relief valve

To check or set the concrete pump pressure 9. Put the concrete pump forward / neutral / reverse
adjustments, follow these steps: switch on the rear control panel into the forward
position. The unit will stroke no more than once,
then the rock cylinder will retract. Oil leaving the
1. Wear safety glasses when checking or setting
hydraulic pumps will be blocked in the brain. This
pressures.
is called high-pressuring the concrete pump.
2. Be sure that the waterbox covers and guards are
10. Read the pressure on the gauge. Pressure should
installed on the waterbox. Use of the remote
read as shown for the concrete pump circuit main
control box for the following pressure setting
relief valve setting on the hydraulic schematic.
procedure is NOT recommended.
Return the pump control to neutral whether the
3. Start the truck engine, and put the PTO and pressure needs adjustment or not. If no adjustment
transmission into gear just as you would to pump a is needed, skip to step (14.) on page 6-218. If
job. adjustment is needed, proceed to step (10.).
4. See Figure 174. Locate and close the concrete
pump shutoff valve, and the soft switch shutoff Setting the main relief valve
valve. (These valves are also known as quarter The main relief valve is the primary pressure control
turn valves). device on units equipped with Rexroth A7VO
5. Install a 0 - 400 or 0 - 600 bar gauge in the gauge hydraulic pumps.
port. CAUTION! The main relief valve is set to very high
6. Put the rear control panel switch remote / local pressure (at least 350 bar). Use the rear control panel
into the local position. switch when checking the pressure of the main relief
7. Be sure that all emergency stop switches are in the valve so you will be out of the way if a hose or fitting
up (not activated) position. Reset the e-stop circuit. blows. See Figure 5. If the main relief valve needs
8. Using the switch on the rear control panel, rev the adjustment, proceed as follows:
truck engine up to full RPM.

revDate
178 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Soft switch
shutoff valve

Main pressure
gauge port

Concrete pump
shutoff valve hif
low
br
n.
ep
s

Figure 175
Showing the concrete pump and soft switch shutoff

closed

Groove lined up with ports


- open open
grooves.eps

Groove at 90 to ports
- closed
op
n-c
lsd
.ep
s

Figure 176
Shutoff valve open / closed orientation

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 179
HOME PRINT

Pressure Settings

Gauge port

Hif
lrv
vw
.ep
s

Main relief valve

Soft switch
relief valve

Figure 177
Location of the main relief valve

1. Open the soft switch shutoff valve, as shown in


1. Wear safety glasses when checking or adjusting Figure 176. The rest of the unit should still be set
pressures. up as though you were going to check concrete
pump pressure.
2. Using a 9/16 spanner wrench, loosen the jam nut
2. High pressure the concrete pump. The pressure
on the main relief valve adjusting screw (Figure gauge should read 60 or 80 bar (check your
177). schematic). If adjustment is needed, proceed to
3. Insert a 5/32 allen wrench in the adjustment screw. step (4), below. If no adjustment is needed, skip to
Turn the screw in to raise pressure, out to lower the step (4.).
pressure. Always go back to the rear panel before 3. Loosen the jam nut on the soft switch relief valve
checking the pressure. with a 9/16 spanner wrench. Adjust the pressure up
4. Once the pressure is correct to the hydraulic or down, as needed, using a 5/32 Allen wrench.
schematic, retighten the jam nut. Tightening the
When the correct pressure is achieved, re-lock the
nut tends to raise the pressure, so check pressure
jam nut.
again after tightening. Dont forget to turn the
pressure cut-off adjustment screws back out 1 turn 4. Be sure to open the concrete pump shutoff valve on
each and verify the correct pressure setting before the side of the brain (shown in Figure 176) when
unplugging the gauge. you are finished. The unit cannot stroke with this
valve closed.
5. If you will not be setting the soft switch pressure,
open the shutoff valves. The unit will not stroke
Load-sensing boom pressures
with closed shutoff valves.
(7 place proportional circuit) If your unit has a load-
Setting the soft switch circuit relief sensing proportional system, it will have different
pressure pressure adjustments than if it is equipped with a black
To check or adjust the soft switch pressure setting, and white boom system. The following instructions are
proceed as follows: for load-sensing proportional systems. If you have a
unit equipped with a black and white boom system,
contact Schwing Service for the correct instruction
pages.

revDate
180 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Preheat the oil system. Generally, the pump puts out enough oil to
Note! Whenever you set pressures for any circuit on maintain a 20 bar higher pressure at the pump than
any unit, the hydraulic oil should be at normal operat- what the cylinders actually require. This 20 bar is
ing temperature (40 - 60 C). Instructions for heating called delta P (P). Additionally, we set the hydraulic
the hydraulic oil are found in section on page 217. pump so that it always puts out a small amount of oil,
even if no oil is needed for the system. This oil is used
About proportional boom systems to ensure that you have control when you need it. The
In a black and white boom system, the hydraulic pump setting to maintain this minimum amount of oil is
puts out an unchanging amount of oil, and speed called Q-min (pronounced cue min). To set the boom
control is done by restricting the oil to certain functions or outrigger hydraulic pressures on a load-sensing
with orifices. In a load-sensing system, the pump puts system, begin by setting Q-min and P. See figure 180.
out more or less oil to respond to the needs of the

Manual P regulator Q-min adjustment screw


boom handvalves

CONCRETE PUMP

REV FWD

s
.ep
loc
XL
32

Figure 178
Locations of components
used to check and set
boom pressures
E-Stop manifold

Read all of the instructions before beginning any pres-


sure settings. You will need an assistant for parts of the
procedure. You and any assistants should wear eye pro-
tection when checking or setting pressures.

Setting P
Note! Do not adjust P or Q-min if your boom is
running as you like it. The pressure setting procedure
uses a standard starting point and must be fine tuned
from there. It was fine tuned at the factory, and should
not be adjusted unless absolutely necessary.
You must not adjust Q-min with the drive shafts
turning! Each time the Q-min screw must be
adjusted, the engine must be stopped, or at least the
transmission must be taken out of gear so that the
drivelines stop turning. To check or set P, follow
these steps:
1. Stop the truck engine and place a Do Not
Operate sign on the truck windshield.
2. Install a 0-40 or 0-60 bar gauge in the 0-400 bar
gauge port of the manual boom handvalves. Take
care not to accidently install the gauge in the 0-60
bar port. (See Figure 179.)

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 181
HOME PRINT

Pressure Settings

140 bar gauge port (use 0-400


bar gauge when checking)

140 bar downside


relief cartridge
0-400 bar
gauge port
0-60 bar
gauge port

boom control
ps
block relief valve
v.e
itprd
ap

15 bar pretension
adjustment screw

Figure 179
Location of the boom circuit pressure devices
(Hoses removed for clarity.)
3. To be sure that the pump is putting out only enough boom or outrigger functions, you will damage
oil needed to maintain P, we need to change the the 0 - 40 bar gauge. Make sure that all
setting of the Q-min screw. Q-min is adjusted by a emergency stop switches are in the up (not
screw on the boom hydraulic pump (see Figure activated) position. Pressure can be read on the 0 -
180). Unscrew the Q-min screw three full turns. 40 bar gauge that you installed. Pressure should
Check that all personnel are clear of the truck, then read 20 bar. If no adjustment is needed, simply
restart the engine, engage the pumps, and leave the reset the Q-min screw as described in . If
engine at an idle. CAUTION! If you activate any adjustment is needed, continue to step (4.).

Q-min
adjustment screw

Q-minscrew.eps

Q-max

Figure 180
Location of the Q-min adjustment screw

4. Delta P is adjusted by the P screw on the P outward to decrease pressure until it is set at 20 bar
regulator (see Figure 181). Loosen the jam nut and (1). Contact Schwing Americas Service
adjust the screw inward to increase pressure, or Department if you are unable to adjust the pressure
revDate
182 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
to spec. NOTE! If the boom is not smooth at 20 affect how the boom operates, so if P adjustment
bar, you must fine tune the adjustment. In that case, does not seem to help, reset to 20 bar and check the
REMOVE THE GAUGE, and adjust P until the electrical settings. Once electrical settings are
boom is responsive and smooth. When done, the verified, you could again refine the boom action
gauge (reinstalled) must read between 14 and 25 with the P adjustment.
bar. The electronics in the control system can also

CAUTION
Do not operate any functions while setting P.

000435.eps

T
P adjustment screw

Figure 181
The P regulator valve

Setting Q-min pressure is correct, tighten the jam nut on the


You must check Q-min pressure when the engine adjustment screw before continuing with the other
is at the maximum specified RPM, but you must procedures.
adjust it with the engine stopped.
Setting boom pressures
1. If you unscrewed the Q-min screw as the first step
of P adjustment, begin by returning the screw to (Load sensing proportional booms.) Now that P and
its original position (see Figure 180). Q-min are set, you can check or set the boom valve
2. Remove the 0 - 40 bar gauge from the 0 - 400 bar pressures.
gauge port, and install the 0 - 600 bar gauge in its There are three pressure settings on the boom
place. circuit: (see Figure 182)
3. Clear all personnel away from the drive lines, start 1. Pressure regulator (the high-pressure adjustment
the truck engine, engage the pumps, and bring screw on the P regulator valve), set at 300 bar.
engine RPM to max. All boom functions must be in 2. The redundant relief valve located in the
neutral, and all emergency stop buttons should be emergency stop manifold, set at 330 bar.
up (not engaged).
4. Read the pressure on the 0 - 600 gauge. Pressure
should be at 40 - 45 bar. If no adjustment is needed,
stop the drivelines from turning, be sure the jam
nut on the Q-min screw is tight, then continue to
paragraph to check the rest of the boom and
outrigger pressures. If adjustment is needed,
continue to step (5.).
5. Turn the Q-min screw in to raise the pressure
(Figure 180). Turn it out to lower the pressure. Be
sure that you stop the drive shafts from turning
each time before making the adjustment. When

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 183
HOME PRINT

Pressure Settings
3. The boom control block relief valve, set at 350 bar.
NOTE! This relief valve is nonadjustable. If
pressure is not maintained with the specification
limits, the valve must be replaced.

High pressure Redundant


adjustment screw relief valve

MP
1

TT

M
10
16
78

P1
92
-7.
ep
s

P4
P2
P3
0-400 bar
gauge port
0-60 bar
gauge port

.ep
s Figure 182
nly
ipo
ap
boom control The three boom pressure devices
block relief valve

To check the setting of the valve with the highest over the relief valve.
pressure, you must first raise the pressure of the
lower two: The telltale hiss of an open relief valve should be
4. Loosen the jam nut of the high pressure adjustment coming from the Apitech control block relief valve
screw of the P regulator. Turn the screw in two- now. If it isnt, raise the setting of the other
and-a-half turns. This will raise the pressure on the pressure devices until the hiss originates at the
regulator above 350 bar. Apitech control block relief valve. Read the
pressure on the gauge. It should read 350 bar. If
5. Loosen the jam nut of the adjustment screw of the
pressure is correct, proceed to step (4.).
redundant relief valve in the emergency stop
manifold. Turn the screw in one-and-a-half turns.
NOTE! Although the pressure specification for the
This will raise the pressure setting of the relief
Apitech relief valve is 350 bar, you may continue
valve to above 350 bar.
to use the relief valve as long as the cartridge
6. Pressure out any boom cylinder except #1 down by maintains at least 330 bar. If you must replace the
pushing or pulling the control handle. To pressure valve, proceed to step (4.) before using the
out a cylinder, retract a fully retracted cylinder or machine again, and redo this entire procedure
extend a fully extended cylinder. The oil is forced when you have installed the new valve. If pressure
revDate
184 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
on the Apitech relief valve is below 290 bar, you 5. If adjustment is needed, loosen the set screw of the
should not use the machine until the valve is 140 bar relief valve with the 2.5 mm allen wrench.
replaced. While you activate #1 down, adjust the relief
7. Screw out the e-stop manifold redundant relief cartridge with the screwdriver until the pressure
valve adjustment screw one-and-a-half turns. reads just under 140 bar. Retightening the set screw
Pressure out any boom cylinder except #1 down, will raise the pressure slightly. Recheck the
and read the gauge. Pressure should read 330 bar. pressure, and readjust if needed.
If it does not, turn the screw in to raise pressure, or 6. When the pressure is set at 140 bar with the set
out to lower pressure until it is set at 330 bar. If the screw tight, you can remove the whip hose gauge
location of this valve causes you to be near the and replace the cap on the gauge port.
drivelines, be sure to stop them from turning before 7. The boom pressure setting sequence is complete. If
accessing the valve. you are done with the boom, slew it back into the
8. You will need a helper for this step. While transport position, and lower #1 into the cradle.
pressuring out any boom cylinder except #1 down, Reattach the boom strap.
have your helper adjust the high pressure screw of
the P regulator out (lowering the pressure) until Setting the outrigger pressures
the gauge reads 300 bar. Release the pressurized After the boom pressures are set, you can set the
function and lock the jam nut. The boom pressures outrigger pressure.
are now set. If you did not get the readings In this system, the boom, outriggers, water pump,
specified after following the instructions, contact and compressor circuits have all been put together
Schwing Americas Service Department at (651) in the boom valve manifold. (See Figure 46). When
429-0999 for advice on how to continue. the outrigger selector pushbutton is activated, the
outrigger valve routes oil to the two outrigger
Setting the 140 bar down side relief valve handvalve banks, one on each side of the unit. A
pressure relief valve inside the passenger side bank limits
Set the pressure of the 140 bar down side relief valve. the entire outrigger circuit to 280 bar (4060 PSI)
This valve is a secondary relief valve for #1 cylinder instead of the 300 bar (4350 PSI) of the boom
retract function. Proper adjustment ensures that the #1 relief valve.
boom and the A-frame wont be damaged by putting To set the 280 bar relief valve for the outrigger
the boom in the cradle. (See figure 183.) To adjust this circuit: (See Figure 46 & Figure 47).
valve (requires a 2.5 mm Allen wrench and a standard
screwdriver):
1. Install a 0 - 400 bar or 0 - 600 bar gauge into the 1. Wear safety glasses whenever you check or set
140 bar gauge port (shown in Figure 183). pressures.
2. Unfold the #2 section from #1 until it is straight. 2. Plug the whip hose of a 0-400 or 0-600 bar gauge
For the following procedure we must bring #1 all into the gauge port. Location is shown as item 1 in
the way down until the cylinder bottoms out. figure 46.
Position the boom so this can be done without 3. If not already done, start the truck engine and set
hitting the truck or any other obstacle. the transmission and PTO as you would for a
3. Bring #1 down until the cylinder is completely pumping job.
bottomed out. The cylinder does NOT bottom out 4. Locate the 280 bar relief valve on the back of the
if you are setting the folded boom into the A-frame outrigger valve, as shown in Figure 185.
(travel position). 5. Set the engine RPM to maximum.
4. Activate the #1 down (retract) handvalve The 6. Select outrigger with the outrigger pushbutton.
boom will not be able to move because the cylinder This will route oil to the outrigger handvalves.
is already bottomed out. Read the pressure on the
gauge that you just installed. It should read 140
bar. If no adjustment is necessary, skip to step 6.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 185
HOME PRINT

Pressure Settings

140 bar
gauge port

140 bar relief valve

ps
0.e
it14
ap

Figure 183
Location of the 140 bar relief valve and gauge port

1
Gauge port

s
.ep
hd
itor
ap

Outrigger handle

Figure 184
Position of the outrigger selector valve on units
equipped with Apitech proportional valves

revDate
186 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

280 bar
Lower Relief Valve

32Porct5.eps
PS
oc
bb
ck.
Higher ep
s

Turn body of valve


to adjust.

REAR EXTEND FRONT EXTEND REAR FOOT FRONT FOOT

Figure 185
Location of the 280 bar outrigger
pressure relief valve.
(Hoses removed for clarity).

7. Assuming that the outriggers are folded into the 11. When the pressure is correct, either go on to other
travel position, activate the passenger side pressure settings, or remove the whip hose and
handvalve jacking cylinder retract for either the gauge, and cap the gauge port with the attached
front or rear outrigger. Note! You will get an cap.
incorrect reading if you select extension cylinder 12. Return the RPM of the truck to an idle, take the
retract by mistake. If you select extend by transmission and PTO out of gear, and shut off the
mistake, the outriggers will extend instead of truck, or go on to the other pressure settings, as
reading the relief valve setting. The handles are required.
spring loaded and will return to neutral as soon as
you let go. Setting the water pump hyd. pressure
8. Read the pressure on the gauge. It should read 280 With a seven place handvalve, the water pump
bar (4060 PSI). If no adjustment is needed, skip to hydraulic control is inside the boom control block.
step 10. There is not a separate relief for this circuit, and
9. If adjustment is needed, turn the outside body of therefore nothing that must be set.
the relief valve that is located at the back of the
outrigger valve. Turn in to raise pressure, turn out Setting 15 bar pretension
to lower pressure. There is no jam nut on this To check or set pretension, follow these steps:
valve.
1. Stop the truck engine. Plug the 0 - 40 bar gauge
10. Activate the outrigger jacking retract handvalve into the pretension check port of the Apitech
and read the pressure on the gauge again. Repeat handvalve (Figure 183).
steps 8. and 9. until the gauge reads 280 bar.
2. Start the truck engine, but leave it at an idle.
(Pretension adjustment is made at an idle to
establish the minimum pressure setting. As RPM is

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 187
HOME PRINT

Pressure Settings

CAUTION
Truck engine must be at an idle while setting pretension.

increased, pressure will rise. Damage to the 0 - 40 3. Read the pressure on the gauge. If it reads 15 bar
bar gauge is possible if RPM is raised while the 1 bar, the pressure is set correctly. If adjustment is
gauge is connected.) needed, proceed to step (4.).

Pretension
gauge port

s
.ep
rtn
itp
ap

Pretension adjustment screw

Figure 186
Pretension adjustment screw and gauge port

4. Loosen the jam nut on the pretension valve. Turn 2. Unscrew the cover from the gauge port. Plug in the
the screw in to raise pressure, and out to lower 0-600 bar gauge and whip hose that came in the
pressure. When the pressure is correct, retighten toolbox.
the jam nut. 3. Start the engine, if not already running.
5. Stop the engine, and remove the 0 - 40 bar gauge. 4. Close the agitator shutoff valve. (See Figure 188.)
Pretension setting is complete. Note! If your unit does not have a shutoff valve,
you can order one using part number 10004680
To set the agitator circuit pressure: (valve) and part number 30303432 (tube). Contact
The agitator relief valve is located in the agitator Schwing Americas Service Department at (651)
forward / neutral / reverse handvalve, at the rear of the 429-0999 for installation instructions.
unit on the drivers side. The relief valve limits the 5. Activate the agitator in forward. Read the pressure
pressure in the agitator circuit to 200 bar (2900 PSI). on the gauge.
(See Figure 187). There is a gauge port for checking or 6. If adjustment is needed, put your wrench on the
setting the pressure in this circuit. The port is located body of the relief valve, which is located on the
on the agitator handvalve. To check or set the agitator back of the agitator handvalve. While reading the
pressure, follow these steps: gauge, turn the body in to raise pressure, or out to
1. Remove the aluminum diamond plate cover from lower pressure until 200 bar is achieved.
over the agitator handvalve. 7. Put the agitator handle in neutral.
8. Remove the whip hose and pressure gauge.
Replace the gauge port cover.
revDate
188 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

agitator pressure check.eps L


Gauge port Relief valve on this
side (not visible from
this angle).

Figure 187
Showing the agitator handvalve and gauge port.
(Diamond plate removed for this illustration.)

closed ag
its
o.
ep
s

open
Figure 188
The agitator shutoff valve

9. Replace the aluminum diamond plate over the


agitator handvalve.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 189
HOME PRINT

Pressure Settings

revDate
190 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
32 XL Hi-Flow Prop, A11VO off, and the key in your pocket, remove the plug
(item 2). The oil should be at the level of the
bottom of the hole in the case. If oil is needed, add
Units above 450 l/m (-5 and -6 units)
by removing the breather (item 1) and pouring in
Check the fluid level of the distribution gearcase. through the top. This gearcase uses 90W gearlube.
(See Figure 189). Be sure the truck is on
reasonably level ground. With the truck engine

Breather / filler
grbx-5-6.eps

Check port

Figure 189
Drain port
Check, drain and fill ports of the Stiebel
gearcase.
Main ports (left illustration)
Spline flange ports (right illustration)

Check the mounting hardware of the subframe, the part number 30303432 (tube). Contact Schwings
oil and water tanks, the delivery pipeline, the Service Department at (651) 429-0999 for
pumpkit, the differential cylinders, the material installation instructions.
cylinders and the driveline hardware. Check for 2. Turn on the agitator. The agitator will not be able
bolt tightness, cracks and other abnormalities. to turn, and the oil will be forced over the relief
valve.
Check hydraulic pressures
3. At an idle (approx. 600 rpm), about 5.4 horsepower
Check all hydraulic pressures. Changes in is being converted to heat. Shut off the agitator
pressures can indicate trouble in one or more when the temperature gauge on the rear control
components. Pressure settings must be made with panel shows 40 C. Dont forget to open the shutoff
the oil at normal operating temperatures (40 to valve when the procedure is finished.
60 C).The specifications for all circuit pressures
are found on the hydraulic schematics in the Check the concrete pump pressure (2020,
appendix section of this manual. 2023, 2525 pumpkits)
Preheat the hydraulic oil Because the Hi-flow pumpkits have the ability to create
high pressure on the concrete the pressure settings have
Because of the new load sensing and pressure cut-
to be tailored specifically for each model. This means
off regulated hydraulic systems, you cant use the
that we cannot simply list a pressure specification for
concrete pump or boom circuit to preheat the
all units. The correct pressure specifications for your
hydraulic oil (they stop putting out oil if you try).
unit are shown on the hydraulic schematic in section 7
To heat the oil to operating temperature:
of this manual. (See Figure 37). Additionally, the
1. Locate the agitator shutoff valve and close it. There pressure is not limited by the main relief valve, but
is a picture of the location on page 6-228. Note! If rather by a pressure cutoff adjustment on the concrete
your unit does not have a shutoff valve, you can
order one using part number 10004680 (valve) and
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 191
HOME PRINT

Pressure Settings
pump circuit hydraulic pumps.
To check or set the concrete pump pressure
adjustments, follow these steps:

Gauge port

Hif
lrv
vw
.ep
s

Main relief valve

Soft switch
relief valve

Figure 190
Location of the concrete pump circuit
main relief valve and soft switch relief

then the rock cylinder will retract. Oil leaving the


1. Wear safety glasses when checking or setting hydraulic pumps will be blocked in the brain. This
pressures. is called high-pressuring the concrete pump.
2. Be sure that the waterbox covers and guards are 10. Read the pressure on the gauge. Pressure shown on
installed on the waterbox. Use of the remote the gauge is actually the hydraulic pump cutoff
control box for the following pressure setting pressure, because it is set to the lowest setting.
procedure is NOT recommended. Pressure should be as shown for the concrete pump
3. Start the truck engine, and put the PTO and circuit hydraulic pumps on the hydraulic
transmission into gear just as you would to pump a schematic. Return the pump control to neutral
job. whether the pressure needs adjustment or not. If no
adjustment is needed, skip to step (14.) on page 6-
4. See Figure 38. Locate and close the concrete pump 218. If adjustment is needed, proceed to step (11.).
shutoff valve, and the soft switch shutoff valve.
(These valves are also known as quarter turn 11. Shut off the truck, put the key in your pocket, and
valves). put a Do not operate sign on the truck
windshield.
5. Install a 0 - 400 or 0 - 600 bar gauge in the gauge
port. 12. See Figure 192. Loosen the jam nut (13mm
spanner wrench) on both pressure cutoff
6. Put the rear control panel switch remote / local adjustment screws. Using a 4mm Allen wrench,
into the local position. turn the screw in to raise pressure, or out to lower
7. Be sure that all emergency stop switches are in the
up (not activated) position. Reset the e-stop circuit.
8. Using the switch on the rear control panel, rev the
truck engine up to full RPM.
9. Put the concrete pump forward / neutral / reverse
switch on the rear control panel into the forward
position. The unit will stroke no more than once,
revDate
192 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Soft switch
shutoff valve

Main pressure
gauge port

Concrete pump
shutoff valve hif
low
br
n.
ep
s

closed
Groove lined up with ports
- open

grooves.eps

Groove at 90 to ports
- closed
open

Figure 191
Showing the concrete pump and soft switch shutoff valves
and their open/closed orientation op
n-c
lsd
.ep
s

pressure. Turn the screw on each pump an equal Setting the main relief valve
amount. On these screws, very small adjustments The main relief valve is not the primary pressure con-
make a big pressure difference. trol device on units with Hi-flo pumpkits.

Pressure cut-off adjustment screws CAUTION! The main relief valve is set to very high
pressure (at least 350 bar). Use the rear control panel
switch when checking the pressure of the main relief
valve so you will be out of the way if a hose or fitting
blows. Always wear eye protection when setting
pressures! See Figure 5. If the main relief valve needs
adjustment, proceed as follows:
1. If you ever need to check or adjust the main relief
valve, you must first screw in the pressure cut-off
screws on the hydraulic pumps by 1 turn each.
A11ctoff.eps
Then, when you high pressure the concrete pump,
Figure 192 you will be reading the setting of the main relief
Location of the pressure cut- valve.
off adjustment screws

13. Clear the area around the drivelines, then restart


the truck. Repeat steps (7.) through (12.) until the
pressure is as specified on the hydraulic schematic.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 193
HOME PRINT

Pressure Settings

Gauge port

Hif
lrv
vw
.ep
s

Main relief valve

Soft switch
relief valve

Figure 193
Location of the main relief valve

2. Using a 9/16 spanner wrench, loosen the jam nut 2. High pressure the concrete pump. The pressure
on the main relief valve adjusting screw (Figure gauge should read 60 or 80 bar (check your
193). schematic). If adjustment is needed, proceed to
step (4), below. If no adjustment is needed, skip to
3. Insert a 5/32 allen wrench in the adjustment screw. step (4.).
Turn the screw in to raise pressure, out to lower the 3. Loosen the jam nut on the soft switch relief valve
pressure. Always go back to the rear panel before
with a 9/16 spanner wrench. Adjust the pressure up
checking the pressure.
4. Once the pressure is correct to the hydraulic or down, as needed, using a 5/32 allen wrench.
schematic, retighten the jam nut. Tightening the When the correct pressure is achieved, re-lock the
nut tends to raise the pressure, so check pressure jam nut.
again after tightening. Dont forget to turn the 4. Be sure to open the concrete pump shutoff valve on
pressure cut-off adjustment screws back out 1 turn the side of the brain (shown in Figure 191) when
each and verify the correct pressure setting before you are finished. The unit cannot stroke with this
unplugging the gauge. valve closed.
5. If you will not be setting the soft switch pressure,
open the shutoff valves. The unit will not stroke Setting boom pressures
with closed shutoff valves. (7 place proportional circuit) If your unit has a load-
sensing proportional system, it will have different
Setting the soft switch circuit relief pressure adjustments than if it is equipped with a black
pressure and white boom system. The following instructions are
To check or adjust the soft switch pressure setting, for load-sensing proportional systems. If your unit is
proceed as follows: equipped with a black and white boom system, these
1. Open the soft switch shutoff valve, as shown in instructions will be wrong. Contact Schwing Americas
figure 191. The rest of the unit should still be set up Service Department at (651) 429-0999 to obtain
as though you were going to check concrete pump correct instructions.
pressure.

revDate
194 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Preheat the oil out more or less oil to respond to the needs of the
Note! Whenever you set pressures for any circuit on system. Generally, the pump puts out enough oil to
any unit, the hydraulic oil should be at normal maintain a 20 bar higher pressure at the pump than
operating temperature (40 - 60 C). Instructions for what the cylinders actually require. This 20 bar is
heating the hydraulic oil are found in section on page called delta P (P). Additionally, we set the hydraulic
6-217. pump so that it always puts out a small amount of oil,
even if no oil is needed for the system. This oil is used
About proportional boom systems to ensure that you have control when you need it. The
In a black and white boom system, the hydraulic pump setting to maintain this minimum amount of oil is
puts out an unchanging amount of oil, and speed called Q-min (pronounced cue min). To set the boom
control is done by restricting the oil to certain functions or outrigger hydraulic pressures on a load-sensing
with orifices. In a load-sensing system, the pump puts system, begin by setting Q-min and P. See figure 41.

Manual P regulator Q-min adjustment screw


boom handvalves

CONCRETE PUMP

REV FWD

Figure 194
Locations of components
used to check and set 32XLHF+.eps

boom pressures
E-Stop manifold

3. To be sure that the pump is putting out only enough


Read all of the instructions before beginning any oil needed to maintain P, we need to change the
pressure settings. You will need an assistant for parts of setting of the Q-min screw. Q-min is adjusted by a
the procedure. You and any assistants should wear eye screw on the boom hydraulic pump (see Figure
protection when checking or setting pressures. 195). Unscrew the Q-min screw three full turns.
Check that all personnel are clear of the truck, then
Setting P restart the engine, engage the pumps, and leave the
Note! Do not adjust P or Q-min if your boom is engine at an idle. CAUTION! If you activate any
running as you like it. The pressure setting procedure boom or outrigger functions, you will damage
uses a standard starting point and must be fine tuned the 0 - 40 bar gauge. Make sure that all
from there. It was fine tuned at the factory, and should emergency stop switches are in the up (not
not be adjusted unless absolutely necessary. activated) position. Pressure can be read on the 0 -
You must not adjust P or Q-min with the drive 40 bar gauge that you installed. Pressure should
shafts turning! Each time the P or Q-min screw read 20 bar. If no adjustment is needed, simply
must be adjusted, the engine must be stopped, or at reset the Q-min screw as described in . If
least the transmission must be taken out of gear so adjustment is needed, continue to step (4.).
that the drivelines stop turning. To check or set P, 4. Delta P is adjusted by the P screw on the boom
follow these steps: pump regulator (see Figure 195). Loosen the jam
1. Stop the truck engine and place a Do Not nut and adjust the screw inward to increase
Operate sign on the truck windshield. pressure, or outward to decrease pressure until it is
set at 20 bar (1). Contact Schwing Americas
2. Install a 0-40 or 0-60 bar gauge in the 0-400 bar Service Department if you are unable to adjust the
gauge port of the manual boom handvalves. Take pressure to spec. NOTE! If the boom is not smooth
care not to accidently install the gauge in the 0-60 at 20 bar, you must fine tune the adjustment. In that
bar port. (See Figure 195.) case, REMOVE THE GAUGE, and adjust P until
the boom is responsive and smooth. When done,
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 195
HOME PRINT

Pressure Settings
the gauge (reinstalled) must read between 14 and and check the electrical settings. Once electrical
25 bar. The electronics in the control system can settings are verified, you could again refine the
also affect how the boom operates, so if P boom action with the P adjustment.
adjustment does not seem to help, reset to 20 bar

Pressure Cut-off P adjustment screw


adjustment screw

Q-min.
adjustment screw

Hi
pm
pb
m.
ep
s

Figure 195
Boom pump adjustment screws

CAUTION
Do not operate any functions while setting P.

140 bar gauge port (use 0-400


bar gauge when checking)

140 bar downside


relief cartridge
0-400 bar
gauge port
0-60 bar
gauge port

boom control
ep
s
block relief valve
itprdv.
ap

15 bar pretension
adjustment screw

Figure 196
Showing the location of the boom circuit pressure devices.
(Hoses removed for clarity.)
revDate
196 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Setting Q-min 4. With the drive shafts stopped, loosen the jam nut of
You must check Q-min pressure when the engine the high pressure adjustment screw of the boom
is at the maximum specified RPM, but you must hydraulic pump pressure regulator. Turn the screw
adjust it with the engine stopped. in two-and-a-half turns. This will raise the pressure
of the regulator above 350 bar.
1. If you unscrewed the Q-min screw as the first step
of P adjustment, begin by returning the screw to 5. Loosen the jam nut of the adjustment screw of the
its original position (see Figure 195). redundant relief valve in the emergency stop
manifold. Turn the screw in one-and-a-half turns.
2. Remove the 0 - 40 bar gauge from the 0 - 400 bar
This will raise the pressure setting of the relief
gauge port, and install the 0 - 600 bar gauge in its
valve to above 350 bar.
place.
3. Clear all personnel away from the drive lines, start Pressure out any boom cylinder except #1 down by
the truck engine, engage the pumps, and bring pushing or pulling the control handle. To pressure out a
engine RPM to max. All boom functions must be in cylinder, retract a fully retracted cylinder or extend a
neutral, and all emergency stop buttons should be fully extended cylinder. The oil is forced over the relief
up (not engaged). valve.
4. Read the pressure on the 0 - 600 gauge. Pressure The telltale hiss of an open relief valve should be
should be at 40 - 45 bar. If no adjustment is needed, coming from the Apitech control block relief valve
stop the drivelines from turning, be sure the jam now. If it isnt, raise the setting of the other pressure
nut on the Q-min screw is tight, then continue to devices until the hiss originates at the Apitech control
paragraph to check the rest of the boom and block relief valve. Read the pressure on the gauge. It
outrigger pressures. If adjustment is needed, should read 350 bar. If pressure is correct, proceed to
continue to step (5.). step (4.).
5. Turn the Q-min screw in to raise the pressure
(Figure 44). Turn it out to lower the pressure. Be NOTE! Although the pressure specification for the
sure that you stop the drive shafts from turning Apitech relief valve is 350 bar, you may continue to
each time before making the adjustment. When use the relief valve as long as the cartridge maintains at
pressure is correct, tighten the jam nut on the least 330 bar. If you must replace the valve, proceed to
adjustment screw before continuing with the other step (4.) before using the machine again, and redo this
procedures. entire procedure when you have installed the new
valve. If pressure on the Apitech relief valve is below
Setting boom pressures 290 bar, you should not use the machine until the valve
(Load sensing proportional booms.) Now that P is replaced.
and Q-min are set, you can check or set the boom valve 6. Screw out the e-stop manifold redundant relief
pressures. valve adjustment screw one-and-a-half turns.
There are three pressure settings on the boom Pressure out any boom cylinder except #1 down,
circuit: (see Figure 197) and read the gauge. Pressure should read 330 bar.
1. Pressure regulator (the high-pressure adjustment If it does not, turn the screw in to raise pressure, or
screw on the boom hydraulic pump), set at 300 bar. out to lower pressure until it is set at 330 bar. If the
location of this valve causes you to be near the
2. The redundant relief valve located in the
drivelines, be sure to stop them from turning before
emergency stop manifold, set at 330 bar.
accessing the valve.
3. The boom control block relief valve, set at 350 bar.
7. With the truck engine off, adjust the high pressure
NOTE! This relief valve is nonadjustable. If
screw of the boom hydraulic pump regulator out
pressure is not maintained with the specification
(lowering the pressure) two-and-a-half turns. Start
limits, the cartridge valve must be replaced.
the engine, pressure out any boom cylinder except
To check the setting of the valve with the highest #1 down, and read the pressure on the gauge. It
pressure, you must first raise the pressure of the should read 300 bar. If not, repeat step (7.),
lower two: adjusting the screw a small amount each time, until
the gauge reads 300 bar when a cylinder is
pressured out.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 197
HOME PRINT

Pressure Settings

Redundant
relief valve

MP
1

TT

M 0-400 bar
gauge port
10
16
78 0-60 bar
P1

92
-7.
ep
s
gauge port
P4
P2
P3

s
.ep
nly
ipo
ap
boom control
block relief valve

Pressure Cut-off
adjustment screw

ILbmpmp.eps

Figure 197
The three boom pressure devices

8. With the truck engine off, lock the jam nut on the
high pressure screw you were adjusting in step (7.).
The boom pressures are now set. If you did not get
the readings specified after following the
instructions it is possible that there is a problem
with the emergency stop manifold (see Figure
198). You can plumb the malfunctioning circuit out
of the system to test it. Use only approved
hydraulic dead plugs to plug the inlet hose to the
malfunctioning circuit. If pressure can now be
achieved, the e-stop manifold is the source of the
problem. If pressure still cannot be achieved, the
problem is elsewhere. Contact Schwing Americas
Service Department for advice on how to continue.
If the problem was found to be the e-stop manifold,
repair it before using the unit again. Remember, the
emergency stop switches do nothing if the e-stop

revDate
198 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
manifold is plumbed out of the system. Remove
the whip hose from the 300 bar gauge port. Before
folding up the boom, proceed to the instructions
for setting the 140 bar down side relief valve.

S
MP
Boom/outrigger
T circuit dump
valve
S
MP

P3
ps
res.e
opp
est

P2
Boom
P4 P1
override
button

Boom/outrigger Figure 198


inlet port Emergency stop manifold

Setting the 140 bar down side relief valve 5. If adjustment is needed, loosen the set screw of the
pressure 140 bar relief valve with the 2.5 mm allen wrench.
While you activate #1 down, adjust the relief
Set the pressure of the 140 bar down side relief valve.
cartridge with the screwdriver until the pressure
This valve is a secondary relief valve for #1 cylinder
reads just under 140 bar. Retightening the set screw
retract function. Proper adjustment ensures that the #1
will raise the pressure slightly. Recheck the
boom and the A-frame wont be damaged by putting
pressure, and readjust if needed.
the boom in the cradle. (See figure 199.) To adjust this
valve (requires a 2.5 mm Allen wrench and a standard 6. When the pressure is set at 140 bar with the set
screwdriver): screw tight, you can remove the whip hose gauge
and replace the cap on the gauge port.
1. Install a 0 - 400 bar or 0 - 600 bar gauge into the
140 bar gauge port (shown in Figure 199). 7. The boom pressure setting sequence is complete. If
you are done with the boom, slew it back into the
2. Unfold the #2 section from #1 until it is straight.
transport position, and lower #1 into the cradle.
For the following procedure we must bring #1 all
Attach the boom strap.
the way down until the cylinder bottoms out.
Position the boom so this can be done without
hitting the truck or any other obstacle.
3. Bring #1 down until the cylinder is completely
bottomed out. The cylinder does NOT bottom out
if you are setting the folded boom into the A-frame
(travel position).
4. Activate the #1 down (retract) handvalve The
boom will not be able to move because the cylinder
is already bottomed out. Read the pressure on the
gauge that you just installed. It should read 140
bar. If no adjustment is necessary, skip to step 6.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 199
HOME PRINT

Pressure Settings

140 bar
gauge port

140 bar relief valve

ps
0.e
it14
ap

Figure 199
location of the 140 bar relief valve and gauge port.

Setting the outrigger 3. If not already done, start the truck engine and set
pressures (7 place boom valve systems) the transmission and PTO as you would for a
pumping job.
After the boom pressures are set, you can set the
outrigger pressure. 4. Locate the 280 bar relief valve on the back of the
In this system, the boom, outriggers, water pump, outrigger valve, as shown in Figure 201.
and compressor circuits have all been put together 5. Set the engine RPM to maximum.
in the boom valve manifold. (See Figure 199). 6. Select outrigger with the outrigger pushbutton.
When the outrigger selector push-button is This will route oil to the outrigger handvalves.
activated, the outrigger valve routes oil to the two 7. Assuming that the outriggers are folded into the
outrigger handvalve banks, one on each side of the travel position, activate the passenger side
unit. A relief valve inside the passenger side bank handvalve jacking cylinder retract for either the
limits the entire outrigger circuit to 280 bar (4060 front or rear outrigger. Note! You will get an
PSI) instead of the 300 bar (4350 PSI) of the boom incorrect reading if you select extension cylinder
relief valve. retract by mistake. If you select extend by
To set the 280 bar relief valve for the outrigger mistake, the outriggers will extend instead of
circuit: (See Figure 201). reading the relief valve setting. The handles are
spring loaded and will return to neutral as soon as
you let go.
1. Wear safety glasses whenever you check or set
8. Read the pressure on the gauge. It should read 280
pressures.
bar (4060 PSI). If no adjustment is needed, skip to
2. Plug the whip hose of a 0-400 or 0-600 bar gauge step 10.
into the gauge port. Location is shown as item 1 in
figure 201.

revDate
200 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
7plcORhndl.eps

Outrigger handle

Gauge port

1
Gauge port
SECTION 1 SECTION 2 SECTION 3 SECTION 4 SLEWING AIR / WATER BOOM / OUTRIG.

DANGER WARNING
Electrocution hazard. Do not operate this
Stay back from high machine without
training. Understand
voltage wires at least SAFETY

the warnings in safety

1
17 feet (5 meters). MANUAL
manuals and on decals.

Figure 200
h d.e
ps Position of the outrigger selector valve
itor
ap
Monsun-Tyson black & white (right)
Outrigger handle Apitech proportional (left)

280 bar
Lower Relief Valve
32Porct5.eps

PS
oc
bb
ck.
Higher ep
s

Turn body of valve


to adjust.

REAR EXTEND FRONT EXTEND REAR FOOT FRONT FOOT

Figure 201
Location of the 280 bar outrigger
pressure relief valve.
(Hoses removed for clarity).

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 201
HOME PRINT

Pressure Settings
9. If adjustment is needed, turn the outside body of
the relief valve that is located at the back of the
outrigger valve. Turn in to raise pressure, turn out Setting 15 bar pretension
to lower pressure. There is no jam nut on this To check or set pretension, follow these steps:
valve. 1. Stop the truck engine. Plug the 0 - 40 bar gauge
10. Activate the outrigger jacking retract handvalve into the pretension check port of the Apitech
and read the pressure on the gauge again. Repeat handvalve (Figure 202).
steps 8. and 9. until the gauge reads 280 bar. 2. Start the truck engine, but leave it at an idle.
11. When the pressure is correct, either go on to other (Pretension adjustment is made at an idle to
pressure settings, or remove the whip hose and establish the minimum pressure setting. As RPM is
gauge, and cap the gauge port with the attached increased, pressure will rise. Damage to the 0 - 40
cap. bar gauge is possible if RPM is raised while the
12. Return the RPM of the truck to an idle, take the gauge is connected.)
transmission and PTO out of gear, and shut off the 3. Read the pressure on the gauge. If it reads 15 bar
truck, or go on to the other pressure settings, as 1 bar, the pressure is set correctly. If adjustment is
required. needed, proceed to step (4.).

CAUTION
Truck engine must be at an idle while setting pretension.

Pretension
gauge port

Figure 202 rtn


.ep
s
itp
Pretension adjustment screw and gauge ap

port Pretension adjustment screw

4. Loosen the jam nut on the pretension valve. Turn setting the pressure in this circuit. The port is located
the screw in to raise pressure, and out to lower on the agitator handvalve. To check or set the agitator
pressure. When the pressure is correct, retighten pressure, follow these steps:
the jam nut. 1. Remove the aluminum diamond plate cover from
5. Stop the engine, and remove the 0 - 40 bar gauge. over the agitator handvalve.
Pretension setting is complete. 2. Unscrew the cover from the gauge port. Plug in the
0-600 bar gauge and whip hose that came in the
To set the agitator circuit pressure: toolbox.
The agitator relief valve is located in the agitator 3. Start the engine, if not already running.
forward / neutral / reverse handvalve, at the rear of the 4. Close the agitator shutoff valve. (See Figure 204.)
unit on the drivers side. The relief valve limits the Note! If your unit does not have a shutoff valve,
pressure in the agitator circuit to 200 bar (2900 PSI). you can order one using part number 10004680
(See Figure 203). There is a gauge port for checking or

revDate
202 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

agitator pressure check.eps L


Relief valve on this
side (not visible from
this angle).
Gauge port

Figure 203
Showing the agitator handvalve and
gauge port.
(Diamond plate removed
for this illustration.)

(valve) and part number 30303432 (tube). Contact


Schwings Service Dept. for installation
instructions.

closed

s
ep
o.
its
ag

open
Figure 204
The agitator shutoff valve

5. Activate the agitator in forward. Read the pressure


on the gauge.
6. If adjustment is needed, put your wrench on the
body of the relief valve, which is located on the
back of the agitator handvalve. While reading the
gauge, turn the body in to raise pressure, or out to
lower pressure until 200 bar is achieved.
7. Put the agitator handle in neutral.
8. Remove the whip hose and pressure gauge.
Replace the gauge port cover.
9. Replace the aluminum diamond plate over the
agitator handvalve.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 203
HOME PRINT

Pressure Settings

revDate
204 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
KVM 32 XG Check the concrete pump pressure (2020,
2023, 2525 pumpkits)
Because the Hi-flow pumpkits have the ability to create
Check hydraulic pressures high pressure on the concrete, the pressure settings
The following pages provide the proper techniques for have to be tailored specifically for each model. This
checking and setting hydraulic pressures of each means that we cannot simply list a pressure
system included on units up to 450 l/m. specification for all units. The correct pressure
Check all hydraulic pressures. Changes in pressures specifications for your unit are shown on the hydraulic
can indicate trouble in one or more components. schematic in the Appendix, section of this manual.
Pressure settings must be made with the oil at normal If you wish to order a CD ROM which explains the
operating temperatures (40 to 60 C). The pressure setting procedure for a specific model (all
specifications for all circuit pressures are found on the pumpkits), call SAI Spare Parts Department at (800)
hydraulic schematics in the Appendix section of this 328 - 9635 and request the CD using the following part
manual. numbers:
61/58 meter . . . . . . . . . . . . . . . . . . . . . . .30365860
Preheat the hydraulic oil 52 meter . . . . . . . . . . . . . . . . . . . . . . . . . .30354732
Because of the new load-sensing hydraulic systems 45/47 meter . . . . . . . . . . . . . . . . . . . . . . .30356770
regulated by pressure cut-off, you cant use the 42 meter . . . . . . . . . . . . . . . . . . . . . . . . . .30355485
concrete pump or boom circuit to preheat the hydraulic
39 meter . . . . . . . . . . . . . . . . . . . . . . . . . .30365861
oil (they stop putting out oil rather than send it over
relief). To heat the oil to operating temperature: 34 meter . . . . . . . . . . . . . . . . . . . . . . . . . .30356772
32 meter . . . . . . . . . . . . . . . . . . . . . . . . . .30355486
1. Locate the agitator shutoff valve (Figure 36) and
close it. Note! If your unit does not have a shutoff 31 meter . . . . . . . . . . . . . . . . . . . . . . . . . .30365862
valve, you can order one using part number NOTE!
10004680 (valve) and part number 30303432 Use of the remote control box for the
(tube). Contact the Schwing Service Department at following pressure setting procedure is NOT
(651) 429-0999 for installation instructions. recommended.
2. Turn on the agitator. The agitator will not be able To check or set the concrete pump pressure
to turn, and the oil will be forced over the relief adjustments, follow these steps:
valve.
3. At an idle (approximately 600 rpm), about 5.4 WARNING
horsepower is being converted to heat. Shut off the
agitator when the temperature gauge on the rear Wear safety glasses any time you check
or set pressures. Oil expulsion hazard!

000438.eps
control panel shows 40 C. Dont forget to open
the shutoff valve when the procedure is finished.
1. Be sure that the waterbox covers and guards are
agitoff.eps
installed on the waterbox.
2. Start the truck engine, and put the PTO and
transmission into gear just as you would to pump a
job.
3. Locate and close the concrete pump shutoff valve
and the soft switch shutoff valve (Figure 38 next
page). (These valves are also known as quarter
Agitator quarter turn turn valves).
shutoff valve (open position) Motor 4. If your concrete pump pressure gauge is not
already plumbed into the gauge port (Figure 37),
install a 0 - 400 or 0 - 600 bar gauge in the gauge
Figure 21 port.
Agitator shutoff valve
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 205
HOME PRINT

Pressure Settings
5. The local/remote switch located on the controller If your unit has any pumpkit other than a
cover must be in the local position. Hi-flo -4, call SAI Service Department and
ask for the proper pressure setting
6. Be sure that all emergency stop switches are in the procedures for your specific pumpkit.
up (not activated) position. Reset the E-stop circuit.
The main relief valve is the primary pressure control
7. Using the throttle switch on the rear control panel, device on units equipped with Rexroth A7VO
bring the truck engine up to full RPM. hydraulic pumps.
8. CAUTION! The main relief valve (Figure 39) is
If the main relief valve needs adjustment, proceed as
set to very high pressure (at least 350 bar). Use the
follows:
rear control panel switch when checking the
pressure of the main relief valve, so you will be out 1. Wear safety glasses when checking or adjusting
of the way if a hose or fitting blows. pressures.
9. Place the concrete pump forward / neutral / reverse 2. Using a 9/16 spanner wrench, loosen the jam nut
switch on the rear control panel into the forward on the main relief valve adjusting screw (Figure
position. The unit will stroke no more than once; 37).
then the rock cylinder will retract. Oil leaving the
3. Insert a 5/32 allen wrench in the adjustment screw.
hydraulic pumps will be blocked in the brain. This
is called high-pressuring the concrete pump. Turn the screw in to raise pressure and out to lower
the pressure. Always go back to the rear panel
10. Read the pressure on the gauge. The target pressure
before checking the pressure.
for the concrete pump circuit main relief valve is
shown on the hydraulic schematic in the Appendix 4. Once the pressure is correct to the hydraulic
section of this manual. Return the pump control to schematic, retighten the jam nut. Tightening the
neutral whether the pressure needs adjustment or nut tends to raise the pressure, so check pressure
not. If no adjustment is needed, skip to step 14 of again after tightening.
the next procedure. If adjustment is needed, 5. If you will not be setting the soft switch pressure,
proceed to next paragraph. open the shutoff valves. The unit will not stroke
with closed shutoff valves.
Setting the main relief valve on -4 pumpkit
NOTE!

Gauge port

Hif
lo_
4.e
ps

Main relief valve

Soft switch
relief valve

Figure 22
Location of the concrete pump circuit main relief
valve and soft switch relief valve

revDate
206 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Soft switch
shutoff valve

Main Pressure
Gauge port

Concrete pump
hif
shutoff valve low
br
n.
ep
s

Figure 23
Showing the concrete pump and soft switch shutoff
valves

Grooves in handle Closed


Closed Open
soft switch
relief cartridge
Grooves in shaft grooves2.eps Main relief cartridge
openclsd.eps

9/16" jam nut

Open
5/32" Allen head
Mounting screw and washer
removed for illustration 9/16" jam nut

Figure 24
Shutoff valve open / closed orientation

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 207
HOME PRINT

Pressure Settings
Setting the soft switch circuit relief 3. Loosen the jam nut on the soft switch relief valve
pressure (Figure 5) with a 9/16 spanner wrench. Adjust the
To check or adjust the soft switch pressure setting, pressure up or down, as needed, using a 5/32 Allen
proceed as follows: wrench. When the correct pressure is achieved,
1. Open the soft switch shutoff valve (Figure 38). The tighten the jam nut.
rest of the unit should still be set up as though you 4. Be sure to open the concrete pump shutoff valve
were going to check concrete pump pressure. (Figure 38) on the side of the brain when you are
2. High pressure the concrete pump. The pressure finished. The unit cannot stroke with this valve
gauge should read 60 or 80 bar (check your closed.
schematic). If adjustment is needed, proceed to
step (3) below. If no adjustment is needed, skip to
step (4).

Gauge port

Hif
lo_
4.e
ps

Main relief valve

Soft switch
relief valve

Figure 25
Location of the main relief valve

revDate
208 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

0-400 bar
gauge port Boom control
block relief valve
Redundant
relief valve

0-60 bar 15 bar pretension


gauge port adjusment screw

p s
e.e
alv
oo mv
34b newestop.eps

140 bar downside


relief cartridge (non-adjustable)
Figure 26
The boom pressure devices

Setting boom pressures 5. The boom control block relief valve can then be
There are two pressure settings on the boom circuit: the turned out with the handle still activated until the
redundant relief valve and the boom control block gauge reads 300 bar.
relief (Figure 45). NOTE!
1. Install 0-400 or 0-600 bar gauge in the 0-400 bar The gauge will always read the lowest relief
gauge port (Figure 45). setting in the system; therefore, we turn the
pressure up on the boom control block in
2. The redundant relief valve located in the step #3 to assure that it is higher than the
emergency stop manifold (Figure 45) should first 330 bar required for the redundant relief
be turned out two turns by loosening the jam nut valve.
with a 9/16 open end wrench and turning the
140 bar down side relief
cartridge out with a 4 mm Allen wrench.
The down side relief is now a non-adjustable, internal
3. The boom control block relief valve (Figure 45),
valve which is verified at the factory and should not
should then be turned in one turn by using a 1/8 require further attention. If you feel you need to verify
allen wrench to remove the cover guard and a 5/32 the down side relief call Schwing Service Department
allen wrench to turn in the screw. and ask about the proper procedure for doing so.
4. The redundant relief valve, located in the
Setting the outrigger pressures
emergency stop manifold, should be set at 330 bar.
Activate any boom cylinder, except #1, to the boom After the boom pressures are set, you can set the
in or boom down position. The gauge should be outrigger pressure.
reading lower than the target 330 bar. Turn the In this system, the boom, outriggers, water pump, and
screw in until it reaches 330 bar. compressor circuits have all been put together in the
boom valve manifold. When the outrigger selector
pushbutton is pushed, the outrigger valve handle is
activated, which routes oil to the two outrigger
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 209
HOME PRINT

Pressure Settings
0-400 bar Outrigger handle
gauge port

15 bar pretension
adjusment screw

Figure 27
Position of the outrigger selector valve on units ghn
dl.e
ps
otr
new
equipped with Apitech proportional valves

handvalve banks (one on each side of the unit). A relief 8. If adjustment is needed, turn the outside body of
valve inside the passenger side bank limits the entire the relief valve that is located at the back of the
outrigger circuit to 280 bar (4060 PSI) instead of the outrigger valve. Turn in to raise pressure; turn out
300 bar (4350 PSI) of the boom relief valve. to lower pressure. There is no jam nut on this
To set the 280 bar relief valve for the outrigger circuit: valve.
9. Activate the outrigger jacking retract handvalve
and read the pressure on the gauge again. Repeat
WARNING steps (8) and (9) until the gauge reads 280 bar.
Wear safety glasses any time you check 10. When the pressure is correct, either go on to other
or set pressures. Oil expulsion hazard! pressure settings or remove the whip hose and
000438.eps

gauge and cap the gauge port with the attached


cap.
1. Plug the whip hose of a 0-400 or 0-600 bar gauge
into the gauge port shown (Figure 46) or the port 11. Return the RPM of the truck to an idle, take the
on the outrigger hand valve. transmission and PTO out of gear, and shut off the
truck (or go on to the other pressure settings as
2. If not already done, start the truck engine, and set
required).
the transmission and PTO as you would for a
pumping job.
Setting the water pump hydraulic pressure
3. Locate the 280 bar relief valve (Figure 47) on the
bottom of the outrigger valve. With a seven place handvalve, the water pump
hydraulic control is inside the boom control block.
4. Set the engine RPM to maximum. There is not a separate relief for this circuit and,
5. Select outrigger with the outrigger pushbutton or therefore, nothing that must be set.
manual handle (Figure 46). This will route oil to
the outrigger handvalves. Setting 15 bar pretension
6. Assuming that the outriggers are folded into the To check or set pretension, follow these steps:
travel position, activate the passenger side
1. Stop the truck engine. Plug the 0 - 40 bar gauge
handvalve jacking cylinder retract for either
into the pretension check port of the Apitech
the front or rear outrigger.
handvalve (Figure 48 page 211).
NOTE! 2. Start the truck engine, but leave it at an idle.
You will get an incorrect reading if you (Pretension adjustment is made at an idle to
select any other outrigger function. The establish the minimum pressure setting. As RPM is
handles are spring loaded and will return to
neutral as soon as you let go. increased, pressure will rise. Damage to the 0 - 40
bar gauge is possible if RPM is raised while the
7. Read the pressure on the gauge. It should read 280 gauge is connected.)
bar (4060 PSI). If no adjustment is needed, skip to
step 10.
revDate
210 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

34manco3.eps

WARNING
Clear area
before activating
outriggers

REAR EXTEND REAR JACKING FRONT JACKING FRONT EXTEND

otr
gb
lk.e
ps
200
100 300

bar 400

WIKA

280 bar
Relief valve

Figure 28
Location of the 280 bar outrigger
pressure relief valve.
(Hoses removed for clarity).

CAUTION
Truck engine must be at idle to set
000439.eps

pretension. Gauge damage possible!

3. If the pressure reads 15 bar 1 bar, the pressure is Setting the agitator circuit pressure
set correctly. If adjustment is needed, proceed to The agitator relief valve is located in the agitator
the next step. forward / neutral / reverse handvalve (Figure 49). The
4. Loosen the jam nut on the pretension valve. Turn relief valve (not completely visible in Figure 49) limits
the screw in to raise pressure, and out to lower the pressure in the agitator circuit to 200 bar (2900
pressure. When the pressure is correct, retighten PSI). There is a gauge port (not visible in Figure 49)
the jam nut. for checking or setting the pressure in this circuit. The
5. Stop the engine, and remove the 0 - 40 bar gauge. port is located on the agitator handvalve. To check or
Pretension setting is complete. set the agitator pressure, follow these steps:

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 211
HOME PRINT

Pressure Settings
1. Unscrew the cover from the gauge port. Plug in the 2. Start the engine, if its not already running.
0-600 bar gauge and whip hose that came in the
toolbox.

0-60 bar
gauge port

15 bar pretension
adjusment screw

Figure 29
Pretension adjustment screw
ps
n.e
and gauge port new
pre
tns

Agitator hand valve

Relief valve

Gauge Port
34agithandvalve.eps

Figure 30
Agitator handvalve

3. Close the agitator shutoff valve (Figure 50). 30303432 (tube). Contact Schwing
Americas Service Department at (651) 429-
NOTE! 0999 for installation instructions.
If your unit does not have a shutoff valve,
you can order one using part number 4. Activate the agitator, and read the pressure on the
10004680 (valve) and part number gauge.

revDate
212 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
5. If adjustment is needed, put your wrench on the 6. Put the agitator handle in neutral.
body of the relief valve (Figure 49), which is 7. Remove the whip hose and pressure gauge.
located on the back of the agitator handvalve. Replace the gauge port cover.
While reading the gauge, turn the body in to raise
pressure or out to lower pressure until 200 bar is
achieved.
agitoff.eps

Agitator quarter turn


Figure 31 shutoff valve (open position) Motor
The agitator shutoff valve

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 213
HOME PRINT

Pressure Settings
Setting accumulator circuit pressure

45Accreg.eps

Accumulator pump
pressure regulator Redundant
Relief cartridge

Figure 32
Accumulator pump pressure regulator for newredun.eps

A7VO (above) and for A11VO (below)

Boom Pump Figure 33


Accumulator Pump Accumulator redundant relief cartridge

4. Clear all personnel away from the drive lines, start


the truck engine, engage the pumps, and bring the
Standby engine RPM to maximum.
Pressure Screw
5. Read the pressure on the accumulator circuit
Accumulator Pump pressure gauge (Figure 53). The pressure should
Pressure Regulator accumpmp.eps
hgacugc.psd read the value shown on the hydraulic schematic. If
no adjustment is needed, skip to step (7). If
You will need an assistant for parts of this procedure. additional pressure adjustment is needed, continue
There are three relief settings for the accumulator with step (6).
circuit.
45acumpr.epsL

To check or adjust the hydraulic pressure in the


accumulator circuit:
1. Stop the truck, put the key in your pocket, and
place a Do Not Operate sign on the windshield.
2. Loosen the jam nut on the pressure regulator of the
accumulator hydraulic pump (Figure 51). Turn the
screw in two-and-one-half turns. This will raise the
regulator pressure above 300 bar.
3. Loosen the jam nut (Figure 52) on the accumulator
Figure 34
redundant relief cartridge, located on the
Accumulator circuit pressure gauge
emergency stop manifold. Turn the screw in two
turns. This will raise the relief setting above 300
bar.

revDate
214 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
8. After the truck engine is stopped, go back to the
accumulator circuit hydraulic pump pressure
regulator (Figure 51), and turn the screw back out
two-and-one-half turns. This restores it to its
accuman1.eps
original setting.
9. Clear all personnel from the drive line area, start
the truck, and bring the engine RPM up to
maximum.
10. Read the pressure on the accumulator gauge. It
should read the proper accumulator system
pressure.
11. If adjustment is needed, you must stop the truck
engine, or a least stop the drive lines from turning,
each and every time you approach the accumulator
Pressure Relief Cartridge circuit hydraulic pump. Turn the screw in to
Manual bleed valve increase the pressure or out to decrease pressure.
Lock the jam nut when the pressure is correct.

NOTE!
The accumulator circuit hydraulic pump
pressure regulator is sometimes referred to
as the pressure cut-off.

Figure 35
Accumulator manifold pressure
relief cartridge

6. Locate the accumulator manifold pressure relief


cartridge (Figure 54). Loosen the jam nut, and turn
the screw clockwise to increase the pressure or
counter clockwise to decrease the pressure. Tighten
the jam nut when the pressure reaches the value
required.
7. You will need an assistant for this step. With the
engine still running, one person must go to the
redundant relief valve on the emergency stop
manifold (Figure 52) and back out the adjustment
screw while the other person stands by the pressure
gauge to let him know when the pressure reads the
value shown on the schematic for accumulator
redundant relief.

WARNING
Entanglement hazard. Stop drive shafts
before adjusting the accumulator pump
000075.eps

pressure regulator.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 215
HOME PRINT

Pressure Settings

revDate
216 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
S 34 X Check the concrete pump pressure (2020, 2023,
2525 pumpkits)

Check hydraulic pressures Because the Hi-flow pumpkits have the ability to create
high pressure on the concrete, the pressure settings
The following pages provide the proper techniques for have to be tailored specifically for each model. This
checking and setting hydraulic pressures of each means that we cannot simply list a pressure
system included on units up to 450 l/m. specification for all units. The correct pressure
Check all hydraulic pressures. Changes in pressures specifications for your unit are shown on the hydraulic
can indicate trouble in one or more components. schematic in Appendix, Section 7 of this manual.
Pressure settings must be made with the oil at normal If you wish to order a CD ROM which explains the
operating temperatures (40 to 60 C). The pressure setting procedure for a specific model (all
specifications for all circuit pressures are found on the pumpkits), call Schwing Spare Parts Department at
hydraulic schematics in the Appendix section of this (800) 328 - 9635 and request the CD using the
manual. following part numbers:
Preheat the hydraulic oil 61/58 meter . . . . . . . . . . . . . . . . . . . . . . .30365860
Because of the new load-sensing hydraulic systems 52 meter . . . . . . . . . . . . . . . . . . . . . . . . . .30354732
regulated by pressure cut-off, you cant use the 45/47 meter . . . . . . . . . . . . . . . . . . . . . . .30356770
concrete pump or boom circuit to preheat the hydraulic 42 meter . . . . . . . . . . . . . . . . . . . . . . . . . .30355485
oil (they stop putting out oil rather than send it over 39 meter . . . . . . . . . . . . . . . . . . . . . . . . . .30365861
relief). To heat the oil to operating temperature: 34 meter . . . . . . . . . . . . . . . . . . . . . . . . . .30356772
1. Locate the agitator shutoff valve (Figure 36) and 32 meter . . . . . . . . . . . . . . . . . . . . . . . . . .30355486
close it. Note! If your unit does not have a shutoff 31 meter . . . . . . . . . . . . . . . . . . . . . . . . . .30365862
valve, you can order one using part number
10004680 (valve) and part number 30303432 NOTE!
(tube). Contact the Schwing Service Department at Use of the remote control box for the
(651) 429-0999 for installation instructions. following pressure setting procedure is NOT
recommended.
2. Turn on the agitator. The agitator will not be able
to turn, and the oil will be forced over the relief To check or set the concrete pump pressure
valve. adjustments, follow these steps:
3. At an idle (approximately 600 rpm), about 5.4
horsepower is being converted to heat. Shut off the WARNING
agitator when the temperature gauge on the rear
control panel shows 40 C. Dont forget to open Wear safety glasses any time you check
or set pressures. Oil expulsion hazard!

000438.eps
the shutoff valve when the procedure is finished.
agitoff.eps

1. Be sure that the waterbox covers and guards are


installed on the waterbox.
2. Start the truck engine, and put the PTO and
transmission into gear just as you would to pump a
job.
3. Locate and close the concrete pump shutoff valve
and the soft switch shutoff valve (Figure 38).
Agitator quarter turn (These valves are also known as quarter turn
shutoff valve (open position) valves).
Motor
4. If your concrete pump pressure gauge is not
already plumbed into the gauge port (Figure 37),
Figure 36 install a 0 - 400 or 0 - 600 bar gauge in the gauge
Agitator shutoff valve port.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 217
HOME PRINT

Pressure Settings
5. The remote / local switch located on the rear Setting the main relief valve
control panel must be in the local position. The main relief valve is the primary pressure control
6. Be sure that all emergency stop switches are in the device on units equipped with Rexroth A7VO
up (not activated) position. Reset the E-stop circuit. hydraulic pumps.
7. Using the throttle switch on the rear control panel, If the main relief valve needs adjustment, proceed as
bring the truck engine up to full RPM. follows:
CAUTION! The main relief valve (Figure 39) is set to 10. Wear safety glasses when checking or adjusting
very high pressure (at least 350 bar). Use the rear pressures.
control panel switch when checking the pressure of the
11. Using a 9/16 spanner wrench, loosen the jam nut
main relief valve, so you will be out of the way if a
hose or fitting blows. on the main relief valve adjusting screw (Figure
37).
8. Place the concrete pump forward / neutral /
reverse switch on the rear control panel into the 12. Insert a 5/32 Allen wrench in the adjustment
forward position. The unit will stroke no more screw. Turn the screw in to raise pressure and out
than once, and then the rock cylinder will retract. to lower the pressure. Always go back to the rear
Oil leaving the hydraulic pumps will be blocked in panel before checking the pressure.
the brain. This is called high-pressuring the 13. Once the pressure is correct to the hydraulic
concrete pump. schematic, retighten the jam nut. Tightening the
9. Read the pressure on the gauge. The target pressure nut tends to raise the pressure, so check pressure
for the concrete pump circuit main relief valve is again after tightening.
shown on the hydraulic schematic in the Appendix 14. If you will not be setting the soft switch pressure,
section of this manual. Return the pump control to open the shutoff valves. The unit will not stroke
neutral whether the pressure needs adjustment or with closed shutoff valves.
not. If no adjustment is needed, skip to step 14. If
adjustment is needed, proceed to next paragraph.

Gauge port

Hif
lo_
4.e
ps

Main relief valve

Soft switch
relief valve

Figure 37
Location of the concrete pump circuit main relief
valve and soft switch relief valve

revDate
218 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Soft switch
shutoff valve

Main Pressure
Gauge port

Concrete pump
hif
shutoff valve low
br
n.
ep
s

Figure 38
Showing the concrete pump and soft switch shutoff
valves

Grooves in handle Closed


Closed Open
soft switch
relief cartridge
Grooves in shaft grooves2.eps Main relief cartridge
openclsd.eps

9/16" jam nut

Open
5/32" Allen head
Mounting screw and washer
removed for illustration 9/16" jam nut

Figure 39
Shutoff valve open / closed orientation

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 219
HOME PRINT

Pressure Settings
Setting the soft switch circuit relief pressure 3. Loosen the jam nut on the soft switch relief valve
To check or adjust the soft switch pressure setting, (Figure 5) with a 9/16 spanner wrench. Adjust the
proceed as follows: pressure up or down, as needed, using a 5/32 Allen
1. Open the soft switch shutoff valve (Figure 38). The wrench. When the correct pressure is achieved,
rest of the unit should still be set up as though you tighten the jam nut.
were going to check concrete pump pressure.
4. Be sure to open the concrete pump shutoff valve
2. Pressure out the concrete pump. The pressure (Figure 38) on the side of the brain when you are
gauge should read 60 or 80 bar (check your finished. The unit cannot stroke with this valve
schematic). If adjustment is needed, proceed to closed.
step (3) below. If no adjustment is needed, skip to
step (4).

Gauge port

Hif
lo_
4.e
ps

Main relief valve

Soft switch
relief valve

Figure 40
Location of the main relief valve

revDate
220 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Load-sensing boom pressures Setting P
If your unit has a load-sensing proportional system, it NOTE!
will have different pressure adjustments than if it is Do not adjust P or Q-min if your boom is
equipped with a black-and-white boom system. The running as you like it. The pressure setting
following instructions are for seven place, load-sensing procedure uses a standard starting point
proportional systems. If you have a unit equipped with and must be fine tuned from there. It was
a black-and-white boom system, contact Schwing fine tuned at the factory and should not be
adjusted unless absolutely necessary.
Service for the correct instruction pages.
Do not adjust Q-min with the drive shafts turning!
Preheat the oil Each time the Q-min screw is adjusted, the engine must
NOTE! be stopped, or at least the transmission must be taken
out of gear, so that the drivelines stop turning. To check
Whenever you set pressures for any circuit
on any unit, the hydraulic oil should be at or set P, follow these steps:
normal operating temperature (40 - 60 C). 1. Stop the truck engine, and place a Do Not
Instructions for heating the hydraulic oil Operate sign on the truck windshield.
are found on page 217.
2. Install a 0-40 or 0-60 bar gauge in the 0-400 bar
About proportional boom systems gauge port (Figure 42) of the manual boom hand
In a black-and-white boom system, the hydraulic pump valves. Take care not to accidently install the gauge
puts out an unchanging amount of oil, and speed in the 0-60 bar port.
control is done by restricting the oil to certain functions CAUTION! If you activate any boom or outrigger
with orifices. In a load-sensing system, the pump puts functions, you will damage the 0 - 40 bar gauge.
out more or less oil to respond to the needs of the 3. To be sure that the pump is putting out only enough
system. Generally, the pump puts out enough oil to oil to maintain P, we need to change the setting of
maintain a 20 bar higher pressure at the pump than the Q-min screw. Q-min is adjusted by a screw on
what the cylinders actually require. This 20 bar is the boom hydraulic pump (Figure 43). Unscrew the
called delta P (P). Additionally, we set the hydraulic Q-min screw three full turns. Make sure that all
pump so that it always puts out a small amount of oil, emergency stop switches are in the up (not
even if no oil is needed for the system. This oil is used activated) position. Check that all personnel are
to ensure that you have control when you need it. The clear of the truck; then restart the engine, engage
setting to maintain this minimum amount of oil is the pumps, and leave the engine at an idle. Pressure
called Q-min (pronounced cue min). To set the boom can be read on the 0 - 40 bar gauge that you
or outrigger hydraulic pressures on a load-sensing installed. Pressure should read 20 bar. If no
system, begin by setting Q-min and P. adjustment is needed, simply reset the Q-min
Read all of the instructions before beginning any screw as described on page 223. If adjustment is
pressure settings. General locations of the components needed, continue to step (4).
for the following procedures are shown in Figure 41.
You will need an assistant for parts of this procedure.
You and any assistants should wear eye protection
when checking or setting pressures.
Manual boom handvalves,
Delta P adjustment
and E-Stop manifold

Figure 41
Locations of
components used to
check and set boom
pressures 34cmploc.eps

Q-min adjustment screw

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 221
HOME PRINT

Pressure Settings

15 bar pretension
adjustment screw 140 bar gauge port (use 0-400
bar gauge when checking)

0-60 bar
gauge port

0-400 bar
gauge port
Figure 42
Location of the boom circuit
pressure devices boom control 140 bar downside
(Hoses removed for clarity.) block relief valve relief cartridge 34blck.eps

CAUTION Q-min
adjustment screw
Do not operate any function during this
000442.eps

procedure. Gauge damage possible!

4. Delta P is adjusted by the P screw on the P


regulator (Figure 44). Loosen the jam nut, and
adjust the screw inward to increase pressure or Q-minscrew.eps

outward to decrease pressure, until it is set at 20


Q-max
bar (1). Contact Schwing Americas Service
Department if you are unable to adjust the pressure
to specification. NOTE! If the boom is not smooth Figure 43
at 20 bar, you must fine tune the adjustment. In that Location of the Q-min adjustment screw
case, REMOVE THE GAUGE, and adjust P until
the boom is responsive and smooth. When done,
the gauge (reinstalled) must read between 14 and
25 bar. The electronics in the control system can
also affect how the boom operates, so if P
adjustment does not seem to help, reset to 20 bar P adjustment
deltaPvlv.eps

and check the electrical settings. Once electrical screw


settings are verified, you could again refine the
boom action with the P adjustment. T

Figure 44
The P regulator valve

revDate
222 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Setting Q-min 5. Turn the Q-min screw in to raise the pressure
Check Q-min pressure when the engine is at the (Figure 43). Turn it out to lower the pressure. Be
maximum specified RPM, but the engine must be sure that you stop the drive shafts from turning
stopped to adjust the pressure. each time before making the adjustment. When
pressure is correct, tighten the jam nut on the
1. If you unscrewed the Q-min screw as the first step
adjustment screw before continuing with the other
of P adjustment, begin by returning the screw to
procedures.
its original position (Figure 43).
2. Remove the 0 - 40 bar gauge from the 0 - 400 bar Setting boom pressures (Load sensing
gauge port, and install the 0 - 600 bar gauge in its proportional booms.)
place. Now that P and Q-min are set, you can check or set
3. Clear all personnel away from the drive lines, start the boom valve pressures.
the truck engine, engage the pumps, and bring There are three pressure settings (Figure 45) on the
engine RPM to max. All boom functions must be in boom circuit:
neutral, and all emergency stop buttons should be
1. Pressure regulator (the high-pressure adjustment
up (not engaged).
screw on the P regulator valve), set at 300 bar.
4. Read the pressure on the 0 - 600 bar gauge.
Pressure should be at 40 - 45 bar. If no adjustment 2. The redundant relief valve located in the
is needed, stop the drivelines from turning, be sure emergency stop manifold, set at 330 bar.
the jam nut on the Q-min screw is tight, and 3. The boom control block relief valve, set at 350 bar.
proceed to Setting boom pressures. If adjustment is NOTE!
needed, continue to the next step. This relief valve is nonadjustable. If
pressure is not maintained with the
specification limits, the valve must be
replaced.

High pressure Redundant


deltaPvlv.eps

adjustment screw relief valve

15 bar pretension
adjustment screw 140 bar gauge port (use 0-400
bar gauge when checking)

0-60 bar
newestop.eps
gauge port

0-400 bar
gauge port
Figure 45
The three boom pressure
boom control 140 bar downside
block relief valve
devices
relief cartridge 34blck.eps

To check the setting of the valve with the highest two:


pressure, you must first raise the pressure of the lower
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 223
HOME PRINT

Pressure Settings
1. Loosen the jam nut of the high pressure adjustment specified after following the instructions, contact
screw (Figure 45) of the P regulator. Turn the Schwing Americas Service Department at (651)
screw in two-and-a-half turns. This will raise the 429-0999 for advice on how to continue.
pressure on the regulator above 350 bar.
Setting the 140 bar down side relief valve pressure
2. Loosen the jam nut of the adjustment screw of the
redundant relief valve (Figure 45) in the Set the pressure of the 140 bar (Figure 45) down side
emergency stop manifold. Turn the screw in one- relief valve. Down side relief is a secondary relief valve
and-a-half turns. This will raise the pressure setting for #1 cylinder retract function. Proper adjustment
of the relief valve to above 350 bar. ensures that the #1 boom and the A-frame wont be
damaged by putting the boom in the cradle. To adjust
3. Pressure out any boom cylinder except #1 down by
this valve (requires a 2.5 mm Allen wrench and a
activating the control handle. To pressure out a
standard screwdriver):
cylinder, retract a fully retracted cylinder or extend
a fully extended cylinder. The oil is then forced 1. Install a 0 - 400 bar or 0 - 600 bar gauge into the
over the relief valve. 140 bar gauge port shown in Figure 45.
The telltale hiss of an open relief valve should be 2. Unfold the #2 section from #1 until it is fully
coming from the Apitech control block relief valve extended. For the following procedure we must
now. If it isnt, raise the setting of the other bring #1 all the way down until the cylinder
pressure devices until the hiss originates at the bottoms out. Position the boom so this can be done
Apitech control block relief valve. Read the without hitting the truck or any other obstacle.
pressure on the gauge. It should read 350 bar. If 3. Bring #1 down until the cylinder is completely
pressure is correct, proceed to the next step. bottomed out. The cylinder does NOT bottom out
NOTE! if you are setting the folded boom into the A-frame
Although the pressure specification for the (travel position).
Apitech relief valve is 350 bar, you may 4. Activate the #1 down (retract) handvalve. The
continue to use the relief valve as long as the boom will not be able to move because the cylinder
cartridge maintains at least 330 bar. If you is already bottomed out. Read the pressure on the
must replace the valve and dont have one
on hand, proceed to the next step before gauge that you just installed. It should read 140
using the machine again. Redo this entire bar. If no adjustment is necessary, skip to step 6.
procedure when you have installed the new 5. If adjustment is needed, loosen the set screw of the
valve. If pressure on the Apitech relief valve 140 bar relief valve (Figure 45) with the 2.5 mm
is below 290 bar, you should not use the
machine until the valve is replaced. Allen wrench. While you activate #1 down, adjust
the relief cartridge with the screwdriver until the
4. Screw out the E-stop manifold redundant relief pressure reads just under 140 bar. Retightening the
valve (Figure 45) adjustment screw one-and-a-half set screw will raise the pressure slightly. Recheck
turns. Pressure out any boom cylinder except #1 the pressure, and readjust if needed.
down, and read the gauge. Pressure should read
6. When the pressure is set at 140 bar with the set
330 bar. If it does not, turn the screw in to raise
screw tight, you can remove the whip hose gauge
pressure or out to lower pressure until it is set at
and replace the cap on the gauge port.
330 bar. If the location of this valve causes you to
be near the drivelines, be sure to stop them from 7. The boom pressure setting sequence is complete. If
turning before accessing the valve. you are done with the boom, fold it back into the
transport position, and reattach the boom strap.
5. You will need a helper for this step. While
pressuring out any boom cylinder except #1 down,
have your helper adjust the high pressure screw of
the P regulator out (lowering the pressure) until
the gauge reads 300 bar. Release the pressurized
function, and lock the jam nut. The boom pressures
are now set. If you did not get the readings

revDate
224 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Setting the outrigger pressures

Outrigger handle

0-400 bar
gauge port

otrghndl.eps

Figure 46
Position of the outrigger selector valve on units
equipped with Apitech proportional valves

After the boom pressures are set, you can set the 4. Set the engine RPM to maximum.
outrigger pressure. 5. Select outrigger with the outrigger pushbutton.
In this system, the boom, outriggers, water pump, and This will route oil to the outrigger handvalves.
compressor circuits have all been put together in the 6. Assuming that the outriggers are folded into the
boom valve manifold. When the outrigger selector travel position, activate the passenger side
pushbutton is pushed, the outrigger valve handle is handvalve jacking cylinder retract for either
activated, which routes oil to the two outrigger the front or rear outrigger.
handvalve banks (one on each side of the unit). A relief
valve inside the passenger side bank limits the entire NOTE!
outrigger circuit to 280 bar (4060 PSI) instead of the You will get an incorrect reading if you
select any other outrigger function. The
300 bar (4350 PSI) of the boom relief valve. handles are spring loaded and will return to
To set the 280 bar relief valve for the outrigger circuit: neutral as soon as you let go.
7. Read the pressure on the gauge. It should read 280
bar (4060 PSI). If no adjustment is needed, skip to
WARNING step 10.
Wear safety glasses any time you check 8. If adjustment is needed, turn the outside body of
or set pressures. Oil expulsion hazard! the relief valve that is located at the back of the
000438.eps

outrigger valve. Turn in to raise pressure, and turn


out to lower pressure. There is no jam nut on this
1. Plug the whip hose of a 0-400 or 0-600 bar gauge valve.
(Figure 46) into the gauge port.
9. Activate the outrigger jacking retract handvalve
2. If not already done, start the truck engine and set and read the pressure on the gauge again. Repeat
the transmission and PTO as you would for a steps (8) and (9) until the gauge reads 280 bar.
pumping job.
3. Locate the 280 bar relief valve (Figure 47) on the
back of the outrigger valve.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 225
HOME PRINT

Pressure Settings

34manco3.eps

280 bar
10 9 Relief valve

2 4 6 8
AGITATOR
3 5 7
CONCRETE PUMP

SECTION 1
SECTION 2
SECTION 3
SECTION 4
SLEWING
AIR / WATER
BOOM / OUTRIG.

DANGER WARNING
Electrocution hazard.
4 Stay back from high
Do not operate this
machine without
voltage wires at least training. Understand
17 feet (5 meters). the warnings in safety
3

manuals and on decals.

WARNING
Clear area
before activating
outriggers

REAR EXTEND REAR JACKING FRONT JACKING FRONT EXTEND

otr
gb
lk.e
ps

200
100 300

bar 400

WIKA

Figure 47
Location of the 280 bar outrigger
pressure relief valve
(Hoses removed for clarity)

10. When the pressure is correct, either go on to other Setting the water pump hydraulic pressure
pressure settings or remove the whip hose and With a seven place handvalve, the water pump
gauge and cap the gauge port with the attached hydraulic control is inside the boom control block.
cap. There is not a separate relief for this circuit and,
11. If there are not other pressure settings required, therefore, nothing that must be set.
return the RPM of the truck to an idle, take the
transmission and PTO out of gear, and shut off the Setting 15 bar pretension
truck. To check or set pretension, follow these steps:
1. Stop the truck engine. Plug the 0 - 40 bar gauge
into the (0 - 60 bar) pretension check port of the
Apitech handvalve (Figure 48).

revDate
226 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

CAUTION
Truck engine must be at idle to set

000439.eps
pretension. Gauge damage possible!

2. Start the truck engine, but leave it at an idle. Setting the agitator circuit pressure
(Pretension adjustment is made at an idle to The agitator relief valve is located in the agitator
establish the minimum pressure setting. As RPM is forward / neutral / reverse handvalve (Figure 49).
increased, pressure will rise. Damage to the 0 - 40 The relief valve (not completely visible in Figure 49)
bar gauge is possible if RPM is raised while the limits the pressure in the agitator circuit to 200 bar
gauge is connected.) (2900 PSI). There is a gauge port (not visible in Figure
3. If the pressure reads 15 bar 1 bar, the pressure is 49) for checking or setting the pressure in this circuit.
set correctly. If adjustment is needed, proceed to The port is located on the agitator handvalve. To check
the next step. If not skip to step (5). or set the agitator pressure, follow these steps:
4. Loosen the jam nut on the pretension valve. Turn 1. Unscrew the cover from the gauge port. Plug in the
the screw in to raise pressure and out to lower 0-600 bar gauge and whip hose that came in the
pressure. When the pressure is correct, retighten toolbox.
the jam nut. 2. Start the engine if its not already running.
5. Stop the engine, and remove the 0 - 40 bar gauge.
Pretension setting is complete.

15 bar pretension
adjustment screw

0-60 bar
gauge port

Figure 48
Pretension adjustment screw
and gauge port
pretnsn.eps

30303432 (tube). Contact Schwing


3. Close the agitator shutoff valve (Figure 50). Americas Service Department at (651) 429-
NOTE! 0999 for installation instructions.
If your unit does not have a shutoff valve, 4. Activate the agitator, and read the pressure on the
you can order one using part number gauge.
10004680 (valve) and part number
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 227
HOME PRINT

Pressure Settings

34manco3.eps

agitator
handvalve 10 9

Gauge port Relief valve 2 4 6 8


AGITATOR
3 5 7
CONCRETE PUMP

SECTION 1
SECTION 2
SECTION 3
SECTION 4
SLEWING
AIR / WATER
BOOM / OUTRIG.

DANGER WARNING
Electrocution hazard.
4 Stay back from high
Do not operate this
machine without
voltage wires at least training. Understand
17 feet (5 meters). the warnings in safety

1
manuals and on decals.

AGITATOR s
ep WARNING
dv.
forward/reverse agit
han Clear area
before activating
outriggers

REAR EXTEND REAR JACKING FRONT JACKING FRONT EXTEND

CONCRETE PUMP
forward/reverse

200
100 300

Figure 49
bar 400

WIKA

Agitator handvalve

5. If adjustment is needed, put your wrench on the 6. Put the agitator handle in neutral.
body of the relief valve (Figure 49), which is 7. Remove the whip hose and pressure gauge.
located on the back of the agitator handvalve. Replace the gauge port cover.
While reading the gauge, turn the body in to raise
pressure or out to lower pressure until 200 bar is
achieved.
agitoff.eps

Agitator quarter turn


Figure 50 shutoff valve (open position) Motor
The agitator shutoff valve

Setting accumulator circuit pressure To check or adjust the hydraulic pressure in the
You will need an assistant for parts of this procedure. accumulator circuit:
There are three relief settings for the accumulator 1. Stop the truck, put the key in your pocket, and
circuit. place a Do Not Operate sign on the windshield.

revDate
228 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

45Accreg.eps

Accumulator pump Redundant


pressure regulator Relief cartridge

newredun.eps

Figure 51 Figure 52
Accumulator pump pressure regulator for Accumulator redundant relief cartridge
A7VO (above) and for A11VO (below)

2. Loosen the jam nut on the pressure regulator of the


accumulator hydraulic pump (Figure 51). Turn the 4. Clear all personnel away from the drive lines, start
screw in two-and-one-half turns. This will raise the the truck engine, engage the pumps, and bring the
regulator pressure above 300 bar. engine RPM to maximum.
3. Loosen the jam nut (Figure 52) on the accumulator 5. Read the pressure on the accumulator circuit
redundant relief cartridge, located on the pressure gauge (Figure 53). The pressure should
emergency stop manifold. Turn the screw in two read the value shown on the hydraulic schematic. If
turns. This will raise the relief setting above 300 no adjustment is needed, skip to step (7). If
bar. additional pressure adjustment is needed, continue
with step (6).

@@@@@@@@



;;;;;;;;
QQQQQQQQ
@@@@@@@@


;;;;;;;;
QQQQQQQQ

45acumpr.epsL

@@@@@@@@


;;;;;;;;
QQQQQQQQ

@@@@@@@@


;;;;;;;;
QQQQQQQQ

@@@@@@@@


;;;;;;;;
QQQQQQQQ

@@@@@@@@


;;;;;;;;
QQQQQQQQ

@@@@@@@@


;;;;;;;;
QQQQQQQQ

@@@@@@@@


;;;;;;;;
QQQQQQQQ

Figure 53
Accumulator circuit pressure gauge

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 229
HOME PRINT

Pressure Settings
8. After the truck engine is stopped, go back to the
accumulator circuit hydraulic pump pressure
regulator (Figure 51) and turn the screw back out
two-and-one-half turns. This restores it to its
accuman1.eps
original setting.
9. Clear all personnel from the drive line area, start
the truck, and bring the engine RPM up to
maximum.
10. Read the pressure on the accumulator gauge. It
should read the proper accumulator system
pressure.
11. If adjustment is needed, you must stop the truck
engine, or a least stop the drive lines from turning,
each and every time you approach the accumulator
Pressure Relief Cartridge circuit hydraulic pump. Turn the screw in to
Manual bleed valve increase the pressure or out to decrease pressure.
Lock the jam nut when the pressure is correct.

NOTE!
The accumulator circuit hydraulic pump
pressure regulator is sometimes referred to
as the pressure cut-off.

Figure 54
Accumulator manifold pressure
relief cartridge

6. Locate the accumulator manifold pressure relief


cartridge (Figure 54). Loosen the jam nut, and turn
the screw clockwise to increase the pressure or
counterclockwise to decrease the pressure. Tighten
the jam nut when the pressure reaches the value
required.
7. You will need an assistant for this step. With the
engine still running, one person must go to the
redundant relief valve on the emergency stop
manifold (Figure 52) and back out the adjustment
screw while the other person stands by the pressure
gauge to let him know when the pressure reads the
value shown on the schematic for accumulator
redundant relief.

WARNING
Entanglement hazard. Stop drive shafts
before adjusting the accumulator pump
000075.eps

pressure regulator.

revDate
230 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
KVM 36X-42M (pre-1998) As mentioned earlier before we check or adjusts
settings of the pressure limit valve or the two relief
valves, we must make sure the Delta-P and Q-
Pressure Settings for KVM 36X
minimum settings are correct.
Proportional Load Sensing
NOTE!
NOTE:All pressure settings must be done
when the hydraulic oil is at 50 to 70 degrees
Celsius.
Please read all instructions before attempting to check
or set pressures.
There is a pressure limit valve and two different relief
valves in the KVM 36X boom circuit. Before checking
or setting these 3 valves, you should make sure that the
Delta-P setting on the pressure regulator and the Q
minimum setting on the hydraulic pump are properly
set. In order to help you better understand this, we will
describe the functions of each valve and the hydraulic
pump before attempting to set or check pressures.
Refer to Illustration 1on Page- D2 for the location of
each item as it is mounted on the unit.
Figure 1 of this page, is called the pressure regulator.
Adjusting screw (item 4) is the pressure limit function
of the pressure regulator. Adjusting screw (item 3) is
the Delta-P function of the regulator. The Delta-P
function senses pressure on both sides of the boom
handvalve, and adjusts the output flow of the hydraulic
pump.
Figure 2 of this page is the "normally open" relief
valve. (Normally open denotes that unless the coil is
energized, the relief valve will not develop any
pressure). This is the valve that opens and vents your
boom circuit to tank when you hit the red emergency
shut off button on your remote control box or
operations panel.
Figure 3 of this page is the boom handvalve. (Item
10) is pointing to the relief valve located on the
handvalve. It's function is to protect the handvalves
from any pressure spikes that might be in the system.
(Item G2) is a gauge port.
Figure 4 of this page is the boom circuit hydraulic
pump. This style of hydraulic pump has a variable
output depending on the requirements of the boom,
which is controlled by the pressure regulator described
in Figure 1 (above).

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 231
HOME PRINT

Pressure Settings
Component Location Guide KVM 36 X W/
Rexroth Handvalves

FIGURE 1 FIGURE 2 FIGURE 4 FIGURE 3

1200 / 36 X

Illustration 1

item
4

item 3

FIGURE 1
item
2
item
STOP for Q min 1

STOP for Qmax

FIGURE 4 FIGURE 2

item
10
24V

item
G2
24V

FIGURE 3

revDate
232 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Pressure Settings for KVM 36X 2. Q Minimum setting: the Q minimum stop on the
Proportional Load Sensing hydraulic pump, (Figure 4, item 1).
1. 1.Delta-P setting on the pressure regulator. With all boom functions in the neutral position,
(Figure 1, Item 3) emergency stop buttons up, the engine at
With all boom functions in the neutral position, maximum specified RPM's, the pressure on the
emergency stop buttons up, the engine at minimum main gauge (0-600 bar) should be:
RPM's (idle), the pressure that will be read on both
a) . . . KVM 32 & 36 = 40 Bar;
the pretension gauge and the main pressure gauge
b) . . . KVM 42 = 40-45 Bar;
is either Delta-P or an idle Q-minimum. To
determine what indeed is creating this pressure, we c) . . . KVM 52 = 50-55 Bar.
must do at least ONE of the three following If the pressure is incorrect, the Q-min. screw on the
procedures: hydraulic pump must be adjusted accordingly. Turn
a. A.Back off the Q-min. screw at least 3 turns on the Q-min screw inward to increase the pressure and
the hydraulic pump to insure that it is only outward to decrease the pressure.
producing the amount of flow that the regulator
is requiring to maintain Delta-P pressure. Now
read an accurate Delta-P pressure on either the
pretension gauge or the main pressure gauge.
This requires that the Q-min. be re-adjusted;
(refer to paragraph 2. for Q minimum setting).
b. B.While observing the pretension or the main
pressure gauge you increase the engine RPM
by 300 RPM in 3 increments of 100 RPM
each, making sure that the pressure does not
increase. This will assure that you are indeed
observing accurate Delta-P. If the pressure
does increase, then the pressure observed is an
idle Q-min. and not a true Delta-P. You should
then follow the procedures in paragraph 1. A.
c. C.Install a high pressure (0-600 Bar) gauge in
the X port of the regulator with a "T" fitting.
While operating a boom function, monitor the
pressure between the main pressure gauge and
the gauge at the X port of the regulator. There
should be exactly 20 Bar less pressure at the X
port continuously.
Adjusting Delta-P: The Delta-P pressure should be 20
Bar plus or minus 1 Bar; (this is the same for KVM 32,
KVM 36X, KVM 42 and KVM 52 machines). If the
Delta-P pressure is incorrect, then the regulator must
be adjusted accordingly. Turn the small screw (Figure
1, item 3) on the regulator inward to increase or
outward to decrease the Delta-P pressure. If the Delta-
P pressure cannot be adjusted to proper pressure, then
the regulator is probably defective. Do not replace the
regulator until the orifices in the base plate have been
checked to make sure they are not obstructed or
improperly sized. Refer to Figure 5 on Page - D4 for
proper orifice sizes.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 233
HOME PRINT

Pressure Settings
Pressure Regulator Cutaway

Pressure
Regulator

P
Regulator

X
A T

P 0.8 mm

ORIFICE
KVM 36X . . . . 1.6 mm
KVM 36 LW . . 1.6 mm
KVM 42 . . . . . .1.6 mm
KVM 52 . . . . . .not used

Figure 205

revDate
234 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Pressure Settings for Regulator and Releif
Valves
Now that we know our delta-P and Q-minimum are set
correct we can check and reset the pressure limit and
two relief valves. The correct pressure settings are as
follows:
1. PRESSURE REGULATOR (Figure 1, item 4)310
Bar
2. NORMALLY OPEN BYPASS VALVE (Figure 2,
item 2)330 Bar
3. HANDVALVE RELIEF (Figure 3, item 10)340
Bar
In order to reset the valve with the highest pressure, we
must first raise the pressure of the other two valves.
a. A.Install a 0-600 Bar gauge in the gauge port
(Figure 3, item G2) of the handvalve.
b. B.To set the pressure regulator (Figure 1),
loosen the lock nut (Item 4), and turn the
adjusting screw inward approximately two
turns. This will raise the pressure of this valve
higher than 340 bar.
c. C.To set the normally open bypass valve
(Figure 2), loosen the lock nut (Item 2), and
turn the adjusting screw inward approximately
one turn. This will raise the pressure of this
valve higher than 340 bar.
d. D.Pressure out any boom section except main
down. The pressure can now be read on the 0-
600 Bar gauge that you have installed on the
handvalves. The gauge should read 340 Bar. If
it does not, adjust the relief valve on the boom
handvalves (Figure 3, item 10). After you
have this relief set to 340 Bar you can lock the
locknut and move on to the normally open
bypass valve.
e. E.While you continue to hold a function
pressured out you can adjust the normally open
bypass valve (Figure 2, item 2), until the
pressure gauge now reads 330 Bar. After this
pressure is set and the locknut is locked,
proceed to the pressure regulator.
f. F.While still holding a function pressured out
you can now adjust the pressure regulator (Fig.
1, Item 4), until the pressure gauge reads 310
Bar. When this pressure has been set and the
locknut is locked, you are finished setting the
main circuit pressures on the boom.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 235
HOME

236
Handvalve
PRINT

OUT- WTR SLEW BOOM BOOM BOOM BOOM


BOOM HANDVALVE RIG CMP R&L 4 3 2 1

KVM 36LW & 36X


Pressure Settings

(Waterpump/Compressor & Outrigger)

5 3 1 1 1 1

1 - BOOM EXTEND SPEED


9 9 G1
KVM 36 LW & 36 X W/Rexroth Boom

2 - BOOM RETRACT SPEED

24V
3 - SWING RIGHT SPEED

4 - SWING LEFT SPEED 8 8


5 - WATERPUMP RPM
11 7
6 - COMPRESSOR RPM

Service Manual
7 - OUTRIGGER SPEED 10 10
8 - PRETENTION VALVE

24V
9 - PRETENTION RELIEF G2

10 - HIGH PRESS. RELIEF (340 Bar)


6 4 Orifice 2 2 2 2
11 - SECTION COMPENSATORS
O-ring

G1 - PRETENTION GAUGE PORT Filter

G2 - HIGH PRESS. GAUGE PORT O-ring

revDate
HOME PRINT
SERVICE TRAINING
Pressure Settings
Pressure Settings for KVM 42 (B&W Load
sensing and Proportional Load Sensing
NOTE!
NOTE:All pressure settings must be done
when the hydraulic oil is at 50 to 70 degrees
Celsius.
Please read all instructions before attempting to check
or set pressures.
There is a pressure limit valve and two different relief
valves in the KVM 42 boom circuit. Before checking
or setting these 3 valves, you should make sure that the
Delta-P setting on the pressure regulator and the Q
minimum setting on the hydraulic pump are properly
set. In order to help you better understand this, we will
describe the functions of each valve and the hydraulic
pump before attempting to set or check pressures.
Refer to Illustration 2 on Page- D8 for the location of
each item as it is mounted on the unit.
Figure 1 of this page, is called the pressure regulator.
Adjusting screw (item 4) is the pressure limit function
of the pressure regulator. Adjusting screw (item 3) is
the Delta-P function of the regulator. The Delta-P
function senses pressure on both sides of the boom
handvalve, and adjusts the output flow of the hydraulic
pump.
Figure 2 of this page is the "normally open" relief
valve. (Normally open denotes that unless the coil is
energized, the relief valve will not develop any
pressure). This is the valve that opens and vents your
boom circuit to tank when you hit the red emergency
shut off button on your remote control box or
operations panel.
Figure 3 of this page is the boom handvalve. (Item 9)
designates the main pressure relief valve located on the
handvalve. It's function is to protect the handvalves
from any pressure spikes that might be in the system.
(Item 11) designates the relief valve for the main
section down.
Figure 4 of this page is the boom circuit hydraulic
pump. This style of hydraulic pump has a variable
output depending on the requirements of the boom,
which is controlled by the pressure regulator described
in Figure 1 (above).
As mentioned earlier before we check or adjusts
settings of the pressure limit valve or the two relief
valves, we must make sure the Delta-P and Q-
minimum settings are correct.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 237
HOME PRINT

Pressure Settings
Component Location Guide KVM 42 W/
Rexroth Handvalves

FIGURE 1 FIGURE 4 FIGURE 2 FIGURE 3

Illustration 2

item
4

item 3

FIGURE 1
item
2
item
STOP for Q min 1

STOP for Qmax

FIGURE 4 FIGURE 2

item 11
item 9

FIGURE 3

revDate
238 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Pressure Settings for KVM 42LW 2. Q Minimum setting: the Q minimum stop on the
Proportional Load Sensing hydraulic pump, (Figure 4, item 1).
1. Delta-P setting on the pressure regulator. (Figure With all boom functions in the neutral position,
1, Item 3) emergency stop buttons up, the engine at
With all boom functions in the neutral position, maximum specified RPM's, the pressure on the
emergency stop buttons up, the engine at minimum main gauge (0-600 bar) should be:
RPM's (idle), the pressure that will be read on both
a) . . . KVM 32 & 36 = 40 Bar;
the pretension gauge and the main pressure gauge
b) . . . KVM 42 = 40-45 Bar;
is either Delta-P or an idle Q-minimum. To
determine what indeed is creating this pressure, we c) . . . KVM 52 = 50-55 Bar.
must do at least ONE of the three following If the pressure is incorrect, the Q-min. screw on the
procedures: hydraulic pump must be adjusted accordingly. Turn
a. A.Back off the Q-min. screw at least 3 turns on the Q-min screw inward to increase the pressure and
the hydraulic pump to insure that it is only outward to decrease the pressure.
producing the amount of flow that the regulator
is requiring to maintain Delta-P pressure. Now
read an accurate Delta-P pressure on either the
pretension gauge or the main pressure gauge.
This requires that the Q-min. be re-adjusted;
(refer to paragraph 2. for Q minimum setting).
b. B.While observing the pretension or the main
pressure gauge you increase the engine RPM
by 300 RPM in 3 increments of 100 RPM
each, making sure that the pressure does not
increase. This will assure that you are indeed
observing accurate Delta-P. If the pressure
does increase, then the pressure observed is an
idle Q-min. and not a true Delta-P. You should
then follow the procedures in paragraph 1. A.
c. C.Install a high pressure (0-600 Bar) gauge in
the X port of the regulator with a "T" fitting.
While operating a boom function, monitor the
pressure between the main pressure gauge and
the gauge at the X port of the regulator. There
should be exactly 20 Bar less pressure at the X
port continuously.
Adjusting Delta-P: The Delta-P pressure should be 20
Bar plus or minus 1 Bar; (this is the same for KVM 32,
KVM 36X, KVM 42 and KVM 52 machines). If the
Delta-P pressure is incorrect, then the regulator must
be adjusted accordingly. Turn the small screw (Figure
1, item 3) on the regulator inward to increase or
outward to decrease the Delta-P pressure. If the Delta-
P pressure cannot be adjusted to proper pressure, then
the regulator is probably defective. Do not replace the
regulator until the orifices in the base plate have been
checked to make sure they are not obstructed or
improperly sized. Refer to Figure 5 on Page - D10 for
proper orifice sizes.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 239
HOME PRINT

Pressure Settings
Pressure Regulator Cutaway

Pressure
Regulator

P
Regulator

X
A T

P 0.8 mm

ORIFICE
KVM 36X . . . . 1.6 mm
KVM 36 LW . . 1.6 mm
KVM 42 . . . . . .1.6 mm
KVM 52 . . . . . .not used
Figure 206
Regulator Valve

revDate
240 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Pressure Settings for Regulator and Relief e. While still holding a function pressured out
Valves KVM 42 you can now adjust the pressure regulator
(Figure 1, Item 4), until the pressure gauge
Now that we know our delta-P and Q-minimum are set
reads 310 Bar on Black & White units or 290
correct we can check and reset the pressure limit and
Bar on Proportional units. When this pressure
two relief valves. The correct pressure settings are as
has been set and the locknut is locked, you are
follows:
finished setting the main circuit pressures on
1) PRESSURE REGULATOR (Figure the boom.
1, item 4): f. There is also a relief valve for the main boom
down function (Figure 3, item 11); (this relief
KVM 42 B&W 310 Bar valve is either located in the handvalve housing
KVM 42 Prop. 290 Bar directly in front of the manual hand lever for
the main section), or: (is Td into the steel tube
2) NORMALLY OPEN BYPASS VALVE that comes out of the "A" port on the frontside
(Figure 3, item 2): of the main section handvalve). Before setting
All 42 Meters 320 Bar the downside relief valve, you must bring the
boom to its fully retracted position. This is
3) HANDVALVE HIGH PRESSURE best accomplished with the boom swung off to
RELIEF (Figure 3, item 9): the side of the truck with the outriggers fully
extended. While holding the main section
All 42 Meters 330 Bar
pressured out in the fully retracted position,
you can now adjust the downside relief
In order to reset the valve with the highest pressure, we cartridge until you read 100 Bar on the 0-600
must first raise the pressure of the other two valves. Bar gauge.

a. To set the pressure regulator (Figure 1), loosen


the lock nut (Item 4), and turn the adjusting
screw inward approximately two turns. This
will raise the pressure of this valve higher than
330 bar.
b. To set the normally open bypass valve (Figure
2), loosen the lock nut (Item 2), and turn the
adjusting screw inward approximately one
turn. This will raise the pressure of this valve
higher than 330 bar.
c. Pressure out any boom section except the main
down. The pressure can now be read on the 0-
600 Bar gauge that is near the handvalves. The
gauge should read 330 Bar. If it does not,
adjust the relief valve on the boom handvalves
(Figure 3, item 9). After you have this relief
set to 330 Bar you can lock the locknut and
move on to the normally open bypass valve.
d. While you continue to hold a function
pressured out you can adjust the normally open
bypass valve (Figure 2, item 2), until the
pressure gauge now reads 320 Bar. After this
pressure is set and the locknut is locked,
proceed to the pressure regulator.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 241
HOME

242
KVM 42LW BOOM HANDVALVE
(Waterpump/Compressor,Throttle, & Outrigger)
PRINT

1 - BOOM EXTEND SPEED


Pressure Settings

2 - BOOM RETRACT SPEED


3 - SWING RIGHT SPEED
4 - SWING LEFT SPEED BOOM BOOM BOOM BOOM SWING RPM WTR/ OUT-
1 2 3 4 R/L COMP. RIGGER
5 - WATERPUMP RPM
6 - COMPRESSOR RPM
7 - OUTRIGGER SPEED
8 - PRETENTION VALVE
9 - HIGH PRESS. RELIEF (330 Bar)
10 - SECTION COMPENSATORS 1 1 1 1 3 5
KVM 42 LW, W/Rexroth BoomHandvalve

11 11 - DOWN-SIDE RELIEF VALVE

9 24V 24V 24V 24V 24V 24V 24V

24V

Service Manual
7
O-ring O-ring

8 8
10
Filter Orifice

24V 24V 24V 24V 24V 24V 24V

24V
2 2 2 2 4 6

revDate
HOME PRINT
SERVICE TRAINING
Pressure Settings
KVM 36X 1. Locate the agitator shutoff valve, and close it
(Figure 10). The general location of the agitator
Check all hydraulic pressures shutoff valve is shown in Figure 93.

Check all hydraulic pressures. Changes in pressures NOTE!


can indicate trouble in one or more components. If your unit does not have a shutoff valve,
order one using part #10004680 (valve) and
NOTE! #30303432 (tube). Contact the Schwing Ser-
Hydraulic pressures setting shown in the vice Department for installation instruc-
following procedures are for a 1200 single tions. If you cant wait for a shutoff valve,
circuit pump kit and a 2023 twin circuit you will need to remove one of the hoses
pump kit. However, because different pump from the agitator motor, and plug the hose
kits may be used in this unit, all pressure and the open fitting with approved hydrau-
settings should be verified with the pressure lic dead plugs. Do not substitute other plugs,
settings shown on the applicable hydraulic such as a steel bearing, inside a cap fitting.
schematic. The hydraulic schematics for
2. Position the agitator lever in the forward or reverse
your pump kit are in the Appendix of this
position The agitator will not be able to turn, and
manual.
the oil will be forced over the relief valve.
If you wish to order a CD ROM which explains the
3. At idle speed (about 600 RPM), about 4.5
pressure setting procedure for a specific model (All
horsepower is being converted to heat. Position the
pumpkits), call SAI Spare Parts Department at (800)
agitator lever to the off (center) position when the
328 - 9635 and request the CD using the following part
temperature gauge on the main control panel
numbers:
indicates 50C.
61/58 meter. . . . . . . . . . . . . . . . . . . . . . . 30365860
4. Open the agitator shutoff valve or remove the plug,
52 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30354732 and reconnect the hose to the agitator motor.
45/47 meter. . . . . . . . . . . . . . . . . . . . . . . 30356770
42 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30355485
52qrttrn.epsL
39 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30365861
34 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30356772 OFF
32 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30355486
31 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30365862
Read all of the instructions before beginning any
pressure settings. You will need an assistant for parts of
the procedure.
You and any assistants should wear eye protection
when checking or setting pressures.
Be sure that the waterbox covers are installed on the
waterbox. Figure 10
We do not recommend using the remote control box for Agitator shutoff valve
the following procedures.
Wear safety glasses when setting pressures.
Position the remote/local switch on the main control
panel to the local position.
Pressure settings must be made with the oil at normal
operating temperatures (40C 60C). The agitator
circuit must be used to heat the hydraulic oil. Do not
jam the paddles to force the oil over relief by stopping
the movement of the agitator. To preheat the hydraulic
oil using the agitator circuit, follow these instructions.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 243
HOME PRINT

Pressure Settings
The general location of the components used to
check or set hydraulic pressures in shown in Fig-
ure 93.

36Xdside.eps
Boom (Section #1) Down
Pressure Relief Valve and Boom Hand Valves and
Gauge Port Gauge Port

Concrete Pump Shutoff


Valve
Concrete Pump Pressure
Soft Switch Shutoff Valve Gauge
(twin circuit)
Side panel box
Main Relief Valve Concrete pump forward/
reverse hand valve
Outrigger hand valves and
Outrigger Hand Valves t gauge port
E-Stop Manifold and Gauge
Accumulator Unloading Remote Control Connector
Manifold Valve and Gauge
(twin circuit)

Agitator Shutoff Valve Rear Control Panel

Agitator Hand Valve and


Gauge Port

Figure 11
General location of components
used to set hydraulic pressures

Set the concrete pump main relief valve valve is located at the front of the control block
(single- circuit) (towards the truck cab). To check or set the main relief
pressure perform the following steps:
The BPL 1200 concrete pump is designed to operated
at a maximum pressure of 300 bar (4350 PSI). It is
controlled by the main relief valve (Figure 79), which
revDate
244 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Mount bolt and washer


removed for illustration

grooves2.eps

Grooves in handle should


line up with grooves
in valve shaft

Lower Raise
pressure pressure

gray valve.eps L

Figure 12
Concrete pump main relief valve

1. Close the concrete pump shutoff valve (Figure 80)


2. Use the throttle switch on the main control panel to
rev the engine up to full RPM. quarter turn.eps

3. Use the concrete pump forward/neutral/reverse


Figure 13
switch to put the pump into the forward position.
Concrete pump shutoff valve
The unit will stroke only once, then the rock
cylinder will retract. Oil will have nowhere to go
except over the concrete pump main relief valve.
4. Read the pressure on the concrete pump pressure
gauge, located on the main control block. It should 5. If adjustment is required, loosen the jam nut on the
read 300 bar. Position the concrete pump switch to relief valve adjusting screw with a 13-mm spanner
the off (neutral) position. If no adjustment is wrench (Figure 79).
needed, skip to Step 8. 6. Turn the adjustment knob on the relief valve to
adjust the pressure. Turn the adjustment knob in to
raise pressure or out to lower the pressure.
7. Retighten the jam nut. (Tightening the jam nut
tends to raise the pressure. If this happens, hold the
adjustment knob while tightening the jam nut.)
8. Put the concrete pump into the forward position
again. The machine will not stroke this time, but
will develop maximum pressure. Read the pressure
on the control block pressure gauge. If more
adjustment is needed, return the pump to neutral,
then repeat Steps 5 through Step 8 until the
pressure is at 300 bar.
9. Open the shutoff valve. The unit will not stroke
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 245
HOME PRINT

Pressure Settings
with the shutoff valve closed. 7. Read the pressure on the concrete pump pressure
gauge located on the main control block. It should
NOTE!
read 350 bar. Position the concrete pump switch to
If you cannot adjust the pressure up to 300
the off (neutral) position. If no adjustment is
bar, you have a problem. In this case, turn
needed, skip to Step 11.
the adjustment knob out by several turns so
that your pressure isnt too high once the 8. If adjustment is needed, use a 9/16 inch spanner
problem is found. Contact Schwing Amer- wrench, loosen the jam nut on the main relief valve
icas Service Department for advice on how adjusting screw (Figure 5).
to continue. 9. Insert a 5/32 inch allen wrench in the adjustment
Set the concrete pump main relief valve (twin screw. Turn the screw in to raise pressure or out to
circuit) lower the pressure.
10. Once the pressure is correct (350) bar retighten the
The main relief valve is the primary pressure control
jam nut. Tightening the nut tends to raise the
device on units equipped with Rexroth A7VO
pressure, so check pressure again after tightening.
hydraulic pumps. This pump is designed to operate at a
Verify the correct pressure setting (350 bar).
maximum pressure of 350 bar (5075 PSI).
11. Open the concrete pump shutoff and soft switch
valves. The unit will not stroke with theses valves
closed.
WARNING
Hot oil expulsion hazard. stand away
from pumpkit when checking hydraulic
pressures.
W008.eps

The main relief valve is set to very high


pressure (at least 350 bar). Use the controls
on the rear control panel when checking the
pressure of the main relief valve, so you will
be out of the way if a hose or a fitting mal-
functions.
Refer to Figure 5 for the location of the components
used to set the concrete pump pressures. Use the
following steps to set the main relief valve pressure:
1. Be sure that the waterbox covers are installed on
the waterbox. We do not recommend using the
remote control box for the following procedure.
2. Wear safety glasses when setting pressures.
3. Close the concrete pump shutoff and soft switch
valves (Figure 5).
4. Position the remote / local switch on the main
control panel to the local position.
5. Use the throttle switch on the main control panel to
rev the engine up to full RPM.
6. Use the concrete pump forward/neutral/reverse
switch to put the pump into the forward position.
The unit will stroke only once, then the rock
cylinder will retract. Oil will have no where to go
except over the concrete pump main relief valve.
revDate
246 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
w

Gauge port

39
hif
lw1
.ep
s

Main relief valve

Soft switch
relief valve

Mount bolt and washer


Soft switch removed for illustration
shutoff valve

grooves2.eps

Concrete pump Grooves in handle should


39
shutoff valve hif
low
.ep
line up with grooves
s
in valve shaft

Figure 14
Location of the main relief valve

Setting the soft switch circuit relief 2. High pressure the concrete pump. The pressure
pressure gauge should read 60 or 80 bar (check your
schematic). If no adjustment is needed, skip to Step
To check or adjust the soft switch pressure setting,
4.
proceed as follows:
3. If adjustment is needed, loosen the jam nut on the
1. Close the concrete pump shutoff valve. Open the
soft switch relief valve with a 9/16 inch spanner
soft switch shutoff valve. The rest of the unit
wrench. Adjust the pressure up or down, as needed,
should still be set up as though you were going to
using a 5/32 inch Allen wrench. When the correct
check concrete pump pressure.
pressure is achieved, re-lock the jam nut.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 247
HOME PRINT

Pressure Settings
4. Be sure to open the concrete pump shutoff valve
when you are finished. The unit cannot stroke with
e-stop/right.epsL
this valve closed.
Relief Valve and
Gauge Port
Set accumulator circuit
Units with a pressure- compensated pump
You will need an assistant for parts of this procedure.
To check or adjust the hydraulic pressure in the
accumulator circuit, perform the following steps:
1. Stop the truck, put the key in your pocket, and
place a Do Not Operate sign on the windshield.
2. Loosen the jam nut on the pressure regulator of the
accumulator hydraulic pump. Turn the screw in
two-and-a-half turns. This will raise the regulator
pressure above 300 bar (Figure 83).
. Figure 16

5. Clear all personnel away from the drive lines, start


the truck engine, engage the pumps, and bring the
engine RPM to maximum.
Accumreg.eps
6. Read the pressure on the accumulator circuit gauge
located on the accumulator manifold block (Figure
85). Pressure should read 300 bar (4350 PSI). If no
adjustment is needed, skip to (Step 8).
7. If additional pressure adjustment is needed, locate
the accumulator manifold pressure relief valve
Accumulator pump
pressure regulator
(Figure 85). Loosen the jam nut, and turn the screw
in to increase pressure or out to decrease pressure.
Tighten the jam nut when pressure is at 300 bar.
Figure 15
Accumulator pump pressure regulator

3. Connect the whip hose of a 0-600 bar gauge into


the gauge port of the E-Stop manifold (Figure 84).
4. Loosen the jam nut on the accumulator relief valve,
located on the E-Stop manifold. Turn the screw in
two turns. This will raise the relief setting above
300 bar (Figure 84).

revDate
248 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Setting the outrigger pressure
SAFETY INSTRUCTIONS
Accumulator Safety Rules
2. Always relieve the
the system is relieved
of oil pressure.
1. Never assume that hydraulic system of pressure before
dis-assembly for clean
out, repair, or maintenance.
WARNING
Stored hydraulic energy.
With a seven place hand valve, the boom/outrigger
circuit pressure gauge
to verify zero
Release all hydraulic

selector valve is inside the boom control block. This


3. Check accumulator
system pressure.
4. Never assume that
it is safe to put your hands
in the concrete
pressure and verify zero
valve. does not guarantee zero
system pressure.
5. Stopping the engine pump electrically does not de-pressurize
pressure on gauge before
6. Stopping the concrete servicing.
the accumulator circuit.compressed air to charge the accumulator!
or pressure
7. NEVER use oxygen without the correct nitrogen
the machine
8. Operation of Before charging the accumulator,

valve is activated when the outrigger enable push


could damage the accumulator.Read the operation manual.
understand the procedure.

button is pushed. There is not a separate relief for this


circuit and, therefore nothing that must be set.
The outrigger circuit is set to a maximum of 280-bar
(4060 PSI) by the relief valve located on the passenger
side outrigger hand valve assembly (Figure 102). The
valve routes the oil to the two outrigger hand valve
banks, one on each side of the unit. A relief valve
inside the passenger side bank limits the entire
Relief Valve outrigger circuit to 280-bar.

36accum.eps
Lower
Figure 17 Turn body of valve
Accumulator manifold pressure relief Higher
to adjust.
valve

8. You will need an assistant for this step. With the 280 bar
engine still running, adjust the relief valve of the E-
Stop manifold. Back out the adjustment screw Relief Valve
until pressure reads 260 bar (3770 PSI) on the
gauge connected to the E-Stop manifold.

WARNING
Entanglement hazard. Stop drive shafts
before adjusting the accumulator pump
pressure regulator.
W010.eps

Figure 18
Outrigger hand valve
9. After the truck engine is stopped, back out the
accumulator circuit hydraulic pump pressure regu-
lator two-and-a-half-turns. This restores the pres-
sure regulator to its original setting (Figure 83). 1. Connect the whip hose of a 0400 or 0600 bar to
10. Clear all personnel from the drive line area, start the gauge port on the right side of the outrigger
the truck, and rev the engine RPM to maximum. hand valve.
11. Read the pressure on the accumulator gauge. It 2. If it is not already done, start the truck engine and
should read 200 bar (2900 PSI). set the transmission and PTO as you would for a
pumping job.
12. If additional adjustment is needed, you must stop
the truck engine each time you approach the accu- 3. Set the engine RPM to maximum.
mulator circuit hydraulic pump (Figure 83). Adjust 4. Push the outrigger enable pushbutton located next
the accumulator pump pressure regulator screw in to the outrigger hand valve (passenger side). Hold
to increase pressure or out to decrease pressure. one of the outrigger hand valve levers in the
Lock the jam nut when pressure is correct (200 jacking-retract position. The oil coming from the
bar). pump has nowhere to go but over the outrigger
relief valve.
NOTE!
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 249
HOME PRINT

Pressure Settings
You cannot use the extend position for this boom hydraulic pressures is shown in Figure 19.
adjustment because extend has a nonadjust-
NOTE!
able secondary relief functions built into the
Do not adjust P or Q-min if your boom is
valve.
running as you like it. The pressure setting
5. Turn the outside body of the relief valve that is procedure uses a standard starting point
located at the back of the passenger side outrigger and must be fine tuned from there. It was
hand valve (Figure 102). Turn in to raise pressure fine tuned at the factory and should not be
or turn out to lower pressure. adjusted unless absolutely necessary.
6. When the pressure on the gauge connected to the
outrigger hand valve is 280-bar, release the enable
push button and the outrigger hand valve.
7. Remove the whip hose and gauge from the
WARNING
outrigger handvalve, and replace the cap on the
Entanglement hazard. Stop drive shafts
gauge port before adjusting Q-min.

W009.eps
Pressure reducing valve
This valve is preset at the factory. Contact Schwing
Americas Service Department at (651) 429-0999 for
information on checking or setting this valve. Each time the Q-min screw must be
adjusted, the engine must be stopped, or at
Electric stroke limiter
least the transmission must be taken out of
This valve is preset at the factory. Contact Schwing gear so that the drivelines stop turning.
Americas Service Department at (651) 429-0999 for
information on checking or setting this valve
Load-sensing boom pressures (7 place
proportional circuit)
If your unit has a load-sensing proportional system, it
will have different pressure adjustments than if it is
equipped with a black and white boom system. The
following instructions are for load-sensing proportional
systems. If you have a unit equipped with a black and
white boom system, contact Schwing Service
Department for the correct instruction pages.
In a black and white boom system, the hydraulic pump
puts out an unchanging amount of oil, and speed
control is done by restricting the oil to certain functions
with orifices. In a load-sensing system, the pump puts
out more or less oil to respond to the needs of the
system. Generally, the pump puts out enough oil to
maintain a 20 bar higher pressure at the pump than
what the cylinders actually require. This 20 bar is
called delta P (P). Additionally, we set the hydraulic
pump so that it always puts out a small amount of oil,
even if no oil is needed for the system. This oil is used
to ensure that you have control when you need it. The
setting to maintain this minimum amount of oil is
called Q-min (pronounced cue min). To set the boom
or outrigger hydraulic pressures on a load-sensing
system, begin by setting Q-min and P.
The general locations of the components used to set
revDate
250 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Boom Hand Valves Q-min Adjust Screw P Regulator E-Stop Manifold

36Xdside.eps

Figure 19
Location of components used to
check or set boom pressures

0-400 bar
gauge port
0-60 bar
gauge port

boom control
block relief valve
s
ep
dv.
itpr
ap
36

15 bar pretension
adjustment screw

Figure 20
Boom hand valves

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 251
HOME PRINT

Pressure Settings
Check or set P Remove the gauge, and adjust P until the boom is
To check or set P follow these steps: responsive and smooth. When done, the gauge
(reinstalled) must read between 14 and 25 bar. The
1. Stop the truck engine, and place a Do Not electronics in the control system can also affect how
Operate sign on the truck windshield. the boom operates, so if P adjustment does not seem
2. Install a 0-40 or 0-60 bar gauge in the 0-400 bar to help, reset to 20 bar and check the electrical settings.
gauge port of the manual boom handvalves. Take Once electrical settings are verified, you could again
care not to accidently install the gauge in the 0-60 refine the boom action with the P adjustment.
bar port (Figure 20). CAUTION! Do not operate any functions while
3. To be sure that the pump is putting out only enough setting P.
oil needed to maintain P, we need to change the
setting of the Q-min screw. Q-min is adjusted by a
screw on the boom hydraulic pump (Figure 21).
Unscrew the Q-min screw three full turns. Check

deltaPvlv.eps
that all personnel are clear of the truck, then restart
the engine, engage the pumps, and leave the engine
at an idle. CAUTION! If you activate any boom P adjust
T
or outrigger functions, you will damage the 0 - screw
40 bar gauge. Make sure that all emergency stop
switches are in the up (not activated) position. Figure 22
Pressure can be read on the 0 - 40 bar gauge that P regulator valve
you installed. Pressure should read 20 bar. If no Check or set Q-min
adjustment is needed, simply reset the Q-min
screw as described in the Check or set Q-min steps. You must check Q-min pressure when the engine is at
If adjustment is needed, continue to Step 4. the maximum specified RPM, but you must adjust it
with the engine stopped. To check or set the Q-min
follow these steps:
Q-min
adjustment screw 1. If you unscrewed the Q-min screw as the first step
of P adjustment, begin by returning the screw to
its original position (Figure 21).
2. Remove the 0 - 40 bar gauge from the 0 - 400 bar
gauge port, and install the 0 - 600 bar gauge in its
place (Figure 20).
3. Clear all personnel away from the drive lines, start
Q-minscrew.eps
the truck engine, engage the pumps, and bring
Q-max engine RPM to max. All boom functions must be
in neutral, and all emergency stop buttons
should be up (not engaged).
Figure 21
Q-min adjust screw 4. Read the pressure on the 0 - 600 gauge. Pressure
should be at 40 - 45 bar. If no adjustment is needed,
4. Delta P is adjusted by the P screw on the P stop the drive lines from turning, be sure the jam
regulator (Figure 22). Loosen the jam nut, and nut on the Q-min screw is tight, then continue to
adjust the screw inward to increase pressure or Set boom pressures to check the rest of the boom
outward to decrease pressure until it is set at 20 bar pressures.
(1). Contact Schwing Americas Service 5. If adjustment is needed, turn the Q-min screw in to
Department if you are unable to adjust the pressure raise the pressure (Figure 21). Turn it out to lower
to specification. the pressure. Be sure that you stop the drive shafts
from turning each time before making the
NOTE! adjustment. When pressure is correct, tighten the
If the boom does not operate smoothly at 20 jam nut on the adjustment screw before continuing
bar, you must fine tune the adjustment. with the other procedures.
revDate
252 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Set boom pressures
(load sensing proportional booms)
Now that P and Q-min are set, you can check or set
the boom valve pressures.There are three pressure
settings on the boom circuit (Figure 23).
1. Pressure regulator (the high-pressure adjustment
screw on the P regulator valve), set at 290 bar 0-400 bar
(4205 PSI). gauge port
2. The redundant relief valve located in the 0-60 bar
gauge port
emergency stop manifold, set at 320 bar (4640
PSI). boom control
3. The boom control block relief valve, set at 350 bar block relief valve
(5075 PSI). Bo
om
Va
.eps

36

NOTE! 15 bar pretension


adjustment screw
The boom control block relief valve is non-
adjustable. If pressure is not maintained
within the specification limits, the valve
P Regulator Valve
must be replaced.
(high pressure
adjustment screw)
deltaPvlv.eps

e-stop/right.epsL

E-Stop Manifold
Redundant Relief Valve

Figure 23
Boom hydraulic pressure adjustment
components

To check the setting of the valve with the highest


pressure, you must first raise the pressure of the lower
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 253
HOME PRINT

Pressure Settings
two: pressurized function and lock the jam nut. The
1. Loosen the jam nut of the high pressure adjustment boom pressures are now set. If you did not get the
screw of the P regulator. Turn the screw in two- readings specified after following the instructions,
and-a-half turns. This will raise the pressure on the contact Schwing Americas Service Department at
P regulator above 350 bar. (651) 429-0999 for advice on how to continue.
2. Loosen the jam nut of the adjustment screw on the
E-stop manifold redundant relief valve. Turn the
screw in one-and-a-half turns. This will raise the
pressure setting of the relief valve to above 350 bar.
3. Pressure out any boom cylinder except #1 down by
pushing or pulling the control handle. To pressure
out a cylinder, retract a fully retracted cylinder or
extend a fully extended cylinder. The oil is forced
over the relief valve.
4. The tell tale hiss of an open relief valve should be
coming from the Apitech control block relief valve
now. If it isnt, raise the setting of the other
pressure devices until the hiss originates at the
Apitech control block relief valve. Read the
pressure on the gauge connected to the 0-400 bar
gauge port on the boom hand valve block. It should
read 350 bar. If pressure is correct, proceed to Step
5.
NOTE!
Although the pressure specification for the
Apitech relief valve is 350 bar, you may con-
tinue to use the relief valve as long as the
cartridge maintains at least 330 bar. If you
must replace the valve, proceed to Step 5
before using the concrete pump again, and
redo this entire procedure when you have
installed the new valve. If pressure on the
Apitech relief valve is below 290 bar, you
should not use the concrete pump until the
valve is replaced.
5. Screw out the E-Stop manifold redundant relief
valve adjustment screw one-and-a-half turns.
Pressure out any boom cylinder except #1 down,
and read the gauge. Pressure should read 320 bar.
If it does not, turn the screw in to raise pressure or
out to lower pressure until it is set at 320 bar. If the
location of this valve causes you to be near the
drive lines, be sure to stop them from turning
before accessing the valve.
6. You will need a helper for this step. While
pressuring out any boom cylinder (except #1
down) have your helper adjust the high pressure
screw of the P regulator out (lowering the
pressure) until the gauge reads 290 bar. Release the

revDate
254 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

0-400 bar
gauge port
0-60 bar
gauge port

boom control
block relief valve
s
ep
dv.
itpr
ap
36

15 bar pretension
adjustment screw

Figure 24
Pretension adjustment screw
and gauge port

Set 15 bar pretension valve is inside the boom control block. There is not a
To check or set pretension, follow these steps: separate relief valve for this circuit and, therefore,
nothing that must be set.
1. Stop the truck engine. Plug the 0 - 40 bar gauge
into the 0-60 bar gauge port of the Apitech hand Set water pump pressure
valve (Figure 24).
With a seven place hand valve, the water pump
2. Start the truck engine, but leave it at an idle.
hydraulic control is inside the boom control block.
(Pretension adjustment is made at an idle to
There is not a separate relief valve for this circuit and,
establish the minimum pressure setting. As RPM is
therefore nothing that must be set.
increased, pressure will rise. Read the pressure on
the gauge. If it reads 15 bar 1 bar, the pressure is
Set the agitator pressure
set correctly.
The agitator circuit has a maximum pressure of 200 bar
NOTE! (2900 PSI), limited by the relief valve located in the
Damage to the 0 - 40 bar gauge is possible if agitator hand valve (Figure 117). The gauge port for
RPM is raised while the gauge is connected. checking or setting the agitator pressure is located on
3. If adjustment is needed, loosen the jam nut on the the agitator hand valve.
pretension valve (Figure 24). Turn the screw in to
raise pressure and out to lower pressure. When the
pressure is correct, retighten the jam nut.
4. Stop the engine, and remove the 0 - 40 bar gauge.
#1 boom down - brake valve
With a seven place hand valve, the #1 down brake -
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 255
HOME PRINT

Pressure Settings

AgitHdVl.eps
All of these fittings and many, many more
extremely useful items are included in the
Troubleshooting Kit, part number 30308553. We
highly recommend purchase of this kit. It will pay
for itself many times over. You will need:
Relief Valve - Qty 2 VS-16S locking plugs, part number
10016803
- Qty 1 GS-16S straight fitting, part number
10008088
- Qty 2 16S capnuts, part number 10001743
6. Be sure that one of the locking plugs and capnuts
Gauge Port are tightened on the straight fitting and that the
dead plugs are securely tightened to the hose and
the open motor fitting.
7. Locate the relief valve on the agitator hand valve.
8. Be sure that all personnel are clear, and restart the
engine.
9. Activate the agitator hand valve by pushing or
Figure 25 pulling the handle. This will send the oil against
Agitator hand valve the high pressure plug. The oil will have nowhere
to go, so it will return to the tank over the relief
1. Stop the unit, and put the key in your pocket.
valve in the agitator hand valve. The pressure at
2. Connect the whip hose of 0-400 or a 0600-bar which it relieves can be seen on the gauge. It
gauge to the gauge port on the agitator hand valve should read 200-bar.
(Figure 117).
10. If adjustment is needed, turn the outside body of
3. If your unit is equipped with an the relief valve that is located at the back of the
4. agitator shut off valve, close it (Figure 20). Skip to agitator hand valve. Turn in to raise pressure or
Step 6. turn out to lower pressure.
11. When the pressure is set at 200-bar, stop the engine
52qrttrn.epsL and remove the key. Open the shut off valve or
remove the dead plugs and store them in a clean
Closed
area or in a plastic bag or something similar to
keep dirt from entering the fittings. Reattach the
hose to the agitator motor fitting and tighten
securely. (Torque is correct if you make one
complete revolution after feeling initial resistance
Shown in the increase.)
open position 12. Remove the whip hose and pressure gauge.
Replace the gauge port cover.

Figure 26
Agitator shutoff valve
5. If your unit is not equipped with an agitator shut
off valve, remove one of the hoses from the
agitator motor and plug the hose and the open
fitting with approved hydraulic dead plugs. Do not
improvise on these plugs. If you dont have any,
contact the Schwings Spare Parts Department and
order them before continuing with this procedure.
revDate
256 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
KVM 39X
52qrttrn.epsL
Closed
Check all hydraulic pressures
Check all hydraulic pressures. Changes in pressures
can indicate trouble in one or more components.
NOTE!
Hydraulic pressure settings shown in the
following procedures are for a 2023 twin
circuit pump kit. However, because Shown in the
different pump kits may be used in this unit, open position
all pressure settings should be verified with
the pressure settings shown on the Figure 27
applicable hydraulic schematic. The Agitator shutoff valve
hydraulic schematics for your pump kit are
in the Appendix of this manual.
Read all of the instructions before beginning any
pressure settings. You will need an assistant for parts of
the procedure.
You and any assistants should wear eye protection
when checking or setting pressures.
Be sure that the waterbox covers are installed on the
waterbox.
We do not recommend using the remote control box for
the following procedures.
Wear safety glasses when setting pressures.
Position the remote/local switch on the rear control
panel to the local position.
Pressure settings must be made with the oil at normal
operating temperatures (40C 60C). The agitator
circuit must be used to heat the hydraulic oil. Do not
jam the paddles to force the oil over relief by stopping
the movement of the agitator. To preheat the hydraulic
oil using the agitator circuit, follow these instructions.
1. Locate the agitator shutoff valve, and close it
(Figure 10). The general location of the agitator
shutoff valve is shown in Figure 93.
2. Position the agitator lever in the forward or reverse
position. The agitator will not be able to turn, and
the oil will be forced over the relief valve.
3. At idle speed (about 600 RPM), about 4.5
horsepower is being converted to heat. Position the
agitator lever to the off (center) position when the
temperature gauge on the rear control panel
indicates 50C.
4. Open the agitator shutoff valve or remove the plug,
and reconnect the hose to the agitator motor.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 257
HOME PRINT

Pressure Settings
The general location of the components used to 61/58 meter. . . . . . . . . . . . . . . . . . . . . . . 30365860
check or set hydraulic pressures is shown in Figure 52 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30354732
93. 45/47 meter. . . . . . . . . . . . . . . . . . . . . . . 30356770
If you wish to order a CD ROM which explains the 42 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30355485
pressure setting procedure for a specific model (All 39 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30365861
pumpkits), call SAI Spare Parts Department at (800) 34 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30356772
328 - 9635 and request the CD using the following part 32 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30355486
numbers:
31 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30365862

39Xtop.eps

Hydraulic Controls
Enclosure
Boom Hand Valves
Soft Switch Shutoff Valve and Gauge Port
(twin circuit) Forward/Reverse
Hand Valve
Agitator Hand
Valve and Gauge
Port
Main Relief Valve E-Stop Manifold
Soft Switch Relief Valve and Gauge port
Pilot Air Regulator
Concrete Pump Shutoff Stroke Limiter
Valve

Outrigger Hand Valves Outrigger Hand Valves


and Gauge Port
Accumulator Unloading
Manifold Valve (twin Rear Control Panel
circuit)
Accumulator Gauge
Agitator Shutoff Valve
Concrete Pump
Pressure Gauge

Figure 28
General location of components
used to set hydraulic pressures

revDate
258 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Set the concrete pump main relief valve 9. Insert a 5/32 inch allen wrench in the adjustment
(twin circuit) screw. Turn the screw in to raise pressure or out to
lower the pressure.
The main relief valve is the primary pressure control
device on units equipped with Rexroth A7VO 10. Once the pressure is correct (350 bar) retighten the
hydraulic pumps. This pump is designed to operate at a jam nut. Tightening the nut tends to raise the
maximum pressure of 350 bar (5075 PSI). pressure, so check pressure again after tightening.
Verify the correct pressure setting (350 bar).
11. Open the concrete pump shutoff valve and soft
WARNING switch shutoff valve. The unit will not stroke with
these valves closed.
Hot oil expulsion hazard. Stand away
from pumpkit when checking hydraulic
pressures.

W008.eps

The main relief valve is set to very high


pressure (at least 350 bar). Use the controls
on the rear control panel when checking the
pressure of the main relief valve, so you will
be out of the way if a hose or a fitting
malfunctions.
Refer to Figure 5 for the location of the components
used to set the concrete pump pressures. Use the
following steps to set the main relief valve pressure:
1. Be sure that the waterbox covers are installed on
the waterbox. We do not recommend using the
remote control box for the following procedure.
2. Wear safety glasses when setting pressures.
3. Close the concrete pump shutoff and soft switch
shutoff valves (Figure 5).
4. Position the remote / local switch on the rear
control panel to the local position.
5. Use the throttle switch on the rear control panel to
rev the engine up to full RPM.
6. Use the concrete pump forward/neutral/reverse
switch to put the pump into the forward position.
The unit will stroke only once, then the rock
cylinder will retract. Oil will have no where to go
except over the concrete pump main relief valve.
7. Read the pressure on the concrete pump pressure
gauge located on the main control block. It should
read 350 bar. Position the concrete pump switch to
the off (neutral) position. If no adjustment is
needed, skip to Step 11.
8. If adjustment is needed, use a 9/16 inch spanner
wrench, loosen the jam nut on the main relief valve
adjusting screw (Figure 5).
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 259
HOME PRINT

Pressure Settings
w

Gauge port

39
hif
lw1
.ep
s

Main relief valve

Soft switch
relief valve

Mount bolt and washer


Soft switch
removed for illustration
shutoff valve

grooves2.eps

Concrete pump Grooves in handle should


39
shutoff valve hif
low
.ep line up with grooves
s
in valve shaft

Figure 29
Location of the main relief valve

Setting the soft switch circuit relief bar (check your schematic). If no adjustment is
pressure needed, skip to Step 4.
To check or adjust the soft switch pressure setting, 3. If adjustment is needed, loosen the jam nut on the
proceed as follows: soft switch relief valve with a 9/16 inch spanner
wrench. Adjust the pressure up or down, as needed,
1. Close the concrete pump shutoff valve. Open the
using a 5/32 inch Allen wrench. When the correct
soft switch shutoff valve. The rest of the unit
pressure is achieved, re-lock the jam nut.
should still be set up as though you were going to
check concrete pump pressure. 4. Be sure to open the concrete pump shutoff valve
when you are finished. The unit cannot stroke with
2. Increase the engine RPM to high pressure the
this valve closed.
concrete pump. The pressure gauge should read 80
revDate
260 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Set accumulator circuit .

(units with a pressure- compensated pump)


You will need an assistant for parts of this procedure.
To check or adjust the hydraulic pressure in the
accumulator circuit, perform the following steps:
1. Stop the truck, put the key in your pocket, and
Accumreg.eps
place a Do Not Operate sign on the windshield.
2. Loosen the jam nut on the pressure regulator of the
accumulator hydraulic pump. Turn the screw in
two-and-a-half turns. This will raise the regulator
pressure above 300 bar (Figure 83).
NOTE! Accumulator pump
If your unit is a current production model pressure regulator
Figure 6, skip Steps 3,4, and 8 of this
procedure.
Figure 31
Accumulator pump pressure regulator

3. Connect the whip hose of a 0-600 bar gauge into


the gauge port of the E-Stop manifold (Figure 84).
4. Loosen the jam nut on the accumulator circuit
ps
relief valve, located on the E-Stop manifold. Turn
rt.e
ca
no
the screw in two turns. This will raise the relief set-
ting above 300 bar (Figure 84).

e-stop/right.epsL

Relief Valve and


Figure 30
Gauge Port
E-Stop manifold
(current production)

Figure 32
E-Stop manifold relief valve,
accumulator circuit (original
production)
5. Clear all personnel away from the drive lines, start
the truck engine, engage the pumps, and bring the
engine RPM to maximum.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 261
HOME PRINT

Pressure Settings
6. Read the pressure on the accumulator circuit gauge 11. Read the pressure on the accumulator gauge. It
located below the rear control panel. Pressure should read 200 bar (2900 PSI).
should read 300 bar (4350 PSI). If no adjustment is 12. If additional adjustment is needed, you must stop
needed, skip to Step 8. the truck engine each time you approach the accu-
7. If additional pressure adjustment is needed, locate mulator circuit hydraulic pump (Figure 83). Adjust
the accumulator manifold pressure relief valve the accumulator pump pressure regulator screw in
(Figure 85). Loosen the jam nut, and turn the screw to increase pressure or out to decrease pressure.
in to increase pressure or out to decrease pressure. Lock the jam nut when pressure is correct (200
Tighten the jam nut when pressure is at 300 bar. bar).

45s3blck.epsL
Set the outrigger pressure
With a seven place hand valve, the boom/outrigger
selector valve is inside the boom control block. This
valve is activated when the outrigger enable push
button is pushed. There is not a separate relief for this
circuit and, therefore, nothing that must be set.
The outrigger circuit is set to a maximum of 280-bar
(4060 PSI) by the relief valve located on the passenger
side outrigger hand valve assembly (Figure 102). The
valve routes the oil to the two outrigger hand valve
banks, one on each side of the unit. A relief valve
inside the passenger side bank limits the entire
Relief Valve
outrigger circuit to 280-bar.

Figure 33 Lower
Accumulator manifold pressure relief Turn body of valve
Higher
valve to adjust.

8. You will need an assistant for this step. With the


280 bar
engine still running, adjust the relief valve on the Relief Valve
E-Stop manifold. Back out the adjustment screw
until pressure reads 260 bar (3771 PSI) on the
gauge connected to the E-Stop manifold.

WARNING
Entanglement hazard. Stop drive shafts
before adjusting the accumulator pump
Figure 34
pressure regulator.
W010.eps

Outrigger hand valve

9. After the truck engine is stopped, back out the


accumulator circuit hydraulic pump pressure regu-
lator two-and-a-half-turns. This restores the pres-
sure regulator to its original setting (Figure 83).
10. Clear all personnel from the drive line area, start
the truck, and rev the engine RPM to maximum.
revDate
262 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
If your unit has a load-sensing proportional system, it
will have different pressure adjustments than if it is
WARNING equipped with a black and white boom system. The
following instructions are for load-sensing proportional
Tipping hazard. Never set outrigger systems. If you have a unit equipped with a black and
pressures with the boom unfolded. white boom system, contact Schwing Service
Pressure setting procedure requires
Department for the correct instruction pages.
retraction of an outrigger jacking
In a black and white boom system, the hydraulic pump

W026.eps
cylinder.
puts out an unchanging amount of oil, and speed
control is done by restricting the oil to certain functions
1. Connect the whip hose of a 0400 or 0600 bar to with orifices. In a load-sensing system, the pump puts
the gauge port on the right side of the outrigger out more or less oil to respond to the needs of the
hand valve. system. Generally, the pump puts out enough oil to
2. If it is not already done, start the truck engine and maintain a 20 bar higher pressure at the pump than
set the transmission and PTO as you would for a what the cylinders actually require. This 20 bar is
pumping job. called delta P (P). Additionally, we set the hydraulic
3. Set the engine RPM to maximum. pump so that it always puts out a small amount of oil,
even if no oil is needed for the system. This oil is used
4. Push the outrigger enable pushbutton located next
to ensure that you have control when you need it. The
to the outrigger hand valve (passenger side). Hold
setting to maintain this minimum amount of oil is
one of the outrigger hand valve levers in the
called Q-min (pronounced cue min). To set the boom
jacking-retract position. The oil coming from the
or outrigger hydraulic pressures on a load-sensing
pump has nowhere to go but over the outrigger
system, begin by setting Q-min and P.
relief valve.
The general locations of the components used to set
NOTE! boom hydraulic pressures is shown in Figure 19.
You cannot use the extend position for this
adjustment because extend has NOTE!
nonadjustable secondary relief functions Do not adjust P or Q-min if your boom is
built into the valve. running as you like it. The pressure setting
procedure uses a standard starting point
5. Turn the outside body of the relief valve that is
and must be fine tuned from there. It was
located at the back of the passenger side outrigger
fine tuned at the factory and should not be
hand valve (Figure 102). Turn in to raise pressure
adjusted unless absolutely necessary.
or turn out to lower pressure.
6. When the pressure on the gauge connected to the
outrigger hand valve is 280-bar, release the enable WARNING
push button and the outrigger hand valve.
7. Remove the whip hose and gauge from the Entanglement hazard. Stop drive shafts
outrigger handvalve, and replace the cap on the before adjusting Q-min.
W009.eps

gauge port.
Pressure reducing valve Each time the Q-min screw must be
This valve is preset at the factory. Contact Schwing adjusted, the engine must be stopped, or at
Americas Service Department at (651) 429-0999 for least the transmission must be taken out of
information on checking or setting this valve. gear so that the drivelines stop turning.
Electric stroke limiter
The stroke limiter valve is preset at the factory. Contact
Schwing Americas Service Department at (651) 429-
0999 for information on checking or setting this valve.
Load-sensing boom pressures (7 place propor-
tional circuit)
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 263
HOME PRINT

Pressure Settings

Boom Hand Valves P Regulator E-Stop Manifold Q-min Adjust Screw

39Xtop.eps

Figure 35
Location of components used to
check or set boom pressures

0-400 bar
gauge port
0-60 bar
gauge port

boom control
block relief valve
s
.ep
rdv
a pitp
36

15 bar pretension
adjustment screw

Figure 36
Boom hand valves

revDate
264 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Check or set P bar, you must fine tune the adjustment.
To check or set P follow these steps: Remove the gauge, and adjust P until the boom is
1. Stop the truck engine, and place a Do Not responsive and smooth. When done, the gauge
Operate sign on the truck windshield. (reinstalled) must read between 14 and 25 bar. The
electronics in the control system can also affect how
2. Install a 0-40 or 0-60 bar gauge in the 0-400 bar
the boom operates, so if P adjustment does not seem
gauge port of the manual boom handvalves. Take
to help, reset to 20 bar and check the electrical settings.
care not to accidently install the gauge in the 0-60
Once electrical settings are verified, you could again
bar port (Figure 20).
refine the boom action with the P adjustment.
3. To be sure that the pump is putting out only enough CAUTION! Do not operate any functions while
oil needed to maintain P, we need to change the setting P.
setting of the Q-min screw. Q-min is adjusted by a
screw on the boom hydraulic pump (Figure 21).
Unscrew the Q-min screw three full turns. Check
that all personnel are clear of the truck, then restart

deltaPvlv.eps
the engine, engage the pumps, and leave the engine
at an idle. CAUTION! If you activate any boom
or outrigger functions, you will damage the 0 - P adjust
T
40 bar gauge. Make sure that all emergency stop screw
switches are in the up (not activated) position.
Pressure can be read on the 0 - 40 bar gauge that Figure 38
you installed. Pressure should read 20 bar. If no P regulator valve
adjustment is needed, simply reset the Q-min
screw as described in the Check or set Q-min steps.
Check or set Q-min
If adjustment is needed, continue to Step 4.
You must check Q-min pressure when the engine is at
Q-min the maximum specified RPM, but you must adjust it
adjustment screw with the engine stopped. To check or set the Q-min
follow these steps:
1. If you unscrewed the Q-min screw as the first step
of P adjustment, begin by returning the screw to
its original position (Figure 21).
2. Remove the 0 - 40 bar gauge from the 0 - 400 bar
gauge port, and install the 0 - 600 bar gauge in its
Q-minscrew.eps
place (Figure 20).
Q-max 3. Clear all personnel away from the drive lines, start
the truck engine, engage the pumps, and bring
Figure 37 engine RPM to max. All boom functions must be
Q-min adjust screw in neutral, and all emergency stop buttons must
be up (not engaged).
4. Read the pressure on the 0 - 600 gauge. Pressure
4. Delta P is adjusted by the P screw on the P should be at 40 - 45 bar. If no adjustment is needed,
regulator (Figure 22). Loosen the jam nut, and stop the drive lines from turning, be sure the jam
adjust the screw inward to increase pressure or nut on the Q-min screw is tight, then continue to
outward to decrease pressure until it is set at 20 bar Set boom pressures to check the rest of the boom
(1). Contact Schwing Americas Service pressures.
Department if you are unable to adjust the pressure 5. If adjustment is needed, turn the Q-min screw in to
to specification. raise the pressure (Figure 21). Turn it out to lower
NOTE! the pressure. Be sure that you stop the drive shafts
If the boom does not operate smoothly at 20 from turning each time before making the

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 265
HOME PRINT

Pressure Settings
adjustment. When pressure is correct, tighten the screw on the P regulator valve), set at 300 bar
jam nut on the adjustment screw before continuing (4350 PSI).
with the other procedures. 3. The redundant relief valve located in the
emergency stop manifold, set at 330 bar (4786
Set boom pressures PSI).
(load sensing proportional booms) NOTE!
Now that P and Q-min are set, you can check or set The boom control block relief valve is
the boom valve pressures. There are three pressure nonadjustable. If pressure is not maintained
settings on the boom circuit (Figure 39 and Figure 23). within the specification limits, the valve
1. The boom control block relief valve, set at 350 bar must be replaced.
(5075 PSI).
2. Pressure regulator (the high-pressure adjustment

e-stop/right.epsL
E-Stop manifold
redundant relief valve

ps
rt.e
ca
no

E-Stop manifold
redundant relief
valve

Figure 39
E-Stop manifold (current production left - original production right

revDate
266 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
now. If it isnt, raise the setting of the other
pressure devices until the hiss originates at the
Apitech control block relief valve. Read the
pressure on the gauge connected to the 0-400 bar
gauge port on the boom hand valve block. It should
read 350 bar. If pressure is correct, proceed to Step
0-400 bar
5.
gauge port
0-60 bar NOTE!
gauge port Although the pressure specification for the
Apitech control block relief valve is 350 bar,
boom control
block relief valve you may continue to use the concrete pump
.eps
as long as the relief valve cartridge
Va
om
36
Bo
maintains at least 330 bar. If pressure on the
15 bar pretension relief valve is below 290 bar, you should not
adjustment screw
use the concrete pump until the relief valve
is replaced. If you need to replace the relief
valve, repeat this entire procedure before
P Regulator Valve
using the concrete pump again.
(high pressure
adjustment screw) 5. Screw out the E-Stop manifold redundant relief
valve adjustment screw one-and-a-half turns.
Pressure out any boom cylinder except #1 down,
and read the gauge. Pressure should read 330 bar.
If it does not, turn the screw in to raise pressure or
out to lower pressure until it is set at 330 bar. If the
deltaPvlv.eps

location of this valve causes you to be near the


drive lines, be sure to stop them from turning
T before accessing the valve.
6. You will need a helper for this step. While
pressuring out any boom cylinder (except #1
Figure 40
down) have your helper adjust the high pressure
Boom hydraulic pressure adjustment
screw of the P regulator out (lowering the
components
pressure) until the gauge reads 300 bar. Release the
To check the setting of the valve with the highest pressurized function, and lock the jam nut. The
pressure, you must first raise the pressure of the lower boom pressures are now set. If you did not get the
two: readings specified after following the instructions,
1. Loosen the jam nut of the high pressure adjustment contact Schwing Americas Service Department at
screw of the P regulator. Turn the screw in two- (651) 429-0999 for advice on how to continue.
and-a-half turns. This will raise the pressure on the
P regulator above 350 bar. Boom holding valves
2. Loosen the jam nut of the adjustment screw on the The boom holding valves are adjusted at the factory.
E-stop manifold redundant relief valve. Turn the Never adjust a holding valve while it is on the boom. If
screw in one-and-a-half turns. This will raise the you suspect that a holding valve is not functioning
pressure setting of the relief valve to above 350 bar. properly contact Schwing Americas Service
Department at (651) 429-0999.
3. Pressure out any boom cylinder except #1 down by
pushing or pulling the control handle. To pressure
out a cylinder, retract a fully retracted cylinder or
extend a fully extended cylinder. The oil is forced
over the relief valve.
4. The tell tale hiss of an open relief valve should be
coming from the Apitech control block relief valve
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 267
HOME PRINT

Pressure Settings

0-400 bar
gauge port
0-60 bar
gauge port

boom control
block relief valve
s
ep
dv.
itpr
ap
36

15 bar pretension
adjustment screw

Figure 41
Pretension adjustment screw
and gauge port

Set 15 bar pretension valve is inside the boom control block. There is not
To check or set pretension, follow these steps: a separate relief valve for this circuit and,
therefore, nothing that must be set.
1. Stop the truck engine. Plug the 0 - 40 bar gauge
into the 0-60 bar gauge port of the Apitech hand Set water pump pressure
valve (Figure 24).
With a seven place hand valve, the water pump
2. Start the truck engine, but leave it at an idle.
hydraulic control is inside the boom control block.
(Pretension adjustment is made at an idle to
There is not a separate relief valve for this circuit and,
establish the minimum pressure setting. As RPM is
therefore nothing that must be set.
increased, pressure will rise. Read the pressure on
the gauge. If it reads 15 bar 1 bar, the pressure is
Set the agitator pressure
set correctly.
The agitator circuit has a maximum pressure of 200 bar
NOTE! (2900 PSI), limited by the relief valve located on the
Damage to the 0 - 40 bar gauge is possible if back of the agitator hand valve (Figure 117). The gauge
RPM is raised while the gauge is connected. port for checking or setting the agitator pressure is
3. If adjustment is needed, loosen the jam nut on the located on top of the agitator hand valve.
pretension adjustment screw (Figure 24). Turn the
screw in to raise pressure and out to lower
pressure. When the pressure is correct, retighten
the jam nut.
4. Stop the engine, and remove the 0 - 40 bar gauge.
With a seven place hand valve, the #1 down brake -
revDate
268 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

39Xcont3.eps

52qrttrn.epsL

Closed

Shown in the
open position

Figure 43
Agitator shutoff valve
Agitator Hand Valve
4. Be sure that one of the locking plugs and capnuts
39Xcontr.eps
are tightened on the straight fitting and that the
dead plugs are securely tightened to the hose and
the open motor fitting.
5. Locate the relief valve on the back of the agitator
hand valve.
6. Be sure that all personnel are clear, and restart the
AGITATOR CONCRETE PUMP
SECTION 1 SECTION 2 SECTION 3 SECTION 4 SLEWING AIR / WATER BOOM / OUTRIG. engine.
7. Activate the agitator hand valve by pushing or
DANGER WARNING
Do not operate this
Electrocution hazard. machine without
Stay back from high training. Understand
voltage wires at least SAFETY
the warnings in safety
17 feet (5 meters). MANUAL
manuals and on decals.

pulling the handle. This will send the oil against


the high pressure plug. The oil will have nowhere
to go, so it will return to the tank over the relief
valve in the agitator hand valve. The pressure at
which it relieves can be seen on the gauge. It
Figure 42 should read 200-bar.
Agitator hand valve (current production top 8. If adjustment is needed, turn the outside body of
and original production bottom) the relief valve that is located at the back of the
agitator hand valve. Turn in to raise pressure or
1. Stop the unit, and put the key in your pocket. turn out to lower pressure (Figure 44).
2. Connect the whip hose of 0-400 or a 0600-bar
gauge to the gauge port on the agitator hand valve
(Figure 44).
3. If your unit is equipped with an agitator shutoff
valve, close it (Figure 20). Skip to Step 5.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 269
HOME PRINT

Pressure Settings

Agitator Relief Valve Turn body of valve


Gauge port to adjust.
Higher

Lower

ps
2.e
itrlf
ag

Figure 44
Agitator relief valve

9. When the pressure is set at 200-bar, stop the engine


and remove the key. Open the shutoff valve or
remove the dead plugs and store them in a clean
area or in a plastic bag or something similar in
order to keep dirt from entering the fittings.
Reattach the hose to the agitator motor fitting and
tighten securely. (Torque is correct if you make one
complete revolution after feeling initial resistance
increase.)
3. Remove the whip hose and pressure gauge.
Replace the gauge port cover.

revDate
270 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
S 42SX 2. Activate the agitator. With the valve closed, the
agitator will not be able to turn, and the oil will be
forced over the relief valve. At an idle (about 600
Setting Pressures
RPM), 4.5 horsepower is being converted to heat.
The following pages provide the proper techniques for
3. When the oil temperature gauge shows 50C, open
checking and setting hydraulic pressures of each
the shutoff valve.
system included on your unit.

Check all hydraulic pressures


Changes in pressures can indicate trouble in one or

  
 agitoff2.eps

more components. The specifications for each circuit 


     
are shown on the hydraulic schematics found in the
Appendix of this manual. The hydraulic schematics are
the only documents in this manual that have been
updated specifically for your unit, by the serial number,
so in each of the following procedures you will be told 
to refer to the schematic for the pressure required.
If you wish to order a CD ROM which explains the Figure 55
pressure setting procedure for a specific model (all Agitator shutoff valve
pumpkits), call SAI Spare Parts Department at (800)
328 - 9635 and request the CD using the following part
numbers:
61/58 meter. . . . . . . . . . . . . . . . . . . . . . . 30365860
52 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30354732
45/47 meter. . . . . . . . . . . . . . . . . . . . . . . 30356770
42 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30355485
39 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30365861
34 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30356772
32 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30355486
31 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30365862

Preheat the hydraulic oil


Pressure settings must be made with the oil at normal
operating temperatures (40 60 C). In the past we
could pressure out a function in the boom or outrigger
system to create heat, but load sensing systems no
longer allow maximum oil flow to be forced over relief.
Because of this the agitator circuit must be used to heat
the hydraulic oil.
To preheat the hydraulic oil:
1. Locate the agitator shutoff valve (Figure 55) and
close it.
NOTE!
If your unit does not have a shutoff valve,
order one from the Schwing Spare Parts
Department using part number 10004680
(valve), and number 30303432 (tube).
Contact the Service Department for
installation instructions.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 271
HOME PRINT

Pressure Settings
Setting pressures on Hi-flo -6 pumpkits 4. If you have not already closed the soft switch
To set the pressure of the main relief valve on Hi-flo shutoff valve and the concrete pump shutoff valve
pumpkits, you must first disable the soft switch circuit. (Figure 56) do so at this time.
Simply locate the ball cock for the soft switch circuit 5. At the rear panel, select local control with the
(Figure 56) and close it by rotating the handle 90 local/remote switch and turn the electric stroke
degrees. limiter knob clockwise to maximum strokes per
minute.
The quarter turn shutoff valve for the concrete pump
(Figure 56) will also need to be closed during this 6. The main system control block pressure must be
procedure. set first to properly set the pressure cutoff on both
pumps. Begin by backing off the jam nut of the
NOTE! main relief cartridge (Figure 58) with a 9/16 inch
Main system adjustments are preset at the wrench.
factory. The following procedure begins
with adjustment of the main relief cartridge 7. Using a 5/32 inch allen wrench, turn the
and pressure cutoff. If proper pressures can adjustment screw out (counterclockwise) until you
not be obtained through these steps, contact can feel no spring tension on the adjustment screw.
the Schwing Service Department for specific
instructions on the adjustment of flow, 8. Now, turn the screw back in (clockwise) two or
horsepower, beginning of stroke regulation, three full turns to give you a proper starting point
and Q-min. and tighten the jam nut.
Pressure setting procedure: 9. Stop the truck engine and put the key in your
pocket. Adjust the pressure cutoff screw (Figure
Soft switch 57) on each pump, by backing off the jam nut with
shutoff valve
a 13mm wrench. Using a 4mm allen wrench, turn
the adjustment screw in (clockwise) one full turn
and tighten the jam nut. Restart the truck engine.
10. Adjust the engine RPM to maximum specification.
Concrete pump
(See decal in truck cab)
hif
shutoff valve lob
rn
.e
ps 11. Pressure out the system by activating the concrete
pump forward switch on the rear panel. Using the
Figure 56 rear panel controls will allow you to read the
Concrete pump and Soft switch concrete pump main system pressure gauge, near
shutoff valves the e-stop manifold, from a safe distance.
NOTE!
1. Be sure that the waterbox covers and guards are in
Because you turned out the pressure relief
place any time you will be working in the area cartridge in step 7, the system pressure
around the main control block. should read low at this time. If it does not
2. Wear safety glasses when working around a and the gauge spikes to 320 bar or more,
concrete pump. disengage the pump immediately. Turn the
relief cartridge out (counterclockwise)
NOTE! more. For safety, it is important to adjust
It is vital that each adjustment screw be the pressure up from below the specified
properly identified prior to making any target pressure rather than down from a
adjustment. All screw adjustments for the pressure which exceeds the target. Continue
system relief must be made with the this procedure until the main system
pumpkit in the neutral position and pressure gauge reads lower than the
adjustments for pressure cutoff must be specified target.
made with the engine shut off. 12. To increase the pressure put the pump in the
3. Start the truck engine, and put the PTO in gear just neutral position and adjust the relief cartridge by
as you would to pump a job. turning it in (clockwise). When increasing the
pressure, the adjustments should be made in
quarter turn increments. If you make adjustments
to increase the pressure but the pressure does not
revDate
272 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
come up, you are probably reading the pressure 18. When you have achieved the same pressure on the
cutoff of the pumps, if so proceed to the next step M1 port gauges, you can begin to adjust the
otherwise skip to step 15.Turn the relief cartridge pressure cutoff screws in or out simultaneously
adjustment screw back out (counterclockwise) until you achieve the desired pressure setting of
until you can no longer see a pressure drop and 350 bar (again, confirm the pressure specification
tighten the jam nut. with the hydraulic schematic).
13. Stop the truck engine, put the key in your pocket. After pressure cutoff is set, return the pump to neutral,
14. Go to the pressure cutoff screw on both hydraulic bring engine RPM to idle, open the soft switch quarter
pumps (Figure 57) and back off the jam nut with a turn valve, and either proceed to other pressure settings
13mm wrench. Turn the adjustment screws in with or take the transmission and PTO out of gear and shut
a 4mm allen wrench one or two more turns, restart off the truck.
the engine and check the pressure again. Repeat
this procedure until the main system relief can be
set to the target pressure.
15. When the proper main relief pressure is achieved,
1 STROKE REGULATION 2 PRESSURE CUT OFF
pressure cutoff can be set. Shut off the engine, put 3 HORSE POWER 4 Q-MIN
the key in your pocket and install 0-600 bar gauges 2
2
with whip hoses to the M1 gauge ports on the 1
3
1 3
bottom of the two hydraulic pumps (Figure 57). 4
4
You must be able to read both gauges
simultaneously to ensure that one pump is not
M1 GAUGE PORT
more dominant than the other. (BOTTOM OF EACH PUMP)
130ajst.eps

NOTE!
The gauges in the M1 ports will read Figure 57
considerably less than the cutoff pressure of A11VO adjustment screws for Hi-flo 6
the pump. On a -6 (190/130 pump units 190/130
combination) the 190 will usually read 85 to
90 bar while the 130 reads about 110 bar.
They could read the same however, at
approximately 110 bar, but the 190 must
never read higher than the 130. The actual
cutoff pressure will be read on the concrete
pump main system pressure gauge near the
e-stop manifold.
16. Activate concrete pump forward to pressure out the
pump and read the pressure on the two gauges in
the M1 ports.
17. Always stop the truck engine and put the key in
your pocket before making any adjustment on the
hydraulic pump. If the cutoff on one pump is set
higher than the other, that pump will be more
dominant. The pressure gauge in the M1 port of the
dominant pump will however, read lower than the
other. To equalize the two pumps you must either
adjust the cutoff screw in (clockwise) to increase
the pressure of the pump showing the higher
reading or adjust the cutoff screw of the dominant
pump showing the lower reading out
(counterclockwise) to reduce the pressure. These
adjustments must be made until the two gauges in
the M1 ports are reading approximately the same.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 273
HOME PRINT

Pressure Settings

Closed Open
soft switch
relief valve

openclsd.eps
Main relief valve
5/32" Allen head
9/16" jam nut
Figure 58
Soft switch components

Setting the soft switch relief pressure Load-sensing boom hydraulic controls
First, open the soft switch quarter turn valve (Figure This unit is equipped with a load-sensing, proportional
58, right) that you closed in the previous procedure. boom hydraulic system. In a black-and-white system,
The rest of the unit should still be set up as if you were the hydraulic pump puts out an unchanging amount of
going to check the main relief valve pressure (concrete oil, and speed control is done by restricting the oil to
pump shutoff valve still closed). certain functions with orifices. In a load-sensing
When you put the pump in forward now, the main system, the pump puts out more or less oil to respond
concrete pump pressure gauge should read the pressure to the needs of the system. Generally, the pump puts
shown on the schematic for soft switch. If adjustment out enough oil to maintain 20 bar higher pressure at the
is needed, loosen the soft switch relief valve jam nut pump than the cylinders actually require. This 20 bar is
(Figure 58, right) with a 9/16 open end wrench, and use called delta P (P). Additionally, we set the hydraulic
a 5/32 allen wrench to adjust the pressure. Turn the pump so that it always puts out a small amount of oil,
adjustment screw in (clockwise) to raise the pressure or even if no oil is needed for the system. This oil is used
out (counter clockwise) to lower the pressure. When to ensure that you have control when you need it. The
you attain the required pressure, tighten the jam nut setting to maintain this minimum amount of oil is
while holding the allen wrench to keep the pressure called Q-min (pronounced cue min). To set the boom
from rising. Be sure to open the concrete pump shutoff or outrigger hydraulic pressures on a load-sensing
valve on the side of the brain (Figure 58, left) when system, begin by setting P and Q-min.
you are finished. The unit will not stroke with this
valve closed.

Setting boom circuit pressures WARNING


NOTE! Entanglement hazard. Stop drive shafts
Any time you set pressures for any circuit before adjusting Delta P on A11VO pump.
W020.eps

on any unit, the hydraulic oil should be at


normal operating temperature (4060 C).
Instructions on heating the hydraulic oil are
found in the first step of this checking
hydraulic pressures segment.
Read all of the instructions before beginning any
pressure settings. You will need an assistant for parts of
the procedure. You and any assistants should wear eye
protection when setting pressures.

revDate
274 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

0-600 bar
gauge port
ps
0.e
60
top
es

pretension
only Boom pressure
33-35 bar relief cartridge

0-600 bar
gauge port
45bmcnbl.epsL

Figure 59
(Left) The 060 bar gauge port is located at the top of the boom control block, and the 0-600
bar port is at the bottom. (Right) A 0600 bar gauge port is located on the E-stop manifold.

Setting delta P pressure bar. After achieving proper P, tighten the jam nut
Do not adjust P or Q-min if your boom is running as and bring the engine RPM up. If the pressure
you like it. The pressure setting procedure uses a gauge continues to read 20 bar, you are reading the
standard starting point and must be fine tuned from that true P pressure and may move on to setting the Q-
point. The pressure was fine tuned at the factory and min. If the pressure rises with the RPM, however,
should not be adjusted unless absolutely necessary. you may be reading the Q-min pressure instead of
true P. If that happens, stop the engine, put the
1. Start by turning off the engine and putting the key key in your pocket, and place a Do Not Operate
in your pocket; then place a Do Not Operate sign sign on the windshield of the truck before
on the windshield of the truck. proceeding.
2. Install a 0-100 bar gauge in the high pressure test
port at the bottom of the boom control block
(Figure 16).
pressreg.eps

Regulator pressure
NOTE! adjustment
Do not activate any boom/outrigger
T
functions or release any e-stops with a low Adjustment for P pressure
pressure gauge attached to a high pressure
port. Delta-P

3. Delta P is adjusted on the pressure regulator


(Figure 43, top) if your unit has an A7VO pump or
(Figure 43, bottom) if your unit has an A11VO
boom pump. When all personnel are clear of the
truck, restart the engine, engage the pumps, and
leave the engine at an idle. P pressure should read smdeltap.eps

17 bar, which is the standard starting point.


Figure 60
4. There are two adjustment screws on the pressure
Pressure regulator for A7VO boom pumps
regulator (Figure 43, top) for A7VO pumps. The
(top) and A11VO pumps (bottom)
smaller screw is used in this procedure to adjust
P. On the A11VO pumps there is only one P
screw (Figure 43, bottom).
5. If adjustment is required, loosen the jam nut, and
adjust the screw inward to increase pressure or
outward to decrease pressure until it is set at 20
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 275
HOME PRINT

Pressure Settings

Q-min
Delta-P Pressure cut-off
adjustment screw

A7VX section min.top.eps

hifloreg.eps

Q max Q-min Q-max (bottom of pump)

Figure 61
Location of Q-min screw on the A7VO (left) and all adjustment screws of the A11VO (right)

6. Unscrew the Q-min screw (Figure 61) three full


turns. This step will help ensure that the pump
produces only the amount of flow needed to
maintain P pressure. Once all personnel are clear
of the truck, restart the engine, engage the pumps,
and recheck at an idle. Pressure should now read
17 bar. If it does not, go back and adjust P until it
does.
pressreg.eps

Regulator pressure
If pressure cannot be set correctly, there is a problem adjustment
either with the orifices in the base of the regulator or
with the regulator itself. Contact the Schwing Service T
Adjustment for P pressure
Department to determine how to continue.
If the boom does not run smoothly at 17 bar, you
must fine tune the adjustment. Remove the gauge, and Figure 62
turn the P adjustment screw until the boom is Boom pressure regulator for units
responsive and smooth. After adjusting, the gauge with A7VO pumps
(reinstalled) must read between 14-25 bar. The
electronics in the control system can also affect how
the boom operates, so if P adjustment does not seem
to help, reset to 17 bar and check the electrical settings.
Once electrical settings are verified, you could again
try to refine the boom action with the P adjustment.
NOTE!
The pressure regulator (Figure 62) is
usually mounted on the inside of the
subframe, near the cab end of the
differential cylinders.

revDate
276 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Setting Q-min 4. Identify the main boom pressure relief cartridge on
Check Q-min when the engine is at maximum specified the boom control block (Figure 64) and loosen the
RPM. You must not adjust Q-min with the drive jam nut. Then unscrew the adjustment two full
shafts turning! Each time the Q-min screw must be turns.
adjusted, the engine must be stopped or, at least, the 5. Take engine RPM to full throttle and activate boom
transmission must be taken out of gear so that the retract for any boom section except #1.
drivelines stop turning. 6. Now adjust pressure, which is read at the main
1. If you unscrewed the Q-min screw as part of the P boom gauge port, to the setting found on the
adjustment, begin by returning the screw to its schematic by turning the boom pressure relief
original position. cartridge in, or clockwise, using no more than 1/4
2. All boom functions must be in neutral, and all turn increments.
emergency stop buttons should be up (not 7. When desired pressure is achieved, lock down the
engaged). Clear away all personnel, start the truck jam nut.
engine, engage the pumps and bring engine RPM
to max. Read the pressure at the 0600 bar main
boom gauge port (Figure 63) with a 0-100 bar
gauge. Pressure should be at 30 bar. If no
adjustment is needed, be sure the jam nut on the 0-600 bar
Q-min screw is tight; then continue to set the rest gauge port
of the boom and outrigger pressures. If adjustment ps
0.e
60
is needed, continue to the next step. es
top

3. Turn the Q-min screw (Figure 61) in to raise the


pressure. Turn it out to lower the pressure. Be sure
that you stop the drive shafts from turning each
Boom pressure
time before making the adjustment. When pressure
relief cartridge
is correct, tighten the jam nut on the adjustment
screw before continuing with the other procedures;
then recheck P to make sure that it hasnt
changed during the Q-min adjustment.
NOTE!
If you dont have a 0-100 bar gauge you can Figure 63
order one from Schwing Spare Parts
Department at (800) 328-9635, part # Boom pressure relief cartridge
10004659.
8. The next step is to return to the e-stop manifold
Setting boom pressures boom pressure relief cartridge (Figure 63) and
Now that P and Q-min are set, you can remove the 0- back off the jam nut (30 mm). Turn the relief
100 bar pressure gauge and proceed to check and cartridge (32mm) out, or counter clockwise, until
adjust the main boom pressures. you achieve the pressure shown on the schematic,
for the boom pressure relief cartridge. When the
1. Loosen jam nut of the boom pressure relief
proper pressure is achieved, lock the jam nut.
cartridge (Figure 63) with a 30mm open end
wrench.
2. Turn the adjustment cartridge clockwise all the
way in with a 32mm wrench.
3. Loosen the jam nut on the pressure relief screw of
the regulator (Figure 62) or the pressure cut-off
(Figure 61), and tighten the screw all the way
down.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 277
HOME PRINT

Pressure Settings
Setting outrigger pressure
mainrlf.eps

After the boom circuit is properly set, you can set the
outrigger pressure. Find the relief cartridge
located on the front of the passenger side outrigger
control valve (Figure 48).

#1 down side
relief cartridge

Main boom pressure


relief cartridge

1. Attach 0-600 bar whip gauge to the gauge port


(Figure 48) below the outrigger valve bank.
2. Push the outrigger enable button.
Figure 64 3. Activate an outrigger jacking cylinder to retract.
Main boom pressure adjustment and By retracting a fully retracted cylinder, the oil
piston side relief coming from the pump has nowhere to go but over
the relief valve. You cannot use an extension or
slewing cylinder because they have secondary
relief functions (nonadjustable) built into the valve.
While holding the handle to retract, read the
9. The next pressure setting is the regulator pressure.
pressure gauge.
Locate the regulator adjustment screw (Figure 61)
or pressure cut-off screw (Figure 62). Back off the 4. The pressure should read the bar value shown on
jam nut, and turn the screw counterclockwise until the hydraulic schematic. Adjust by loosening the
you achieve the pressure shown on the schematic; jam nut with a 9/16 open end wrench and turning
then lock the jam nut. the cartridge (Figure 48) in or out with 5/32 allen
wrench. When the proper pressure is achieved, let
10. The final boom pressure setting is the #1 boom rod
go of the handle and release the outrigger enable
side relief setting. This relief cartridge is in close
button.
proximity to the main boom relief (Figure 64), so
be sure to locate the proper adjustment. This testport.eps

procedure should be performed with the outriggers


extended and the boom unfolded over the cab.
Disconnect all gauges from gauge ports prior to REAR SLEW REAR JACKING FRONT JACKING FRONT EXTEND

operating any boom or outrigger functions.


30354359

Bring section #1 all the way down until the


cylinder bottoms out. Install a 0-600 bar gauge in
the main boom gauge port of the e-stop manifold
Relief
(Figure 63), and activate boom #1 down. The Cartridge
pressure should read the setting shown on the Gauge Port
schematic. If adjustment is required, back off the
jam nut and turn the relief cartridge in or out as
required until the desired pressure is achieved; then
lock down the jam nut. Figure 65
Outrigger valve bank relief cartridge
and gauge port

revDate
278 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

CONCRETE PUMP
FORWARD/REVERSE

AGITATOR

Relief valve
Gauge port

Figure 66
Agitator component location

Setting the agitator pressure


The agitator circuit has a maximum pressure shown on

  
 agitoff2.eps

the hydraulic schematic, which is limited by the relief


cartridge (Figure 50) in the agitator hand valve. The 
     
relief cartridge is located on the back side of the
agitator manual control handle (Figure 50). The
cartridge is adjustable with just an 19mm open end
wrench.
1. Plug the 0600 bar whip gauge into the gauge port
(Figure 50) for checking or setting agitator 
pressure.
2. Locate the agitator shutoff (Figure 67) valve and
Figure 67
close it. If your unit does not have a shutoff valve,
Agitator shutoff valve
order one from the Schwing Spare Parts
Department using part numbers 10004680 (valve)
and 30303432 (tube). Contact the Service
Department for installation instructions, or if you Plugs Straight Fitting
cant wait for a shutoff valve, you will need to
remove one of the hoses from the agitator motor Figure 68
and plug the hose and open fitting with approved Approved hydraulic
hydraulic dead plugs (Figure 68). dead plugs capplug.eps

NOTE!
Do not jam the paddles to force the oil over
relief by stopping the movement of the Cap Nuts
agitator.
3. Increase the throttle to any speed above idle.
Activate the agitator valve handle in either forward
or reverse, and read the gauge. If it does not read
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 279
HOME PRINT

Pressure Settings
the specified pressure, adjustment is required. Turn January 1, 2000, it will have an emergency stop
the entire valve body (Figure 50) in to increase manifold similar to the illustration shown in the bottom
pressure or out to decrease pressure. of Figure 52, which no longer has a redundant relief
4. When the pressure is set, deactivate the agitator by cartridge, and you must skip steps 3. and 7. in the
placing the manual control handle in the neutral following procedure.
position. To check or adjust the hydraulic pressure in the
5. Remove the whip gauge. accumulator circuit:
6. Reopen the shutoff valve or remove the dead plugs 1. Stop the truck, put the key in your pocket, and
and reconnect the capped hydraulic line. place a Do Not Operate sign on the windshield.
2. Loosen the jam nut on the pressure regulator of the
Setting accumulator circuit pressure accumulator hydraulic pump (Figure 51). Turn the
screw in two-and-one-half turns. This will raise the
regulator pressure above 300 bar.
3. Loosen the jam nut (Figure 52) on the accumulator
redundant relief cartridge located on the
emergency stop manifold. Turn the screw in two
000289a.eps
turns. This will raise the relief setting above 300
bar.
Accumulator pump
pressure regulator accurlf2.eps

Accumulator redunant
relief cartridge

Figure 69
Accumulator pump pressure regulator for Figure 70
A7VO (above) and for A11VO (below) Accumulator redundant relief cartridge
(above) is only present on early production
Boom Pump models. New e-stop (below) has no redundant
relief cartridge.

Accumulator Pump
Pressure Regulator

Accumulator Pump 000446a.eps

4. Clear all personnel away from the drive lines, start


You will need an assistant for parts of this procedure.
the truck engine, engage the pumps, and bring the
There are three relief settings for the accumulator
engine RPM to maximum.
circuit if your unit is equipped with an accumulator
redundant relief cartridge in the emergency stop
manifold(Figure 52, top). If your pump was built after
revDate
280 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
5. Read the pressure on the accumulator circuit screw while the other person stands by the pressure
pressure gauge (Figure 53). The pressure should gauge to let him know when the pressure reads the
read the value shown on the hydraulic schematic. If value shown on the schematic for accumulator
no adjustment is needed, skip to step number 7. If redundant relief.
additional pressure adjustment is needed, continue
with step number 6.

@@@@@@@@



;;;;;;;;
QQQQQQQQ
@@@@@@@@


;;;;;;;;
QQQQQQQQ

45acumpr.epsL

@@@@@@@@


;;;;;;;;
QQQQQQQQ

@@@@@@@@


;;;;;;;;
QQQQQQQQ

;;;;;;;;
@@@@@@@@


QQQQQQQQ

@@@@@@@@


;;;;;;;;
QQQQQQQQ

;;;;;;;;
@@@@@@@@


QQQQQQQQ

;;;;;;;;
@@@@@@@@


QQQQQQQQ

8. After the truck engine is stopped, go back to the
accumulator circuit hydraulic pump pressure
Figure 71 regulator (Figure 51), and turn the screw back out
Accumulator circuit pressure gauge two-and-one-half turns. This restores it to its
original setting.
acumrlf.epsL
9. Clear all personnel from the drive line area, start
the truck, and bring the engine RPM up to
maximum.
10. Read the pressure on the accumulator gauge. It
should read the proper accumulator system
pressure.
11. If adjustment is needed, you must stop the truck
engine, or a least stop the drive lines from turning,
each and every time you approach the accumulator
circuit hydraulic pump. Turn the screw in to
increase the pressure or out to decrease pressure.
Lock the jam nut when the pressure is correct.
NOTE!
The accumulator circuit hydraulic pump
pressure regulator is referred to as the
pressure cut-off.

Figure 72
Accumulator manifold pressure
relief cartridge
6. Locate the accumulator manifold pressure relief
cartridge (Figure 54). Loosen the jam nut, and turn
the screw clockwise to increase the pressure or
counterclockwise to decrease the pressure. Tighten
the jam nut when the pressure reaches the value
required.
7. You will need an assistant for this step. With the
engine still running, one person must go to the
redundant relief valve on the emergency stop
manifold (Figure 52) and back out the adjustment
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 281
HOME PRINT

Pressure Settings

revDate
282 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
KVM 42M - Proportional pocket, remove the check plug from the check port. The
oil should be at the level of the bottom of the hole in
(Apitech) Single Circuit the case. If oil is needed, add it by removing the
Check the fluid level of the distribution gearcase breather and pouring the oil through the top of the fill
(Figure 10). Be sure the truck is on reasonably level port. This gearcase uses 90W gear lube.
ground. With the truck engine off and the key in your

Breather (fill port)

4194 gearcase scan.eps


Check port

Drain port

Figure 10
Fill, check, and drain ports
of Stiebel 4194 gearcase

Check the mounting hardware of the subframe, the oil 1. Place a 4-by-4 in front of the agitator paddle.
and water tanks, the delivery pipeline, the pumpkit, the 2. Turn on the agitator. The agitator will not be able
differential cylinders, the material cylinders, and the to turn, and the oil will be forced over the relief
driveline hardware. Check for bolt tightness, cracks, valve.
and other abnormalities.
At an idle (about 600 RPM), you are converting about
4.5 horsepower to heat, which is a good-sized heater.
Check hydraulic pressures
Shut off the concrete pump when the oil shows 40C
Check all hydraulic pressures. Changes in pressures on the temperature gauge of the operators panel.
can indicate trouble in one or more components.
Pressure settings must be made with the oil at normal Setting concrete pump pressure (single-
operating temperature (4060C). The specifications circuit units)
for all circuits are shown on the hydraulic schematics
in the appendix of this manual. Schwing single-circuit pumpkits are designed to be
operated at a maximum pressure of 300 bar (4350 PSI).
Preheat the hydraulic oil The pressure in the system is controlled by the main
relief valve on the forward end (toward the truck cab)
Pressure settings must be made with the oil at normal of the main control block (Figure 11).
operating temperatures (40 60C). Because the
system is load-sensing, the boom circuit cannot be used
to heat the hydraulic oil. The agitator circuit must be
used instead. To preheat the hydraulic oil using the
agitator circuit, follow these instructions:
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 283
HOME PRINT

Pressure Settings

Jam nut

Lower Raise Adjustment handle


pressure pressure

gray valve.eps L

Figure 11
Concrete pump circuit main relief valve

3. Start the truck engine, and put the PTO and


To check or set the main relief pressure:

1. When setting pressures, always wear safety


transmission into gear, just as you would to pump a
glasses.
job.
2. Be sure that the waterbox covers and guards are
4. Close the shutoff valve (also known as the
installed on the waterbox. Schwing does not
ballcock or quarter-turn valve)(Figures 12).
recommend using the remote control box when
setting the main relief pressure.

Shutoff valve

quarter turn.eps

Figure 12
Concrete pump shutoff valve

5. Put the main operators panel remote / local will retract. Oil will be forced over the main relief
switch into the local position. valve. This procedure is called high-pressuring the
6. Using the switch on the main operators panel, rev concrete pump.
the truck engine up to full RPM.
7. Put the operators panel forward / neutral /
reverse switch into the forward position. The
unit will stroke only once; then the rock cylinder

revDate
284 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Groove at 90 to ports
Closed

Groove lined up with ports


Open
Ball cock grooves.eps

Figure 13
Open/closed orientation of concrete pump shutoff valve

8. Read the pressure on the gauge. It should read 300 12. Put the concrete pump into the forward position
bar. Return the pump to neutral whether it needs again. The machine will not stroke this time, but it
adjustment or not. If no adjustment is needed, skip will high-pressure again. Read the pressure on the
to step (n). gauge. If more adjustment is needed, return the
9. Using a 13-mm spanner wrench, loosen the jam pump to neutral, then repeat steps (i) through (l)
nut on the relief valve adjusting screw (Figure 11). until the pressure is correct.
Note! If you cannot adjust the pressure up to
10. Turn the knob on the relief valve to adjust the
specification, you have a problem. In this case,
pressure. Screw the handle in to raise pressure, and
unscrew the adjustment handle several turns so that
out to lower pressure.
your pressure is not too high when you find the
11. Retighten the jam nut. Tightening the nut tends to problem. Contact Schwing Americas Service
raise the pressure setting. If the rise in pressure Department for advice on how to continue.
becomes a problem, hold the knob while tightening
13. Return the pump to the neutral position.
the jam nut.
14. Open the concrete pump shutoff valve (Figure 14).

Shutoff valve

quarter turn.eps

Figure 14
Concrete pump shutoff valve

15. Return the RPM of the truck to idle, take the truck, or go on to other pressure settings.
transmission and PTO out of gear, and shut off the
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 285
HOME PRINT

Pressure Settings
Setting boom circuit pressures oil, and speed is controlled by restricting the oil to
Note! Whenever you set pressures for any circuit on certain functions with orifices. In a load-sensing
any unit, the hydraulic oil should be at normal system, the pump puts out more or less oil to respond
operating temperature (4060C). Instructions on to the needs of the system. Generally, the pump puts
preheating the hydraulic oil for this procedure are in out enough oil to maintain 20 bar higher pressure at the
section on page 6-97. Read all of the instructions pump than what the cylinders actually require. This 20
before beginning any pressure settings. You will need bar is called delta P (P). Additionally, we set the
an assistant for parts of the procedure. You and any hydraulic pump so that it always puts out a small
assistants should wear eye protection when setting amount of oil, even if no oil is needed for the system.
pressures. This oil ensures that you have control when you need
it. The setting to maintain this minimum amount of oil
Load-sensing boom hydraulic controls is called Q-min (pronounced cue min). To set the
boom or outrigger hydraulic pressures on a load-
This unit is equipped with a load-sensing, proportional sensing system, begin by setting Q-min and P (Figure
boom hydraulic system. In a black-and-white system, 15).
the hydraulic pump puts out an unchanging amount of

Figure 20 Figure 18 Figure 17 Figure 16

42 Location Page 1

Component Locations
Figure 16Boom control handvalves
Figure 17Q-min adjustment screw
Figure 18P regulator
Figure 20E-stop manifold

Figure 15
Locations of components used to check boom pressures

Setting P
You must not adjust Q-min with the drive shafts
turning! Each time the Q-min screw must be adjusted,
the engine must be stopped, or at least the transmission
must be taken out of gear so that the drivelines stop
turning. To check or set P, follow these steps:
1. Stop the truck engine and place a Do Not
Operate sign on the windshield of the truck.
2. Install a 040 bar gauge in the pressure check port
of the boom handvalve. Take care not to accidently
install the gauge in the pretension check port
(Figure 16).

revDate
286 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

42 apitech back.epsL

Adjustment screw
(15 bar pretension)

Pretension check
port (040)

Pressure check port (except pretension)


0-40 and 0-600

Figure 16
Boom control handvalve (Apitech)
3. To be sure that the pump is only putting out the oil
needed to maintain P, we need to change the
setting of the Q-min screw. Q-min is adjusted by a
screw on the boom hydraulic pump (Figure 17).

Q-min
adjustment screw

Q-minscrew.eps

Q-max

Figure 17
Location of the Q-min adjustment screws

CAUTION
Do not operate any functions while setting P.

4. Unscrew the Q-min screw three full turns. Check Make sure that all emergency stop switches are in
that all personnel are clear of the truck, then restart the up (not engaged) position. Pressure can be read
the engine, engage the pumps, and leave the engine on the 040 bar gauge that you installed. Pressure
at an idle. If you activate any boom or outrigger should read 20 bar. If no adjustment is needed,
functions, you will damage the 040 bar gauge.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 287
HOME PRINT

Pressure Settings
simply reset the Q-min screw as described in 5. Delta P is adjusted by the P adjustment screw on
paragraph . If adjustment is needed, continue to the boom pump (Figure 18). Loosen the jam nut,
step (5). and adjust the screw inward to increase pressure, or
outward to decrease pressure until it is set at 20 bar
1.

deltaPvlv.eps
pressreg.eps

Regulator pressure
adjustment

T
Adjustment for P pressure

Figure 18
P regulator valve

6. If pressure cannot be set correctly, contact the each time before making the adjustment. When
Schwing Service Department to determine how to pressure is correct, tighten the jam nut on the
continue. adjustment screw before continuing with the other
procedures.
Setting Q-min
You must check Q-min pressure when the engine is at Setting boom pressure
the maximum specified RPM, but you must adjust it Now that P and Q-min are set, you can check or set
with the engine stopped. the main boom pressures. There are three pressure
1. If you unscrewed the Q-min screw as the first step settings:
of P adjustment, begin by returning the screw to
its original position (see Figure 17).
2. Remove the 040 bar gauge from the pressure
check port, and install the 0600 bar gauge in its
place.
3. Clear all personnel away from the drive lines, start
the truck engine, engage the pumps, and bring
engine RPM to max. All boom functions must be
in neutral, and all emergency stop buttons should
be up (not engaged). Read the pressure on the 0
600 bar gauge. Pressure should be at 4045 bar. If
no adjustment is needed, stop the drivelines, be
sure the jam nut on the Q-min screw is tight, then
continue to paragraph to check the rest of the
boom and outrigger pressures. If adjustment is
needed, continue to step (4).
4. Turn the Q-min screw in to raise the pressure (see
Figure 17). Turn it out to lower the pressure. Be
sure that you stop the drive shafts from turning
revDate
288 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
1. Pressure regulator (the high-pressure adjustment
screw on the P regulator valve), set at 290 bar
(Figure 18)

deltaPvlv.eps
pressreg.eps
Regulator pressure
adjustment

T
Adjustment for P pressure
Figure 19
P regulator valve

2. Redundant relief valve located in the emergency


stop manifold, set at 320 bar (Figure 20).
10167892-3.eps

P3
P2
P4
P1
M

TT

1
MP

Figure 20
Emergency stop manifold,
and boom redundant relief

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 289
HOME PRINT

Pressure Settings
3. Boom control block relief, set at 350 bar.

NOTE! This relief valve is nonadjustable. If


pressure is not maintained within the specification
limits, the valve must be replaced (Figure 21).

42 apitech relief.eps
350 bar
relief

30 bar relief

Figure 21
Apitech boom control block relief

To check the setting of the valve with the highest NOTE! Although the pressure specification for the
pressure, you must first raise the pressure of the lower Apitech relief valve is 350 bar, you may continue
two: to use the relief valve as long as the cartridge
1. Loosen the jam nut of the high-pressure adjustment maintains at least 330 bar. If you must replace the
screw of the P regulator (see Figure 18). Turn the valve, proceed to step (4) before using the machine
screw in two-and-a-half turns. This will raise the again, and redo this entire procedure when you
pressure on the regulator above 350 bar. have installed the new valve. If pressure on the
Apitech relief valve is below 290 bar, you should
2. Loosen the jam nut of the adjustment screw of the
not use the machine until the valve is replaced.
redundant relief valve in the emergency stop
manifold (see Figure 20). Turn the screw in one- 4. Screw out the redundant relief valve adjustment
and-a-half turns. This will raise the pressure on the screw (see Figure 20) one-and-a-half turns.
relief valve to above 350 bar. Pressure out any boom cylinder except #1 down,
and read the gauge. Pressure should read 320 bar.
3. Pressure out any boom cylinder except #1 down by
If does not, turn the screw in to raise pressure, or
pushing or pulling the control handle. To pressure
out to lower pressure until it is at 320 bar. If the
out a cylinder, retract a fully retracted cylinder or
location of this valve causes you to be near the
extend a fully extended cylinder. The oil is forced
drivelines, be sure to stop them from turning before
over the relief valve.
accessing the valve.
The telltale hiss of an open relief valve should be
coming from the Apitech control block relief valve 5. You will need a helper for this step. While
now. If it isnt, raise the setting of the other pressuring out any boom cylinder except #1 down,
pressure devices until the hiss originates at the have your helper adjust the high-pressure screw of
Apitech control block relief valve. Read the the P regulator out (lowering the pressure) until
pressure on the gauge. It should read 350 bar. If the gauge reads 290 bar (see Figure 18). Release
pressure is correct, proceed to step (4). the pressurized function and lock the jam nut. The
boom pressures are now set. If you did not get the
revDate
290 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
readings specified after following the instructions, 2. Stop the truck engine. Plug the 040 bar gauge into
contact Schwings Service Department for advice the pretension gauge port of the Apitech handvalve
on how to continue. (Figure 22).
3. Start the truck engine, but leave it at an idle. Read
Setting pretension the pressure on the gauge. If it reads 15 bar 1 bar,
To check or set pretension follow these steps: the pressure is set correctly. If the pressure is not
1. Remember that the oil must be at normal operating set correctly, continue to point (4.)
temperature (4060C). See point for
information about preheating the oil.

CAUTION
Truck engine must be at idle when pretension is set.

4. Loosen the jam nut on the pretension valve. Turn


the screw in to raise pressure, and out to lower
pressure. When the pressure is correct, retighten
the jam nut (Figure 22).

Adjustment screw
Gauge port

Apitech pretnscrw.eps

Figure 22
Pretension adjustment
screw and gauge port

5. Stop the engine, and remove the 040 bar pressure


gauge. Pretension setting is now complete.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 291
HOME PRINT

Pressure Settings

revDate
292 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
KVM 42M - Proportional pocket, remove the check plug from the check port. The
oil should be at the level of the bottom of the hole in
(Apitech) Twin Circuit the case. If oil is needed, add it by removing the
Check the fluid level of the distribution gearcase breather and pouring in the oil through the top. This
(Figure 23). Be sure the truck is on reasonably level gearcase uses 90W gear lube.
ground. With the truck engine off and the key in your

Breather (fill port)

4194 gearcase scan.eps


Check port

Drain port

Figure 23
Fill, check, and drain ports of Stiebel 4194 gear

Check the mounting hardware of the subframe, the oil 2. Turn on the agitator. The agitator will not be able
and water tanks, the delivery pipeline, the pumpkit, the to turn, and the oil will be forced over the relief
differential cylinders, the material cylinders, and the valve.
driveline hardware. Check for bolt tightness, cracks, 3. At an idle (about 600 RPM), you are converting
and other abnormalities. about 4.5 horsepower to heat, which is a pretty
good-sized heater. Shut off the concrete pump
Check hydraulic pressures when the oil shows 40C on the temperature gauge
Check all hydraulic pressures. The specifications for of the operators panel.
each circuit are shown on the hydraulic schematics in
the appendix of this manual. Changes in pressures can Setting concrete pump pressure (High-
indicate trouble in one or more components. flow pumpkits)
Schwing units with high-flow pumpkits are designed to
Preheat the hydraulic oil be operated at a maximum pressure of 320 bar (4640
Pressure settings must be made with the oil at normal PSI). The pressure in the system is limited by the relief
operating temperatures (40 60C). Because the valve located on the forward end (toward the truck cab)
system is load-sensing, the boom circuit cannot be used of the main control block (Figure 24). In addition, the
to heat the hydraulic oil. The agitator circuit must be hydraulic pumps have a pressure cutoff function, set at
used instead. To preheat the hydraulic oil using the 350 bar.
agitator circuit, follow these instructions: To check or set concrete pump circuit pressures, follow
1. Place a 4-by-4 in front of the agitator paddle. these steps:
1. Wear safety glasses when setting pressures.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 293
HOME PRINT

Pressure Settings
2. Be sure that the waterbox covers and guards are 9. Loosen the jam nut on the relief valve adjusting
installed on the waterbox. Schwing does not screw (Figure 24).
recommend using the remote control box when 10. Insert a hex key (allen) wrench into the screw, and
setting the main relief pressure. turn the screw to adjust the pressure. Turn the
3. Start the truck engine, and put the PTO and screw in to raise pressure, out to lower pressure.
transmission into gear, just as you would to pump a 11. Retighten the jam nut. (Tightening the nut tends to
job. raise the pressure. If the rise in pressure becomes a
4. Locate and close the concrete pump shutoff valve problem, hold the hex key wrench while tightening
(quarter-turn valve), and the soft switch shutoff the jam nut.)
valve (quarter-turn valve) (Figures 25 and 26). 12. High-pressure the concrete pump again. Read the
5. Put the operators panel remote / local switch pressure on the gauge. If more adjustment is
into the local position. needed, return the concrete pump switch to
6. Using the switch on the operators panel, rev the neutral, then repeat steps (i) through (l) until the
truck engine up to full RPM. pressure is correct.
7. Put the operators panel forward / neutral /
Note! If you cannot adjust the pressure up to
reverse switch into the forward position. The
specification, you have a problem. In this case,
unit will stroke only once, then the rock cylinder
unscrew the adjustment knob several turns so that
will retract. The oil leaving the hydraulic pumps
your pressure is not too high when you find the
will be forced over the main relief valve. This
problem. Contact Schwing Americas Service
procedure is called high-pressuring the concrete
Department at (612) 429-0999 for advice on how
pump.
to continue.
8. Read the pressure on the gauge, as shown. It
13. If you will not be setting the soft switch pressure,
should read 320 bar. Return the pump control to
open the shutoff valves. The unit will not stroke
neutral, whether it needs adjustment or not. If no
with closed shutoff valves.
adjustment is needed, skip to step (13).

Soft switch Closed Open


shutoff valve    
  

Main Pressure


Gauge port


   

  

 
 

Concrete pump Figure 24


hif
shutoff valve lob
rn
.e
Locations of the concrete pump
ps
and soft switch relief valves

revDate
294 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Soft switch
shutoff valve

Main Pressure
Gauge port

Concrete pump
hif
shutoff valve lob
rn
.e
ps

Figure 25
Locations of the concrete pump and soft switch shutoff valves

Groove lined up with ports Closed Open


- open

grooves.eps

openclsd.eps
Groove at 90 to ports
- closed

Figure 26
Open/closed orientation of the concrete pump shutoff
valve (left) and the soft switch shutoff valve (right)

Setting the soft switch circuit relief concrete pump shutoff valve on the side of the
pressure brain (shown in Figure 25) when you are finished.
The unit will not stroke with this valve closed.
To check or adjust the soft switch pressure setting,
proceed as follows:
1. Open the soft switch shutoff valve. The rest of the
unit should still be set up as if you were going to
check concrete pump pressure (Figure 27).
2. High-pressure the concrete pump. The pressure
gauge should read 80 bar (1160 PSI) instead of 320
bar. If adjustment is needed, loosen the jam nut of
the relief valve cartridge. Using the hex key
wrench, adjust the pressure up or down as needed,
and lock into place with the jam nut. Recheck.
Hold the screw with the hex key wrench, if
necessary, to prevent the screw from turning while
tightening the jam nut. Be sure to open up the

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 295
HOME PRINT

Pressure Settings

Soft switch
shutoff valve Open

Main Pressure
Gauge port

sftopen.eps
Soft switch
relief valve

Concrete pump
hif
shutoff valve lob
rn Figure 27
.e
ps
Soft switch circuit components

reheat the oil to check pressures


Note! Any time you set pressures for any circuit on any
unit, the hydraulic oil should be at normal operating
temperature (4060C). Instructions on heating the
hydraulic oil for this procedure are found in section
on page 6-97. Read all of the instructions before
beginning any pressure settings. You will need an
assistant for parts of the procedure. You and any
assistants should wear eye protection when setting
pressures.

Load-sensing boom hydraulic controls


This unit is equipped with a load-sensing, proportional
boom hydraulic system. In a black-and-white system
such as the 28X, the hydraulic pump puts out an
unchanging amount of oil, and speed control is done by
restricting the oil to certain functions with orifices. In a
load-sensing system, the pump puts out more or less oil
to respond to the needs of the system. Generally, the
pump puts out enough oil to maintain 20 bar higher
pressure at the pump than what the cylinders actually
require. This 20 bar is called delta P (P).
Additionally, we set the hydraulic pump so that it
always puts out a small amount of oil, even if no oil is
needed for the system. This oil is used to ensure that
you have control when you need it. The setting to
maintain this minimum amount of oil is called Q-min
(pronounced cue min). To set the boom or outrigger
hydraulic pressures on a load-sensing system, begin by
setting Q-min and P (Figure 15).

revDate
296 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Figure 20 Figure 18 Figure 17 Figure 16

42 Location Page 1

Component Locations
Figure 16Boom control handvalves
Figure 17Q-min adjustment screw
Figure 18P regulator
Figure 20E-stop manifold

Figure 28
Locations of components used to check boom pressures

Setting P 1. Stop the truck engine and place a Do Not


You must not adjust Q-min with the drive shafts Operate sign on the windshield of the truck.
turning! Each time the Q-min screw must be adjusted, 2. Install a 040 bar gauge in the pressure check port
the engine must be stopped, or at least the transmission of the boom handvalve. Take care not to accidently
must be taken out of gear so that the drive lines stop install the gauge in the pretension check port
turning. To check or set P, follow these steps: (Figure 29).
42 apitech back.epsL

Adjustment screw
(15 bar pretension)

Pretension check
port (040)

Pressure check port (except pretension)


0-40 and 0-600

Figure 29
Boom control handvalve (Apitech)

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 297
HOME PRINT

Pressure Settings
3. To be sure that the pump is only putting out the oil
needed to maintain P, we need to change the
setting of the Q-min screw. Q-min is adjusted by a
screw on the boom hydraulic pump (Figure 30).

Q-min
adjustment screw

Q-minscrew.eps

Q-max

Figure 30
Locations of the Q-min adjustment screws

CAUTION
Do not operate any functions while setting 20 bar P.

4. Unscrew the Q-min screw three full turns. Check simply reset the Q-min screw as described in
that all personnel are clear of the truck, then restart paragraph . If adjustment is needed, continue to
the engine, engage the pumps, and leave the engine step (5).
at an idle. If you activate any boom or outrigger 5. Delta P is adjusted by the P adjustment screw on
functions, you will damage the 040 bar gauge. the P regulator (Figure 31). Loosen the jam nut,
Make sure that all emergency stop switches are in and adjust the screw inward to increase pressure, or
the up (not engaged) position. Pressure can be read outward to decrease pressure until it is set at 20 bar
on the 040 bar gauge that you installed. Pressure 1.
should read 20 bar. If no adjustment is needed,
deltaPvlv.eps
pressreg.eps

Regulator pressure
adjustment

T
Adjustment for P pressure

Figure 31
Delta P regulator valve

6. If pressure cannot be set correctly, contact the continue.


Schwing Service Department to determine how to
revDate
298 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Setting Q-min continue to paragraph to check the rest of the
You must check Q-min pressure when the engine is at boom and outrigger pressures. If adjustment is
the maximum specified RPM, but you must adjust it needed, continue to step (4).
with the engine stopped. 4. Turn the Q-min screw in to raise the pressure (see
1. If you unscrewed the Q-min screw as the first step Figure 30). Turn it out to lower the pressure. Be
of P adjustment, begin by returning the screw to sure that you stop the drive shafts from turning
its original position (see Figure 30). each time before making the adjustment. When
pressure is correct, tighten the jam nut on the
2. Remove the 040 bar gauge from the pressure adjustment screw before continuing with the other
check port, and install the procedures.
0600 bar gauge in its place.
3. Clear all personnel away from the drive lines, start Setting boom pressure
the truck engine, engage the pumps, and bring
Now that P and Q-min are set, you can check or set
engine RPM to max. All boom functions must be
the main boom pressures.
in neutral, and all emergency stop buttons should
be up (not engaged). Read the pressure on the 0 There are three pressure settings:
600 bar gauge. Pressure should be at 4045 bar. If 1. Pressure regulator (the large adjustment screw on
no adjustment is needed, stop the drive lines, be the P regulator valve), set at 290 bar (Figure 295).
sure the jam nut on the Q-min screw is tight, then
deltaPvlv.eps
pressreg.eps

Regulator pressure
adjustment

T
Adjustment for P pressure
Figure 45
P regulator valve

2. Redundant relief valve located in the emergency


stop manifold, set at 320 bar (Figure 32).
10167892-3.eps
P3
P2
P4
P1
M

TT

1
MP

Figure 32
Emergency stop manifold, and
boom redundant relief valve
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 299
HOME PRINT

Pressure Settings
3. Boom control block relief, set at 350 bar.

NOTE! This relief valve is nonadjustable. If


pressure is not maintained within the specification
limits, the valve must be replaced (Figure 33).

42 apitech relief.eps
350 bar
relief

30 bar relief

Figure 33
Apitech boom control block relief valve

To check the setting of the valve with the highest


pressure, you must first raise the pressure of the lower NOTE! Although the pressure specification for the
two: Apitech relief valve is 350 bar, you may continue
1. Loosen the jam nut of the high-pressure adjustment to use the relief valve as long as the cartridge
screw of the P regulator (see Figure 295). Turn maintains at least 330 bar. If you must replace the
the screw in two-and-a-half turns. This will raise valve, proceed to step (4) before using the machine
the pressure on the regulator above 350 bar. again, and redo this entire procedure when you
have installed the new valve. If pressure on the
2. Loosen the jam nut of the adjustment screw of the
Apitech relief valve is below 290 bar, you should
redundant relief valve in the emergency stop
not use the machine until the valve is replaced.
manifold (see Figure 20). Turn the screw in one-
and-a-half turns. This will raise the pressure on the 4. Screw out the redundant relief valve adjustment
relief valve to above 350 bar. screw one-and-a-half turns (see Figure 34).
Pressure out any boom cylinder except #1 down,
3. Pressure out any boom cylinder except #1 down by
and read the gauge. Pressure should read 320 bar.
pushing or pulling the control handle. To pressure
If does not, turn the screw in to raise pressure, or
out a cylinder, retract a fully retracted cylinder or
out to lower pressure until it is at 320 bar. If the
extend a fully extended cylinder. The oil is forced
location of this valve causes you to be near the
over the relief valve.
drive lines, be sure to stop them from turning
The telltale hiss of an open relief valve should be
before accessing the valve.
coming from the Apitech control block relief valve
now. If it is not, raise the setting of the other 5. You will need a helper for this step. While
pressure devices until the hiss originates at the pressuring out any boom cylinder except #1 down,
Apitech control block relief valve. Read the have your helper adjust the high-pressure screw
pressure on the gauge. It should read 350 bar. If (see Figure 21) of the P regulator out (lowering
pressure is correct, proceed to step (4). the pressure) until the gauge reads 290 bar. Release

revDate
300 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
the pressurized function and lock the jam nut. The 1. Stop the truck engine. Plug the 040 bar gauge into
boom pressures are now set. If you did not get the the pretension check port of the Apitech handvalve
readings specified after following the instructions, (Figure 33).
contact Schwings Service Department for advice 2. Start the truck engine, but leave it at an idle. Read
on how to continue. the pressure on the gauge. If it reads 15 bar 1 bar,
the pressure is set correctly. If the pressure is not
Setting 15 bar pretension set correctly, continue to point (4.)
To check or set pretension follow these steps:

CAUTION
Truck engine must be at idle when pretension is set.

3. Loosen the jam nut on the pretension valve. Turn


the screw in to raise pressure, and out to lower
pressure. When the pressure is correct, retighten
the jam nut (Figure 34).

Apitech pretnscrw.eps
Figure 34
Pretension adjustment
screw and check port

4. Stop the engine, and remove the 040 bar pressure


gauge. Pretension setting is now complete.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 301
HOME PRINT

Pressure Settings

revDate
302 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
KVM 42M - Proportional pocket, remove the check plug from the check port. The
oil should be at the level of the bottom of the hole in
(Rexroth) the case. If oil is needed, add it by removing the
Check the fluid level of the distribution gearcase breather and pouring the oil through the top of the fill
(Figure 35). Be sure the truck is on reasonably level port. This gearcase uses 90W gear lube.
ground. With the truck engine off and the key in your

Breather (fill port)

4194 gearcase scan.eps


Check port

Drain port

Figure 35
Check, drain, and fill ports of Stiebel 4194 gearcase

Check the mounting hardware of the subframe, the number 30303432 (tube). Contact the Schwing
oil and water tanks, the delivery pipeline, the America Service Department for installation
pumpkit, the differential cylinders, the material instructions.
cylinders, and the driveline hardware. Check for 2. Turn on the agitator. The agitator will not be able
bolt tightness, cracks, and other abnormalities. to turn, and the oil will be forced over the relief
valve.
Check hydraulic pressures
At an idle (about 600 RPM), about 4.5 horsepower is
Check all hydraulic pressures. Changes in pressures being converted to heat. Shut off the concrete pump
can indicate trouble in one or more components. The when the oil temperature gauge on the operators panel
specifications for all circuits are shown on the shows 40C.
hydraulic schematics in the appendix of this manual.
Setting concrete pump pressure (single-
Preheat the hydraulic oil circuit units)
Pressure settings must be made with the oil at normal Schwing single-circuit pumpkits are designed to be
operating temperature (40 60C). The agitator circuit operated at a maximum pressure of 300 bar (4350 PSI).
must be used to heat the hydraulic oil. To preheat the The pressure in the system is controlled by the main
hydraulic oil using the agitator circuit, follow these relief valve on the forward end (toward the truck cab)
instructions: of the main control block (Figure 36).
1. Locate the agitator shutoff valve and close it.

NOTE! If your unit does not have a shutoff valve,


order one, using part number 10004680 (valve) and
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 303
HOME PRINT

Pressure Settings

Jam nut

Lower Raise Adjustment handle


pressure pressure

gray valve.eps L

Figure 36
Concrete pump circuit main relief valve
3. Start the truck engine, and put the PTO and
To check or set the main relief pressure:

1. When setting pressures, always wear safety


transmission into gear, just as you would to pump a
glasses.
job.
2. Be sure that the waterbox covers and guards are
4. Close the shutoff valve (also known as the
installed on the waterbox. Schwing does not
ballcock or quarter-turn valve) (Figures 37 and
recommend using the remote control box when
38).
setting the main relief pressure.

Shutoff valve

quarter turn.eps

Figure 37
Concrete pump shutoff valve

5. Put the rear operation panel remote / local switch


into the local position.
6. Using the switch on the rear operation panel, rev
the truck engine up to full RPM.
7. This procedure is called high-pressuring the
concrete pump. Put the main operation panel
forward / neutral / reverse switch into the

revDate
304 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
forward position. The unit will stroke only once;
then the rock cylinder will retract. Oil will be
forced over the main relief valve.

Groove at 90 to ports
Closed

Groove lined up with ports


Open
Ball cock grooves.eps

Figure 38
Open/closed orientation of concrete pump shutoff valve

8. Read the pressure on the gauge. It should read 300 12. Put the concrete pump into the forward position
bar. Return the pump to neutral, whether it needs again. The machine will not stroke this time, but it
adjustment or not. If no adjustment is needed, skip will high-pressure again. Read the pressure on the
to step (14). gauge. If more adjustment is needed, return the
9. Using a 13-mm spanner wrench, loosen the jam pump to neutral, then repeat steps (9) through
nut on the relief valve adjusting screw (see Figure (11) until the pressure is correct.
13).
IMPORTANT! If you cannot adjust the pressure
10. Turn the knob on the relief valve to adjust the
up to specification, you have a problem. In this
pressure. Screw the handle in to raise pressure, and
case, unscrew the adjustment handle several turns
out to lower pressure.
so that your pressure is not too high when you find
11. Retighten the jam nut. Tightening the nut tends to the problem. Contact Schwing Americas Service
raise the pressure setting. If the rise in pressure Department for advice on how to continue.
becomes a problem, hold the knob while tightening
13. Return the pump to the neutral position.
the jam nut.
14. Open the concrete pump shutoff valve (Figure 39).

Shutoff valve

quarter turn.eps

Figure 39
Concrete pump shutoff valve
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 305
HOME PRINT

Pressure Settings
15. Return the RPM of the truck to idle, take the Load-sensing boom hydraulic controls
transmission and PTO out of gear, and shut off the This unit is equipped with a load-sensing, proportional
truck, or go on to other pressure settings. boom hydraulic system. In a black-and-white system,
the hydraulic pump puts out an unchanging amount of
Setting boom circuit pressures oil, and speed control is done by restricting the oil to
NOTE! Any time you set pressures for any circuit on certain functions with orifices. In a load-sensing
any unit, the hydraulic oil should be at normal system, the pump puts out more or less oil to respond
operating temperature (4060 C). Instructions on to the needs of the system. Generally, the pump puts
heating the hydraulic oil for this procedure are found out enough oil to maintain 20 bar higher pressure at the
on page 6-97. Read all of the instructions before pump than what the cylinders actually require. This 20
beginning any pressure settings. You will need an bar is called delta P (P). Additionally, we set the
assistant for parts of the procedure. You and any hydraulic pump so that it always puts out a small
assistants should wear eye protection when setting amount of oil, even if no oil is needed for the system.
pressures. This oil is used to ensure that you have control when
you need it. The setting to maintain this minimum
amount of oil is called Q-min (pronounced cue min).
To set the boom or outrigger hydraulic pressures on a
load-sensing system, begin by setting Q-min and P
(Figure 42).

Figure 43 Figure 18 Figure 45 Figure 16

42 Location Page 1

Component Locations
Figure 16Boom control handvalves
Figure 18Q-min adjustment screw
Figure 43P regulator (original locationinside frame; current locationoutside frame)
Figure 45Normally open bypass valve

Figure 40
Locations of components used to check boom pressures

Setting P 1. Stop the truck engine, put the key in your pocket,
You must not adjust Q-min with the drive shafts and place a Do Not Operate sign on the
turning! Each time the Q-min screw must be adjusted, windshield of the truck.
the engine must be stopped, or at least the transmission 2. Install a 0-600 bar gauge and a 0-40 bar gauge in
must be taken out of gear so that the drivelines stop the boom control hand valve (Figure 41).
turning.
To check or set P, follow these steps:

revDate
306 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

SECTION 1 SECTION 2 SECTION 3 SECTION 4 SLEWING OUTPUT + / - AC / WP BOOM / OUTRIG.


FORWARD / REV.

WARNING
Do not operate at DANGER WARNING
pressures exceeding Electrocution hazard. Do not operate this
the rating of the Stay back from high machine without
voltage wires at least training. Understand
entire material the warnings in safety
delivery system. 17 feet (5 meters).
manuals and on decals.

0-40
42 rexman.epsL

0-600

Figure 41
Boom control handvalve (Rexroth)

3. To be sure that the pump is putting out only enough the boom hydraulic pump (Figure 42).
oil to maintain P, we need to change the setting of
the Q-min screw. Q-min is adjusted by a screw on

Q-min
adjustment screw

Q max

Figure 42
Location of Q-min screw

CAUTION
Do not operate any functions when setting P.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 307
HOME PRINT

Pressure Settings
Unscrew the Q-min screw three full turns. Check 20 bar. If no adjustment is needed, simply reset the
that all personnel are clear of the truck, then restart Q-min screw. If adjustment is needed, continue
the engine, engage the pumps, and leave the engine with step (5).
at an idle. If you activate any boom or outrigger 4. Delta P is adjusted on the P adjustment screw of
functions, you will damage the 040 bar gauge. the P regulator (Figure 43). There are two
Make sure that all emergency stop switches are in adjustment screws on the P regulator. The smaller
the up (not engaged) position. Pressure can be read screw is used to adjust P. Loosen the jam nut, and
on either the main boom gauge (0600 bar) or the adjust the screw inward to increase pressure, or
pretension (040 bar) gauge. Pressure should read outward to decrease pressure, until it is set at 20
bar (1).

High-pressure
adjustment screw

P
T

Figure 43
Delta P regulator.
5. If pressure cannot be set correctly, contact the Setting Q-min
Schwing Service Department to determine how to You must check Q-min pressure when the engine is at
continue. the maximum specified RPM, but you must adjust it
with the engine stopped.
1. If you unscrewed the Q-min screw as the first step
of P adjustment, begin by returning the screw to
its original position (Figure 44).

Q-min
adjustment screw

Q-minscrew.eps

Q-max

Figure 44
Q-min screw
2. Clear all personnel away from the drivelines, start no adjustment is needed, stop the drivelines, be
the truck engine, engage the pumps and bring sure the jam nut on the Q-min screw is tight, then
engine RPM to max. All boom functions must be continue to Setting boom pressure to set the rest
in neutral, and all emergency stop buttons should of the boom and outrigger pressures. If adjustment
be up (not engaged). Read the pressure on the 0 is needed, continue to step 3.
600 bar gauge. Pressure should be at 4045 bar. If
revDate
308 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
3. Turn the Q-min screw in to raise the pressure. Turn High-pressure adjustment screw of the P regula-
it out to lower the pressure. Be sure that you stop tor (the large adjustment screw on the P regula-
the drive shafts from turning each time before tor), set at 290 bar (see Figure 43).
making the adjustment. When pressure is correct, Normally open bypass valve (the valve that opens
tighten the jam nut on the adjustment screw before when an E-stop switch is activated), set at 320 bar
continuing with the other procedures. (see Figure 45).
Handvalve relief (located in the boom control
Setting boom pressure
block), set at 330 bar (Figure 46).
Now that P and Q-min are set, you can check or To check or adjust the high pressure settings on the
adjust the boom circuit high pressure settings. boom circuit, follow these steps:
1. Loosen the jam nut of the large adjustment screw
NOTE! These instructions apply to units built of the P regulator. (see Figure 43). Turn the screw
before January, 1997. in two full turns. This will raise the pressure on the
regulator above 330 bar.
There are three pressure settings on the boom circuit:

WARNING
If the P regulator is located inside the frame, stop the drivelines
from turning before making adjustments.

2. Loosen the jam nut on the normally open bypass adjusting screw in one full turn. This will raise the
valve adjustment screw (see Figure 45). Turn the pressure of this valve above 330 bar.

Jam nut

Adjustment
screw
3
age

Protective
nP
atio
Loc

cover
42

Figure 45
Normally open bypass valve
3. Pressure out any boom cylinder except #1 down, tings of the other pressure devices until the hiss
by pushing or pulling the control handle. To pres- originates at the boom control block relief valve.
sure out a cylinder, retract a fully retracted cylinder Read the pressure on the gauge. It should read 330
or extend a fully extended cylinder. The oil is bar. If no adjustment is needed, skip to step (4). If
forced over the relief valve. The telltale hiss of an adjustment is needed, proceed to step (4).
open relief valve should be coming from the con-
trol block relief valve now. If it isnt, raise the set-
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 309
HOME PRINT

Pressure Settings
4. Adjust the pressure by turning the adjustment pressure. When pressure is correct, lock the jam
screw on the boom handvalve relief valve (Figure nut, and continue to step (4).
46). Screw in to raise pressure, or out to lower

Handvalve relief valve


is located here.

rxboomblk.eps Front view Side view


Figure 46
Boom hand valve relief valve

5. You will need a helper for this step. Pressure out the A-frame when the boom is being folded into the
any boom cylinder except #1 down, as described in transport position. To prevent this, there is a secondary
(3) above. Read the gauge while your helper turns relief valve that regulates only the pressure on the #1
the adjustment screw of the normally open bypass retract function (Figure 47).
valve out (lowering the pressure). Continue adjust-
ing until the pressure reads 320 bar. Lock the jam
nut before proceeding.
6. While pressuring out any boom cylinder except #1
down, have your helper turn the high-pressure
adjustment screw of the pressure regulator out
(lowering the pressure) until the gauge reads 290
bar. Lock the jam nut. The boom pressures are now
set. If you did not get the readings specified after
following the instructions, contact Schwings Ser-
vice Department for advice on how to continue.

Set the #1 down side pressure


Because gravity pulls the boom down, high pressure is
not needed to bring section #1 down. Allowing high
pressure to be available leaves open the possibility of
an inattentive operator causing damage to the boom or
revDate
310 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Down side relief valve is located


behind this section.

rxdnside.eps Front view Side view

Figure 47
Down side relief valve

1. Set up the unit as if to pump a job. Put down the 7. Stop the truck engine. Remove the gauges from the
outriggers, avoiding overhead wires and other boom control block. The job is now complete.
obstructions.
2. Bottom out the #1 cylinders completely. No posi- Setting outrigger pressure
tion can allow the boom to do this without hitting After the boom circuit is properly set, you can set the
something unless the boom is unfolded. Unfold outrigger pressure. Find the relief valve on the back
side of the passenger side outrigger control bank relief
sections #2, #3, and #4 away from section #1. valve (Figure 48).
3. Slew the boom to a position that will allow section
#1 to come all the way down without hitting any-
thing, then bring section #1 down.
4. When the #1 cylinders have completely bottomed
out, the oil coming from the pump will have
nowhere to go except over the relief valve. Read
the gauge; it should say 100 bar. (Although pres-
sure is specified as 80 bar, the gauge will read 100
bar because of the 20 bar P that we set earlier.) If
no adjustment is needed, skip to step (6). If adjust-
ment is needed, proceed to step (5).
5. Loosen the jam nut on the down side relief car-
tridge. Adjust the pressure by turning the screw in
to increase pressure, or out to decrease pressure.
When the gauge reads 100 bar, retighten the jam
nut.
6. Fold up the boom, stow the outriggers, and refasten
the tie-down strap, or move on to other mainte-
nance procedures.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 311
HOME PRINT

Pressure Settings

280 Bar
280 Bar
relief valve
relief valve

Lower Lower

Higher PS
ou
trig Higher 6p
lc
cn ou
trb tri
lk- g
42 cn
.ep trb
s
lk
-4
2.
ep
s

Turn body of Turn body of


valve to adjust. valve to adjust.

Manitrol valve system Pushbutton system


Figure 48
Outrigger valve bank relief valves
To check the pressure, follow these steps:
1. On original units, pull the outrigger/boom selector
valve to the outrigger position. On units in current
production, push the outrigger enable button (Fig-
ure 26).

Outrigger
enable button

EXTEND REAR EXTEND FRONT FOLD REAR FOLD FRONT FOOT REAR FOOT FRONT
42 p.s. outrigger.epsL

Figure 49
Passenger side outrigger enable button (current production)
2. Pressure out an outrigger jacking cylinder. Pressure into the valve. While holding the handle, have your
out by retracting a retracted cylinder. The oil from helper read the pressure gauge installed on the
the pump will be forced over the relief valve. You boom control block.
cannot use an extension cylinder, because these
have secondary, nonadjustable relief functions built
revDate
312 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
3. The pressure should read 280 bar. Adjust by turn- Set agitator pressure
ing the body of the valve in or out. When 280 bar is The agitator circuit has a maximum pressure of 200 bar
reached, let go of the handle. (2900 PSI), which is limited by the relief valve in the
4. On original units, restore the outrigger/boom selec- agitator handvalve (Figure 50).
tor valve to the boom position. On units in current 1. There is a gauge port for checking or setting agita-
production, release the pushbutton. tor pressure. Plug the 0600 bar whip gauge into
the port.

AGITATOR

FORWARD REVERSE

Gauge port
behind here

Relief valve
42 E Stop & PS Agit Lever.eps

Figure 50
Agitator relief valve
2. With the engine shut off and the key in your number 30308553. Schwing recommends that you
pocket, remove one of the hoses from the agitator purchase this kit. It will pay for itself many times
motor and plug the hose and the open fitting with over.
approved hydraulic dead plugs. Do not substitute Be sure that one of the locking plugs and cap nuts
other plugs. If you have no hydraulic dead plugs, are tightened on the straight fitting, and that the
contact the Schwing America Spare Parts Depart- dead plugs are securely tightened to the hose and
ment and order them before continuing with this the open motor fitting.
procedure. You will need:
3. Restart the engine, engage the pumps, and bring
the throttle anywhere above idle. Activate the agi-
Qty. 2 VS-16S locking plugs, part number tator valve handle in either forward or reverse.
10016803 Read the gauge. If adjustment is needed, turn the
Qty. 1 GS-16S straight fitting, part number entire valve body in to increase pressure, or out to
10008088 decrease pressure.
Qty. 2 16S cap nuts, part number 10001743 4. When the pressure is set, stop the engine and
or remove the key. Remove the dead plugs and store
Qty. 1 size 16 shutoff valve, part number 10004680 in a clean area or in a plastic bag or another con-
tainer to keep dirt out of the fittings. Reattach the
Qty. 1 size 16 tube, part number 30303432.
hose to the agitator motor fitting and tighten
If you install the shutoff valve, you can leave it
securely. (Torque is correct if you make one com-
installed for future use.
plete revolution after initial resistance increases.)
All of these fittings and many more useful
items are included in the troubleshooting kit, part
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 313
HOME PRINT

Pressure Settings
5. Remove the whip gauge. Restart the engine, if nec- b. Loosen the jam nut on the accumulator unloading
essary. valve. Turn the accumulator unloading valve
adjustment screw in two-and-a-half turns. This will
Set accumulator circuit hydraulic oil raise the pressure above 300 bar (Figure 86).
pressure (units with accumulator
unloading valves)
5.3-7 You will need an assistant for parts of this pro-
cedure. To check or adjust the hydraulic pres-
sure in the accumulator circuit, follow these
steps:
a. Stop the truck, put the key in your pocket, and
place a Do Not Operate sign on the windshield.

Jam nut

Accumulator unloading
valve adjustment screw

s
.ep
Figure 51 un
lvlv

Accumulator unloading valve

c. Loosen the jam nut on the accumulator redundant


relief valve. (This valve is located on the emer-
gency stop manifold.)

NOTE: The emergency stop manifold was added


to units built after January 1, 1997.) Turn the screw
in two turns. This will raise the relief setting above
300 bar (Figure 52).

revDate
314 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

s
ep
rl.
an
cm
Accumulator relief valve

ac
P1 P4 P2

P3

MP
S

MP
S

Figure 52
Accumulator redundant relief valve
d. Clear all personnel away from the drive lines, start adjustment is needed, skip to (g). If additional
the truck engine, engage the pumps, and bring pressure adjustment is needed, continue to (f).
engine RPM to maximum. f. Locate the accumulator manifold pressure relief
e. Read the pressure on the accumulator circuit gauge valve (Figure 53). Loosen the jam nut, and turn the
located just between the hopper and the A-frame. screw in to increase pressure, or out to decrease
Pressure should read 300 bar (4350 PSI). If no pressure. Tighten the jam nut when pressure is at
300 bar.

Pressure relief valve

acc
ma
nrlf
.ep
s

Figure 53
Accumulator manifold pressure relief

g. You will need an assistant for this step. With the redundant relief valve on the emergency stop mani-
engine still running, one person must go to the fold and back out the adjustment screw. The other
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 315
HOME PRINT

Pressure Settings
person should stand by the pressure gauge to let
him know when pressure reads 260 bar (3770 PSI).
h. After the truck engine is stopped, go back to the
accumulator circuit hydraulic pump pressure regu-
lator and the turn the screw back out two-and-one-
half turns. This restores it to its original setting.
i. Read the pressure on the accumulator gauge. It
should read 200 bar (2900 PSI).
j. If adjustment is needed, you must stop the truck
engine, or at least stop the drivelines from turning
each and every time you approach the accumulator
circuit hydraulic pump. Turn the screw in to
increase pressure, or out to decrease pressure. Lock
the jam nut when the pressure is correct.

revDate
316 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
S 45/47SX

Spline flange breather

Figure 54
Oil check plug for spline flange cavity Oil check plug
(4400 gearcase) flange.eps

Setting Pressures 


  
 agitoff2.eps

The following pages provide the proper techniques for 


     
checking and setting hydraulic pressures of each
system included on your unit.

Check all hydraulic pressures.


Changes in pressures can indicate trouble in one or
more components. The specifications for each circuit 
are shown on the hydraulic schematics found in the
Appendix of this manual. The hydraulic schematics are
Figure 55
the only documents in this manual that have been
Agitator shutoff valve
updated specifically for your unit, by the serial number,
so in each of the following procedures you will be told
3. When the oil temperature gauge shows 50C, open
to refer to the schematic for the pressure required.
the shutoff valve.
Preheat the hydraulic oil
Pressure settings must be made with the oil at normal Setting pressures on Hi-flo -6 pumpkits
operating temperatures (40 60 C). In the past we a. To set the pressure of the main relief valve on
could pressure out a function in the boom or outrigger Hi-flo pumpkits, you must first disable the soft
system to create heat, but load sensing systems no switch circuit. Simply locate the ball cock for
longer allow maximum oil flow to be forced over relief. the soft switch circuit (Figure 56) and close it
Because of this the agitator circuit must be used to heat by rotating the handle 90 degrees.
the hydraulic oil. b. The quarter turn shutoff valve for the concrete
To preheat the hydraulic oil: pump (Figure 56) will also need to be closed
1. Locate the agitator shutoff valve (Figure 55) and during this procedure.
close it. NOTE! If your unit does not have a Note: Main system adjustments are preset at the
shutoff valve, order one from the Schwing Spare factory. The following procedure begins with
Parts Department using part number 10004680 adjustment of the main relief cartridge and pressure
(valve), and number 30303432 (tube). Contact the cutoff. If proper pressures can not be obtained through
Service Department for installation instructions. these steps, contact the Schwing Service Department
2. Activate the agitator. With the valve closed the for specific instructions on the adjustment of flow,
agitator will not be able to turn and the oil will be horsepower, beginning of stroke regulation and Q-min.
forced over the relief valve. At an idle (about 600 Pressure setting procedure:
RPM), 4.5 horsepower is being converted to heat.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 317
HOME PRINT

Pressure Settings
a 13mm wrench. Using a 4mm allen wrench, turn
Soft switch the adjustment screw in (clockwise) one full turn
shutoff valve and tighten the jam nut. Restart the truck engine.
Main Pressure 10. Adjust the engine RPM to maximum specification.
Gauge port (See decal in truck cab)
11. Pressure out the system by activating the concrete
pump forward switch on the rear panel. Using the
rear panel controls will allow you to read the
Concrete pump
concrete pump main system pressure gauge, near
shutoff valve hif
lob
rn
.e
the e-stop manifold, from a safe distance.
ps

Note: Because you turned out the pressure relief


Figure 56 cartridge in step 7, the system pressure should read low
Concrete pump and Soft switch at this time. If it does not and the gauge spikes to 320
shutoff valves bar or more, disengage the pump immediately. Turn the
1. Be sure that the waterbox covers and guards are in relief cartridge out (counterclockwise) more. For
place any time you will be working in the area safety, it is important to adjust the pressure up from
around the main control block. below the specified target pressure rather than down
from a pressure which exceeds the target. Continue this
2. Wear safety glasses when working around a procedure until the main system pressure gauge reads
concrete pump. lower than the specified target.
Note! It is vital that each adjustment screw be properly 12. To increase the pressure put the pump in the
identified prior to making any adjustment. All screw neutral position and adjust the relief cartridge by
adjustments for the system relief must be made with turning it in (clockwise). When increasing the
the pumpkit in the neutral position and adjustments for pressure, the adjustments should be made in
pressure cutoff must be made with the engine shut off. quarter turn increments. If you make adjustments
3. Start the truck engine, and put the PTO in gear just to increase the pressure but the pressure does not
as you would to pump a job. come up, you are probably reading the pressure
4. If you have not already closed the soft switch cutoff of the pumps, if so proceed to the next step
shutoff valve and the concrete pump shutoff valve otherwise skip to step 15.Turn the relief cartridge
(Figure 56) do so at this time. adjustment screw back out (counterclockwise)
5. At the rear panel, select local control with the until you can no longer see a pressure drop and
local/remote switch and turn the electric stroke tighten the jam nut.
limiter knob clockwise to maximum strokes per 13. Stop the truck engine, put the key in your pocket.
minute. 14. Go to the pressure cutoff screw on both hydraulic
6. The main system control block pressure must be pumps (Figure 57) and back off the jam nut with a
set first to properly set the pressure cutoff on both 13mm wrench. Turn the adjustment screws in with
pumps. Begin by backing off the jam nut of the a 4mm allen wrench one or two more turns, restart
main relief cartridge (Figure 58) with a 9/16 inch the engine and check the pressure again. Repeat
wrench. this procedure until the main system relief can be
7. Using a 5/32 inch allen wrench, turn the set to the target pressure.
adjustment screw out (counterclockwise) until you 15. When the proper main relief pressure is achieved,
can feel no spring tension on the adjustment screw. pressure cutoff can be set. Shut off the engine, put
8. Now, turn the screw back in (clockwise) two or the key in your pocket and install 0-600 bar gauges
three full turns to give you a proper starting point with whip hoses to the M1 gauge ports on the
and tighten the jam nut. bottom of the two hydraulic pumps (Figure 57).
You must be able to read both gauges
9. Stop the truck engine and put the key in your simultaneously to ensure that one pump is not
pocket. Adjust the pressure cutoff screw (Figure more dominant than the other.
57) on each pump, by backing off the jam nut with

revDate
318 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Note: The gauges in the M1 ports will read After pressure cutoff is set, return the pump to neutral,
considerably less than the cutoff pressure of the pump. bring engine RPM to idle, open the soft switch quarter
On a -6 (190/130 pump combination) the 190 will turn valve, and either proceed to other pressure settings
usually read 85 to 90 bar while the 130 reads about 110 or take the transmission and PTO out of gear and shut
bar. They could read the same however, at off the truck.
approximately 110 bar, but the 190 must never read
higher than the 130. The actual cutoff pressure will be 2 PRESSURE CUT OFF
1 STROKE REGULATION
read on the concrete pump main system pressure gauge
3 HORSE POWER 4 Q-MIN
near the e-stop manifold.
16. Activate concrete pump forward to pressure out the 2 2
1
pump and read the pressure on the two gauges in 1 3
3
the M1 ports. 4
4
17. Always stop the truck engine and put the key in
your pocket before making any adjustment on the
hydraulic pump. If the cutoff on one pump is set M1 GAUGE PORT
higher than the other, that pump will be more (BOTTOM OF EACH PUMP)
dominant. The pressure gauge in the M1 port of the 130ajst.eps

dominant pump will however, read lower than the


other. To equalize the two pumps you must either Figure 57
adjust the cutoff screw in (clockwise) to increase A11VO adjustment screws for Hi-flo 6
the pressure of the pump showing the higher units 190/130
reading or adjust the cutoff screw of the dominant
pump showing the lower reading out
(counterclockwise) to reduce the pressure. These
adjustments must be made until the two gauges in
the M1 ports are reading approximately the same.
18. When you have achieved the same pressure on the
M1 port gauges, you can begin to adjust the
pressure cutoff screws in or out simultaneously
until you achieve the desired pressure setting of
350 bar (again, confirm the pressure specification
with the hydraulic schematic).

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 319
HOME PRINT

Pressure Settings

Soft switch Closed Open


shutoff valve
   
Main Pressure   

Gauge port


Concrete pump
shutoff valve hif
lob

   

  

rn
.e
ps

 
 

Figure 58
Soft switch components

Setting the soft switch relief pressure Load-sensing boom hydraulic controls
First, open the soft switch quarter turn valve (Figure 58 This unit is equipped with a load-sensing, proportional
right) that you closed in the previous procedure. The boom hydraulic system. In a black-and-white system,
rest of the unit should still be set up as if you were the hydraulic pump puts out an unchanging amount of
going to check the main relief valve pressure (concrete oil, and speed control is done by restricting the oil to
pump shutoff valve still closed). certain functions with orifices. In a load-sensing
When you put the pump in forward now, the main system, the pump puts out more or less oil to respond
concrete pump pressure gauge should read the pressure to the needs of the system. Generally, the pump puts
shown on the schematic for soft switch. If adjustment out enough oil to maintain 20 bar higher pressure at the
is needed, loosen soft switch relief valve jam nut pump than the cylinders actually require. This 20 bar is
(Figure 58 right) with a 9/16 open end wrench, and use called delta P (P). Additionally, we set the hydraulic
a 5/32 allen wrench to adjust the pressure. Turn the pump so that it always puts out a small amount of oil,
adjustment screw in (clockwise) to raise the pressure or even if no oil is needed for the system. This oil is used
out (counter clockwise), to lower the pressure. When to ensure that you have control when you need it. The
you attain the required pressure, tighten the jam nut setting to maintain this minimum amount of oil is
while holding the allen wrench to keep the pressure called Q-min (pronounced cue min). To set the boom
from rising. Be sure to open the concrete pump shutoff or outrigger hydraulic pressures on a load-sensing
valve on the side of the brain (Figure 58 left) when you system, begin by setting P and Q-min.
are finished. The unit will not stroke with this valve Note: The illustration in Figure 59 shows a gauge port
closed. in the center of the main control block. Your main con-
crete pump pressure gauge should be plumbed to that
Setting boom circuit pressures port.
Note! Any time you set pressures for any circuit on any
unit, the hydraulic oil should be at normal operating WARNING
temperature (4060 C). Instructions on heating the
hydraulic oil are found in the first step of this Entanglement hazard. Stop drive shafts
checking hydraulic pressures segment. before adjusting Delta P on A11VO pump.
W020.eps

Read all of the instructions before beginning any pres-


sure settings. You will need an assistant for parts of the
procedure. You and any assistants should wear eye pro-
tection when setting pressures.

revDate
320 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

0-600 bar
gauge port
ps
0.e
60
top
es

pretension
only
Boom pressure
33-35 bar
relief cartridge

0-600 bar
gauge port
45bmcnbl.epsL

Figure 59
(Left) The 060 bar gauge port is located at the top of the boom control block, and the 0-600
bar port is at the bottom. (Right) A 0600 bar gauge port is located on the E-stop manifold.

Setting delta P pressure 5. If adjustment is required, loosen the jam nut, and
Note! Do not adjust P or Q-min if your boom is adjust the screw inward to increase pressure or
running as you like it. The pressure setting procedure outward to decrease pressure until it is set at 20
uses a standard starting point and must be fine tuned bar. After achieving proper P, tighten the jam nut
from that point. The pressure was fine tuned at the and bring the engine RPM up. If the pressure
factory and should not be adjusted unless absolutely gauge continues to read 20 bar, you are reading the
necessary. true P pressure and may move on to setting the Q-
min. If the pressure rises with the RPM however,
1. Start by turning off the engine and putting the key you may be reading the Q-min pressure instead of
in your pocket; then place a Do Not Operate sign true P. If that happens, stop the engine, put the
on the windshield of the truck. key in your pocket, and place a Do Not Operate
2. Install a 0-100 bar gauge in the high pressure test sign on the windshield of the truck before
port at the bottom of the boom control block proceeding .

(Figure 59). NOTE! Do not activate any boom/


outrigger functions or release any e-stops with a
low pressure gauge attached to a high pressure
pressreg.eps

port. Regulator pressure


adjustment
3. Delta P is adjusted on the pressure regulator
(Figure 60 top) if your unit has an A7VO pump or T

(Figure 60 bottom) if your unit has an A11VO Adjustment for P pressure


boom pump. When all personnel are clear of the Delta-p
truck, restart the engine, engage the pumps, and
leave the engine at an idle. P pressure should read
20 bar, which is the standard starting point.
4. There are two adjustment screws on the pressure
regulator (Figure 60 top) for A7VO pumps. The
smaller screw is used in this procedure to adjust smdeltap.eps

P. On the A11VO pumps there is only one P


screw (Figure 43 bottom). Figure 60
Pressure regulator for A7VO boom pumps
(top) and A11VO pumps (bottom)

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 321
HOME PRINT

Pressure Settings

Q-min
Delta-p Pressure Cut-off
adjustment screw

A7VX section min.top.eps

hifloreg.eps

Q max Q-min Q-max (Bottom Of Pump)

Figure 61
Location of Q-min screw on the A7VO (left) and all adjustment screws of the A11VO (right)

6. Unscrew the Q-min screw (Figure 61) three full


turns. This step will help ensure that the pump
produces only the amount of flow needed to
maintain P pressure. Once all personnel are clear
of the truck, restart the engine, engage the pumps,
and recheck at an idle. Pressure should now read
20 bar. If it does not, go back and adjust P until it
does.
pressreg.eps

Regulator pressure
If pressure cannot be set correctly, there is a problem adjustment
either with the orifices in the base of the regulator or
with the regulator itself. Contact the Schwing Service T

Department to determine how to continue. Adjustment for P pressure


Note: If the boom does not run smoothly at 20 bar,
you must fine tune the adjustment. Remove the gauge, Figure 62
and turn the P adjustment screw until the boom is Boom pressure regulator for units
responsive and smooth. After adjusting, the gauge with A7VO pumps
(reinstalled) must read between 14-25 bar. The elec-
tronics in the control system can also affect how the
boom operates, so if P adjustment does not seem to
help, reset to 20 bar and check the electrical settings.
Once electrical settings are verified, you could again
try to refine the boom action with the P adjustment.
Note: The pressure regulator (Figure 62) is usually
mounted on the inside of the subframe, near the cab
end of the differential cylinders.

revDate
322 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Setting Q-min 5. Identify the main boom pressure relief cartridge on
Check Q-min when the engine is at maximum specified the boom control block (Figure 64) and loosen the
RPM. You must not adjust Q-min with the drive jam nut. Then unscrew the adjustment two full
shafts turning! Each time the Q-min screw must be turns.
adjusted, the engine must be stopped, or at least the 6. Take engine RPM to full throttle and activate boom
transmission must be taken out of gear so that the retract for any boom section except #1.
drivelines stop turning. 7. Now adjust pressure, which is read at the main
1. If you unscrewed the Q-min screw as part of the P boom gauge port, to the setting found on the
adjustment, begin by returning the screw to its schematic by turning the boom pressure relief
original position. cartridge in, or clockwise, using no more than 1/4
2. All boom functions must be in neutral, and all turn increments.
emergency stop buttons should be up (not 8. When desired pressure is achieved, lock down the
engaged). Clear away all personnel, start the truck jam nut.
engine, engage the pumps and bring engine RPM
to max. Read the pressure at the 0600 bar main
boom gauge port (Figure 63) with a 0-100 bar
gauge. Pressure should be at 4045 bar. If no
adjustment is needed, be sure the jam nut on the 0-600 bar
Q-min screw is tight, then continue to set the rest gauge port
of the boom and outrigger pressures. If adjustment ps
0.e
60
is needed, continue to the next step. es
top

3. Turn the Q-min screw (Figure 61) in to raise the


pressure. Turn it out to lower the pressure. Be sure
that you stop the drive shafts from turning each
Boom pressure
time before making the adjustment. When pressure
relief cartridge
is correct, tighten the jam nut on the adjustment
screw before continuing with the other procedures,
then recheck P to make sure that it hasnt
changed during the Q-min adjustment.
Note: If you dont have a 0-100 bar gauge you can
order one from Schwing Spare Parts Department at
Figure 63
(800) 328-9635, part # 10004659.
Boom pressure relief cartridge
Setting boom pressures
9. The next step is to return to the e-stop manifold
Now that P and Q-min are set, you can remove the 0- boom pressure relief cartridge (Figure 63), and
100 bar pressure gauge and proceed to check and back off the jam nut (30 mm), and turn the relief
adjust the main boom pressures. cartridge (32mm) out, or counter clockwise, until
1. Loosen jam nut of the boom pressure relief the pressure shown on the schematic, for the boom
cartridge (Figure 63) with a 30mm open end pressure relief cartridge, is achieved. When the
wrench. proper pressure is achieved, lock the jam nut.
2. Turn the adjustment cartridge clockwise all the
way in with a 32mm wrench.
3. Loosen the jam nut on the pressure relief screw of
the regulator (Figure 62) or the pressure cut-off
(Figure 61), and tighten the screw all the way
down.
4.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 323
HOME PRINT

Pressure Settings
Setting outrigger pressure
mainrlf.eps

After the boom circuit is properly set, you can set the
outrigger pressure. Find the relief cartridge
located on the front of the passenger side outrigger
control valve (Figure 48).

#1 down side
relief cartridge

Main boom pressure


relief cartridge

1. Attach 0-600 bar whip gauge to the gauge port


(Figure 48) below the outrigger valve bank.
Figure 64 2. Push the outrigger enable button.
Main boom pressure adjustment and 3. Activate an outrigger jacking cylinder to retract.
piston side relief By retracting a fully retracted cylinder, the oil
coming from the pump has nowhere to go but over
10. The next pressure setting is the regulator pressure.
the relief valve. You cannot use an extension or
Locate the regulator adjustment screw (Figure 61)
slewing cylinder because they have secondary
or pressure cut-off screw (Figure 62). Back off the
relief functions (nonadjustable) built into the valve.
jam nut, and turn the screw counter clockwise until
While holding the handle to retract, read the
you achieve the pressure shown on the schematic;
pressure gauge.
then lock the jam nut.
4. The pressure should read the bar value shown on
11. The final boom pressure setting is the #1 boom
the hydraulic schematic. Adjust by loosening the
piston side relief setting. This relief cartridge is in
jam nut with a 9/16 open end wrench and turning
close proximity to the main boom relief (Figure
the cartridge (Figure 65) in or out with 5/32 allen
64), so be sure to locate the proper adjustment.
wrench. When the proper pressure is achieved, let
This procedure should be performed with the
go of the handle and release the outrigger enable
outriggers extended and the boom unfolded over
button.
the cab. Disconnect all gauges from gauge ports
prior to operating any boom or outrigger testport.eps

functions. Bring section #1 all the way down until


the cylinder bottoms out. Install a 0-600 bar gauge
in the main boom gauge port of the e-stop manifold
REAR SLEW REAR JACKING FRONT JACKING FRONT EXTEND

(Figure 63), and activate boom #1 down. The


30354359

pressure should read the setting shown on the


schematic. If adjustment is required, back off the
jam nut and turn the relief cartridge in or out as
required until the desired pressure is achieved; then
Relief Valve
lock down the jam nut.
Gauge Port

Figure 65
Outrigger valve bank relief cartridge
and gauge port
revDate
324 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

CONCRETE PUMP
FORWARD/REVERSE

AGITATOR

Relief valve
Gauge port

Figure 66
Agitator component location

Set the agitator pressure


The agitator circuit has a maximum pressure shown on

  
 agitoff2.eps

the hydraulic schematic, which is limited by the relief


cartridge (Figure 66) in the agitator hand valve. The 
     
relief cartridge is located on the back side of the
agitator manual control handle (Figure 67). The
cartridge is adjustable with just an 19mm open end
wrench.
1. Plug the 0600 bar whip gauge into the gauge port
(Figure 66) for checking or setting agitator 
pressure.
2. Locate the agitator shutoff (Figure 67) valve and
Figure 67
close it. If your unit does not have a shutoff valve,
Agitator shutoff valve
order one from the Schwing Spare Parts
Department using part numbers 10004680 (valve)
and 30303432 (tube). Contact the Service Plugs Straight Fitting
Department for installation instructions, or if you
cant wait for a shutoff valve, you will need to Figure 68
remove one of the hoses from the agitator motor Approved hydraulic
and plug the hose and open fitting with approved dead plugs capplug.eps
hydraulic dead plugs (Figure 68).
NOTE! Do not jam the paddles to force the oil over
relief by stopping the movement of the agitator. Cap Nuts

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 325
HOME PRINT

Pressure Settings
3. Increase the throttle to any speed above idle. redundant relief cartridge in the emergency stop
Activate the agitator valve handle in either forward manifold(Figure 52 top). If your pump was built after
or reverse, and read the gauge. If it does not read January 1, 2000. It will have an emergency stop
the specified pressure, adjustment is required. Turn manifold similar to the illustration shown in the bottom
the entire valve body (Figure 66) in to increase of Figure 52 which no longer has a redundant relief
pressure or out to decrease pressure. cartridge and you must skip steps 3. and 7. in the
4. When the pressure is set, deactivate the agitator by following procedure.
placing the manual control handle in the neutral To check or adjust the hydraulic pressure in the
position. accumulator circuit:
5. Remove the whip gauge. 1. Stop the truck, put the key in your pocket, and
place a Do Not Operate sign on the windshield.
6. Reopen the shutoff valve or remove the dead plugs
and reconnect the capped hydraulic line. 2. Loosen the jam nut on the pressure regulator of the
accumulator hydraulic pump (Figure 69). Turn the
Set accumulator circuit pressure screw in two-and-one-half turns. This will raise the
regulator pressure above 300 bar.
3. Loosen the jam nut (Figure 70) on the accumulator
redundant relief cartridge located on the
emergency stop manifold. Turn the screw in two
turns. This will raise the relief setting above 300
bar.
45Accreg.eps
accurlf2.eps

Accumulator pump Accumulator redunant


pressure regulator relief cartridge

Figure 69
Accumulator pump pressure regulator for Figure 70
A7VO (above) and for A11VO (below) Accumulator redundant relief cartridge
(above) is only present on early production
Boom Pump models. New e-stop (below) has no redundant
Accumulator Pump relief cartridge.

Standby
Pressure Screw

Accumulator Pump
Pressure Regulator accumpmp.eps
hgacugc.psd

You will need an assistant for parts of this procedure. 4. Clear all personnel away from the drive lines, start
There are three relief settings for the accumulator the truck engine, engage the pumps, and bring the
circuit if your unit is equipped with an accumulator, engine RPM to maximum.

revDate
326 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
5. Read the pressure on the accumulator circuit counter clockwise to decrease the pressure.
pressure gauge (Figure 71). The pressure should Tighten the jam nut when the pressure reaches the
read the value shown on the hydraulic schematic. If value required.
no adjustment is needed, skip to step number 7. If 7. You will need an assistant for this step. With the
additional pressure adjustment is needed, continue engine still running, one person must go to the
with step number 6. redundant relief valve on the emergency stop

@@@@@@@@



;;;;;;;;
QQQQQQQQ
manifold (Figure 70) and back out the adjustment

@@@@@@@@


;;;;;;;;
QQQQQQQQ

45acumpr.epsL

screw while the other person stands by the pressure

@@@@@@@@


;;;;;;;;
QQQQQQQQ

gauge to let him know when the pressure reads the
value shown on the schematic for accumulator

@@@@@@@@


;;;;;;;;
QQQQQQQQ

;;;;;;;;
@@@@@@@@
redundant relief.



QQQQQQQQ

@@@@@@@@


;;;;;;;;
QQQQQQQQ

;;;;;;;;
@@@@@@@@


QQQQQQQQ

;;;;;;;;
@@@@@@@@
Figure 71 

QQQQQQQQ

Accumulator circuit pressure gauge

acumrlf.epsL

8. After the truck engine is stopped, go back to the


accumulator circuit hydraulic pump pressure
regulator (Figure 69), and turn the screw back out
two-and-one-half turns. This restores it to its
original setting.
9. Clear all personnel from the drive line area, start
the truck, and bring the engine RPM up to
maximum.
10. Read the pressure on the accumulator gauge. It
should read the proper accumulator system
pressure.
11. If adjustment is needed, you must stop the truck
engine, or a least stop the drive lines from turning,
each and every time you approach the accumulator
circuit hydraulic pump. Turn the screw in to
increase the pressure or out to decrease pressure.
Lock the jam nut when the pressure is correct.
Note: The accumulator circuit hydraulic pump pressure
Figure 72 regulator is referred to as the pressure cut-off.
Accumulator manifold pressure
relief cartridge

6. Locate the accumulator manifold pressure relief


cartridge (Figure 72). Loosen the jam nut, and turn
the screw clockwise to increase the pressure or

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 327
HOME PRINT

Pressure Settings

revDate
328 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
S 45SX Hi-Flow - 6
Breather
Breather filter grbx-5-6.eps

filler spout
Oil check plug

Oil Check Plug

Oil Drain Plug

Drain plug 4194 gearcase scan.eps

Figure 73
Check fluid level of distribution gearcase Stiebel
box 4194 (left) or 4400 (right)

Spline flange breather

Figure 74
Oil check plug for spline flange cavity Oil check plug
(4400 gearcase) flange.eps

Setting Pressures Pressure settings must be made with the oil at normal
operating temperatures (40 60 C). In the past we
The following pages provide the proper techniques for could pressure out a function in the boom or outrigger
checking and setting hydraulic pressures of each system to create heat, but load sensing systems no
system included on your unit. longer allow maximum oil flow to be forced over relief.
Because of this the agitator circuit must be used to heat
Check all hydraulic pressures. the hydraulic oil.
Changes in pressures can indicate trouble in one or To preheat the hydraulic oil:
more components. The specifications for each circuit
1. Locate the agitator shutoff valve (Figure 55) and
are shown on the hydraulic schematics found in the
close it. NOTE! If your unit does not have a
Appendix of this manual. The hydraulic schematics are
shutoff valve, order one from the Schwing Spare
the only documents in this manual that have been
Parts Department using part number 10004680
updated specifically for your unit, by the serial number,
(valve), and number 30303432 (tube). Contact the
so in each of the following procedures you will be told
Service Department for installation instructions.
to refer to the schematic for the pressure required.
Preheat the hydraulic oil

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 329
HOME PRINT

Pressure Settings
2. Activate the agitator. With the valve closed the 1. Be sure that the waterbox covers and guards are in
agitator will not be able to turn and the oil will be place any time you will be working in the area
forced over the relief valve. At an idle (about 600 around the main control block.
RPM), 4.5 horsepower is being converted to heat. 2. Wear safety glasses when working around a
concrete pump.

  
 agitoff2.eps


      Note! It is vital that each adjustment screw be properly
identified prior to making any adjustment. All screw
adjustments for the system relief must be made with
the pumpkit in the neutral position and adjustments for
pressure cutoff must be made with the engine shut off.
3. Start the truck engine, and put the PTO in gear just
 as you would to pump a job.
4. If you have not already closed the soft switch
Figure 75 Agitator shutoff valve shutoff valve and the concrete pump shutoff valve
3. When the oil temperature gauge shows 50C, open (Figure 56) do so at this time.
the shutoff valve. 5. At the rear panel, select local control with the
local/remote switch and turn the electric stroke
Setting the main relief pressure and limiter knob clockwise to maximum strokes per
pressure cutoff on Hi-flo -6 pumpkits minute.
a. To set the pressure of the main relief valve on 6. The main system control block pressure must be
Hi-flo pumpkits, you must first disable the soft set first to properly set the pressure cutoff on both
switch circuit. Simply locate the ball cock for pumps. Begin by backing off the jam nut of the
the soft switch circuit (Figure 76) and close it main relief cartridge (Figure 78) with a 9/16 inch
by rotating the handle 90 degrees. wrench.
b. The quarter turn shutoff valve for the concrete 7. Using a 5/32 inch allen wrench, turn the
pump (Figure 76) will also need to be closed adjustment screw out (counterclockwise) until you
during this procedure. can feel no spring tension on the adjustment screw.
Note: Main system adjustments are preset at the 8. Now, turn the screw back in (clockwise) two or
factory. The following procedure begins with three full turns to give you a proper starting point
adjustment of the main relief cartridge and pressure and tighten the jam nut.
cutoff. If proper pressures can not be obtained through 9. Stop the truck engine and put the key in your
these steps, contact the Schwing Service Department pocket. Adjust the pressure cutoff screw (Figure
for specific instructions on the adjustment of flow, 57) on each pump, by backing off the jam nut with
horsepower, beginning of stroke regulation and Q-min. a 13mm wrench. Using a 4mm allen wrench, turn
Pressure setting procedure: the adjustment screw in (clockwise) one full turn
and tighten the jam nut. Restart the truck engine.
Soft switch 10. Adjust the engine RPM to maximum specification.
shutoff valve
(See decal in truck cab)
Main Pressure 11. Pressure out the system by activating the concrete
Gauge port
pump forward switch on the rear panel. Using the
rear panel controls will allow you to read the
concrete pump main system pressure gauge, near
the e-stop manifold, from a safe distance.
Concrete pump Note: Because you turned out the pressure relief
shutoff valve hif
lob
rn.
ep
s cartridge in step 7, the system pressure should read low
Figure 76 at this time. If it does not and the gauge spikes to 320
Concrete pump, Soft switch shutoff valves bar or more, disengage the pump immediately. Turn the
relief cartridge out (counterclockwise) more. For
safety, it is important to adjust the pressure up from
revDate
330 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
below the specified target pressure rather than down other. To equalize the two pumps you must either
from a pressure which exceeds the target. Continue this adjust the cutoff screw in (clockwise) to increase
procedure until the main system pressure gauge reads the pressure of the pump showing the higher
lower than the specified target. reading or adjust the cutoff screw of the dominant
12. To increase the pressure put the pump in the pump showing the lower reading out
neutral position and adjust the relief cartridge by (counterclockwise) to reduce the pressure. These
turning it in (clockwise). When increasing the adjustments must be made until the two gauges in
pressure, the adjustments should be made in the M1 ports are reading approximately the same.
quarter turn increments. If you make adjustments 18. When you have achieved the same pressure on the
to increase the pressure but the pressure does not M1 port gauges, you can begin to adjust the
come up, you are probably reading the pressure pressure cutoff screws in or out simultaneously
cutoff of the pumps, if so proceed to the next step until you achieve the desired pressure setting of
otherwise skip to step 15.Turn the relief cartridge 350 bar (again, confirm the pressure specification
adjustment screw back out (counterclockwise) with the hydraulic schematic).
until you can no longer see a pressure drop and After pressure cutoff is set, return the pump to neutral,
tighten the jam nut. bring engine RPM to idle, open the soft switch quarter
13. Stop the truck engine, put the key in your pocket. turn valve, and either proceed to other pressure settings
14. Go to the pressure cutoff screw on both hydraulic or take the transmission and PTO out of gear and shut
pumps (Figure 77) and back off the jam nut with a off the truck.
13mm wrench. Turn the adjustment screws in with
a 4mm allen wrench one or two more turns, restart
the engine and check the pressure again. Repeat
this procedure until the main system relief can be
set to the target pressure.
15. When the proper main relief pressure is achieved,
pressure cutoff can be set. Shut off the engine, put
the key in your pocket and install 0-600 bar gauges
with whip hoses to the M1 gauge ports on the
bottom of the two hydraulic pumps (Figure 77).
You must be able to read both gauges
-6adjust.eps
simultaneously to ensure that one pump is not
more dominant than the other.
Note: The gauges in the M1 ports will read
considerably less than the cutoff pressure of the pump.
On a -6 (190/130 pump combination) the 190 will Figure 77
usually read 85 to 90 bar while the 130 reads about 110 A11VO adjustment screws for Hi-flo 6
bar. They could read the same however, at units 190/130
approximately 110 bar, but the 190 must never read
higher than the 130. The actual cutoff pressure will be
read on the concrete pump main system pressure gauge
near the e-stop manifold.
16. Activate concrete pump forward to pressure out the
pump and read the pressure on the two gauges in
the M1 ports.
17. Always stop the truck engine and put the key in
your pocket before making any adjustment on the
hydraulic pump. If the cutoff on one pump is set
higher than the other, that pump will be more
dominant. The pressure gauge in the M1 port of the
dominant pump will however, read lower than the
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 331
HOME PRINT

Pressure Settings

Main and soft switch


relief cartridges Concrete pump Closed Open
gauge port
soft switch
NOTE: The main control relief cartridge
Main relief cartridge
block (brain) of a 2525

opencls.eps
pumpkit will be rotated 9/16" jam nut
180 degrees from the
illustration shown
5/32" Allen head
ga
ug
pr
t.e
ps
9/16" jam nut

Figure 78
Location of soft switch shutoff and relief cartridges

Setting the soft switch relief pressure Load-sensing boom hydraulic controls
First, open the soft switch quarter turn valve (Figure 78 This unit is equipped with a load-sensing, proportional
right) that you closed in the previous procedure. The boom hydraulic system. In a black-and-white system,
rest of the unit should still be set up as if you were the hydraulic pump puts out an unchanging amount of
going to check the main relief valve pressure (concrete oil, and speed control is done by restricting the oil to
pump shutoff valve still closed). certain functions with orifices. In a load-sensing
When you put the pump in forward now, the main system, the pump puts out more or less oil to respond
concrete pump pressure gauge should read the pressure to the needs of the system. Generally, the pump puts
shown on the schematic for soft switch. If adjustment out enough oil to maintain 20 bar higher pressure at the
is needed, loosen Soft switch relief valve jam nut pump than the cylinders actually require. This 20 bar is
(Figure 78 right) with a 9/16 open end wrench, and use called delta P (P). Additionally, we set the hydraulic
a 5/32 allen wrench to adjust the pressure. Turn the pump so that it always puts out a small amount of oil,
adjustment screw in (clockwise), to raise the pressure even if no oil is needed for the system. This oil is used
or out (counter clockwise), to lower the pressure. When to ensure that you have control when you need it. The
you attain the require pressure, tighten the jam nut setting to maintain this minimum amount of oil is
while holding the allen wrench, to keep the pressure called Q-min (pronounced cue min). To set the boom
from rising. Be sure to open the concrete pump shutoff or outrigger hydraulic pressures on a load-sensing
valve on the side of the brain (Figure 78 left) when you system, begin by setting P and Q-min.
are finished. The unit will not stroke with this valve Note: The illustration in Figure 78 shows a gauge port
closed. in the center of the main control block. Your main
concrete pump pressure gauge should be plumbed to
Setting boom circuit pressures that port
Note! Any time you set pressures for any circuit on any
unit, the hydraulic oil should be at normal operating
temperature (4060 C). Instructions on heating the
hydraulic oil are found in the first step of this
checking hydraulic pressures segment.
Read all of the instructions before beginning any pres-
sure settings. You will need an assistant for parts of the
procedure. You and any assistants should wear eye pro-
tection when setting pressures.

revDate
332 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
KVM 52M (pre-1998) As mentioned earlier before we check or adjusts
settings of the pressure limit valve or the two relief
valves, we must make sure the Delta-P and Q-
Pressure Settings for KVM 52 Proportional
minimum settings are correct.
Load Sensing
NOTE!
NOTE:All pressure settings must be done
when the hydraulic oil is at 50 to 70 degrees
Celsius.
Please read all instructions before attempting to check
or set pressures.
There is a pressure limit valve and two different relief
valves in the KVM 52 boom circuit. Before checking
or setting these 3 valves, you should make sure that the
Delta-P setting on the pressure regulator and the Q
minimum setting on the hydraulic pump are properly
set. In order to help you better understand this, we will
describe the functions of each valve and the hydraulic
pump before attempting to set or check pressures.
Refer to Illustration 3 on Page- E2 for the location of
each item as it is mounted on the unit.
Figure 1 of this page, is called the pressure regulator.
Adjusting screw (item 4) is the pressure limit function
of the pressure regulator. Adjusting screw (item 3) is
the Delta-P function of the regulator. The Delta-P
function senses pressure on both sides of the boom
control blocks, and adjusts the output flow of the
hydraulic pumps.
Figure 2 of this page is the "normally open" relief
valve. (Normally open denotes that unless the coil is
energized, the relief valve will not develop any
pressure). This is the valve that opens and vents your
boom circuit to tank when you hit the red emergency
shut off button on your remote control box or
operations panel.
Figure 3 of this page shows one of the two boom
control blocks. (Item 5) is pointing to the primary
relief valve located on the control block. It's function
is to protect the block from any pressure spikes that
might be in the system.
Figure 4 of this page is the boom circuit hydraulic
pump. This style of hydraulic pump has a variable
output depending on the requirements of the boom,
which is controlled by the pressure regulator described
in Figure 1 (above).
Figure 5 of this page is the pre-control block. (Item 6)
designates the gauge port. (Item 7) designates the 34
Bar pressure reducing valve. (Item 8) designates the
50 Bar pretension relief valve.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 333
HOME PRINT

Pressure Settings
Component Location Guide- KVM 52

FIGURE 2 FIGURE 4 FIGURE 1 FIGURE 3 FIGURE 5

KVM 52M

Illustration 3

item item 5
4

item 3 a6 b6
A6
T

FIGURE 1 a5 b5
A5 B5

item 2 a4
b4
24V A4 B4

FIGURE 2 FIGURE 3

item item
1 8
STOP for Q min

L
P
item
6

STOP for Qmax

item
7
FIGURE 4 FIGURE 5

Pressure Settings for KVM 52 Proportional is either Delta-P or an idle Q-minimum. To


Load Sensing determine what indeed is creating this pressure, we
1. .Delta-P setting on the pressure regulator. (Figure must do at least ONE of the three following
1, Item 3) procedures:
With all boom functions in the neutral position, a. .Back off the Q-min. screw at least 3 turns on
emergency stop buttons up, the engine at minimum the hydraulic pump to insure that it is only
RPM's (idle), the pressure that will be read on both producing the amount of flow that the regulator
the pretension gauge and the main pressure gauge is requiring to maintain Delta-P pressure. Now
revDate
334 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
read an accurate Delta-P pressure on either the
pretension gauge or the main pressure gauge.
This requires that the Q-min. be re-adjusted;
(refer to paragraph 2. for Q minimum setting).
b. While observing the pretension or the main
pressure gauge you increase the engine RPM
by 300 RPM in 3 increments of 100 RPM
each, making sure that the pressure does not
increase. This will assure that you are indeed
observing accurate Delta-P. If the pressure
does increase, then the pressure observed is an
idle Q-min. and not a true Delta-P. You should
then follow the procedures in paragraph 1. A.
c. Install a high pressure (0-600 Bar) gauge in the
X port of the regulator with a "T" fitting.
While operating a boom function, monitor the
pressure between the main pressure gauge and
the gauge at the X port of the regulator. There
should be exactly 20 Bar less pressure at the X
port continuously.
Adjusting Delta-P: The Delta-P pressure should be 20
Bar, plus or minus 1 Bar; (this is the same for KVM 32,
KVM 36 X, KVM 42 and KVM 52 machines). If the
Delta-P pressure is incorrect, then the regulator must
be adjusted accordingly. Turn the small screw (Figure
1, item 3) on the regulator inward to increase or
outward to decrease the Delta-P pressure. If Delta-P
pressure cannot be adjusted to proper pressure, the
regulator may be defective.
2. Q Minimum setting: the Q minimum stop on the
hydraulic pump, (Figure 4, item 1).
With all boom functions in the neutral position,
emergency stop buttons up, the engine at
maximum specified RPM's, the pressure on the
main gauge (0-600 bar) should be:
a) KVM 32 & 36 = 40 Bar;

b) KVM 42 = 40-45 Bar;

c) KVM 52 = 50-55 Bar.


If the pressure is incorrect, the Q-min. screw on the
hydraulic pump must be adjusted accordingly. Turn
the Q-min screw inward to increase the pressure and
outward to decrease the pressure.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 335
HOME PRINT

Pressure Settings
Pressure Regulator Cutaway KVM 52

Pressure
Regulator

P
Regulator

X
A T

P 0.8 mm
NOTE:
NO ORIFICE
USED ON KVM 52

revDate
336 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Pressure Settings for Regulator and Releif Setting Pretension Pressure(Refer to
Valves KVM 52 Figure 5)
Now that we know our delta-P and Q-minimum are set a. To set the pretension pressure, install a 0-250
correct we can check and reset the pressure limit and Bar gauge and connection hose on the gauge
two relief valves. The correct pressure settings are as port (item 6). Loosen the locknut on the
follows: pressure reducing valve (item 7), and turn the
adjusting screw inward approximately two
1) PRESSURE REGULATOR (Figure turns. This will raise the valves pressure
1, item 4)320 Bar higher than 50 Bar.
b. While holding a function pressured out, adjust
2) CONTROL BLOCK RELIEF (Figure the pretension relief valve (item 8), until the
3, item 5)350 Bar gauge reads 50 Bar.
c. Remove 0-250 Bar gauge, and install a 0-40
3) NORMALLY OPEN BYPASS VALVE
Bar gauge. With all boom functions in neutral
(Figure 2, item 2)360 Bar and engine at full rpms (this provides Q-Min),
In order to reset the valve with the highest pressure, we adjust the pressure reducing valve (item 7),
must first raise the pressure of the other two valves. until the gauge reads 34 Bar.
a. To set the pressure regulator (Figure 1), loosen (CAUTION!!! - do not activate any boom
the lock nut (Item 4), and turn the adjusting functions during this operation or damage
screw inward approximately two turns. This to the 0-40 Bar gauge will result).
will raise the pressure of this valve higher than
360 bar.
b. To set the control block (Figure 3), loosen the
lock nut (item 5), and turn the adjusting screw
inward approximately one turn. This will raise
the relief pressure higher than 360 Bar.
c. Pressure out any boom section. The pressure
can now be read on the 0-600 Bar gauge that is
near the control blocks. The gauge should read
360 Bar. If not, adjust the normally open
bypass valve, (Figure 2, item 2). After you
have this relief set to 360 Bar, you can lock the
locknut and move on to the control block
relief. (Be careful not break off the electrical
connections or over-torque the locknuts on this
valve.
d. While you continue to hold a function
pressured out you can adjust the control block
relief valve (Figure 3, item 5), until the
pressure gauge now reads 350 Bar. After this
pressure is set and the locknut is locked,
proceed to the pressure regulator.
e. While still holding a function pressured out
you can now adjust the pressure regulator (Fig.
1, Item 4), until the pressure gauge reads 320
Bar. When this pressure has been set and the
locknut is locked, you are finished setting the
main circuit pressures on the boom.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 337
HOME PRINT

Pressure Settings
Control Block 1 for KVM 52 Boom 3, Boom 4, & Slewing

52 METER CONTROL BLOCK 1


BOOM 3, BOOM 4, SLEWING

a3 b3
A3 B3 BOOM #3
BOOM DOWN TIME
SPEED ADJUSTMENT a2 b2
A2 B2 BOOM #4

a1
b1
A1 B1 SLEWING

BOOM UP TIME
SPEED ADJUSTMENT

A1-A3 B1-B3

SLEWING RELIEF-190 BAR SLEWING RELIEF-190 BAR


BLEED SCREW BLEED SCREW

T
a1-a3 b1-b3
P

revDate
338 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Control Block 2 for KVM 52 Boom 1, Boom 2, & Outriggers

52 METER CONTROL BLOCK 2


BOOM 1, BOOM 2, OUTRIGGER

350 BAR PRIMARY RELIEF

a6 b6
A6
OUTRIGGER

a5 b5
A5 B5 BOOM #1

a4
b4
BOOM DOWN TIME
A4 B4 BOOM #2
SPEED ADJUSTMENT

BOOM UP TIME
SPEED ADJUSTMENT

A4-A6 B4-B6

BLEED SCREW BLEED SCREW

T
a4-a6 b4-b6
P

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 339
HOME PRINT

Pressure Settings
Pre-Control Block 1-A for KVM 52

52 PRE-CONTROL BLOCK 1-A


FILTER

PRETENSION RELIEF
O-ring
50 Bar

Filter

O-ring

Orifice
NOT USED

24V
L

PV (PST)

24V

PRESSURE
REDUCING
NOTE: 34 Bar
GAUGE PORT FOR CHECKING THESE PRESSURES
IS ON THE PRE-CONTROL BLOCK 2-A.

revDate
340 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Pre-Control block 1-B for KVM 52

52 PRE-CONTROL BLOCK 1-B

24V 24V 24V

TOP VIEW
b3 b2 b1

a1- #3 Boom Extend


b1- #3 Boom Retract
b3 b2 b1
a2- #4 Boom Extend INPUT INPUT INPUT
b2- #4 Boom Retract
a3- #1 Boom Extend
b3- #1 Boom Retract

24V 24V 24V

PV

BOTTOM VIEW
REXROTH a1 a2 a3
M10-100S

a1 a2 a3
INPUT INPUT INPUT

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 341
HOME

342
PRINT

Pressure Settings

52 PRE-CONTROL BLOCK 1-C


PART # 995 120 002 651 (Complete)
Pre-Control Block 1-C for KVM 52

PV
(PST)

50

Service Manual
BAR

34
BAR

P L b1 b1 a1 a1 b2 b2 a2 a2 b3 b3 a3 a3

revDate
HOME
PRINT

52 PRE-CONTROL BLOCK 2-A


b4- #2 Boom retract a4- #2 Boom Extend
b5- Slewing - Right a5- Slewing Left

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


b6- Outriggers

SIDE VIEW TOP VIEW SIDE VIEW


Pre-Control Block 2-A for KVM 52

Service Manual
24V 24V 24V 24V 24V 24V 24V

PV PV
SERVICE TRAINING

(PST) (PST)
b4 a4 b5 a5 b6

L REXROTH L
Quick
M10-1006
Gauge
Port

b4 a4 b5 a5 b6
INPUT INPUT INPUT INPUT INPUT
Pressure Settings

343
HOME

344
PRINT

Pressure Settings

52 PRE-CONTROL BLOCK 2-B


PART #995 120 003 651 (Complete)
Pre-Control Block 2-B for KVM 52

PV (PST) PV (PST)
GAUGE PORT

L X L

Service Manual
b4 b4 a4 a4 b5 b5 a5 a5 b6 b6

revDate
HOME PRINT
SERVICE TRAINING
Pressure Settings
Electric Bypass Valve for KVM 52

52 METER ELECTRIC BYPASS


360 Bar RELIEF

A A
360 Bar

CAUTION: OVER TIGHTENING WILL CAUSE


DAMAGE TO THE VALVE!
24V 24V
TORQUE VALUES:

PRESSURE ADJUSTMENT
15 FT.LBS.

LOCK NUT
7.5 FT.LBS.
CARTRIDGE(COMPLETE)
37 FT.LBS.

Y X

A A A

SAI ITEM#
(Cartridge Only)
B 10055188

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 345
HOME PRINT

Pressure Settings

revDate
346 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
S 52 SX 2. Activate the agitator. With the valve closed, the
agitator will not be able to turn and the oil will be
forced over the relief valve. At an idle (about 600
Setting Pressures RPM), 4.5 horsepower is being converted to heat.
The following pages provide the proper techniques for 3. When the oil temperature gauge shows 50C, open
checking and setting hydraulic pressures of each the shutoff valve.
system included on your unit. Agitator quarter turn
000174.eps

shutoff valve (open position)

Check and adjust all hydraulic pressures


Changes in pressures can indicate trouble in one or Figure 79
more components. The specifications for each circuit Agitator shutoff
are shown on the hydraulic schematics found in the valve Motor
Appendix of this manual. The hydraulic schematics are
the only documents in this manual that have been
updated specifically for your unit by the serial number,
so in each of the following procedures you will be told
to refer to the schematic for the pressure required.
If you wish to order a CD ROM which explains the
pressure setting procedure for a specific model (All
pumpkits), call SAI Spare Parts Department at (800)
328 - 9635 and request the CD using the following part
numbers:
61/58 meter. . . . . . . . . . . . . . . . . . . . . . . 30365860
52 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30354732
45/47 meter. . . . . . . . . . . . . . . . . . . . . . . 30356770
42 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30355485
39 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30365861
34 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30356772
32 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30355486
31 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30365862

Preheat the hydraulic oil


Pressure settings must be made with the oil at normal
operating temperatures (40 60 C). In the past we
could pressure out a function in the boom or outrigger
system to create heat, but load sensing systems no
longer allow maximum oil flow to be forced over relief.
Because of this the agitator circuit must be used to heat
the hydraulic oil.
To preheat the hydraulic oil:
1. Locate the agitator shutoff valve (Figure 55) and
close it.
NOTE!
If your unit does not have a shutoff valve,
order one from the Schwing Spare Parts
Department using part number 10004680
(valve) and number 30303432 (tube). Con-
tact the Service Department for installation
instructions.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 347
HOME PRINT

Pressure Settings
Setting pressures on Hi-flo -6 pumpkits shutoff valve and the concrete pump shutoff valve
To set the pressure of the main relief valve on (Figure 56), do so at this time.
Hi-flo pumpkits, you must first disable the soft 5. At the Vector controller, select local control with
switch circuit. Simply locate the ball cock the local/remote switch, and activate the electric
shutoff for the soft switch circuit (Figure 56), stroke limiter switch to maximum strokes per
and close it by rotating the handle 90 degrees. minute.
The quarter turn shutoff valve for the concrete 6. The main system control block pressure must be
pump (Figure 56) will also need to be closed set first to properly set the pressure cutoff on both
during this procedure. pumps. Begin by backing off the jam nut of the
NOTE! main relief cartridge (Figure 58) with a 9/16 inch
wrench.
Main system adjustments are preset at the
factory. The following procedure begins 7. Using a 5/32 inch allen key, turn the adjustment
with adjustment of the main relief cartridge screw out (counterclockwise) until you can feel no
and pressure cutoff. If proper pressures can spring tension on the adjustment screw.
not be obtained through these steps, contact
the Schwing Service Department for specific 8. Now, turn the screw back in (clockwise) two or
instructions on the adjustment of flow, three full turns to give you a proper starting point,
horsepower, beginning of stroke regulation and tighten the jam nut.
and Q-min.
9. Stop the truck engine, and put the key in your
Pressure setting procedure: pocket. Adjust the pressure cutoff screw (Figure
57) on each pump by backing off the jam nut with
Soft switch a 13mm wrench. Using a 4mm allen key, turn the
shutoff valve adjustment screw in (clockwise) one full turn, and
tighten the jam nut. Restart the truck engine.
Main Pressure
Gauge port 10. Adjust the engine RPM to maximum specification.
(See decal in truck cab)
11. Pressure out the system by activating the concrete
pump forward switch on the rear panel. Using the
rear panel controls will allow you to read the
Concrete pump
shutoff valve 00
02
concrete pump main system pressure gauge, near
74
.e
ps
the e-stop manifold, from a safe distance.

Figure 80 NOTE!
Concrete pump and Soft switch shutoff Because you turned out the pressure relief
cartridge in step 7, the system pressure
1. Be sure that the waterbox covers and guards are in should read low at this time. If it does not,
place any time you will be working in the area and the gauge spikes to 320 bar or more,
disengage the pump immediately. Turn the
around the main control block. relief cartridge out (counterclockwise)
2. Wear safety glasses when working around a more. For safety, it is important to adjust
concrete pump. the pressure up from below the specified
target pressure rather than down from a
NOTE! pressure which exceeds the target. Continue
It is vital that each adjustment screw be this procedure until the main system pres-
properly identified prior to making any sure gauge reads lower than the specified
adjustment. All screw adjustments for the target.
system relief must be made with the pump- 12. To increase the pressure put the pump in the
kit in the neutral position, and adjustments neutral position, and adjust the relief cartridge by
for pressure cutoff must be made with the turning it in (clockwise). When increasing the
engine shut off.
pressure, the adjustments should be made in
3. Start the truck engine, and put the PTO in gear just
quarter turn increments. If you make adjustments
as you would to pump a job.
to increase the pressure but the pressure does not
4. If you have not already closed the soft switch come up, you are probably reading the pressure
revDate
348 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
cutoff of the pumps. If so, proceed to the next step; 16. Activate concrete pump forward to pressure out the
otherwise skip to step 15. Turn the relief cartridge pump, and read the pressure on the two gauges in
adjustment screw back out (counterclockwise) the M1 ports.
until you can no longer see a pressure drop, and 17. Always stop the truck engine and put the key in
tighten the jam nut. your pocket before making any adjustment on the
13. Stop the truck engine and put the key in your hydraulic pump. If the cutoff on one pump is set
pocket. higher than the other, that pump will be more
14. Go to the pressure cutoff screw on both hydraulic dominant. The pressure gauge in the M1 port of the
pumps (Figure 57), and back off the jam nut with a dominant pump will, however, read lower than the
13mm wrench. Turn the adjustment screws in with other. To equalize the two pumps, you must either
a 4mm allen key one or two more turns, restart the adjust the cutoff screw in (clockwise) to increase
engine, and check the pressure again. Repeat this the pressure of the pump showing the higher
procedure until the main system relief can be set to reading or adjust the cutoff screw of the dominant
the target pressure. pump showing the lower reading out
(counterclockwise) to reduce the pressure. These
15. When the proper main relief pressure is achieved,
adjustments must be made until the two gauges in
pressure cutoff can be set. Shut off the engine, put
the M1 ports are reading approximately the same.
the key in your pocket, and install 0-600 bar
gauges with whip hoses to the M1 gauge ports 18. When you have achieved the same pressure on the
on the bottom of the two hydraulic pumps (Figure M1 port gauges, you can begin to adjust the
57). You must be able to read both gauges pressure cutoff screws in or out simultaneously
simultaneously to ensure that one pump is not until you achieve the desired pressure setting of
more dominant than the other. 350 bar (again, confirm the pressure specification
with the hydraulic schematic).
NOTE!
19. After pressure cutoff is set, return the pump to
The gauges in the M1 ports will read consid-
erably less than the cutoff pressure of the neutral, bring engine RPM to idle, open the soft
pump. On a -6 (190/130 pump combina- switch quarter turn valve, and either proceed to
tion), the 190 will usually read 85 to 90 bar, other pressure settings or take the transmission and
while the 130 reads about 110 bar. They PTO out of gear and shut off the truck.
could read the same, however, at approxi-
mately 110 bar, but the 190 must never read
higher than the 130. The actual cutoff pres-
sure will be read on the concrete pump main
system pressure gauge near the e-stop mani-
fold.

000277.eps

1 Stroke Regulation 2 Pressure Cut Off


3 Horse Power 4 Q-Min

2
2
3
1 1
3
4 4

Figure 81
A11VO adjustment screws M1 GAUGE PORT
for Hi-flo 6 units 190/130 (BOTTOM OF EACH PUMP)

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 349
HOME PRINT

Pressure Settings

Soft switch
shutoff valve Closed Open

Main Pressure soft switch


Gauge port relief cartridge
Main relief cartridge

000276.eps
9/16" jam nut

Concrete pump 5/32" Allen head


shutoff valve 00
02
74
.e
ps
9/16" jam nut

Figure 82
Soft switch components

Setting the soft switch relief pressure Load-sensing boom hydraulic controls
First, open the soft switch quarter turn valve (Figure This unit is equipped with a load-sensing, proportional
58, right) that you closed in the previous procedure. boom hydraulic system. In a black-and-white system,
The rest of the unit should still be set up as if you were the hydraulic pump puts out an unchanging amount of
going to check the main relief valve pressure (concrete oil, and speed control is done by restricting the oil to
pump shutoff valve still closed). certain functions with orifices. In a load-sensing
When you put the pump in forward now, the main system, the pump puts out more or less oil to respond
concrete pump pressure gauge should read the pressure to the needs of the system. Generally, the pump puts
shown on the schematic for soft switch. If adjustment out enough oil to maintain 20 bar higher pressure at the
is needed, loosen soft switch relief valve jam nut pump than the cylinders actually require. This 20 bar is
(Figure 58 right) with a 9/16 open end wrench, and use called delta P (P). Additionally, we set the hydraulic
a 5/32 allen key to adjust the pressure. Turn the pump so that it always puts out a small amount of oil,
adjustment screw in (clockwise) to raise the pressure or even if no oil is needed for the system. This oil is used
out (counterclockwise) to lower the pressure. When to ensure that you have control when you need it. The
you attain the required pressure, tighten the jam nut setting to maintain this minimum amount of oil is
while holding the allen key to keep the pressure from called Q-min (pronounced cue min). To set the boom
rising. Be sure to open the concrete pump shutoff valve or outrigger hydraulic pressures on a load-sensing
on the side of the brain (Figure 58, left) when you are system, begin by setting P and Q-min.
finished. The unit will not stroke with this valve closed. Note: The illustration in Figure 58 shows a gauge port
in the center of the main control block. Your main
Setting boom circuit pressures concrete pump pressure gauge should be plumbed to
Read all of the instructions before beginning any that port.
pressure settings. You will need an assistant for parts of
the procedure. You and any assistants should wear eye
protection when setting pressures.
WARNING
NOTE!
Any time you set pressures for any circuit
on any unit, the hydraulic oil should be at Entanglement hazard. Stop drive shafts
000004.eps

normal operating temperature (4060 C). before adjusting Delta P on A11VO pump.
Instructions on heating the hydraulic oil are
found in the first step of this checking
hydraulic pressures segment.

revDate
350 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

gauge ports
for Delta P

Figure 83
Gauge ports for setting Delta P
delta/p.eps

Setting Delta P pressure


NOTE! Delta-p
Do not adjust Delta P or Q-min if your
boom is running as you like it. The pressure
setting procedure uses a standard starting
point and must be fine tuned from that
point. The pressure was fine tuned at the
factory and should not be adjusted unless
absolutely necessary.
1. Start by turning off the engine and putting the key
in your pocket; then place a Do Not Operate sign 000281.eps

on the windshield of the truck. Figure 84


2. Install a 0-400 bar gauge in the high pressure test Pressure regulator for A11VO pumps
port at the bottom of the boom control block
(Figure 16). 7. When the proper Delta P is achieved, use the
3. Install a second 0-400 bar gauge (Figure 16) in the following spaces to document the pressure.
port marked LS (load-sensing). NOTE!
4. Delta P is adjusted on the pressure regulator Remember that the documented Delta P
(Figure 43) if your unit has an A11VO boom pressure applies only to the unit with the
pump. When all personnel are clear of the truck, serial number shown in the front of this
restart the engine, engage the pumps, and increase book.
the engine speed to max RPM.
5. Activate any boom cylinder to maximum speed Date__________________ P__________bar
and read both gauges as the boom section moves. Date__________________ P__________bar
The difference between the two pressures should
be 20 bar + or - 5. Date__________________ P__________bar
6. If adjustment is required, loosen the jam nut, and Date__________________ P__________bar
adjust the screw inward to increase pressure or Date__________________ P__________bar
outward to decrease pressure until the boom runs
smoothly.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 351
HOME PRINT

Pressure Settings
If pressure cannot be set correctly, there is a problem NOTE!
with the regulator itself. Contact the Schwing Service If you dont have a 0-100 bar gauge, you can
Department to determine how to continue. order one from Schwing Spare Parts
Department at (800) 328-9635, part #
If the boom does not run smoothly at 20 bar, you must 10004659.
fine tune the adjustment. Remove the gauge, and turn
the P adjustment screw until the boom is responsive
and smooth. After adjusting, the difference between the
gauges (reinstalled) must read between 14-25 bar. The
electronics in the control system can also affect how
the boom operates, so if P adjustment does not seem Boom pressure
relief cartridge
to help, reset to 20 bar and check the electrical settings.
When the electrical settings are verified, you could
again try to refine the boom action with the P
adjustment.
ps
lf.e
ssr
pre

0-600 bar
WARNING gauge port

Wear safety glasses any time you check


000438.eps

or set pressures. Oil expulsion hazard!

Figure 85
0-600 bar gauge port
Setting Q-min
Check Q-min when the engine is at maximum specified
RPM. You must not adjust Q-min with the drive
shafts turning! Each time the Q-min screw must be
adjusted, the engine must be stopped, or at least the
transmission must be taken out of gear so that the
drivelines stop turning.
1. All boom functions must be in neutral, and all Delta-p Pressure Cut-off
emergency stop buttons should be up (not
engaged). Clear away all personnel, start the truck
engine, engage the pumps, and bring engine RPM
to max. Read the pressure at the 0600 bar main
boom gauge port (Figure 124) with a 0-100 bar
gauge. Pressure should be at 4045 bar. If no
adjustment is needed, be sure the jam nut on the
Q-min screw is tight, then continue to set the rest
of the boom and outrigger pressures. If adjustment
is needed, continue to the next step. 000282.eps

2. Turn the Q-min screw (Figure 125) in to raise the Q-min Q-max (Bottom Of Pump)
pressure. Turn it out to lower the pressure. Be sure
that you stop the drive shafts from turning each
time before making the adjustment. When pressure Figure 86
is correct, tighten the jam nut on the adjustment Location of Q-min screw
screw before continuing with the other procedures;
then, recheck P to make sure that it hasnt
changed during the Q-min adjustment.

revDate
352 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Setting boom pressures
Now that P and Q-min are set, you can remove the 0-
100 bar pressure gauge and proceed to check and
adjust the main boom pressures.

Setting main pressure


1. The main pressure is the highest pressure of the
three boom system settings. The only way you will
be able to see the main pressure on the gauge is to
turn the pressure of the two lower systems up to a
level which is higher than that of the main pressure
relief valve.
2. Loosen the jam nut of the boom pressure relief
Disconnect hose
cartridge (Figure 126) with a 30mm open end hose1.eps

wrench, turn the adjustment cartridge in all the


way with a 32mm wrench, and lock the jam nut Figure 88
back down. Hose for boom section number two

Plugs Straight Fitting

Boom pressure
relief cartridge
Figure 89 000257.eps

Approved dead
plugs Cap Nuts
ps
lf.e
ssr
pre

0-600 bar 6. Install a 0 - 600 bar gauge in the main pressure


gauge port gauge port (Figure 129).
7. Increase the engine speed to maximum RPM, and
activate the manual control handle for boom
number two in the direction that will pressurize the
Figure 87 disconnected and plugged hose.
Boom pressure relief cartridge
8. Now adjust the pressure to the setting found on the
schematic by turning the main boom pressure relief
3. Loosen the jam nut on the pressure cut-off screw cartridge on the boom control block (Figure 129)
(Figure 131), tighten the screw all the way down, with a 4mm allen key. Read the pressure on the 0-
and tighten the jam nut back down. 600 bar gauge installed in step 6. When desired
4. Identify the main boom pressure relief cartridge on pressure is achieved, lock down the jam nut with a
the control block (Figure 129), loosen the jam nut 12mm wrench.
with a 12mm wrench, then unscrew the adjustment
Setting boom pressure (redundant) relief
two full turns with a 4mm allen key.
9. Return to the e-stop manifold boom pressure relief
5. Setting the main pressure will require cartridge (Figure 126), and back off the jam nut
disconnecting a hose for boom section number two (30mm). Turn the cartridge (32mm) out, or counter
(Figure 127) and installing an approved dead plug clockwise, until the pressure gauge reads the
on each of the open fittings. number shown on the schematic for the boom
pressure relief cartridge. Lock down the jam nut.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 353
HOME PRINT

Pressure Settings
Setting pressure cut-off
Delta-p Pressure Cut-off
10. Return to the pressure cut-off screw (Figure 131).
Back off the jam nut, and turn the screw counter
clockwise until you achieve the pressure shown on
the schematic, then lock the jam nut.

Setting slewing pressure


11. The slewing function has two relief valves which
must be set individually. Since there is no way to
block the slewing function, it is also necessary to
disconnect the supply hoses which go to the
slewing motor one at a time and install an approved 000282.eps

dead plug to the open fitting. Q-min Q-max (Bottom Of Pump)


12. Install a 0 - 600 bar gauge in line on the open hose.
Figure 92
Pressure cut-off screw
14. The final boom pressure setting is the #1 boom
Gauge Main piston side relief setting. The relief cartridge is
port relief
shown in Figure 64. This procedure should be
performed with the outriggers extended and the
boom unfolded over the cab. Extend section #1 all
the way until the cylinder bottoms out. Install a 0-
600 bar gauge in the gauge port shown in Figure
129. Activate boom #1 extend. The pressure should
read 230 bar. If adjustment is required, back off the
jam nut with a 12mm wrench, and turn the relief
cartridge (Figure 64) in or out using a 4mm allen
mainrlf.eps key as required until the desired pressure is
Figure 90 achieved; then, lock down the jam nut.
Main boom control block
13. Activate the slewing handle in a direction which
will pressurize the disconnected hose and read the
gauge. If the pressure is not what the schematic
calls for, adjust the appropriate relief valve located
directly under the valve (Figure 130).

dwnsdrlf.eps

Figure 93
Piston side relief

NOTE!
Figure 91
HWslew.eps If you are unable to achieve 230 bar by
Boom slewing adjusting the relief valve in Figure 64, call
Boom Slewing
relief valves relief valves the Schwing Service Department and ask if
the unit has a redundant relief valve.

revDate
354 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Setting outrigger pressure Setting the agitator pressure
The agitator circuit has a maximum pressure shown on
WARNING the hydraulic schematic, which is limited by the relief
cartridge (Figure 50) in the agitator hand valve. The
Tipping hazard. Never set outrigger relief cartridge is located on the back side of the
pressures with the boom unfolded. agitator manual control handle (Figure 50). The
Pressure setting procedure requires cartridge is adjustable with just a 19mm open end
retraction of an outrigger jacking wrench.

000359.eps
cylinder. 1. Plug the 0600 bar whip gauge into the gauge port
(Figure 50) for checking or setting agitator pres-
After the boom circuit is properly set, you can set the sure.
outrigger pressure. Find the relief cartridge 2. Locate the agitator shutoff valve (Figure 67), and
located on the front of the passenger side outrigger close it. If your unit does not have a shutoff valve,
control valve (Figure 48). order one from the Schwing Spare Parts Depart-
1. Attach 0-600 bar whip gauge to the gauge port ment using part numbers 10004680 (valve) and
below the outrigger valve bank. 30303432 (tube). Contact the Service Department
2. Push the outrigger enable button. for installation instructions. If you cant wait for a
shutoff valve, you will need to remove one of the
3. Activate an outrigger jacking cylinder to retract.
hoses from the agitator motor and plug the hose
By retracting a fully retracted cylinder, the oil
and open fitting with approved hydraulic dead
coming from the pump has nowhere to go but over
plugs (Figure 68).
the relief valve. You cannot use an extension or
slewing cylinder because they have secondary NOTE!
relief functions (nonadjustable) built into the valve. Do not jam the paddles to force the oil over
While holding the handle to retract, read the relief by stopping the movement of the
pressure gauge. agitator.
4. The pressure should read the bar value shown on 3. Increase the throttle to any speed above idle. Acti-
the hydraulic schematic. Adjust by loosening the vate the agitator valve handle in either forward or
jam nut and turning the cartridge (Figure 48) in or reverse, and read the gauge. If it does not read the
out. When the proper pressure is achieved, let go of specified pressure, adjustment is required. Turn the
the handle, and release the outrigger enable button. entire relief valve cartridge (Figure 50) in to
increase pressure or out to decrease pressure.
4. When the pressure is set, deactivate the agitator by
placing the manual control handle in the neutral
position.
5. Remove the whip gauge.
6. Reopen the shutoff valve or remove the dead plugs,
Outrigger valve and reconnect the capped hydraulic line.
Agitator Relief Valve Turn body of valve
relief cartridge Gauge port Higher
to adjust.

Lower

ps
2.e
itrlf
ag

otrigrlf.eps

Figure 95
Figure 94 Agitator relief cartridge located on
Outrigger valve bank relief cartridge back side hand valve

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 355
HOME PRINT

Pressure Settings

000174.eps
Agitator quarter turn
shutoff valve (open position)

Motor

Figure 96
Agitator shutoff valve
000289.eps

Plugs Straight Fitting

Accumulator pump
Figure 97 pressure regulator
000257.eps
Approved hydraulic
dead plugs
Cap Nuts
Figure 98
Accumulator pump pressure regulator for
A7VO (above) and for A11VO on a unit
Setting accumulator circuit pressure with a stiebel gearcase (below)
To check or adjust the hydraulic pressure in the
accumulator circuit:
1. Stop the truck, put the key in your pocket, and
Boom Pump
place a Do Not Operate sign on the windshield.
Accumulator Pump
2. Loosen the jam nut on the pressure regulator of the
accumulator hydraulic pump (Figure 51). Turn the
screw in two-and-one-half turns. This will raise the
regulator pressure above 300 bar.

Accumulator Pump
Pressure Regulator
Standby 000446.eps

Pressure Screw hgacugc.psd

revDate
356 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

000449.eps

Manual bleed
Boom pressure valve
relief cartridge

ps
lf.e
ssr
pre

0-600 bar Pressure relief


gauge port cartridge

Figure 99
New e-stop has no redundant Figure 101
relief cartridge. Accumulator manifold pressure
relief cartridge

3. Clear all personnel away from the drive lines, start


the truck engine, engage the pumps, and bring the 5. Locate the accumulator manifold pressure relief
engine RPM to maximum. cartridge (Figure 54). Loosen the jam nut, and turn
the screw clockwise to increase the pressure or
4. Read the pressure on the accumulator circuit pres-
counterclockwise to decrease the pressure. Tighten
sure gauge (Figure 53). The pressure should read
the jam nut when the pressure reaches the value
the value shown on the hydraulic schematic. If no
required.
adjustment is needed, skip to step number 7. If
additional pressure adjustment is needed, continue
with step number 5.
000292.eps

Figure 100
Accumulator circuit pressure gauge

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 357
HOME PRINT

Pressure Settings

WARNING
Entanglement hazard. Stop drive shafts
before adjusting the accumulator pump

000075.eps
pressure regulator.

6. After the truck engine is stopped, go back to the


accumulator circuit hydraulic pump pressure regu-
lator (Figure 51), and turn the screw back out two-
and-one-half turns. This restores it to its original
setting.
7. Clear all personnel from the drive line area, start
the truck, and bring the engine RPM up to maxi-
mum.
8. Read the pressure on the accumulator gauge. It
should read the proper accumulator system pres-
sure.
9. If adjustment is needed, you must stop the truck
engine, or a least stop the drive lines from turning,
each and every time you approach the accumulator
circuit hydraulic pump. Turn the screw in to
increase the pressure or out to decrease pressure.
Lock the jam nut when the pressure is correct.

Note: The accumulator circuit hydraulic pump pressure


regulator is referred to as the pressure cut-off.

revDate
358 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
KVM 52M replaced in a different configuration the grooves in
the handle may no longer indicate the proper open/
Preheat the hydraulic oil. Pressure settings must be closed orientation of the valve. The grooves in the
made with the oil at normal operating temperatures shaft give the only true indication of the valves
(50 to 60 C). In the past we could pressure out a position.
function in the boom or outrigger system to create heat, Note! If your unit is an early production model,
but today, load sensing systems no longer allow and does not have an agitator shutoff valve, order
maximum oil flow to be forced over relief. Because of one from the Schwing Spare Parts Department,
this, the agitator circuit must be used to heat the using part number 10004680 (valve) and number
hydraulic oil. 30303432 (tube). Contact the Service Department
To heat the oil to operating temperature: for installation instructions.
1. Locate the agitator shutoff valve (Figure 102) and 2. Activate the agitator. With the valve closed, the
close it. The quarter turn shutoff valve has a agitator will not be able to turn and the oil will be
grooved line (Figure 102) on the shaft or pivot forced over the relief valve. At an idle (about 600
point of the handle as well as on the handle itself, RPM) you will be converting 4.5 horsepower to
which will indicate the open or closed heat.
configuration of the valve. If the handle is removed 3. When the oil temperature gauge shows 50 C, open
from the agitator shutoff valve (Figure 102) or the the shutoff valve.
concrete pump shutoff valve (Figure 103) and

agitoff.eps

Agitator quarter turn


shutoff valve (open position) Motor

Figure 102
Agitator shutoff valve (left) and Open/closed orientation of shutoff valve (right)

Setting relief pressure and pressure cutoff


on Hi-flo -6 pumpkits
a. To set the pressure of the main relief valve on
Hi-flo pumpkits, you must first disable the soft
switch circuit. Simply locate the ball cock for
the soft switch circuit (Figure 56) and close it
by rotating the handle 90 degrees.
b. The quarter turn shutoff valve for the concrete
pump (Figure 103) will also need to be closed
during this procedure.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 359
HOME PRINT

Pressure Settings

Soft switch
shutoff valve

Main Pressure
Gauge port
Figure 103
Concrete pump and Soft switch shutoff
valves

Concrete pump
hif
shutoff valve low
br
n.
ep
s

Note: Main system adjustments are preset at the 8. Now, turn the screw back in (clockwise) two or
factory. The following procedure begins with three full turns to give you a proper starting point
adjustment of the main relief cartridge and pressure and tighten the jam nut.
cutoff. If proper pressures can not be obtained through 9. Stop the truck engine, put the key in your pocket
these steps, contact the Schwing Service Department and adjust the pressure cutoff screw (Figure 104)
for specific instructions on the adjustment of flow, on each pump, by backing off the jam nut with a
horsepower, beginning of stroke regulation and Q-min. 13mm wrench. Using a 4mm allen wrench, turn the
Pressure setting procedure: adjustment screw in (clockwise) one full turn and
1. Be sure that the waterbox covers and guards are in tighten the jam nut. Restart the truck engine.
place any time you will be working in the area 10. Adjust the engine RPM to maximum specification.
around the main control block. (See decal in truck cab)
2. Wear safety glasses when working around a 11. Pressure out the system by activating the concrete
concrete pump. pump forward switch on the rear panel. Using the
Note! It is vital that each adjustment screw be properly rear panel controls will allow you to read the
identified prior to making any adjustment. All screw concrete pump main system pressure gauge, near
adjustments for the system relief must be made with the e-stop manifold, from a safe distance.
the pumpkit in the neutral position and adjustments for Note: Because you turned out the pressure relief
pressure cutoff must be made with the engine shut off. cartridge in step 7, the system pressure should read low
3. Start the truck engine, and put the PTO in gear just at this time. If it does not and the gauge spikes to 320
as you would to pump a job. bar or more, disengage the pump immediately. Turn the
4. If you have not already closed the soft switch relief cartridge out (counterclockwise) more. For
shutoff valve and the concrete pump shutoff valve safety, it is important to adjust the pressure up from
(Figure 103) do so at this time. below the specified target pressure rather than down
from a pressure which exceeds the target. Continue this
5. At the rear panel, select local control with the
procedure until the main system pressure gauge reads
local/remote switch and turn the electric stroke
lower than the specified target.
limiter knob clockwise to maximum strokes per
minute. 12. To increase the pressure put the pump in the
6. The main system control block pressure must be neutral position and adjust the relief cartridge by
set first to properly set the pressure cutoff on both turning it in (clockwise). When increasing the
pumps. Begin by backing off the jam nut of the pressure, the adjustments should be made in
main relief cartridge (Figure 104) with a 9/16 inch quarter turn increments. If you make adjustments
wrench. to increase the pressure but the pressure does not
7. Using a 5/32 inch allen wrench, turn the come up, you are probably reading the pressure
adjustment screw out (counterclockwise) until you cutoff of the pumps, if so proceed to the next step
can feel no spring tension on the adjustment screw. otherwise skip to step 15.Turn the relief cartridge

revDate
360 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
adjustment screw back out (counterclockwise) 16. Activate concrete pump forward to pressure out the
until you can no longer see a pressure drop and pump and read the pressure on the two gauges in
tighten the jam nut. the M1 ports.
13. Stop the truck engine, put the key in your pocket. 17. Always stop the truck engine and put the key in
14. Go to the pressure cutoff screw on both hydraulic your pocket before making any adjustment on the
pumps and back off the jam nut with a 13mm hydraulic pump. If the cutoff on one pump is set
wrench. Turn the adjustment screws in with a 4mm higher than the other, that pump will be more
allen wrench one or two more turns, restart the dominant. The pressure gauge in the M1 port of the
engine and check the pressure again. Repeat this dominant pump will however, read lower than the
procedure until the main system relief can be set to other. To equalize the two pumps you must either
the target pressure. adjust the cutoff screw in (clockwise) to increase
the pressure of the pump showing the higher
15. When the proper main relief pressure is achieved,
reading or adjust the cutoff screw of the dominant
pressure cutoff can be set. Shut off the engine, put
pump showing the lower reading out
the key in your pocket and install 0-600 bar gauges
(counterclockwise) to reduce the pressure. These
with whip hoses to the M1 gauge ports on the
adjustments must be made until the two gauges in
bottom of the two hydraulic pumps (Figure 105).
the M1 ports are reading approximately the same.
You must be able to read both gauges
simultaneously to ensure that one pump is not 18. When you have achieved the same pressure on the
more dominant than the other. M1 port gauges, you can begin to adjust the
pressure cutoff screws in or out simultaneously
Note: The gauges in the M1 ports will read
until you achieve the desired pressure setting of
considerably less than the cutoff pressure of the pump.
350 bar (again, confirm the pressure specification
On a -6 (190/130 pump combination) the 190 will
with the hydraulic schematic).
usually read 85 to 90 bar while the 130 reads about 110
bar. They could read the same however, at After pressure cutoff is set, return the pump to neutral,
approximately 110 bar, but the 190 must never read bring engine RPM to idle, open the soft switch quarter
higher than the 130. The actual cutoff pressure will be turn valve, and either proceed to other pressure settings
read on the concrete pump main system pressure gauge or take the transmission and PTO out of gear and shut
near the e-stop manifold. off the truck.

Main and soft switch


relief cartridges Closed Open
Concrete pump
soft switch
gauge port
relief cartridge
Main relief cartridge
openclsd.eps

9/16" jam nut

5/32" Allen head


ga
ug
pr
t.e
ps
9/16" jam nut

Figure 104
Location of soft switch shutoff and relief cartridges

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 361
HOME PRINT

Pressure Settings

130-6.eps

1 Stroke Regulation 2 Pressure Cut Off


3 Horse Power 4 Q-Min

2
2
3
1 1
3
4 4

M1 GAUGE PORT
(BOTTOM OF EACH PUMP)
Figure 105
A11VO adjustment screws for Hi-flo 6 units 190/130

NOTE: The main control block (brain) of a 2525 Set boom circuit pressures
pumpkit will be rotated 180 degrees from the NOTE! Any time you set pressures for any circuit on
illustration shown in Figure 57. any unit, the hydraulic oil should be at normal
operating temperature (50 to 60 C). Instructions on
Setting the soft switch circuit relief heating the hydraulic oil for this procedure are found in
pressure step on page 6-359.
a. If you havent already done so, open the soft
Please read all of the instructions before beginning any
switch quarter turn valve (Figure 104). The rest
pressure settings. You will need an assistant for parts of
of the unit should still be set up as though you
the following procedure. You and any assistants should
were going to check the main relief valve
wear eye protection when setting pressures.
pressure (concrete pump shutoff valve still
closed). Current production model 52 meter pumps are
b. When you put the pump in forward now, the equipped with a load sensing, proportional boom
pressure gauge should read the pressure shown hydraulic system. If the system were black and white,
on the schematic for soft switch. If adjustment the hydraulic pump would put out an unchanging
is needed, loosen the jam nut of the soft switch amount of oil and speed control is done by restricting
relief cartridge (Figure 57) with a 9/16 inch the oil to certain functions with orifices. With a load
open end wrench, and use a 5/32 inch allen sensing system, the pumps put out more or less oil to
wrench to adjust the pressure. Turn the respond to the needs of the system. Generally, the
adjustment screw in (clockwise) to raise the pump always puts out enough oil to maintain 20 bar
pressure or out (counter clockwise) to lower higher pressure at the pump than the boom cylinders
the pressure. When you attain the required actually require. This 20 bar is called delta P. You may
pressure, tighten the jam nut while holding the see it referred to by a symbol ( P). Additionally, we
allen wrench, to keep the pressure from rising. set the hydraulic pump so that it always puts out a
Be sure to open the concrete pump quarter turn small amount of oil, even if none is needed for the
valve on the side of the brain (Figure 57) when system. This oil is used to ensure that you have control
you are finished. The unit will not stroke with when you need it. The setting to maintain this
this valve closed. minimum amount of oil is called Q-min (pronounced

revDate
362 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
cue min). To set the boom or outrigger hydraulic
CAUTION! When checking Delta P, it is important to
pressures on a load sensing system, begin by checking note that you will be installing a low pressure gauge into
P and Q-min.t a high pressure port. Any activation of a boom function
or activation of an e-stop, while this gauge is attached
Checking and Setting P pressure will destroy your gauge. On Comfort control units,
Note! Do not adjust delta P or Q-min if your boom is always center the boom speed switch on the remote box
running as you like it. The pressure setting procedure to prevent accidental activation of a joy stick.
uses a standard starting point and must be fine tuned 1. Install a 0-100 bar whip gauge in the high pressure
from that point. The pressure was fine tuned at the test port (Figure 106) located on the inside of the
factory, and should not be adjusted unless absolutely right boom control block as you face the three
necessary. valve blocks.
rtblock2.eps

Figure 106
The high pressure gauge
port is located between the
blocks on the inside edge of
the right boom control

High pressure
gauge port

2. With the engine at idle, turn the adjustable relief turns. Remember exactly how much you move this
cartridge (Figure 107) on the boom pilot control cartridge because it will need to be returned to the
valve, out (counter clockwise) approximately three original position.

adjustable relief
cartridge
P
L

52pilot.eps

preset pressure
reducing valve

gauge port

Figure 107
Location of adjustable relief cartridge on the boom pilot control valve

3. With the engine running and the relief cartridge showing Delta P. The pressure could be anywhere
backed out, the gauge (Figure 16) should be from 16-25 bar.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 363
HOME PRINT

Pressure Settings
4. Increase the throttle RPM and the pressure should and adjusting the screw (3mm allen wrench)
remain the same. If the pressure fluctuates with clockwise to increase pressure or counter
engine RPM you are probably still reading Q-min, clockwise to decrease it.
and the adjustable relief cartridge (Figure 108) will 7. The delta P adjustment screw on the A11VO boom
need to be turned out more. pump also shown in Figure 43 below, requires a
5. If no further adjustment is needed, return the pilot 13mm open end wrench and a 4mm allen wrench.
valve relief cartridge to its original position. If 8. If no further adjustment is needed, return the pilot
adjustment is required, proceed to the next step. valve relief cartridge to its original position, and
6. Delta P is adjusted on the bottom (smaller) screw proceed to Q-min.
of the pressure regulator shown in Figure 108 9. If pressure cannot be correctly set, there is a
below, if your unit has an A7VO boom pump, by problem, contact Schwing Service Department to
loosening the jam nut (10mm open end wrench), determine how to continue.

Delta-p
pressreg.eps

Regulator pressure
adjustment

T
Adjustment for P pressure

smdeltap.eps

Figure 108
Location of the delta P adjustment screw for a unit with A7VO pump
(left) and A11VO pump (right)

Set Q-min

WARNING
Stop the engine before adjusting
the Q-min screw or Delta P on A11.
Driveline entanglement hazard!

Check Q-min with the engine at maximum specified 2. All boom functions must be in neutral, and all
RPM. Each time the Q-min screw must be adjusted, the emergency stop buttons should be up (not
engine must be stopped, or at least the transmission engaged). Clear away all personnel, start the truck
must be taken out of gear so that the drivelines stop engine, engage the pumps and bring engine RPM
turning. to maximum specification.
1. Before proceeding, remove the 0-100 bar whip 3. Read the pressure. If the pressure reads less than
gauge from the high pressure gauge port (Figure 100 bar, remove the high pressure gauge and
16) and install a 0-400 or 0-600 bar gauge to the reinstall the 0-100 bar gauge. Pressure should be at
same port, to make certain that the higher pressure 50-55 bar. If adjustment is needed, continue to
wont destroy your 0-100 bar gauge. point 4.
4. Stop the engine and turn the Q-min screw (Figure
109) in (clockwise) to raise the pressure, or out
(counter-clockwise) to lower the pressure. Be sure
that you stop the drive shafts from turning each
revDate
364 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
time before making the adjustment. When pressure Note! If you dont have a 0-100 bar gauge you can
is correct, tighten the jam nut on the adjustment order one from Schwing Spare Parts Department at
screw before continuing with the other procedures. (800) 328-9635, part #10004659.

Delta-p Pressure Cut-off


Q-min
adjustment screw

A7VX section min.top.eps

hifloreg.eps

Q-min Q-max (Bottom Of Pump) Q max


Figure 109
Location of Q-min screw on A11VO (left) and A7VO (right)

Checking boom pressures 3. Read the gauge. It should be showing the lowest
After the Delta P and Q-min are set, remove the 0-100 relief pressure setting of the boom circuit (pressure
bar gauge and proceed to check and adjust, if regulator or cutoff) + or - 5 bar (See schematic). If
necessary, the main boom pressures. it does not, a minor adjustment can be made by
going to the pressure regulator (large screw) for
1. To check the boom pressure, install a 0-600 bar units with A7VO pumps or after stopping the
gauge in the boom circuit high pressure gauge port engine, the pressure cutoff screw for units with
(Called out but not visible in Figure 110). A11VO pumps, backing off the jam nut and
2. With the engine at full RPM and the boom folded, turning the adjustment screw to achieve the desired
activate boom #2, #3, or #4 to the in position, pressure. If the pressure can not be reached, return
which will pressure out the function. A function the screw to the original setting and proceed to
must be pressured out each time you want to check Setting boom circuit pressures.
the pressure.
Down side dynamic
gauge port

Main boom pressure


gauge port (Hidden)

Figure 110
Main boom circuit high pressure gauge port
(not visible on illustration)

Main relief cartridge

lftblock.eps

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 365
HOME PRINT

Pressure Settings
Setting main boom circuit pressures 2. Since the gauge will always show you the lowest of
1. Review the hydraulic schematic and identify the the three settings, it is necessary to raise the two
three different pressure settings involved in this lowest pressures enough to allow us to see the
circuit. 1) Boom block main relief, 2) e-stop highest one, which will be the main relief at the
manifold relief, and boom block (Figure 111).
3) pressure regulator.
Down side dynamic
gauge port

Main boom pressure


gauge port (Hidden)

Figure 111
Main relief adjustment screw and gauge ports

Main relief cartridge

lftblock.eps

3. Loosen the jam nut on the large screw of the


pressure regulator or the pressure cutoff screw
(Figure 112), depending which one your unit has,
and turn the adjustment screw clockwise, all the
way in.
Delta-p Pressure Cut-off
pressreg.eps

Regulator pressure
adjustment

T
Adjustment for P pressure

hifloreg.eps

Q-min Q-max (Bottom Of Pump)

Figure 112
Pressure regulator adjustment (A7VO left) and Pressure cutoff screw (A11VO right)
4. Loosen the jam nut on the boom circuit relief If the pressure reading is still lower than the maximum
cartridge located on the e-stop manifold (Figure shown on the schematic, loosen the jam nut on the
113) using a 9/16 wrench and turn the adjustment control block main relief (Figure 111) adjustment
screw using a 5/32 allen wrench in until you can screw and turn the adjusting screw in. This will raise
see the maximum pressure of the boom block main the pressure of the main relief valve until the desired
relief showing on the gauge while pressuring out a pressure is achieved. Tighten the jam nut to secure the
boom function. adjustment screw.
revDate
366 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

;;;;
@@

 @@

@@;;


;; @@;;

 @@;@


@@;;


;; @@

 @@


;; @@


;; @@


;;
@@


;; @@


;;
52estp1.eps

@@;;


;; @@;;

 @@;;

 @@;;

 @@


;;
@@;;


;; @@

 @@


;; @@


;; @@


@@;;


;; @@;;

 @@;;

 @@;;

 @@


;;
@@;;


;; @@

 @@


;; @@


;; @@


@@


;; @@


;; @@


;; @@


;; @@


;;
@@


;;
QQ
 @@


;;
QQ
 @@


;;
QQ
 @@


;;
QQ
 @@


;;
Q;@
Figure 113
Boom circuit relief cartridge on e-stop  @@


;;
QQ @@


;;
QQ
 QQ

@@


;; @@


;;
QQ
 @@


;; @


;
Q

@@


;;
QQ
 @@


;;
QQ @@


;;
QQ @@


;;
QQ
 @@


;;
Q;@
manifold
@@


;;
QQ

@@


;; @@


;;
QQ

@@


;; @@


;;
QQ

@@


;; @@


;;
QQ

@@


;; @@


;;
@


;
Q

@@;;


;;
QQ

@@


;; @@;;


;;
QQ

@@

 @@


;;
QQ

@@

 @@


;;
QQ

@@


;; @@


;; @


;
Q
 ;@
@@


;;
QQ

@@


;; @@


;;
QQ

@@


;; @@;;


;;
QQ

@@


;; @@;;


;;
QQ

@@

 @@


;;
Q;@ ;@ @


;
@@


;;
QQ

@@


;; @@


;;
QQ

@@


;; @@


;;
QQ

@@


;; @@


;;
QQ

@@


;; @@


@


;
Q


@@relief

;;
QQ

@@


;; 
@@;;

;;
QQ

Boom
@@


;; 
@@

;;
QQ

@@

 
@@;;

;;
QQ

circuit
@@


;; @@


;; 
@

;
Q
 ;@
@@


;;
QQ
 @@


;;
QQ
 @@


;;
QQ
 @@


;;
QQ
 @@

 @


;
@@


;; @@


;; @@


;; @@


;; Q;@Q;@ ;@;@
@@


;;
cartridge
@@;;


;;
QQ

@@


;; @@;;


;;
QQ

@@

 @@;;


;;
QQ

@@

 @@;;


;;
QQ

@@

 @@


5. Now return to the boom circuit relief cartridge Checking pretension pressure
(Figure 113) and turn the adjustment screw back This procedure is to check the pretension pressure only.
out (counter-clockwise) until the second highest The pressure you will be reading is from the factory
pressure on the boom circuit schematic is achieved, preset pressure reducing valve (Figure 114) which can
and tighten the jam nut to secure the adjustment not be adjusted.
screw.
1. Install a 0-60 bar whip gauge on the gauge port of
6. Finally, return to the pressure regulator or pressure the precontrol block (Figure 114) and bring the
cutoff (Figure 112) and turn the adjustment screw engine RPM to full throttle. The gauge should read
out until the lowest pressure on the schematic is 33-35 bar. If the pressure reading is different than
achieved, and lock the jam nut. that, contact the Schwing Service Department for
instructions on how to proceed.

adjustable relief
cartridge
P
L

lrgpilot.eps

preset pressure
reducing valve

gauge port

Figure 114
Showing the precontrol valve gauge port and adjustment points

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 367
HOME PRINT

Pressure Settings
Set the outrigger pressure use an extension cylinder because they have
To set the outrigger pressure. Find the relief cartridge secondary relief functions (non-adjustable) built
(Figure 115) located on the passenger side outrigger into the valve. While holding the push-button and
control valve. activating either handle number 4 or 5 Figure 48, to
retract position, read the pressure on the gauge.
1. Attach 0-600 bar whip gauge to gauge port shown
in Figure 48. 4. Check the schematic to see what the pressure
should read. Adjust by loosening the jam nut with a
2. Push the outrigger button. 9/16 open end wrench and turning the cartridge
3. Activate an outrigger jacking cylinder to retract. with a 5/32 allen wrench. When the desired
By attempting to retract a cylinder which is already pressure is reached, let go of the handle and the
retracted the oil coming from the pump has no push-button.
where to go but over the relief valve. You cannot 5. Remove the whip gauge when the job is complete.
PScntrl#.eps

1 2 3 4
EXTEND FOLD - REAR FOLD - FRONT FOOT

Relief cartridge PULL PULL PULL PULL

Relief cartridge

Gauge port
Gauge port
1 2 3 4 5 otrgrlf2.eps

Outrigger controls after mid 1999


Outrigger controls prior to mid 1999
1. Front extend
1. Front extend
2. Rear fold
2. Rear fold
3. Front fold
3. Front fold
4. Rear foot
4. Foot
5. Front foot

Figure 115
Passenger side outrigger valve bank for units built after mid 1999 (left) and prior
to mid 1999 (right)

revDate
368 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Set the agitator pressure 1. Plug the 0 - 600 bar whip gauge into the gauge port
The agitator circuit has a maximum pressure, shown on which is located on the front of the agitator hand
the schematic, which is limited by the relief cartridge valve (not shown in this illustration).
(Figure 116) in the agitator hand valve. The cartridge is
adjustable with a 19mm socket or wrench.

Relief cartridge

Figure 116
Location of the agitator
relief cartridge

agitrlf.eps

2. Locate the agitator shutoff valve (Figure 117) and qty 1 GS-16S straight fitting, part number
close it. If your unit does not have a shutoff valve, 10008088
order one from the Schwing Spare Parts qty 2 16S capnuts, part number 10001743.
Department using part number 10004680 (valve),
All of these fittings and many, many more extremely
and number 30303432 (tube). Contact the Service
useful items are included in the trouble shooting kit,
Department for installation instructions. If you
part number 30308553.
cant wait for a shutoff valve, you will need to shut
off the engine and place the key in your pocket as 3. Be sure that one of the locking plugs and capnuts
you remove one of the hoses from the agitator are tightened on the straight fitting, and that the
motor and plug the hose and open fitting with dead plugs are securely tightened to the hose and
approved hydraulic dead plugs (Figure 117). the open motor fitting.
qty 2 VS-16S locking plugs, part number 4. Be sure that all personnel are clear, and restart the
10016803 engine.

WARNING
Do not jam agitator paddles to force
oil over relief. Entanglement hazard!

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 369
HOME PRINT

Pressure Settings

agitoff.eps

Plugs Straight Fitting

capplug.eps

Agitator quarter turn Cap Nuts


shutoff valve (open position) Motor

Figure 117
Agitator shutoff valve and approved hydraulic dead plugs

5. Increase the engine RPM to full throttle and


activate the agitator hand valve in either forward or
reverse and read the gauge. If it does not read the
specified pressure, turn the body of the relief valve
using a 19mm socket or wrench. The cartridge
should be turned in (clockwise) to increase
pressure or out (counterclockwise) to decrease
pressure.
6. After the pressure is set, deactivate the agitator
system by placing the manual control handle in the
neutral position.
7. Remove the whip gauge.
Reopen the shutoff valve or stop the engine and remove
the key. Remove the dead plugs and store them in a
clean area. Re-attach the hose to the agitator motor
fitting and tighten securely. (Torque is correct if you
make one complete revolution after feeling initial
resistance increase).

revDate
370 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
KVM 55M could pressure out a function in the boom or outrigger
system to create heat, but today, load sensing systems
no longer allow maximum oil flow to be forced over
Check all hydraulic pressures
relief. Because of this, the agitator circuit must be used
Changes in pressure can indicate trouble in one or to heat the hydraulic oil.
more components and will serve as early warning indi- To heat the oil to operating temperature:
cators if you check them on a regular basis. The speci- 1. Locate the agitator shutoff valve (Figure 102), and
fications for each circuit are shown on the hydraulic close it. The quarter turn shutoff valve has a
schematics found in the Appendix section of this man- grooved line (Figure 102) on the shaft or pivot
ual. The hydraulic schematics are the only documents point of the handle as well as on the handle itself,
in this manual that have been updated specifically for which will indicate the open or closed configura-
your unit, by the serial number, so in each of the fol- tion of the valve. If the handle is removed from the
lowing procedures you will be told to refer to the sche- agitator shutoff valve (Figure 102) or the concrete
matic for the pressure required. pump shutoff valve (Figure 56) and replaced in a
If you wish to order a CD ROM which explains the different configuration, the grooves in the handle
pressure setting procedure for a specific model (All may no longer indicate the proper open/closed ori-
pumpkits), call SAI Spare Parts Department at (800) entation of the valve. The grooves in the shaft give
328 - 9635 and request the CD using the following part the only true indication of the valves position.
numbers: NOTE:
61/58 meter. . . . . . . . . . . . . . . . . . . . . . . 30365860 If your unit is an early production model and does
52 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30354732 not have an agitator shutoff valve, order one from
the Schwing Spare Parts Department, using part
45/47 meter. . . . . . . . . . . . . . . . . . . . . . . 30356770
number 10004680 (valve) and number 30303432
42 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30355485 (tube). Contact the Service Department for instal-
39 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30365861 lation instructions.
34 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30356772 2. Activate the agitator. With the valve closed, the
32 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30355486 agitator will not be able to turn and the oil will be
31 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30365862 forced over the relief valve. At an idle (about 600
RPM) you will be converting 4.5 horsepower to
Preheat the hydraulic oil heat.
Pressure settings must be made with the oil at normal 3. When the oil temperature gauge shows 50 C, open
operating temperatures (50 to 60 C). In the past we the shutoff valve.

Grooves in handle Closed


agitoff2.eps
Agitator quarter turn
shutoff valve (open position)
Grooves in shaft grooves2.eps

Motor Open
Mounting screw and washer
removed for illustration
Figure 46
Agitator shutoff valve (left) and Open/closed orientation of shutoff valve (right)

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 371
HOME PRINT

Pressure Settings

Soft switch
shutoff valve

Main Pressure
Gauge port
Figure 47
Concrete pump and Soft switch shutoff
valves

Concrete pump
hif
shutoff valve low
br
n.
ep
s

Setting relief pressure and pressure cutoff 6. If you have not already closed the soft switch shut-
on Hi-flo -6 pumpkits off valve and the concrete pump shutoff valve (Fig-
ure 56), do so at this time.
1. To set the pressure of the main relief valve on Hi-
flo pumpkits, you must first disable the soft switch 7. At the rear panel, select local control with the
circuit. Simply locate the ball cock for the soft local/remote switch, and turn the electric stroke
switch circuit (Figure 56), and close it by rotating limiter knob clockwise to maximum strokes per
the handle 90 degrees. minute.
2. The quarter turn shutoff valve for the concrete 8. The main system control block pressure must be
pump (Figure 56) will also need to be closed dur- set first to properly set the pressure cutoff on both
ing this procedure. pumps. Begin by backing off the jam nut of the
main relief cartridge (Figure 104) with a 9/16 inch
Note: Main system adjustments are preset at the fac-
wrench.
tory. The following procedure begins with adjustment
of the main relief cartridge and pressure cutoff. If 9. Using a 5/32 inch allen wrench, turn the adjust-
proper pressures cannot be obtained through these ment screw out (counterclockwise) until you can
steps, contact the Schwing Service Department for spe- feel no spring tension on the adjustment screw.
cific instructions on the adjustment of flow, horse- 10. Now, turn the screw back in (clockwise) two or
power, beginning of stroke regulation, and Q-min. three full turns to give you a proper starting point,
Pressure setting procedure: and tighten the jam nut.
3. Be sure that the waterbox covers and guards are in 11. Stop the truck engine, put the key in your pocket,
place any time you will be working in the area and adjust the pressure cutoff screw (Figure 57) on
around the main control block. each pump, by backing off the jam nut with a
4. Wear safety glasses when working around a con- 13mm wrench. Using a 4mm allen wrench, turn the
crete pump. Note! It is vital that each adjustment adjustment screw in (clockwise) one full turn, and
screw be properly identified prior to making any tighten the jam nut. Restart the truck engine.
adjustment. All screw adjustments for the system 12. Adjust the engine RPM to maximum specification.
relief must be made with the pumpkit in the neutral (See decal in truck cab)
position, and adjustments for pressure cutoff must 13. Pressure out the system by activating the concrete
be made with the engine shut off. pump forward switch on the rear panel. Using the
5. Start the truck engine, and put the PTO in gear just rear panel controls will allow you to read the con-
as you would to pump a job. crete pump main system pressure gauge, near the
e-stop manifold, from a safe distance.
revDate
372 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
NOTE: 16. Activate the concrete pump forward to pressure out
Because you turned out the pressure relief cartridge in the pump and read the pressure on the two gauges
step 7, the system pressure should read low at this time. in the M1 ports.
If it does not and the gauge spikes to 320 bar or more, 17. Always stop the truck engine, and put the key in
disengage the pump immediately. Turn the relief car- your pocket before making any adjustment on the
tridge out (counterclockwise) more. For safety, it is hydraulic pump. If the cutoff on one pump is set
important to adjust the pressure up from below the higher than the other, that pump will be more dom-
specified target pressure rather than down from a pres- inant. The pressure gauge in the M1 port of the
sure which exceeds the target. Continue this procedure dominant pump will, however, read lower than the
until the main system pressure gauge reads lower than other. To equalize the two pumps, you must either
the specified target. adjust the cutoff screw in (clockwise) to increase
14. To increase the pressure, put the pump in the neu- the pressure of the pump showing the higher read-
tral position and adjust the relief cartridge by turn- ing, or adjust the cutoff screw of the dominant
ing it in (clockwise). When increasing the pressure, pump showing the lower reading out (counter-
the adjustments should be made in quarter turn clockwise) to reduce the pressure. These adjust-
increments. If you make adjustments to increase ments must be made until the two gauges in the M1
the pressure but the pressure does not come up, you ports are reading approximately the same.
are probably reading the pressure cutoff of the 18. When you have achieved the same pressure on the
pumps. If so, proceed to the next step; otherwise M1 port gauges, you can begin to adjust the pres-
skip to step 15. sure cutoff screws in or out simultaneously until
Turn the relief cartridge adjustment screw back out you achieve the desired pressure setting of 350 bar
(counterclockwise) until you can no longer see a (again, confirm the pressure specification with the
pressure drop, and tighten the jam nut. hydraulic schematic).
Stop the truck engine, and put the key in your After pressure cutoff is set, return the pump to neutral,
pocket. bring engine RPM to idle, open the soft switch quarter
Go to the pressure cutoff screw on both hydraulic turn valve, and either proceed to other pressure settings
pumps, and back off the jam nut with a 13mm or take the transmission and PTO out of gear; then shut
wrench. Turn the adjustment screws in with a 4mm off the truck.
allen wrench one or two more turns, restart the
engine, and check the pressure again. Repeat this
procedure until the main system relief can be set to
the target pressure.
15. When the proper main relief pressure is achieved,
pressure cutoff can be set. Shut off the engine, put
the key in your pocket, and install 0-600 bar
gauges with whip hoses to the M1 gauge ports on
the bottom of the two hydraulic pumps (Figure 57).
You must be able to read both gauges simulta-
neously to ensure that one pump is not more domi-
nant than the other.
NOTE:
The gauges in the M1 ports will read considerably less
than the cutoff pressure of the pump. On a -6 (190/130
pump combination) the 190 will usually read 85 to 90
bar while the 130 reads about 110 bar. They could read
the same at approximately 110 bar, but the 190 must
never read higher than the 130. The actual cutoff pres-
sure will be read on the concrete pump main system
pressure gauge near the e-stop manifold.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 373
HOME PRINT

Pressure Settings

Main and soft switch


relief cartridges Closed Open
Concrete pump
soft switch
gauge port
relief cartridge
Main relief cartridge

openclsd.eps
9/16" jam nut

5/32" Allen head


ga
ug
pr
t.e
ps
9/16" jam nut

Figure 48
Location of soft switch shutoff and relief cartridges

130-6.eps

1 Stroke Regulation 2 Pressure Cut Off


3 Horse Power 4 Q-Min

2
2
3
1 1
3
4 4

M1 GAUGE PORT
(BOTTOM OF EACH PUMP)

Figure 49
A11VO adjustment screws for Hi-flo 6 units 190/130

NOTE: The main control block (brain) of a 2525


pumpkit will be rotated 180 degrees from the illustra-
tion shown in Figure 57.

revDate
374 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Setting the soft switch circuit relief on a load sensing system, begin by checking P and
pressure Q-min.
1. If you havent already done so, open the soft Checking and setting P pressure
switch quarter turn valve (Figure 57). The rest of
the unit should still be set up as though you were NOTE: Do not adjust delta P or Q-min if your boom is
going to check the main relief valve pressure (con- running as you like it. The pressure setting procedure
crete pump shutoff valve still closed). uses a standard starting point and must be fine tuned
2. When you put the pump in forward now, the pres- from that point. The pressure was fine tuned at the fac-
sure gauge should read the pressure shown on the tory and should not be adjusted unless absolutely nec-
schematic for soft switch. If adjustment is needed, essary.
loosen the jam nut of the soft switch relief cartridge
(Figure 57) with a 9/16 inch open end wrench, and rtblock2.eps

use a 5/32 inch allen wrench to adjust the pressure.


Turn the adjustment screw in (clockwise) to raise
the pressure or out (counter clockwise) to lower the
pressure. When you attain the required pressure,
tighten the jam nut while holding the allen wrench
to keep the pressure from rising. Be sure to open
the concrete pump quarter turn valve on the side of
the brain (Figure 57) when you are finished. The
unit will not stroke with this valve closed.

Setting boom circuit pressures


High pressure
NOTE! Any time you set pressures for any circuit on
gauge port
any unit, the hydraulic oil should be at normal operat-
ing temperature (50 to 60 C). Instructions on heating
the hydraulic oil for this procedure are found on
page 371.
Please read all of the instructions before beginning any
pressure settings. You will need an assistant for parts of
the following procedure. You and any assistants should
wear eye protection when setting pressures. Figure 50
Current production model 52/55 meter pumps are The high pressure gauge
equipped with a load sensing, proportional boom port is located between the
hydraulic system. If the system were black and white, blocks on the inside edge of
the hydraulic pump would put out an unchanging the right boom control
amount of oil, and speed control would be done by block.
restricting the oil to certain functions with orifices. CAUTION! When checking delta P, it is important to
With a load sensing system, the pumps put out more or note that you will be installing a low pressure gauge
less oil to respond to the needs of the system. Gener- into a high pressure port. Any activation of a boom
ally, the pump always puts out enough oil to maintain function or activation of an e-stop while this gauge is
20 bar higher pressure at the pump than the boom cyl- attached will destroy your gauge. On Comfort Control
inders actually require. This 20 bar is called delta P. units, always center the boom speed switch on the
You may see it referred to by a symbol ( P). Addition- remote box to prevent accidental activation of a joy
ally, we set the hydraulic pump so that it always puts stick.
out a small amount of oil, even if none is needed for the
system. This oil is used to ensure that you have control
when you need it. The setting to maintain this mini-
mum amount of oil is called Q-min (pronounced cue
min). To set the boom or outrigger hydraulic pressures
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 375
HOME PRINT

Pressure Settings
3. With the engine running and the relief cartridge
backed out, the gauge (Figure 16) should be show-
WARNING ing delta P. The pressure could be anywhere from
16-25 bar.
Entanglement hazard. Stop drive shafts 4. Increase the throttle RPM, and the pressure should
before adjusting Delta P on A11VO pump.

W020.eps
remain the same. If the pressure fluctuates with
engine RPM, you are probably still reading Q-min,
1. Install a 0-100 bar whip gauge in the high pressure and the adjustable relief cartridge (Figure 107) will
test port (Figure 16), located on the inside of the need to be turned out more.
right boom control block as you face the three
5. If no further adjustment is needed, return the pilot
valve blocks.
valve relief cartridge to its original position. If
2. With the engine at idle, turn the adjustable relief adjustment is required, proceed to the next step.
cartridge (Figure 107) on the boom pilot control
6. Delta P is adjusted on the bottom (smaller) screw
valve out (counter clockwise) approximately three
of the pressure regulator shown in Figure 43 below,
turns. Remember exactly how much you move this
if your unit has an A7VO boom pump you can do
cartridge, because it will need to be returned to the
so by loosening the jam nut (10mm open end
original position.
wrench) and adjusting the screw (3mm allen
wrench) clockwise to increase pressure or counter
adjustable relief clockwise to decrease it.
cartridge
7. The delta P adjustment screw on the A11VO boom
pump, also shown in Figure 43 below, requires a
L
P
13mm open end wrench and a 4mm allen wrench.
8. If no further adjustment is needed, return the pilot
valve relief cartridge to its original position, and
52pilot.eps

preset pressure proceed to Q-min.


reducing valve 9. If pressure cannot be correctly set, there is a prob-
lem; contact Schwing Service Department to deter-
gauge port mine how to continue.

Figure 51
Location of adjustable relief cartridge
on the boom pilot control valve

Delta-p
pressreg.eps

Regulator pressure
adjustment

T
Adjustment for P pressure

smdeltap.eps

Figure 52
Location of the delta P adjustment screw for a unit with A7VO pump
(left) and A11VO pump (right)

revDate
376 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Setting Q-min

Delta-p Pressure Cut-off


Q-min
adjustment screw

A7VX section min.top.eps

hifloreg.eps

Q-min Q-max (Bottom Of Pump) Q max


Figure 53
Location of Q-min screw on A11VO (left) and A7VO (right)
Check Q-min with the engine at maximum specified NOTE: If you dont have a 0-100 bar gauge, you can
RPM. Each time the Q-min screw must be adjusted, the order one from Schwing Spare Parts Department at
engine must be stopped, or at least the transmission (800) 328-9635, part #10004659.
must be taken out of gear so that the drivelines stop
turning. Checking boom pressures
After the delta P and Q-min are set, remove the 0-100
WARNING bar gauge, and proceed to check and adjust the main
boom pressures, if necessary.
Entanglement hazard. Stop drive shafts
1. To check the boom pressure, install a 0-600 bar
before adjusting Q-min.
W009.eps

gauge in the boom circuit high pressure gauge port


(called out but not visible in Figure 111).
1. Before proceeding, remove the 0-100 bar whip 2. With the engine at full RPM and the boom folded,
gauge from the high pressure gauge port (Figure activate boom #2, #3, or #4 to the in position,
16), and install a 0-400 or 0-600 bar gauge to the which will pressure out the function. A function
same port to make certain that the higher pressure must be pressured out each time you want to check
wont destroy your 0-100 bar gauge. the pressure.
2. All boom functions must be in neutral, and all 3. Read the gauge. It should be showing the lowest
emergency stop buttons should be up (not relief pressure setting of the boom circuit (pressure
engaged). Clear away all personnel, start the truck regulator or cutoff) + or - 5 bar (see schematic). If
engine, engage the pumps, and bring engine RPM it does not, a minor adjustment can be made by
to maximum specification. going to the pressure regulator (large screw) for
3. Read the pressure. If the pressure reads less than units with A7VO pumps (Figure 45), backing off
100 bar, remove the high pressure gauge and rein- the jam nut and turning the adjustment screw to
stall the 0-100 bar gauge. Pressure should be at 50- achieve the desired pressure. For units with
55 bar. If adjustment is needed, continue to point 4. A11VO pumps, after stopping the engine, back off
4. Stop the engine, and turn the Q-min screw (Figure the jam nut on the pressure cutoff screw (Figure
109) in (clockwise) to raise the pressure or out 45) and make the adjustment. If the pressure can-
(counter-clockwise) to lower the pressure. Be sure not be reached, return the screw to the original set-
that you stop the drive shafts from turning each ting, and proceed to Setting boom circuit pressures.
time before making the adjustment. When pressure
is correct, tighten the jam nut on the adjustment
screw before continuing with the other procedures.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 377
HOME PRINT

Pressure Settings

Down side dynamic


gauge port

Main boom pressure


gauge port (Hidden)

Figure 54
Main relief cartridge
Main relief adjustment screw and
gauge ports. (High pressure gauge
port not visible on illustration) lftblock.eps

Setting main boom circuit pressures 3. Loosen the jam nut on the large screw of the pres-
sure regulator or the pressure cutoff screw (Figure
1. Review the hydraulic schematic, and identify the
45), depending which one your unit has, and turn
three different pressure settings involved in this cir-
the adjustment screw clockwise, all the way in.
cuit. 1) boom block main relief, 2) e-stop manifold
relief, and 3) pressure regulator.
2. Since the gauge will always show you the lowest of WARNING
the three settings, it is necessary to raise the two
lowest pressures enough to allow us to see the Entanglement hazard. Stop drive shafts
highest one, which will be the main relief at the before adjusting Pressure cut-off on

W021.eps
boom block (Figure 111). A11VO pump.

Delta-p Pressure Cut-off


pressreg.eps

Regulator pressure
adjustment

T
Adjustment for P pressure

hifloreg.eps

Q-min Q-max (Bottom Of Pump)

Figure 55
Pressure regulator adjustment (A7VO left) and Pressure cutoff screw (A11VO right)

revDate
378 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Boom circuit
relief cartridge
s
ep
trl.
crc
bm

Figure 56
Boom circuit relief cartridge
on e-stop manifold

4. Loosen the jam nut on the boom circuit relief car- 7. Finally, return to the pressure regulator or pressure
tridge located on the e-stop manifold (Figure 113) cutoff (Figure 45), and turn the adjustment screw
using a 9/16 wrench, and turn the adjustment screw out until the lowest pressure on the schematic is
in using a 5/32 allen wrench until you can see the achieved. Lock the jam nut.
maximum pressure of the boom block main relief
showing on the gauge while pressuring out a boom Checking pretension pressure
function.
This procedure is to check the pretension pressure only.
5. If the pressure reading is still lower than the maxi- The pressure you will be reading is from the factory
mum shown on the schematic, loosen the jam nut preset pressure reducing valve (Figure 114), which can
on the control block main relief adjustment screw, not be adjusted.
(Figure 111) and turn the adjusting screw in. This
1. Install a 0-60 bar whip gauge on the gauge port of
will raise the pressure of the main relief valve until
the precontrol block (Figure 114), and bring the
the desired pressure is achieved. Tighten the jam
engine RPM to full throttle.
nut to secure the adjustment screw.
2. The gauge should read 33-35 bar. If the pressure
6. Now return to the boom circuit relief cartridge
reading is different than that, contact the Schwing
(Figure 113), and turn the adjustment screw back
Service Department for instructions on how to pro-
out (counter-clockwise) until the second highest
ceed.
pressure on the boom circuit schematic is achieved.
Tighten the jam nut to secure the adjustment screw.

adjustable relief
cartridge
P
L

lrgpilot.eps

preset pressure
reducing valve

Figure 57
The precontrol valve gauge gauge port
port and adjustment points

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 379
HOME PRINT

Pressure Settings
Setting the outrigger pressure use an extension cylinder because they have sec-
ondary relief functions (non-adjustable) built into
To set the outrigger pressure, find the relief cartridge
the valve. While holding the push-button and acti-
(Figure 48) located on the passenger side outrigger
vating handle number 4 (Figure 48) to retract posi-
control valve.
tion, read the pressure on the gauge.
1. Attach a 0-600 bar whip gauge to the gauge port
4. Check the schematic to see what the pressure
shown in Figure 48.
should read. Adjust by loosening the jam nut with a
2. Push the outrigger button. 9/16 open end wrench and turning the cartridge
3. Activate an outrigger jacking cylinder to retract. with a 5/32 allen wrench. When the desired pres-
By attempting to retract a cylinder which is already sure is reached, let go of the handle and the push-
retracted, the oil coming from the pump has no button.
where to go but over the relief valve. You cannot 5. Remove the whip gauge when the job is complete.

PScntrl#.eps

Outrigger controls on units


built in U.S. prior to 2000 EXTEND FOLD - REAR FOLD - FRONT FOOT

PULL PULL PULL PULL

1. Front extend
Relief cartridge
2. Rear fold
3. Front fold
4. Foot (jacking) 1 2 3 4
Gauge port

Figure 58
Passenger side outrigger valve bank

revDate
380 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

Agitator Relief Valve Turn body of valve


Gauge port to adjust.
Higher

Lower

Figure 59 2.e
ps
itrlf
Location of the agitator relief ag

cartridge and gauge port

Set the agitator pressure motor and plug the hose and open fitting with
approved hydraulic dead plugs (Figure 117).
The agitator circuit has a maximum pressure, shown on
the schematic, which is limited by the relief cartridge Qty 2 VS-16S locking plugs, part number
(Figure 50) in the agitator hand valve. The cartridge is 10016803
adjustable with a 19mm socket or wrench. Qty 1 GS-16S straight fitting, part number
10008088
1. Plug the 0 - 600 bar whip gauge into the gauge
port, which is located on the top of the agitator Qty 2 16S capnuts, part number 10001743
hand valve. 3. All of these fittings and many, many more
2. Locate the agitator shutoff valve (Figure 117), and extremely useful items are included in the trouble
close it. If your unit does not have a shutoff valve, shooting kit, part number 30308553.
order one from the Schwing Spare Parts Depart- 4. Be sure that one of the locking plugs and capnuts
ment using part number 10004680 (valve) and are tightened on the straight fitting, and that the
number 30303432 (tube). Contact the Service dead plugs are securely tightened to the hose and
Department for installation instructions. If you the open motor fitting.
cant wait for a shutoff valve, you will need to shut 5. Be sure that all personnel are clear, and restart the
off the engine and place the key in your pocket as engine.
you remove one of the hoses from the agitator
agitoff2.eps
Agitator quarter turn Plugs Straight Fitting
shutoff valve (open position)

capplug.eps

Motor Cap Nuts

Figure 60
Agitator shutoff valve and approved hydraulic dead plugs
6. Increase the engine RPM to full throttle, activate and read the gauge. If it does not read the specified
the agitator hand valve in either forward or reverse, pressure, turn the body of the relief valve using a
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 381
HOME PRINT

Pressure Settings
19mm socket or wrench. The cartridge should be
turned in (clockwise) to increase pressure or out
(counterclockwise) to decrease pressure.
7. After the pressure is set, deactivate the agitator sys-
tem by placing the manual control handle in the
neutral position. 45Accreg.eps

8. Remove the whip gauge.


9. Reopen the shutoff valve or stop the engine and
remove the key. Remove the dead plugs and store
them in a clean area. Re-attach the hose to the agi-
tator motor fitting and tighten securely. (Torque is Accumulator pump
correct if you make one complete revolution after pressure regulator
feeling initial resistance increase).
Figure 61
Set accumulator circuit pressure Accumulator pump pressure regulator
You will need an assistant for parts of this procedure. for A7VO (above) and for A11VO (below)
There are three relief settings for the accumulator cir-
cuit if your unit is equipped with an accumulator Boom Pump
redundant relief cartridge in the emergency stop mani- Accumulator Pump
fold (Figure 62). If your pump was built after January
1, 2000. It will have an emergency stop manifold
which no longer has a redundant relief cartridge. In that
case, you must skip steps 3 and 7 in the following pro-
cedure.
To check or adjust the hydraulic pressure in the Standby
accumulator circuit: Pressure Screw
1. Stop the truck, put the key in your pocket, and
place a Do Not Operate sign on the windshield. Accumulator Pump
Pressure Regulator accumpmp.eps
hgacugc.psd
2. Loosen the jam nut on the pressure regulator of the
accumulator hydraulic pump (Figure 61). Turn the
screw in two-and-one-half turns. This will raise the
regulator pressure above 300 bar.
3. Loosen the jam nut (Figure 62) on the accumulator accurlf2.eps

redundant relief cartridge located on the emer-


gency stop manifold. Turn the screw in two turns.
This will raise the relief setting above 300 bar.

Accumulator redunant
relief cartridge

Figure 62
Accumulator redundant relief
cartridge

revDate
382 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
4. Clear all personnel away from the drive lines, start
the truck engine, engage the pumps, and bring the acumrlf.epsL

engine RPM to maximum.


5. Read the pressure on the accumulator circuit pres-
sure gauge (Figure 63). The pressure should read
the value shown on the hydraulic schematic. If no
adjustment is needed, skip to step number 7. If
additional pressure adjustment is needed, continue
with step number 6.

@@@@@@@@


;;;;;;;;
QQQQQQQQ
@@@@@@@@


;;;;;;;;
QQQQQQQQ

45acumpr.epsL

@@@@@@@@


;;;;;;;;
QQQQQQQQ

@@@@@@@@


;;;;;;;;
QQQQQQQQ

@@@@@@@@


;;;;;;;;
QQQQQQQQ

@@@@@@@@


;;;;;;;;
QQQQQQQQ

;;;;;;;;
@@@@@@@@


QQQQQQQQ

;;;;;;;;
@@@@@@@@

Figure 63

QQQQQQQQ

Accumulator circuit pressure gauge Figure 64
Accumulator manifold pressure
6. Locate the accumulator manifold pressure relief relief cartridge
cartridge (Figure 64). Loosen the jam nut, and turn
the screw clockwise to increase the pressure or 8. After the truck engine is stopped, go back to the
counter clockwise to decrease the pressure. accumulator circuit hydraulic pump pressure regu-
Tighten the jam nut when the pressure reaches the lator (Figure 61), and turn the screw back out two-
value required. and-one-half turns. This restores it to its original
7. You will need an assistant for this step. With the setting.
engine still running, one person must go to the 9. Clear all personnel from the drive line area, start
redundant relief valve on the emergency stop mani- the truck, and bring the engine RPM up to maxi-
fold (Figure 62) and back out the adjustment screw mum.
while the other person stands by the pressure gauge 10. Read the pressure on the accumulator gauge. It
to let him know when the pressure reads the value should read the proper accumulator system pres-
shown on the schematic for accumulator redundant sure.
relief. 11. If adjustment is needed, you must stop the truck
engine, or a least stop the drive lines from turning,
each and every time you approach the accumulator
WARNING circuit hydraulic pump. Turn the screw in to
increase the pressure or out to decrease pressure.
Entanglement hazard. Stop drive shafts Lock the jam nut when the pressure is correct.
before adjusting the accumulator pump
pressure regulator. NOTE: The accumulator circuit hydraulic pump pres-
W010.eps

sure regulator is referred to as the pressure cut-off.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 383
HOME PRINT

Pressure Settings

revDate
384 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
S 58/61SX RPM), 4.5 horsepower is being converted to heat.
3. When the oil temperature gauge shows 50C, open
The following pages provide the proper techniques for
the shutoff valve.
checking and setting hydraulic pressures of each
system included on your unit. Agitator quarter turn
000174.eps

shutoff valve (open position)

Check all hydraulic pressures


Figure 118
Changes in pressures can indicate trouble in one or Agitator shutoff
more components. The specifications for each circuit valve
are shown on the hydraulic schematics found in the Motor

Appendix of this manual. The hydraulic schematics are


the only documents in this manual that have been
Setting pressures on Hi-flo -6 pumpkits
updated specifically for your unit by the serial number,
so in each of the following procedures you will be told To set the pressure of the main relief valve on
to refer to the schematic for the pressure required. Hi-flo pumpkits, you must first disable the soft
switch circuit. Simply locate the ball cock
If you wish to order a CD ROM which explains the shutoff for the soft switch circuit (Figure 56),
pressure setting procedure for a specific model (All and close it by rotating the handle 90 degrees.
pumpkits), call SAI Spare Parts Department at (800)
The quarter turn shutoff valve for the concrete
328 - 9635 and request the CD using the following part
pump (Figure 56) will also need to be closed
numbers:
during this procedure.
61/58 meter. . . . . . . . . . . . . . . . . . . . . . . 30365860
52 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30354732 NOTE!
45/47 meter. . . . . . . . . . . . . . . . . . . . . . . 30356770 Main system adjustments are preset at the
factory. The following procedure begins
42 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30355485 with adjustment of the main relief cartridge
39 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30365861 and pressure cutoff. If proper pressures can
not be obtained through these steps, contact
34 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30356772 the Schwing Service Department for specific
32 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30355486 instructions on the adjustment of flow,
31 meter . . . . . . . . . . . . . . . . . . . . . . . . . 30365862 horsepower, beginning of stroke regulation
and Q-min.
Preheat the hydraulic oil
Pressure setting procedure:
Pressure settings must be made with the oil at normal
operating temperatures (40 60 C). In the past we
Soft switch
could pressure out a function in the boom or outrigger shutoff valve
system to create heat, but load sensing systems no
longer allow maximum oil flow to be forced over relief. Main Pressure
Because of this the agitator circuit must be used to heat Gauge port
the hydraulic oil.
To preheat the hydraulic oil:
1. Locate the agitator shutoff valve (Figure 55) and
close it.
NOTE! Concrete pump
shutoff valve 00
02
If your unit does not have a shutoff valve, 74
.e
ps

order one from the Schwing Spare Parts


Department using part number 10004680 Figure 119
(valve) and number 30303432 (tube). Con- Concrete pump and Soft switch shutoff
tact the Service Department for installation
instructions.
2. Activate the agitator. With the valve closed, the 1. Be sure that the waterbox covers and guards are in
agitator will not be able to turn and the oil will be place any time you will be working in the area
forced over the relief valve. At an idle (about 600 around the main control block.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 385
HOME PRINT

Pressure Settings
2. Wear safety glasses when working around a more. For safety, it is important to adjust
concrete pump. the pressure up from below the specified
target pressure rather than down from a
NOTE! pressure which exceeds the target. Continue
It is vital that each adjustment screw be this procedure until the main system pres-
properly identified prior to making any sure gauge reads lower than the specified
adjustment. All screw adjustments for the target.
system relief must be made with the pump- 12. To increase the pressure put the pump in the
kit in the neutral position, and adjustments neutral position, and adjust the relief cartridge by
for pressure cutoff must be made with the turning it in (clockwise). When increasing the
engine shut off.
pressure, the adjustments should be made in
3. Start the truck engine, and put the PTO in gear just
quarter turn increments. If you make adjustments
as you would to pump a job.
to increase the pressure but the pressure does not
4. If you have not already closed the soft switch come up, you are probably reading the pressure
shutoff valve and the concrete pump shutoff valve cutoff of the pumps. If so, proceed to the next step;
(Figure 56), do so at this time. otherwise skip to step 15. Turn the relief cartridge
5. At the Vector controller, select local control with adjustment screw back out (counterclockwise)
the local/remote switch, and activate the electric until you can no longer see a pressure drop, and
stroke limiter switch to maximum strokes per tighten the jam nut.
minute. 13. Stop the truck engine and put the key in your
6. The main system control block pressure must be pocket.
set first to properly set the pressure cutoff on both 14. Go to the pressure cutoff screw on both hydraulic
pumps. Begin by backing off the jam nut of the pumps (Figure 57), and back off the jam nut with a
main relief cartridge (Figure 58) with a 9/16 inch 13mm wrench. Turn the adjustment screws in with
wrench. a 4mm allen key one or two more turns, restart the
7. Using a 5/32 inch allen key, turn the adjustment engine, and check the pressure again. Repeat this
screw out (counterclockwise) until you can feel no procedure until the main system relief can be set to
spring tension on the adjustment screw. the target pressure.
8. Now, turn the screw back in (clockwise) two or 15. When the proper main relief pressure is achieved,
three full turns to give you a proper starting point, pressure cutoff can be set. Shut off the engine, put
and tighten the jam nut. the key in your pocket, and install 0-600 bar
9. Stop the truck engine, and put the key in your gauges with whip hoses to the M1 gauge ports
pocket. Adjust the pressure cutoff screw (Figure on the bottom of the two hydraulic pumps (Figure
57) on each pump by backing off the jam nut with 57). You must be able to read both gauges
a 13mm wrench. Using a 4mm allen key, turn the simultaneously to ensure that one pump is not
adjustment screw in (clockwise) one full turn, and more dominant than the other.
tighten the jam nut. Restart the truck engine. NOTE!
10. Adjust the engine RPM to maximum specification. The gauges in the M1 ports will read consid-
(See decal in truck cab) erably less than the cutoff pressure of the
pump. On a -6 (190/130 pump combina-
11. Pressure out the system by activating the concrete tion), the 190 will usually read 85 to 90 bar,
pump forward switch on the rear panel. Using the while the 130 reads about 110 bar. They
rear panel controls will allow you to read the could read the same, however, at approxi-
concrete pump main system pressure gauge, near mately 110 bar, but the 190 must never read
the e-stop manifold, from a safe distance. higher than the 130. The actual cutoff pres-
sure will be read on the concrete pump main
NOTE! system pressure gauge near the e-stop mani-
Because you turned out the pressure relief fold.
cartridge in step 7, the system pressure 16. Activate concrete pump forward to pressure out the
should read low at this time. If it does not, pump, and read the pressure on the two gauges in
and the gauge spikes to 320 bar or more, the M1 ports.
disengage the pump immediately. Turn the
relief cartridge out (counterclockwise) 17. Always stop the truck engine and put the key in
revDate
386 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
your pocket before making any adjustment on the 18. When you have achieved the same pressure on the
hydraulic pump. If the cutoff on one pump is set M1 port gauges, you can begin to adjust the
higher than the other, that pump will be more pressure cutoff screws in or out simultaneously
dominant. The pressure gauge in the M1 port of the until you achieve the desired pressure setting of
dominant pump will, however, read lower than the 350 bar (again, confirm the pressure specification
other. To equalize the two pumps, you must either with the hydraulic schematic).
adjust the cutoff screw in (clockwise) to increase After pressure cutoff is set, return the pump to neutral,
the pressure of the pump showing the higher bring engine RPM to idle, open the soft switch quarter
reading or adjust the cutoff screw of the dominant turn valve, and either proceed to other pressure settings
pump showing the lower reading out or take the transmission and PTO out of gear and shut
(counterclockwise) to reduce the pressure. These off the truck.
adjustments must be made until the two gauges in
the M1 ports are reading approximately the same.

000277.eps

1 Stroke Regulation 2 Pressure Cut Off


3 Horse Power 4 Q-Min

2
2
3
1 1
3
4 4

Figure 120
A11VO adjustment screws M1 GAUGE PORT
for Hi-flo 6 units 190/130 (BOTTOM OF EACH PUMP)

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 387
HOME PRINT

Pressure Settings

Soft switch
shutoff valve Closed Open
soft switch
Main Pressure
relief cartridge
Gauge port Main relief cartridge

000276.eps
9/16" jam nut

Concrete pump 5/32" Allen head


shutoff valve 00
02
74
.e
ps
9/16" jam nut

Figure 121
Soft switch components

Setting the soft switch relief pressure Load-sensing boom hydraulic controls
First, open the soft switch quarter turn valve (Figure This unit is equipped with a load-sensing, proportional
58, right) that you closed in the previous procedure. boom hydraulic system. In a black-and-white system,
The rest of the unit should still be set up as if you were the hydraulic pump puts out an unchanging amount of
going to check the main relief valve pressure (concrete oil, and speed control is done by restricting the oil to
pump shutoff valve still closed). certain functions with orifices. In a load-sensing
When you put the pump in forward now, the main system, the pump puts out more or less oil to respond
concrete pump pressure gauge should read the pressure to the needs of the system. Generally, the pump puts
shown on the schematic for soft switch. If adjustment out enough oil to maintain 20 bar higher pressure at the
is needed, loosen soft switch relief valve jam nut pump than the cylinders actually require. This 20 bar is
(Figure 58 right) with a 9/16 open end wrench, and use called delta P (P). Additionally, we set the hydraulic
a 5/32 allen key to adjust the pressure. Turn the pump so that it always puts out a small amount of oil,
adjustment screw in (clockwise) to raise the pressure or even if no oil is needed for the system. This oil is used
out (counterclockwise) to lower the pressure. When to ensure that you have control when you need it. The
you attain the required pressure, tighten the jam nut setting to maintain this minimum amount of oil is
while holding the allen key to keep the pressure from called Q-min (pronounced cue min). To set the boom
rising. Be sure to open the concrete pump shutoff valve or outrigger hydraulic pressures on a load-sensing
on the side of the brain (Figure 58, left) when you are system, begin by setting P and Q-min.
finished. The unit will not stroke with this valve closed. Note: The illustration in Figure 58 shows a gauge port
in the center of the main control block. Your main
Setting boom circuit pressures concrete pump pressure gauge should be plumbed to
Read all of the instructions before beginning any that port.
pressure settings. You will need an assistant for parts of
the procedure. You and any assistants should wear eye
protection when setting pressures.
NOTE! WARNING
Any time you set pressures for any circuit
on any unit, the hydraulic oil should be at Entanglement hazard. Stop drive shafts
normal operating temperature (4060 C).
before adjusting Delta P on A11VO pump.
000004.eps

Instructions on heating the hydraulic oil are


found in the first step of this checking
hydraulic pressures segment.

revDate
388 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

gauge ports
for Delta P

Figure 122
Gauge ports for setting Delta P
delta/p.eps

Setting Delta P pressure


NOTE! Delta-p
Do not adjust Delta P or Q-min if your
boom is running as you like it. The pressure
setting procedure uses a standard starting
point and must be fine tuned from that
point. The pressure was fine tuned at the
factory and should not be adjusted unless
absolutely necessary.
1. Start by turning off the engine and putting the key
in your pocket; then place a Do Not Operate sign
000281.eps
on the windshield of the truck.
2. Install a 0-400 bar gauge in the high pressure test Figure 123
port at the bottom of the boom control block Pressure regulator for A11VO pumps
(Figure 16).
3. Install a second 0-400 bar gauge (Figure 16) in the 7. When the proper Delta P is achieved, use the
port marked LS (load-sensing). following spaces to document the pressure.
4. Delta P is adjusted on the pressure regulator NOTE!
(Figure 43) if your unit has an A11VO boom Remember that the documented Delta P
pump. When all personnel are clear of the truck, pressure applies only to the unit with the
restart the engine, engage the pumps, and increase serial number shown in the front of this
the engine speed to max RPM. book.
5. Activate any boom cylinder to maximum speed
and read both gauges as the boom section moves. Date__________________ P__________bar
The difference between the two pressures should Date__________________ P__________bar
be 20 bar + or - 5.
Date__________________ P__________bar
6. If adjustment is required, loosen the jam nut, and
Date__________________ P__________bar
adjust the screw inward to increase pressure or
outward to decrease pressure until the boom runs Date__________________ P__________bar
smoothly.
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 389
HOME PRINT

Pressure Settings
If pressure cannot be set correctly, there is a problem NOTE!
with the regulator itself. Contact the Schwing Service If you dont have a 0-100 bar gauge, you can
Department to determine how to continue. order one from Schwing Spare Parts
Department at (800) 328-9635, part #
If the boom does not run smoothly at 20 bar, you must 10004659.
fine tune the adjustment. Remove the gauge, and turn
the P adjustment screw until the boom is responsive
and smooth. After adjusting, the difference between the
gauges (reinstalled) must read between 14-25 bar. The
electronics in the control system can also affect how
the boom operates, so if P adjustment does not seem
Boom pressure
to help, reset to 20 bar and check the electrical settings.
relief cartridge
When the electrical settings are verified, you could
again try to refine the boom action with the P
adjustment.
ps
lf.e
ssr
pre

WARNING
0-600 bar
Wear safety glasses any time you check gauge port
or set pressures. Oil expulsion hazard!
000438.eps

Figure 124
0-600 bar gauge port
Setting Q-min
Check Q-min when the engine is at maximum specified
RPM. You must not adjust Q-min with the drive
shafts turning! Each time the Q-min screw must be
adjusted, the engine must be stopped, or at least the
transmission must be taken out of gear so that the
drivelines stop turning. Delta-p Pressure Cut-off
1. All boom functions must be in neutral, and all
emergency stop buttons should be up (not
engaged). Clear away all personnel, start the truck
engine, engage the pumps, and bring engine RPM
to max. Read the pressure at the 0600 bar main
boom gauge port (Figure 124) with a 0-100 bar
gauge. Pressure should be at 4045 bar. If no
adjustment is needed, be sure the jam nut on the
Q-min screw is tight, then continue to set the rest
of the boom and outrigger pressures. If adjustment
000282.eps
is needed, continue to the next step.
Q-min Q-max (Bottom Of Pump)
2. Turn the Q-min screw (Figure 125) in to raise the
pressure. Turn it out to lower the pressure. Be sure
that you stop the drive shafts from turning each Figure 125
time before making the adjustment. When pressure Location of Q-min screw
is correct, tighten the jam nut on the adjustment
screw before continuing with the other procedures;
then, recheck P to make sure that it hasnt
changed during the Q-min adjustment.
revDate
390 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Setting boom pressures
Now that P and Q-min are set, you can remove the 0-
100 bar pressure gauge and proceed to check and
adjust the main boom pressures.

Setting main pressure


1. The main pressure is the highest pressure of the
three boom system settings. The only way you will
be able to see the main pressure on the gauge is to
turn the pressure of the two lower systems up to a
level which is higher than that of the main pressure
relief valve.
2. Loosen the jam nut of the boom pressure relief
cartridge (Figure 126) with a 30mm open end Disconnect hose
hose1.eps
wrench, turn the adjustment cartridge in all the
way with a 32mm wrench, and lock the jam nut Figure 127
back down. Hose for boom section number two

Plugs Straight Fitting

Boom pressure
relief cartridge
Figure 128 000257.eps

Approved dead
plugs
ssr
lf.e
ps Cap Nuts
pre

0-600 bar 6. Install a 0 - 600 bar gauge in the main pressure


gauge port gauge port (Figure 129).
7. Increase the engine speed to maximum RPM, and
activate the manual control handle for boom
Figure 126 number two in the direction that will pressurize the
Boom pressure relief cartridge disconnected and plugged hose.
on the e-stop manifold
8. Now adjust the pressure to the setting found on the
schematic by turning the main boom pressure relief
3. Loosen the jam nut on the pressure cut-off screw cartridge on the boom control block (Figure 129)
(Figure 131), tighten the screw all the way down, with a 4mm allen key. Read the pressure on the 0-
and tighten the jam nut back down. 600 bar gauge installed in step 6. When desired
4. Identify the main boom pressure relief cartridge on pressure is achieved, lock down the jam nut with a
the control block (Figure 129), loosen the jam nut 12mm wrench.
with a 12mm wrench, then unscrew the adjustment
Setting boom pressure (redundant) relief
two full turns with a 4mm allen key.
9. Return to the e-stop manifold boom pressure relief
5. Setting the main pressure will require cartridge (Figure 126), and back off the jam nut
disconnecting a hose for boom section number two (30mm). Turn the cartridge (32mm) out, or counter
(Figure 127) and installing an approved dead plug clockwise, until the pressure gauge reads the
on each of the open fittings. number shown on the schematic for the boom
pressure relief cartridge. Lock down the jam nut.

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 391
HOME PRINT

Pressure Settings
Setting pressure cut-off
10. Return to the pressure cut-off screw (Figure 131). Delta-p Pressure Cut-off
Back off the jam nut, and turn the screw counter
clockwise until you achieve the pressure shown on
the schematic, then lock the jam nut.

Setting slewing pressure


11. The slewing function has two relief valves which
must be set individually. Since there is no way to
block the slewing function, it is also necessary to
disconnect the supply hoses which go to the
slewing motor one at a time and install an approved 000282.eps

dead plug to the open fitting. Q-min Q-max (Bottom Of Pump)


12. Install a 0 - 600 bar gauge in line on the open hose.
Figure 131
Pressure cut-off screw
14. The final boom pressure setting is the #1 boom
Gauge Main piston side relief setting. The relief cartridge is
port relief shown in Figure 64. This procedure should be
performed with the outriggers extended and the
boom unfolded over the cab. Extend section #1 all
the way until the cylinder bottoms out. Install a 0-
600 bar gauge in the gauge port shown in Figure
129. Activate boom #1 extend. The pressure should
read 230 bar. If adjustment is required, back off the
jam nut with a 12mm wrench, and turn the relief
cartridge (Figure 64) in or out using a 4mm allen
key as required until the desired pressure is
mainrlf.eps
achieved; then, lock down the jam nut.
Figure 129
Main boom control block
13. Activate the slewing handle in a direction which
will pressurize the disconnected hose and read the
gauge. If the pressure is not what the schematic
calls for, adjust the appropriate relief valve located
directly under the valve (Figure 130).

dwnsdrlf.eps

Figure 132
Piston side relief

NOTE!
Figure 130 HWslew.eps
If you are unable to achieve 230 bar by
Boom slewing adjusting the relief valve in Figure 64, call
Boom Slewing the Schwing Service Department and ask if
relief valves relief valves
the unit has a redundant relief valve.
revDate
392 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings
Setting outrigger pressure Setting the agitator pressure
The agitator circuit has a maximum pressure shown on
WARNING the hydraulic schematic, which is limited by the relief
cartridge (Figure 50) in the agitator hand valve. The
Tipping hazard. Never set outrigger relief cartridge is located on the back side of the
pressures with the boom unfolded. agitator manual control handle (Figure 50). The
Pressure setting procedure requires cartridge is adjustable with just a 19mm open end
retraction of an outrigger jacking wrench.

000359.eps
cylinder. 1. Plug the 0600 bar whip gauge into the gauge port
(Figure 50) for checking or setting agitator pres-
After the boom circuit is properly set, you can set the sure.
outrigger pressure. Find the relief cartridge 2. Locate the agitator shutoff valve (Figure 67), and
located on the front of the passenger side outrigger close it. If your unit does not have a shutoff valve,
control valve (Figure 48). order one from the Schwing Spare Parts Depart-
1. Attach 0-600 bar whip gauge to the gauge port ment using part numbers 10004680 (valve) and
below the outrigger valve bank. 30303432 (tube). Contact the Service Department
2. Push the outrigger enable button. for installation instructions. If you cant wait for a
shutoff valve, you will need to remove one of the
3. Activate an outrigger jacking cylinder to retract.
hoses from the agitator motor and plug the hose
By retracting a fully retracted cylinder, the oil
and open fitting with approved hydraulic dead
coming from the pump has nowhere to go but over
plugs (Figure 68).
the relief valve. You cannot use an extension or
slewing cylinder because they have secondary NOTE!
relief functions (nonadjustable) built into the valve. Do not jam the paddles to force the oil over
While holding the handle to retract, read the relief by stopping the movement of the
pressure gauge. agitator.
4. The pressure should read the bar value shown on 3. Increase the throttle to any speed above idle. Acti-
the hydraulic schematic. Adjust by loosening the vate the agitator valve handle in either forward or
jam nut and turning the cartridge (Figure 48) in or reverse, and read the gauge. If it does not read the
out. When the proper pressure is achieved, let go of specified pressure, adjustment is required. Turn the
the handle, and release the outrigger enable button. entire relief valve cartridge (Figure 50) in to
increase pressure or out to decrease pressure.
4. When the pressure is set, deactivate the agitator by
placing the manual control handle in the neutral
position.
5. Remove the whip gauge.
6. Reopen the shutoff valve or remove the dead plugs,
and reconnect the capped hydraulic line.
Outrigger valve Agitator Relief Valve
   
relief cartridge 
    







otrigrlf.eps

Figure 133 Figure 134


Outrigger valve bank relief cartridge Agitator relief cartridge located on
back side hand valve
Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm
Service Manual 393
HOME PRINT

Pressure Settings

000174.eps
Agitator quarter turn
shutoff valve (open position)

Motor

Figure 135
Agitator shutoff valve
000289.eps

Plugs Straight Fitting




Figure 136
   
Approved hydraulic
dead plugs 000257.eps

Figure 137
Cap Nuts Accumulator pump pressure regulator for
A7VO (above) and for A11VO on a unit
Setting accumulator circuit pressure with a stiebel gearcase (below)
To check or adjust the hydraulic pressure in the
accumulator circuit: Boom Pump
Accumulator Pump
1. Stop the truck, put the key in your pocket, and
place a Do Not Operate sign on the windshield.
2. Loosen the jam nut on the pressure regulator of the
accumulator hydraulic pump (Figure 51). Turn the
screw in two-and-one-half turns. This will raise the
regulator pressure above 300 bar.
Accumulator Pump
Pressure Regulator
Standby 000446.eps

Pressure Screw hgacugc.psd

revDate
394 Service Manual
HOME PRINT
SERVICE TRAINING
Pressure Settings

000449.eps

Manual bleed
valve
Boom pressure
relief cartridge

ps
lf.e
ssr
pre
Pressure relief
0-600 bar cartridge
gauge port

Figure 138 Figure 140


New e-stop has no redundant Accumulator manifold pressure
relief cartridge. relief cartridge

3. Clear all personnel away from the drive lines, start 5. Locate the accumulator manifold pressure relief
the truck engine, engage the pumps, and bring the cartridge (Figure 54). Loosen the jam nut, and turn
engine RPM to maximum. the screw clockwise to increase the pressure or
4. Read the pressure on the accumulator circuit pres- counterclockwise to decrease the pressure. Tighten
sure gauge (Figure 53). The pressure should read the jam nut when the pressure reaches the value
the value shown on the hydraulic schematic. If no required.
adjustment is needed, skip to step number 7. If
additional pressure adjustment is needed, continue
with step number 5.
000292.eps

Figure 139
Accumulator circuit pressure gauge

Media:Service_ Service Manual Set:2008:SERVICE_MANUAL:PressureSettings.fm


Service Manual 395
HOME PRINT

Pressure Settings

WARNING
Entanglement hazard. Stop drive shafts
before adjusting the accumulator pump

000075.eps
pressure regulator.

6. After the truck engine is stopped, go back to the


accumulator circuit hydraulic pump pressure regu-
lator (Figure 51), and turn the screw back out two-
and-one-half turns. This restores it to its original
setting.
7. Clear all personnel from the drive line area, start
the truck, and bring the engine RPM up to maxi-
mum.
8. Read the pressure on the accumulator gauge. It
should read the proper accumulator system pres-
sure.
9. If adjustment is needed, you must stop the truck
engine, or a least stop the drive lines from turning,
each and every time you approach the accumulator
circuit hydraulic pump. Turn the screw in to
increase the pressure or out to decrease pressure.
Lock the jam nut when the pressure is correct.

Note: The accumulator circuit hydraulic pump pressure


regulator is referred to as the pressure cut-off.

revDate
396 Service Manual
HOME PRINT
SERVICE TRAINING
Electrical

Electrical Information
Boom Control Systems and the Advantages of Each
Manual Controls
Manual Black and White (On-Off) System:
Totally, completely reliable.
Electrical malfunctions are impossible.
Cable Remote Controls
Remote Controlled Black and White System:
Operator can go to the location with the best possible view of the boom and job.
Allows mobility to move around the unit.
Analog Proportional Remote Control System:
Infinitely variable speed control.
No need to use the feathering technique of speed control.
Start and stop the boom with smooth acceleration and deceleration.
Hydraulic stroke limiter can be adjusted from the remote box.
Digital Proportional Remote Control System:
Less susceptible to external noise interference (from radio transmitters, for example).
Cable requires only 6 wires, instead of 25. One for power, one for ground, two for the emergency stop cir-
cuit, and two for data transfer.
More precise adjustment of boom speed than previous systems.
Troubleshooting a non-working system can be done in minutes via a hand held test device.
Increased safety because of numeric operating principles. (Cannot go out of adjustment).
A digital system can be updated or expanded by E-prom replacement or reprogramming. (Analog sys-
tems are not possible to improve without hardware replacement).
The proportional valve amplifiers are self diagnosing via L.E.D.s.
The boom can go slower before shut-off than with an analog system.
Digital system has built in ramp functions, which makes it impossible to accidentally go to full speed by
bumping a joystick.
Comfort Proportional Remote Control System
Has the Schwing information system
1. Pumped volume determination by means of stroke counter and pumped volume calculation.
2. Extensive operational data acquisition and display.
3. Safely stored malfunction list of last 100 malfuction messages.
4. Manual operation of lubricating cycles.
5. Status display of all signals of the electronic control.
6. Password-protected parameter setting for the central lubricating system
7. Password-protected parameter setting for the proportional boom fuctions.
Has the Schwing diagnostic system.
1. The diagnosis system monitors the control unit, the machine and partly also the vehicle for mal-
functions or inadmissible states of operation.
2. The system recognizes e.g. parting of cables or short-circuits in electric lines of solenoids, Fault
sensors, contaminated oil filters or critical hydraulic oil or diesel engine temperatures and displays
different operating conditions.
3. The system is to assist the concrete pump operator in his work on site and to inform him about the
possible causes of malfunctions when they occur.

Service Manual 397


HOME PRINT
SERVICE TRAINING
Electrical
4. The malfunction messages are displayed as continuous text in the form of an easily understand-
able plain language message with additional fault code.
Radio Remote Controls
Digital Black and White Radio Remote Control System FW 16:
Operator doesnt have to drag around a cable when moving.
The operator is not connected to the unit if a power line is contacted. (This does not protect others
around the unit if contact is made).
Digital Radio Remote Control System FW18:
Quicker response time than FW 16.
Greater safety than FW16, because of binary code transmissions.
Higher power output gives greater range than FW16.
Digital Radio Remote Control System FW 20/24:
Radio receiver is built into the digital proportional system (no separate receiver)
Radio receiver has 2 separate frequency drivers, selectable by the operator with a switch. If interference
is shutting down the system, just switch to the other frequency.
The receiver has many indicating lamps that tell the status of the radio systems.
Higher power output gives greater range and fewer interference shut-downs than FW 18.
Advanced filtration circuits cut down on interference shut-downs versus FW 18.
The antenna is internal to the remote box. Nothing external to get broken.
Spread Spectrum Radio Remote System
The Schwing Spread Radio system employ frequency hopping spread spectrum technology to provide
the optimum performance allowable under present FCC and ISC regulations. This technology provides a
unigue performance advantage compared to conventional fixed frequency systems. The major benefits
are listed below:
1. Interference Free: It cannot be jammed by other RF transmitters or extraneous noise source.
2. Coordination Free: All Schwing-spread spectrum transmitters are factory coded. The user does not
need to worry about which frequency the unit is operating on. It operates as if there ia s unique fre-
quency for each unit in existence. Any number of these units can be operated in the same location
at the same time.
3. License Free: These radios are certified by the U.S. and Canadian governments to meet their crite-
ria for license-free operation. With Spread Spectrum Technology, these radios are allowed to trans-
mit as much power and sometimes more than conventional licensed products. This makes for very
high performance reliable RF links through many types of material and over very great distances
should the application require it.
4. Security: Combine the Spread Spectrum robustness with the added 16-bit address space and
CRC16 error-detection code built into the data protocol, and these units provide extremely reliable,
error-free control.

398 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
Boom Control Systems

A
MANUAL - BLACK
AND WHITE
TO
BOOM

lts
B

vo
12
REMOTE CONTROL Switches +
s
BLACK AND WHITE +12 volt Relay Box
TO
BOOM

1000 mA
to

C
0
20

ANALOG Potentiometers
lt s
PROPORTIONAL 6 to 9 vo Proportional
Amplifiers TO
BOOM
0 1 1 0100 1 1 0 1 1 0 0 1 0
0 1 0 10 0 1 0
011 0

D
0 101 1
0 01

DIGITAL
PROPORTIONAL
A/D Converters
Radio
0 10

1000 mA
to

D
0
20

DIGITAL A/D Converters D/A Converter


PROPORTIONAL 01010010 & Proportional
Cable TO
Amplifiers BOOM

Service Manual 399


HOME PRINT
SERVICE TRAINING
Electrical
Introduction to Proportional Controls
The difference between the proportional and the black and white control is the function performed from the signal.
With the black and white control, the signal will be either on or off only. With the proportional control, the function
will vary according to the movement given to the potentiometer by the Joystick.

The proportional system can be broken down into 3 major components. They are as follows:
A. The Joystick with the Potentiometer.
B. The Proportional amplifier
C. The Solenoid valves.

The Joystick with Potentiometer


There is a 15 volt supply at connection 1 of the potentiometer (See Figure). If you tilt the Joystick up and down, the
voltage going into the amplifier will be changed (input signal - connection 2 of the potentiometer). Simultaneously,
when the N.O. micro-switch is closed the relay on the power supply card is switched and the circuit is activated.

BOOM FUNCTION

7.5 VOLTS
UP DOWN
+ 1.5 VOLTS
MICROSWITCH -

OPEN DOWN TO 6 VOLTS UP TO 9 VOLTS


CLOSED CLOSED (BOOM DOWN) (BOOM UP)
I MIN I MIN
I MAX I MAX

1 3

7.5 VOLTS 7.5 VOLTS

V V

15 VOLTS

1 3
2

400 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
The Proportional Amplifier
The proportional amplifier receives a voltage signal from the potentiometer and amplifies the input voltage signal
to the desired output current (See Figure).
24 VOLTS

MICROSWITCH

7.5 VOLTS

15 VOLTS 0 VOLTS

PROPORTIONAL AMPLIFIER CARD

SIGNAL COMMON SIGNAL


BOOM UP GROUND BOOM DOWN

RELAY

GROUND PILOT VALVES


BOOM BOOM
UP DOWN

The Solenoid Valves


Schematic of a proportional valve with a current to pressure ratio diagram.
PRESSURE RANGE UP TO 30 BAR
30

28

26

24

22
PRESSURE AT PORT "A" IN BAR

20

18
A T
16

14

12

10

8
P
6

0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CURRENT IN AMPS

More current = More pressure at port A.


More pressure at port A = Increase the hydraulic flow at the slave valve.
Increased hydraulic flow = Boom acceleration

Service Manual 401


HOME PRINT
SERVICE TRAINING
Electrical
The Proportional Amplifier in Use with the Radio
The signal from the radio remote control to the proportional amplifier is 12 V6 V, instead of 7.5 V 1.5 V as
with the cable remote control. For instance:
Boom up 12 V 6V
Boom down 12 V 18 V
In order to make the proportional controls work with these input voltages, we need to switch relays on the
proportional amplifier cards. This is accomplished with a bridge wired into the connecting cable for the radio
remote, from the receiver to the operators control panel. The bridge is wired in the plug that connects to the control
panel. It is because of this bridge that two different cables are required.

TRANSMITTER
MICRO-
SWITCH

RADIO
SIGNAL

CONNECTING CABLE
RELAY
RECEIVER
BRIDGE FOR
RADIO REMOTE

12 21 22 24

PROPORTIONAL CARD

PILOT VALVES

BOOM BOOM
UP DOWN

402 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
Motherboard for Proportional Units

POWER SUPPLY CARD


(PART# BEFORE 1992 10074135 AFTER 1992 10023316)

PROPORTIONAL AMPLIFIER CARD


(PART# BEFORE 1992 10074136 AFTER 1992 10023317)

PROPORTIONAL AMPLIFIER CARD


(PART# BEFORE 1992 10074136 AFTER 1992 10023317)

PROPORTIONAL AMPLIFIER CARD


(PART# BEFORE 1992 10074136 AFTER 1992 10023317)

ADAPTER CARD
FOR TEST METER
(PART# BEFORE 1992 10074136
AFTER 1992 10023317)

EMPTY
SLOT

9 1 2 3 5

Service Manual 403


HOME PRINT
SERVICE TRAINING
Electrical
Power Supply - Slot 9

CARD 9

LED Voltage Function


1 7.5 V Must be on at all times.

2 15 V Must be on at all times.

3 18 V Must be on at all times.

4 24 V Emergency Stop. Must be on


when the Emergency Stop has
LED 1 been activated.

LED 2 5 Fuse for voltage regulation. It


should be off. When it is on,
LED 3 check the fuse.

LED 4

LED 5

404 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
Proportional Amplifier - Slot 1,2,3

CARD 1, 2, 3

MIN
MAX
LED Function
LED 1
Channel 1 1 Illuminates when the corresponding function has
MIN been activated.
MAX
2 Illuminates when the corresponding function has
LED 2 been activated.

MIN 3 Illuminates when the corresponding function has


MAX been activated.

LED 3 4 Illuminates when the corresponding function has


Channel 2 been activated.
MIN
MAX 5 Should be off. If it illuminates when a channel 1
function has been activated, check fuse.
LED 4
6 Should be off. If it illuminates when a channel 1
LED 5 function has been activated, check fuse.

LED 6

Service Manual 405


HOME PRINT
SERVICE TRAINING
Electrical
Calibration of Proportional Amplifier Cards
Note:
The average Proportional solenoid valve operates between 300 and 800 mA.
1. Push the emergency stop button (Only if not using the Schwing proportional card test meter).
2. Connect Amp meter in the circuit of the proportional function that is to be calibrated. The most convenient way
to measure the current is using the Schwing proportional card test meter
(ID 77706).
3. Release the Emergency Stop button.
4. Tilt the Joystick to the point that the
micro-switch is in the closed position (trigger point is at I min). The circuit is now in a closed position, the LED
on the proportional amplifier card is illuminated, and the current can be read on the test meter.
5. Adjust the minimum current (at the min potentiometer) to the point where the boom section just starts to move
(approximately 300 - 450 mA).
6. Tilt the Joystick all the way (I max.). Adjust your maximum current (at the max potentiometer) on the propor-
tional amplifier card (approximately 700 - 800 mA).
After adjusting the maximum current, repeat steps 4 though 6 until the correct result has been achieved. The reason
for this is because as the min or max is adjusted, the other is effected.

CARD 1, 2, 3

BOOM FUNCTION

UP DOWN
MICROSWITCH

CLOSED OPEN CLOSED


I MIN I MIN
I MAX I MAX MIN
MAX

LED 1
Channel 1
MIN
MAX

LED 2

MIN
MAX

LED 3
Channel 2
MIN
MAX

LED 4

LED 5

LED 6
1 3
2

406 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
Linear Signal Diagram

1000
MAXIMUM CURRENT OUTPUT (mA)

900

800
MAX
700

600

500
MIN
400

300

200

100

0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
MIN MAX
PRETENSION PRESSURE (Bar)

The optimum adjustment makes full use of the joysticks range of travel. Other adjustments
result in poor response and on/off switching of valves, which in turn causes jerky motion of the
bomm and possible structure damage.

MIN
0 5 0
MIN
MAX MAX
36 36 36 36

1 3 1 3
2 2

IMPROPERLY ADJUSTED PROPERLY ADJUSTED

Service Manual 407


HOME PRINT
SERVICE TRAINING
Electrical
Decal of Proportional Motherboard
POSITIONING OF THE CIRCUIT BOARDS IN THE BASE PALTE

PN
2 4 6 8 10 12 14 16 18 20 22
327524

9 SLOT 1 2 3 4 5

MIN
MAX
Slew Boom 2 Boom 4

SERVICE CARD SLOT


RIGHT DOWN DOWN

Slew Boom 2 Boom 4 EMPTY SLOT


LEFT UP UP

7.5v
Output
15v Main Boom 3 volume
DOWN DOWN CABLE
18v
24v
ES
Output
Main Boom 3 volume
UP UP RADIO
FU
FUSE 1 FUSE 1 FUSE 1

FUSE 2 FUSE 2 FUSE 2

+ + - - 20 18 16 14 12 10 8 6 4 2

408 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
Wiring Diagram - DUVAC II 12V / 24V Transformer

Truck batteries

GND
IGN.
24v 12v

30A 30A + 12V - + 12V -

+ 12V - + 12V -

Ignition
switch
(on)

PTO (on)
switch

12V 12V
ACTUATED ACTUATED

24v solenoid 12v solenoid

24v output 12v output


to Schwing unit to Schwing unit

DUVAC II . . . . . . . . . . . . . . Part #319438


SOLENOID . . . . . . . . . . . . .Part #302563
(continuous duty)
01/26/95
PTO SWITCH . . . . . . . . . . .Part #302178 GRP
(cam type)

Service Manual 409


HOME PRINT
SERVICE TRAINING
Electrical
Wiring Diagram - DUVAC II 12V / 24V Transformer

Truck batteries

GND
IGN.
24v 12v A C
30A 30A + 12V - + 12V -

+ 12V - + 12V -
B D

Ignition
switch
(on)
PTO (on)
switch

12V 12V
ACTUATED ACTUATED

24v solenoid 12v solenoid


24v output 12v output 01/26/95
to Schwing unit to Schwing unit GRP

1. Determine which battery doesnt have any accessary power leads. This will be the battery used
to create the 24V power.
2. Disconnect the truck cables from that battery (BE CERTAIN THERE ISNT ANY OTHER WIRES
CONNECTED TO THE 24V BATTERY OR SEVERE DAMAGE COULD RESULT TO OTHER
CIRCUITS ON THE UNIT).
3. Connect jumper from Battery "A" (+ positive) to Battery "B" (- negative) and then connect Battery
"B" (+ positive) to the 24V wire disconnected from the Duvacs 24V post.
4. It may be required to swap Battery "B" with Battery "D" if operated in this mode for an extended
period of time because the battery used to create 24V isnt being charged.

410 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
Digital Proportional - Overview (1 of 5)
Overview
The term DigiProp is used to describe Schwing Americas digital proportional control system. Proportional refers to the fact
that the boom adjusts it's speed in response to the movement of the joysticks. The farther the joystick is moved, the faster the
boom moves. Digital means that the movement of the joystick is translated (by an analog to digital converter) to numbers (zeros
and ones). Once translated to numbers the signal moves into a processor not unlike a computer. The processor responds to the
joystick movements and compares them to a set of values that are preprogrammed into memory. It then translates the numbers
into a signal that is fed to the coils of the hydraulic valves. See Figure 1.

ANALOG 1000 mA
PROPORTIONAL

o
0t
20
Potentiometers
15 volts Proportional
Amplifiers
6 to 9 v olts TO
BOOM

DIGITAL 1000 mA

o
PROPORTIONAL
0t
20

A/D Converters 010 Digital control


01010
system
1 10 1 0 110 TO
BOOM

Figure 1
ana/digi compare.eps

Digital systems have definite advantages over the analog proportional system found on older machines. Because
everything is translated into numbers, there can be no mis-adjustments. Instead of adjusting a trim pot to fine tune
the response, you simply enter in the parameters that you want, and the processor takes care of the rest. In addition,
the zeros and ones (referred to as bits) travel to the processor in groups (referred to as bytes). Each bit in the
byte tells the processor something about the condition of the machine. If you could translate one of the bytes into
plain English, it would look something like this:
I am a Schwing with an ID number of 7. Emergency stop is not activated. Concrete pump is activated in forward.
Boom #3 retract joystick is activated to 48% travel. Boom #2 extend joystick is activated to 85% travel.

Service Manual 411


HOME PRINT
SERVICE TRAINING
Electrical
The processor updates these signals many times per second. The byte always starts with the identification of the
system (I am a Schwing) so that electrical noise from the surrounding area cannot activate a function. Some
types of noise that could send a false signal are cellular phones, garage door openers, police radar, etc. Because of
the identification process, however, these false signals are ignored. See Figure 2.
Digital Code

10101110011000010100100011000100101010010100010 11010001

Identifier

SCHWING F W 20 K28 V24

NG NF MC2 MC1
ST 1
UF K1 TEL ST 2
UE1 K2 REL
UCC1 PROP
UE2 TEL
UCC2 TST 3
NOT1 TST 2
K1 TST 1

A/D Converters RADIO CONTROL FW20


FCC ID. DA87G6 FW20RL
T2 T1

SCHWING AMERICA INC.


GERMANY
SERIAL NR 003 143
FREQ. 456.962S
(mHZ) 457.762S

Figure 2

M.A.T.
The M.A.T. is a hand held programmer that can be plugged into the digital controller. It consists of an 8 digit
alphanumeric display and a 4 button keypad. Its used to access information and program the system. This is
important because you cant troubleshoot a digital system with a test light. However, the advantage of a digital
system is that in most cases the processor already knows what is wrong by the time you notice a problem. See
Figure 3.

*scv

P
C
M.A.T.

Figure 3

412 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
Processor Unit
The digital control system is housed in the device called the Processor unit. The processor unit replaces the relay
enclosure found on analog systems.
This processor unit contains various types of electronic function cards and the optional radio receiver.
The SCV9 card is the master card in the system. Its function is to coordinate the entire system by decoding
instructions from the operator control panels, then sending commands to the appropriate slave cards.
The SCV9 card holds all the programmed settings. It has been programmed at the factory for your specific
machine. Replacement cards contain generic settings. In an emergency, they can be used as is, but they should be
programmed to match the hydraulic system on your machine.
The HC2 and DG8 cards are known as slave cards because they receive commands from the master card, SCV9.
See Figure 4

+ .A12 + A11 + .A10 + .A9 + .A8 + .A7 + .A6 + .A5 + .A4 + .A3
REC 2 SCV HC2L-1 HC2L-1 HC2L-1 HC2L-1 HC2L-1 HC2L-1 DG8-1 DG8-1

M.A.T.
CONNECTOR

DG 8
SCV 9 HC 2
(slave card
(master card) (slave card

Figure 4

Service Manual 413


HOME PRINT
SERVICE TRAINING
Electrical
Card Functions
The HC2 cards provide proportional control of the placing boom and concrete pump output. The HC2 cards send
a 50 milliamp diagnostic signal, generated by the SCV9 card, which continuously tests the various proportional
electrical circuits.
The DG8 cards provide on/off control of the concrete pump, horns, motors and other accessories.
Each of the slave cards control specific functions which are determined by their location in the
digital processor unit. The card positions (numbered horizontally) are also used when troubleshooting with the
M.A.T. to indicate the location of communication errors. The vertical numbers on the right of the drawing indicate
the output channels for the slave card functions. See Figure 5.

1 2 3 4 5 6 7 8
+ .A12 + A11 + .A10 + .A9 + .A8 + .A7 + .A6 + .A5 + .A4 + .A3
REC 2 SCV HC2L-1 HC2L-1 HC2L-1 HC2L-1 HC2L-1 HC2L-1 DG8-1 DG8-1

1
2
3
M.A.T.
CONNECTOR
DIGITAL INPUTS
4
+
5
MIN RES.
6
7
MOTOR
8

Figure 5

414 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
Control System Arrangement
The arrangement of the control systems is shown in Figure 6 below. You can see that the control system is made up
of individual function blocks. Each block is an electronic card. Data is transferred between the cards via the RS485
bus shown in the diagram. The entire coordination of the system is performed by the SCV card which is the
MASTER of the control system. The HC2 and DG8 cards are SLAVE cards that receive commands from the
MASTER and pass them on to the machine. All parameters, i.e. machine-specific settings and functions are stored
in and managed by the MASTER, which is the SCV card, therefore, it is possible to exchange any SLAVE card for
another SLAVE card of the same type without altering any functions or settings in the control system. All
parameters can only be adjusted or changed in the SCV card. All external control instructions are sent by either the
BDI-F (cable remote control), the BDI-A (rear panel control), or radio remote interface in the SCV card to the SCV
MASTER via the bus system. The SCV master card accepts these control instructions, and based on the parameters
stored, sends them via the RS 485 bus to the appropriate slave card (HC2 or DG8). The slave cards then send an
acknowledgment back to the SCV card as to whether or not they can properly follow the control instruction
.

Digital Control Unit

Proportional Control On/Off Control


Throttle Con pump Machines with
Boom 1 Boom 2 Boom 3 Boom 4 Slewing Stroke Limiter Etc. For/Rev Etc. Agitators only

HC2 HC2 HC2 HC2 HC2 HC2 DG8 DG8 DG8


1 2 3 4 5 6 7 8 12

RS 485 BUS

SCV RS232/V24 FW 20/RC


Relay Radio Reciever
Board 9

M.A.T. Push FW 20/R


BDI_A BDI_F
Buttons Transmitter

REC____Relay card (p/n 126442) SBP BUS____Motherboard (p/n 126390)


HC2____Prop. output, 2 function (p/n 125849) FW20RC____Radio control receiver (36X, 42 p/n 130877)
DG8 ____Digital output, 8 function (p/n 125848) FW20TR____Radio control transmitter (52 p/n 147676)
SCV____Interface converter and central processing MAT____Manual adjustment terminal (p/n132426)
unit (p/n 125851) Cable remote control box complete (p/n 13539)
BDI_S____(can be programmed for either BDI_A or BDI_F) Cable remote control cable (p/n 124956)
BDI_A____Rear operators panel interface card (p/n 125846)
BDI_F____Cable remote control interface card (p/n 125847)

Figure 6

Service Manual 415


HOME PRINT
SERVICE TRAINING
Electrical
Digital Proportional - Programming
Programming
To get the most from the programming and self-diagnostic capabilities of the system, you must be able to use the
hand-held M.A.T. and menu survey to navigate to specific locations. See Figure 7.
Think of the menu survey as a road map that allows you to navigate through the system software and the M.A.T. as
the vehicle that takes you from place to place.

Software

*scv
CUSTOMER MENU Version 2.4X

Controller Main Menu Submenus Display Translation

To cable
remote &
back
panel

P *SCV 9 ?PAR ?AUSL ?AUSL 1H 1H1 200


1H2 300
1H3 900
Min. stop current (mA.)

Min. start current (mA.)


Max. current (mA.)
Boom up
Section 1

?AUSL 1S 1S1 200 Min. stop current (mA.)


Boom down
To slave 1S2 300 Min. start current (mA.) Section 1

C cards
?AUSL 2H
1S3 900
2H1 200
2H2 300
Max. current (mA.)
Min. stop current (mA.)

Min. start current (mA.)


Boom up
Section 2

2H3 900 Max. current (mA.)


Min. stop current (mA.)

M.A.T. ?AUSL 2S 2S1 200 Boom down


2S2 300 Min. start current (mA.) Section 2
2S3 900 Max. current (mA.)

?AUSL 3H 3H1 200 Min. stop current (mA.)


Boom up
3H2 300 Min. start current (mA.) Section 3
3H3 900 Max. current (mA.)

?AUSL 3S 3S1 200 Min. stop current (mA.)


Boom down
3S2 300 Min. start current (mA.) Section 3
3S3 900 Max. current (mA.)

?AUSL 4H 4H1 200 Min. stop current (mA.)


Boom up
4H2 300 Min. start current (mA.) Section 4
4H3 900 Max. current (mA.)
?AUSL 4S 4S1 200 Min. stop current (mA.)
Boom down
4S2 300 Min. start current (mA.) Section 4
4S3 900 Max. current (mA.)

?MAST L ML1 200 Min. stop current (mA.)

ML2 300 Min. start current (mA.) Slew


left
ML3 900 Max. current (mA.)
?MAST R MR1 200 Min. stop current (mA.)
Slew
MR2 300 Min. start current (mA.)
right
MR3 900 Max. current (mA.)
?F.MENGE FM1 200 Min. stop current (mA.)
Stroke
FM2 300 Min. start current (mA.) limiter
FM3 900 Max. current (mA.)

Figure 7 (PG-1)

MAT Operation
The MAT (Manual Adjustment Terminal) is the setting and diagnostic unit for the digital proportional control
system.When plugged into the 9 pin front panel connector it goes through an initializing phase, then *SCV 9 or
? SCV 9 appears in the 8-digit, alphanumeric display.
There are 4 keys on the M.A.T. which allow you to scroll through the menu structure in order to set system parameters to there
required values, observe the non-adjustable entries, or perform well aimed signal tracing while troubleshooting.
The symbols on the keys stand for the following:

P = Program = Up

C = Clear = Down

416 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
Menu Structure
Looking at the menu structure you can see it is laid out in columns. This was done to make it easier to follow the
multitude of existing parameters and entries, that are combined into the submenus and main menus. See Figure 8.
The menu system consists of:
Controller Selection
Main Menu
Submenus
Parameters
Entries
The controller selection is marked by an asterisk (*) in the first digit of the M.A.T. display when using software
version 2.4. In software versions 2.2 and 2.3, a question mark will display in the first digit.
Menus have a question mark (?) displayed in the first digit.
Entries are information from the system that cannot be externally changed (similar to measured values obtained by
the connection of instruments).
Parameters are adjustable values which must be set to the conditions found on the machine (e.g., valve currents).
Software
MENU STRUCTURE Version 2.4X

Controller Main Menu Submenus Display Translation

To cable
remote &
back
panel

*SCV 9 ?PAR ?AUSL ?AUSL 1H 1H1 200 Min. stop current (mA.)
Boom up
1H2 300 Min. start current (mA.) Section 1
1H3 900 Max. current (mA.)

?AUSL 1S 1S1 200 Min. stop current (mA.)


Boom down
To slave 1S2 300 Min. start current (mA.) Section 1
cards 1S3 900 Max. current (mA.)

2H1 200 Min. stop current (mA.)


?AUSL 2H Boom up
2H2 300 Min. start current (mA.) Section 2

2H3 900 Max. current (mA.)

2S1 200 Min. stop current (mA.)


?AUSL 2S Boom down
2S2 300 Min. start current (mA.) Section 2
2S3 900 Max. current (mA.)

?AUSL 3H 3H1 200 Min. stop current (mA.)


Boom up
3H2 300 Min. start current (mA.) Section 3
3H3 900 Max. current (mA.)

?AUSL 3S 3S1 200 Min. stop current (mA.)


Boom down
3S2 300 Min. start current (mA.) Section 3
3S3 900 Max. current (mA.)

?AUSL 4H 4H1 200 Min. stop current (mA.)


Boom up
4H2 300 Min. start current (mA.) Section 4
4H3 900 Max. current (mA.)
?AUSL 4S 4S1 200 Min. stop current (mA.)
Boom down
4S2 300 Min. start current (mA.) Section 4
4S3 900 Max. current (mA.)

?MAST L ML1 200 Min. stop current (mA.)

ML2 300 Min. start current (mA.) Slew


left
ML3 900 Max. current (mA.)
?MAST R MR1 200 Min. stop current (mA.)
Slew
MR2 300 Min. start current (mA.)
right
MR3 900 Max. current (mA.)
?F.MENGE FM1 200 Min. stop current (mA.)
Stroke
FM2 300 Min. start current (mA.) limiter
FM3 900 Max. current (mA.)

Service Manual 417


HOME PRINT
SERVICE TRAINING
Electrical
Moving Through The Menu Survey
Using the M.A.T. to navigate through the menu survey is simply a matter of pressing the buttons on the key pad and
noting your location with the alphanumeric display. See Figures 9, 10, & 11.

To scroll to the right, press the P or program key.

?PAR ?AUSL ?AUSL 1H 1H1 200 M

1H2 300 M
1H3 900 M

?AUSL 1S 1S1 200 M

1S2 300 M
Figure 9 1S3 900 M

To scroll to the left, press the C or clear key once.


To return to the SCV 9 starting point, press C twice.

?PAR ?AUSL ?AUSL 1H 1H1 200


1H2 300
1H3 900
?AUSL 1S 1S1 200
1S2 300
Figure 10 1S3 900

Use the arrow keys to scroll up and down.

?PAR ?AUSL ?AUSL 1H 1H1 200


1H2 300
1H3 900
?AUSL 1S 1S1 200
1S2 300
1S3 900
?AUSL 2H 2H1 200
2H2 300
Figure 11

418 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
Access The Service Menu
Versions 2.4 and later have two levels of menu access. Connecting the M.A.T. automatically brings you to the
customer menu. The second menu level called the service menu, is hidden. See Figure 12.
To access the service menu:
Press the letter P to enter main menu
Scroll down the main menu to system
Then, press P again
The M.A.T. display now reads SCV S. Press the P key once, the C key once, and the up arrow key once.
The display will now read NR500.
Press the P key again; a dotted line will appear in the display.
Use the up arrow key to change the value in the display to 530. Press P again, a dashed line will replace the
dotted line meaning the setting has been saved.
You now have access to the service menu items.

?RAMPE ?RAMP UP T1LU 1.0


T1RU 1.0
T2LU 1.0
T2RU 1.0
T3LU 1.0
T3RU 1.0
?RAMP DN T1LD 0.5
T1RD 0.5
T2LD 0.5
T2RD 0.5
T3LD 0.5
Customer T3RD 0.5

Menu RP1 25
RP2 50
(White) RP3 75

?INS ?V24 OK 0
CE 0
FE 0
PE 0
OE 0
VE 0
?TELEGR. W0 0000
W1 0000
W2 0000
W3 0000
W4 0000
W5 0000
Service CRC 00

Menu ?SELECT A1Hs ON


A1Ss ON
(Gray) A2Hs ON
A2Ss ON
A3Hs ON
A3Ss ON
A4Hs ON
A4Ss ON
MLs ON
MRs ON
FMs ON

CERR
NA_F OFF
NA_C OFF
STOER 0
(PG-2) PERR

Figure 12

Service Manual 419


HOME PRINT
SERVICE TRAINING
Electrical
Identifying the Entries and Parameters
Each entry or parameter is shown in the 8-digit display of the MAT. The left side shows an alphanumerical abbreviation with
a maximum of four digits which serves to explain the value shown on the right. Within this abbreviation, lower case letters are
used to describe the origin or the type of representation of the value. The individual letters stand for the following:

a Signal from the rear panel


f Signal from remote control (radio or cable)
r Signal from the rack
s Function selection (this parameter serves to activate or deactivate certain functions)
p Display value in percent

SCV Card Main Menus

Note: Some of the definitions listed are common to both menu structures, while others are specific to the 2.4 menu.
After selecting the *SCV 9 controller, you can scroll the individual main menu items with the and keys.

The following main menus can be found in the *SCV 9 controller:

?PAR = Parameter Setting main menu display or selection.

?INS = Installation or Start-Up Auxiliary Functions submenu display or selection.

?DIN = Digital Input Data submenu display or selection.

?SOUT1 = First Menu Digital Switching Outputs submenu display or selection.

?SOUT2 = Second Menu Digital Switching Outputs submenu display or selection.

?POUT1 = First Menu Proportional Valve Outputs submenu display or selection.

?POUT2 = Second Menu Proportional Valve Outputs submenu display or selection.

?DIAG = Diagnostic Information submenu display or selection.

?SYSTEM= System Control submenu display or selection.

?GERAET= Unit Control submenu display or selection.

?PAR Main Menu

After selecting the ?PAR main menu, you can scroll the individual submenus with the and keys.

The following submenus can be found in the ?PAR main menu:

?AUSL= Boom Settings submenu display or selection including:

?AUSL_H= Boom 1 Up Current Value Settings submenu display


or selection.

?AUSL_S= Boom 1 Down Current Value Settings submenu display


or selection
?AUSL_H= Boom 2 Up Current Value Settings submenu display or
selection.

420 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

?AUSL_S= Boom 2 Down Current Value Settings submenu display or


selection.

?AUSL_H= Boom 3 Up Current Value Settings submenu display or


selection.

?AUSL_S= Boom 3 Down Current Value Settings submenu display or


selection.

?AUSL_H= Boom 4 Up Current Value Settings submenu display or


selection.

?MAST_L = Slewing Left Current Value Settings submenu display or selection.

?MAST_R = Slewing Right Current Value Settings submenu display or selection.

?F.MENGE = Stroke Limiter Current Value Settings submenu display or selection.

?RAMPE = Ramp Value and Time Settings submenu display or selection


(for R_A2)

Submenus Functions and Parameters

?AUSL_XY = Settings the XY boom current values, where: X = 1 - 4; Y = H or S


The individual parameters are:

XY1 200 =Here, the jump-out or minimum stop current can be set within the
range from 50 to 1100 mA.
Default 200 mA.
XY2 300=Here, the jump-in or minimum start current can be set within the range
from 50 to 1100mA.
Default 300 mA.
XY3 900 = Here, the maximum current can be set within the range from 50 to
1100 mA.
Default 900 mA.
?MAST_X = Setting the current values for boom slewing X, where: X = L (left) or R (eight).
The individual parameters are:
MX1 200 = Here, the jump-out or minimum stop current can be set within the
range from 50 to 1100 mA.
Default 200 mA.
MX2 300 = Here, the jump-in or minimum start current can be set within the
range from 50 to 1100 mA.
Default 300 mA.
MX3 900 = Here, the jump-in or minimum start current can be set within the
range from 50 to 1100 mA.
Default 900 mA.
F.MENGE = Setting the stroke limiter current values
The individual parameters are:
FM1 200 = Here, the jump-out or minimum stop current can be set within the
range from 50 to 1100 mA.
Default 200 mA.
FM2 300 = Here, the jump-out or minimum stop current can be set within the
range from 50 to 1100 mA.

Service Manual 421


HOME PRINT
SERVICE TRAINING
Electrical
Default 300 mA.
FM3 900 = Here, the jump-out or minimum stop current can be set within the
range from 50 to 1100 mA.
Default 900 mA.

RAMPE = Setting ramp control data


(For R_A2 or R_MD types only.)
including:
?RAMP_UP= Submenu with the ramp-uptimes (when push-button is belong pressed,
or when changing over from low ramp value to higher one while
push-button is being held depressed).
The individual parameters are:
TXYU 1.0 = Here, the ramp-up time for speed step X, triggered by control
switch Y, can be set within the range from 0.1 to 5.0 sec/100%.
Default 1.0.
Where: X = 1 - 3; Y = L (left)(/ R (ight).

?RAMP_DN= Submenu with the ramp-down times (when push-button is being


released, or when changing over from high ramp value to lower one
while push-button is being held depressed).
The individual parameters are:
TXYD 1.0= Here, the ramp- time for speed step X, triggered by
control switch Y, can be set within the range from 0.1 to
5.0 sec/100%.
Default 1.0.
Where: X = 1 - 3; Y = L (eft)( / R (ight).

RP1 25 = Here, the speed step 1 ramp value can be set within the range from 0 to 99%.
Default: 25.

RP2 50 = Here, the speed step 2 ramp value can be set within the range from 0 to 99%.
Default: 50.

RP2 75 = Here, the speed step 3 ramp value can be set within the range from 0 to 99%.
Default: 75.

?SELECT
Submenu Functions and Parameters (In Service Menu Only!)
?SELECT = Submenu for locking or unlocking prop channels (In service menu only!).
The individual parameters are:

AXYsON = Parameter, by means of which the prop output for boom XY


(X = 1 - 4; Y = U/D) can be activated or deactivated.

MX ON= Parameter, by means of which the prop output for boom slewing X
(X = L/R) can be activated or deactivated.

FM ON= Parameter, by means of which the prop output for the stroke limiter
can be activated or deactivated.

422 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
?V24 Submenu Functions and Parameters
?V24 = V 24 (radio remote) interface state display submenu.
The individual displays are:
OK 00 = Indicating the number of correctly received data blocks.
For proper operation, this number must continuously grow.
CE 00 = Indicating the number of errors determined when the checksum was
checked (Checksum Error).
For proper operation, this number must not grow or may only grow
slowly.
FE 00 = Indicating the number of errors determined when the length of a data
block was checked (Framing Error).
For proper operation, this number must not grow or may only grow
slowly.
PE 00 = Indicating the number of errors determined when the parity was
checked (Parity Error).
For proper operation, this number must not grow or may only grow
slowly.
OE 00 = Indicating the number of errors caused by telegram buffer overflow
(Overflow Error).
For proper operation, this number must not grow or may only grow
slowly.
VE 00 = Indicating the number of errors caused by software telegram buffer
overflow buffer Overflow Error).
For proper operation, this number must not grow or may only grow
slowly.

?TELEGR.=RS 232 Interface Original Telegram submenus display or selection


(In service menu only!)
W0 0000= Original data word 0 in hexadecimal representation.
Start and mode ID.

W1 0000= Original data word 1 in hexadecimal representation.


Pulse channels 16 - 1.

W2 0000= Original data word 2 in hexadecimal representation.


Pulse channels 32 - 17.

W3 0000= Original data word 3 in hexadecimal representation.


Prop channels 1 + 2.

W4 0000= Original data word 4 in hexadecimal representation.


Prop channels 3 + 4.

W5 0000= Original data word 5 in hexadecimal representation.


Prop channels 5 + 6.

CRC 00= Original data byte 13 in hexadecimal representation.


Checksum.

?DIN Main Menu


After selecting the ?DIN main menu, you can scroll the individual entries with the and keys.
In the ?DIN main menu, all the input signals recognized by the system are represented. They are divided into submenus as-
signed to the individual signal sources.

Service Manual 423


HOME PRINT
SERVICE TRAINING
Electrical
The following submenus can be found:

?BDI_A= Input Date from BDI_A (Rear Panel) Display submenu display or selection.

?BDI_F= Input Date from BDI_F (Cable or Radio Remote Control) Display submenu
display or selection.

?RACK= Input Date from Rack Display submenu display or selection.

?RACK Submenu Functions and Parameters


?RACK= Submenu for the display of input date from the rack.
The individual displays are:
LDK O/F = Entry indicating how the system recognized the alternator (D+)
input nstruction.

UMSO/F= Entry indicating how the system recognized the outrigger input
instruction.

DWLO/F= Entry indicating how the system recognized the limit switch slewing
left input instruction.

DWRO/F= Entry indicating how the system recognized the limit switch slewing
right input instruction.

BPVO/F= Entry indicating how the system recognized the concrete pump
forward input instruction from site control.

BRPO/F= Entry indicating how the system recognized the concrete pump
reverseinput instruction from site control.

WMNrO/F= Entry indicating how the system recognized the water level
minimuminput instruction.

RWKO/F = Entry indicating how the system recognized the agitator ON input
instruction.
(Input active for AGRs = 1 function.)

REPO/F= Entry indicating how the system recognized the Maintenance ON input
instruction.
(Input active for MTNs = ON function.

424 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
?BDI A Submenu Functions and Parameters
?BDI_A= Submenu for the display of the input data from the rear panel.
The individual displays are:
Sxa 0000= Entry indicating the hexadecimal code of the rear panel input ports.
(In service menu only!)

Detailed hardware knowledge is necessary to understand this entry. One can


determine the following guideline for servicing: Each actuation of a switching
element must cause a digit in the display to change.

?DIGa = Digital Inputs from BDI_A (Rear Panel) submenu display or


selection.
The individual displays are:
ASWO/F= Entry indicating how the system recognized the spotlight ON
input instruction.

HUPaO/F= Entry indicating how the system recognized the horn


(communication) input instruction.

RTHaO/F= Entry indicating how the system recognized the vibrator


manual input instruction.

RTAaO/F= Entry indicating how the system recognized the vibrator


automatic input instruction.
KPRaO/F= Entry indicating how the system recognized the compressor
ON input instruction.
WPEaO/F= Entry indicating how the system recognized the water pump
ON input instruction.
BPVaO/F= Entry indicating how the system recognized the concrete pump
forward input instruction.
BPRaO/F= Entry indicating how the system recognized the concrete pump
reverse input instruction.
MONaO/F= Entry indicating how the system recognized the motor ON
input instruction.
MOFaO/F= Entry indicating how the system recognized the motor OFF
input instruction.
MUPaO/F= Entry indicating how the system recognized the rpm + input
instruction.
MDNaO/F= Entry indicating how the system recognized the rpm - input
instruction.
FSTaO/F= Entry indicating how the system recognized the remote control
OFF input instruction.
REiaO/F= Entry indicating how the system recognized the spare X
input instruction. Where X = 1 to 3.
FMpaO = Entry representing the stroke limiter potentiometer setting
recognized. 0...99 = MIN...MAX potentiometer setting in %.

Service Manual 425


HOME PRINT
SERVICE TRAINING
Electrical
?BDI F Submenu Functions and Parameters
?BDI_F = Submenu for the display of the remote control input data (cable or radio).
The individual displays are:
Sxf 0000=Entry indicating the hexadecimal code of the remote control input ports.
(In service menu only!)
Detailed hardware knowledge is necessary to understand this entry. One can determine the following guideline for
servicing: Each actuation of a switching element must cause a digit in the display to change.

DIGf = Digital inputs from BDI_A (Remote Control) submenu display or selection.
The individual displays are:

MSTS= Switches from Joystick submenu display or selection.


M1 O/F= Entry indicating how the system recognized the boom 1
input instruction.
M23O/F= Entry indicating how the system recognized the boom 2/3
input instruction.
M4 O/F= Entry indicating how the system recognized the boom 4
input instruction.
MMO/F= Entry indicating how the system recognized the slewing
input instruction.
DSLO/F= Entry indicating how the system recognized the push-button
left input instruction.
DSRO/F= Entry indicating how the system recognized the push-button
right input instruction.
HUPO/F= Entry indicating how the system recognized the horn
(communication) input instruction.
BPVO/F = Entry indicating how the system recognized the concrete pump
forward input instruction.
BPRO/F = Entry indicating how the system recognized the concrete pump
reverse input instruction.
MONfO/F= Entry indicating how the system recognized the motor ON
input instruction.
MOFfO/F= Entry indicating how the system recognized the motor ON
input instruction.
MUPfO/F= Entry indicating how the system recognized the rpm + input
instruction.
MDNfO/F= Entry indicating how the system recognized the rpm - input
instruction.
RTAfO/F= Entry indicating how the system recognized the vibrator automatic
input instruction.
RP1fO/F= Entry indicating how the system recognized the ramp 1 input
instruction.
For the FBP type, this entry is substituted by:
SP2fO/F= Entry indicating how the system recognized the drum speed 2
input instruction.

RP3fO/F= Entry indicating how the system recognized the ramp 3 input
instruction.
For the FBP type, this entry is substituted by:
AUTfO/F= Entry indicating how the system recognized the automatic
input instruction.
RWVfO/F= Entry indicating how the system recognized the agitator forward
input instruction.

426 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
RWRfO/F= Entry indicating how the system recognized the agitator reverse
input instruction.
A1p 0= Entry representing the boom 1 control switch actuation converted into
percent.
0... 99 = Control switch up actuation.
0...-99 = Control switch down actuation.
A2p 0= Entry representing the boom 2 control switch actuation converted into
percent.
0... 99 = Control switch up actuation.
0...-99 = Control switch down actuation.
A3p 0= Entry representing the boom 3 control switch actuation converted into
percent.
0... 99 = Control switch up actuation.
0...-99 = Control switch down actuation.
A4p 0= Entry representing the boom 4 control switch actuation converted into
percent.
0... 99 = Control switch up actuation.
0...-99 = Control switch down actuation.
MDp 0= Entry representing the slewing control switch actuation converted into
percent.
0... 99 = Control switch right actuation.
0...-99 = Control switch left actuation.
FMpf 0= Entry representing the stroke limiter potentiometer setting converted
into percent.
0... 99 = MIN...MAX potentiometer setting.

?SOUT" Main Menu

After selecting the ?SOUT_1 main menu, you can scroll the individual entries with the and keys.

In the ?SOUT_1 main menu, the first group of the digital outputs as to be given out by the system is represented. The fol-
lowing individual entries can be found:

MOF O/F = Entry indicating whether the system wants to give out the motor OFF
output instruction.
MON O/F = Entry indicating whether the system wants to give out the motor ON
output instruction.
MDN O/F = Entry indicating whether the system wants to give out the rms - output
instruction.
MUP O/F = Entry indicating whether the system wants to give out the rms + output
instruction.
HP1 O/F = Entry indicating whether the system wants to give out the horn 1
(communication) output instruction.
HP2 O/F = Entry indicating whether the system wants to give out the horn 2
(slewing mechanism end position) output instruction.
ASW O/F = Entry indicating whether the system wants to give out the spotlight output
instruction.
RTE O/F = Entry indicating whether the system wants to give out the vibrator
output instruction.
After selecting the ?SOUT_2 main menu, you can scroll the individual entries with the and keys.
In the ?SOUT_2 main menu, the second group of the digital outputs as to be given out by the system is represented. The
following individual entries can be found:

Service Manual 427


HOME PRINT
SERVICE TRAINING
Electrical
BPR O/F = Entry indicating whether the system wants to give out the concrete pump
reverseoutput instruction.
BPV O/F = Entry indicating whether the system wants to give out the concrete pump
forwardoutput instruction.
UMS O/F = Entry indicating whether the system wants to give out the outrigger output
instruction.
WPE O/F = Entry indicating whether the system wants to give out the water pump
output instruction.
KPR O/F = Entry indicating whether the system wants to give out the compressor
output instruction.
RWK O/F = Entry indicating whether the system wants to give out the agitator output
instruction.
MFU O/F = Entry indicating whether the system wants to give out the boom movement
output instruction.
BPK O/F = Entry indicating whether the system wants to give out the oil cooler
output instruction.

?POUT Main Menu


After selecting the ?POUT_1 main menu, you can scroll the individual entries with the and keys.

In the ?POUT_1 main menu, the first group of the proportional outputs as to be given out by the system is represented. The
following individual entries can be found:

A1H XXX = Entry indicating what current the system wants to drive through the boom
1 up valve.
A1S XXX = Entry indicating what current the system wants to drive through the boom
1 down valve.
A2H XXX = Entry indicating what current the system wants to drive through the boom
2 up valve.
A2S XXX = Entry indicating what current the system wants to drive through the boom
2 down valve.
A3H XXX = Entry indicating what current the system wants to drive through the boom
3 up valve.
A3S XXX = Entry indicating what current the system wants to drive through the boom
3 down valve.
A4H XXX = Entry indicating what current the system wants to drive through the boom
4 up valve.
A4S XXX = Entry indicating what current the system wants to drive through the boom
4 down valve.

After selecting the ?POUT_2 main menu, you can scroll the individual entries with the and keys.

In the ?POUT_2 main menu, the second group of the proportional outputs as to be given out by the system is represented.
The following individual entries can be found:

MR XXX = Entry indicating what current the system wants to drive through the
slewing right valve.
ML XXX = Entry indicating what current the system wants to drive through the
slewing left valve.
FM XXX = Entry indicating what current the system wants to drive through the
stroke limiter valve.

428 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
?DIAG Main Menu

After selecting the ?DIAG main menu, you can scroll the individual submenus and entries with the and keys.

In the ?DIAG main menu, a few entries can be found for easier diagnosing. The following individual entries can be found:

WAS O/F = This entry indicates whether the control system is under restart protection
for the time being, i.e. no output signal is given unless all instruction
sources of the newly selected mode (LOCAL or REMOTE) are at their
neutral positions.
NAH O/F = Entry indicating whether the control system is in LOCAL mode.
FERN O/F = Entry indicating whether the control system is in REMOTE mode.
REPB O/F = Entry indicating whether the control system is in maintenance mode.
(On-site control active!)
MAST O/F = Entry indicating whether the control system wants to five out the
boom active output instruction.
DWL O/F = Entry indicating how the system recognized the limit switch slewing left
input instruction.
DWR O/F = Entry indicating how the system recognized the limit switch slewing
right input instruction.
LDK O/F = Entry indicating how the system recognized the alternator (D+) input
instruction.
WMH O/F = Entry indicating how the system recognized the water level minimum
input instruction.

?SYSTEM Main Menu


After selecting the ?SYSTEM main menu, you can scroll the individual submenus and entries with the aid of the and
keys.

In the ?SYSTEM main menu, some system information and setting aids can be found. This menu should only be used by
especially trained personnel as system data can be changed here that may result in system failure when entered in the wrong
way!!! The following individual entries can be found:
SCV_S = This entry indicates which hardware (which card) and which software
(program) can be found.

This entry allows for opening the service menu:


1.Pressing key P once: SCV_S menu
2.Pressing key C once: SCV_S menu
3.Pressing key once: NO500
4.Enter and save the code number (530) as for normal parameters

V2.4x = This entry indicates what software version is found. (See Explanation of Different Software Versions).
TYPXXX = This entry indicates what type of unit the card is currently programmed to.

No re-programming is possible here!


Types of units which can be indicated:NORMBoom 2 / 3 changeover
R_A2Boom 2 ramp control

hh : mm : ss = This entry indicates the time of operation since the last reset or restart.
USAGE XX = This entry indicates the current usage of the bus system in percent (0...99).
!RESET = By selecting this item, a so-called warm start can be initiated, i.e. the system
is brought to the same condition as after turning on the supply voltage.

! N E W = Selecting this item brings all parameters in the system to factory-set default.

Service Manual 429


HOME PRINT
SERVICE TRAINING
Electrical
In such case, the system will request you to acknowledge by the same keys
if you really want to change the parameters.

?GERAET Main Menu (In Service Menu Only!)


After selecting the ?GERAET main menu, you can scroll the individual submenus and entries with the and keys.

In the ?GERAET main menu, all unit-specific settings are concentrated. The following
individual entries can be found:

TYP XXX = The type of equipment can be selected here:


NORM Boom 2 / 3 changeover
R_A2 Boom 2 ramp control
Default: NORM

REP OFF = This serves to select the concrete pump on-site control mode.
If on-site control is to be activated by a release switch, this parameter must be programmed ON.
Default: OFG

RWK 0 = This switches off the optional agitator (0), and activates it for simple functioning forward only / 1), or for
extended functioning (forward and reverse / 2).
Default: 0

FHYS 2.0 = This serves to set the hysteresis compensation factory within the range from 1.0 to 10.0.
Default 2.0

IVOR 50 = This serves to set the driver current within the range from 0 to 200mA.
Default: 50 mA

V2.4 Menus
The V2.4x software version has two different levels of access, the customer menu and the service menu. The customer menu
has the parameter settings for the current that is used for driving the hydraulic valves. These settings are changeable from the
customer menu in the ?PAR portion of the main menu. The customer menu also allows you to view non-changeable entries
such as inputs to and outputs from the SCV card. The customer menu only allows you access to the SCV card.

The service menu allows you to access some extra troubleshooting entries in the SCV card along with all HCL and DG cards.
Along with this, you can also view the BDI_A (rear operators panel card and the BDI_F (cable remote) card.

On the following pages containing the 2.4 menu structure, the service menu entries are all the entries in the shaded boxes. All
the entries in the unshaded boxes can be accessed from the customer or the service menu. To access the service menu, do the
following:

1. From the SCV entry in the controller column, you press the P button. This will bring
up the ?PAR entry in the main menu column.
2. Press the arrow key down until the ?SYSTEM entry is displayed on the mat.
3. Press P to display SCV_S.
4. Press the P key one, then the C key once, and finally the arrow up key once.
The display should now read NR500.
5. Press the P key and a dotted line will appear under the NR500.
6. Press the arrow up key until the display reads NR530.
7. Press the P key and a dashed line will appear under the NR530. You now have access
to all entries in the customer and service entries.

Every time the unit is reset, either by shutting off the power and turning it back on, or my using the reset function in the mat,
you will automatically be in the customer menu and must re-enter the code to access the service menu.

430 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
Software Versions
There are a few different software versions used on the digital proportional units. The SCV cards have versions
2.2x, 2.3x and 2.4x. The x denotes that there could be another digit in that location, for example 2.46 or 2.48. The
earlier versions (2.2x and 2.3x) have a ? in front of the SCV display on the MAT. The 2.4x version will have a * in
front of the SCV displayed on the MAT. You can also see what version software you have by scrolling to the
system entry in the main menu column. Version 2.3x and 2.4x can be used in place of a version 2.2x. The 2.2x
and 2.3x version cannot be used in a unit that has ramp functions for boom controls or remote agitator control, as
used in the 52ms. The 2.2x and 2.3x also cannot be used in units that have on site activation switches.

On the following pages there is one menu structure for the 2.2x and 2.3x version and one menu structure for the
2.4x version.

The BDI cards or the cards used for the rear panel and remote control box can also have various versions. The
versions are either 1.xx or 2.xx. In the 1.xx version the cards were specific to their location, ie., the BDIA card was
used for the rear panel and the BDIF card was used for the remote box. The 2.xx version is called BDI S and it can
be programmed to be used in the rear panel or remote box. The versions are interchangeable, however the 1.xx
version cannot be used in systems with remote agitator controls as used in the 52m.

The HCL and DG cards have different versions and they are interchangeable and compatible with all SCV card
version

Service Manual 431


HOME PRINT
SERVICE TRAINING
Electrical

Software
MENU STRUCTURE Version 2.4X

Controller Main Menu Submenus Display Translation

To cable
remote &
back
panel

*SCV 9 ?PAR ?AUSL ?AUSL 1H 1H1 200 Min. stop current (mA.)
Boom up
1H2 300 Min. start current (mA.) Section 1
1H3 900 Max. current (mA.)

?AUSL 1S 1S1 200 Min. stop current (mA.)


Boom down
To slave 1S2 300 Min. start current (mA.) Section 1
cards 1S3 900 Max. current (mA.)

2H1 200 Min. stop current (mA.)


?AUSL 2H Boom up
2H2 300 Min. start current (mA.) Section 2

2H3 900 Max. current (mA.)

2S1 200 Min. stop current (mA.)


?AUSL 2S Boom down
2S2 300 Min. start current (mA.) Section 2
2S3 900 Max. current (mA.)

?AUSL 3H 3H1 200 Min. stop current (mA.)


Boom up
3H2 300 Min. start current (mA.) Section 3
3H3 900 Max. current (mA.)

?AUSL 3S 3S1 200 Min. stop current (mA.)


Boom down
3S2 300 Min. start current (mA.) Section 3
3S3 900 Max. current (mA.)

?AUSL 4H 4H1 200 Min. stop current (mA.)


Boom up
4H2 300 Min. start current (mA.) Section 4
4H3 900 Max. current (mA.)
?AUSL 4S 4S1 200 Min. stop current (mA.)
Boom down
4S2 300 Min. start current (mA.) Section 4
4S3 900 Max. current (mA.)

?MAST L ML1 200 Min. stop current (mA.)

ML2 300 Min. start current (mA.) Slew


left
ML3 900 Max. current (mA.)
?MAST R MR1 200 Min. stop current (mA.)
Slew
MR2 300 Min. start current (mA.)
right
MR3 900 Max. current (mA.)
?F.MENGE FM1 200 Min. stop current (mA.)
Stroke
FM2 300 Min. start current (mA.) limiter
FM3 900 Max. current (mA.)

432 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

Controller Main Menu Submenus Display Translation

?RAMPE ?RAMP UP T1LU 1.0 Only when ramp function is


activated
T1RU 1.0
T2LU 1.0
T2RU 1.0
T3RU 1.0
T3RU 1.0
?RAMP DN T1LD 0.5
T1RD 0.5
T2LD 0.5
T2RD 0.5
T3LD 0.5
T3RD 0.5

RP1 25
RP2 50
RP3 75

?INS ?V24 OK 0 No. of correctly received data blocks.


For proper operation, no. must cont. grow.
No. of errors determined when the checksum
CE 0 was checked. No. must not grow/grow slowly.
No. of errors determined when lengh of a data
FE 0 block checked. No. must not grow/grow slowly.
No. of errors determined when parity was checked.
PE 0 No. must not grow/grow slowly.
No. of errors caused by telegram buffer overflow.
OE 0 No. must not grow/grow slowly.
VE 0 No. of errors caused by software telegram
buffer overflow. No. must not grow/grow slowly.

?TELEGR. W0 0000
W1 0000
W2 0000
W3 0000
W4 0000
W5 0000
CRC 00

?SELECT A1Hs ON
A1Ss ON
A2Hs ON Lock/Unlock
A2Ss ON Proportional
A3Hs ON Outputs
A3Ss ON
A4Hs ON
A4Ss ON
MLs ON
MRs ON
FMs ON

CERR Communication error (See Pg. 4 )

NA_F OFF --------


NA_C OFF --------
STOER 0 --------
Version 2.4X Prop. output
PERR Hardware error

Service Manual 433


HOME PRINT
SERVICE TRAINING
Electrical

Controller Main Menu Submenus Display Translation


Rear panel all functions
Sxa 0000 Hexidecimal code

?DIN ?BDI-A
?DIGa Spotlight
ASWa O/F
Horn
HUPa O/F
RTHa O/F Vibrator Manual
Vibrator Automatic
RTAa O/F
Compressor
KPRa O/F
Water Pump
WPEa O/F
Concrete Pump Forward
BPVa O/F
Concrete Pump Reverse
BPRa O/F
Engine Start
MONa O/F
Engine Stop
MOFa O/F
RPM Up
MUPa O/F
RPM Down
MDNa O/F
Local (on)/Remote (off)
FSTa O/F
RE1a O/F Spare

RE2a O/F Spare


Spare
RE3a O/F
FMpa O Stroke Limiter
Remote control all functions
Sxf 0000 hexidecimal code
?BDI_F
?DIGf ?MSTS M 1 O/F Boom 1 Joystick Microswitch
M 23 O/F Boom 2/3 Joystick Microswitch
M 4 O/F Boom 4 Joystick Microswitch

MM O/F Slewing
DSL O/F Push button Left

DSR O/F Push button Right

HUPf O/F Horn


BPV f O/F Concrete Pump Forward
BPRf O/F Concrete Pump Reverse
MON f O/F Engine Start
MOF f O/F Engine Stop

MUPf O/F RPM Up

MDN f O/F RPM Down


RTAf O/F Vibrator Automatic

RP1f O/F Ramp 1

RP3f O/F Ramp 3

RWVf O/F Agitator Forward


RWRf O/F Agitator Reverse

A1p 0 Boom 1 Potentiometer

A2p 0 Boom 2 Potentiometer

A3p 0 Boom 3 Potentiometer

A4p 0 Boom 4 Potentiometer


MDp 0 Slewing Potentiometer
FMpfs 0 Stroke Limiter Potentiometer

Version 2.4X

434 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

Controller Main Menu Submenus Display Translation

?RACK LDKr O/F Alternator D+


UMSr O/F Outrigger
DWLr O/F Slew Left Limit Switch
DWRr O/F Slew Right Limit Switch
BPVr O/F Concrete Pump Forward

BPRr O/F Concrete Pump Reverse

WMNr O/F Water Level Min


RWKr O/F Agitator

REPr O/F Maintenance On

?SOUT 1 MOFo O/F Engine Stop


MONo O/F Engine Start
MDNo O/F RPM Down
MUPo O/F RPM Up
HP1o O/F Horn 1
HP2o O/F Horn 2
ASWo O/F Spotlight
RTEo O/F Vibrator

?SOUT 2 BPRo O/F Concrete Pump Reverse


BPVo O/F Concrete Pump Forward
UMSo O/F Outrigger
WPEo O/F Water Pump
KPRo O/F Compressor
RWKo O/F Agitator
MFUo O/F Boom Movement
BPK o O/F Oil Cooler
RWVo O/F Agitator Forward
RWRo O/F Agitator Reverse

?POUT 1 A1Ho 0 Boom 1 Up Prog. Output Current

A1So 0 Boom 1 Dn Prog. Output Current

A2Ho 0 Boom 2 Up Prog. Output Current

A2So 0 Boom 2 Dn Prog. Output Current


A3Ho 0 Boom 3 Up Prog. Output Current
A3So 0 Boom 3 Dn Prog. Output Current
A4Ho 0 Boom 4 Up Prog. Output Current

A4So 0 Boom 4 Dn Prog. Output Current

?POUT 2 MR o 0 Slewing R. Programmed Current


ML o 0 Slewing L. Programmed Current
FM o 0 Stroke Limiter Progammed Current

Version 2.4X

Service Manual 435


HOME PRINT
SERVICE TRAINING
Electrical

Controller Main Menu Submenus Display Translation

?DIAG WAS ON Restart Protection


NAH O/F Local Mode
FERN O/F Remote Mode

REPB O/F Maintenance Mode


MAST O/F Boom
DWL r O/F Slewing Limit Switch Left
DWR r O/F Slewing Limit Switch Right
LDK r O/F Alternator

WMH r O/F Water Level Min

?SYSTEM SCVS Hardware Version


V2.48 Software Version
TYP NORM Type of Unit

HH:MM:SS Time of Operation Since Last Reset


USAGE XX Current Usage by Bus System in %
! RESET Reset the System
! NEW Return to Factory Setting

Norm R_A2 Boom 2/3 Change


?GERAET TYP NORM Boom 2 Ramp

REPs ON
RWKs 2 Agitator For/Rev mode
FHYs 2.0 Refer to balancing valve currents
IVOR 50 Refer to balancing valve currents

Version 2.4X

436 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

Software Rear Panel Card - Controller No. 10 BDI - s


Version 2.1X Card Menu

Controller Main Menu Submenus Display Translation

?BD12 10 SWH HHHH All functional hexadecimal code

?DIGITAL
ASW O/F Spotlight
HUP O/F Horn
RTH O/F Vibrator manual

RTA O/F Vibrator automatic


RPR O/F Compressor
WPE O/F Water pump

BPV O/F Concrete pump forward


BPR O/F Concrete pump reverse
MON O/F Engine start

MOF O/F Engine stop


MUP O/F RPM up
MDH O/F RPM down

FST O/F Remote control/Manual


RE1 O/F Spare
RE2 O/F Spare
RE3 O/F

FMpa XX Stroke limiter set value

"System information" Main Menus


?SYS BDI S Card type/hardware
V2.10 Software version
hh:mm:ss Time of operation since last RESET

USP XX Percentage bus employment


!RESET Reset system / warm start
!N E W Reset parameter to default

TYP A 10 Type selection parameter

Service Manual 437


HOME PRINT
SERVICE TRAINING
Electrical

Software Rear Panel Card - Controller No. 10 BDI - A


Version 1.30 Card Menu

Controller Main Menu Submenus Display Translation

?BD12 10 SWH HHHH All functional hexadecimal code

% FM XX Stroke limiter set value

?DIGITAL
ASW O/F Spotlight
HUP O/F Horn
RTH O/F Vibrator manual

RTA O/F Vibrator automatic


RPR O/F Compressor
WPE O/F Water pump

BPV O/F Concrete pump forward


BPR O/F Concrete pump reverse
MON O/F Engine start

MOF O/F Engine stop


MUP O/F RPM up
MDH O/F RPM down

FST O/F Remote control/Manual


RE1 O/F Spare
RE2 O/F Spare
RE3 O/F Spare

?SYS
USP XX Percentage bus employment
TAS XX Task posed by bus communication
BDI A Card type/hardware

V1.30 Software version


hh:mm:ss Time of operation since last RESET

438 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

Software Remote Control Panel - BDI - S Card Menu


Version 2.1x Programmed Type: F11
Controller No. 11
Controller Main Menu Submenus Display Translation

*BDI 11 SWH HHHH All functional hexadecimal code

?DIGITAL ?MSTS
M1 O/F Boom 1 microswitch

M23 O/F Boom 2/3 microswitch


M4 O/F Boom 4 microswitch
MM O/F Slewing microswitch
DSL O/F Lt-hand pushbutton
DSR O/F Rt-hand pushbutton

HUPf O/F Horn

BPVf O/F Concrete pump forward

BPRf O/F Concrete pump reverse


MONf O/F Engine start
MOFf O/F Engine stop
MUPf O/F RPM up
MDHf O/F RPM down

RTAf O/F Vibrator automatic input


RP1f O/F Ramp step 1
RP3f O/F Ramp step 3
RWVf O/F Agitator forward
RWRf O/F Agitator reverse

?ANALOG
A1p XX Boom 1 potentiometer (-99 to 99%)

A2p XX Boom 2 potentiometer (-99 to 99%)


A3p XX Boom 3 potentiometer (-99 to 99%)
A4p XX Boom 4 potentiometer (-99 to 99%)
MDp XX Slewing potentiometer (-99 to 99%)
FMp XX Stroke limiter potentiometer (0 - 99%)
?HEXIN
A1x HHH Boom 1 input value

A23xHHH Boom 2/3 input value


A4x HHH Boom 4 input value
MDx HHH Slewing input value

FMx HHH Stroke limiter input value

?CALIB "Calibration" Main Menu

!C START Start automatic calibration

!C STOP Stop automatic calibration


OFS HHHH ADC offset setting
To be continued on next page ...

Service Manual 439


HOME PRINT
SERVICE TRAINING
Electrical

Software Remote Control Panel - BDI - S Card Menu


Version 2.1x Programmed Type: F11
Controller No. 11
Controller Main Menu Submenus Display Translation

Continued
?PARM1
1PN HHHH Calibration (do not change)
1PX HHHH Calibration (do not change)
1NN HHHH Calibration (do not change)
1NX HHHH Calibration (do not change)
2PN HHHH Calibration (do not change)
2PX HHHH Calibration (do not change)
2NN HHHH Calibration (do not change)
2NX HHHH Calibration (do not change)
4PN HHHH Calibration (do not change)
4PX HHHH Calibration (do not change)
4NN HHHH Calibration (do not change)
4NX HHHH Calibration (do not change)

?PARM2
MPN HHHH Calibration (do not change)
MPX HHHH Calibration (do not change)
MNN HHHH Calibration (do not change)
MNX HHHH Calibration (do not change)
FPN HHHH Calibration (do not change)
FPX HHHH Calibration (do not change)
FNN HHHH Calibration (do not change)
FNX HHHH Calibration (do not change)
MI1 HHHH Calibration (do not change)
MI2 HHHH Calibration (do not change)
MI4 HHHH Calibration (do not change)
MIM HHHH Calibration (do not change)
MF1 HHHH Calibration (do not change)

?SYSTEM "System Information" Main Menu

BDI S Version/ hardware

V2.10 Software version

hh:mm:ss Time of operation since last RESET


USAGE XX Percent bus usage
!RESET Reset system / warm start
! NEW Reset parameter to default

TYP F 11 Type selection parameter

440 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

Software Remote Control Panel - BDI - F


Version 1.30 Card Menu
Controller No. 11
Controller Main Menu Submenus Display Translation

?BDI1 11
?ANALOG
%A1 XX Boom 1 potentiometer (-99% - 99%)

%A2 XX Boom 2 potentiometer (-99% - 99%)


%A3 XX Boom 3 potentiometer (-99% - 99%)
%A4 XX Boom 4 potentiometer (-99% - 99%)
%MD XX Slewing potentiometer (-99% - 99%)
%FM XX Strk lmtr potentiometer (-99% - 99%)

?HEXIN
A1 HHH Boom 1 (Hexidecimal code)

A23 HHH Boom 2/3 (Hexidecimal code)


A4 HHH Boom 4 (Hexidecimal code)
MD HHH Slewing (Hexidecimal code)

FM HHH Stroke limiter (Hexidecimal code)

?DIGITAL
SWH HHHH All function hexadecimal code
M1 O/F Boom 1 microswitch

M23 O/F Boom 2/3


M4 O/F Boom 4
MM O/F Boom slewing
U23 O/F Boom 2/3 pushbutton
HUP O/F Horn

BPV O/F Concrete pump forward

BPR O/F Concrete pump reverse


MON O/F Engine start
MOF O/F Engine stop
MUP O/F RPM up
MDN O/F RPM down

RTA O/F Vibrator automatic


RE1 O/F Spare 1
RE2 O/F Spare 2
RE3 O/F Spare 3

To be continued on next page ...

Service Manual 441


HOME PRINT
SERVICE TRAINING
Electrical

Software Remote Control Panel - BDI - F


Version 1.30 Card Menu
Controller No. 11
Controller Main Menu Submenus Display Translation
Continued

?CALIB ?PARMS
1PN HHHH Calibration (dont change)
1PX HHHH Calibration (dont change)
1NN HHHH Calibration (dont change)
1NX HHHH Calibration (dont change)
BDI 11

!C START Calibration (dont change)

!C STOP Calibration (dont change)


OFS HHHH Calibration (dont change)

?SYS
USP XX Percentage bus usage

TASK XX Task posed by bus communication

BDI F Version type / hardware


V1.30 Software version
hh:mm:ss Time of operation since last RESET
?NEW P Reset parameter to default

442 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
.

Software Proportional Current Output Card - HC2L


Version 1.1x Card Menu
Controller Nos. 1 ... 6
Controller Main Menu Submenus Display Translation

*HC2 X ?DATA I1 XXXX Current 1 output


I2 XXXX Current 2 output
S14 :::: Inputs S1, S2, S3, S4
S58 :::: Inputs S5, S6, S7, S8
ER EOK Error message

?CONFIG DFQ XXX Dither frequency in Hz


RPV XXX Solenoid coil initial resistance

?SYSTEM HC2 S Card type / hardware


V1.10 Software version
HH:MM:SS Time of operation since last RESET
USP XX Percent bus usage

! RESET Reset system / warm start


! NEW Set parameter to default

Service Manual 443


HOME PRINT
SERVICE TRAINING
Electrical

Software Proportional Current Output Card - HC2L


Version 1.0x Card Menu
Controller Nos. 1 ... 6
Controller Main Menu Submenus Display Translation

?HC2 X ?SERV HH:MM:SS Time of operation since last RESET


HC2L S Hardware version
V1.0x Software version
USAGE XX Percent bus usage
TASK XX Task posed by bus communication

?CALIB I1L HHHH (Dont change)


I1H HHHH (Dont change)
I2L HHHH (Dont change)
I2H HHHH (Dont change)

PV 3.0 ----------------
TN 0.06 ----------------
!NEW ENA ----------------
!NEW Return to factory setting

?VARI I1 XXXX Real current 1

I2 XXXX Real current 2

S41 Digital input (4-1)


S85 Digital input (8-5)
ER EOK Error indication

?ALLG DF XXX Frequency setting (Hz)

444 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

Switching Valve Output Card -


Software Controller Nos. 7, 8 and 12. Resp. DG8 Card Menu
Version 1.0x (For Agitator FWD/REV Only)

Controller Main Menu Submenus Display Translation

?DG8 X

?SERV "Service Data" Main Menu

hh:mm:ss Time of operation since last RESET


DG8 S Card type / hardware
V1.0x Software version
USAGE XX Percent bus usage
TASK XX Task posed by bus communication

?VARI "Variables" Main Menu

V41 - - - - Outputs V4, V3, V2, V1


V85 - - - - Outputs V8, V7, V6, V5
S41 : : : : Inputs S4, S3, S2, S1
S85 : : : : Inputs S8, S7, S6, S5

ER EOK Error message

Service Manual 445


HOME PRINT
SERVICE TRAINING
Electrical

Switching Valve Output Card -


Software Controller Nos. 7, 8 and 12. Resp. DG8 Card Menu
Version 1.1x (For Agitator FWD/REV Only)

Controller Main Menu Submenus Display Translation

*DG8 X Controller type w/ network no. (7, 8 or 12)


?VARI "Data" Main Menu
V14 - - - - Outputs V1, V2, V3, V4
V58 - - - - Outputs V5, V6, V7, V8
S14 : : : : Inputs S1, S2, S3, S4
S58 : : : : Inputs S5, S6, S7, S8

?SYSTEM "System Information" Main Menu

DG8 S Card type / hardware


V1.1X Software version
hh:mm:ss Time of operation since last RESET
USP XX Percent bus usage

! RESET Reset system / warm start

?TEST "Output Test" Main Menu

TFREE Teset enable


TEST 0/1 Activate test output
TV1 0/1 Act. or deact. V1 output test
TV2 0/1 Act. or deact. V2 output test

TV3 0/1 Act. or deact. V3 output test

TV4 0/1 Act. or deact. V4 output test

TV5 0/1 Act. or deact. V5 output test


TV6 0/1 Act. or deact. V6 output test
Act. or deact. V7 output test
TV7 0/1
TV8 0/1 Act. or deact. V8 output test

446 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

Software Version
MENU STRUCTURE 2.2X & 2.3X

Controller Main Menu Submenus Display Translation


To cable
remote &
back
panel

?SCV 9 ?PAR ?ALLGEM. Fhys 2.0 Refer to balancing valve current


IVOR 50 Refer to balancing valve current

RWK Software version 2.3 only


RAMP Software version 2.3 only

?AUSL.1H 1H1 200 Min. stop current (mA.)


To slave Boom up
1H2 300 Min. start current (mA.) Section 1
cards 1H3 900 Max. current (mA.)

?AUSL.1S 1S1 200 Min. stop current (mA.)


Boom down
1S2 300 Min. start current (mA.) Section 1
1S3 900 Max. current (mA.)

2H1 200 Min. stop current (mA.)


?AUSL.2H Boom up
2H2 300 Min. start current (mA.) Section 2

2H3 900 Max. current (mA.)


Min. stop current (mA.)
?AUSL.2S 2S1 200 Boom down
2S2 300 Min. start current (mA.) Section 2
2S3 900 Max. current (mA.)

?AUSL.3H 3H1 200 Min. stop current (mA.)


Boom up
3H2 300 Min. start current (mA.) Section 3
3H3 900 Max. current (mA.)

?AUSL.3S 3S1 200 Min. stop current (mA.)


Boom down
3S2 300 Min. start current (mA.) Section 3
3S3 900 Max. current (mA.)

?AUSL.4H 4H1 200 Min. stop current (mA.)


Boom up
4H2 300 Min. start current (mA.) Section 4
4H3 900 Max. current (mA.)
?AUSL.4S 4S1 200 Min. stop current (mA.)
Boom down
4S2 300 Min. start current (mA.) Section 4
4S3 900 Max. current (mA.)

?MAST L ML1 200 Min. stop current (mA.)


Slew
ML2 300 Min. start current (mA.)
left
ML3 900 Max. current (mA.)

?MAST R MR1 200 Min. stop current (mA.)


Slew
MR2 300 Min. start current (mA.) right
MR3 900 Max. current (mA.)

?F.MENGE FM1 200 Min. stop current (mA.)


Stroke
FM2 300 Min. start current (mA.) limiter
FM3 900 Max. current (mA.)

Service Manual 447


HOME PRINT
SERVICE TRAINING
Electrical

Controller Main Menu Submenus Display Translation

?INS ?V24 INTS 0


Data received from radio.
bytes.
Amount of received

OK 0 Data received from radio. Amount of correctly


received data.
Data received from radio. Amount of partity
PY 00 faults.
Data received from radio. Amount of reoccuring
OV 00 faults.
FR 00 Data received from radio. Amount of format
faults.
Data received from radio.
W0 0000
W1 0000 Data received from radio.
W2 0000 Data received from radio.
W3 0000 Original data bytes.
W4 0000 Data received from radio.
W5 0000 Data received from radio.
CRC 00 Check overall sum

CERR 0 Communication error (See Pg. 4)

NA_F AUS --------


NA_C AUS --------
STOER 0 --------
Proportional output.
PERR 0 Hardware error.
A1H EIN
A1S EIN
A2H EIN
A2S EIN
A3H EIN
A3S EIN Lock/unlock proportional output
A4H EIN
A4S EIN
ML EIN
MR EIN
FM EIN

?DIN AS 0000 Hexidecimal code from rear panel


FB 0000 Hexidecimal code from remote box
A1 0 Boom 1 Potentiometer (-99 ... 99)

A2 0 Boom 2 Potentiometer (-99 ... 99)

A3 0 Boom 3 Potentiometer (-99 ... 99)

A4 0 Boom 4 Potentiometer (-99 ... 99)


A5 0 Slewing Potentiometer (-99 ... 99)
FM 0 Strk. Limt. Potentiometer (0 ... 99)

Version 2.2X & 2.3X

448 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

Controller Main Menu Submenus Display Translation

?SOUT MOF AUS Engine stop


MON AUS Engine start

MDN AUS RPM Down


MUP AUS RPM Up
HP1 AUS Boom horn
HP2 AUS Slewing horn
ASW AUS Spot light
RTE AUS Vibrator

BPR AUS Concrete Pump Reverse

BPV AUS Concrete pump forward


UMS AUS Boom/outrigger

WPE AUS Water pump

KRP AUS Compressor

RS1 AUS Spare


RS2 AUS Spare
BPK AUS Oil cooler

?POUT A1H 0 Boom 1 Up Prog. Output Current

A1S 0 Boom 1 Down Prog. Output Current

A2H 0 Boom 2 Up Prog. Output Current

A2S 0 Boom 2 Down Prog. Output Current


A3H 0 Boom 3 Up Prog. Output Current

A3S 0 Boom 3 Down Prog. Output Current

A4H 0 Boom 4 Up Prog. Output Current


A4S 0 Boom 4 Down Prog. Output Current

MR 0 Slew Rt. Prog. Output Current

ML 0 Slew Lft. Prog. Output Current


FM 0 Strk. Limit. Prog. Output Current

?SYS !RESET Reset system (power off)

USP XX -------------

TASK XX -------------
SCV_S Hardware Version
V2.21 Software Version
HH:MM:SS Time since last reset
? NEW P Return to the factory setting

Version 2.2X & 2.3X

Service Manual 449


HOME PRINT
SERVICE TRAINING
Electrical

Controller Main Menu Submenus Display Translation

?DG8 8 ?SERV Time since last reset


HH:MM:SS
DG8_S Hardware version
V1.00 Software version

USAGE XX --------------

TASK XX -------------

?VARI V41 Output transistor status (4-1)

V85 Output transistor status (8-5)


S41 Digital input (4-1)

S85 Digital input (8-5)

ER EOK Error indication

?DG8 7 (SAME AS THE "DG8 8")

?HC2 6 ?SERV HH:MM:SS Time of operation since last reset

HC2L_S Hardware version

V1.00 Software version

USAGE XX Percent of bus usage

TASK XX Task passed by bus comm.

?CALIB I1L XXXX (Dont change)

I1H XXXX (Dont change)

I2L XXX (Dont change)

I2H XXXX (Dont change)

PV 3.0 --------------
TN 0.06 --------------
!NEW ENA --------------

!NEW Return to factory setting

?VARI I1 XXXX Real current 1

I2 XXXX Real current 2

S41 Digital input (4-1)

S85 Digital input (8-5)


ER EOK Error indication

?ALLG DF 200 Frequency setting (Hz)

?HC2 5 (SAME AS THE "HC2 6")

?HC2 4 (SAME AS THE "HC2 6")


?HC2 3 (SAME AS THE "HC2 6")
?HC2 2 (SAME AS THE "HC2 6")
?HC2 1 (SAME AS THE "HC2 6")

Version 2.2X & 2.3X

450 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

Controller Main Menu Submenus Display Translation

?BDI1 11 ?ANALOG %A1 XX Boom 1 Potentiometer (-99% = 99)


%A2 XX Boom 2 Potentiometer (-99% = 99)
%A3 XX Boom 3 Potentiometer (-99% = 99)
%A4 XX Boom 4 Potentiometer (-99% = 99)
%MD XX Slewing Potentiometer (-99% = 99)
%FM XX StrkLimiter Pot (-99% = 99)

?HEXIN A1 HHH Boom 1 (Hexidecimal code)

A23 HHH Boom 2/3 (Hexidecimal code)


A4 HHH Boom 4 (Hexidecimal code)

MD HHH Slewing (Hexidecimal code)


FM HHH Strk. Limit. (Hexidecimal code)

?DIGITAL SWH HHHH All functions (Hexidecimal code)


M1 OFF Boom 1 Microswitch
M23 OFF Boom 2/3 Microswitch

M4 OFF Boom 4 Microswitch


MM OFF Slewing Microswitch
U23 OFF Boom 2/3 Pushbutton
HUP OFF Horn

BPV OFF Concrete pump forward


BPR OFF Concrete pump reverse
MON OFF Engine start
MOF OFF Engine stop
MUP OFF RPM Up
MDN OFF RPM Down
RTA OFF Vibrator Automatic
RE1 OFF Spare
RE2 OFF Spare
RE3 OFF Spare

?CALIB ?PRAMS 1PN HHHH Calibration (dont change)

1PX HHHH Calibration (dont change)


1NN HHHH Calibration (dont change)

1NX HHH Calibration (dont change)


BDI 11 Calibration (dont change)

!C_START Calibration (dont change)

!C_STOP Calibration (dont change)


OFS HHHH Calibration (dont change)

?SYS USP XX ----------------

TASK XX ----------------
BDI_F Hardware Version

V1.30 Software Version


HH:MM:SS Time since last reset
?NEW P Return to factory setting

Version 2.2X & 2.3X

Service Manual 451


HOME PRINT
SERVICE TRAINING
Electrical

Controller Main Menu Submenus Display Translation

?BDI2 10 %FM XX Stroke Limiter (%)

?DIGITAL SWH HHHH All Functions (Hexidecimal code)


ASW OFF Spotlight
HUP OFF Horn
RTH OFF Vibrator Manual
RTA OFF Vibrator Automatic
KPR OFF Compressor

WPE OFF Water Pump


BPV OFF Concrete Pump Forward

BPR OFF Concrete Pump Reverse


MON OFF Engine Start

MOF OFF Engine Stop


MUP OFF RPM Up
MDN OFF RPM Down

FST OFF Remote Control/Manual


RE1 OFF Spare
RE2 OFF Spare
RE3 OFF Spare

?SYS USP XX ---------------


TASK XX ---------------
BDI_A Hardware version
V1.30 Software version
HH:MM:SS Time since last reset

Version 2.2X & 2.3X

452 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
Digital Proportional - Balancing Valve Currents
Balancing The Valve Currents
With the digital proportional control system, you no longer have to adjust trim pots to fine tune control response.
You can now simply enter the parameters you want and the microprocessor takes care of the rest.
This is called balancing the valve currents, and it is necessary to provide precise synchronization between joystick
control and boom movement.
Incorrect valve current settings will have an adverse affect on the proportionality of the boom.
There are three adjustments or parameters to set for each boom section as well as for slewing and concrete output.
They are the:
Minimum start current.
Minimum stop current.
And maximum driver current.
The minimum start current controls how the boom reacts as the joystick is moved from the neutral position. It is
the lowest level of driver current required to start the boom moving.
Moving the joystick from the neutral position activates a micro switch. Immediately after the micro switch is
activated the current should be at the minimum start level.
This will provide linear proportional control when setting the boom in motion. See Figure 13.

mA MINIMUM START CURRENT

1000
MAXIMUM CURRENT OUTPUT

900

800
MAX
700

600

500
MIN
400

300

200

100

0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
MIN MAX
PRETENSION PRESSURE (BAR)
MAX MIN

MICROSWITCH
CLOSED

Figure 13

Service Manual 453


HOME PRINT
SERVICE TRAINING
Electrical
If the minimum start current is set too low, the boom will not move with the joystick. This results in a dead spot
as the joystick is moved off the neutral position and the micro switch is activated.
Setting the minimum start current too high will cause the boom to start abruptly and bounce after the micro switch
has been activated.
The minimum stop current controls how the boom slows to a stop as the joystick is moved to the neutral position. It
is the precise point at which the driver current falls below the level necessary to keep the boom in motion.
When the driver current reaches this setting, the micro switch should open. This causes the system to go to the 50
milliamp diagnostic level.
If the minimum stop current is set too high, the boom will be moving too fast when the micro switch closes,
causing it to stop abruptly and bounce.
If it is set too low, the boom will stop before the micro switch closes, and you will have an increased dead area.

mA MINIMUM START CURRENT

1000
MAXIMUM CURRENT OUTPUT

900

800
MAX
700

600

500
MIN
400

300

200
MIN, START
100
SETTING
0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
MIN MAX
PRETENSION PRESSURE (BAR)
MAX MIN
"DEAD" AREA

MICROSWITCH
CLOSED

Figure 14

The maximum current setting controls the amount of driver current available. When properly adjusted, the
hydraulic valve should just contact the mechanical stop as the joystick reaches the 100% position. See Figure 15.

454 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

mA MINIMUM START CURRENT

1000

MAXIMUM CURRENT OUTPUT


900

800
MAX
700

600

500
MIN
400

300

200

100

0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
MIN MAX
PRETENSION PRESSURE (BAR)
MAX MIN

MICROSWITCH
CLOSED

Figure 15

Hysteresis
Because of the inertia generated by the weight of the boom, the system responds differently when increasing the
driver current (accelerating the boom) than it does to decreasing driver current (slowing the boom). This difference
in response is referred to as hysteresis. To provide smooth transitions when controlling boom speed, a hysteresis
compensation factor is programmed into the system. This setting is located in the FHYS 2.0 submenu, but the
value should not be changed.

Diagnostic Signal
Part of the systems self diagnostic ability is a result of a 50 mA driver current programmed into the system. This
diagnostic current is applied to both values on axis at the same time. This small amount of current is not enough to
run the boom; however, it does allow the system to detect an open circuit such as a broken wire or faulty solenoid.

Setting Valve Currents


The procedure for setting the valve currents requires the use of the M.A.T. and menu survey. First, find the value
you want to adjust in the display column of the menu survey. These are located in the P-A-R section of the main
menu.Then chart a course back to the SCV9 starting point. Use the M.A.T. to scroll to the desired location and
observe the current value.
Use the following procedure to change the setting:
7. press the program key once. A dotted line appears under the alpha numeric display, the value can now be changed.

Service Manual 455


HOME PRINT
SERVICE TRAINING
Electrical
8. Press the arrow keys to adjust the value up or down to the desired setting. If you make a mistake, press the C key to start
over.
9. When the parameter is set to the desired value, press the program key again. The dotted line changes to a dashed line indi-
cating the change has been saved.
After setting the driver currents, check the operation of the hydraulic valve by watching the boom and the handle
on the hydraulic valve as you move the joy stick. The boom should just start to move as you move the joy stick off
neutral and you hear the micro switch activate. Then move the joy stick to the 100% position, the handle on the
hydraulic valve should just contact the maximum stop.
Correctly balancing the valve currents precisely tailors the digital controller to the hydraulic system on your unit.
This provides smooth proportional control of boom functions and concrete output.
The initial settings that were programmed into your machine are located on a decal near the digital processor. See
Figure 16.

CURRENT MEASUREMENT DATA


PROPORTIONAL BOOM - DIGITAL
MODEL:
SERIAL NO.
MIN STOPPING CURRENT MIN STARTING CURRENT MAXIMUM CURRENT
FUNCTION (mA) (mA) (mA)

1H1 1H2 1H3

1S1 1S2 1S3

2H1 2H2 2H3

2H1 2H2 2H3

3H1 3H2 3H3

3S1 3S2 3S3

4H1 4H2 4H3

4S1 4S2 4S3

ML1 ML2 ML3

MR1 MR2 MR3

FM1 FM2 FM3

HYSTERESIS COMPENSATION:
DRIVER CURRENT:
Figure 16

456 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
Digital Proportional - Troubleshooting
The digital proportional control is designed with self-diagnostic capabilities built-in to help you quickly and
efficiently locate faults in the system.
When the unit is activated, it continuously monitors the systems and communicates their status using LEDs
located on the digital processor. See Figure 17.

Troubleshooting
LEDs

+ .A12 + A11 + .A10 + .A9 + .A8 + .A7 + .A6 + .A5 + .A4 + .A3
REC 2 SCV HC2L-1 HC2L-1 HC2L-1 HC2L-1 HC2L-1 HC2L-1 DG8-1 DG8-1

M.A.T.
CONNECTOR

Figure 17

If a problem exists, the first step is to check the status of the LEDs on the digital controller. Use the charts to
interpret the messages communicated by the LEDs, then follow the appropriate troubleshooting (T.S.) procedure
on the following page.

Service Manual 457


HOME PRINT
SERVICE TRAINING
Electrical

Troubleshooting
Message Meaning
procedure

None (If a boom function is


All LEDs steady green No faults, system ready inoperative see T. S. proce-
dure 1)

E Stop pressed, Main


All LEDs off No power to unit
power switch off

SCV 9 steady green all


Communication error T. S. procedure 2
others off

SCV 9 & HC 2 flashing Hardware fault T. S. procedure 3

SCV 9 flashing Intermit hardware fault T. S. procedure 4


SCV Red M.A.T. plugged in None

Rear panel card off


No faults None
(inside rear panel)

Rear panel blinking Matching blinking error T. S. procedure 4


(inside rear panel) from SCV card

Red LED on cable remote Matching blinking error


T. S. procedure 4
box or LED on card inside from SCV card
cable remote box blinking.

Rear card or cable card


Problem in card Replace card
steady red

NOTE: The rear panel board will light for approximately 1 second on system activation or restart.
Note: The troubleshooting procedures listed below pertain to the electrical system. Make sure that there are no
problems with the hydraulic system before performing any of these procedures.

458 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
Troubleshooting procedure 1
If one boom function is not working and the LEDs are steady green, youll need to use the M.A.T. and menu
survey to pinpoint the problem.
To do this, first connect the M.A.T. and scroll to the P-A-R main menu, then to the affected boom display. Check
the minimum start, stop and max current parameters. They should approximate the values written on the decal. If
not, reprogram the function to the correct values. If the parameters are set correctly, scroll to the P-OUT main
menu, then to the affected boom display. Move the joystick and watch the value. When the joystick is at the
neutral position, the reading should be 50, indicating the 50 milliamp diagnostic current. As the joystick is moved
towards the 100% position, the reading should rise to the max current setting. If these functions are not correct, try
using the other remote control panel. If that doesnt help or the readings are correct but the boom function still is
not working, check the output current of the affected HC 2 card.

Troubleshooting procedure 2
If none of the control functions are working and the SCV9 card is steady green, but the other cards are off, it
indicates a communication error between SCV9 and one or more of the slave cards.
To locate the problem, connect the M.A.T. and scroll to the INS main menu. Then scroll to the C-E-R-R display
which is the entry for communication errors. The number in the display indicates the position to the right of the
SCV 9 card where the first error occurred. To determine if the problem is on the card, swap it into another position
of the same card type and reset the system. If the error follows to the new position, the board is defective. If the
error is still in the same position, call Schwing Service for assistance.

Troubleshooting procedure 3
If the card that controls the problem function is flashing, along with the SCV9 card, there is a hardware fault
somewhere between the output of the digital processor and the hydraulic valve. To determine if the problem is the
solenoid or the wiring, swap the solenoid caps. If the problem is unchanged, replace the solenoid. If the problem
follows the solenoid caps, the problem is in the wiring. If this is the case, you should consult the electrical
schematics to track the faulty wire.

Troubleshooting procedure 4
If the SCV9 is the only card flashing, it means the problem is intermittent, possibly a bad connection. It continues
to flash because it stores fault information in its memory until the system is reset.
Because of the sensitivity of the system the SCV light may blink for various reasons, if resetting the system does
not clear the problem refer to troubleshooting procedure 3.
Resetting the system can be accomplished either by turning the power off and on, or by using the M.A.T.

Service Manual 459


HOME PRINT
SERVICE TRAINING
Electrical
Troubleshooting The Radio
The radio remote consists of a transmitter built into the battery powered remote control and a receiver built into the
digital processing unit.
All commands transmitted are safety coded, that is they contain an identifier, so that the unit will only respond to
commands from the correct remote control. The receiver checks the command and passes it on only if it is
complete and correct.
If there is interference, the unit will automatically shut down, however, there are two frequencies available that can
be switched at the remote control. See Figure 18.
When using the radio remote, it is important to stay within a safe operating range, always knowing where the boom
is.

Low Battery Communications E- stop


LED LED LED

Emergency Stop Frequency Selector


Figure 18
There are 3 LEDs on the radio remote. The one on the left warns you when the radio battery voltage is getting low.
The center LED indicates when a digital message is being sent. The E-stop LED lights when the emergency stop
on the transmitter has been pressed.
The rechargeable transmitter battery will operate the system for about 8 hours, depending on the age of the
batteries and the operating conditions.
When the battery warning light starts to flash, you have about thirty minutes operating time left before the unit
shuts down due to low battery voltage. The battery charger is located in the cab of the truck. See Figure 19.

POWER

Figure 19

460 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
The other half of the radio remote control is the receiver, which is located in the truck mounted digital processor. It
receives the digital code from the transmitter, checks to make sure the instructions are correct and complete, then
passes them on to the digital processor. See Figure 20.

SCHWING 20 K28

NG NF MC2 MC1
ST 1
UF K1 TEL ST 2
UE1 K2 REL
UCC1 PROP
UE2 TEL
UCC2 TST 3
NOT1 TST 2
K1 TST 1

T 2 T 1

RADIO CONTROL
FCC ID. DA87G6 FW
SCHWING AMERICA .
GERMANY
SERIAL NR 003 143
FREQ. 456.962S
(mHZ) 457.762S

Radio Receiver

Figure 20

Operation
With the Local/Remote switch located on the rear operators panel in the local mode:
1. Connect the Funk plug or cable remote to the remote receptacle (one or the other must be connected to operate a digital
machine). See Figure 21.
2. Properly set the machine, as described in the operators manual, then turn the mode switch back to the remote position.
FUNK

Figure

3. Make sure all the function switches on the remote control transmitter are in the neutral position.
4. Turn the remote control power supply on. (the LED on the right should start flashing)
5. Turn the power switch located on the transmitter to the on position. (the E-stop LED should flash faster) See Figure 22.

Service Manual 461


HOME PRINT
SERVICE TRAINING
Electrical
6. Pull the emergency stop button. (the communication LED should now be on)
7. Activate one of the control functions. (the communication LED should start flashing, indicating messages are being sent)

Low Battery Communications E- stop


LED LED LED

Emergency Stop Frequency Selector

Figure 22

Emergency Stop
Pushing the emergency stop button stops the main functions of the machine.

Automatic Shut down


The unit will automatically shut down in case of:
Low battery voltage
Message errors.
Electronic module failure.
No command messages sent for 30 minutes.

462 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
Trouble-shooting
Many problems with the radio remote control can be identified by interpreting the LEDs on the radio receiver.
The following is a brief explanation of the LEDs:
NG= power supply
UF= vehicle system voltage
UE 1= controller 1 supply
UCC 1= controller 1 supply (+5V)
UE 2= controller 2 supply
UCC 2= controller 2 supply (+5V)
NOT 1= EMERGENCY STOP circuit of controller 1 for controller MC 1
NOT 2 = EMERGENCY STOP circuit of controller 1 for controller MC 2
HF= receiver
K1= RF-channel 1 selected
K2= RF-channel 2 selected
MC 2= controller 2
data message reception
TEL= data message recepton
MC 1= controller 1
ST 1= controller 1 failure
ST 2= controller 2 failure
REL= relay output defective
PROP= proportional control output defective
TEL= data message recepton
TST3= data message error 3
TST2= data message error 2
TST1= data message error1

SCHWING F W 20 K28 V24

NG HF MC2 MC1
ST 1
UF K1 TEL ST 2
UE1 K2 REL
UCC1 PROP
UE2 TEL
UCC2 TST 3
NOT1 TST 2
NOT2 TST 1

T2 T1

RADIO CONTROL FW20


FCC ID. DA87G6 FW20RL
SCHWING AMERICA INC.
GERMANY
SERIAL NR 003 143
FREQ. 456.962S
(mHZ) 457.762S

Service Manual 463


HOME PRINT
SERVICE TRAINING
Electrical
Troubleshooting tables

REMEDIAL
LED DISPLAY MESSAGE
ACTION
UF, UE1, UCC1, UE2, Switch in, check power
None lit Machine power failure
UCC2 supply

UF, On Power supply failure, short-


Call Schwing Service
UE1, UCC1, UE2, UCC2 One off circuit in receiver

Emergency stop activated


Unlock E stop
NOT1, NOT2 ON Fault detected by electronic
See MC1
system

NOT1, NOT2 Off but no function Fuse defective Replace fuse

REMEDIAL
LED DISPLAY MESSAGE
ACTION
Switch on transmitter,
Transmitter scan, no radio
choose better transmitter
K1, K2 Alternately flashing contact
location, check antenna
Message format error
See MC1

REMEDIAL
LED DISPLAY MESSAGE
ACTION
Transmitter off, no radio Switch on transmitter,
contact choose better transmitter
TEL Irregular flashing
Transmitter defective, RF location, check antenna
section defective Call Schwing Service

REMEDIAL
LED DISPLAY MESSAGE
ACTION
Failure in MC1 or in periph-
ST1 On ery module, e.g. REL, NG, Call after Schwing Service
PROP

Failure in MC2, no
ST2 On Call after Schwing Service
exchange of data

464 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

REMEDIAL
LED DISPLAY MESSAGE
ACTION
Vehicle power supply volt-
PROP On Check vehicle power supply
age <20V resp.>28V

TEL No radio reception


Irregular flashing Check transmitter and
Transmitter off or defective
antenna
TST2 On Antenna not installed or
Call Schwing Service
defective

REMEDIAL
TST TST TST
MESSAGE ACTION
3 2 1


No empty message after switch-on emergency Set control element to 0 position
shut-off activated Unlock E stop
HF interference3 Call Schwing Service

Format error in pulse-coded message


Change frequency if fault cannot be rectified
Call Schwing Service

Format error in proportional message


Change frequency if fault cannot be rectified
Call Schwing Service

Another transmitter with the same frequency


nearby, message affected by address error
Change frequency if fault cannot be rectified
Call Schwing Service

Message affected by mode error, encoder


switch in wrong position
Change frequency check encoder switch.
Call Schwing Service

Message affected by cyclic redundancy check


error
Change frequency if fault cannot be rectified
Call Schwing Service

Emergency stop message Rectify fault, unlock E stop

= LED ON = LED OFF = LED Flashing

Service Manual 465


HOME PRINT
SERVICE TRAINING
Electrical

466 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

Comfort Control Manual


Chp. Contents Page

1.0 Working with the info & diagnosis system


1.1 Introduction into the info & diagnosis system 2
1.2 Menu structure of the info & diagnosis system / Operation data display 4

2.0 Parameter setting concrete pump efficiency / Central lubricating system /


Prop characteristics
2.1 Password entry and parameter selection menu 9
2.2 Setting the concrete pump efficiency for pumped volume determination 10
2.3 Setting the central lubricating system 11
2.4 Setting proportional parameters for boom functions 12

3.0 I/O status display signals & references


3.1 Machine control 15
3.2 Concrete pump control 17
3.3 Boom control 18
3.4 Rear panel 20
3.5 Extension module (central lubricating system) 22

4.0 Fault messages and fault causes


4.1 Introduction / Structure of error codes 23
4.2 Control diagnosis electronic modules (fault code S) 24
4.3 Remote control system diagnosis (fault code F) 25
4.4 Machine diagnosis - General (fault code A) 26
4.5 Diesel engine diagnosis / P.T.O. (fault code D) 28
4.6 Concrete pumpe diagnosis (fault code B) 30
4.7 Boom control diagnosis (fault code M) 31
4.8 Central lubricating system
diagnosis / Extension (fault code Z / E) 34

5.0 Interdependence list of most important output signals 35

Annex :Overview info center menu

Vers.: 1.2 Status:02.10.97 U.Weber (TEW)

Service Manual 467


HOME PRINT
SERVICE TRAINING
Electrical
1.0 Working with the info & diagnosis system

1.1 Introduction into the info & diagnosis system

The SCHWING info & diagnosis system for truck-mounted concrete pumps is located in the rear panel unit at the
rear step-ladder of the machine and is operated with the display and the 6 function buttons below.

The info system offers the following functions :

-Pumped volume determination by means of stroke counter and pumped volume calculation
(cf. 1.2.3)
-Extensive operational data acquisition and display (cf. 1.2.4)
-Safely stored malfunction list of the last 100 malfunction messages (cf. 1.2.5)
-Manual operation of lubricating cycles (cf. 1.2.6)
-Status display of all signals of the electric control (cf. 1.2.7 & 3.0)
-Password-protected efficiency adjustment for the pumped volume determination of the concrete pump (cf. 2.0)
-Password-protected parameter setting for the central lubricating system (cf. 2.0)
-Password-protected parameter setting for the proportional boom functions (cf. 2.0)

The diagnosis system monitors the control unit, the machine and partly also the vehicle for malfunctions or
inadmissible states of operation.
The system recognizes e.g. parting of cables or short-circuits in electric lines of solenoids, Fault sensors,
contaminated oil filters or critical hydraulic oil or diesel engine temperatures and displays different operating
conditions.
The system is to assist the concrete pump operator in his work on site and to inform him about the possible causes
of malfunctions when they occur.
The malfunction messages are displayed as continuous text in the form of an easily understandable plain language
message with additional fault code. The manual contains a detailed description of the faults for each fault code (cf
4.0)

In case of recognized malfunctions, the diagnosis system distinguishes between minor faults and severe faults.
Minor faults do not require immediate elimination of the fault cause and the machine can be used - possibly with
some restrictions - until the job is finished
A severe fault bears the risk that the machine or the vehicle may be severely damaged. An immediate elimination of
the fault cause is therefore necessary.

If the integrated diagnosis system recognizes a malfunction or an inadmissible state of operation of the machine, a
horn sounds intermittently and a fault message appears on the display of the rear panel unit.
Moreover, the last 100 recognized malfunctions are stored safely in a malfunction list together with date and time.
They can be recalled at any time.

468 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
In case of a minor fault, the horn signal and the fault message can be switched off by means of the "Hupe / quitt"
button on the remote control box or the cable control box. Switching off the horn does not delete the fault message.
To prevent fault messages from getting lost, a fault message is recalled whenever one of the two "hydraulic on
outriggers" buttons (at the outrigger control block) is recalled and displayed, and until the operator has read the
fault message displayed and acknowledged the message at the rear panel stand with the [QUITT] button below the
display.
Pressing the [QUITT] button once only shuts off the horn signal with the fault message still being displayed. Only
after the [QUITT] button has been depressed a second time, the fault message is deleted from the display.

In the event of severe faults, the horn signal cannot be cancelled with the buttons on the remote control box.

The operator can therefore recognize severe faults by the fact that the horn signal continues to sound although the
[Hupe / quitt] button on the remote control box or the cable control box has been actuated.
Since severe faults cause considerable damage of the machine, the concrete pump operator must inform himself at
the display of the diagnosis system on the machine about the fault occurred. In the event of severe faults, the horn
signal can be cancelled and the fault message be deleted only with the [QUITT] button below the diagnosis display.

Fault messages are also definitely cancelled when the electric control system is switched off.

The operator himself is responsible for the elimination of indicated faults in order to prevent the machine from
being damaged.
If the message of a fault that has not been eliminated is being cancelled, there is no new fault indication.
A persistant fault will however be recognized and reported again by the diagnosis system after the machine has
been de-activated with the EMERGENCY SHUT-OFF button on the machine or on the remote control box.

SCHWING is not responsible for damage caused by non-eliminated faults of the machine !

Service Manual 469


HOME PRINT
SERVICE TRAINING
Electrical
1.2 Menu structure info & diagnosis system / Operation data display
The SCHWING diagnosis system is operated with 6 buttons below the display at the rear panel stand.
The diagnosis system is based on an easily understandable menu system in form of a so-called tree structure.
Depressing the [ENTER] button always branches into the next menu level or recalls the displayed function. The
[CLEAR] button returns to the previous menu level. If further branching into another sub-menu is possible, the
second line in the display shows " / / ENTER / CLEAR ".
Depressing [ENTER] switches the info & diagnosis system on, displaying the main menu after the standard
window.
(cf. annex : Overview info center menu)

The buttons on the display have the following functions :


[ ] or [ ]menu up or down
[ENTER]menu item selection / confirmation / activation of next menu level
[CLEAR]interrupt actual function and back to previous level in menu system
[QUITT]fault message acknowledge / horn shut-off
[START]start of a function (pumped volume counter / manual lubrication)

The operation of the diagnosis system on all menu levels is explained on the following pages.
The message displayed is shown in a frame. The menu functions and the selection of special functions is described
by the key symbols in brackets and the pertaining explanantions.

1.2.1 Standard display & malfunction messages

INFO SYSTEM [ ENTER ] Call up main menu (cf. 1.2.2)


ENTER = On

When the diagnosis system recognizes a malfunction of the machine or the electrical system, the actual
message on the display is overwritten with the actual fault message.

MALFUNCTION 1. x [ QUITT ] Shut off horn signal


(CODE) FAULT MESSAGE
2. x [ QUITT ] Fault message cancel / acknowledge !

Please observe also the detailed description of fault acknowledgement in 1.1.

470 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
1.2.2 Main menu

PUMPED VOLUME [ ENTER ] Sub-menu "Pump Volume" for


/ ENTER / CLEAR
pump volume calculation (cf. 1.2.3)
[] [ CLEAR ] Back to start window

OPERATION DATA [ ENTER ] Call up "Operation Data" sub-menu


/ / ENTER / CLEAR
(cf. 1.2.4)
[ ] [ ] [ CLEAR ] Back to start window

MALFUNCTION LIST [ ENTER ] Call up "Malfunction List" sub-menu


/ / ENTER / CLEAR
(cf. 1.2.5)
[ ] [ ] [ CLEAR ] Back to start window

LUBRICATION-UNIT [ ENTER ] Call up "Central Lubrication" sub-menu


/ / ENTER / CLEAR
(cf. 1.2.6)
[ ] [ ] [ CLEAR ] Back to start window

I/O STATUS DISPL [ ENTER ] Call up "I/O display" sub-menu


/ / ENTER / CLEAR
(cf. 1.2.7)
[ ] [ ] [ CLEAR ] Back to start window

INTERNAL TIMER [ ENTER ] Display of date and time of internal timer


/ / ENTER / CLEAR
(CLEAR = back)
[ ] [ ] [ CLEAR ] Back to start window

SCROLLING [ ENTER ] Scrolling rate fault message adjust


/ / ENTER / CLEAR
(cf. 1.2.8)
[ ] [ ] [ CLEAR ] Back to start window

PARAMETERS [ ENTER ] Call up "Parameter" menu


/ ENTER / CLEAR
(cf. 2.0)
[ ] [ CLEAR ] Back to start window

Service Manual 471


HOME PRINT
SERVICE TRAINING
Electrical
1.2.3 "PUMP VPUME" sub-menu

PUMPED ON JOB (S) [ START ] Start new pump volume determination &
1723.5 cbm
delete old value (cf. 2.2)
[ CLEAR ] Back to main menu

1.2.4 "OPERATION DATA" sub-menu

HYD OIL TEMP Display of actual oil temperature in hydraulic oil reservoir
062 C
[] [ CLEAR ] Back to main menu

PTO SHAFT RPM Display of actual rpm of PTO.


1270 rpm
[] [] [ CLEAR ] Back to main menu

HYD PRESSURE CP Display of actual oil pressure in concrete pump circuit


159 bars
[] [] [ CLEAR ] Back to main menu

CONCR-PUMP HOURS Display of stored operating hours concrete pump


328.3 h
[] [] [ CLEAR ] Back to main menu

BOOM HOURS Display of stored operating hours


406.1 h
placing boom
[] [] [ CLEAR ] Back to main menu

PTO HOURS Display of stored operating hors


469.8 h
PTO.
[] [] [ CLEAR ] Back to main menu

TOTAL STROKES CP Display of stored total number of strokes of concrete pump


18529417 strokes
[] [] [ CLEAR ] Back to main menu

TOTAL VOL. PUMPED Display of stored total pumped quantity of concrete pump
1491258 cbm
[] [] [ CLEAR ] Back to main menu
STROKES PER MIN Display of actual number of strokes of concrete pump in strokes/
21.4 S/min
min
[] [ CLEAR ] Back to main menu

472 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
1.2.5 "MALFUNCTION LIST" sub-menu

16.03.93 / 12:34 [ ] / [ ] Scrolling up & down malfunction list


(CODE) FAULT TEXT (cf. 4.0)
[ CLEAR ] Back to main menu

1.2.6 "LUBRICATION-UNIT" sub-menu

MANUAL LUBRIC. [ START ] Manual lubrication starts


CP & Agitator
[] [ CLEAR ] Back to main menu

MANUAL LUBRIC. [ START ] Manual lubrication starts


Boom
[] [] [ CLEAR ] Back to main menu

MANUAL LUBRIC. [ START ] Manual lubrication starts


Outriggers
[] [ CLEAR ] Back to main menu

1.2.7 "I/O DISPLAY" sub-menu

MACHINE-CONTROL [ ENTER ] Call up I/O display for machine control module (cf.
/ ENTER / CLEAR
3.1)
[] [ CLEAR ] Back to main menu

CP-CONTROL [ ENTER ] Call up I/O display for concrete pump control mod-
/ / ENTER / CLEAR
ule (cf. 3.2)
[] [] [ CLEAR ] Back to main menu

BOOM-CONTROL [ ENTER ] Call up I/O display for boom control module (cf.
/ / ENTER / CLEAR
3.3)
[] [] [ CLEAR ] Back to main menu

REAR PANEL [ ENTER ] Call up I/O display for rear panel module (cf. 3.4)
/ / ENTER / CLEAR
[] [] [ CLEAR ] Back to main menu
EXTENSION I/O [ ENTER ] Call up I/O display for extension module
/ ENTER / CLEAR
(cf. 3.5)
[] [ CLEAR ] Back to main menu

Service Manual 473


HOME PRINT
SERVICE TRAINING
Electrical
1.2.8 SCROLLING" sub-menu

This sub-menu can be used to adjust the so-called "SCROLLING rate" (running speed) of fault message texts in the
display.
For easier checking during adjustment, the "SCROLL-speed" text always moves through the first line of the display
at the actually set speed.

Depressing [ ENTER ] activates the adjusting mode for the scrolling rate.
The activation of the adjusting mode is indicated by a flashing scrolling rate (300 ms) in the display.
By depressing the [ ] [ ] keys, the scrolling-speed rate can be changed by 50 ms at a time. Depressing [ ENTER
] stores the set value and quits the adjusting mode.

Scrolling speed [ ENTER ] Activate adjusting mode


300 ms
[ ENTER ] Store set value
[ CLEAR ] Back to main menu

474 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
2.0 Concrete pump efficiency parameter setting / Central lubrication / Prop
characteristics
2.1 Password entry and parameter selection menu

Unintentional or unauthorized access to the adjustment of set values (parameters) for the pumped volume
determination of the concrete pump for the central lubrication and the prop current characteristics of the boom
functions is protected by a password.
After selecting "PARAMETER" in the main menu, the password must be entered first.

PASSWORD **** [ ] [ ] Enter password and then press


/ / ENTER / CLEAR
[ ENTER ]
[ CLEAR ] Back to main menu

Explanation :

The password can be entered with the [ ] [ ] keys. If one of the keys is kept depressed, the password display
starts incrementing slowly. After abt. 5 seconds, the display starts incrementing faster and after further 5 seconds,
the speed increases once again.

After pressing [ ENTER ] and after the correct password has been selected, the display shows "Password OK" and
jumps to the parameter selection menu.
In the event of a wrong password, the display shows "Password wrong" and the diagnosis system goes back to the
standard display.

CP EFFICIENCY [ ENTER ] Parameter setting for pumped volume calculation


/ / ENTER / CLEAR
of concrete pump
(cf. 2.2)
[] [ CLEAR ] Back to PASSWORD entry

LUBRIC. PARAM [ ENTER ] Call up parameter menu for central lubrication (cf.
/ / ENTER / CLEAR
2.3)
[] [ CLEAR ] Back to PASSWORD entry

PROP-CUR SLEW [ ENTER ] Select parameter setting for BOOM SLEW function
/ / ENTER / CLEAR
[] [ CLEAR ] Back to PASSWORD entry

PROP-CUR BOOM 1 [ ENTER ] Select parameter setting for boom function BOOM
/ / ENTER / CLEAR
1
[] [] [ CLEAR ] Back to PASSWORD entry

Service Manual 475


HOME PRINT
SERVICE TRAINING
Electrical

PROP-CUR BOOM 2 [ ENTER ] Select parameter setting for boom function BOOM
/ / ENTER / CLEAR
2
[] [] [ CLEAR ] Back to PASSWORD entry

PROP-CUR BOOM 3 [ ENTER ] Select parameter setting for boom function BOOM
/ / ENTER / CLEAR
3
[] [] [ CLEAR ] Back to PASSWORD entry

PROP-CUR BOOM 4 [ ENTER ] Select parameter setting for boom function BOOM
/ / ENTER / CLEAR
4
[] [] [ CLEAR ] Back to PASSWORD entry

PROP-CUR BOOM 5 [ ENTER ] Select parameter setting for boom function BOOM
/ / ENTER / CLEAR
5
[] [ CLEAR ] Back to PASSWORD entry

2.2 Setting the concrete pump efficiency for pumped volume determination

The volumetric efficiency of the pumped volume calculation (efficiency CP) of the concrete pump can be set in this
parameter menu.
The setting acts on the pumped volume counter (PUMPED VOLUME) and on the total pumped quantity of the
concrete pump (TOTAL VOL. PUMPED).
The pumping volume of the concrete pump is determined by counting the pump strokes and by calculating the
delivery rate by means of the pumped volume of the pumping cylinder and the CP EFFICIENCY:
EFFICIENCY CP should therefore be an average value for the pump efficiency of the concrete pump depending on
the most often pumped concrete qualities.

[ ENTER ] activates the setting mode for the "Concrete pump efficiency" parameter.
The activation of the adjusting mode is indicated by a flashing percentage for the pumped quantity efficiency in the
display.
The efficiency concrete pump value can then be changed in steps of 1% by pressing the [ ] [ ] keys.
Depressing [ ENTER ] stores the set value and quits the adjusting mode.

EFFICIENCY CP [ ENTER ] Activate adjusting mode


92 %
[ ENTER ] Store set value

[ CLEAR ] Back to parameter selection menu

476 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
2.3 Adjusting the central lubrication
The lubricant amount of the individual circuits of the central lubrication system can be set individually by
presetting the number of greasing cycles if the supplementary module for intelligent central lubrication is installed.

[ ENTER ] activates the adjusting mode for one lubricating circuit.


The activation of the adjusting mode is indicated by a flashing lubricating cycle number in the display.
The number of lubricating cycles can be re-adjusted for the selected lubricating circuit within a range of 0 and 20
greasing cycles by depressing the [ ] [ ] keys. Depressing [ ENTER ] stores the set value and quits the adjusting
mode.

If "0" lubricating cycles have been preset, the corresponding lubricating circuit is shut off.

LUBRIC. CYCLE [ ENTER ] Activate parameter setting for placing boom greas-
BOOM 09
ing circuit
[] [ CLEAR ] Back to parameter selection menu

LUBRIC. CYCLE [ ENTER ] Activate parameter setting for concrete pump/agita-


CP/AGITATOR 12
tor greasing circuit
[ ] [ ] [ CLEAR ] Back to parameter selection menu

LUBRIC. CYCLE [ ENTER ] Activate parameter setting for outrigger greasing


OUTRIGGERS 07
circuit
[ ] [ CLEAR ] Back to parameter selection menu

Service Manual 477


HOME PRINT
SERVICE TRAINING
Electrical
2.4 Adjusting the proportional parameters for boom functions
The electrical characteristics of the proportional valves can be individually adjusted for each boom function.
The correct adjustment of a proportional characteristics curve requires profound machine knowledge and should
only be carried out by specially trained personnel.
Since a machine with wrong settings may get into unsafe operating states, SCHWING GMBH assumes no liability
for events occurring as a consequence of proportional characteristics settings modified by the customer.
After selection of a boom function, 4 parameters can be adjusted for each axis.
For each direction (extend / retract or slew right / left) the pertaining MIN and MAX value of the proportional
characteristics curve can be set.
Depending on the proportional valves installed in the machine, there are two different methods of setting the prop
value parameters.
For prop-current-controlled valves (e.g. REXROTH) the characteristic values are set as current values in mA (valve
type: PROP).
For PWM-controlled valves (e.g. APITECH) the characteristic values are set as percentages of the PWM ratio
(valve type: PULSAR).

[ ENTER ] activates the adjusting mode for a prop parameter.


The activation of the adjusting mode is indicated by a flashing prop parameter value in the display.
The set value can then be changed by depressing [ ] [ ] by 10 mA resp. 1 % for the selected prop parameter.
Depressing [ ENTER ] stores the set value and quits the adjusting mode.

The adjusting ranges of the prop current values are limited as follows :
- Current value for "I min" within 250 mA to 1000 mA.
(The set value must be less than the value for "I max")
- Current value for "I max" within 500 mA to 1500 mA.
(The set value must be greater than the value for "I min")

The adjusting ranges of the PWM percentages are limited as follows :


- Value for "PWM min" in a range of 20 % to 60 %.
(The set value must be less than the value for "PWM max")
- Value for "PWM max" in a range of 40 % to 100 %.
(The set value must be greater than the value for "PWM min")

The following examples illustrate changes of the proportional values for the BOOM SLEWING MECHANISM for
valves of the PROP type and for BOOM SECTION 1 for valves of the PULSAR type.

478 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
Proportional characteristics adjustment for the BOOM SLEW function with PROP valve
types :

BOOM SLEW RIGHT Display of actual value for proportional current boom slew
I act 510 mA
right !

[] [ CLEAR ] Back to boom functions selection menu

BOOM SLEW RIGHT [ ENTER ] Activate parameter adjustment for MIN current of
I min 340 mA
boom slew right function

[ ] [ ] [ CLEAR ] Back to boom functions selection menu

BOOM SLEW RIGHT [ ENTER ] Activate parameter adjustment for MAX current of
I max 850 mA
boom slew right function

[ ] [ ] [ CLEAR ] Back to boom functions selection menu

BOOM SLEW LEFT Display of actual value for proportional current boom slew left
I act 470 mA

[ ] [ ] [ CLEAR ] Back to boom functions selection menu

BOOM SLEW LEFT [ ENTER ] Activate parameter adjustment for MIN current of
I min 340 mA
boom slew left function

[ ] [ ] [ CLEAR ] Back to boom functions selection menu

BOOM SLEW LEFT [ ENTER ] Activate parameter adjustment for MAX current of
I max 850 mA
boom slew left function

[ ] [ CLEAR ] Back to boom functions selection menu

etc. for all boom sections

Service Manual 479


HOME PRINT
SERVICE TRAINING
Electrical
Proportional characteristics adjustment for the BOOM 1 function with PULSAR valve
types :

BOOM 1 EXTEND Display of actual value for the actual PWM boom 1 extend
PWM act 43 %
value

[] [ CLEAR ] Back to boom functions selection menu

BOOM 1 EXTEND [ ENTER ] Activate parameter adjustment for MIN value of


PWM min 31 %
boom 1 extend function

[ ] [ ] [ CLEAR ] Back to boom functions selection menu

BOOM 1 EXTEND [ ENTER ] Activate parameter adjustment for MAX value of


PWM max 87 %
boom 1 extend function

[ ] [ ] [ CLEAR ] Back to boom functions selection menu

BOOM 1 RETRACT Display of actual value for the actual PWM boom 1 retract
PWM act 49 %
value

[ ] [ ] [ CLEAR ] Back to boom functions selection menu

BOOM 1 RETRACT [ ENTER ] Activate parameter adjustment for MIN value of


PWM min 23 %
boom 1 retract function

[ ] [ ] [ CLEAR ] Back to boom functions selection menu

BOOM 1 RETRACT [ ENTER ] Activate parameter adjustment for MAX value of


PWM max 67 %
boom 1 retract function

[ ] [ CLEAR ] Back to boom functions selection menmu

etc. for all boom sections

480 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
3.0 I/O status display - signals & references

The status display of all inputs & outputs shows the real state of the respective input or output!
( = high = +24 V / = Low = 0 V )
The arrow keys [ ] [ ] are used to move between the status displays !
[ CLEAR ] returns to the module selection of the I/O displays !

3.1 Machine control

INP MACHINE-C1
12345678

LED Signal Module / Assembly Connector / Pin


1 ??? Gearbox in neutral position Machine control 1 (-A231) -X231 / 05
2 Battery charge monitor (signal at D+) Machine control 1 (-A231) -X231 / 17
3 Pushbutton "Hydraulic on outriggers" Machine control 1 (-A231) -X231 / 19
4 Signal "High truck coolant temperature" Machine control 1 (-A231) -X231 / 28
5 Signal "Engine safety stop" Machine control 1 (-A231) -X231 / 10
6 Signal "Low truck oil pressure" Machine control 1 (-A231) -X231 / 23
7 Reserve Machine control 1 (-A231) -X231 / 21
8 Prox-switch PTO RPM Machine control 1 (-A231) -X231 / 13

OUTP MACHINE-C1
12345678

LED Signal Module / Assembly Connector / Pin


1 Engine Start Machine control 1 (-A231) -X231 / 04
2 Engine Stop Machine control 1 (-A231) -X231 / 16
3 Engine RPM speed up Machine control 1 (-A231) -X231 / 06
4 Engine RPM speed down Machine control 1 (-A231) -X231 / 15
5 Solenoid "Agitator forwards" Machine control 1 (-A231) -X231 / 08
6 Solenoid "Agitator backwards" Machine control 1 (-A231) -X231 / 18
7 Solenoid "Hydraulic on outriggers" Machine control 1 (-A231) -X231 / 27
8 Relay oil cooler on Machine control 1 (-A231) -X231 / 07

Service Manual 481


HOME PRINT
SERVICE TRAINING
Electrical

INP MACHINE-C2
12345678

LED Signal Module / Assembly Connector / Pin


1 Level switch water reservoir Machine control 2 (-A251) -X251 / 05
2 Signal "PTO engaged" Machine control 2 (-A251) -X251 / 17
3 Oil filter monitor concrete pump Machine control 2 (-A251) -X251 / 19
4 Oil filter monitor boom hydraulics Machine control 2 (-A251) -X251 / 28
5 Level switch hydraulic reservoir Machine control 2 (-A251) -X251 / 10
6 Over-temperature switch compressor Machine control 2 (-A251) -X251 / 23
7 Engine Start ch. pump rams Machine control 2 (-A251) -X251 / 21
8 Engine Stop ch. pump rams Machine control 2 (-A251) -X251 / 13

OUTP MACHINE-C2
12345678

LED Signal Module / Assembly Connector / Pin


1 Relay "Agitator on" Machine control 2 (-A251) -X251 / 04
2 Solenoid "Water pump on" Machine control 2 (-A251) -X251 / 16
3 Relay "Boom horn" Machine control 2 (-A251) -X251 / 06
4 Relay "Slewing-gear horn" Machine control 2 (-A251) -X251 / 15
5 Solenoid "Compressor on" Machine control 2 (-A251) -X251 / 08
6 Solenoid "High-pressure water pump" Machine control 2 (-A251) -X251 / 18
7 Solenoid "End-hose unlock" Machine control 2 (-A251) -X251 / 27
8 Alarm output (optional !) Machine control 2 (-A251) -X251 / 07

482 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
3.2 Concrete pump control

INP CP-CONTROL
12345678

LED Signal Module / Assembly _____ Connector / Pin


1 Local switch concrete pump on Concrete-pump control (-A201) -X201 / 05
2 Local switch concrete pump forwards Concrete-pump control(-A201) -X201 / 17
3 Local switch concrete pump reverse Concrete-pump control(-A201) -X201 / 19
4 ??? Hopper-grate limit switch Concrete-pump control (-A201) -X201 / 28
5 Soft-start limit switch on Concrete-pump control (-A201) -X201 / 10
6 Soft-start limit switch off Concrete-pump control (-A201) -X201 / 23
7 CP stroke count limit switch Concrete-pump control (-A201) -X201 / 21
8 Reserve Concrete-pump control (-A201) -X201 / 13

OUTP CP-CONTROL
12

LED Signal Module / Assembly Connector / Pin


1 Switch valve CP forwards ON Concrete-pump control (-A201) -X201 / 04
2 Switch valve CP reverse ON Concrete-pump control (-A201) -X201 / 16

STROKE LIMITER Tendency display prop current stroke limiter



adjustment for concrete pump!
[]

PRESS LIMITER CP Tendency display prop current pressure



limiting valve! (at present not relevant)
[]

HYD PRESSURE CP Tendency display for pressure pick-up signal



concrete pump hydraulics!
[]

HYD OIL TEMP Tendency display temperature sensor signal



hydraulic reservoir!
Signal Module / Assembly Connector / Pin
Output pressure-regulating valve stroke lim. CP Concrete pump control (-A201) -X201 / 11
Output pressure-regulating valve soft-start Concrete pump control (-A201) -X201 / 02
Analog input oil pressure concrete pump Concrete pump control (-A201) -X201 / 25
Analog input oil temperature hydraulics Concrete pump control (-A201) -X201 / 14

Service Manual 483


HOME PRINT
SERVICE TRAINING
Electrical
3.3 Boom control

INP BOOM-C1
123456

LED Signal Module / Assembly Connector/Pin


1 Cam switch boom-slew right 1 Boom control 1 (-A161) -X161 / 07
2 Cam switch boom-slew right 2 Boom control 1 (-A161) -X161 / 17
3 Cam switch boom-slew left 1 Boom control 1 (-A161) -X161 / 26
4 Cam switch boom-slew left 2 Boom control 1 (-A161) -X161 / 08
5 Boom-slew cab protection switch 1 Boom control 1 (-A161) -X161 / 25
6 Boom-slew cab protection switch 2 Boom control 1 (-A161) -X161 / 27

INP BOOM-C2
123456

LED Signal Module / Assembly Connector/Pin


1 Cab protection switch boom 1 < 50 grd 1 Boom control 2 (-A181) -X181 / 07
2 Cab protection switch boom 1 < 50 grd 2 Boom control 2 (-A181) -X181 / 17
3 Cab protection switch boom 2 < 20 grd 1 Boom control 2 (-A181) -X181 / 26
4 Cab protection switch boom 2 < 20 grd 2 Boom control 2 (-A181) -X181 / 08
5 Cab protection switch boom 1 > 180 grd 1 Boom control 2 (-A181) -X181 / 25
6 Cab protection switch boom 1 > 180 grd 2 Boom control 2 (-A181) -X181 / 27

BOOM-SLEW RIGHT Tendency display prop output value boom- slewing!



[]

BOOM-SLEW LEFT

[]

BOOM 1 EXTEND Tendency display prop output value



boom 1
[]

BOOM 1 RETRACT
[]

BOOM 2 EXTEND Tendency display prop output value


boom 2!
[]

484 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

BOOM 2 RETRACT

[]

BOOM 3 EXTEND Tendency display prop output value


boom 3!
[]

BOOM 3 RETRACT

[]

BOOM 4 EXTEND Tendency display prop output value


boom 4!
[]

BOOM 4 RETRACT

[]

BOOM 5 EXTEND Tendency display prop output value


boom 5
[]

BOOM 5 RETRACT

Signal Module / Assembly Connector / Pin
Output "boom-slew right" solenoid Boom control (-A161) -X161 / 21
Output "boom-slew left" solenoid Boom control 1 (-A161) -X161 / 12
Output "boom 1 extend" solenoid Boom control 1 (-A161) -X161 / 03
Output "boom 1 retract" solenoid Boom control 1 (-A161) -X161 / 13
Output "boom 2 extend" solenoid Boom control 1 (-A161) -X161 / 04
Output "boom 2 retract" solenoid Boom control 1 (-A161) -X161 / 09
Output "boom 3 extend" solenoid Boom control 2 (-A181) -X181 / 21
Output "boom 3 retract" solenoid Boom control 2 (-A181) -X181 / 12
Output "boom 4 extend" solenoid Boom control 2 (-A181) -X181 / 03
Output "boom 4 retract" solenoid Boom control 2 (-A181) -X181 / 13
Output "boom 5 extend" solenoid Boom control 2 (-A181) -X181 / 04
Output "boom 5 retract" solenoid Boom control 2 (-A181) -X181 / 09

Service Manual 485


HOME PRINT
SERVICE TRAINING
Electrical
3.4 Rear panel

INP REAR PANEL 1


12345678

LED Signal Module / Assembly Connector / Pin


1 Switch signal "Rear panel" Panel at step-ladder (-A1) -1X / 01
2 Pushbutton signal "Engine start" Panel at step-ladder (-A1) -1X / 02
3 Pushbutton signal "Engine stop" Panel at step-ladder (-A1) -1X / 03
4 Pushbutton signal "r.p.m.speed up" Panel at step-ladder (-A1) -1X / 04
5 Pushbutton signal "r.p.m. speed down" Panel at step-ladder (-A1) -1X / 05
6 Switch signal "CP forwards" Panel at step-ladder (-A1) -1X / 06
7 Switch signal "CP backwards" Panel at step-ladder (-A1) -1X / 07
8 Switch signal "Agitator forwards" Panel at step-ladder (-A1) -1X / 08

INP REAR PANEL 2


12345678

LED Signal Module / Assembly Connector / Pin


1 Switch signal "Agitator backwards" Panel at step-ladder (-A1) -1X / 09
2 Switch signal "Agitator manual ON" Panel at step-ladder (-A1) -1X / 10
3 Switch signal "Agitator automatic ON" Panel at step-ladder (-A1) -1X / 11
4 Pushbutton signal"Boom-horn ON" Panel at step-ladder (-A1) -1X / 12
5 Switch signal "Water pump ON" Panel at step-ladder (-A1) -1X / 13
6 Switch signal "Compressor ON" Panel at step-ladder (-A1) -1X / 14
7 Switch signal "High-pressure WP ON" Panel at step-ladder (-A1) -1X / 15
8 Pushbutton signal "End-hose unlock" Panel at step-ladder (-A1) -1X / 16

INP REAR PANEL 3


1234

LED Signal Module / Assembly Connector / Pin


1 Agitator reverse Panel at step-ladder (-A1) -1X / 17
2-4 Reserve Panel at step-ladder (-A1) -1X / 18 - 20

OUTP REAR PANEL


1234

LED Signal Module / Assembly Connector / Pin


1 Cab protection warning lamp Panel at step-ladder (-A1) -1X / 21
2-4 Reserve Panel at step-ladder (-A1) -1X / 22 - 24

486 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

POT REAR PAN SL Tendency display potentiometer input signal



stroke limiter concrete pump !

Signal Module / Assembly Connector / Pin


Potentiometer input "Stroke limiter CP" Panel at step-ladder (-A1) -1X / 25

3.5 Extension module

INP EXTENSION
12345678

LED Signal Module / Assembly Connector / Pin


1 Cycle switch lubric. circuit 1 (boom) Machine control 3 (-A271) -X271 / 05
2 Cycle switch lubric. circuit 2 (CP) Machine control 3 (-A271) -X271 / 17
3 Cycle switch lubric. circuit 3 (outriggers) Machine control 3 (-A271) -X271 / 19
4 Input "Central lubrication inhibit" Machine control 3 (-A271) -X271 / 28
5 Free digital input 1 Machine control 3 (-A271) -X271 / 10
6 Free digital input 2 Machine control 3 (-A271) -X271 / 23
7 Free digital input 3 Machine control 3 (-A271) -X271 / 21
8 Free digital input 4 Machine control 3 (-A271) -X271 / 13

OUTP EXTENSION
12345678

LED Signal Module / Assembly Connector / Pin


1 Lubricating pump on Machine control 3 (-A271) -X271 / 04
2 Lubric. distrib. valve circuit 1 (boom) Machine control 3 (-A271) -X271 / 16
3 Lubric. distrib. valve circuit 2 (CP) Machine control 3 (-A271) -X271 / 06
4 Lubric. distrib. valve circuit 3 (outriggers) Machine control 3 (-A271) -X271 / 15
5 Free digital output 1 Machine control 3 (-A271) -X271 / 08
6 Free digital output 2 Machine control 3 (-A271) -X271 / 18
7 Free digital output 3 Machine control 3 (-A271) -X271 / 27
8 Free digital output 4 Machine control 3 (-A271) -X271 / 07

Service Manual 487


HOME PRINT
SERVICE TRAINING
Electrical
4.0 Fault messages and fault causes
4.1Introduction

Each fault message has its own fault code permitting to obtain further information about a special fault from this
list.
This fault code consists of the machine section identification, a number and the fault category !

A fault message is shown on the rear panel display as follows :

MALFUNCTION !!! "MALFUNCTION" flashing


(CODE) FAULT MESSAGE
Fault code and continuous malfunction message text !

The following letters identify the machine section:


S = System B = Concrete pump
F = Remote control M = Boom control
A = General machine Z = Central lubrication
D = Truck engine or PTO E = Extensions

Three fault categories can be displayed:


L = minor fault, horn cancelling from control box possible.
(rectification of fault cause required only upon completion of job !)
S = severe fault, horn cancelling from control box not possible.
(immediate rectification of fault cause required !)
M = operating fault, only message displayed, cancelling not required.
(no storage of fault in diagnosis system !)

Example : B01S B = machine section "concrete pump"


01 = number 01
S = fault category "severe"

Meaning of the "Disconnected" or "Overload" fault messages

The "Disconnected" fault is reported when the cable from this output to the relay / solenoid is broken.
This fault can only be detected when the output is not activated !
The cause of this fault is either a broken cable or a disconnected solenoid connector !

The "Overload" fault is reported when an inadmissibly high current has been detected for this output.
This fault can only be detected when the output is activated!
The cause of this fault is either a short-circuit in the electric cable to the relay / solenoid or a defect of the solenoid
coil (charred) !
This applies to all following faults reported as "Disconnected" or "Overload" faults !!!

488 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
4.2 Control diagnosis electronic modules(fault code S !)

Code Message / source of fault message / fault detection time


S01L Boom-Control Board 1 Fault (system fault !)
Module monitoring by central board !

S02L Boom-Control Board 2 Fault (system fault !)


Module monitoring by central board !

S03L Machine-Control Board 1 Fault (system fault !)


Module monitoring by central board !

S04L Machine-Control Board 2 Fault (system fault !)


Module monitoring by central board !

S05L Machine-Control Board 3 Fault (system fault !)


Module monitoring by central board !

S06L Concrete-Pump Control Board Fault (system fault !)


Module monitoring by central board !

S07L Rear Panel Board Fault (system fault !)


Module monitoring by central board !

S08L Info-Center Board Fault (system fault !)


Module monitoring by central board !

S09L Network-Fault / Central-Board Fault (system fault !)


When network monitor on central board detects
a malfunction of the CAN network !

S10L Network-Fault Central Board - Info-Center (system fault !)


Detected by Info-Center if CAN communication with
Central Board cannot be established !

System faults are reported when the module in question does not work perfectly. All modules are regularly checked
by the central module !
In the event of a system fault, the electric control of the truck-mounted concrete pump should be switched off once
for ca. 5 secs. with the key-operated switch in the driver's cab.

This fault message may have the following causes:


- power supply to one of the modules interrupted (check fuse !)
- electronic components on module Fault, e.g. storage defect(replace module !)
- communication fault with central module(replace module!)

Service Manual 489


HOME PRINT
SERVICE TRAINING
Electrical
4.3 Remote-control system diagnosis (fault code F!)

Code Message / source of fault message / fault detection time

F01M Emergency-Stop on Radio Control Box active


Source: REMOTE-CONTROL DIAGNOSIS
Indicated when emergency shut-off button on radio control box has been actuated !

F02M Actuator Switches on Control Box out of Neutral Position


Source: REMOTE-CONTROL DIAGNOSIS
Indicated when control box actuators after activation of radio control box have not been once in neutral
position !

F03M No Radio Control Transmission


Source: REMOTE-CONTROL DIAGNOSIS
Indicated when radio control box is off or when - for other reasons - there is no radio contact between
transmitter and revceiver.

F05L Joy-Stick 1 from Remote-Control Fault


Source: REMOTE-CONTROL DIAGNOSIS
Indicated when control box has detected a fault at joy-stick 1 !

F06L Joy-Stick 2 from Remote-Control Fault


Source: REMOTE-CONTROL DIAGNOSIS
Indicated when control box has detected a fault at joy-stick 2 !

F07L Joy-Stick 3 from Remote-Control Fault


Source: REMOTE-CONTROL DIAGNOSIS
Indicated when control box has detected a fault at joy-stick 3 !

F08M CAN-Transmission with Remote-Control Fault


Source: REMOTE-CONTROL DIAGNOSIS
Indicated after 30 seconds when CAN data transmission between control unit and remote-control sys-
tem is interrupted

F09L Emergency-Stop Switch on Radio Control Box Fault


Source: REMOTE-CONTROL DIAGNOSIS
Indicated when control box has detected a fault at emergency-stop button !

F10M Radio Control Signal with Faulty Address received


Source: REMOTE-CONTROL DIAGNOSIS
Indicated when radio receiver has received a radio data telegram from another radio control box or from
a wrongly adjusted radio control box.

490 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
4.4 Machine diagnosis-General (fault code A!)

Code Message / source of fault message / fault detection time


A01M Emergency-Stop on Machine active
Source: DIAGNOSIS SYSTEMfault detection time :20 sec.!
Indicated when central board detects that all electronic modules except the central module, operating
panel at step-ladder and Info-Center have been shut off !

A02S Hydraulic Oil Temperature exceeded


Source: HYD OIL TEMP / CPfault detection time:5 sec.!
Indicated when oil temperature sensor detects that the maximum oil temperature hzas been exceeded
(set value CP module) !

A03L Temperatur Transmitter Hydraulic Oil Fault


Source: HYD OIL TEMP / CP inputfault detection time:30 sec.!
Indicated when monitor detects sensor oil temperature outside the valid range ( 500 - 2000 ohms ) !

A04L Exchange Hydraulic Oil Filter Boom


Source: Input 4 / INP MACHINE-C2fault detection time :10 Sek.!
Indicated when pressure filter monitor (differential pressure switch in oil filter) detects excessive pres-
sure drop in hydraulic oil filter at an oil temperature above 30 C !

A05L Exchange Hydraulic Oil Filter Concrete Pump


Source: Input 3 / INP MACHINE-C2fault detection time :10 Sek.!
Indicated when pressure filter monitor (differential pressure switch in oil filter) detects excessive pres-
sure drop in hydraulic oil filter at an oil temperature above 30 C !

A06L Low Level Hydraulic Oil


Source: Input 5 / INP MACHINE-C2fault detection time :3 Sek.!
Indicated when level switch in hydraulic oil reservoir (option !) detects insufficient oil level !

A07M Low Level Water Reservoir


Source: Input 1 / INP MACHINE-C2fault detection time :3 Sek.!
Indicated when level switch in water tank (option !) detects insufficient level in tank for cleaning water
(dry-run protection) !

A08L High Temperature Air-Compressor


Source: Input 6 / INP MACHINE-C2fault detection time :3 Sek.!
Indicated when over-temperature protection in compressor (bi-metal switch) responds !

Service Manual 491


HOME PRINT
SERVICE TRAINING
Electrical
Code Message / source of fault message / fault detection time

A09M Operating Mode for Changing Pump Rams active


Source: Input 1 / INP CONCRETE PUMPoperating mode display !
Indicated when "ram change" mode has been selected at separate controls for "CP inching" !

A10M Actuator Switches on Rear Panel out of Neutral Position


Source: DIAGNOSIS SYSTEM
Indicated when actuators on rear panel have not been at least once in neutral position after an EMER-
GENCY SHUT-OFF or after switching over from REMOTE to LOCAL (rear panel!) control.

A30L Disconnected Oil-Cooler Relay


A31L Overload Oil-Cooler Relay
A32L Disconnected Vibrator Relay
A33L Overload Vibrator Relay
A34L Disconnected Boom-Horn Relay
A35L Overload Boom Horn Relay
A36L Disconnected Slew-Horn Relay
A37L Overload Slew-Horn Relay
A38L Disconnected Alarm Output
A39L Overload Alarm Output

A40L Disconnected Waterpump Solenoid


A41L Overload Waterpump Solenoid
A42L Disconnected Compressor Solenoid
A43L Overload Compressor Solenoid
A44L Disconnected Agitator Forwards Solenoid
A45L Overload Agitator Forwards Solenoid
A46L Disconnected Agitator Reverse Solenoid
A47L Overload Agitator Reverse Solenoid
A48L Disconnected Hydraulic-on-Outriggers Solenoid
A49L Overload Hydraulic-on-Outriggers Solenoid

A50L Disconnected High-Pressure Waterpump Solenoid


A51L Overload High-Pressure Waterpump Solenoid
A52L Disconnected End-Hose unlocking Solenoid
A53L Overload End-Hose unlocking Solenoid

For "Disconnected" and "Overload" faults cf. "Introduction" (4.1) !

492 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
4.5 Engine/PTO Diagnosis (fault code D!)

Code Message / source of fault message / fault detection time

D01S Engine Safety Stop / High Coolant Temperature


Source: Input 4 / INP MACHINE-C1fault detection time:5 sec.!
Indicated when engine saftety stop (option !) has occurred because of excessive temperature of vehicle
engine (cooling-water temperature switch) !

D02S Engine Safety Stop


Source: Input 5 / INP MACHINE-C1fault detection time:5 sec.!
Indicated when engine safety stop has occurred from customer-specific option (e.g. hydraulic oil level-
falling)

D03S Engine Safety Stop / Low Truck Oil Pressure


Source: Input 6 / INP MACHINE-C1fault detection time:5 sec.!
Indicated when engine safety stop (option !) has occurred from insufficient vehicle engine oil pressure
(oil pressure switch) !

D04L PTO is not working or Prox-Switch PTO-RPM Fault


Source: DIAGNOSIS SYSTEMfault detection time:120 sec.!
Indicated when - in spite of engine running (D+ signal) and PTO engaged (PTO limit switch) - no pulses
are transmitted from RPM sensor at pump transfer gearbox (inductive proximity switch) for more than 30
seconds.

D05L PTO RPM Exceeded


Source: DIAGNOSIS SYSTEMfault detection time:5 sec.!
Indicated when PTO RPM exceeds the set maximum limit (set value machine control 1 module) !

D06S Battery Charging on Truck Fault


Source: DIAGNOSIS SYSTEMfault detection time:120 sec.!
Indicated when - in spite of PTO RPM detected (pulses from prox-switch and PTO engaged) - there is
no D+ signal (alternator running) !

D07L Indicator switch PTO=ON/OFF Fault


Source: DIAGNOSIS SYSTEMfault detection time:120 sec.!
Indicated when - in spite of engine running (D+ signal) and PTO RPM detected (pulses from prox-
switch) - there is no signal from "PTO engaged" indicator switch.

D30L Disconnected Engine Start Relay


D31L Overload Engine Start Relay
D32L Disconnected Engine Stop Relay
D33L Overload Engine Stop Relay
D34L Disconnected Engine Speed-Up Relay
D35L Overload Engine Speed-Up Relay
D36L Disconnected Engine Speed-Down Relay
D37L Overload Engine Speed-Down Relay

For "Disconnected" and "Overload" faults cf. "Introduction" (4.1) !

Service Manual 493


HOME PRINT
SERVICE TRAINING
Electrical
4.6 Concrete pump diagnosis (fault code B!)

Code Message / source of fault message / fault 0detection time

B01L Power Limiter Concrete Pump active


Source: Input HYD OIL TEMPfault detection time:5 sec.!
Indicated when the temperature of the hydraulic oil in the reservoir has exceeded the set limit (set value
CP module) and after the concrete pump power limiter has been activated !

B02L Pressure Limiter Concrete Pump active


Source: Input CP OIL PRESSUREfault detection time:15 sec.!
Indicated when the pressure of the concrete pump hydraulic oil has exceeded the set limit (set value CP
module) and after the electronic pressure limiter has been activated !

B03L Pressure Transmitter CP Hydraulics Fault


Source: Input CP OIL PRESSUREfault detection time:30 sec.!
Indicated when monitor detects that measured value of hydraulic oil pressure transmitter is out of valid
range ( 4 - 20 mA ) !

B04L Prox-Switch Soft-Start / Pumped Volume Fault


Quelle : DIAGNOSIS SYSTEMfault detection time:120 sec.!
Indicated when - within 120 seconds of concrete pump operation (engine running, PTO engaged and
CP forwards or backwards ON) no pulses from the soft-start / pump volume proximity switches are
being detected !

B05L Hopper Grate open / CP jammed / Prox-Switch Stroke Counter Fault


Source: DIAGNOSIS SYSTEMfault detection time:120 sec.!
Indicated when - within 120 seconds of concrete pump operation (engine running, PTO engaged and
CP forwards or backwards ON) no pulses from the stroke counter proximity switch on the concrete
pump are being detected!
ATTENTION, hopper grate must be closed and CP must not be jammed !

B30L Disconnected CP Forwards Solenoid


B31L Overload CP Forwards Solenoid
B32L Disconnected CP Reverse Solenoid
B33L Overload CP Reverse Solenoid
B34L Disconnected CP Stroke Limiter Solenoid
B35L Overload CP Stroke Limiter Solenoid
B36L Disconnected CP Pressure Limiter CP Solenoid
B37L Overload CP Pressure Limiter CP Solenoid

For "Disconnected" and "Overload" faults cf. "Introduction" (4.1) !

494 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
4.7 Boom control diagnosis (fault code M!)

Code Message / source of fault message / fault detection time

M01L Limit Switch Boom Slewing Right 1 Fault


Source: Input 1 / INP BOOM-C1statistical function: (5 x 5 sec.!)
Indicated when limit switch monitor detects that the redundant limit switches "boom-slew right" 1 & 2 are
in different signal states.

M02L Limit Switch Boom Slewing Right 2 Fault


Source: Input 2 / INP BOOM-C1statistical function: (5 x 5 sec.!)
Indicated when limit switch monitor detects that the redundant limit switches "boom-slew right" 1 & 2 are
in different signal states.

M03L Limit Switch Boom Slewing Left 1 Fault


Source: Input 3 / INP BOOM-C1statistical function: (5 x 5 sec.!)
Indicated when limit switch monitor detects that the redundant limit switches "boom-slew left" 1 & 2 are
in different signal states.

M04L Limit Switch Boom Slewing Left 2 Fault


Source: Input 4 / INP BOOM-C1statistical function : (5 x 5 sec.!)
Indicated when limit switch monitor detects that the redundant limit switches "boom-slew left" 1 & 2 are
in different signal states.

M05L Truck Cab Protection Switch 1 Boom 2 < 20 Degree Fault (cab protection)
Source: Input 3 / INP BOOM-C2statistical function: (5 x 5 sec.!)
Indicated when limit switch monitor detects that the redundant limit switches "boom 2 < 20 degrees" 1 &
2 are in different signal states.

M06L Truck Cab Protection Switch 2 Boom 2 < 20 Degree Fault (cab protection)
Source: Input 4 / INP BOOM-C2statistical function: (5 x 5 sec.!)
Indicated when limit switch monitor detects that the redundant limit switches "boom 2 < 20 degrees" 1 &
2 are in different signal states.

M07L Truck Cab Protection Switch 1 Boom 1 < 50 Degree Fault (cab protection)
Source: Input 1 / INP BOOM-C2statistical function: (5 x 5 sec.!)
Indicated when limit switch monitor detects that the redundant limit switches "boom 1 < 50 degrees" 1 &
2 are in different signal states.

M08L Truck Cab protection Switch 2 Boom 1 < 50 Degree Fault (cab protection)
Source: Input 2 / INP BOOM-C2statistical function: (5 x 5 sec.!)
Indicated when limit switch monitor detects that the redundant limit switches "boom 1 < 50 degrees" 1 &
2 are in different signal states.

Service Manual 495


HOME PRINT
SERVICE TRAINING
Electrical
Code Message / source of fault message / fault detection time

M09L Truck Cab Protection Switch 1 Boom 1 > 180 Degree Fault (cab protection)
Source: Input 5 / INP BOOM-C2statistical function : (5 x 5 sec.!)
Indicated when limit switch monitor detects that the redundant limit switches "boom 1 > 180 degrees" 1
& 2 are in different signal states.

M10L Truck Cab Protection Switch 2 Boom 1 > 180 Degree Fault (cab protection)
Source: Input 6 / INP BOOM-C2statistical function: (5 x 5 sec.!)
Indicated when limit switch monitor detects that the redundant limit switches "boom 1 > 180 degrees" 1
& 2 are in different signal states.

M11L Truck Cab Protection Switch 1 Boom Slewing Fault (cab protection)
Source: Input 5 / INP BOOM-C1statistical function: (5 x 5 sec.!)
Indicated when limit switch monitor detects that the redundant limit switches "cab protection boom slew-
ing" 1 & 2 are in different signal states.

M12L Truck Cab Protection Switch 2 Boom Slewing Fault (cab protection)
Source: Input 6 / INP BOOM-C1statistical function: (5 x 5 sec.!)
Indicated when limit switch monitor detects that the redundant limit switches "cab protection boom slew-
ing" 1 & 2 are in different signal states.

Code Message / source of fault message / fault detection time

M30L Disconnected Boom Slewing Right Solenoid


M31L Overload Boom Slewing Right Solenoid
M32L Disconnected Boom Slewing Left Solenoid
M33L Overload Boom Slewing Left Solenoid
M34L Disconnected Boom 1 Extend Solenoid
M35L Overload Boom 1 Extend Solenoid
M36L Disconnected Boom 1 Retract Solenoid
M37L Overload Boom 1 Retract Solenoid
M38L Disconnected Boom 2 Extend Solenoid
M39L Overload Boom 2 Extend Solenoid
M40L Disconnected Boom 2 Retract Solenoid
M41L Overload Boom 2 Retract Solenoid
M42L Disconnected Boom 3 Extend Solenoid
M43L Overload Boom 3 Extend Solenoid
M44L Disconnected Boom 3 Retract Solenoid
M45L Overload Boom 3 Retract Solenoid
M46L Disconnected Boom 4 Extend Solenoid
M47L Overload Boom 4 Extend Solenoid
M48L Disconnected Boom 4 Retract Solenoid
M49L Overload Boom 4 Retract Solenoid
M50L Disconnected Boom 5 Extend Solenoid
M51L Overload Boom 5 Extend Solenoid
M52L Disconnected Boom 5 Retract Solenoid
M53L Overload Boom 5 Retract Solenoid

For "Disconnected" and "Overload" faults cf. "Introduction" (4.1) !

496 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
4.8 Central lubrication/extension diagnosis (fault code Z/E!)

Code Message / source of fault message / fault detection time

Z01L Malfunction Lubrication Boom / Slewing Gear


Source: Input 1 / INP EXTENSIONfault detection time : Parameter !
Indicated when - after activation of the "boom / slewing gear" greasing circuit - there are no pulses com-
ing from the corresponding cycle switch in the progressive distributor after a certain time.

Z02L Malfunction Lubrication CP / Agitator


Source: Input 2 / INP EXTENSIONfault detection time : Parameter !
Indicated when - after activation of the "CP / agitator" greasing circuit - there are no pulses coming from
the corresponding cycle switch in the progressive distributor after a certain time.

Z03L Malfunction Lubrication Outriggers


Source: Input 3 / INP EXTENSIONfault detection time : Parameter !
Indicated when - after activation of the "outrigger" greasing circuit - there are no pulses coming from the
corresponding cycle switch in the progressive distributor after a certain time.

Z04L Lubrication Switched OFF


Source: Input 4 / INP EXTENSIONfault detection time :5 sec.!
Indicated when central lubrication has been switched off with the service switch.

Z30L Disconnected Lubrication Pump Relay


Z31L Overload Lubrication Pump Relay
Z32L Disconnected Lubrication Boom Solenoid
Z33L Overload Lubrication Boom Solenoid
Z34L Disconnected Lubrication CP / Agitator Solenoid
Z35L Overload Lubrication CP / Agitator Solenoid
Z36L Disconnected Lubrication Outriggers Solenoid
Z37L Overload Lubrication Outriggers Solenoid

E30L Disconnected PLC-Outp 1


E31L Overload PLC-Outp 1
E32L Disconnected PLC-Outp 2
E33L Overload PLC-Outp 2
E34L Disconnected PLC-Outp 3
E35L Overload PLC-Outp 3
E36L Disconnected PLC-Outp 4
E37L Overload PLC-Outp 4

For "Disconnected" and "Overload" faults cf. "Introduction" (4.1) !

Service Manual 497


HOME PRINT
SERVICE TRAINING
Electrical
5.0 Output signal interdependence list
The present list supplies information about the input signals and control states governing the most important output
signals !

Boom control
Boom-slewing right / left (prop. or switched output !)depends on :
- Emergency-stop not actuated !
- Restart protection after emergency-stop or change of Local / Remote mode of operation !
- Slewing gear limit switch 1 or 2 on slewing ring not actuated !
- Boom limiting (cab protection at KVM 52 & S 45 SX) not active !
- REMOTE mode selected and RAM CHANGE mode not activated !
- Slewing function on remote-control box activated, [HARE/SNAIL] switch not in "0" position !

Boom 1/2 retract/extend (prop. or switched output !)depends on:


- Emergency-stop not actuated !
- Restart protection after emergency-stop or change of Local / Remote mode of operation !
- Boom limiting (cab protection at KVM 52 & S 45 SX) not active !
- REMOTE mode selected and RAM CHANGE mode not activated !
- Boom function 1/2 on remote-control box activated, [HARE/SNAIL] switch not in "0" position !

Boom 3/4/5 retract/extend (prop. or switched output !)depends on:


- Emergency-stop not actuated !
- Restart protection after emergency-stop or change of Local / Remote mode of operation !
- REMOTE mode selected and RAM CHANGE mode not activated !
- Boom function 3/4/5 on remote-control box activated, [HARE/SNAIL] switch not in "0" position !

Concrete pump control


Concrete pump forwards/backwards ON (switched output !) depends on:
- Emergency-stop not actuated !
- Limit switch at hopper grate not actuated and CP not blocked at control block !
- Restart protection after emergency-stop or change of LOCAL / REMOTE mode of operation !
- Correct mode of operation LOCAL / REMOTE selected and RAM CHANGE mode not activated !
- Concrete pump FORWARDS or BACKWARDS activated on remote-control box or at rear panel !

CP stroke limiting (prop. output !) depends on:


- Emergency-stop not actuated !
- Correct mode of operation LOCAL / REMOTE selected and RAM CHANGE mode not activated !
- Concrete pump FORWARDS or BACKWARDS activated !
- Stroke limiter adjustment on remote-control box or at rear panel !
- Limiting functions and soft-start / automatic pumping rate increase, if activated !

Agitator ON (switched output !) depends on:


- Emergency-stop not actuated !
- Restart protection after emergency-stop or change of LOCAL / REMOTE mode of operation !
- Limit switch at hopper grate not actuated !
- Correct mode of operation LOCAL / REMOTE selected !
- Agitator activated on remote-control box or at rear panel !
- Momentary contact functions "Agitator reversing" !
Vibrator ON (switched output !) depends on:
- Emergency-stop not actuated !
- Restart protection after emergency-stop or change of LOCAL / REMOTE mode of operation !

498 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
- Correct mode of operation LOCAL / REMOTE selected !
- Vibrator activated on remote-control box or at rear panel in MANUAL mode or vibrator
in AUTO mode and CP FORWARDS activated at the same time !

Cleaning systems
Water pump ON (switched output !) depends on:
- Emergency-stop not actuated !
- Restart protection after emergency-stop or change of LOCAL / REMOTE mode of operation !
- Correct mode of operation LOCAL / REMOTE selected !
- Water tank level switch indicates sufficient amounts of water in tank !
(dry running protection for water pump !)
- Water pump activated on remote-control box or at rear panel !

Compressor ON (switched output !) depends on:


- Emergency-stop not actuated !
- Restart protection after emergency-stop or change of LOCAL / REMOTE mode of operation!
- Correct mode of operation LOCAL / REMOTE selected !
- Compressor activated on remote-control box or at rear panel!

Truck engine control


Engine Start (switched output !) depends on:
- Emergency-stop not actuated !
- Restart protection after emergency-stop or change of LOCAL / REMOTE mode of operation !
- Correct mode of operation LOCAL / REMOTE selected and RAM CHANGE mode not activated !
- Gearbox in neutral position !
- Engine not yet running (D+ signal) !
- Safety delay of "Engine Stop" command (ca. 5 seconds) already elapsed !
- Engine Start activated on remote-control box or at rear panel !

Engine Stop (switched output !) depends on:


- Emergency-stop not actuated !
- Restart protection after emergency-stop or change of LOCAL / REMOTE mode of operation !
- Correct mode of operation LOCAL / REMOTE selected and RAM CHANGE mode not activated !
- Gearbox in neutral position !
- Engine Stop activated on remote-control box or at rear panel!

Engine RPM +/- adjust (switched output !) depends on:


- Emergency-stop not actuated !
- Restart protection after emergency-stop or change of LOCAL / REMOTE mode of operation!
- Correct mode of operation LOCAL / REMOTE selected and RAM CHANGE mode not activated!
- Engine RPM +/- adjust activated on remote-control box or at rear panel!

Service Manual 499


HOME PRINT
SERVICE TRAINING
Electrical
Info-Center Menu Overview Status: 03.02.97

INFO-SYSTEM [ ... ] = key !


Enter=On

[ENTER]

PUMPED VOLUME [ENTER] PUMPED ON JOB (S !) [START] Restart delivery-rate mea-


/ /Enter/Clear [CLEAR] ~ 1752.3 cbm surement!

[] [] ------------------------------------------------------------------------------------------------------------------------

OPERATION DATA [ENTER] HYD OIL TEMP Display temperature of oil in


//Enter/Clear [CLEAR] 62 C hydraulic reservoir !
[] []

PTO SHAFT RPM Display RPM of PTO shaft !


1270 rpm
[] []

HYD PRESSURE CP Display concrete pump


159 bars hydraulic oil pressure !
[] []

CONCR-PUMP HOURS Concrete pump operating


328.3 h hours !
[] []

BOOM HOURS Placing boom operating


406.1 h hours !
[] [] [] []

PTO HOURS PTO operating hours !


469.8 h
[] []

TOTAL STROKES CP Total number of concrete


1398743 strokes pump strokes !
[] []

TOTAL VOL. PUMPED Total pumped volume of


109125 cbm concrete pump !
[] []

STROKES PER MIN Actual number of strokes of


21 strokes/min concrete pump unit !

------------------------------------------------------------------------------------------------------------------------

500 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

MALFUNCTION LIST [ENTER] 16.03.95 / 12:34 Display of last stored fault


//Enter/Clear [CLEAR] (Code) fault text message !

[] []
14.02.95 / 10:17 Display of previous fault
(Code) fault text message !
[] [] [] [] etc !
------------------------------------------------------------------------------------------------------------------------

LUBRICATION-UNIT [ENTER] MANUAL LUBRIC. [START] Manual lubrication of con-


//Enter/Clear [CLEAR] CP & Agitator crete pump and agitator !
[] []

MANUAL LUBRIC. Manual lubrication of boom


Boom and slewing gear !
[] [] [] []

MANUAL LUBRIC. Manual lubrication of outrig-


Outriggers gers!

------------------------------------------------------------------------------------------------------------------------

I/O-STATUS DISPL [ENTER] MACHINE-CONTROL Display of I/O status of indi-


//Enter/Clear [CLEAR] / /Enter/Clear vidual control modules
[] []

CP-CONTROL Cf. page 3


//ENTER/CLEAR I/O display sub-menu
[] []

BOOM-CONTROL
//ENTER/CLEAR
[] [] [] []

REAR PANEL
//ENTER/CLEAR
[] []

EXTENSION I/O
//ENTER/CLEAR

------------------------------------------------------------------------------------------------------------------------

INTERNAL TIMER [ENTER] DATE 23.08.95 Display of date & time


//Enter/Clear [CLEAR] TIME 16:32

[] [] ------------------------------------------------------------------------------------------------------------------------

SCROLLING [ENTER] Scroll rate [ENTER] Setting of scroll rate


//Enter/Clear [CLEAR] 400 ms [ENTER] with & keys

[] [] ------------------------------------------------------------------------------------------------------------------------

Service Manual 501


HOME PRINT
SERVICE TRAINING
Electrical

PARAMETER [ENTER] PASSWORD **** Password entry for


//Enter/Clear [CLEAR] //Enter/Clear parameter adjustment
[] []

EFFICIENCY CP Cf. page 5


//Enter/Clear Parameter adjustment menu
[] []

LUBRIC. PARAM
//Enter/Clear
[] []

PROP-CUR SLEW
//Enter/Clear
[] []

PROP-CUR BOOM 1
//Enter/Clear
[] []

PROP-CUR BOOM 2
//Enter/Clear
[] []

PROP-CUR BOOM 3
//Enter/Clear
[] []

PROP-CUR BOOM 4
//Enter/Clear
[] []

PROP-CUR BOOM 5
//Enter/Clear

502 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical
Sub-menu I/O display overview Status : 03.02.97

MACHINE-CONTROL [ENTER] INP MACHINE-C1 Machine-control 1


/ /ENTER/CLEAR [CLEAR] 12345678 Digital-inputs
[] []

OUTP MACHINE-C1 Machine-control 1


12345678 Digital-outputs
[] [] [] []

INP MACHINE-C2 Machine-control 2


12345678 Digital-inputs
[] []

OUTP MACHINE-C2 Machine-control 2


12345678 Digital-outputs

------------------------------------------------------------------------------------------------------------------------

CP-CONTROL [ENTER] INP CP-CONTROL Concrete pump control


//ENTER/CLEAR [CLEAR] 12345678 Digital-inputs
[] []

OUTP CP-CONTROL Concrete pump control


12 Digital-outputs
[] []

STROKE LIMITER Concrete pump control


Prop-output stroke limiter
CP
[] [] [] []

PRESS LIMITER CP Concrete pump control


Prop-output pressure limit-
ing
[] []

HYD PRESSURE CP Concrete pump control


Analogue-input oil pressure
CP
[] []

HYD OIL TEMP Concrete pump control


Analogue-input hydraulic oil
temperature

------------------------------------------------------------------------------------------------------------------------

Service Manual 503


HOME PRINT
SERVICE TRAINING
Electrical

BOOM-CONTROL [ENTER] INP BOOM-C1 Boom-control 1


//ENTER/CLEAR [CLEAR] 123456 Digital-inputs

[] []

INP BOOM-C2 Boom-control 2


123456 Digital-inputs
[] []

BOOM-SLEW RIGHT Boom-control 1


Prop-output boom-slew right
[] []

BOOM-SLEW LEFT Boom-control 1


Prop-output boom-slew left
[] []

BOOM 1 EXTEND Boom-control 1


Prop-output boom 1 extend
[] []

BOOM 1 RETRACT Boom-control 1


Prop-output boom 1 retract
[] []

BOOM 2 EXTEND Boom-control 1


Prop-output boom 2 extend
[] [] [] []

BOOM 2 RETRACT Boom-control 1


Prop-output boom 2 retract
[] []

BOOM 3 EXTEND Boom-control 2


Prop-output boom 3 extend
[] []

BOOM 3 RETRACT Boom-control 2


Prop-output boom 3 retract
[] []

BOOM 4 EXTEND Boom-control 2


Prop-output boom 4 extend
[] []

BOOM 4 RETRACT Boom-control 2


Prop-output boom 4 retract
[] []

504 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

BOOM 5 EXTEND Boom-control 2


Prop-output boom 5 extend
[] []

BOOM 5 RETRACT Boom-control 2


Prop-output boom 5 retract

------------------------------------------------------------------------------------------------------------------------

REAR PANEL [ENTER] INP REAR PANEL 1 Rear panel


//ENTER/CLEAR [CLEAR] 12345678 Digital-inputs 1
[] []

INP REAR PANEL 2 Rear panel


12345678 Digital-inputs 2
[] []

INP REAR PANEL 3 Rear panel


1234 Digital-inputs 3
[] [] [] []

OUTP REAR PANEL Rear panel


1234 Digital-outputs
[] []

POT REAR PAN SL Rear panel


Analogue-input stroke limiter
CP

------------------------------------------------------------------------------------------------------------------------

EXTENSION I/O [ENTER] INP EXTENSION Machine-control 3


//ENTER/CLEAR [CLEAR] 12345678 Digital-inputs
[] []

OUTP EXTENSION Machine-control 3


12345678 Digital-outputs

Service Manual 505


HOME PRINT
SERVICE TRAINING
Electrical
Parameter adjustment menu overview Status : 03.02.97

Entry of PASSWORD and access to parameter adjustment menu

PARAMETER [ENTER] PASSWORD **** Enter password with


//ENTER/CLEAR [CLEAR] //ENTER/CLEAR [] [] keys
[] []

PASSWORD 1234 End password entry with


//ENTER/CLEAR [ENTER] key
[] [] [ENTER]

PASSWORD 1234 Correct password entry con-


Password OK firmed
[] []

EFFICIENCY CP Display of PARAMETER


//ENTER/CLEAR ADJUSTMENT MENU

Parameter adjustment menu for EFFICIENCY concrete pump / Central lubrication / Prop cur-
rent values

EFFICIENCY CP [ENTER] EFFICIENCY CP [ENTER] Parameter adjustment ON


//ENTER/CLEAR [CLEAR] 94 % [ENTER] [] [] change EFFICIENCY
CP

[] [] ------------------------------------------------------------------------------------------------------------------------

LUBRIC. PARAM [ENTER] LUBRIC. CYCLES [ENTER] Parameter adjustment ON


//ENTER/CLEAR [CLEAR] BOOM 07 [ENTER] [] [] change number of
cycles
[] []

LUBRIC. CYCLES [ENTER] Parameter adjustment ON


CP / AGITATOR 09 [ENTER] [] [] change number of
cycles
[] [] [] []

LUBRIC. CYCLES [ENTER] Parameter adjustment ON


OUTRIGGERS 12 [ENTER] [] [] change number of
cycles

------------------------------------------------------------------------------------------------------------------------

The parameter adjustment menu for prop current values of the current control (Rexroth valves) please turn over

506 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

PROP-CUR SLEW [ENTER] BOOM-SLEW RIGHT Online-display of effective


//ENTER/CLEAR [CLEAR] I act 530 mA prop-current
[] []

BOOM-SLEW RIGHT [ENTER] Parameter adjustment ON


I min 450 mA [ENTER] [] [] adjust MIN-current
[] []

BOOM-SLEW RIGHT [ENTER] Parameter adjustment ON


I max 820 mA [ENTER] [] [] adjust MAX-current
[] [] [] []

BOOM-SLEW LEFT Online-display of effective


I act 610 mA prop-current
[] []

BOOM-SLEW LEFT [ENTER] Parameter adjustment ON


I min 520 mA [ENTER] [] [] adjust MIN-current
[] []

BOOM-SLEW LEFT [ENTER] Parameter adjustment ON


I max 810 mA [ENTER] [] [] adjust MAX-current

------------------------------------------------------------------------------------------------------------------------

PROP-CUR BOOM 1 [ENTER] BOOM 1 EXTEND Online-display of effective


//ENTER/CLEAR [CLEAR] I act 530 mA prop-current
[] []

BOOM 1 EXTEND [ENTER] Parameter adjustment ON


I min 450 mA [ENTER] [] [] adjust MIN-current
[] []

BOOM 1 EXTEND [ENTER] Parameter adjustment ON


I max 820 mA [ENTER] [] [] adjust MAX-current
[] []

BOOM 1 RETRACT Online-display of effective


I act 610 mA prop-current
[] [] [] []

BOOM 1 RETRACT [ENTER] Parameter adjustment ON


I min 520 mA [ENTER] [] [] adjust MIN-current
[] []

BOOM 1 RETRACT [ENTER] Parameter adjustment ON


I max 810 mA [ENTER] [] [] adjust MAX-current

------------------------------------------------------------------------------------------------------------------------

Service Manual 507


HOME PRINT
SERVICE TRAINING
Electrical

PROP-CUR BOOM 2 [ENTER] Cf. boom section 1!


//ENTER/CLEAR [CLEAR]

[] [] ------------------------------------------------------------------------------------------------------------------------

PROP-CUR BOOM 3 [ENTER] Cf. boom section 1


//ENTER/CLEAR [CLEAR]

[] [] ------------------------------------------------------------------------------------------------------------------------

PROP-CUR BOOM 4 [ENTER] Cf. boom section 1


//ENTER/CLEAR [CLEAR]

[] [] ------------------------------------------------------------------------------------------------------------------------

PROP-CUR BOOM 5 [ENTER] Cf. boom section 1


//ENTER/CLEAR [CLEAR]

The parameter adjustment menu for prop-current values PWM-controlled (Apitech valves) please turnover
PROP-CUR SLEW [ENTER] SLEW RIGHT Online-display of effective
//ENTER/CLEAR [CLEAR] PWM act 33 % current value of valve
[] []

SLEW RIGHT [ENTER] Parameter adjustment ON


PWM min 10 % [ENTER] [] [] adjust MIN-value
[] []

SLEW RIGHT [ENTER] Parameter adjustment ON


PWM max 95 % [ENTER] [] [] adjust MAX-value
[] [] [] []

SLEW LEFT Online-display of effective


PWM act 48 % current value of valve
[] []

SLEW LEFT [ENTER] Parameter adjustment ON


PWM min 10 % [ENTER] [] [] adjust MIN-value
[] []

SLEW LEFT [ENTER] Parameter adjustment ON


PWM max 93 % [ENTER] [] [] adjust MAX-value

------------------------------------------------------------------------------------------------------------------------

508 Service Manual


HOME PRINT
SERVICE TRAINING
Electrical

PROP-CUR BOOM 1 [ENTER] BOOM 1 EXTEND Online-display of effective


//ENTER/CLEAR [CLEAR] PWM act 29 % current value of valve
[] []

BOOM 1 EXTEND [ENTER] Parameter adjustment ON


PWM min 14 % [ENTER] [] [] adjust MIN-value
[] []

BOOM 1 EXTEND [ENTER] Parameter adjustment ON


PWM max 92 % [ENTER] [] [] adjust MAX-value
[] []

BOOM 1 RETRACT Online-display of effective


PWM IST 63 % current value of valve
[] [] [] []

BOOM 1 RETRACT [ENTER] Parameter adjustment ON


PWM min 15 % [ENTER] [] [] adjust MIN-value
[] []

BOOM 1 RETRACT [ENTER] Parameter adjustment ON


PWM max 97 % [ENTER] [] [] adjust MAX-value

------------------------------------------------------------------------------------------------------------------------

PROP-CUR BOOM 2 [ENTER] Cf. boom section 1


//ENTER/CLEAR [CLEAR]

[] [] ------------------------------------------------------------------------------------------------------------------------

PROP-CUR BOOM 3 [ENTER] Cf. boom section 1!


//ENTER/CLEAR [CLEAR]

[] [] ------------------------------------------------------------------------------------------------------------------------

PROP-CUR BOOM 4 [ENTER] Cf. boom section 1


//ENTER/CLEAR [CLEAR]

[] [] ------------------------------------------------------------------------------------------------------------------------

PROP-CUR BOOM 5 [ENTER] Cf. boom section 1


//ENTER/CLEAR [CLEAR]

Service Manual 509


HOME PRINT
SERVICE TRAINING
Electrical

510 Service Manual


HOME PRINT

Service Manual

SCHWING Control system VECTOR


SERVICE MANUAL

Part Number 30100425

2
1
OK OFF

0 x1000 3
PTO 1500 rpm 62C

Menu: [ENTER]=ON

HOME + HELP START

CLEAR - ENTER QUIT

PART 1: OPERATION
PART 2: TEACH MODE
PART 3: EASy MODE (SHORT INSTRUCTIONS)
5900 Centerville Road
White Bear, Mn. 55127
Tel. (651) 429-0999
Fax (651) 429-3464
www.schwing.com

Copyright 2007, Schwing America, Inc.


All rights reserved

VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

START SCREEN:

Control status
Oil cooler "On"
PTO Speed OK System is running
Hydraulic oil temperature
Start
Start up control unit
Control switches not
1 2
OK Off?
in neutral position
Emergency stop
STOP!
activated
Entry expected
0 x1000 3
Modes of operation
PTO 1350 rpm 62C
Remote mode
Menu: [ENTER]=ON
Local mode

Menu bar for Concrete pump Ram change mode


further screens delivery rate Teach
mode! Teach mode

StartScreen.eps

512 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

PART 1

SCHWING control system 'VECTOR'

OPERATION
The present instructions are intended to serve as a 'memory aid'. They do not refer to any
particular type of machine and do not relieve the user of familiarizing himself with the operating
manual of the machine in question.

CONTENTS

Commissioning .......................................................................................514
Selecting local control .............................................................................515
Selecting remote control .........................................................................516
Ram change mode:.................................................................................517
Emergency stop buttons .........................................................................518
Override of the E-stop manifold ..............................................................518
Options box .............................................................................................519
Control and monitoring components .......................................................520
Menu control ...........................................................................................521
Local control............................................................................................522
Remote control........................................................................................523
Menu overview - Main menu ...................................................................524
Menu overview - submenus ....................................................................528
Menu operation - Example: .....................................................................529
Diagnostic system/Fault handling .........................................................530
Acknowledging faults ..............................................................................532
Fault definition.........................................................................................532
Summary of messages ...........................................................................540
Heat the oil first .......................................................................................552

VECTOR CONTROLLER-SERVICE MANUAL 513


HOME PRINT

Service Manual

Part 1 Operation Select the desired mode of operation with the


switch in the lower right corner of the vector
cover. The mode will then be indicated in the
Commissioning
display window at the right side, center of the
The electrical machine control system can only be start screen (Figure 1).
activated if the drive configuration has been properly
selected:
Parking brake set
Ignition key on, engine running at idle.
Transmission in neutral
Activate the PTO switch
vectorramchange.eps

When Indicator light comes on, put


transmission in proper pumping gear. When the control mode is selected, the display
will indicate that with a picture (Figure 2).

A bar graph on the display will indicate that the system


is being initialized.
The start screen (Figure 1) will be displayed after
localcontrol.eps
initialization.

remotecontrol.eps

1 2
Start OFF

0 x1000 3
NA 1760 U/min 52C

Menu: [ENTER]=ON

HOME + HELP START

CLEAR - ENTER QUIT


Figure 2
Vector control mode display, local (top)
commissionart2.eps
remote (center) ram change (bottom)

1 2
Start

0 x1000 3
PTO 1760 rpm 52C

Menu: [ENTER]=ON
vectornormal.eps

Figure 1
Vector start screen

514 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

Selecting local control

1 2
OK
0 x1000 3 2
PTO 1500 rpm 62C

Menu: [ENTER]=ON

Figure 3
Vector display window

This symbol is displayed in section #2 of Figure 3 Start up the system by activating the I switch on the
when local control is selected. front panel of the controller (Figure 1).

localcontrol.eps

Iswitch.eps

This symbol will flash in section 1 of Figure 3 when


any E-stop on the machine is activated. Check that all Starting is confirmed by a brief beep and the symbol
E-stop buttons are released. below is displayed in section 1 of Figure 3.

OK
STOP!
estop.eps

This symbol flashes in section 1 when a switch on the


rear operaors panel is on.
Set all switches to neutral.

This symbol flashes in section 1 of Figure 3 when the


system is ready for start-up.

Start
Istart.eps

VECTOR CONTROLLER-SERVICE MANUAL 515


HOME PRINT

Service Manual

Selecting remote control

2
1
OK
1
30356 534 C

0 x1000 3 2 2
3

PTO 1500 rpm 62C 303 623


48

4
5 6
displayID.eps

7
3

8
2

9
1
0 10

Menu: [ENTER]=ON remotebox.eps

Figure 4
Display screen for remote control

This symbol is displayed in section 2 of


the screen (Figure 4).
remotecontrol.eps

This symbol flashes in section 1 (Figure


4) when an emergency stop button on
the machine or on the remote control
STOP! box has been pressed.
estop.eps
The symbol flashes also when the
remote control box is off.
Unlock all E-stops or turn on the remote.

This symbol flashes in section 1 (Figure


4) when a switch on the remote control
box is on.
Set all switches to neutral.

This symbol flashes in section 1 (Figure


Start 4) when the system is ready for start-up:
Istart.eps

Start up the control with this switch on


the remote control box.
activate"I".eps

The starting is confirmed by a brief beep


OK and the symbol on the left is displayed in
section 1(Figure 4).

516 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

Ram change mode: The ram change position disables both local (rear
panel) and remote control, brings the engine to idle,
reduces the stroke limiter to minimum output, and
gives complete concrete pump control to the concrete
pump fwd/rev switch located at the ram change station
vectorramchange.eps
(Figure 6). See the Maintenance section of the
This symbol is displayed in section 2 of operation manual for ram change instructions.
the screen (Figure 4).

This symbol flashes in section 1 (Figure


4) when any E-stop on the machine is
STOP! pushed. Unlock all E-stops. 2
estop.eps 1
OK OFF

0 x1000 3
PTO 1500 rpm 62C

Menu: [ENTER]=ON

This symbol flashes in section 1 (Figure


4) when the system is ready for start-up.
Start HOME + HELP START

Istart.eps
CLEAR - ENTER QUIT

panelID.eps
switch
Start up the controller with the I switch
in (Figure 5). Figure 5
Iswitch.eps
Vector control panel

Starting is confirmed by a brief beep and


OK the symbol on the left is displayed in
section 1 (Figure 4).

32ramchange.eps

Figure 6
Ram change station

VECTOR CONTROLLER-SERVICE MANUAL 517


HOME PRINT

Service Manual

Emergency stop buttons


BY-PASS
NORM. BY-PASS

E_Stopbutton.eps

Figure 7
E-stop button by-pass2.eps

When and E-stop is pushed, all hydraulic functions of If the problem is actually a bad solenoid, the pilot
the machine will stop. Do not use the emergency stop signal to the dump valve can be overridden by having
for an on/off switch. It is for emergencies only. one person push and hold the override handle on the E-
In normal operating conditions, always stop the stop manifold while the other person activates the
machine functions with the controls provided for that manual controls for the nonworking system.
purpose.

Override of the E-stop manifold


Bypass mode Bypass
Key
OFF
2
1
OK

WARNING 0 x1000 3
PTO 1500 rpm 62C

Menu: [ENTER]=ON

Emergency stop switches are disabled


HOME HELP START
when manual override is activated. +

CLEAR ENTER QUIT


Use the by-pass key switch only for -

folding the boom in an emergency and


000360.eps

bypasskeyswitch.eps
for clean out
Figure 8
Use override only for emergency fold-up Bypass key switch location
and cleaning.
Emergency stop buttons do not function
when the bypass mode is used.
If there is a malfunction in the E-stop circuit and the
dump valves (in the E-stop manifold) open, oil will be
routed from the hydraulic pump directly back to the
tank. The dump valves also open when any emergency
stop button is pushed.
If the dump valves open and the machine cannot be
repaired immediately, the power supply to the dump
valves can be reactivated by using the bypass switch
(Figure 8).
By activating the bypass key switch to the bypass
position, you send power to the solenoid of the
normally open dump valve. If the solenoid is functional
the dump valve will close and you should be able to
fold up the boom and outriggers with the manual
controls.

518 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

Options box The bottom of the two switches (Figure 11) is used to
control the function of the optional concrete shut-off
valve.
The three position switch allows the operator to control
the function of the valve in three different modes:
Position number 1 is Auto-mode. This
mode should be used for normal operation. The
shut-off valve will work in relationship to the
concrete pump on-off switch. When the
machine is pumping, the concrete shut-off
valve is open and when the pump is stopped,
power is removed from the solenoid and the
valve inflates to stop concrete from draining
out of the boom. The valve can be overridden
via the remote box. If you are standing near the
boom with the remote box and wish to drain
the concrete from the boom, activate the switch
in Figure 12 to the down position which is the
concrete shut-off icon and the valve will open.
The switch is located to the left of the E-stop
button on the remote box.
optionsbox.eps Concrete shut-off valve
disable switch
Figure 9
Electrical options box for Vector units

shutoffswtch.eps
Night light switch
1
3035653 4 C
2
3

3036 2348
5 6
4

7
3

8
2

9
1

0 10

switchlocation.eps

valveicon.eps

Figure 10 Figure 12
Switch to activate the Switch on the remote box (left)
night light kit shut-off valve icon (right)
The switch shown in Figure 10 is used to activate the
Position number 2 closes the valve full time.
optional night light kit.
NOTE!
Concrete shut-off valve switch Do not activate the concrete pump in this
mode with full air pressure on the valve.
Damage could occur!
Position number three supplies power to the
concrete shut-off valve full time and disables
the valve. This position can be used instead of
the disable switch shown in Figure 12, to allow
Figure 11 the boom to drain prior to inserting a cleanout
Concrete shut-off ball, or any time the concrete needs to be
valve switch removed from the boom by gravity.

VECTOR CONTROLLER-SERVICE MANUAL 519


HOME PRINT

Service Manual

Control and monitoring components On start-up the following data is displayed on screen
(Figure 14):
Controller cabinet (Figure 13)
1. PTO speed
6 2. Hydraulic oil temperature
1 3. Oil cooler ON
4. Control status
5 5. Selected mode of operation
6. Concrete pump delivery rate
2
1
OK OFF

0 x1000 3
PTO 1500 rpm 62C
7. Menu options
Menu: [ENTER]=ON

NOTE!
2 4 After pressing arrow down key on the menu
HOME + HELP START
control panel, further operational data will
CLEAR - ENTER QUIT
3 be displayed:
- Concrete pump hydraulic oil
panelID.eps
pressure -
Figure 13
- Hydraulic oil level indication menuarrowdwn.eps
Component locations on the (optional equipment)
controller cabinet
- Engine load factor (optional
1. Display window equipment.)
2. Key: menu control Control status indications
3. Operating mode selector Section 4 (Figure 14) of the screen displays the
Local mode following conditions:
Remote mode
Ram change mode OK Control system is running
4. Momentary contact I switch (Start switch)
5. Key switch: E-stop bypass
6. Connector: radio or remote control System ready for start up.
Display window (Figure 14) Start
Istart.eps

1 2 3 4 Starting not possible: switches not in


neutral position.
2
1
OK Starting not possible: emergency stop
STOP! activated
0 x1000 3 5 estop.eps

PTO 1500 rpm 62C Operating mode display


allcallouts.eps

Section 5 (Figure 14) of the screen displays one of


Menu: [ENTER]=ON these modes of operation: Local-Remote-Ram change
7 6
Figure 14
localcontrol.eps
Display window data remotecontrol.eps

information

520 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

Menu control Fast selection/abbreviated function keys


(shortcuts):
Basic functions of the keys (Figure 15) Press the following keys at the same time:

HOME + -
and or
HOME + HELP START home.eps down.eps

To set the contrast of the LCD display


CLEAR - ENTER QUIT manually.
menubuttons.eps
During setting, the contrast is indicated on
display between 0 and 99%.
Figure 15
Menu Keys HOME
and HELP
home.eps help.eps

To go to the manual language selection for all


displays.

Each key performs a different function as follows:

Full return to start screen HOME

home.eps

Up one item in the menu selection list +

Down one item in the menu selection list -


down.eps

Supplementary information for certain


screens of the diagnostic function. Presently HELP
help.eps
not implemented.

Execution of certain actions, e.g. resetting S TAR T


start.eps
of the concrete pump delivery rate counter.

One step back in menu. CLEAR


clear.eps

Select indicated menu item or activate


change. E NTE R
enter.eps

Confirmation and reset of diagnostic


messages. QUIT
quit.eps

VECTOR CONTROLLER-SERVICE MANUAL 521


HOME PRINT

Service Manual

Local control

HP

RPM engine
(-) = down Compressor
(+) = up

Concrete pump delivery rate


Vehicle engine (-) = decrease
(0) = stop (+) = increase
(I) = start
Agitator
Work light
(R) = reverse (suction)
(0) = off R
(I) = on
Agitator
Water pump (P) = forwards (pumping)
P
(T)= momentary (special control)
(0) = off
(I) = locked (continuous)
Concrete pump

Vibrator reverse (suction)

Concrete pump
forwards (pumping)
Ball injection system

High-pressure water pump

522 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

Remote control

1
30356534 C
2
3

48
303623
5 6
4

7
3

8
2

9
1
0 10

RPM engine
(-) = down Water pump
(+) = up
Agitator in:
Vehicle engine ( ) = forward
( ) = reverse
(0) = off (stopping)
(I) = on (starting)
Concrete pump
forwards (pumping)
Control on
Diagnostic horn signal confirm
Concrete pump
(shut-off)
reverse (suction)

Vehicle signal horn on


boom speed slow
(placing operations)
End hose shutoff valve (0) boom functions off
boom speed fast
(set-up and take-down)

Ball injection system Radio remote control only:

LED:
Concrete pump delivery rate charge condition of transmitter battery

(-) = decrease
(+) = increase LED:
tansmitter state of operation:
continuously on = transmitter ready
Vibrator in automatic mode(on)
flashing = transmitting control
signals

VECTOR CONTROLLER-SERVICE MANUAL 523


HOME PRINT

Service Manual

Menu overview - Main menu

2 E-Stop Chain OK Oil Temp. Hydr. 84C


1
OK 1 2
OK Dump Valve BOOM On OK Diesel Engine Off OK
Dump Valve CP On
Dump Valve MPS On Output 0
0 x1000 3 0 x1000 3
PTO 1500 rpm PTO 1500 rpm 33
Function: Function: h
Menu: [ENTER]=Ein Status-Screen? E-Stop C Oilcooler C

CP Hydraulic Engine Active :Radio Outrigger Station 0


2 100 100 OK Error :No CAN Data! OK Brakes Lim-Sw right 0 OK
1 3 SigPTOl : =OK Brakes Lim-Sw left 0
50 75 Valve Output 0
0%
p 0C
0 4 0 50 0 0
0 bar ---% ---% Function: h Function: h
Radio Remote C Outrigger C

Command Switch Command OFF


Valve A: 0 B: 0 OK Hopper Grate close OK
Valve C: 0 D: 0 Rever. Station No
Valve DW: 0 E: 0 Valve Output OFF

0 0
Function: h Function: h
Boom C Agitator C

Switch/Command OFF Switch Command 0


Hopper Grate CLOSE OK Hopper Grate close OK
Stroke Limiter 0%
Valve Output OFF Output 0

33 0
Function: h Function: h
Concrete Pump C Vibrator C

Switch/Command 0 Manufacturer/Type
Water Tank OK OK KFZ.-TYP OK
Valve Output 0 Truck Serial Number
KFZ.-NR
0
Function: h
Water Pump C Truck Data C

Switch/Command 0 Main ID : 03.09.002


Water Tank OK OK SW : V01.10 OK
MMI ID : 03.09.002
Valve Output 0 SW : V01.10
Remote ID : PROTOTYP
0 Manufact. : OX
Function: h
HP-Water Pump C System Data C

Switch/Command 0 Mach.-Nr. :TEST SHE


Overheating No OK Mach.Type :03.09.001 OK
CP-Type :LS
Valve Output 0 Hyd.-Type :.-.-.-.-.-.-

O Hotline 1-888-292-0262
Function: h
Compressor C Machine Data C

Switch/Command 0 interPTOl clock!!!


Output 0 OK cond. batt. :OK OK
Switch/Command 0
Output 0 date d.m.y :
time h.m.s :
33
Function: h
Diesel Engine C System Clock C

Pumped Volume?

524 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

Menu overview - Main menu (continued)

Status-Screen?

Pumped Volume Counter


2
1
OK Start
Pumped on the job:
2.4 cbm
0 x1000 3
PTO 1500 rpm Reset ? - > [START]

Pumped Volume? Pumped Volume C

2
1
OK Malfunction List
Start

! n/a !!
0 x1000 3
PTO 1500 rpm

Malfunct.List? Malfunct.List! C

Oil Pressure CP 69.8 bar


2
1
OK Oil Temperature
Oil Tank Level
64
---.-
C
%
PTO Hours 33.84 h
0 x1000 3 CP Hours 0.09 h
PTO 1500 rpm Boom Hours 0.10 h

Oper.Data? Oper. Data! C

Water Pump Hrs 0.00 h


Hp-Water Pump Hrs 0.00 h
Compressor Hrs 0.00 h
Agitator Hrs 0.05 h
Oilcooler Hrs 33.51 h
Vibrator Hrs 0.00 h

Oper. Data! C

Pumped Vol. Job 2.4 cbm


Pumped Vol. Ttl 3.0 cbm
Strokes CP Ttl 40
Stroke Rate CP 00.0 st/m

Central Lubr. Hrs 0.00 h

Oper. Data! C

! Hours when moving !

Boom 0.00 h
Slewing 0.00 h
Outrigger 0.00 h

Oper. Data! C

I/O-Readout?

VECTOR CONTROLLER-SERVICE MANUAL 525


HOME PRINT

Service Manual

Menu overview - Main menu (continued)

Oper.Data?

2
1
OK
Dig. Input?
0 x1000 3
NA 1350 U/min

I/O-Readout?

-- Silent Diagnostic ?--


2
1
OK 1 2
OK Current: No OK
------------------------
Change? [ENTER]
0 x1000 3 0 x1000 3 Select Y/N [ ] [ ]
NA 1350 U/min NA 1350 U/min Store? [ENTER]

Parameters? Silent Diagn? Silent Diagn!

2 --- System-Language ---


1
OK Current: English OK
------------------------
Change? [ENTER]
0 x1000 3
Select Language [ ] [ ]
NA 1350 U/min Store? [ENTER]

Language MMI? Language MMI!

2
1
OK Pumped Volume shown in:
Current: cbm OK
------------------------
0 x1000 3 Change? [ENTER]
NA 1350 U/min Select Language [ ] [ ]
Store? [ENTER]
Display cbm/cby?
Displ cbm/cby!

2 Please Enter Password


1
OK **** OK
------------------------
0 x1000 3
Input [ ] [ ]
NA 1350 U/min
Store? [ENTER]
Password?
Password!

526 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

Menu overview - Main menu (continued)

I/O-Readout?
2
1
OK
0 x1000 3
NA 1350 U/min DI11 F31 Pwr Supply Dig Out 1 PO41 Slew right 0 mA
2
DI12 F32 Pwr Supply PropOut 1
1
OK PO42 Slew left 0 mA
Dig. Input? DI13 F20 Pwr Supply Dig Out 1 PO43 Boom A extend 0 mA
DI14 F18 Pwr Supply Inputs 1 PO44 Boom A retract 0 mA
0 x1000 3
DI15 Dump Valve Boom 1 PO45 Boom B extend 0 mA
DI16 Dump Valve CP 1 NA 1350 U/min PO46 Boom B retract 0 mA
DI17 Dump Valve MPS 1 PO47 Boom C extend 0 mA
DI18 E-STOP Chain 1 Prop. Output? PO48 Boom C retract 0 mA

DI21 D+ Signal Diesel 0 PO51 Boom D extend 0 mA


DI22 PTO On 0 PO52 Boom D retract 0 mA
DI23 Overheating Diesel 0 PO53 Boom E extend 0 mA
DI24 Oil Press. Diesel LOW 0 PO54 Boom E retract 0 mA
DI25 Limit Sw Boom A<22 0
DI26 Limit Sw Outr. right 0
DI27 Limit Sw Outr. left 0 PO55 StrokeLimiter CP 704 mA
DI28 Prox Sw Stroke Counter 0 PO56 Outrigger Prop. 2 mA

DI31 Limit Sw Slew 180 0


DI32 Limit Sw Boom A<50 0 SI11 Switch Water Pump 0
2
DI33 Limit Sw Boom A<20 0
1
OK SI12 Switch CP Forw. 0
DI34 Boom above the Hopper 0 SI13 Switch BP Rev 0
DI35 Limit Sw Slew 0 0 SI14 Switch St. Limiter + 0
0 x1000 3
DI36 Agitator Rever.Station 0 SI15 Switch St. Limiter - 0
NA 1350 U/min SI16 Switch Agitator Forw. 0
DI37 Horn Station 0
DI38 Limit Sw Hopper Grate 1 SI17 Switch Agitator Rev. 0
MMI Input? SI18 Switch Compressor 0
DI41 Oil Filter Boom 1
SI21 Switch HD-Water Pump 0
DI42 Oil Filter CP 1
SI22 Switch Engine Start 0
DI43 Limit Sw Slew right 1
SI23 Switch Engine Stop 0
DI44 Limit Sw Slew left 1
SI24 Switch Cl. Ball Inject 0
DI45 Outrigger Station 0
SI25 Switch Vibrator On 0
DI46 Water Tank MIN 1
SI26 Switch rpm (+) 0
DI47 Overheating Compressor 1
SI27 Switch rpm (-) 0
DI48 PTO rpm Prox Switch 0
SI28 Switch Option 0
DI51 RC Station Eng. Start 0 SI31 Rear Panel Detection 0
DI52 RC Station Eng. Stop 0 SI32 Switch Control Start 0
DI53 RC Station CP Forw. 0 SI33 Switch Op.Mode Local 0
DI54 RC Station CP Rev. 0 SI34 Switch Op.Mode Ch.rams 0
DI55 Dump Valves Bypassed! 0
DI56 Telescope Disabled! 0
DI57 Boom disabled! 0
DI58 Boom on Rest 0 Set Valve Stroke Lim. CP 30%

DO11 Start E-Stop Module 1 RI11 Switch Ctl. Start/Quit 0


2
1 2
OK DO12
DO13
BTS Driver Vibrator
BTS Driver Oilcooler
0
0
1
OK RI12 Switch Horn 0
RI13 Switch CP Reverse 0
DO14 Relay K01 Power MainB 1 RI14 Switch CP Forward 0
0 x1000 3 DO15 BTS Driver CP Lub.Sys. 0 0 x1000 3 RI15 Switch Vibrator Auto 0
NA 1350 U/min DO16 BTS Driver Horn Boom C 0 NA 1350 U/min RI16 Switch Open Air Cuff 0
DO17 BTS Driver Horn Slew 0 RI17 Switch Rabbit 0
Dig. Output? DO18 Buzzer Power Board 0 Remote Input? RI18 Switch Snail 0
DO21 Valve Agitator Forw. 0
DO22 Valve Agitator Rev. 0 RI21 Switch rpm (+) 0
DO23 Valve CP Forw. 0 RI22 Switch rpm (-) 0
DO24 Valve CP Rev. 0 RI23 Switch Engine Start 0
DO25 Valve Outriggers 0 RI24 Switch Engine Stop 0
DI26 Valve Water Pump 0 RI25 Switch Agitator Auto 0
DI27 Valve HP-Water Pump 0 RI26 Switch C1. Ball Inject.0
DI28 Valve Compressor 0 RI27 Switch Compressor 0
RI28 Switch Water Pump 0
DO31 engine Start 0
DO32 Engine Stop 0 RI31 Prop Boom A +000 %
DO33 rpm (+) 0 RI32 Prop Boom B +000 %
DO34 rpm (-) 0 RI33 Prop Boom C +000 %
DO35 Valve Boom Lub. Sys. 0 RI34 Prop Boom D +000 %
DO36 LED Slew Stowed Pos. 0 RI35 Prop Boom E /Tel. +000 %
DO37 Air Cuff 0 RI36 Prop Slew +000 %
DO38 Cleaning Ball Injector 0 RI37 Prop Str. Limiter +000 %
RI38 Prop Option +000 %

AI11 87 mV
2
1
OK AI12
AI13
5100
9810
mV
mV
AI14 9790 mV
0 x1000 3 AI15 4330 mV
NA 1350 U/min AI16 9800 mV
AI17 06.8 mV
Analog Input? AI18 06.4 mV

VECTOR CONTROLLER-SERVICE MANUAL 527


HOME PRINT

Service Manual

Menu overview - submenus

Status Screen? Pumped Volume? Fault list? Oper. data? I/O readout? Parameters?

E-stop pumping Malfunction list oil parame- digital input? silent


volume counter ters - DI11-DI58 diagnostic
remote con-
trol operating digital output? language
boom hours: - DO11-DO38 MMI?
concrete - P.T.O
pump - CP analog input?
display
water pump - boom - AI11-AI22
- cbm / cby?
high-pressure
water pump operating prop output?
password:
compressor hours: - PO41-PO56
- limit SR CP
- other
diesel engine
MMI input?
oil cooler
CP delivery - SI11-SI34 - Efficiency
outrigger rate: CP?
agitator - day / total
remote con-
vibrator - strokes trol?
- RI11-RI38
machine data
moving
truck data
hours:
system data - boom
system clock - slew drive
- stabilizers

528 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

Menu operation - Example:

RESETTING THE CONCRETE PUMP DAILY DELIVERY RATE

ACTION: RESULT:

menu line on opening screen:


Press:
Menu: [ENTER] = ON

next menu line:


Press:
Status Screens? E C

next menu line:


Press:
Pumped Volume? E C

Press: display of daily pumping rate, e.g.:


18.0 m

Press: daily pumping rate reset to


0.0 m

Press: return to opening screen

VECTOR CONTROLLER-SERVICE MANUAL 529


HOME PRINT

Service Manual

Diagnostic system/Fault handling

The integrated diagnostic system informs the The following message origins are available
operator about certain operating states, displays (1st column):
faults, and indicates the possible causes.
B = Boom (placing boom control)
The corresponding messages are displayed on
the screen of the control unit 1 (Fig. 1). D = Diesel engine (truck diesel engine)

The information displayed is always composed M = Machine


of a code and the corresponding message. (general machine control)

0 = Optional
(Optional control functions)
MESSAGE
P = Pump (concrete pump)
CODE
R = Remote (remote control system)

CODE S = System

The four-digit code is composed as follows:


The following types of message are existing:
X xx X
M = Message
X............: Origin of message
L = Low-level fault (minor fault)
xx........: Number of message
X : Type of message H = High-level fault (severe fault)

Example: 8
1
P01M
P............: Pump (concrete pump) 7
6
01.......: Number of message 1 2
OK OFF

0 x1000 3

M.....: Message PTO 1500 rpm 62C

Menu: [ENTER]=ON
5

2 4
HOME + HELP START

CLEAR - ENTER QUIT


3

Fig. 1

530 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

Display language

Texts can be displayed in three languages; Text messages, as well as international symbols,
English, German, and Spanish. may include additional information for service
personnel.
The language of text displays can be selected in
the "Parameter?" menu under "Language
Example 1: Text display
MMI?".
If "International" is selected, the messages are Disconnected / Overload
displayed without text by means of symbols. Solenoid Slewing Right
- PO41 !
The Summary of Messages section of this book
contains a complete list of the text messages
together with the international symbols. Example 2: International display
The messages are sorted by their code in alpa-
betical order.
PO41
Example 1: Text display

PO41 designates, for instance:


Message: Pressure Limiter
Concrete Pump
Activated ! Proportional Output 41

P01M The following additional information is possible:


Code:
PO = Proportional Output
Example 2: International display DO = Digital Output

K = Relay
Message: F = Fuse

Code: P01M

Important:
Since the international display makes multiple
use of the various symbols, it is absolutely
essential to consult Summary of Messages
for a clear identification of the message.

VECTOR CONTROLLER-SERVICE MANUAL 531


HOME PRINT

Service Manual

Acknowledging messages
NOTE!
Messages are not faults! They
are announced only visually on
CLEAR
the display and can be
clear.eps acknowledged with the
CLEAR key.

Acknowledging faults
Low level faults are announced visually on the screen
and acoustically by an intermittent tone from the
controller and the warning horn. These faults can be
acknowledged via remote control or directly on the
control cabinet.
High level faults are also announced visually on
display and acoustically by an intermittent tone from
the controller and the warning horn. They can only be
acknowledged on the control cabinet
NOTE!
In both cases the acoustic signal can be shut
off via remote control.

Fault definition
Low level fault
In the event of a low level fault, the job can still be
finished even if only with certain restrictions.

High level faults


High level faults can cause direct damage to the
machine. The control system will go to E-stop mode.
The operator must then decide if the fault displayed
will affect operational safety.
NOTE!
The operator is responsible for rectifying
any fault reported as soon as he possible
can, in order to prevent possible damage to
the machine. After a fault message has been
canceled, it will not be repeated.
Schwing assumes no liability for damage
caused by faults that have not been rectified.
When a low level fault is reported, this does
not mean that it can be ignored completely,
only that the job can be finished with
possible restrictions.

532 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

Silent diagnostic

In the "Parameter?" m u u d r "Silent a ?"


en n e di g ,

the op ra or ca s l c w
e t n r a faul is sig all d i
ee t hethe t n e n

the "REMOTE" mod of op ra io by


e or or wi
e t n the h n th the buzzer in the control cabinet.
MENU OVERVIEW Silent a nostic di g

D splay menu l ne / Key:


i i

Menu: [ENTER] = EIN


[ENTER]
Status screen? E C
[ ]
Pumped Volume? E C
[ ]
Fault l st?
i E C
[ ]
Oper. d ata? E C
[ ]
I/O splay?
di E C
[ ]
Parameter? E C [ENTER] > Silent diagnostic? E C
[ENTER]
Current : No

Change? [ENTER]

Select y/n [ ][ ]

Store? [ENTER]
Silent Diagn? E C

d
Silent iagnostic: Yes

m e ssage displayed on the screen

acoustic signal from buzzer

Silent diagnostic: No

m e ssage displayed on the screen

acoustic signal from horn

VECTOR CONTROLLER-SERVICE MANUAL 533


HOME PRINT

Service Manual

Reporting and acknowledging of faults

The way faults are acknowledged depends on the 2. Mode of operation : LOCAL
se lected mode of operation (LOCAL or REMOTE)
and on the severity of the fault: Silent diagnostic : Yes or No

1. Mode of operation : LOCAL Severe fault

Silent diagnostic : Yes or No


In the LOCAL mode of operation, severe faults
Minor fault are reported and acknowledged in the same
manner as described for minor faults.
In the LOCAL mode of operation, minor faults
are reported and acknowledged in the same In addition, the control system goes to e-stop
way, irrespective of whether Yes or No has mode.
been selected for the silent diagnostic:. Optional shutdown of the engine is also
possible.
The fault is displayed on the screen and A severe fault can only be acknowledged from
an nounced by the buzzer in the control cabinet. LOCAL.

- Depress the "QUIT" key on the


control panel (Fig. 1) once. ATTENTION:
RISK OF ACCIDENT AND DAMAGE
The buzzer stops sounding. After shut-off by a severe fault, the
control system and, if applicable,
The message continues to be the drive engine must be restarted.
displayed and can be read without It is absolutely vital to have a
hurry. severe fault rectified before re-
starting. Otherwise there is the
- Depress "QUIT" once more. risk of irreparable damage to the
machine.
The fault message is definitely
acknowledged.

The message is deleted from


the display and logged in the
faults list.

2
1
OK OFF

0 x1000 3
PTO 1500 rpm 62C

Menu: [ENTER]=ON

HOME + HELP START

CLEAR - ENTER QUIT

Fig. 1
QUIT key

534 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

3. Mode of operation : REMOTE

Silent diagnostic : No

Minor fault

The fault is displayed on the screen and an-


nounced by a horn signal.

- Activate "QUIT" on the remote Important:


control box (Fig. 1) once. Minor faults acknowledged
immediately with the "QUIT"
The horns stop sounding. key on the control cabinet
in the REMOTE mode are not
The message is deleted from the reported again when changing
display. modes.

- After switching the mode of op-


eration from Remote to Local,
the fault is displayed on the
screen and announced by the
buzzer in the control cabinet.

- Depress the "QUIT" key on the 1

control cabinet (Fig. 2) once. 2


3
30356534 C

48
303623
5 6

The buzzer stops sounding.


4

7
3

8
2

9
1
0 01

The message continues to be


QUIT switch
displayed and can be read without Fig. 1
hurry.

- Depress "QUIT" once more.

The fault message is definitely


acknowledged.

The message is deleted from the 2


1
OK
display and logged in the faults 0 x1000 3
PTO 1500 rpm
OFF

62C

list. Menu: [ENTER]=ON

HOME + HELP START

CLEAR - ENTER QUIT

QUIT key Fig. 2

VECTOR CONTROLLER-SERVICE MANUAL 535


HOME PRINT

Service Manual

4. Mode of operation : R E MOTE

Silent diagnostic : Yes

Minor fault

T he fault is displayed on the screen and an-


nounced by the buzzer in the control cabinet.

- Activate "QUIT" on the remote Important:


control box (F ig. 1) once. Low- level faults acknowledged
immediately with the "QUIT"
T he buzzer stops sounding (if not key on the control cabinet
switched off manually, the buzzer in the R E MOTE mode are not
will be stopped automatically after reported again when switching
60 seconds). over from LOC AL to R E MOT E mode.

T he message is deleted from the


display.

- After switching the mode of op-


eration from R EM O TE to LO CAL,
the fault is displayed on the
screen and announced by the
1

buzzer in the control cabinet. 2


3
30356 534 C

48
303623

- Depres s the "QUIT" key on the 4


5 6

7
3

8
2
control cabinet (F ig. 2) once.

9
1
0 10

QUIT switch
T he buzzer stops sounding. Fig. 1
T he message continues to be
displayed and can be read without
hurry.

- Depress the "QUIT" key on the


control cabinet (F ig. 2) once
more. 2
1
OK OFF

0 x1000 3
PTO 1500 rpm 62C

T he fault message is definitely Menu: [ENTER]=ON

acknowledged.
HOME + HELP START

T he message is deleted from the CLEAR - ENTER QUIT

display and logged in the faults


list.
QUIT key Fig. 2

536 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

5. Mode of operation : REMOTE

Silent diagnostic : No

Severe fault

The fault is displayed on the screen and an- Important:


nounced by the horns.
High-level faults can only be acknowl-
In addition, the control system goes to e-stop
edged with the "QUIT" key on the
mode. control cabinet, irrespective of the
Optional shutdown of the engine is also selected mode LOCAL or REMOTE.
possible.
- Activate "QUIT" on the remote
control box (Fig. 1) once.

The horns stop sounding.

The message continues to be


displayed and can be read without 1
2
30356 534 C

hurry. 3

48
303623
5 6
4

7
- Depress the "QUIT" key on the

8
2

9
1
0 10

control cabinet (Fig. 2).


QUIT switch
The fault message is definitely Fig. 1
acknowledged.

The message is deleted from the


display and logged in the faults
list.

2
1
OK
ATTENTION: 0 x1000 3
OFF

PTO 1500 rpm

RISK OF ACCIDENT AND DAMAGE


62C

Menu: [ENTER]=ON

After shut-off by a high- level fault,


the control system and, if applicable, HOME + HELP START

the drive engine must be restarted. CLEAR - ENTER QUIT

It is absolutely vital to have a


severe fault rectified before re- QUIT key Fig. 2
starting. Otherwise there is the
risk of irreparable damage to the
machine.

VECTOR CONTROLLER-SERVICE MANUAL 537


HOME PRINT

Service Manual

6. Mode of operation : REMOTE Important:


Silent diagnostic : Yes Severe faults can only be acknowl-
edged with the "QUIT" key on the
Severe fault control cabinet irrespective of the
selected mode LOCAL or REMOTE.
The fault is displayed on the screen and an-
nounced by the buzzer in the control cabinet.
In addition, the control system goes to e-stop
mode.
Optional shutdown of the engine is also 1
303565 34 C

possible.
2
3

48
303 623
5

Activate "QUIT" on the remote


4 6

7
3

8
2

9
1
0 10

control box (Fig. 1) once.


QUIT switch
Fig. 1
The buzzer stops sounding (if
not switched off manually, the
buzzer will be stopped auto-
matically after 60 seconds).
2
1
OK OFF

The message continues to be 0 x1000 3


PTO 1500 rpm 62C

displayed and can be read


Menu: [ENTER]=ON

without hurry. HOME + HELP START

CLEAR - ENTER QUIT

Depress the "QUIT" key on the


control cabinet (Fig. 2). QUIT key Fig. 2

VECTOR REMOTE DATA ABBREVIATIONS


The fault message is definitely
acknowledged. = NO DATA SEND
= HYD. PRESSURE IN BAR

The message is deleted from = PTO RPM (all digits are numbers)

the display and logged in the = STROKES/MINUTE

faults list. = HYD. OIL TEMP (Degrees Celsius)

= EMERGENCY STOP ACTIVATED


ATTENTION: = START CONTROL SYSTEM
RISK OF ACCIDENT AND DAMAGE = MACHINE in LOCAL MODE

After shut-off by a high- level fault, = MACHINE in RAM CHANGE MODE

the control system and, if applicable, = MACHINE in TEACH MODE

the drive engine must be restarted. = MACHINE IN CLEANING MODE

It is absolutely vital to have a = PUT SWITCHES TO NEUTRAL

severe fault rectified before re- = HOPPER GRATE OPEN


Fig. 3
starting. Otherwise there is the = WATER TANK LOW
30364527
risk of irreparable damage to the
The LCD window on the Radio remote will have
machine.
abbreviated codes which are explained in Figure 3.
NOTE:
Cable remote has no LCD window.

538 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

Acknowledging of several faults


ACKNOWLEDGING SEVERAL FAULTS

If several messages are existing, a


symbol appears in the lower right-
hand corner of the display:

Acknowledge the first message


as usual.

The next message appears and


the buzzer sounds.

Acknowledge this as well as any


following message until no further
message is displayed.

Switching off the control system


Switching off electrical control to the system, any
existing faults will be stored to memory.
Any fault will be re-detected and reported again when
the diagnostic system is restarted.

VECTOR CONTROLLER-SERVICE MANUAL 539


HOME PRINT

Service Manual

Summary of messages

Code international version (symbolic) plain text messages

B = Boom

Limitation
Slewing Gear
B01M Activated !

BOOM Limitation
Activated !
B02M

Disconnected / Overload
E-Stop Solenoid BOOM !
B04L
Disconnected / Overload
Solenoid Slewing Right
PO41 - PO41 !
B05L
Disconnected / Overload
Solenoid Slewing Left
PO42 - PO42 !
B06L
Disconnected / Overload
Solenoid BOOM A extend
PO43 - PO43 !
B07L
Disconnected / Overload
Solenoid BOOM A retract
PO44 - PO44 !
B08L
Disconnected / Overload
Solenoid BOOM B extend
PO45 - PO45 !
B09L

540 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

Disconnected / Overload
Solenoid BOOM B retract
PO46 - PO46 !
B10L
Disconnected / Overload
Solenoid BOOM C extend
PO47 - PO47 !
B11L
Disconnected / Overload
Solenoid BOOM C retract
PO48 - PO48 !
B12L
Disconnected / Overload
Solenoid BOOM D extend
PO51 - PO51 !
B13L
Disconnected / Overload
Solenoid BOOM D retract
PO52 - PO52 !
B14L
Disconnected / Overload
Solenoid BOOM E extend
PO53 - PO53 !
B15L
Disconnected / Overload
Solenoid BOOM E retract
PO54 - PO54 !
B16L
! Machine Safety Stop !

BOOM Control Fault !


B17H

D = Diesel Engine

Some Hydraulic Functions


Not In Neutral!
Diesel Start Disabled!
D01M
Power Limitation
Diesel Engine
Activated !
D02M
PTO is not working or
Prox-Switch PTO-RPM
Fault !
D03L

VECTOR CONTROLLER-SERVICE MANUAL 541


HOME PRINT

Service Manual

PTO RPM-Limit exceeded !


D04L
Indicator-Switch
PTO = ON/OFF
Fault !
D05L
Indicator-Signal
Engine Load
Fault !
D06L
Indicator Lvel
Diesel-Reservoir
Fault !
D07L
Disconnected
Truck Interface
DO31 Diesel Start - D031 !
D08L
Overload
Truck Interface
DO31 Diesel Start - D031 !
D09L
Disconnected
Truck Interface
DO32 Diesel Stop - D032 !
D10L
Overload
Truck Interface
DO32 Diesel Stop - D032 !
D11L
Disconnected
Truck Interface
DO33 RPM (+) - D033 !
D12L
Overload
Truck Interface
DO33 RPM (+) - D033 !
D13L
Disconnected
Truck Interface
DO34 RPM (-) - D034 !
D14L
Overload
Truck Interface
DO34 RPM (-) - D034 !
D15L

542 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

! Machine Safety Stop !


High Truck Coolant
Temperature !
D16H
! Machine Safety Stop !
Low Truck Oil Pressure !
D17H
! Machine Safety Stop !
Low Level
Hydraulic Oil !
D18H
! Machine Safety Stop !
Battery charging
On Truck Fault !
D19H

M = Machine

Ball Injector
Activated !
M01M

End-Hose Shut-Off
Activated !
M02M

Temperature Transmitter
Hydraulic Oil Fault !
M03L
Hydraulic Oil Filter
BOOM Contaminated !
Please Exchange Filter!
M04L
Hydraulic Oil Filter
CP Contaminated !
Please Exchange Filter!
M05L
Low Level
Hydraulic Oil
Reservoir !
M06L
High Temperature
Air Compressor !
M07L

VECTOR CONTROLLER-SERVICE MANUAL 543


HOME PRINT

Service Manual

Level Transmitter
Hydraulic Reservoir
Fault !
M08L
Transmitter
Oil Pressure Service
Fault !
M09L
Transmitter
Cleaning Ball Detection
Fault !
M10L

Disconnected PowerOutput
DO13 Oil Cooler - DO13 !
M11L
Overload / Fuse
PowerOutput
DO13 Oil Cooler - DO13 !
M12L

Disconnected PowerOutput
DO12 Vibrator - DO12 !
M13L
Overload / Fuse
PowerOutput
DO12 Vibrator - DO12 !
M14L

Disconnected PowerOutput
DO16 Horn Boom C - DO16 !
M15L
Overload / Fuse
PowerOutput
DO16 Horn Boom C - DO16 !
M16L

Disconnected PowerOutput
DO17 Horn Slew - DO17 !
M17L
Overload / Fuse
PowerOutput
DO17 Horn Slew - DO17 !
M18L
Disconnected Solenoid
Ball-Injector
DO38 - DO38 !
M19L

544 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

Overload Solenoid
Ball-Injector
DO38 - DO38 !
M20L

Disconnected Solenoid
DO26 Water Pump - DO26 !
M21L

Overload Solenoid
DO26 Water Pump - DO26 !
M22L
Kabelbruch Schaltventil
Kompressor - DO28 !
DO28
M23L

Disconnected Solenoid
DO28 Air-Compressor - DO28 !
M24L
Disconnected Solenoid
Agitator
DO21 Forward - DO21 !
M25L
Overload Solenoid
Agitator
DO21 Forward - DO21 !
M26L
Disconnected Solenoid
Agitator
DO22 Reverse - DO22 !
M27L
Overload Solenoid
Agitator
DO22 Reverse - DO22 !
M28L
Disconnected Solenoid
Hydraulic On Outriggers
DO25 - DO25 !
M29L
Overload Solenoid
Hydraulic On Outriggers
DO25 - DO25 !
M30L
Disconnected Solenoid
High Pressure
DO27 Water Pump - DO27 !
M31L

VECTOR CONTROLLER-SERVICE MANUAL 545


HOME PRINT

Service Manual

Overload Solenoid
High Pressure
DO27 Water Pump - DO27 !
M32L
Disconnected Solenoid
End-Hose Shut-Off
DO37 - DO37 !
M33L
Overload Solenoid
End-Hose Shut-Off
DO37 - DO37 !
M34L
Disconnected / Overload
Solenoid Hydraulic On
PO56 Outrigger - PO56 !
M35L
! Machine Safety Stop !
Hydraulic Oil
Temperature Exceeded !
M36H

O = Optional

Disconnected PowerOutput
Central Lubrication
DO15 CP active / Pump - DO15!
O01L
Overload PowerOutput
Central Lubrication
DO15 CP active / Pump - DO15!
O02L
Disconnected Output
Central Lubrication
DO35 BOOM active - DO35 !
O03L
Overload Output
Central Lubrication
DO35 BOOM active - DO35 !
O04L

Disconnected LED-Output
DO36 BOOM above rest - DO36 !
O05L

Overload LED-Output
DO36 BOOM above rest - DO36 !
O06L

546 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

P = Pump

Pressure Limiter
Concrete Pump
Activated !
P01M
Stroke Rate Limitation
Concrete Pump
Activated !
P02M

Hopper Grate Open !


P03M
Low Level
Water Reservoir !
P04M
Oil Temperature High,
Power Limiter Concrete
Pump Activated !
P05L
Transmitter
Oil Pressure Concrete
Pump Fault !
P06L
Prox-Switch Stroke
Counter Fault or
CP jammed !
P07L

Disconnected / Overload
E-Stop Solenoid CP !
P08L

Disconnected / Overload
E-Stop Solenoid MPS !
P09L
Disconnected Solenoid
Concrete Pump
DO23 Forward - DO23 !
P10L
Overload Solenoid
Concrete Pump
DO23 Forward - DO23 !
P11L

VECTOR CONTROLLER-SERVICE MANUAL 547


HOME PRINT

Service Manual

Disconnected Solenoid
Concrete Pump
DO24 Reverse - DO24 !
P12L
Overload Solenoid
Concrete Pump
DO24 Reverse - DO24 !
P13L
Disconnected / Overload
Solenoid Stroke Limiter
PO55 - PO55 !
P14L

R = Remote

R01M Emergency-Stop On
Radio Control Box
Activated !
R02M Low Battery In Radio
Control Box !

R03M CAN-FST /
Transmission With
Remote Control Fault !
R04M No Radio Control
Transmission !

R05L Joy-Stick 1 From


Remote Control Fault !

R06L Joy-Stick 2 From


Remote Control Fault !

R07L Joy-Stick 3 From


Remote Control Fault !

R08L Emergency-Stop Switch


On Radio Control Box
Fault !

548 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

Radio Control Signal


With Faulty Address
Received !
R09L
Disconnected
Boom Release
Solenoid !
R10L
Overload
Boom Release
Solenoid !
R11L
! Machine Safety Stop !
Hydraulic Enable Fault!
R12H

S = System

Disconnected
Rear Panel !
S01M
Power Supply
MAIN-Board
Fault !
S02L
Power Supply
MMI-Board
Fault !
S03L

CAN-Communication to MMI
or MMI-Board Fault !
S04L
Relay Contact
K 13
K 13 Override / Fault !
S05L

Fuse F 18 Fault !
F 18
S06L

VECTOR CONTROLLER-SERVICE MANUAL 549


HOME PRINT

Service Manual

Fuse F 20 Fault !
F 20
S07L

Fuse F 16 Fault !
F 16
S08L

Fuse F 31 Fault !
F 31
S09L

Fuse F 32 Fault !
F 32
S10L
MF1 : Power Supply
Diagnosis E-Stop Board
MF1 DI15 - DI18 Fault !
S11L
MF2 : Power Supply
Truck Interface etc.
MF2 DI21 - DI27 Fault !
S12L
MF3 : Power Supply
DI28,DI38,DI46,DI48
MF3 Fault !
S13L
MF4 : Power Supply
DI31-DI37,DI43,DI44
MF4 Fault !
S14L
MF5 : Power Supply
DI36,DI37,DI45
MF5 Fault !
S15L
MF6 : Power Supply
DI41,DI42,DI47,AI21,AI22
MF6 Fault !
S16L
MF7 : Power Supply
RAM-Change Station
MF7 DI51-DI54 Fault !
S17L
MF8 : Power Supply
DI55 - DI58
MF8 Fault !
S18L

550 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

Reference Voltage for


analog Sensors AI12,
AI13,AI14,AI16 Fault !
S19L
Multi Fuse
MMI-Board
Fault !
S20L

VECTOR CONTROLLER-SERVICE MANUAL 551


HOME PRINT

Service Manual

PART 2

SCHWING control system 'VECTOR'

TEACH MODE
NOTE! Restore original factory settings
Setting the parameters in Teach Mode When setting parameters you will need to take your
should only be done by persons with a remote control with you and go to the main controller.
complete understanding of the vector
control system. If your boom parameters have been changed and you
would like to have them revert to where they were
Teach mode offers the user the opportunity to teach the
originally, you can perform a simple procedure to
main controller how he or she would prefer to have the
restore the original factory settings.
boom respond to the remote control joystick
movements by setting parameters for minimum and 1. Open the front cover and without activating the I
maximum response times of each boom movement. switch, insert the Teach Key into the connector
MIN being the amount of signal it takes to start boom shown in Figure 17.
movement and MAX is the signal required to make the 2. The display window on the front cover should now
boom manual control handle travel all the way to the be showing you the screen shown in Figure 16.
mechanical stop. Setting these parameters requires
setting up the unit and unfolding the boom. Be certain
Restore parameters
that the boom has room to move safely during this
procedure.
to factory setting Start
NOTE! no yes
When the unit is in teach mode, the concrete [CLEAR] [ENTER]
pump and agitator are disabled to prevent
the operator from accidentally trying to
pump while the teach mode key is installed.
Teach Mode E C
vectorrestore.eps

Figure 16
WARNING Vector display window for restoring
to factory settings
Improper setup causes job site accidents:
Look for power lines before unfolding 3. Push the ENTER button to select yes. The
W024.eps

Be sure of unit's stability


controller will then restore the parameters to the
values set in the Schwing Test Department. After
about 10 seconds the system will reset itself.
NOTE!
When the system restart screen appears
Heat the oil first after setting the parameters, allow the
When setting the boom parameters the hydraulic oil controller time to complete the process
temperature must be at least 50 C and the engine RPM before performing any other system
should be increased to normal operating speed. functions to prevent losing your stored
information.

552 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

4. Select the Remote mode and activate the reset I


switch on the remote box.
5. Operate each function of the boom to see if it is
1 2
now responding the way you prefer. If it is, no Start
further action is required. Teach
NOTE! 0 x1000 3 mode!
The boom operates normally while in teach NA 1760 U/min 52C
mode so the key can be left in while testing
each boom function. Menu: [ENTER]=ON
6. If the boom is still not performing as you prefer, it teachmode.eps

will be necessary to continue with setting each


Figure 18
parameter individually by completing the steps that
Teach mode screen
follow.
NOTE!
Setting parameters If the unit is in local control when the teach
1. Place controller in Remote mode and activate the key is inserted the display will tell you that
I switch on the remote box. you must change to remote control to enter
the teach mode. Switch the local/remote
2. Open the front cover of the Vector controller and switch to the remote position and activate
plug in the hardware Teach Key to the connector the I switch on the remote box. If the
shown in Figure 17. display again asks the question Restore the
parameters to factory setting?, Press the
Clear button to say no.
Vector Teach Key
4. The display on the radio remote will display the
Connector
code shown in Figure 19.

1
303565 34 C
2
3

48
303 623
5 6
4
7
3

8
2

connectorlocation.eps
9
1

0 10

Figure 17 Teach mode


Location of Teach key connector

3. The display window on the controller cover will Figure 19


show that the unit is in teach mode and the I in Teach mode display
the upper right hand corner will be flashing, which
indicates that you need to activate the reset I
switch to start the teach mode process (Figure
18).

VECTOR CONTROLLER-SERVICE MANUAL 553


HOME PRINT

Service Manual

5. After activating the I switch, the display window 7. Start by holding down the I switch on the remote
will show you the screen in Figure 20. This chart box while you activate the right hand joystick
shows you RPM, Oil temperature, a picture of a forward to the extend positon.
boom cylinder, and six different boom options. The
far left column is where the boom slewing
adjustment will show, while columns A through E
represent each boom section A=1, B=2, C=3, D=4,
and E=5 if you have a five section boom.
activate"I".eps

1760 rpm 52 C
OK Figure 22
Activate I switch and hold
A B C D E
Teach NOTE!
mode! Boom movement is not proportional in
Teach mode so the joystick can be moved
all the way to extend or half way, it doesnt
Teach Mode matter as long as the boom function is
teachfunctionscreen.eps
activated.
Figure 20 8. When the joystick is activated and the I switch is
Teach mode parameter screen still being held down, the display will show a bar
graph like the one shown in Figure 23, at which
6. You are now ready to teach the controller what time the I switch can be released. The joystick
parameters you prefer. Well use boom #1 extend however, must remain activated or the screen will
as an example. Before you activate the function to revert to the one shown in Figure 20 and you will
be adjusted, you must decide which parameter you need to start over at the previous step. The
want to adjust (MIN or MAX). The selection is percentage shown on the graph indicates the
made with the Rabbit/Off/Snail switch. Choose amount of signal to this particular function (45%).
Rabbit for MAX or Snail for MIN. So to set the #1
boom extend MIN, you must first place the switch
to the Snail position (Figure 21). Engine speed (RPM) Oil temperature

1760 rpm 52 C
OK
snailspeed.eps

Figure 21
A
15
45 %
50
Teach
mode!
Choose Snail speed to set MIN
45
Teach Mode
minparameterscreen.eps

Cylinder ID Cylinder extend


MIN

Figure 23
#1 boom extend MIN screen

554 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

9. If the boom is not moving you should increase the 11. If you felt that the boom took off too fast when
percentage to this function by activating the joystick was activated and the percentage needs to
throttle switch to the + position. Each time you be decreased, tap the throttle switch Figure 24 to
tap the switch the duty cycle percentage will the - position until the boom responds as you like
increase by 1%. and store with the horn button as explained in the
previous step before releasing the joystick.
12. You should now activate the #1 boom joystick to
the retract position and adjust the percentage the
same way as you did for extend, and after storing
vectorthrtlpicto.eps

the parameter with the horn switch, the display


should look like Figure 26.

Figure 24 1760 rpm 52 C


Throttle switch on remote box OK
A B C D E
Teach
mode!

Teach Mode
10. When the boom just begins to move, you have minretractstored.eps

attained the required MIN signal and you will be Retract MIN
required to push up on the horn switch Figure 22 to stored
store the number. If you release the joystick before
Figure 26
beeping the horn, the percentage will revert to
Boom #1 retract MIN stored
where it was when you began. After you store the
information for #1 boom extend MIN the screen
will display a single mark in the A column as 13. You now have the option of continuing on to set the
shown in Figure 25. MIN on the other boom sections or moving the
rabbit/snail switch to the rabbit position (Figure
27) and set the MAX for boom #1 as follows.
1760 rpm 52 C
OK
A B C D E
Teach rabbitspeed.eps

mode!
Figure 27
Rabbit speed
Teach Mode NOTE!
extendstored.eps

Extend MIN Setting the MAX parameters requires


opening the hydraulic enclosure to gain
stored access to the boom hand valve (Figure 28).
Figure 25 This procedure applies to all units except
the 45/47 meter units which have no visible
Boom #1 extend MIN stored hand valve handles to view. The MAX
parameter on those units must be set by
checking the boom times found in the
Specification section of the operation
manual and operating each boom section to
monitor those times.

VECTOR CONTROLLER-SERVICE MANUAL 555


HOME PRINT

Service Manual

1760 rpm 52 C
OK
A
60
80 %
95
Teach
mode!
80
Teach Mode
maxparameterscreen.eps

s
Figure 29

V.ep
vlvR
MAX parameter screen
xbm
42s

16. The handle on the boom valve should now have


Figure 28 moved to the full extend position. Grab the handle
Manual boom control handles and pull or push it in the same direction it has
already moved. If the handle will not move any
further, it has reached the mechanical stop. If you
feel it is solidly against the stop and should be
backed off slightly, tap the throttle switch to the -
position until the pressure is relieved from the
14. Activate the I switch on the remote box and hold mechanical stop. If on the other hand the handle
it down. Move the right hand joystick to the extend moves freely and is not in contact with the
position. mechanical stop, tap the throttle switch to the +
NOTE! position until the handle comes in light contact
Boom movement is not proportional in with the stop. When you feel that the handle is
Teach mode so the joystick can be moved properly adjusted activate the horn button to store
all the way to extend or half way, it doesnt the parameter and release the joystick. The display
matter as long as the boom function is should now look like the one in Figure 30.
activated.
NOTE!
15. When the joystick is activated (Figure 28) and the
With the apitech hand valve it is necessary
I switch is still being held down, the display will to have pulsation in the handle after MAX
show a bar graph like the one shown in Figure 29, parameter is set. If pulsation stops, the
at which time the I switch can be released. The MAX is too high.
joystick however, must remain activated or the
screen will revert to the one shown in Figure 26
and you will need to start over at the previous step.

556 VECTOR CONTROLLER-SERVICE MANUAL


HOME PRINT

Service Manual

18. The procedure is the same for all functions, so


1760 rpm 52 C activate the I switch and move to the next
OK function until you have completed all parameter
settings. Any time you have entered information
A B C D E and then change the position of the local/remote
Teach
switch, the controller will first ask if you want to
mode! store the new parameters Figure 32.

Teach Mode
Extend MAX
stored
maxextendstored.eps

Store new parameters ?

no yes
?
Figure 30 [CLEAR] [ENTER]
Boom #1 MAX extend stored

17. Now activate the I switch again and move the Teach Mode E C
right hand joystick to the retract position. Follow Storenew.eps

the same procedure adjusting the manual control


handle to the mechanical stop on the opposite side.
When the adjustment is complete and you have Figure 32
stored the information by sounding the horn, Window for storing new parameters
release the joystick and the display window should
look like the one in Figure 31.
19. IF you answer yes, the system will restart and store
the new parameters Figure 33. If you answer no,
the window will ask If you want to restore to the
original factory settings. If you answer no to that
1760 rpm 52 C question the system will remain unchanged.
OK
A B C D E
Teach
mode! SYSTEM MESSAGE
!!! Attention !!!

Teach Mode Parameter changed


maxretractstored.eps
by Terminal !
Retract MAX
stored MAIN Board will
restart automatically !
Figure 31
rebootscreen.eps
Boom #1 MAX retract stored
Figure 33
System restart screen will appear when the
local/remote switch is moved

VECTOR CONTROLLER-SERVICE MANUAL 557


HOME PRINT

Service Manual

NOTE!
When the system restart screen appears
after setting the parameters, allow the
controller time to complete the process
before performing any other system
functions to prevent losing your stored
information. The restart takes only seconds
and when completed the display will again
show the screen below (Figure 34).

1 2
Start

0 x1000 3
PTO 1760 rpm 52C

Menu: [ENTER]=ON
vectornormal.eps

Figure 34
Vector normal operation screen

558 VECTOR CONTROLLER-SERVICE MANUAL


HOME
PRINT

REVISED
1/25/94
CROSS REFERENCE CHART FOR S.A.I. CABLE REMOTE CONTROL SYSTEMS GRP

REMOTE CONTROL FUNCTIONS * PIN ASSIGNMENTS FOR CONNECTORS USED ON S.A.I. REMOTE BOXES, PRIMARY CABLES AND EXTENSION REELS
HARTING WEILAND BURNDY HARTING AMPHENOL INTERCON 16 POLE HARTING 15 POLE INTERCON 12 POLE
PROPORTIONAL UNITS BLACK & WHITE UNITS w/throttle without
42 POLE 24 POLE 23 POLE 25 POLE 19 POLE BPLs S.P.B.s S.P.B.s BPLs
up & down throttle

#1 POTENTIOMETER # 1 BOOM EXTEND 1 1 A A-7 G 1 1 A-1 A-1 1 1


BOOM MICRO-SWITCH # 1 BOOM RETRACT 8 2 B A-8 H 2 2 A-2 A-2 2 2
BOOM # 2 AND # 3 RELAY # 2 BOOM EXTEND 2 3 C A-1 A 7 7 B-2 B-2 7 7
REMOTE HORN SWITCH # 2 BOOM RETRACT 9 4 D A-2 B 8 8 B-3 B-3 8 8
Radio Remotes

#2 & 3 POTENTIOMETER # 3 BOOM EXTEND 3 5 E A-3 C 5 5 A-5 A-5 5 5


BOOM MICRO-SWITCH # 3 BOOM RETRACT 10 6 F A-4 D 6 6 B-1 B-1 6 6
#4 POTENTIOMETER # 4 BOOM EXTEND 4 7 G A-5 E
BOOM MICRO-SWITCH # 4 BOOM RETRACT 11 8 H A-6 F
Cross Reference Wiring Chart

POTENTIOMETER BOOM SLEWING (CCW) 6 9 J A-9 J 3 3 A-3 A-3 3 3


BOOM
SLEW MICRO-SWITCH BOOM SLEWING (CW) 13 10 K B-2 K 4 4 A-4 A-4 4 4
ENGINE START (KVM 52M) BOOM SLEW SPEED I 15 16 L
ENGINE STOP (KVM 52M) BOOM SLEW SPEED II 22 17 M B-3 L
HOPPER VIBRATOR BOOM SLEW SPEED III 32 15 R B-4 M

Service Manual
POT. VOLTAGE + 15V UN-ASSIGNED 31 11 S
POT. VOLTAGE + 0V UN-ASSIGNED 42 12 T
ELEC. STROKE LIMITER CONCRETE PUMP POWER 7 21 X 14 C-4 C-2 12 9
MAIN POWER 24 VOLTS MAIN POWER 12 VOLTS 36 22 Z B-5 N 11 11 C-1 C-1 11 11
SERVICE TRAINING

UN-ASSIGNED MOTOR "ON" (S.P.B.) 9 B-4


UN-ASSIGNED MOTOR "OFF" (S.P.B.) 10 B-5
INDICATOR LAMP (NOT USED) 30 18 U C-6 V
ENGINE THROTTLE DECREASE 16 13 N B-7 R 10 B-5 10
ENGINE THROTTLE INCREASE 23 14 P B-6 P 9 B-4 9
CONCRETE PUMP REVERSE STROKE 17 19 V B-8 S 13 12 C-2 C-3
CONCRETE PUMP FORWARD STROKE 24 20 W C-1 T 12 13 C-3 C-4
VOLTAGE OUTPUT TO EMERGENCY DUMP VALVE RELAY 39 23 Y C-9 U 15 C-5

S0063.eps
* Per this chart, designations of the boom slewing speed functions for KVM 32XL and KVM 32XL with Flyaway Boom are NOT applicable. Refer to the repective electrical print for wiring information.

559
Remote Control Cable/Radio
HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

560 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Radio Control FW 18 Only specialists are allowed to repair the radio


controls.
In case of any failure, notify the SCHWING
Table of Contents after-sales service.
Only persons authorized by Messrs.
SCHWING are allowed to open leaded housings.
Black-and-white control / proportional control
Unauthorized manipulations may result in
(as from series 1987)
great damages and render all warranty claims void.
See also section 4.1.
1. SAFETY AND ACCIDENT PREVENTION
REGULATIONS ATTENTION! Before welding the machine, make
2. SHORT INSTRUCTIONS absolutely sure that the plugs of the connection
3. PREFACE cables are detached from sockets 7, 8, and 9 of the
4. EXTRACT FROM THE TERMS OF receiver. Protect the socket by means of a sealing
WARRANTY cap. Non-observance would result in damage to
5. MODEL PLATES the electronic control system (see also customer
6. TECHNICAL DATA information K 29).
7. SHORT DESCRIPTION
8. CONTROL AND MONITORING EQUIPMENT
9. COMMISSIONING
10. OPERATING THE RADIO CONTROL 4
11. PUTTING OUT OF OPERATION -
CHANGEOVER 5
12. SAFETY DEVICES AND TROUBLESHOOTING
13. MAINTENANCE WORKS AND CHECKS,
14. CHANGING AND CHARGING OF BATTERY
7 9 8
1. Safety and Accident
Prevention Regulations
The safety and accident prevention regulations
stipulated in the operating instructions for the
truck-mounted concrete pump are applicable and
binding for the operation with the remote control
too.
To avoid any unintended working movement of
the machine and before changing from one control
system to another:

!SET ALL CONTROL ELEMENTS IN THE


DRIVERS CAB AND ON THE REMOTE
CONTROL PANEL TO ZERO POSITION.
STOP DRIVING ENGINE.

Service Manual 561


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
Safety Regulations - Concrete Pumps with Traveling
placing booms Drive on bridges, decks, etc. only if the bearing
READ OPERATION MANUAL FOR THE & height capacity is adequate.
MACHINE. It describes the safe, proper, and most The vehicle must not travel with an unfolded
efficient way to operate. KNOW YOUR boom.
MACHINE! When traveling, the shut-off valves of the out-
rigger cylinders must be shut, and the outrigger
When operating the concrete pumps must be locked by means of the transport safety
and placing booms, the safety regula- devices.
tions of the responsible employers lia-
bility insurance company have to be Jacking
observed. The observation of these reg- Prior to jacking, check soil conditions. If nec-
ulations shall be the responsibility of essary, increase the support foot area by placing
the contractor and operator. square timbers underneath.
Keep sufficient distance from excavations;
The following are some supplementary recom- slopes could break away because of support pres-
sures.
mendations:
All safety devices and provisions against acci- On inclines, place chocks behind the wheels,
release the break, let the vehicle run against the
dents, such as warning labels and information
chocks, and apply the brake again; then jack.
signs, coverings, etc., must be in place. Do not
After jacking, close the shut-off valves of the
remove or tamper with them. If they are miss-
outrigger cylinders, otherwise the cylinders will
ing, replace them.
lose oil, and the machine could sink to one side.
See the following drawings for location of labels:
Concrete Pump
KVM 23 - 309903 KVM 32 - 309779 In order to avoid concrete splashes due to suc-
KVM 25 - 309918 KVM 36 - 309780 tion of air, the agitator hopper must always be filled
KVM 28 - 309778 KVM 42 - 309855 with concrete up to the mixing shaft.
KVM 31 - 309878 KVM 52 - 309930 DO NOT OPERATE THE CONCRETE
Check the operational reliability of the PUMPS WITHOUT THE HOPPER GRILL
machine each time before it is put into operation. FIRMLY BOLTED DOWN.
Any defects found must be repaired immediately. NEVER ALLOW HANDS NEAR THE
Allow the machine to be operated and main- GATE, VALVE, OR AGITATOR HOPPER
tained by qualified personnel only. WHILE THE MACHINE IS RUNNING.
Make use of handles and steps when ascending Before the gate or valve housing is opened,
or descending. stop the driving motor. If this is not possible (e.g.
Keep steps, platforms, control and monitoring in the case of cleaning work), the remote control
devices, etc. free of dirt, oil, snow, and ice. cable has to be disconnected to avoid unintentional
Before leaving the machine, protect it from movement of the valve. The concrete pump opera-
unauthorized use and unintentional movements. tor must make sure that no unauthorized person is
Unauthorized presence in the immediate area present in the area of the open gate or valve hous-
of the concrete pump and placing boom is not ing or starts the concrete pump accidently.
allowed. Warn persons who are in the immediate
area. Stop work if persons do not leave the area Placing Boom
after having been warned. The placing boom may be operated only up to
Wear personal protective equipment when a maximum wind speed of 48 m.p.h. (77 km/h =
operating the machine. wind force 8).

562 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
Under all circumstances, keep the boom suffi- enough to permit easy discharge of the con-
ciently away from obstacles such as boom cranes, crete.
scaffolds, buildings, etc. f. The pipe cleaning head must be equipped with
The placing boom must never be used as a a working gauge and a properly sized air regu-
crane for lifting materials. lator hand valve.
The length of the end hose must not exceed 4 g. The plug must be long enough to ensure air
meters (13 feet) in length. The end hose should not tight sealing of the pipeline at the catch basket
be kinked during pumping operations. The safety after the pipeline has been blown out.
cable between the boom pipeline and the end hose h. The plug must be tight-fitting to prevent com-
must be in place and attached. pressed air from flowing around the plug and
If end hose is replaced with a combination of into the concrete.
reducers and hoses (for example, a 5-4 reducer and i. Work at the pipeline is allowed only after the
4 hose), then all hoses, reducers, etc. must be fas- pipeline has been relieved of compressed air.
tened with safety cables and may not exceed the Ensure that the air pressure has been com-
weight of the recommended end hose. Any of the pletely relieved.
above mentioned items should be capable of han- j. Single pipe sections and short pipes up to a
dling the pumping pressures of the specific equip- length of 40 feet must not be blown out. Great
ment. danger of accidents exists because of rapid
Perform regular maintenance and lubrication expulsion due to too little mass!
of boom at 1 year prescribed intervals and do a When laying pipeline, use as few bends as pos-
complete check of the boom and tower annually sible. Horizontal pipelines must be adequately sup-
using Schwing Americas Regular Check-Up ported. When installing a vertical pipeline, the best
Concrete Placing Booms form, SAE-510. This method is to use upright struts supporting the low-
form is supplied with all units and is available from est vertical pipe. Each succeeding pipe should then
Schwing America. be anchored to the building.
It is preferable to install pipelines within build-
Pipelines
ings whenever possible. See operators manual and
PIPELINE AND CLAMPS MUST BE SUFFI- Pumping Concrete booklets for more informa-
CIENT FOR PUMP CAPABILITY. tion on pipeline installation.
The pipeline connections must not be opened
under working pressure. Before the pipeline is Remote Controls
opened, pressure must be relieved by sucking back To avoid unintended operating movements of
the concrete. Secure couplings after assembly of the machine, set all control levers or switches in the
the pipeline. operators cabin and on the remote control panel to
Because of the increased danger of accidents, the neutral position prior to any switch-over to
the following important points must be adhered to local or remote control and prior to disconnection
when blowing out the pipeline with compressed of the remote control line.
air:
a. Blowing-out should be performed under the Electrical Connections on the site-
supervision of an expert. Hydraulic Power Packs, etc.
b. No pipe bends or hoses should be connected to The power supply connection for electrically
the end of the pipeline during the blow-out driven stationary concrete pumps or the electric
process. power packs for pumps or booms has to be
c. No person is allowed to be next to the concrete arranged by the contractor.
discharge end. The power supply on construction sites,
d. A catch basket must be fitted to the concrete according to VDE 0100 paragraph 55, may be
outlet. taken only from a special feed point, e. g. an elec-
e. The concrete outlet should be positioned high trical distribution box with current-operated

Service Manual 563


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
ground protection. The connection of the power trol command is indicated on the transmitter and
supply cable to the feed point may be carried out receiver by the green LEDs flashing.
only by a qualified electrician. If no command is sent within a period of 20
Fuse protection and conductor size are the seconds, the transmitter reverts to idle state. The
responsibility of the electrician and must comply LED of the receiver indicates permanently GREEN
with the National Electrical Code and any local = READY. The idle state is cancelled by operat-
codes. ing any switch.

2. Short Instructions IMPORTANT:


Comply with safety and accident prevention
NOTE: These short instructions are to be regarded
regulations.
as a memory aid only and do not dispense from the
Consider maximum range of transmitter.
full knowledge of the complete operating instruc-
tions. Avoid radio shadows.
Switch the transmitter off by turning the selec-
tor switch to OFF. All machine functions are
Preparing the Commissioning immediately interrupted when the EMERGENCY
OFF button is pressed.
Switch all controls on the machine and on the
transmitter to 0 and off.
Reasons for Automatic Switch-off
Switch truck engine off when warm.
Interference by external transmitters
Check whether the cables are connected to the
Insufficient range due to radio shadows
antenna, power supply, receiver control, and
machine control panel. Empty battery
Transmitter controls are not switched to 0 or
Making Ready for Operation OFF when switching on the receiver.
Switch ignition on.
Place charged rechargeable battery into the 3. Preface
transmitter and the spare battery into the charger. The operating instructions contain important infor-
NOTE! Place battery into charger with poles in the mation concerning the operation and maintenance
correct position. of your
Set selector switch on machine control panel to SCHWING MACHINE.
Remote Control.
Unlock all EMERGENCY OFF buttons on the A copy thereof should always be within easy reach
machine. of the machine operator and the members of the
Switch on receiver. LED indicates: RED. maintenance crew. Any handling of the machine
Unlock EMERGENCY OFF button of trans- implies knowledge and close observation of the
mitter. operating instructions. It is advisable, therefore,
Switch on transmitter power supply (selector especially prior to commissioning, to read the
switch to ON). LED on receiver lights up instructions carefully several times and to become
GREEN. familiar with the machine.
If there is no reason for a fault, every further
control command will be passed on by receiver to NOTE: Perfect operation and maintenance ensure
the machine pilot control. lasting operational reliability.
Operating Mode
Downtimes as the result of avoidable maintenance
Start truck engine.
work can largely be avoided if particular attention
The transmission and reception of a valid con- is given to the following points:

564 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
Always operate the machine gently and with- 4. Extract from the Terms of
out force!
Never change of your own values set or speci-
Warranty
fied by the manufacturer, such as hydraulic oil The following extract from the terms of warranty
pressures, tightening torques, etc.! deals with those damages which may result from
Carry out all the prescribed maintenance and incorrect operation and maintenance:
inspection work completely and punctually!
Use only lubricants and operating supplies The warranty does not extend
according to our recommendations!
During operation, regularly read all the built-in a. to defects arising in consequences of natural
monitoring instruments and note any unusual reac- wear and tear, inadequate installation and erec-
tions (noises, lack of power, etc.)! tion work by third parties, inadequate commis-
Install only ORIGINAL SCHWING SPARES! sioning, inadequate or negligent handling,
subjection to unsuitable stresses and loadings;
During operation and maintenance work, the rele- b. to defects caused by modifications or repair
vant safety regulations must be strictly observed. work carried out by the purchaser or by third
parties without our prior approval.
(Note the extract from the terms of warranty.) c. to defects arising due to the installation of
spare parts which are not genuine SCHWING
parts.
In the event of failure, possible queries, and for
ordering spare parts, please contact:
If a defective machine continues to be used in spite
Schwing America, Inc. of the defect, the warranty shall be confined only
5900 Centerville Road to the original defect.
White Bear, MN 55110
**Complete terms of warranty, see section 7 of the
(651) 429-0999
TWX: 910-563-3539 General Trading Terms.
Subsidiary of: Friedrich Wilh. Schwing GmbH
When exporting our machines, special regulations
or the authorized representative for your area. possibly in force in the destination country must
Always quote the machine model, the serial num- be complied with.
*Any export of SCHWING machines without
ber, and the information on the model plates.
authorization from SCHWING is not allowed.
Appropriate Applications
Carry out operation and maintenance of the chas-
The machine is assigned exclusively to the appli-
sis and the engine installed according to the
cation purposes mentioned in these operating
makers instructions.
instructions.

The company of Schwing will not be liable for


damages, if
the machine is used for operations which are
not the normal practice.
the operation instructions, the safety regula-
tions, and the accident prevention regulations are
not observed.

Service Manual 565


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

5. Model Plates Transmission of the


A model plate is attached to both the transmitter control functions : digital
and the receiver.
Charging unit for
Radio remote control can only be performed with transmitter battery : installed in the
equipment which have identical characteristics on receiver
their model plates.
Receiver:
Operation of the radio remote control is without
charge in the FRG according to PTT approval Operating frequency : in the 70 cm band
AGB-242. (27.55 inches)

Please note here: Telegram evaluation : by microcomputer

Model: ______________________ Operating voltage : 11.5 to 14.5 V or


23 to 28 V, 200 mA
Equipment Number: ______________________
Relay outputs : 18
Frequency: _____________________
of your remote control equipment, and always Analogous outputs : 8 in sequence + 6,
quote them in case of queries, etc. 12, 18, V for 24 V
or : 8 in sequence = 3,
6, 9 V for 12 V
6. Technical Data
Proportional control

Transmitter:
7. Brief Description
The new generation of SCHWING RADIO
Operating Frequency : in the 70 cm band REMOTE CONTROLS are an advanced develop-
(27.55 inches) ment of the systems first introduced in 1983.
Radio remote controls can be retrofitted or fitted at
RF output power : 4 mW the factory.

Control channels : 18 black-and-white Dependent on the machine model, black-and-


and 8 proportional white or proportional controls are available.

Operating voltage and


Transmitter
power requirements : 9,6 V DC 70 mA
The transmitter is powered by a rechargeable
nickel-cadmium battery. An inbuilt idle state cir-
Type of operation : portable hand
cuit ensures optimized utilization of the battery
transmitter
charge. The idle state circuit switches the power
supply off when no switch is operated within a
Transmission range : approximately 50
period greater than 20 seconds. The power supply
m (164.5 feet)
switches on again when a switch is operated. The
operating voltage is permanently monitored.

566 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
An LED indicates to the machine operator that the The radio telegram emitted by the transmitter is
battery needs to be changed. If the battery is not detected and monitored by the receiver. If the
changed in approximately 30 minutes, the moni- receiver electronics recognizes the radio tele-
toring circuit blocks the transmitter. gram as correct and complete, the signal is sent to
the connected machine pilot control.
The coding electronics converts every switch
operation into an unmistakable transmit signal The transmitter and receiver are precisely tuned to
which is combined with a special identification each other. An external transmitter cannot affect
code before being sent by the transmitter. operation because different information (e.g.
equipment no.) belongs to the contents of each
As is known from the cable remote control system, radio telegram, and this is checked by the receiver.
the boom speed with PROPORTIONAL CON-
TROL is dependent on the excursion of the control In the event of an electronic fault or loss of tele-
lever: gram, the previous functions initiated are stopped.
The two-colour LED indicates the state of the
Short excursion = low speed receiver electronics: FAULT, READY,
Long excursion = high speed OPERATING. A storage rack incorporating the
recharge electronics for one transmitter battery is
By a precise graduation of the ranges of adjust- mounted in the receiver housing.
ment, the speed is almost continuously variable.
With the respective actuation of the control levers,
several movements can be made simultaneously.

Receiver
The receiver is mounted in the drivers cabin and is
powered by the truck voltage. The hydraulic com-
ponent (pilot control) is connected by cable to the
machine control panel via the socket provided.

NOTE: ONLY connect the receiver of the PRO-


PORTIONAL CONTROL to 24 V on-board volt-
ages with negative pole connected to the chassis
(negative to ground). The BLACK-AND-WHITE
CONTROL receiver can be connected to 24 V on-
board voltages with negative to ground or, AFTER
SPECIFIC READJUSTMENTS, to 12 V systems,
or AT ZERO POTENTIAL to systems with posi-
tive to ground.

NOTE! INCORRECT VOLTAGE, SHORT-CIR-


CUIT, AND OVERLOAD destroy the electronics.
For warranty reasons, we advise against installing
the system by yourself.

Service Manual 567


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

8. Control and Monitoring 6*- Selector switch: vibrator on/off


7*- Button: horn on truck
Equipment 8 - LED: EMERGENCY OFF button operated
9 - Selector switch: truck engine speed adjustment
Radio Remote 10*- Selector switch: engine on/off
Figure 1 = Black-and-white transmitter 11- Selector switch: concrete pump (pumping - off
Figure 2 = Proportional transmitter
- reverse)
12- LED: battery charge monitor
1 - Control lever with spring-centered 0-position 13- LED: radio signal output monitor
for placing boom functions 14- Selector switch: transmitter power supply ON/
2 - see 1
OFF
3 - EMERGENCY OFF button
4 - Potentiometer: output adjustment of concrete * = Optional extra
pump
5 - Antenna socket with removable antenna

1 1 5 2
8 12 13 8
12 13 4
3

11
4
14 6 4 11
10 9 10 14
9

568 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
Receiver RED = battery INCORRECTLY inserted
(pole), replace correctly (turn) immediately
1 - Toggle Switch: receiver ON/OFF OFF = no battery inserted
2*- 0.4 A fuse (receiver power supply) 6 - Plug-in module: transmitter battery charger
3*- 1.6 A fuse (charger power supply) 7 - Socket for connecting cable to machine control
4 - Two -colour LED: receiver state panel
GREEN = receiver READY 8 - Antenna socket
GREEN, flashing = receiver OPERATING 9 - Socket: power supply for receiver and charger
RED = receiver FAULT
5 - Two-colour LED: Battery charge control * = Not included in the new radio remote control
GREEN = battery CORRECTLY inserted series
(pole), charging

3 2 4
1
6
5

4
7 9 8
5

Service Manual 569


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

9. Commissioning
Preparations
3 2
1. Switch all controls on the machine and on the 1
transmitter to 0 or OFF.
2. Switch truck engine off when warm and with PTO
switched on.
NOTE: After a remote start, the engine should
run smoothly immediately. The remote control can 4
give no cold start assistance. 5
3. Disconnect remote control cable from control
panel and replace with cable: receiver - control 6. Unlock EMERGENCY OFF button of transmitter
panel. by turning to the right.
4. Check whether power supply cable, antenna cable,
and connecting cable are connected to the receiver. 2
5. Check whether antennas for transmitter and
receiver are mounted. If not, install. 1
8
Ready for operation 12 13
3
1. Switch on ignition.
2. Insert charged battery into the transmitter and spare 11
battery into charger. 4
14
NOTE! Make sure that the charger is inserted with 10
the correct polarity 9
3. Set selector switch on machine control panel to
remote control.

WARNING
Do not operate at
pressures exceeding
the rating of the
7. Set selection switch to ON. This causes the
entire material
delivery system.

1 following:
1 a) The power supply of the transmitter is
4 5 switched on. The red LED lights up for a short
time and extinguishes if the battery volt-
15 20
DO
IN

NO

10 U/minx100 25
RED
T OPERATE
ZONE

40 60 5 30
80
20 100
!

8 age is correct. The rhythmical flashing of the LED


C
0 35

6 O I O I
7 9 indicates that a radio telegram is being
M
ERGENC
O I O I HAND AUTOMATIK
transmitted.
E

b) The receiver is switched to READY.


STOP
10 13 14 15 The display of the two-colour LED changes to
GREEN.
4. Unlock all EMERGENCY OFF buttons on the If the two-colour LED continues to indi-
machine by turning them to the right. cate RED, the receiver is at FAULT.
5. Switch on the receiver using the toggle switch.
NOTE: The fault may be caused by an
LED lights up: RED. The receiver is waiting for a external transmitter in the immediate vicinity.
control signal.
The equipment is ready for operation.

570 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

10. Operating the Radio Remote Transmitter mode


Control 1. When the receiver is ON, unlock the
EMERGENCY OFF button of the transmitter by
NOTE! In order to avoid undesired movements of turning to the right, and set the selector which to
the machine, ALWAYS switch off the power sup- ON.
ply of the transmitter (selector switch to OFF)
when the machine is not in use.
2
If the engine is not fitted with an engine ON/OFF
switch, start the engine with the ignition key. 1
8
Putting on the transmitter
12 13
1. Insert the spring hooks of the upper belts into the 3
carrying frame.
2. Place the belts over the shoulders. 11
3. Insert the spring hooks of the lower belts into the 4
14
carrying frame. 10
4. Adjust the length of the upper belts as required by 9
means of the buckles.
*If desired, the carrying belt can be completely
removed from the transmitter.

1 5 2
12 13 8

9 10 14 6 4 11

2. If an engine ON/OFF switch is fitted, start the truck


engine using the selector switch.
3. If no control switch is operated when the
transmitter power supply is switched on, the
transmitter first sends address telegrams without
a control command. The LEDs flash GREEN.
After 20 seconds the idle state circuit switches
the transmitter power supply off. The LED
extinguishes. The receiver remains in the
READY state and the LED remains permanently

Service Manual 571


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
GREEN. After operating any switch, the power Transmitter range
supply of the transmitter returns. Work may then For safety reasons, the transmitter range is limited
proceed. but is sufficient for all conceivable construction
site situations. If the transmitter is taken out of this
broadcast range, all of the machines functions
will be stopped automatically.
3 2
1 Radio shadows
The machine operator must select his location in
such a way that he has unrestricted visibility into
the machines working area and that there is no
hindrance to the radio traffic.
4
5 The following may be taken as a rule of thumb:
The location has been chosen correctly if, at a
maximum distance of 50 meters (164.5 feet), the
Operation of the machine by wireless remote con- machine and the receivers antenna can be seen
trol is identical to that for cable remote control. without restrictions.

Please observe the following instructions for safe, Breaks in the work
uninterrupted operation: In order to prevent unauthorized operation of the
Capacity of the transmitter battery machine, the operator should not set down the
The capacity of each battery is dependent upon: transmitter once it has been switched on.
the age of the battery,
the charge level, and
the ambient temperature. 2

Under extreme conditions, the capacity of the 1


transmitter battery may be exhausted after about 8 8
hours of service. (System will be shut down by the 12 13
undervoltage.) 3

In order to ensure uninterrupted operation, we rec- 11


ommend always having a charged battery on hand 4
14
while charging another battery. 10
9
The integrated charge electronics prevents an over-
load.

NOTE: In order to prevent unnecessary reduction


IMPORTANT! Before removing the transmitter,
of NiCd battery lifetime, we recommend that the
switch off the truck engine and press the EMER-
batteries be regularly changed after every 3-4
GENCY OFF button. Set the selector switch to
operating hours BEFORE the voltage monitor
OFF and lock the transmitter into the drivers
indicates a battery change by flashing.
cabin. Secure the machine against unauthorized

572 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
use (see operating instructions of truck-mounted 4. Switch off the receiver by means of the toggle
concrete pump). switch.

Turn the receiver off by means of the toggle


switch. 2
3
1

3 2
1 4
5

4
5. **The LED extinguishes.
5 6. Switch the truck engine off and remove the
ignition key.
7. Lock the transmitter in the drivers cabin and
secure the machine against unauthorized use.
Putting out of Operation
1. Set all controls on the transmitter to 0 or OFF Changeover to Cable Remote Control
position. 1. Put out of operation as described above.
2. Set the selector switch to OFF. 2. Remove the connecting cable: between receiver
and control panel from machine control panel.
3. Connect standard remote control cable to the
2 machine control panel.
4. Perform commissioning as normal for cable
1 remote control.
8
12 13
3

11
4
14
10
9

3. Press the EMERGENCY OFF button.

Service Manual 573


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

12. Safety Facilities switch off the transmitter power supply.


In addition to manual switch-off (EMERGENCY Set all controls of the transmitter to 0 or
OFF position.
OFF button), the radio remote control is provided
with automatic facilities to immediately interrupt Change location (the transmitter may be in a
radio shadow).
or inhibit work operations in the event of a radio
fault. Unlock the EMERGENCY OFF buttons by
turning them to the right, and switch on the
ransmitter power supply.
1. SAFETY TEST DURING COMMISSIONING
The equipment is ready for operation again.
After switch-on, the receiver first tests whether its
radio channels are free and undisturbed.
If a signal is received, the receiver immediately Fuses
returns to the state: FAULT. (not included in new series)
NOTE: After reception of a VALID signal, the
receiver reverts to the state: READY. Sockets to receive two fuses are built into the
2. SAFETY CHECK DURING OPERATION upper part of the receiver.
The operational status will be suspended by: 0.4 A = receiver
switching the system off manually. 1.6 A = charger
actuating one of the EMERGENCY OFF but-
tons.
undervoltage of the transmitter battery.

The undervoltage monitor will shut down the


transmitter if battery voltage falls below the
safety threshold. Work may proceed after exchang-
ing the battery.

receipt of an invalid telegram

Transmission of the control commands from the


transmitter to the receiver is effected
using telegrams. These telegrams consist of a
so-called basic code (address telegram)
in addition to the actual control command. It is on
the basis of this basic code that the
receiver recognizes the voice of its transmitter.
Invalid telegrams may be caused, for example, by:
interference due to external transmitters
radio shadows
contradictory control commands

IMPORTANT! Should you note during operation


that the machine does not execute any control
commands:
press the EMERGENCY OFF button and

574 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

13. Maintenance Works and


Checks
The radio control is virtually maintenance-free. To
insure uninterrupted operation, observe the follow-
ing instructions:
IMPORTANT!
1. The entire system is resistant to splashed water, but
it is not waterproof.
2. Keep all components clean and dry and use the
cover caps to close off immediately any connection
plugs which are not being used.

Changing the transmitter battery NOTE: Check that the cover is correctly mounted.
If mounted upside down, there is a visible gap
1. Switch off the transmitter and press the
through which humidity can penetrate into the bat-
EMERGENCY OFF button.
tery compartment.
2. Undo the locking screws by rotating through 90
degrees.
Charging the transmitter battery
The battery in the charger is exchanged in the
same way as described above, but:
CAUTION! The charger is not equipped with an
automatic polarity switch-over circuit. If the LED
lights up RED, IMMEDIATELY remove the bat-
tery and change over the contact position (turn the
battery around). The LED will indicate GREEN if
the polarity is correct.
NOTE! The time it takes to charge a battery com-
pletely is approximately 14 hours or less, if the
battery is exchanged in good time.

3. Remove battery. NOTE! DO NOT USE any other chargers: RISK


4. Insert charged battery with its contacts first into the OF EXPLOSION.
battery compartment. The position of the positive
and negative poles is not important due to the NOTE! Only use ORIGINAL SCHWING NiCd
automatic polarity switch-over circuit. rechargeable batteries: There is a RISK OF DAM-
5. Replace cover. Turn the locking screws 90 degrees AGE to the equipment if incorrect rechargeable
and clip in by applying a slight pressure. DO NOT batteries are used.
screw in.
NOTE! Do not open the batteries (fumes hazard-
ous to health).

NOTE! Do not throw away batteries that are dead


or defective. Instead, dispose of them at an
approved collection point, which is equipped to
deal with special wastes.

Service Manual 575


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

576 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Radio Control FW 20
Table of Contents

1. TABLE OF CONENTS
2. SHORT OPERATING INSTRUCTIONS
3. FOREWORD
4. DESIGNATED USE, WARRANTY
5. SAFETY REGULATIONS AND ACCIDENT
PREVENTION REGULATIONS
6. CERTIFICATE OF APPROVAL
7. SHORT DESCRIPTION
8. TECHINCAL DATA, RATING PLATES
9. MONITORING-, WARNING-, AND CONTROL
ELEMENTS
10. PRE-OPERATING INSTRUCTIONS
11. OPERATION
12. EMERGENCY SHUT-OFF
13. INTERRUPTIONS OF WORK, END OF
OPERATION
14. REPLACING OF BATTERY
15. MALFUNCTIONS
16. MAINTENANCE, REPLACING OF FUSES
17. REPAIR

Copyrighted. These operating instructions must not be


duplicated, used improperly, or communicated to third
parties without our consent - not even by way of
excerpts.

Service Manual 577


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

2. Short Operating Instructions Pull EMERGENCY SHUT-OFF 1; LEDs 2 and 4


are extinguished; LED 3 is permanently lit: empty
The short operating instructions are to be used as a messages are being transmitted.
short reference only. They are by no means a Actuate control element; LED 3 is flashing: instruc-
replacement for the detailed operating instructions. tion messages are being transmitted.
Please observe also the operating instructions of the
machine! Emergency Shut-Off
Pushing in the EMERGENCY SHUT-OFF BUTTON
Preparations interrupts the main functions of the machine.
Set up the machine.
Set all control elements on the machine and the Automatic Shut-Off
transmitter to their 0 position. for example, in case of:
Shut off the vehicle engine as long as it is still low battery voltage
warm, and leave the ignition on. message errors
Plug in the receiver cable. electronic module failure
Set the operating mode selector switch on the no command instruction messages received
machine to REMOTE. (for more than 30 minutes).
Set the power supply switch of the electric
control to ON. Interruptions of Work
Unlock all EMERGENCY SHUT-OFF buttons Bring placing boom into transport position.
of the machine. Set control elements to 0-position.
Shut-off power supply of transmitter
Ready-for-Operation State
Set power supply switch of the electric control
Switch on power supply of transmitter; LED 4
to OFF.
is flashing.
Lock away transmitter.
Push EMERGENCY SHUT-OFF 1; LED 4 is
flashing faster.

2 3 4 5 6

578 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

3. Foreward or the authorized representative for your area, quoting


always the machine model, the serial number, and the
The present operating instructions are addressed to all information on the model plates.
persons in charge of operating and servicing the
SCHWING RADIO REMOTE-CONTROL UNIT
Carrying out operation and maintenance of the chassis
and the engine installed according to the makers
described overleaf and to owners or users of the instructions.
equipment.
4. Designated Use
The operating instructions are to help you familiarize The equipment is exclusively designed for the control
yourself with the equipment in order to of certain types of SCHWING machines.
use it for the purposes for which it has been
designed,
operate the equipment safely in order to avoid Any other use is considered as contrary to its
dangers, and designated use. The equipment must be used in
accordance with the operating instructions.
use it properly and efficiently in order to save
costs.
In addition to these, the operating instructions of the
machine must also be observed.
The equipment has been built in accordance with state-
of-the-art standards and the recognized safety rules.
Nevertheless, the equipment may constitute a risk to The equipment may only be installed by persons
persons and property if it is incorrectly used, operated, entrusted with such work by SCHWING.
serviced, or repaired. The designated use also includes the observance of the
operating, servicing, and repair instructions prescribed
Using the equipment presupposes the perfect by the manufacturer:
knowledge and strict observance of the operating SCHWING radio remote control units must be
instructions. Therefore, you should read the operating installed, removed, operated, and repaired only by
instructions carefully and repeatedly in order to specially trained and qualified personnel. Unautho-
familiarize yourself with the equipment before putting rized additions and modifications are not permit-
it into operation for the first time. Reading the ted.
instructions after the work has begun is too late! For servicing purposes only, ORIGINAL
SCHWING SPARE PARTS are to be used.
In addition to the operating instructions, the generally Before export, the equipment must be adapted
applicable legal and other mandatory accident by the manufacturer to the regulations in force in
prevention rules in the country of use are to be the country of use.
observed.
Non Designated Use
In the event of failures, possible queries, and for The manufacturer cannot be held liable for damage of
ordering spare parts, please contact: the equipment resulting from use outside its designated
Schwing America, Inc. use and from incorrect and inappropriate operation and
maintenance.
5900 Centerville Road
White Bear, MN 55127
(651) 429-0999
TWX: 910-563-3539

Service Manual 579


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Extract from Terms of Warranty


The conditions mentioned below are an extract from
the terms of warranty relating particularly to damage
which may be caused by incorrect operation and
maintenance.

The warranty does not include:


a) defects due to natural wear, inappropriate
installation and fitting by third parties, incorrect
commissioning, incorrect or negligent treatment and
inappropriate use;
b) defects caused by modifications or repair work
performed by the customer or by third parties without
our previous approval;
c) defects caused by the installation of non-original
SCHWING spare parts.

If defective machinery/equipment is kept in use in spite


of defects, the warranty only includes the original
defect.

For the complete terms of warranty, please refer to our


General Conditions of Sale.

580 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

5. Safety Rules and Accident after-sales service.


Electric welding procedures always bear the
Prevention Regulations risk of damaging electronic components.
The safety rules and accident prevention regulations
contained in the machines operating instructions are
These components must be properly protected by an
also applicable to the operation of the machine with the
expert in electronics before such work is carried out.
radio remote control unit.

If the vehicle is to be retrofitted with a mobile car


Some additional information is given below:
telephone, the safe distance between the two antennas
During the operation, the operator must have a must be at least 2 meters.
clear view of the machine and the concrete placing
site.
Do not place aside the transmitter as long as it If this distance is not respected, telephone calls may
is ready for operation. cause control signal transmission interference.
Always carry the transmitter in such a way that
any intentional contact with the control elements is
avoided.
Cut off the transmitters power supply during
interruptions of the work.
Always protect the transmitter against unau-
thorized use (by locking it away).
Before changing the control mode, set all con-
trol elements of the direct-, cable-, and radio-
remote units to the 0 position.
The transmitter is splash-proof (only when the
cover is closed), but not watertight.
The equipment may only be put into operation when
the cover of the receiver is properly closed.

Keep all parts clean and dry.

Close all unused connectors immediately with the


corresponding caps.

Keep the receiver cover closed when the machine is


being cleaned.

Avoid any contact of the equipment with steam jets and


aggressive detergents.

In case of trouble, never carry out repairs on


the equipment beyond those indicated in the trou-
bleshooting measures of the present operating
instructions, but rather inform the SCHWING

Service Manual 581


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

7. Short Description A power-saving feature automatically switches the


transmitter off during work interruptions in order to
The equipment consists of a portable transmitter, a save battery power.
receiver built into the machine, and a charger device for
the rechargeable transmitter battery.
The equipment bears the type-approval mark of the
Deutsche Bundespost (German Telecommunications
Depending on the type of machine, the equipment can Authority), is approved for use by the general public,
be supplied either in the proportional control version or and is not subject to registration or to licence fees.
in the pulse control version (black-and-white control).

All the control commands transmitted are safety-coated


in the transmitter so that only the pertaining receiver
responds to the signals.

The safety code is an individual code which does not


repeat itself.

Other transmitters, and also those of a different design,


will not cause the receiver to accept command signals.

The receiver checks the input signal, passing it on to


the machine control unit only if it is correct and
complete.

The channel switching of the radio equipment supplied


permits the simultaneous and interference-free
operation of several FW-20 units.

The transmitting and receiving frequencies of the unit


are selected in such a way that interference from other
radio services is virtually excluded. Moreover, the
transmitter is designed for operation with two different
transmitting frequencies.

Frequency switching in the receiver is fully automatic.

In case of interference in spite of these features, the


equipment automatically switches over to the safe
EMERGENCY SHUT-OFF state.

The transmitting range is limited to an area from which


the machine can be clearly seen.

582 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

8. Technical Data:
Transmitter

General
Operating temperature range: . . . . . . . . . . . . . . . . . . . . . . . . . . : -10 to +50 C
Type of protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : IP 65
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : 280 x 140 x 135
Transmitter-rechargeable battery set . . . . . . . . . . . . . . . . . . . . . : 9.6 V / 1000 mAh
Battery replacement at . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : < 9.0 V
Automatic transmitter shut-off at . . . . . . . . . . . . . . . . . . . . . . . . : < 8.7 V
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : approximately 3 kg

Transmitter
Frequency range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : 430 to 470 MHz, 2 RF channels, switch-selected
Transmitter output power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : approximately 5 mW
Transmitting range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : > 100 m

Digital System
CMOS microcontroller
PCM data transmission
Transmission time of radio commands
-pulse control unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : approximately 110 msec
-proportional control system. . . . . . . . . . . . . . . . . . . . . . . . . . . . : approximately 155 msec
Operating time with fully charged battery. . . . . . . . . . . . . . . . . . : approximately 12 hours

Service Manual 583


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
Receiver
General
Operating temperature range: . . . . . . . . . . . . . . . . . . . . . . . . . . : -10 to +50 C
Type of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : IP 00 (casing = IP 55)
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : 19 cassette 3HE/28FE resp. 42 TE
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : approximately 2 kg (without casing)
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : 20 to 28 V
Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : max. 0.5 A

Receiver
Frequency range : 430 to 470 MHz, automatic transmitting frequency
scan
Sensitivity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : 1 uV

Digital System
CMOS microcontroller
PCM data telegramme decoding

Active EMERGENCY SHUT-OFF . . . . . . . . . . . . . . . . . . . . . . . : by EMERGENCY SHUT-OFF message


from transmitter or in case of component
failure in EMERGENCY SHUT-OFF circuit

Passive EMERGENCY SHUT-OFF . . . . . . . . . . . . . . . . . . . . . . : by data message interference of > 1 sec. or


failure of one EMERGENCY SHUT-OFF
channel
Control channel output depending on
type of unit
FW 20 - K28 - V 24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : 32 switching - 6 proportional channels
FW 20 - K42 - IMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : 20 switching - 1 proportional channel
FW 20 - K42 - PROP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : 20 switching - 8 proportional channels
FW 20 - K42 - SANE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : 32 switching - 1 proportional channel

The transmitter and the receiver are equipped with a


rating plate. The unit serial number and the frequency Please note here:
must be the same for both units.
Type of equipment: ________________________

Transmission and reception of radio signals is only


possible with units having the same rating data. Serial number:____________________________

Frequency: ______________________________

of your equipment and indicate these whenever you


have any questions.

584 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

9. Monitoring-, Warning-, and


Control Elements

TRANSMITTER (fig. 1)
2 3 4 5 6
1- EMERGENCY SHUT-OFF button

2- LED: battery voltage monitoring

3-LED: Transmitter signal output monitoring

4-LED: EMERGENCY SHUT-OFF

5- Selector switch: transmitter power supply


ON/OFF 1

6-Selector switch: transmitter channel selection fig. 1


HF1/HF2

The other monitoring-, warning- and control


elements correspond to those of the cable control
units of the coresponding machine.

BATTERY CHARGER (fig. 2)

1-LED: battery charger power supply ON

2- Bi-coloured LED

green LED = battery is being charged

red LED = battery not correctly


inserted - change polarity

3-Socket outlet: power supply

4-Battery compartment
fig. 2

Service Manual 585


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

RECEIVER POWER SUPPLY (fig. 1)

1- Key switch in drivers cab: power supply ON

2- Pilot lamp: power supply ON

fig. 1

INSTALLATION OF RECEIVER (fig. 2)

1-Cover lock

2-Pilot lamp: power supply ON

fig. 2

RECEIVER (fig. 3)

T1-Connector for diagnostic unit

T2-Connector for diagnostic unit

fig. 3

586 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Fig. 1 = proportional control receiver

Fig 2. = black and white control receiver

LEDs

NG = power supply

UF = vehicle system voltage

UE 1 = controller 1 supply

UCC 1 = controller 1 supply (+5V)

UE 2 = controller 2 supply

UCC 2 = controller 2 supply (+5V)

NOT 1 = failure in EMERGENCY SHUT-OFF


circuit of controller 1
fig. 1
HF = receiver

K1 = RF-channel 1 selected

K2 = RF-channel 1 selected

MC 2 = controller 2 data message reception

MC 1 = controller 1

ST 1 = controller 1 failure

ST 2 = controller 2 failure

REL = relay output defective fig. 2

PROP = proportional control output defective

TEL = data message reception

TST3 = data message error 3

TST2 = data message error 2

TST1 = data message error 1

Service Manual 587


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

10. Pre-Operational Instructions During cable-controlled operation, the radio


receiver connector is in the unwired socket.
Position the vehicle as described in the
Lock the cable-connector.
machine operating instructions.
Set selector switch on the machine to
Set all control elements of the cable control
REMOTE.
unit (if connected) and the control elements of the
machine to 0 position. Release all EMERGENCY SHUT-OFF but-
tons of the machine (cf. machine operating instruc-
Shut off drive engine when it is warm. Remote
tions).
control cannot be used to activate any existing
cold-starting aid. Leave the ignition on. Switch on receiver power supply with key
switch in the drivers cab.
If required, remove the cable control unit con-
nector and insert the radio receiver connector into The ON state is indicated by lamps on the
the socket outlet. receiver.

588 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
After the switching on of the power supply, the LEDs
of the receiver must indicate the following state of
operation:

MODULE LED DISPLAY

NG all LEDs on
alternating in 1-second-intervals
HF K1 + K2
(transmitter-scanning)
MC 2 MC 2 flickering irregularly
flickering irregularly
TEL
MC1 on
TST 2
all others off

Service Manual 589


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
Put the transmitter into operation:

2 3 4 5 6

ACTION LED EFFECT

Set all control elements of putting into operation oth-


all LEDs off
transmitter to 0 position erwise not possible
request to test the EMER-
Switch on power supply
LED 4 flashing GENCY SHUT-OFF but-
with selector-switch 5
ton
Push EMERGENCY EMERGENCY SHUT-
LED 4 flashing faster
SHUT-OFF button OFF O.K.
transmitter ready for opera-
Unlock EMERGENCY LEDs 2+4 off; 3 perma-
tion, empty messages are
SHUT-OFF button nently lit
being transmitted

590 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
The following operating state must now be dis-
played at the receiver:

MODULE LED DISPLAY

off (EMERGENCY SHUT-OFF circuit


NG NOT1 + NOT2
closed)
permanently lit (depending on transmitter
HF K1 or K2
channel selection)
flashing regularly (data message transmis-
MC 2 MC 2
sion rate)
MC 1 TEL flashing regularly, all others off
flashing regularly (only for black-and-
REL REL
white control)

The unit is now ready for operation.

In case of trouble, cf. section 15.

Service Manual 591


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

11. Operation The LEDs of the REL module on the black-and-white


control unit receiver indicate that the relay is activated.
IMPORTANT! Depressing the EMERGENCY SHUT-
OFF button in case of danger immediately interrupts
the main functions of the machine. Cf. section 12.

2 3 4 5 6

1
An energy-saving feature prevents the transmitter
battery from deep discharge. The energy-saving feature
is reset after activation of any switch.
Choose your location in such a way that the concrete
placing site and the receiver antenna can be clearly
seen from a distance of not more than 50 meters. If all control elements of the transmitter are in their
0-position, the transmitter power supply is cut off
after 30 minutes.

In case of radio signal interruption, the receiver


switches the machine into the EMERGENCY OFF
state. Cf. section 12.

To reactivate the radio control system (and to close the


EMERGENCY OFF valve), short activation of one of
the control elements of the transmitter is sufficient.

In order to readjust the support outriggers, it is also


sufficient to switch the mode-selector on the machine
to the DIRECT CONTROL position.

Battery Capacity
The capacity of the battery depends on
The operations required to control the machine with the the age of the battery
radio transmitter are the same as with the cable control the charge condition
unit. the ambient temperature

Flashing of LED 3 indicates that active messages are Under normal conditions, the operating time of a new
being transmitted. and fully charged battery is approximately 12 hours.

592 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
It is recommended always to have a charged battery 12. Emergency Shut-Off
available, to charge another battery in the charger, and
to change the batteries about every eight hours or The control unit is equipped with 2 separate
before each new working shift. EMERGENCY SHUT-OFF modules.

Disturbances If a fault is detected by at least one of the modules, the


If, during the operation, the machine does not respond machine control system passes over to the
to control commands: EMERGENCY SHUT-OFF state.
change the transmit frequency. If this is unsuc-
cessful:
The EMERGENCY SHUT-OFF valve in the hydraulic
push the EMERGENCY SHUT-OFF button system opens.
change your location
put the control unit into operation
The hydraulic system is now working in the
check LEDs on transmitter:
pressureless circulation mode and the main functions
2 + 4 = off are stopped.
3 = permanently lit or flashing
The EMERGENCY SHUT-OFF condition is triggered,
If the control unit cannot be put into operation, see for instance, by pressing an EMERGENCY SHUT-
section 15 OFF button or by low battery voltage.

In addition, the receiver carries out constant checks:


2 3 4 5 6
of the transmitted data messages
whether the control commands are executed
(double reading)
the electric components of the receiver and
output circuits.

If faults are detected, the unit passes over to


1 EMERGENCY SHUT-OFF.

Cf. section 15.


Frequency Change
Changing the transmit frequency with selector switch 6 The unit can be restarted only after the fault has
makes sense only if another transmitter with the same been rectified.
frequency is being operated in the vicinity, or if
irregularities in the transmission are suspected.
Cf. section 10.

During a change of the frequency, the operation will be


interrupted for about 3 seconds, as the EMERGENCY
SHUT-OFF circuit of the receiver will be interrupted.

Service Manual 593


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

13. Interruptions of Work/End of


Operation Never use an EMERGENCY SHUT-OFF button for
ordinary shut-off.
Fold placing boom back to its transport posi-
tion.
Set all control elements of the transmitter to If the power supply remains on, the unit continues to
0-position. transmit the EMERGENCY SHUT-OFF signal. This
leads to unnecessary discharging of the battery.
Switch off the transmitter power supply with
selector switch 5.
Switch off the power supply of the receiver
with the key switch in the drivers cab.
2 3 4 5 6 Protect the transmitter against unauthorized
use (lock it away!).
If required, remove the receiver cable from
socket 1 and plug connector into unwired socket 2.

594 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

14. Replacing the Battery Put the machine out of operation.


Set all control elements of the transmitter to
A flashing LED 2 indicates that the rechargeable 0-position.
battery must be replaced.
Switch off transmitter with selector switch 5.
Turn the locking screws of the battery com-
2 3 4 5 6 partment counter-clockwise by 90 degrees and take
off the lid.
Withdraw the battery.
Insert a charged battery with the contacts
ahead into the battery compartments.

Observe battery polarity.

In case of wrong polarity, the transmitter cannot be put It is recommended to interrupt the power-supply of the
into operation. battery charger if longer operating breaks are to be
Put on compartment lid. expected (e.g. weekends).

Turn locking screws clockwise by 90 degrees, and To do so, withdraw cable from socket 3.
engage under slight pressure without further turning. Replace the battery as described on the front
side.
Take care that the lid fits correctly. Turning the lid 180
degrees during fitting leaves a visible air gap. In this The polarity is correct if LED 2 displays green, and it is
position, moisture can penetrate into the battery wrong if it displays red.
compartment.
If the LED shows a red light, remove the bat-
Recharging of Battery
tery immediately and change polarity by turning
The battery charger is permanently connected to the the battery.
power-supply.
Charging of the battery is completed after 14 hours
max.
The ready-for-operation state is indicated by LED 1. The battery cannot be overcharged. If the battery is full,

Service Manual 595


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
the charger automatically switches over to trickle 15. Malfunctions
charge.
Malfunctions are mainly caused by radio signal
interference, leading to an EMERGENCY SHUT-OFF.

Radio signal interference may have different causes:

TRANSMITTER OUT OF RANGE


The transmitter range is limited for safety reasons but
is, nevertheless, sufficient for normal use on
construction sites.
RADIO SHADOW
Choose your location in such a way that the working
range of the machine can be clearly seen and that
ATTENTION - DANGER!
undisturbed radio communications are ensured.
RISK OF EXPLOSION OF THE BATTERY:
Never use chargers from other manufacturers.
Use the following rule of thumb:

RISK OF DAMAGE if the unit is used with the wrong


batteries: The location has been correctly chosen if the concrete
placing site and the receiver antenna can be clearly
Use only ORIGINAL SCHWING BATTER-
seen from a distance of not more than 50 meters max.
IES.

LOW VOLTAGE OF TRANSMITTER BATTERY


NOXIOUS FUMES:
Never open rechargeable batteries. LED 2 gives a warning signal if the low voltage limit of
the battery is exceeded.

ATTENTION - PROTECTION OF THE


ENVIRONMENT! If the battery is not replaced within 30 minutes, the
Always bring unusable batteries to special col- transmitter shuts off automatically.
lection points for disposal.

2 3 4 5 6

596 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
Message Interference
Messages may be disturbed, for instance, by
interference from other transmitters.

An interference of up to 1 second does not affect the


functions of the machine.

The interference is, nevertheless, indicated by LEDs


TST 1, 2, 3, of the MC 1 module on the receiver.

Switch over to another transmit frequency with


selector switch 6 if you suppose message interfer-
ence.

2 3 4 5 6

If the vehicle is retrofitted with a mobile car


telephone, take care that the distance between the
antennas is not less than two meters.

Service Manual 597


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Trouble Shooting
Never attempt repairs beyond those recommended in
For function checking and fault detection, the
the troubleshooting section.
transmitter and the receiver are both equipped with
LEDs.
SCHWING assumes no responsibility for inappropriate
repairs.
In case of proper function, only the green LEDs may be
lit. Red LEDs indicate fault.
[TROUBLESHOOTING TABLE (needs to be made)]
For troubleshooting, use the fault detection tables on
Troubleshooting: Receiver LEDs
the following pages and state the last fault message
recorded if you contact us for help. Troubleshooting Table: Transmitter LED s

= LED on / = LED flashing / X = LED flashing faster / = LED off

+
STOP
LED LED LED DESCRIPTION ACTION
Battery empty, battery wrongly
Charge Battery; Turn Power On
inserted, power OFF
Valid empty messages, energy-
Begin machine control
saving timer ON
Valid control commands Control O.K.
Low battery voltage, approx. 30 Replace battery
minutes operating time left
Transmittter shut-off due to low
Replace battery
battery voltage
EMERGENCY SHUT-OFF See receiver
EMERGENCY SHUT-OFF test Push EMERGENCY SHUT-OFF
request button
Unlock EMERGENCY SHUT-
X EMERGENCY SHUT-OFF O.K.
OFF
Not all control elements in 0 -
Control elements in 0 -
position before the transmitter was position, restart.
switched on.
Only if check is carried out by
Fault detection mode quailified personnel
Module failure Call after-sale service

598 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Table 1: Power Supply (NG)

MESSAGE/ POSSIBLE REMEDIAL


LED DISPLAY
CAUSE OF TROUBLE ACTION
UF, UE1, UCC1, UE2, Switch in, check
none lit Machine power failure
UCC2 power supply
UF
on Power supply failure, short Call after-sales
UE1, UCC1, UE2,
one off circuit in receiver service
UCC2
EMERGENCY SHUT- Rectify fault, unlock
OFF activated EMERGENCY
NOT1, NOT2 ON
Fault detected by electronic SHUT-OFF
system see MC1
off, but no Replace fuse, cf. sec-
NOT1, NOT2 Fuse defective
function tion 16

MESSAGE/POSSIBLE
LED DISPLAY REMEDIAL ACTION
CAUSE OF TROUBLE
Transmitter scan, no radio Switch on transmitter, choose
alternately contact better transmitter location, check
K1, K2
flashing antenna
Message format error see MC1

MESSAGE/POSSIBLE
LED DISPLAY REMEDIAL ACTION
CAUSE OF TROUBLE
Transmitter off, no radio
not flashing Switch on transmitter, choose
contact
at message better transmitter location, check
TEL
transmission antenna
Transmitter defective, RF
rate Call after-sales service
section defective

Service Manual 599


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
Troubleshooting Controller (MC1)

MESSAGE/ POSSIBLE CAUSE OF REMEDIAL


LED DISPLAY
TROUBLE ACTION
Failure in MC 1 or in periphery module, Call after-sales
ST1 on
e.g. REL, NG, PROP service
Call after-sales
ST2 on Failure in MC2, no exchange of data
service
REL on Failure in REL See relay output
Call after-sales
Failure in PROP, analogue outputs out of
service
tolerance, adjuster deregulated
PROP on Check vehicle
Vehicle power supply voltage <20V
power supply volt-
resp. >28V
age
TEL not flashing No radio reception Check transmitter
at the Transmitter off or defective and antenna
rhythm of
transmitted
msg. Call after-sales
TST2 on Antenna not installed or defective service

600 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
Troubleshooting Table: Transmitter LEDs

= LED on / = LED flashing / X = LED flashing faster / = LED off

MESSAGE/POSSIBLE CAUSE
TST3 TST2 TST1 OF TROUBLE REMEDIAL ACTION
No empty message after switch-on Set control element to 0 -pos.
EMERGENCY SHUT-OFF act. Unlock EMERGENCY SHUT-OFF
Contact jamming Call Service Department
Format error in pulse-coded
Call Service Department
message
Format error in proportional
Call Service Department
message
Another transmitter with same
frequency nearby, message affected Call Service Department
by address error
Message affected by mode error;
Call Service Department
encoder switch in wrong position
Message affected by cyclic
Call Service Department
redundancy check error
EMERGENCY SHUT-OFF Rectify fault, unlock EMERGENCY
message SHUT-OFF

MESSAGE/POSSIBLE CAUSE OF REMEDIAL


LED DISPLAY
TROUBLE ACTION
Call after-sales
REL not flashing Relay outputs defective or not connected
service

Service Manual 601


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

16. Maintenance Replacing of Fuses


The control unit is largely maintenance-free. The circuit board of the black-and-white control
Nevertheless, a check should be carried out every 4 receiver and the circuit board of the proportional
years by SCHWING. control receiver are equipped with one fuse each.

Use only miniature fuses 5 x 20 mm, 3.15 A. Open lid of mounting rack with special key.
Swing back lid of mounting rack and replace
fuse.
Fuses can be replaced as follows:
Close mounting rack and put on cover.
Switch off the unit.
Open lock 1 and swing back cover.

602 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

17. Repair
REMOVAL OF RECEIVER
For repairs or for regular checks, the receiver must be
removed from the vehicle and sent to the factory for Push EMERGENCY SHUT-OFF button.
repair complete with the transmitter. Open cover, as described in section 16
Withdraw the (blue) multipole connector from
the circuit board.
For repairs outside Germany, please address to your
Pull off the antenna cable.
local agent.
Loosen the four fastening screws at the front
side.
Take care that the equipment is packed shock-proof.

Depress the screws slightly and turn counter-clockwise


by 90 degrees without further turning.

Withdraw the receiver unit carefully an d smoothly


from its compartment in the vehicle.

INSTALLATION OF THE RECEIVER


Push EMERGENCY SHUT-OFF button.
Insert receiver carefully and smoothly into its
compartment.
Turn the fastening screws clockwise by 90
degrees, and engage under slight pressure without
further turning.
Plug in antenna and multipole connector.
Close the cover.

Service Manual 603


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Operating Instructions - Radio Remote Control FW 20


Dual Fr equency
- Reference Chart -
FREQUENCY COORDINATOR
456.7525 1P-(PFCC)
456.8125 1S-(ITA)
456.8625 1S-(ITA)
456.9625 1S-(ITA)
457.0125 1S-(ITA)
457.5125 1S-(ITA)
457.525 1B-(NABER)
457.5625 1B-(NABER)
456.575 1B-(NABER)
457.6125 1B-(NABER)
457.6625 LM (ATA)
457.6875 LM (ATA)
457.7125 LM (ATA)
457.7625 LM (ATA)

(IS) ITA
SPECIAL INDUSTRIAL RADIO SERVICE INDUSTRIAL
TELECOMMUNICATIONS ASSOCIATION
ATTN. FREQUENCY COORDINATION DEPARTMENT
1110 NORTH GLEBE ROAD, SUITE 500
ARLINGTON, VA 22201
703-528-5115
(IB) NABER NATIONAL ASSOCIATION OF BUSINESS AND EDUCATIONAL
RADIO, INC.
ATTN. FREQUENCY COORDINATION DEPARTMENT
1501 DUKE STREET, SUITE 200
ALEXANDRIA, VA 22314
800-759-0300
703-739-0300
(LM) ATA AMERICAN TRUCKING ASSOCIATION, INC.
ATTN. GUS GYLLENHOFF
2200 MILL ROAD
ALEXANDRIA, VA 22314
703-838-1730
(IP) PFCC PETROLEUM FREQUENCY COORDINATING COMMITTEE
ATTN. MARIE HAWKINS
1110 NORTH GLEBE ROAD, SUITE 500
ARLINGTON, VA 22201
703-528-5115

604 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Radio Control FW 24
Table of Contents
1. Safety Instructions
2. Scope of Application
3. Start-up
4. Operation
5. Charging the Battery
6. Maintenance
7. Operation
8. Fault Indicators

Service Manual 605


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Safety Instructions
SAFETY INSTRUCTIONS

Please read these operating instructions If your remote-control is a "COMFORT-


completely before putting your TELETEC Control" unit, the radio receiver must not be
remote-control into operation. disconnected. Cable operation may
otherwise be impossible.
Observe also the corresponding working
safety and accident prevention regulations. Repair work on the remote-control unit may
only be performed by TELETEC or by
The instructions relating to the operation of qualified personnel duly authorized by
the machine itself are contained in the TELETEC.
machine manual.
Non-observance of the safety instructions
Remote-control units may be used by duly will discharge TELETEC from any and all of
authorized persons after they have been their warranty and liability obligations.
instructed by a specialist.

Do not put the operational transmitter aside,


but always protect it against unauthorized
use by locking it away.

The remote-control may only be used for


purposes complying with its designated use
i.e. only for controlling the machine or plant
for which it is designated.

Any other use is forbidden.

Using the device for purposes other than its


designated use, faulty operation, insufficient
maintenance and unauthorized repairs of
the remote-control unit may cause severe
material damage and injury to persons.

In the event of malfunction or defects of the


remote-control unit depress immediately the
red EMERGENCY SHUT-OFF button,
switch the transmitter off and keep it in a
safe place.

Disconnect all cables from the receiver if


your remote-control is a "MULTI-Control"
unit.

606 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Scope of Application
SCOPE OF APPLICATION

1 2 3
The present operating instructions are
applicable to FW 24 radio remote-control FW24-ID.eps
Stop POWER

units in proportional and digital design


HF1
4
suitable for SCHWING truck-mounted HF2

concrete pumps equipped with control



systems of the "MULTI-Control" and

FW24rmbx.eps
"COMFORT-Control" type. 6 5
The operator panels of the radio
transmitters are the same (with the
exception of switch 6, Fig.1) for both control Fig.1
systems. For detailed description please
refer to chapter 3.

The present manual does not contain Switch 6:


instructions relating to a particular type of
machine.

For machine-specific instructions please


refer to the corresponding machine manual. 0 MULTI-Control

MANUFACTURER

FW 24 remote-control units are


manufactured for SCHWING by:

TELETEC GmbH COMFORT-Control


Paul-Lincke-Ufer 39/40
10999 Berlin
Tel. 030-612 40 45
FAX 030 - 611 50 39

Service Manual 607


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Start-Up
START-UP

Remote-control system 1 2 3
FW24-ID.eps

Transmitter and receiver are each equipped Stop POWER


HF1
4
with an identification plate.
HF2

To permit communication between 

transmitter and receiver it is necessary that

FW24rmbx.eps
6 5
both devices have the same serial number
and frequency.

Proceed as follows to put the system into


operation: Fig.1
3. Switch on the transmitter with "Power"
1. Switch on the receiver: switch 4 by setting the switch to "HF 1" or
"HF 2" (frequency selection).
- Switch on the ignition and the power take-
off of the truck. POWER
HF1
- Apply the parking brake.

- Switch on the machine control unit with the


key-switch in the drivers cab.

- Set the selector switch on the local control HF2


panel to "Remote".

- Insert charged battery pack into the The red light-emitting diode (LED 3) now
transmitter housing and lock the battery starts flashing at a slow rate.
case.
Stop
2. Make sure all switches are in their basic
(or neural) position before switching on the
transmitter (Fig. 1)

Fig. 1 shows only those control and 4. Perform the emergency shut-off test:
monitoring elements as a are typical of
radio remote-control unit. -Depress the emergency shut-off test,
All other elements correspond to those of -The red LED 3 now flashes at a fast rate.
the standard cable remote-control.
- Release the emergency shut-off button
Refer to the machine operating instructions. (unlock).
Unlock the EMERGENCY SHUT-OFF
button. Without unlocking, starting of the
system is inhibited for reasons of safety.

608 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Stop To switch off the transmitter, e.g. after the


work has ended, set the "Power" switch 5 to
1 2 3 neutral position ("0").
POWER
HF1
"MULTI-Control" system"

The green LED 2 (antenna) is lit up


continuously and the red LED 3 is flashing. 0

Enable the control system by setting switch HF2

6 briefly to Do not depress the EMERGENCY SHUT-


OFF button for normal shut-off to prevent
the emergency shut-off signal from being
0 transmitted permanently and the
rechargeable battery from being emptied.

Special transmitter operation features


Only then will the red diode (LED 3) go out 1. Selecting the boom speed
and the green one will flash.
The boom control functions must be
The transmitter is now ready for operation activated with switch 6.
and the commands given with the control
elements are executed by the concrete
pump.

"COMFORT-Control" system:

The red diode (LED 3) goes out and the In the center position ("0") of this switch all
green one (LED 2) is lit up. functions of the boom are deactivated.
The transmitter is now ready for operation Moving the joysticks causes the red diode
and the commands given with the control (LED 3) to light up to indicate that boom
elements are executed by the concrete operation is disabled.
pump.
The switch must be set to the "Snail" or
Note: "Hare" symbol.
The "COMFORT-Control" system does not "Snail" = slow is the preferred speed for
provide an enabling function for switch 6. normal working operation and
Switch 6 is needed for a fault- "Hare" = fast is the speed used for setting
acknowledging function labeled "quitt" up of the placing boom.
[acknowledge].

See also the abbreviated "COMFORT-


Control" operating instructions, i.d. no.
10167123.

Service Manual 609


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Depending on the type of control, the After switching over to another channel, the
selection of either "Snail" or "Hare" has a transmitter must be re-activated as
different effect: described on page 3.1 (EMERGENCY
Control digital proportional SHUT-OFF test etc.).
reduced slewing- 0-50% speed for
gear speed all boom func- The receiver will be switched over
tions automatically to the new transmission
channel.

full slewing-gear 0-100% speed In the event of persisting radio transmission


speed for all boom func- disturbances or other defects, the system
tions shuts itself off automatically and passes into
the protected EMERGENCY SHUT-OFF
state.

Note:

In the neutral position of switch (6) all


functions are available except the placing
boom functions.

This is important when the placing boom is


connected to a stationary delivery line (by a
hose bridge) and must therefore be
prevented from being moved by accident.

2. Changing the transmit channel

If the radio channel in use is disturbed


(transmission of control commands
interrupted or no transmission at all) you
can use the "Power" switch (5) to select
between "HF 1" and "HF 2".
POWER
HF1

HF2

This switch selects the transmission


channel.

610 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Operation
OPERATION

When the remote-control is ready for


operation and after all EMERGENCY

.
SHUT-OFF buttons on the machine have

.
ig

og
C

Pr
Fr
M
been unlocked, all functions of the concrete
pump can be operated with the remote-
control unit (see the machine operating

2
1

2
T

T
C

O
M

M
N

N
instructions.) 4 5 6 7 11

n
de
tt

n
po
Indicator lamps on receiver

tla
de
r

En
Ve

La
8 9 10
Figs. 1 and 2 show the layout of the
receiver front panels:

Fig. 1 = "MULTI-Control" + -
Fig. 2 = "COMFORT-Control"

The red light-emitting diodes 5 and 7 Fig.1


("NOT/EMERGENCY" 1 + 2) monitoring the
emergency shut-off circuits go out if the

2
1

2
T

T
C

O
M

M
N

N
signals from the correctly activated
transmitter are being received. 4 5 6 7 11

n
de
tt

n
po

tla
de
r

En
Ve

La
They are lit up if no valid radio data 8 9 10
telegrams are being received or when the
emergency shut-off button on the
transmitter has been depressed.
+ -
In this case, the receiver in in the
EMERGENCY SHUT-OFF state, i.e.
deactivated.
Fig.2
The green light-emitting diodes 4 and 6 "Multi-Control" only
("MC 1 + 2") indicate by fast flashing that
valid radio data telegrams are being In this system, the green LED 1 ("MC 3")
recieved. and the green LED 2
("Freigabe/Enable") are lit up in addition.

These two LEDs indicate that the built-in


control module is activated, too.

LED 3 ("Prog.") remains off and is not


relevant for working operations.

The diode is used for servicing only.

Service Manual 611


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Charging the Battery


CHARGE THE BATTERY

When the red LED 1 (battery) of the To maintain the full charging capacity of the
transmitter starts to blink during normal battery over a long time, it should be
operation, the battery is almost empty. completely discharged once a week before
Stop recharging.

For this purpose, your charger is equipped


with an automatic discharge function:
Ca. 10 to 20 minutes later the transmitter
will be shut off automatically. For discharging keep the yellow button 11
depressed, insert the battery into the
During this time, the empty battery must be charger and lock.
replaced with a new one.
The yellow LED 10 ("Entladen/Discharge")
After replacing, restart the transmitter as will now light up.
described in chapter 3.
When the battery is completely discharged
Insert the empty battery for recharging into the charger switches automatically to normal
the charging case of the receiver and lock. charge and later on to trickle charge (green
Make sure the battery is inserted into the LED 9 flashing).
case with the correct polarity.

The green LED 9 ("Laden/Charge") on the


g.
3

.
og
ei
C

Pr
Fr
M

receiver panel (fig. 1 or 2) lights up.


1

When the battery is charged (after 3 hours


1

2
T

T
C

O
M

M
N

maximum), this LED begins to flash. 4 5 6 7 11


n
de
tt

n
po

tla
de
r

En
Ve

La

The battery can now either be removed


8 9 10
from the or left in the charger case.

In both ways, the battery will retain its full


charge. + -
if you insert the battery by mistake (+ and _
terminals marked on the housing) with Fig.1
wrong polarity into the charging case (the
battery can be wrongly inserted into the
1

2
1

2
T

T
C

O
M

M
N

case only with force), the red LED 8 4 5 6 7 11


("Verpolt/Wrong polarity") lights up
n
de
tt

n
po

tla
de
r

En
Ve

La

In this case, withdraw the battery and re- 8 9 10

insert correctly.
Note: On compact units, LED 8 is not available. In + -
these units, the green LED 9 ("Laden/Charge") does
not light up when the battery is inserted with wrong
polarity. Fig.2

612 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Maintenance
MAINTENANCE

The FW 24 radio remote-control unit is


largely maintenance-free.

You should nevertheless make sure that

- damaged rubber bellows at the switches


are immediately replaced.

- the transmitter is never exposed to the jet


of a high-pressure cleaner or to caustic
liquids.

- proper functioning of all control elements


is checked at regular intervals.

- all cables are disconnected from the


receiver when electric welding is performed
at the machine (concrete pump).

There is otherwise a risk of damage to


electronic components.

Service Manual 613


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Operation Fault Indicators


OPERATION AND FAULT INDICATORS

The light-emitting diodes indicate different operational states and malfunctions.

= ON = OFF = FLASHING

1. TRANSMITTER

START-UP/OPERATION

LED MESSAGE ACTION

Stop transmitter activated, EMERGENCY depress EMERGENCY SHUT-OFF


SHUT-OFF test required. button (LED flashing faster) and release

Stop "Multi-Control" only:


enable required depress enable button

Stop enable accepted, transmitter ready start working


for operation, no function activated
(basic position)
Stop enable not accepted, restart protection set all switches to "0" position
active

Stop one or more functions activated, machine executes control commands


transmitter sending data

MALFUNCTIONS

Stop boom functions de-actived, "STOP"


lamp lights up when joystick is moved.
select or
Stop EMERGENCY SHUT-OFF button set all switches to "0" position, unlock
actuated EMERGENCY SHUT-OFF

Stop battery empty, remaining time for replace battery


operation = 10 to 20 min.

Stop transmitter defective repair by authorized personnel only

614 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

OPERATION AND FAULT INDICATORS (Cont.)

2. RECEIVER

MC 1 EM 1 wrong charge dis- MESSAGE ACTION


MC 2 EM 2 pol. charge
valid radio data signals machine executes control
are being received commands

no reception change frequency,


choose other location

EMERGENCY SHUT- set all switches on trans-


OFF actuated mitter to "0", unlock EMER-
GENCY SHUT-OFF button.
battery being charged

battery being finished remove battery from or


leave in charger (trickle
charge)

battery inserted with insert battery correctly


wrong polarity

battery being discharged charger switches auto-


matically to normal charge
when the battery is dis-
charged

"MULTI-Control" receiver only

MC 1 EM 1 wrong MESSAGE ACTION


MC 2 EM 2 pol.
built-in control module active

required for servicing purpose only

Service Manual 615


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

616 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

C32/CPC Radio The license-free spread spectrum band goes from


902 to 928 MHz, a 26 MHz wide spectrum using
Remote the full band width. Compare that to a conven-
tional radio that uses a band only 0.03 MHz wide.

Spread Spectrum Technology Where traditional radios tune to one frequency, a


Spread Spectrum radio uses 63 different frequen-
The Schwing T45 Remote Control systems cies. It stays 20 milliseconds on any one fre-
employ frequency hopping spread spectrum tech- quency and then moves on to the next (i.e. it uses
nology to provide the optimum performance 50 different frequencies every second).
allowable under present FCC and ISC regula-
tions. This technology provides a unique perfor- On each frequency the Spread Spectrum transmit-
mance advantage compared to conventional fixed ter sends all the information it reads from the
frequency systems. The major benefits are listed switches and joysticks (both on/off and propor-
below: tional). It adds a unique transmitter address (ID)
plus an error checking code (CRC-16) to make the
Interference Free: It cannot be jammed by other link safe and secure. The Spread Spectrum
RF transmitters or extraneous noise sources. receiver thus gets 50 switch readings from the
transmitter each second, all sent on a different fre-
Coordination Free: All Schwing-spread spec- quencies.
trum transmitters are factory coded. The user does
not need to worry about which frequency the unit If you work in a radio spectrum that is 'clean', the
is operating on. It operates as if there is a unique SSP radio will function just like a traditional nar-
frequency for each unit in existence. Any number row band radio. But if someone else is operating
of these units can be operated in the same location in the same area on the same frequency, you could
at the same time. get blocked or jammed by the other radio signal
making the radio useless at that site. This will not
License Free: These radios are certified by the happen with a Spread Spectrum radio.
U.S. and Canadian governments to meet their cri-
teria for license-free operation. With Spread Spec- If interference causes trouble for the Spread Spec-
trum Technology, these radios are allowed to trum at one frequency, the Spread Spectrum radio
transmit as much power and sometimes more than quickly moves onto another frequency where the
conventional licensed products. This makes for information is likely to get through. It would take
very high performance reliable RF links through hundreds of ordinary radios at a site to block the
many types of material and over very great dis- 26MHz wide spectrum used by the SSP.
tances should the application require it.

Security: Combine the Spread Spectrum robust-


ness with the added 16-bit address space and
CRC16 error-detection code built into the data
protocol, and these units provide extremely reli-
able, error-free control.

SPREAD SPECTRUM OPERATION -


(How does a frequency hopper work?)

Service Manual 617


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Mounting the Receiver where. The mounting bracket may be bolted to the
vehicle frame, but do not allow the antenna whip
Antenna: to contact metal parts! After mounting, insert the
The receiver antenna assembly (Figure 1) consists connector end of the cable into the mating receiver
of a mounting bracket with attached coaxial cable connector and secure the cable with tie-wraps if
and a removable whip antenna. For most close required to prevent damage.
range applications (< 300') the location of the
antenna is not too critical since the receiver is sen- Figure 1. Receiver Antenna Assembly
sitive enough to pick up the signal almost any-

618 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Transmitter Operation To ensure the utmost safety, the Emergency Stop


The transmitter has been designed for the utmost switch is monitored each time during power up. In
in durability and light weight. For ease of mainte- addition, the power off switch provides an addi-
nance, it uses a readily available rechargeable tional level of safety. These switches activate dif-
MAKITA battery unit (Figure 2). In addition, a ferent mechanisms and different relays on the
number of diagnostic features have been built into receiver to ensure that a system can be shut down.
it.
Figure 2. MAKITA battery

Service Manual 619


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
1. RADIO TRANSMITTER ON/OFF SWITCH
If you have depressed and released the E-
To ensure safe operation, the E-Stop switch on the Stop button and both the stop light and
transmitter is checked each time the unit is pow- power light are flashing, you have a
ered up (Figure 3). In addition, all functions must function turned on.
be off or the unit will not power up.
You must honk the horn to clear the E-
(ON) The ON or start up sequence is as follows: Stops and power the E-Stop solenoids.
Ensure all functions are turned OFF.
(OFF) Turning off the Transmitter will cause the
Turn Power switch ON, the Stop light will receiver to go into an E-Stop mode and all
flash slowly until the E-Stop is depressed functions will stop.
and released. If the E-Stop is depressed
on power up, the light will flash rapidly Figure 3. T45 Radio Remote
until it is released.

Radio Transmitter On/Off


#2 Boom Motor Stop/Start Power LED Communication (Not on cable remotes) Boom Control
Speed Control LED
E-Stop LED On/Off
Left Joystick
Right Joystick

Throttle Up/Down Agitator Vibrator


Horn/Reset
Forward/Off/Reverse Off/Automatic
Emergency Stop Concrete Pump Stroke Limiter
Forward/Off/Reverse

620 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
2. POWER LED

The power LED indicates the status of the battery.

(OFF) Battery OK (with communication LED on


or flashing or battery dead with
all LED s off.

(FLAHSING)
Battery low.

3. COMMUNICATION LED

The Power light indicates the status of the trans-


mitter.

(ON) Transmitter on and ready to function

(OFF) Transmitter turned off or no battery


installed

(FLASHING)
Function turned on.

4. E-STOP LED

Depressing the E-Stop will remove power to all


outputs from controller and open the dump valves
located on the E-Stop manifold

(ON) If this light is on, it indicates the E-Stop


button is depressed.

(OFF) Unit is operational, E-Stop clear.

(FLASHING)
E-Stop still active due to power up
sequence or function On.

5. EMERGENCY STOP PUSH BUTTON

All outputs are disabled, E-Stop manifold sole-


noids are de-energized.

Service Manual 621


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Remote Radio Controller have the numbers 1 & 8 printed above it. The
second row SW2 will have 9 & 16 printed above
DIP SWITCH SETTINGS it. In order for the radio to operate, the switches
must be set the same as the decal. EXAMPLE: if
Each T45 transmitter is supplied with a unique ID the punched hole in the decal for SW1-1 is a 1
code (Figure 4). This code is marked on the label (Figure 7), then the corresponding dip switch must
located on the handle mounting plate, along with be set to ON. If the punched hole in the decal for
the radio serial number. The receiver must be set SW1-1 is a 0, then the corresponding dip switch
to match this code. To match the settings, the must be set to OFF. After all switches are set, re-
power to the receiver must be off. power the receiver.

On the cover of the HOPLINK (located in the


receiver) (Figure 5), you will see the dip switches
(Figure 6). In the box marked ID, there are two
rows of switches. The first row is SW1, it will Figure 4. ID Code

622 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
Please note that the HOPLINK units recalculate its *** Make sure that switch #5 of the MODE dip
spread spectrum sequence every time the ID is switch (SW3) is on, all others must be off. SW3
changed -- be patient, it may take up to 5 seconds will also have 1 & 8 printed below it, SW3 is
on the first power up after an ID change before the located closest to the ribbon cable connection.
receiver goes operational.
Figure 5. Hoplink

Figure 6. Dip Switches, Radio Transmitter, and


Receiver

Service Manual 623


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

WARNING
Do not operatre this
machine without
training. Understand
the warnings in safety
manuals and on decals.
ASSY-326-08
SERIAL NUMBER 70136 ISSUE 2

ID CODE 1 1
SW 1: SW 2:
L1393-01 0 0

Figure 7. Dip Switch

0 = Off
ID
1 8
1 = On

SW1

1 2 3 4 5 6 7 8
9 16
SW2

SW3 1 2 3 4 5 6 7 8
Set all switches
to 00001000

1 2 3 4 5 6 7 8
1 8
MODE

624 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
Troubleshooting Table: Transmitter LED s
l = LED on / = LED flashing / X = LED flashing faster / = LED off

+
STOP
LED LED LED DESCRIPTION ACTION
Battery Dead; Power Off Charge Battery; Turn Power
On
E-Stop Test Press E-STOP button

X E-Stop Test Part Two Release E-STOP Button


Not all functions off on E-Stop Set all functions off
release
/ l Valid Data, all functions OK, continue as required

/ Valid Data, 1 + functions on OK, continue as required

/ / l Emergency Stop E-STOP Button Pressed

/ Low Battery Replace/Recharge Battery


X Module failure: Joystick Cycle Power - if not
remedied, call service
X Module failure: Radio Cycle Power - if not
remedied, call service

Service Manual 625


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

626 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Omnex Radio Con-


trol System
1. Introduction
The Comfort Concrete Pump Remote Control Sys-
tem consists of a T47 cable, a T45 radio transmit-
ter, and a custom receiver (grey box). The cable
control has a North American standard 10 pin Sine
connector, and the receiver has a European stan-
dard 12 pin Burndy connector. Both the cable unit
and the receiver communicate to the Comfort Con-
trol system via its standard CAN-Bus interface for
remote control.

This manual describes considerations that should


be taken during installation and documents the
information displayed by the lights and the set-
tings available.

This issue of the manual describes the operation


for the cable unit with Issue 2 of the AFRM-1525-
02 software, the radio transmitter with Issue 3 of
the AFRM-1236-06 software, and the receiver
interface board with Issue 3 of the AFRM-1530-01
software.

Service Manual 627


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

2. Physical Mounting
The receiver should be mounted with the connec-
tors down and in a location that allows the enclo-
sure door to be opened conveniently for access to
the inside.

Shock mounts must be used to mount the enclo-


sure! Under no circumstance should the enclosure
be directly bolted to the machine. The picture
below illustrates how the shock mounts should be
installed:

3. Considerations for
Electrowelding
The high currents and voltages employed by elec-
trowelding can damage the electronics in the Com-
fort Concrete Pump Remote Control System. If
electrowelding must be performed after the Con-
trol System has been installed, observe the follow-
ing precautions to reduce the risk of damage:
Unplug the connectors to the receiver and
The enclosure is sealed and has a NEMA-4 rating. cable units.
When installing, ensure that nothing is done to Do not strike an arc close to the enclosure.
compromise the watertightness of the enclosure.
When performing maintenance, it may be neces-
sary to gain access to the inside of the enclosure;
take care to close the door securely when you are
done.

The antenna should be mounted pointing upward


and should be as high as possible, preferably with
a large metal surface below it but without metal
above or to the side. The antenna must be mounted
on the outside of the machine; do not mount it
inside the cab or in a tool box. Assemble the
antenna as shown below, and turn (finger-tight
only) the connector onto the matching receptacle
on the receiver until it locks.

628 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

4. Receiver Connector table specifies the assignment of each pin, with


corresponding connectors on the TPCB-1527-01
Assignments circuit board for reference.
The receiver has a 12-pin Burndy connector for
power and all output functions. The following

TPCB-1527-01
Function Burndy Conn. Pin
Conn.
Receiver Power (24V Bat.) C J7-6
Receiver Ground D J7-5
E-Stop Contact 1A E J7-4
E-Stop Contact 1B F J7-2
E-Stop Contact 2A G J7-3
E-Stop Contact 2B H J7-1
Hydraulic Enable Valve Output (drives
J J6-3
power out when boom function on)
CAN-Bus High K J6-1
CAN-Bus Low L J6-2

The Receiver Power Input (C) supplies the elec-


tronics, the E-Stop Relays, and the Hydraulic
Enable Output. The total power required is 0.1A +
0.1A + 1.0A = 1.2A. The Ground pin (D) should
go to a low-impedance ground point either on the
vehicle chassis or at the battery or fuse box.

Service Manual 629


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

5. Cable Unit Connector


Assignments
The Cable Unit has a 10-pin Sine connector for
power and all output functions. The following
table specifies the assignment of each pin, with
corresponding internal connectors for reference.

Internal
Function Sine Conn. Pin
Connection
Cable Unit Ground A TPCB-1605-01 J1-4
Cable Unit Power (24V Bat.) B TPCB-1605-01 J1-2
E-Stop Contact 1A C Contact Block 1
E-Stop Contact 2A D Contact Block 2
Hydraulic Enable Valve Output (drives
E PCB-I24-MC DB15-4
power out when boom function on)
CAN-Bus High G PCB-I24-MC DB15-6
CAN-Bus Low H PCB-I24-MC DB15-7
E-Stop Contact 1B J Contact Block 1
E-Stop Contact 2B K Contact Block 2

The Cable Unit Power Input (B) supplies the elec-


tronics and the Hydraulic Enable Output. The total
power required is 0.1A + 1.0A = 1.1A. The
Ground pin (A) should go to a low-impedance
ground point either on the vehicle chassis or at the
battery or fuse box.

6. Fuses
There is one replaceable fuse on the receiver
TPCB-1527-01 circuit board. It is an American
automotive cartridge (ATO) style fuse; F2 should
be 5A (brown color code). It provides power to
the E-Stop relays. The other fuses used are self-
resetting. They need the input power removed in
order to reset after a fault is corrected. The
Hydraulic Enable Output Supply has no internal
protection in either the receiver or the cable unit.

630 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

7. Operations section).
This section describes how the Comfort Concrete
Pump Remote Control System operates. It details 6. BOOM ENABLE
the operation of the lights and special consider- -on =boom function on - hydraulic enable out-
ations. put active
-off=boom functions off - hydraulic enable
7.1 Receiver output off
The receiver is operational when power is applied.
The receiver is designed to be a plug in replace- 7. E-STOP
ment of the German unit. The Hydraulic Enable -on=Receiver in E-Stop mode, E-Stop contacts
Output is capable of supplying 1 Amp. and is open.
short-circuit protected. It has a one-second hold -off=Receiver in operating mode, E-Stop con-
over after all boom functions are released. tacts closed.
-flashing (with RECEIVER MICRO STATUS
on) = restart blocking
7.1.1 Receiver Lights - General Function -other=error condition - see next section
The receiver lights are defined according to the
list below. 7.1.2 Receiver Lights - Error Conditions
The receiver lights also indicate error condi-
1. POWER-on=normal tions as defined according to the list below.
-off=no power, input power fuse blown or power
supply fault on TPCB-1527-01. 1. RECEIVER MICRO STATUS flashing con-
tinuously on first time power up of micro.
2. RECEIVER MICRO STATUS (only will occur if new micro. installed).
-on=normal Cause: CONFIG register programmed.
-off=micro. on TPCB-1527-01 failed Resolution: Cycle power to continue.
-other =error condition - see next section
2. RECEIVER MICRO STATUS flashing once
3. COM LINK -on=radio communications link per second on power up
with transmitter Cause: Software initialization failed.
-off=no link with transmitter Resolution: Cycle power. If not cleared, CPU
or EPROM circuitry is faulty.
4. SIGNAL STRENGTH 3. RECEIVER MICRO STATUS and E-STOP
-on or mostly on =good link with transmitter flashing continuously together.
-mostly off =poor link with transmitter Cause: E-Stop Drive circuitry fault detected.
-off= no data from transmitter Resolution: If COM LINK is on, HopLink
module is faulty. Otherwise, cycle power. It if
5. CAN-BUS MICRO STATUS recurs, TPCB-1527-01 board is faulty.
-blinking continuously=normal when receiv-
ing data 4. RECEIVER MICRO STATUS blinks off
-blink every 2 seconds=no CANBUS link to three times with a 2-second interval.
Comfort but receiver Cause: HopLink failure detected.
interface OK Resolution: Check ribbon cable to HopLink.
-off=normal when E-Stop is on. When E-Stop Check that HopLink ON light is on. Check
is off or blinking: CANBUS micro. failed or power to HopLink. If ON light off and power
interface failed (check error conditions in next is good, then HopLink is faulty. In all other

Service Manual 631


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
cases, the problem could be the HopLink, rib- 7. RECEIVER MICRO STATUS blinks off
bon cable, or interface board. four times with a 2-second interval.
Cause: Communications fault detected to
5. RECEIVER MICRO STATUS blinks off CANBUS board.
two times with a 2-second interval. Resolution: Check wiring between boards.
Cause: Interface to CANBUS board has no Otherwise fault could be on either board.
response.
7.1.3 Operator Adjustments:
Resolution: Check wiring between boards.
The ramping for the Boom (2) functions on the
Otherwise fault could be on either board.
transmitter can be dynamically adjusted using the
6. RECEIVER MICRO STATUS blinks off DIP switches in the receiver from 0.1 second to
one time with a 2-second interval. 2.3 seconds in several steps. The ramp up time is
Cause: CANBUS error detected by CANBUS the time for the signal to go from OFF to the full
board. ON setting (100%). The ramp down time is the
Resolution: Check CANBUS interface wiring time for the signal to from the full ON setting
(external and internal). Internal connections (100%) to OFF. If the Boom (2) switches have
are from the CANBUS board through the 4 pin been set to a lower ON value, the ramp times to
headers on the TPCB-1527-01 board to the that value will be proportionately less. The follow-
ing charts outline the settings available.
output connector on the box.

Time (sec.) DIP Switch #1 DIP Switch #2 DIP Switch #3

0.1 off off off


0.25 off off on
0.5 off on off
0.65 off on on
0.9 on off off
1.1 on off on
1.5 on on off
2.3 on on on

Time (sec.) DIP Switch #4 DIP Switch #5 DIP Switch #6

0.1 off off off


0.25 off off on
0.5 off on off
0.65 off on on

632 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

Time (sec.) DIP Switch #4 DIP Switch #5 DIP Switch #6

0.9 on off off


1.1 on off on
1.5 on on off
2.3 on on on

7.2 Transmitter
7.2.1 Transmitter Lights
The transmitter lights are similar to all the other
transmitter products supplied to SAI. The following Troubleshooting Table: Transmitter LED s
chart details their operation.

= LED on / = LED flashing / X = LED flashing faster / = LED off

+
STOP
LED LED LED DESCRIPTION ACTION
Charge Battery; Turn Power
Battery Dead; Power Off On
E-Stop Test Press E-STOP button
X E-Stop Test Part Two Release E-STOP Button
N/A X E-Stop Failed Set all functions off
Not all functions off on E-Stop
N/A OK, continue as required
release
N/A Valid Data, all functions OK, continue as required
N/A Valid Data, 1 + functions on E-STOP Button Pressed
N/A Emergency Stop Replace/Recharge Battery
Boom Function on when Boom Cycle Power - if not
N/A
disabled remedied, call service
Cycle Power - if not
Low Battery
NORMAL NORMAL remedied, call service
Cycle Power - if not
X Module failure: Joystick remedied, call service
Cycle Power - if not
X Module failure: Radio remedied, call service
Cycle Power - if not
Module failure: Micro remedied, call service

Service Manual 633


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
7.2.2 Operator Controls: (rabbit) setting. The Boom (2) speed switch selects
The position of the operator controls is as per three Boom (2) speeds in each of the Boom Enable
Schwing America and is the same as the units sup- settings. The speed switch settings are as per the
plied out of Germany. The Boom Enabled Slow table below.
(snail) setting cuts all boom control outputs in half
(max.=50%) compared to the Boom Enabled Fast
Boom 2 Speed Switch Boom Enable Fast Boom Enable Slow
I 25% 13%
II 50% 25%
II 100% 50%

7.3 Cable Unit tions since the Comfort System does not supply E-
Stop status information to the cable unit. The fol-
7.3.1 Cable Unit Lights
lowing chart details the operation of the lights.
The cable unit lights are unique. That is, they do
not act the same as other cable units supplied to
SAI. The STOP light is used only for error condi- Troubleshooting Table: Transmitter LED s

= LED on / = LED flashing / X = LED flashing faster / = LED off

+
STOP
LED LED LED DESCRIPTION ACTION
No Power Connect Cable, check fuse
Valid Data, all function off OK, continue as required
Valid Data, 1 + functions on OK, continue as required
Boom Function on with Boom Enable Boom to activate
Disabled Boom Function.
Function on after E-Stop release Reset all function to neutral
Cycle Power - if not
Internal Interface Failure remedied internal wiring or
board faulty
Check cable/truck wiring -
CAN-Bus Interface Failure otherwise - internal I24-MC
board or wiring faulty*
Cycle Power-if not
remedied joystick faulty
Joystick Failure
(LED on faulty joystick ON
when powered)

634 Service Manual


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio
7.3.2 Operator Controls: (rabbit) setting. The Boom (2) speed switch selects
The position of the operator controls is as per three Boom (2) speeds in each of the Boom Enable
Schwing America and is the same as the units sup- settings. The speed switch settings are as per the
plied out of Germany. The Boom Enabled Slow table below.
(snail) setting cuts all boom control outputs in half
(max.=50%) compared to the Boom Enabled Fast

Boom 2 Speed Switch Boom Enable Fast Boom Enable Slow


I 25% 13%
II 50% 25%
II 100% 50%

The Boom (2) Ramp speed is fixed at 1.0-second 8.2 Receiver TPCB-1527-01 Board
ramp up to 100% and 0.25-second ramp down The TPCB-1527-01 board is used in the receiver to
from 100%. provide the interface between the I24-MC board
and the HopLink module. The MAIN BYPASS
8. Troubleshooting Information jumper (JPI) must have a shorting block on pins 2
to 3 (position nearest the edge of the board) in
This section includes information on the circuit
order for the E-stop Relays to work. The on-board
boards in the receiver and cable units, including a
LEDs are defined as follows:
description of on-board LEDs.
CR3 (MICRO PWR) = 5V Power to micropro-
8.1 I24-MC Board cessor.
The I24-MC board is used in both the receiver and CR4 = Relay Drive Power through 5A fuse -
the cable units to provide the CAN-Bus interface F2.
and the Hydraulic Enable Output to the Comfort D6 (Top Red LED) = HopLink E-Stop Relay
Control System. The on-board LEDs are defined Drive OFF.
as follows: D4 (Bottom Red LED) = TPCB-1527-01 E-
LED 1 = CAN-BUS MICRO STATUS Stop Relay Drive OFF.
LED 2 = BOOM ENABLE
LED 3 = CAN-Bus Link Failure
LED 4 = Internal Error (Hydraulic Enable Out-
put shorted to supply)
LED 5 = Internal Diagnostic Mode

Service Manual 635


HOME PRINT
SERVICE TRAINING
Remote Control Cable/Radio

636 Service Manual


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Conversion Charts
METRIC TO AMERICAN AND VICE-VERSA
Abbreviation TO CONVERT MULTIPLY BY TO OBTAIN Abbreviation
A atmospheres 1.0132739 bars b
A atmospheres 1.0333 kilograms/sq. centimeter kgs./cm2
A atmospheres 14.7 pounds/sq. inch PSI
b bars 0.9869 atmospheres A
b bars 1 deka newtons daN
b bars 0.98069 kilograms/sq. centimeter kgs/cm2
b bars 14.5 pounds/sq. inch PSI
btu british thermal units 778.16 foot-pounds ft-lbs
btu/min british thermal units/min. .000393 horsepower hp
btu/min british thermal units/min. 0.01757 kilowatts kw
cm centimeters .03281 feet ft
cm centimeters 0.3937 inches in
cm centimeters 10. millimeters mm
cm centimeters 0.01 meters m
cc or cm3 cubic centimeters 0.001 liters l
cc or cm3 cubic centimeters 0.000001 cubic meters m3
cc or cm3 cubic centimeters 0.00003531 cubic feet ft3
cc or cm3 cubic centimeters 0.061 cubic inches in3
ft3 cubic feet 28,320. cubic centimeters cc or cm3
ft3 cubic feet 1,728. cubic inches in3
ft3 cubic feet 0.03704 cubic yards yd3
ft3 cubic feet 7.48052 gallons (U.S. liquid) G
in3 cubic inches 16.39 cubic centimeters cc or cm3
in3 cubic inches 0.0005787 cubic feet ft3
in3 cubic inches 0.00002143 cubic yards yd3
in3 cubic inches 0.004329 gallons (U.S. liquid) G
in3 cubic inches 0.01639 liters l
m3 cubic meters 1,000,000. cubic centimeters cc or cm3
m3 cubic meters 35.31 cubic feet ft3
m3 cubic meters 1.308 cubic yards yd3
m3 cubic meters 1,000. liters l
m3 cubic meters 264.2 gallons (U.S. liquid) G
m3/hr cubic meters/hour 1.308 cubic yards/hour yd3/hr
yd3 cubic yards 764,600 cubic centimeters cc or cm3
yd3 cubic yards 27. cubic feet ft3
yd3 cubic yards 46,656. cubic inches in3
yd3 cubic yards 764.526 liters l
yd3 cubic yards 202. gallons (U.S. liquid) G
3
yd /hr cubic yards/hour 0.764526 cubic meters/hour m3/hr
daN dekanewtons 1. bars b
daN dekanewtons 14.50377 pounds/sq. inch PSI
ft feet 30.48 centimeters cm
ft feet 0.0003048 kilometers km
ft feet 0.3048 meters m
ft feet 304.8 millimeters mm
ft-lb foot-pounds 0.001286 british thermal units btu
ft-lb foot-pounds 0.1383 kilogram.-meters kg-m
ft-lb foot-pounds 1.356 newton-meters Nm
Metric Conversion01.eps

Service Manual 637


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Abbreviation TO CONVERT MULTIPLY BY TO OBTAIN Abbreviation


ft-lb/sec foot-pounds/second 0.001818 horsepower hp
ft-lb/sec foot-pounds/second 0.001356 kilowatts kw
G gallons 3,785. cubic centimeters cc or cm3
G gallons 0.1337 cubic feet ft3
G gallons 231. cubic inches in3
G gallons 0.003785 cubic meters m3
G gallons 0.004951 cubic yards yd3
G gallons 3.785 liters l
N/A gallons (imp.) 1.20095 U.S. gallons G
G gallons (U.S.) 0.83267 imperial gallons N/A
N/A gallons of water 8.337 pounds of water N/A
g grams 0.001 kilograms kg
g grams 0.03527 ounces (avdp.) oz
hp horsepower 42.44 british thermal units/min. btu/min
hp horsepower 33,000. foot-pounds/min. ft-lbs/min
ps horsepower (metric) 0.9863 horsepower hp
hp horsepower 1.014 horsepower (metric) ps
hp horsepower 0.7457 kilowatts kw
in inches 2.540 centimeters cm
in inches 25.4 millimeters mm
kg kilograms 2.2046 pounds lb
kg kilograms 0.001 metric tons N/A
kg/cm2 kilograms/square centimeter 0.9678 atmospheres A
kg/cm2 kilograms/square centimeter 0.9807 bars b
kg/cm2 kilograms/square centimeter 14.22 pounds/square inch PSI
kg/m2 kilograms/square meter 0.00009807 bars b
kw kilowatts 56.92 brit. thermal units/min. btu/min
kw kilowatts 1.341 horsepower hp
l liters 1000 cubic centimeters cc or cm3
l liters 61.02 cubic inches in3
l liters 0.001 cubic meters m3
l liters 0.001308 cubic yards yd3
l liters 0.2642 gallons (U.S. liquid) G
m meters 3.281 feet ft
m meters 39.37 inches in
m meters 1.094 yards yd
m microns 0.000001 meters m
mm millimeters 0.003281 feet ft
mm millimeters 0.03937 inches in
mm millimeters 0.001 meters m
N newtons 0.2248 pounds lb
Nm newton meters 8.850252 inch-pounds in-lbs
Nm newton meters 0.7375621 foot-pounds ft-lbs
oz ounces 28.3 grams g
oz ounces 0.0625 pounds lb
lb pounds 453.597 grams g
lb pounds 4.4484552 newtons N
lb pounds .4536 kilograms kg
lb pounds 16 ounces oz
lb-ft pound-feet 0.1383 meter-kilograms m-kg
PSI pounds/square inch 0.06804 atmospheres A
PSI pounds/square inch 0.06895 bars b
Metric_Conversion02.eps

638 Service Manual


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Abbreviation TO CONVERT MULTIPLY BY TO OBTAIN Abbreviation

PSI pounds/square inch 0.0703 kilograms/sq. centimeter kg/cm2


cm2 square centimeters 0.155 square inches in2
in2 square inches 6.4516 square centimeters cm2
in2 square inches 645.163 square millimeters mm2
in2 square inches 0.0007716 square yards yd2
m2 square meters 10.7639 square feet ft2
mm2 square millimeters 0.00155 square inches in2
N/A tons (metric) 1000 kilograms kg
N/A tons (metric) 2204.6 pounds lb
N/A tons (metric) 1.1023 tons (short) (U.S.) T
T tons (short) (U.S.) 0.907194 tons (metric) N/A
w watts 0.05688 british thermal units/min. btu/min
w watts 44.27 foot-pounds/min. ft-lb/min
w watts 0.0013405 horsepower hp
w watts 0.001 kilowatts kw
yd yards 0.9144 meters m

Metric_Conversion03.eps

Service Manual 639


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

CONVERSION FORMULAS - TO MILLIMETERS FROM INCHES: MULTIPLY INCHES BY 25.4


- TO INCHES FROM MILLIMETERS: MULTIPLY mm BY 0.03937
MILLIMETERS 0 10 20 30 40 50 60 70 80 90 100 mm

INCHES 0 1/2" 1" 2" 3" 4"

INCHES INCHES
FRACTIONS DECIMALS
mm FRACTIONS DECIMALS
mm
0.00004 0.0010 0.13780 03.5000
0.00039 0.0100 9/64 0.14063 03.5719
0.00079 0.0200 0.15000 03.8100
0.00100 0.0250 5/32 0.15625 03.9688
0.00118 0.0300 0.15748 04.0000
0.00157 0.0400 11/64 0.17188 04.3656
0.00197 0.0500 0.17500 04.4450
0.00200 0.0510 0.17717 04.5000
0.00236 0.0600 3/16 0.18750 04.7625
0.00276 0.0700 0.19685 05.0000
0.00300 0.0762 0.20000 05.0800
0.00315 0.0800 13/64 0.20313 05.1594
0.00354 0.0900 0.21654 05.5000
0.00394 0.1000 7/32 0.21875 05.5562
0.00400 0.1016 0.22500 05.7150
0.00500 0.1270 15/64 0.23438 05.9531
0.00600 0.1524 0.23622 06.0000
0.00700 0.1778 1/4 0.25000 06.3500
0.00787 0.2000 0.25591 06.5000
0.00800 0.2032 17/64 0.26563 06.7469
0.00900 0.2286 0.27500 06.9850
0.00984 0.2500 0.27559 07.0000
0.01000 0.2540 9/32 0.28125 07.1438
0.01181 0.3000 0.29528 07.5000
1/64 0.01563 0.3969 19/64 0.29688 07.5406
0.01575 0.4000 0.30000 07.6200
0.01969 0.5000 5/16 0.31250 07.9375
0.02000 0.5080 0.31496 08.0000
0.02362 0.6000 21/64 0.32813 08.3344
0.02500 0.6350 0.33465 08.5000
0.02756 0.7000 11/32 0.34375 08.7312
0.02950 0.7500 0.35000 08.8900
0.03000 0.7620 0.35433 09.0000
1/32 0.03125 0.7938 23/64 0.35938 09.1281
0.03150 0.8000 0.37402 09.5000
0.03543 0.9000 3/8 0.37500 09.5250
0.03937 1.0000 25/64 0.39063 09.9219
0.04000 1.0160 0.39370 10.0000
3/64 0.04687 1.1910 0.40000 10.1600
0.04724 1.2000 13/32 0.40625 10.3188
0.05000 1.2700 0.41339 10.5000
0.05512 1.4000 27/64 0.42188 10.7156
0.05906 1.5000 0.43307 11.0000
0.06000 1.5240 7/16 0.43750 11.1125
1/16 0.06250 1.5875 0.45000 11.4300
0.06299 1.6000 0.45276 11.5000
0.06693 1.7000 29/64 0.45313 11.5094
0.07000 1.7780 15/32 0.46875 11.9062
0.07087 1.8000 0.47244 12.0000
0.07500 1.9050 31/64 0.48438 12.3031
5/64 0.07813 1.9844 0.49213 12.5000
0.07874 2.0000 1/2 0.50000 12.7000
0.08000 2.0320 0.51181 13.0000
0.08661 2.2000 33/64 0.51563 13.0969
0.09000 2.2860 17/32 0.53125 13.4938
0.09055 2.3000 0.53150 13.5000
3/32 0.09375 2.3812 35/64 0.54688 13.8906
0.09843 2.5000 0.55000 13.9700
0.10000 2.5400 0.55118 14.0000
0.10236 2.6000 9/16 0.56250 14.2875
7/64 0.10937 2.7781 0.57087 14.5000
0.11811 3.0000 37/64 0.57813 14.6844
1/8 0.12500 3.1750 0.59055 15.0000
Conversion_Formulas01.eps

640 Service Manual


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

CONVERSION FORMULAS - TO MILLIMETERS FROM INCHES: MULTIPLY INCHES BY 25.4


- TO INCHES FROM MILLIMETERS: MULTIPLY mm BY 0.03937
MILLIMETERS 0 10 20 30 40 50 60 70 80 90 100 mm

INCHES 0 1/2" 1" 2" 3" 4"

INCHES INCHES
FRACTIONS DECIMALS
mm FRACTIONS DECIMALS
mm
19/32 0.59375 15.0812 1.57480 040.00
0.60000 15.2400 1.65354 042.00
39/64 0.60938 15.4781 1 3/4 1.75000 044.45
0.61024 15.5000 1.77170 045.00
5/8 0.62500 15.8750 1.88976 048.00
0.62992 16.0000 1.96850 050.00
41/64 0.64063 16.2719 2 2.00000 050.80
0.64961 16.5000 2.04724 052.00
0.65000 16.5100 2.16540 055.00
21/32 0.65625 16.6688 2.20472 056.00
0.66929 17.0000 2 1/4 2.25000 057.15
43/64 0.67188 17.0656 2.36220 060.00
11/16 0.68750 17.4625 2 1/2 2.50000 063.50
0.68898 17.5000 2.51968 064.00
0.70000 17.7800 2 3/4 2.75000 069.85
45/64 0.70313 17.8594 2.83464 072.00
0.70866 18.0000 2.95280 075.00
23/32 0.71875 18.2562 3 3.00000 076.20
0.72835 18.5000 3.14960 080.00
47/64 0.73438 18.6531 3 1/2 3.50000 088.90
0.74803 19.0000 3.54330 090.00
3/4 0.75000 19.0500 3.93700 100.00
49/64 0.76563 19.4469 4 4.00000 101.60
0.76772 19.5000 4.33070 110.00
25/32 0.78125 19.8438 4 1/2 4.50000 114.30
0.78740 20.0000 4.72440 120.00
51/64 0.79688 20.2406 5 5.00000 127.00
0.80000 20.3200 5.51180 140.00
0.80709 20.5000 5.90550 150.00
13/16 0.81250 20.6375 6 6.00000 152.40
0.82677 21.0000 6.29920 160.00
53/64 0.82813 21.0344 7.08660 180.00
27/32 0.84375 21.4312 7.87400 200.00
0.84646 21.5000 8 8.00000 203.20
0.85000 21.5900 8.66140 220.00
55/64 0.85938 21.8281 9.44880 240.00
0.86614 22.0000 9.84250 250.00
7/8 0.87500 22.2250 10 10.00000 254.00
0.88583 22.6219 10.23620 260.00
57/64 0.89063 22.8600 11.02360 280.00
0.90000 23.0000 11.81100 300.00
0.90551 23.0188 12 12.00000 304.80
29/32 0.90625 23.0188 12.59840 320.00
59/64 0.92188 23.4156 13.38580 340.00
0.92520 23.5000 13.77950 350.00
15/16 0.93750 23.8125 14.17320 360.00
0.94488 24.0000 14.96060 380.00
0.95000 24.1300 15.74800 400.00
61/64 0.95313 24.2094 16 16.00000 406.40
0.96457 24.5000 17.71650 450.00
31/32 0.96875 24.6062 19.68500 500.00
0.98425 25.0000 20 20.00000 508.00
63/64 0.98438 25.0031 23.62200 600.00
1 1.00000 25.4000 24 24.00000 609.60
1.06299 27.0000 36 36.00000 914.40
1.10240 28.0000 39.37000 1000.00
1.18110 30.0000 48 48.00000 1219.20
1 1/4 1.25000 31.7500 60 60.00000 1524.00
1.29921 33.0000 72 72.00000 1828.80
1.37800 35.0000 78.74000 2000.00
1.41732 36.0000 96 96.00000 2438.40
1 1/2 1.50000 38.1000 118.11000 3000.00
1.53543 39.0000 196.85000 5000.00
Conversion_Formulas02.eps

Service Manual 641


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Fluid Power Formulas


The following represent some of the formulas commonly used when working with concrete pumps
and related equipment. No attempt has been made to list all possible applications for these formulas.

*The diagram below relates 3 formulas regarding force, pressure, and area:

U.S.
F = FORCE (in pounds) (lb)
P = PRESSURE (in pounds per square inch) (P.S.I.)
F F=PxA
A = AREA (in square inches) (in2)
P = F/A
P A METRIC
A = F/P
F = FORCE (in kilograms) (Kg)
P = PRESSURE (in kilograms per square centimeter) (Kg/cm2)
A = AREA (in square centimeters) (cm2)

*The following relates to power required by a hydraulic system

GENERAL
QxP Q = FLOW RATE (unit of volume per time period)
POWER =
CONSTANT P = PRESSURE (unit of force per unit of area)

U.S.
HP = HORSEPOWER
GPM x PSI
HP = GPM = GALLONS PER MINUTE
1714
PSI = POUNDS PER SQUARE INCH
1714 = KNOWN CONSTANT

METRIC
KW = KILOWATTS
LPM x BAR LPM = LITERS PER MINUTE
KW =
600
BAR = METRIC UNIT OF PRESSURE
600 = KNOWN CONSTANT
The above state only the power drawn by the system, and make no allowance for the efficiency of the components.
To determine the power needed to drive a specific system, the answer to the formula must be divided by the efficiency factor.

QxP
REQUIRED POWER = E = EFFICIENCY FACTOR
CONSTANT
E
The rule of thumb for figuring efficiencies is: E = 0.7 for internal combustion engines, or E = 0.85 for electric motors.
It would be the same in Metric as in U.S. calculations.

*The following relates to theoretical flow rates by a hydraulic pump


RPM x PUMP DISPLACEMENT GENERAL
Q=
CONVERSION FACTOR

RPM x CUBIC INCHES/REV. U.S. 231 = number of cubic inches in 1 gallon


Q (in GPM) =
231

RPM x CUBIC CENTIMETERS/REV. METRIC 1000 = number of cubic centimeterss in 1 liter


Q (in liters/min.) =
1000

FluidPowerFormulas01.eps

642 Service Manual


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Torque and Horsepower relations:

T=
P x CONSTANT GENERAL
RPM T = TORQUE

T x RPM P = POWER
P=
CONSTANT RPM = REVOLUTIONS PER MINUTE

P x CONSTANT
RPM =
T

HP x 5252 U.S.
T=
RPM T = TORQUE (in foot-pounds) (ft-lb)
T x RPM HP = HORSEPOWER
HP =
5252 5252 = K NOWN CONSTANT

HP x 5252
RPM =
T

KW x 9543 METRIC
T=
RPM T = TORQUE (in newton-meters) (Nm)
T x RPM KW = KILOWATTS
KW =
9543 9543 = K NOWN CONSTANT
KW x 9543
RPM =
T

Torque and Displacement relations:


U.S.
T = TORQUE (in foot-pounds) (ft-lb)

T=
DxP D = DISPLACEMENT (in cubic inches per revolution) (in3/rev.)
24 P = PRESSURE (in pounds per square inch) (PSI)
= Pi (3.1415927)

Finding pressure on concrete


U.S.
Rubber
Ram PC = PRESSURE ON THE CONCRETE (In PSI)
Piston
Rod PA = PISTON AREA (In square inches) (in2)
(PA) (RRA)
RA = ROD AREA (In square inches) (in2)
(RSA) (RA) RSA = ROD SIDE AREA (In square inches) (in2)
RRA = RUBBER RAM AREA (In square inches) (in2)
PA x MAX. P MAX. P = MAXIMUM HYDRAULIC OIL PRESSURE (In PSI)
(on piston side) PC =
RRA (relief valve setting)

EXAMPLE: Piston diameter 4.72 inches (120mm), Rod diameter 3.15


RSA x MAX. P inches (80mm), Rubber ram diameter 9.05 inches (230mm), relief valve
(on rod side) PC =
RRA set at 4,350 PSI (300 bar).
Area of the piston = 17.5 in2. Area of the rod = 7.79 in2.
Area of the rubber ram = 64.33 in2.
RSA = PA - RA
(17.5 - 7.79) x 4350
(on rod side) PC = (on rod side) PC = 656.6 PSI
64.33

FluidPowerFormulas02.eps

Service Manual 643


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Torque Specifications has a dial scale. If no dial scale is present, the bolts
must be torqued to within 6% of the requirement. For
The following charts show the tightening torques example, a bolt to be torqued to a 200-lb requirement
specified for the bolts used on Schwing equipment. The must be within the range of 208192 ft-lb for a dial
charts are to be followed unless a different torque scale torque wrench. Schwing equipment uses two
specification is indicated for a particular procedure. different types of bolts, one black/yellow chromated
A torque wrench must be calibrated to within 1% of its finish and one Dacromet finish.
indicated value throughout its range. Bolts must be
torqued to within 4% of the requirement if the wrench

644 Service Manual


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

I. APPLICABLE TO:
A. 500 Geomet fasteners, nuts, and washers
B. Black or yellow-chromate fasteners, nuts, and washers (using Cu or MOS2 mounting paste)

Coarse-Pitch Thread Fine-Pitch Thread


*Tightening Torque *Tightening Torque

Property Class Property Class


Designation

Designation
8.8 10.9 12.9 8.8 10.9 12.9
Thread

Thread
Nm ft lb Nm ft lb Nm ft lb Nm ft lb Nm ft lb Nm ft lb

M 4 X 0.7 2.2 1.6 3.2 2.4 3.8 2.8 M 8X1 20 15 28 21 33 24

M 5 X 0.8 4.3 3.2 6.4 4.7 7.5 5.5 M 10 X 1 40 29 57 42 68 50

M 6X1 7.5 5.5 10.8 8.0 12.6 9.3 M 10 X 1.25 37 27 55 41 64 47

M 8 X 1.25 18 13 27 20 31 23 M 12 X 1.25 67 49 100 74 115 85

M 10 X 1.5 36 27 53 39 62 46 M 12 X 1.5 65 48 95 70 110 81

M 12 X 1.75 62 46 90 66 108 80 M 14 X 1.5 105 77 155 114 180 133

M 14 X 2 100 74 140 103 170 125 M 16 X 1.5 160 118 235 173 280 206

M 16 X 2 150 111 225 166 260 192 M 18 X 1.5 240 177 345 254 400 295

M 18 X 2.5 220 162 310 228 365 269 M 20 X 1.5 335 247 475 350 560 413

M 20 X 2.5 300 221 440 324 510 376 M 22 X 1.5 460 339 650 479 750 553

M 22 X 2.5 420 310 590 435 700 516 M 24 X 2 560 413 810 597 940 693

M 24 X 3 530 391 750 553 880 649 M 27 X 2 820 604 1170 862 1390 1025

M 27 X 3 780 575 1120 826 1300 958 M 30 X 2 1170 862 1660 1224 1930 1423

M 30 X 3.5 1080 796 1530 1128 1750 1290 S0180.eps

* The tightening torque corresponds to the axial force in the fastener where the
limit of elasticity of the latter is utilized 90% by tension and torsion
assuming a friction coefficient of m = 0.1.

REFERENCES:
1. DIN 912, 931, 933, 934, 6914, and 6915
2. VDI 2230

Service Manual 645


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

II. APPLICABLE TO:


A. Black and yellow chromate fasteners, nuts, and washers

Coarse-Pitch Thread Fine-Pitch Thread


*Tightening Torque *Tightening Torque

Property Class Property Class


Designation

Designation
8.8 10.9 12.9 8.8 10.9 12.9
Thread

Thread
Nm ft lb Nm ft lb Nm ft lb Nm ft lb Nm ft lb Nm ft lb

M 4 X 0.7 2.7 2.0 4 2.9 4.6 3.4 M 8X1 24 18 35 26 41 30

M 5 X 0.8 5.3 3.9 7.8 5.7 9.0 6.6 M 10 X 1 50 37 70 52 85 63

M 6X1 8 5.9 13.5 10.0 16.2 11.9 M 10 X 1.25 46 34 65 48 80 59

M 8 X 1.25 22 16 32 24 38 28 M 12 X 1.25 83 61 120 88 145 107

M 10 X 1.5 44 32 64 47 75 55 M 12 X 1.5 80 59 115 85 140 103

M 12 X 1.75 76 56 112 83 130 96 M 14 X 1.5 130 96 190 140 230 170

M 14 X 2 120 88 180 133 210 155 M 16 X 1.5 200 147 295 217 350 258

M 16 X 2 185 136 275 203 325 240 M 18 X 1.5 300 221 435 321 510 376

M 18 X 2.5 270 199 385 284 450 332 M 20 X 1.5 425 313 610 450 710 523

M 20 X 2.5 380 280 550 405 640 472 M 22 X 1.5 580 428 825 608 940 693

M 22 X 2.5 520 383 740 545 870 641 M 24 X 2 720 531 1030 759 1210 892

M 24 X 3 650 479 940 693 1095 807 M 27 X 2 1030 759 1480 1091 1750 1290

M 27 X 3 990 730 1390 1025 1620 1194 M 30 X 2 1480 1091 2110 1555 2470 1821

M 30 X 3.5 1300 958 1890 1393 2200 1622 S0181.eps

* The tightening torque corresponds to the axial force in the fastener where the
limit of elasticity of the latter is utilized 90% by tension and torsion
assuming a friction coefficient of m = 0.14.

REFERENCES:
1. DIN 912, 931, 933, 934, 6914, and 6915
3. VDI 2230

646 Service Manual


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Torque Specification: Slewing


Roller Bearing Bolts

Torque - Ft-Lbs
Size (Newton-meters)
Part
Unit (Course Grade DIN
Number Black or Yel- Dacrometer
Threads)
low Cromate Geomet

Bolt 10207022 M20 x 140 10.9 931 405 (550 Nm) 326 (440 Nm)
S 17
Washer 10141124 M20

Bolt 10030718 M24 x 130 10.9 931 694 (940 Nm) 553 (750 Nm)
S 31 XT
Washer 10141125 M24

KVM 32XL Bolt 10072024 M20 X 2.5 X 110 10.9 6914 405 (550 Nm) 326 (440 Nm)
and
KVM 36L Washer 10001509 M21

Bolt 10030718 M24 x 130 10.9 931 694 (940 Nm) 553 (750 Nm)
KVM 34X
Washer 10141125 M24

Bolt 10120666 M20 X 2.5 X 140 12.9 6914 472 (640 Nm) 376 (510 Nm)
KVM 36X
Washer 10001509 M21

Bolt 10009258 M20 X 2 X 150 12.9 960 472 (640 Nm) 376 (510 Nm)

KVM 36 Washer 10001509 M21

Nut 10007993 M20

Bolt 10120666 M20 X 2.5 X 140 12.9 960 472 (640 Nm) 376 (510 Nm)
KVM 39
Washer 10001509 M21

Bolt 10117168 M24 X 150 10.9 931 694 (940 Nm) 553 (750 Nm)
S 42 SX
Washer 10141124 M24

Bolt 10012926 M22 X 2.5 X 180 10.9 931 546 (740 Nm) 440 (592 Nm)

KVM 42 Washer 10012937 M23

Nut 10029928 M23

S 45 SX Bolt 10117168 M24 X 150 10.9 931 694 (940 Nm) 553 (750 Nm)
S 47 SX Washer 10141125 M24

Bolt 10044746 M24 X 3 X 140 10.9 6914 694 (940 Nm) 553 (750 Nm)
KVM 52
KVM 55 Washer 10001504 M25

Service Manual 647


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Bolt 10188613 M24 X 3 X160 10.9 6914 694 (940 Nm) 553 (750 Nm)
S 52 SX
Washer 10188948 M25

S 58 SX Bolt 10188613 M24 X 3 X160 10.9 6914 694 (940 Nm) 553 (750 Nm)
S 61 SX Washer 10188948 M25

648 Service Manual


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Torque for Boom Cylinder Bolts

Torque
Cyl. Part
Unit Piston Cylinder End
No. Number
Nm Ft-Lb Nm Ft-Lb
#1 10004728 128 94 313 231

KVM 23 #2 10000661 128 94 313 231

#3 10004747 36 27 128 94

#1 10025228 627 463 190 140

#2 10032825 627 463 269 199


KVM 24x-4
#3 10025223 627 463 190 140

#4 10079930 626 462 322 238

#1 10004738 128 94 313 231

KVM 25 #2 10004738 128 94 313 231

#3 10004721 73 54 313 231

#1 10082091 1075 793 627 463

#2 10111663 627 463 269 199


KVM 26X-4
#3 10111514 626 462 322 238

#4 10110660 441 325 132 97

#1 10004740 128 94 428 316

KVM 28M #2 10004738 128 94 313 231

#3 10004722 128 94 313 231

#1 10082091 1075 793 627 463

KVM 28X #2 10110776 626 462 322 238

#3 10110660 441 325 132 97

#1 10004724 128 94 313 231

KVM 31 #2 10004734 128 94 313 231

#3 10004722 128 94 313 231

Service Manual 649


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Torque
Cyl. Part Piston Cylinder End
Unit
No. Number
Nm Ft-Lb Nm Ft-Lb

#1 10024056 1075 793 440 325

#2 10023914 1075 793 269 199


KVM 32M
#3 10023699 627 463 269 199

#4 10023615 441 325 269 199

#1 10110190 1075 793 627 463

#2 10023914 1075 793 269 199


KVM 32XL
#3 10062795 627 463 269 199

#4 10023615 441 325 269 199

#1 10158046 960 710 - -

#2 10158047 960 710 - -


KVM 34X
#3 10158049 - - - -

#4 10158050 - - - -

#1 10000655 128 94 428 316

#2 10000651 128 94 428 316


KVM 36 STD
#3 10004738 128 94 313 231

#4 10004721 73 54 313 231

#1 10111029 1075 793 627 463

#2 10110461 1075 793 627 463


KVM 36X
#3 10110776 626 462 322 238

#4 10110660 441 325 132 97

#1 10111029 1075 793 627 463

#2 10110461 1075 793 627 463


KVM 39X
#3 10110776 626 462 322 238

#4 10110660 441 325 132 97

650 Service Manual


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Torque
Cyl. Part Piston Cylinder End
Unit
No. Number
Nm Ft-Lb Nm Ft-Lb

#1 10023914 1075 793 269 199

#2 10080103 1075 793 627 463


KVM 42M
#3 10025228 627 463 190 140

#4 10037135 441 325 269 199

#1 10201085 950 700 -- --

#2 10110461 1075 793 627 463


S 42 SX
#3 10110776 626 462 322 238

#4 10110660 441 325 132 97

#1 10167681 - - 1950 1450


S 45SX #2 10146611 1220 900 960 700
and
S 47SX #3 10146612 1350 1000 - -

#4 10146613 441 325 132 100

10049567 -- -- 2350 1734


#1
10142494 -- -- 2100 1550
KVM 52
and #2 10049568 -- -- 820 605
KVM 55 #3 10049569 -- -- -- --

#4 10049570 -- -- -- --

#1 10185967 -- -- -- --
S 58SX #2 10185968 1150 850
and
S 61SX #3 10185969 -- -- -- --

#4 10185970 -- -- -- --

Service Manual 651


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

WP Number Codes

EXPLANATION OF NOMENCLATURE

WP 1000 XE

World Pump Frame (Concrete Pump)


Pump Model
Twin Circuit (X) or Single Circuit (blank) Switching
Electric (E) or Diesel (blank)

WP 750 - 15XE

World Pump Frame (Concrete Pump)


Pump Model
15 cm Diameter Material Cylinder Bore
Twin Circuit (X) or Single Circuit (blank) Switching
Electric (E) or Diesel (blank)

WP 750 - 18XE

World Pump Frame (Concrete Pump)


Pump Model
18 cm Diameter Material Cylinder Bore
Twin Circuit (X) or Single Circuit (blank) Switching
Electric (E) or Diesel (blank)

In practical usage, it would be common to refer to these units as a 1000, 750-15, and a 750-18.
The pumpkit has its own complete model number. You will nd this used on the output char ts and nomographs for
speci c machines . An example:

Pumpkit: 80 / 50 X 1000 : 180

Differential Cylinder Bore Diameter (in mm)


Differential Cylinder Rod Diameter (in mm)
Stroke Length (in mm)
Material Cylinder Bore Diameter (in mm)

S0014.eps

652 Service Manual


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

BP Model Number Codes


EXPLANATION OF NOMENCLATURE
The model numbers of other Schwing concrete pumps are explained by these code examples:

EXAMPLE BPL 1200 HDR - 23 KVM 32/28 XL - 125


The code for the truck pump
is broken down as follows: BP L 1200 HD R 23

Beton Pumpe (Concrete Pump)


Lastkraftwagen (Truck mounted)
Pumpkit Model#
Heavy - Duty
Rock Valve ("omit" if gate valve)
Diameter of Material Cylinders (in centimeters)
The code for the placing boom
is broken down as follows: K VM 32/28 **** - 125
Knickbarrer Verteiler Mast (Integrated placing boom)
or Derrick Verteiler Mast (Counter-jib placing boom)
Booms Vertical Reach (in meters)
Booms Horizontal reach (in meters)
* Special Dseignations: ("LW" - LightWeight) ("X"-outrigger configuration)
("L"-longer boom reach)
Diameter of Boom Pipeline (in millimeters)

EXAMPLE BPA 3001 HDD - 18R


The code for the trailer pump
is broken down as follows: BP A 3001 HD D 18 HP R

Beton Pumpe (Concrete Pump)


Highway Axle ("omit" if jobsite axle)
Pumpkit Model#
Heavy - Duty
Diesel Engine ("E" if Electric Motor)
Diameter of Material Cylinders (in centimeters)
High Pressure
Rock Valve ("omit" if gate valve)
The pumpkit has its own complete model number. You will find this used 125 / 80 x 2000 - 230
on the output charts and nomographs for specific units. An example:

Differential Cylinder Bore Diameter (in millimeters)


Differential Piston Rod Diameter (in millimeters)
Differential Stroke Length (in millimeters)
Material Cylinder Bore Diameter (in millimeters)
S0015.eps

Service Manual 653


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Outrigger Spreads and Loads

OUTRIGGER SPREADS AND LOADS 1


Schwing America, Inc.

FRONT REAR FRONT to REAR MAXIMUM MAXIMUM REAR


OUTRIGGER OUTRIGGER OUTRIGGER FRONT OUTRIGGER
PRODUCT
SPREAD SPREAD SPREAD OUTRIGGER LOAD
(in) (mm) (in) (mm) (in) (mm) (lbs) (kN) (lbs) (kN)
KVM 17 141 3581 86 2184 173 4394 16,860 75 11,240 50

S 17 2 152 3861 87 2210 184 4674 22,026 98 8,810 39

KVM 23 236 5994 86 2184 222 5639 20,947 93 14,332 64

KVM 23-4 H 225 5715 134 3404 236 5994 22,050 98 15,250 68

KVM 24-4 H 235 5969 142 3607 268 6807 27,000 120 20,500 91
KVM 25 225 5715 134 3404 244 6198 23,200 103 14,300 64

KVM 26-4 235 5969 142 3607 268 6807 29,000 129 23,500 105

KVM 28 245 6223 180 4572 271 6883 27,560 123 17,420 78

KVM 28 X 235 5969 142 3607 268 6807 28,500 127 22,800 101

S 28 X 235 5969 142 3607 259 6579 40,464 180 38,216 170

KVM 31 244 6198 244 6198 248 6299 24,255 108 28,665 128
S 31 EZ (HT) 245 6223 202 5131 293 7442 39,700 177 30,900 137
KVM 32 278 7061 192 4877 271 6883 30,430 135 22,930 102

KVM 32 XL 234 5944 204 5182 294 7468 32,600 145 27,000 120

KVM 34 X 245 6223 225 5715 283 7188 39,500 176 31,500 140
KVM 36 274 6960 294 7468 282 7163 32,630 145 36,380 162

KVM 36 X 292 7417 232 5893 353 8966 37,800 168 33,300 148
KVM 39 X 307 7798 252 6401 359 9119 42,000 187 35,200 157

S 41 SX 312 7925 252 6401 352 8941 42,000 187 35,200 157

KVM 42 HW 354 8992 354 8992 363 9220 49,600 221 52,900 235

KVM 42 LW 335 8509 331 8407 333 8458 43,400 193 45,400 202
S 42 SX 327 8306 327 8306 348 8839 50,700 226 52,900 235
S 45/47 SX 327 8306 327 8306 348 8839 58,500 260 56,200 250
KVM 52/55 374 9500 374 9500 410 10414 60,000 267 60,000 267

S 52 SX 350 8890 411 10439 424 10770 75,308 335 78,680 350

S 58/61 SX 350 8890 493 12522 453 11506 78,680 350 83,176 370

Notes: S0016.eps
1. All dimensions and weights are approximate;
2. Two axle Mack truck listed.

654 Service Manual


HOME
PRINT

(C0)

Issue: 01/31/05
(C4) 5 (C1)
8 6
(B1)
(B0) 2
1 D 7

04/13/05
(B4) (C3) (D4)
(C2)

Prepared by: Mark Berggren


4 12 (D0)
E 9
(D3)
Boom Pin Clearances

3 (D1)
(B2) 10
C 11
(B3) (D2)
B
(A0) (A3)
HP
A
(A2)
Upper
Subject: Maximum Pin-Bushing-Bore Clearances

Lower 5115-1.eps

Service Manual
HP NA A NA B NA 1 2 3 3.1 C 4 5 6 7 7.1 D 8 9 10 11 11.1 E 12
KVM LWR UPR A0 A1 A2 A2.1 A3 A4 B0 B1 B2 B2.1 B3 B4 C0 C1 C2 C2.1 C3 C4 D0 D1 D2 D2.1 D3 D4
SAIE STANDARD

23M .099 .150 .098 ----- .041 ----- .041 ----- .047 .041 .041 ----- .041 .041 .035 .030 .030 ----- .030 .030 ----- ----- ----- ----- ----- -----

Approved by: Jason


25M .108 .138 .098 ----- .047 ----- .047 ----- .044 .047 .047 ----- .047 .047 .035 .030 .030 ----- .030 .030 ----- ----- ----- ----- ----- -----
SERVICE TRAINING

28M .108 .138 .098 ----- .047 ----- .047 ----- .044 .047 .047 ----- .047 .047 .035 .030 .035 ----- .035 .030 ----- ----- ----- ----- ----- -----

Mehl
31M .108 .158 .114 ----- .041 ----- .041 ----- .044 .047 .047 ----- .047 .047 .067 .035 .035 ----- .035 .035 ----- ----- ----- ----- ----- -----
32M .108 .158 .114 ----- .054 ----- .054 ----- .044 .041 .044 ----- .044 .044 .067 .035 .041 ----- .041 .041 .035 .030 .035 ----- .035 .035
32XL Rollix Rollix .045 ----- .044 ----- .044 ----- .044 .041 .044 ----- .044 .044 .045 .035 .041 ----- .041 .041 .035 .030 .035 ----- .035 .035
36M Rollix Rollix .114 ----- .047 ----- .047 ----- .054 .049 .054 ----- .054 .049 .067 .041 .047 ----- .047 .041 .035 .030 .030 ----- .030 .030
NOTES:
1. REFERENCE SAIE 5114 FOR SLEWING BEARING INSPECTION.
2. ALL MEASUREMENTS ARE IN INCHES AND REPRESENT MAXIMUM ALLOWABLE CLEARANCES.
3. FOR SPLIT BOOM AND DETACH TOWER CONNECTIONS, ALLOWED BOOM PIN CLEARANCE IS 0.050 MAXIMUM
Page: 1 of 10

4. CONTACT THE SAI SERVICE DEPARTMENT AT (651) 429-0999 IF YOU HAVE QUESTIONS
Standard: 5115

5. ALL DIMENSIONS ARE IN INCHES.

655
Formulas, Conversions & Specifications
HOME

656
PRINT

Issue: 01/31/05
(C0)
(C4) 5 (C1)
8 6
(B1)

04/13/05
(B0) 2

Prepared by: Mark Berggren


1 D 7.1
(C3) (D4)
(B4) 7 (C2.1) 12 (D0)
4 3.1 (C2) E 9
(B2.1) (D3)
(D1)
3 10
(B2) 11 11.1
C (D2) (D2.1)
(B3)
B
(A0) (A3)
HP
Formulas, Conversions & Specifications

A
(A2)
Upper
Subject: Maximum Pin-Bushing-Bore Clearances

Lower 5115-2.eps

Service Manual
BEARING CLEARANCES
SAIE STANDARD

Approved by: Jason


HP NA A NA B NA 1 2 3 3.1 C 4 5 6 7 7.1 D 8 9 10 11 11.1 E 12
KVM LWR UPR A0 A1 A2 A2.1 A3 A4 B0 B1 B2 B2.1 B3 B4 C0 C1 C2 C2.1 C3 C4 D0 D1 D2 D2.1 D3 D4
SERVICE TRAINING

Mehl
26-4 .108 .138 .060 ----- .044 ----- .044 ----- .041 .041 .041 .047 .041 .047 .045 .035 .035 .041 .035 .041 .027 .027 .024 .032 .024 .032
28X .108 .138 .060 ----- .044 ----- .044 ----- .041 .041 .032 .047 .032 .047 .027 .027 .024 .032 .024 .032 ----- ----- ----- ----- ----- -----
34X Rollix Rollix .045 ----- .049 ----- .049 ----- .049 .047 .047 .049 .047 .049 .045 .038 .038 .047 .038 .047 .032 .032 .032 .032 .032 .032
36LW Rollix Rollix .045 ----- .044 ----- .044 ----- .044 .044 .047 .049 .047 .049 .045 .041 .032 .047 .032 .047 .027 .027 .024 .032 .024 .032
36X Rollix Rollix .045 ----- .044 ----- .044 ----- .044 .047 .047 .049 .047 .049 .038 .038 .032 .047 .032 .047 .024 .024 .024 .032 .024 .032
39X Rollix Rollix .114 ----- .044 ----- .044 ----- .044 .044 .047 .049 .047 .049 .041 .041 .032 .047 .032 .047 .030 .027 .027 .035 .027 .035

NOTES:
Page: 2 of 10

1. REFERENCE SAIE 5114 FOR SLEWING BEARING INSPECTION.


Standard: 5115

2. ALL MEASUREMENTS ARE IN INCHES AND REPRESENT MAXIMUM ALLOWABLE CLEARANCES.


3. FOR SPLIT BOOM AND DETACH TOWER CONNECTIONS, ALLOWED BOOM PIN CLEARANCE IS 0.050 MAXIMUM
4. CONTACT THE SAI SERVICE DEPARTMENT AT (651) 429-0999 IF YOU HAVE QUESTIONS.
5. ALL DIMENSIONS ARE IN INCHES.
HOME
PRINT

Issue: 01/31/05
(C0)
(C4) 5
8 (C1)
6
(B1)

04/13/05
(B0) 2 D

Prepared by: Mark Berggren


1 7
3.1 (C3) (C2) (D4)
(B4) (B2.1)
4 12 (D0)
E 9
(D4) (D3)
3 E
(B2)
12 (D0) (D1)
(D3) 9 10
11
C (D1) (D2)
(B3) 10
B 11 11.1
(A3) KVM 42M L.W. & H.W.
(A0) (D2) (D2.1)
HP
A KVM 42M CURRENT PRODUCTION
(A2)
Subject: Maximum Pin-Bushing-Bore Clearances

5115-3.eps

Service Manual
SAIE STANDARD

Approved by: Jason


SERVICE TRAINING

Mehl
HP NA A NA B NA 1 2 3 3.1 C 4 5 6 7 7.1 D 8 9 10 11 11.1 E 12
KVM A0 A1 A2 A2.1 A3 A4 B0 B1 B2 B2.1 B3 B4 C0 C1 C2 C2.1 C3 C4 D0 D1 D2 D2.1 D3 D4
42M .114 ----- .044 ----- .044 ----- .054 ----- ----- ----- ----- ----- .073 .047 .047 ----- .047 .047 .035 .035 .035 .035 .035 .035
42LW .114 ----- .044 ----- .044 ----- .054 .044 .049 .047 .049 .049 .073 .047 .047 ----- .047 .047 .035 .035 .035 ----- .035 .035
42HW .114 ----- .044 ----- .044 ----- .054 .054 .054 .059 .054 .059 .073 .047 .047 ----- .047 .047 .035 .035 .035 ----- .035 .035
NOTES:
1. REFERENCE SAIE 5114 FOR SLEWING BEARING INSPECTION.
2. ALL MEASUREMENTS ARE IN INCHES AND REPRESENT MAXIMUM ALLOWABLE CLEARANCES.
Page: 3 of 10

3. CONTACT THE SAI SERVICE DEPARTMENT AT (651) 429-0999 IF YOU HAVE QUESTIONS.
Standard: 5115

4. ALL DIMENSIONS ARE IN INCHES.

657
Formulas, Conversions & Specifications
HOME

658
(C0)
PRINT

5
(C4) (C1)
8 6

Issue: 01/31/05
7.1
(C2.1) E
7 (D3) (D4)
(C2) 12
D (D0)

04/13/05
(B1) (C3) 9

Prepared by: Mark Berggren


2 (B2.1) 11
3.1 (D2) 11.1 (D1)
(B0) (D2.1) 10
1 (B2)
(B4) 3
4
(A3)
B
(B3)
C
Formulas, Conversions & Specifications

(A4)
13

A (A0)
Subject: Maximum Pin-Bushing-Bore Clearances

(A2) HP
15
(A2.1)

Service Manual
14
(A1) 5115-4.eps
SAIE STANDARD

Approved by: Jason


HP NA A NA B NA 1 2 3 3.1 C 4 5 6 7 7.1 D 8 9 10 11 11.1 E 12
SERVICE TRAINING

KVM A0 A1 A2 A2.1 A3 A4 B0 B1 B2 B2.1 B3 B4 C0 C1 C2 C2.1 C3 C4 D0 D1 D2 D2.1 D3 D4

Mehl
45SX .045 .051 .051 .075 .051 .075 .054 .054 .049 .051 .049 .051 .044 .044 .047 .054 .047 .054 .045 .032 .027 .035 .027 .035
47SX .045 .051 .051 .075 .051 .075 .054 .054 .049 .051 .049 .051 .044 .044 .047 .054 .047 .054 .045 .032 .027 .035 .027 .035
52M .045 .079 .071 .075 .071 .079 .059 .059 .059 .059 .059 .071 .054 .054 .054 .055 .054 .055 .045 .035 .035 .035 .035 .035
52EX .045 .079 .071 .075 .071 .079 .059 .059 .059 .059 .059 .071 .054 .054 .054 .055 .054 .055 .045 .035 .035 .035 .035 .035
55M .045 .079 .071 .075 .071 .079 .059 .059 .059 .059 .059 .071 .054 .054 .054 .055 .054 .055 .045 .035 .035 .035 .035 .035
58SX .045 .055 .055 .075 .055 .079 .051 .051 .059 .071 .059 .071 .054 .044 .044 .049 .044 .049 .045 .035 .032 .044 .032 .044
61SX .045 .055 .055 .075 .055 .079 .051 .051 .059 .071 .059 .071 .054 .044 .044 .049 .044 .049 .045 .035 .032 .044 .032 .044
Page: 4 of 10

NOTES:
Standard: 5115

1. REFERENCE SAIE 5114 FOR SLEWING BEARING INSPECTION.


2. ALL MEASUREMENTS ARE IN INCHES AND REPRESENT MAXIMUM ALLOWABLE CLEARANCES.
3. CONTACT THE SAI SERVICE DEPARTMENT AT (651) 429-0999 IF YOU HAVE QUESTIONS.
4. ALL DIMENSIONS ARE IN INCHES.
HOME
PRINT

Issue: 01/31/05
(C0)
(C4) 5 (C1)
8 6
(B1)

04/13/05
(B0) 2

Prepared by: Mark Berggren


1 D
(C3) 7 7.1 (D4)
(B4) 12
4 (C2) (C2.1) (D0)
E
(D3) 9
3
(B2) 11 (D1)
(D2) 10
C
11.1
B (B3) (D2.1)
(A3)
(A0)
HP
A
(A2)
Upper
Subject: Maximum Pin-Bushing-Bore Clearances

Lower 5115-5.eps

Service Manual
SAIE STANDARD

Approved by: Jason


HP NA A NA B NA 1 2 3 3.1 C 4 5 6 7 7.1 D 8 9 10 11 11.1 E 12
KVM LWR UPR A0 A1 A2 A2.1 A3 A4 B0 B1 B2 B2.1 B3 B4 C0 C1 C2 C2.1 C3 C4 D0 D1 D2 D2.1 D3 D4

Mehl
SERVICE TRAINING

23-4H .108 .138 .060 ----- .047 ----- .047 ----- .044 .041 .041 ----- .041 .041 .035 .030 .047 .030 .047 .041 .065 .030 .035 .030 .035 .035
24-4H .108 .138 .060 ----- .044 ----- .044 ----- .044 .041 .041 ----- .041 .041 .035 .030 .047 .030 .047 .041 .065 .030 .035 .030 .035 .035
NOTES:
1. REFERENCE SAIE 5114 FOR SLEWING BEARING INSPECTION.
2. ALL MEASUREMENTS ARE IN INCHES AND REPRESENT MAXIMUM ALLOWABLE CLEARANCES.
3. CONTACT THE SAI SERVICE DEPARTMENT AT (651) 429-0999 IF YOU HAVE QUESTIONS.
4. ALL DIMENSIONS ARE IN INCHES.
Page: 5 of 10
Standard: 5115

659
Formulas, Conversions & Specifications
HOME

660
PRINT

Issue: 01/31/05
(C0)
(C4) 5 (C1)
8
6
(B1)

04/13/05
(B0) 2

Prepared by: Mark Berggren


1 D 7
(B4) 3.1 (C3) (C2)
4 (B2.1)

3
(B2)
C
(B3)
B
(A3)
(A0)
Formulas, Conversions & Specifications

HP
A
(A2)
Upper
Subject: Maximum Pin-Bushing-Bore Clearances

Lower 5115-6.eps

Service Manual
SAIE STANDARD

Approved by: Jason


HP NA A NA B NA 1 2 3 3.1 C 4 5 6 7 7.1 D 8 9 10 11 11.1 E 12

Mehl
SERVICE TRAINING

KVM LWR UPR A0 A1 A2 A2.1 A3 A4 B0 B1 B2 B2.1 B3 B4 C0 C1 C2 C2.1 C3 C4 D0 D1 D2 D2.1 D3 D4


17-270 .108 .138 .060 ----- .035 ----- .035 ----- .030 .030 .035 .035 .035 .035 .030 .024 .030 ----- .030 .024 ----- ----- ----- ----- ----- -----
NOTES:
1. REFERENCE SAIE 5114 FOR SLEWING BEARING INSPECTION.
2. ALL MEASUREMENTS ARE IN INCHES AND REPRESENT MAXIMUM ALLOWABLE CLEARANCES.
3. CONTACT THE SAI SERVICE DEPARTMENT AT (651) 429-0999 IF YOU HAVE QUESTIONS.
4. ALL DIMENSIONS ARE IN INCHES.
Page: 6 of 10
Standard: 5115
HOME
PRINT

(D2) (D2.1)

Issue: 01/31/05
11 11.1
10
(D1)
(D3) 9

04/13/05
(C2) E 12 (D0)

Prepared by: Mark Berggren


7 (C2.1) (D4)
7.1
(C3) 6
D
(B4) 5 (C1)
(B0) 4 8 (C0)
1 (C4)
(B1) C
2 (B3)

3.1 3
(B2.1) (B2)

B
(A3)
Subject: Maximum Pin-Bushing-Bore Clearances

(A0)
HP

Service Manual
A
(A2)
SAIE STANDARD

5115-7.eps

Approved by: Jason


SERVICE TRAINING

Mehl
HP NA A NA B NA 1 2 3 3.1 C 4 5 6 7 7.1 D 8 9 10 11 11.1 E 12
KVM A0 A1 A2 A2.1 A3 A4 B0 B1 B2 B2.1 B3 B4 C0 C1 C2 C2.1 C3 C4 D0 D1 D2 D2.1 D3 D4
31-5HT .045 ----- .049 ----- .049 ----- .041 .035 .032 .047 .032 .047 .035 .035 .035 .041 .035 .041 .027 .027 .027 .030 .027 .030
NOTES:
Page: 7 of 10

1. REFERENCE SAIE 5114 FOR SLEWING BEARING INSPECTION.


Standard: 5115

2. ALL MEASUREMENTS ARE IN INCHES AND REPRESENT MAXIMUM ALLOWABLE CLEARANCES.


3. CONTACT THE SAI SERVICE DEPARTMENT AT (651) 429-0999 IF YOU HAVE QUESTIONS.
4. ALL DIMENSIONS ARE IN INCHES.

661
Formulas, Conversions & Specifications
HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Standard: 5115
SAIE STANDARD Page: 8 of 10
Subject: Maximum Pin-Bushing-Bore Clearances

NOTE:
1. CLEARANCE OF SOLID PINS AND HOLLOW PINS TO BORE WITH KEEPER
CAN NOT EXCEED THE FOLLOWING.
2. CLEARANCE BETWEEN INDIVIDUAL PINS AND BUSHINGS ARE PER CHARTS
FROM PREVIOUS PAGES.

PER CHART

0.005 MAX. CLEARANCE


BOOM

BOOM

HYDRAULIC CYLINDER
or GUIDE LEVER

BOOM

PER CHART

0.015 MAX. CLEARANCE TYP.

GUIDE LEVER
OR BOOM

BOOM

PER CHART

0.015 MAX. CLEARANCE TYP.


Prepared by: Mark Berggren Approved by: Jason Mehl
Issue: 01/31/05 04/13/05

662 Service Manual


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Standard: 5115
SAIE STANDARD Page: 9 of 10
Subject: Maximum Pin-Bushing-Bore Clearances

HOLLOW PINS
MAIN COLUMN
OR TURRET

BOOM #1 PER CHART

0.030 MAX. CLEARANCE TYP.


HOLLOW PIN

TURRET

BOOM #1 HOLLOW PIN PER CHART

0.030 MAX. CLEARANCE TYP.

BOOM #3 PER CHART

BOOM #2

0.030 MAX. CLEARANCE TYP.


HOLLOW PIN

Prepared by: Mark Berggren Approved by: Jason Mehl


Issue: 01/31/05 04/13/05

Service Manual 663


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Standard: 5115
SAIE STANDARD Page: 10 of 10
Subject: Maximum Pin-Bushing-Bore Clearances

GUIDE LEVER

PER CHART

0.015 MAX. CLEARANCE


TYP.

GUIDE LINK

HYDR. CYLINDER

0.015 MAX. CLEARANCE


TYP.

Prepared by: Mark Berggren Approved by: Jason Mehl


Issue: 01/31/05 04/13/05

664 Service Manual


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Nozzle Chart

ID NUMBER ORIFICE LETTER EY NUMBER THREADS & FITTING SIZES


SIZE (MM) CODE
10067689 1.2 F N.O.F. R1/4" x 12 mm
10010117 0.7 A EV 302 003 R1/2" x 12 mm
10078594 0.8 G EV 302 003 R1/2" x 12 mm
10010119 1.0 B EV 302 003 R1/2" x 12 mm
10139911 1.1 H EV 302 003 R1/2" x 12 mm
10077812 1.2 F EV 302 003 R1/2" x 12 mm
10010120 1.3 C EV 302 003 R1/2" x 12 mm
10139112 1.4 P EV 302 003 R1/2" x 12 mm
10014925 1.5 I EV 302 003 R1/2" x 12 mm
MALE to MALE 10010122 1.7 D EV 302 003 R1/2" x 12 mm
AR TYPE 10010276 2.0 E EV 302 003 R1/2" x 12 mm
10012077 1.2 F EV 302 001 R1/2" x 16 mm
10012080 1.3 C EV 302 001 R1/2" x 16 mm
10033578 1.5 I EV 302 001 R1/2" x 16 mm
10012079 1.7 D EV 302 001 R1/2" x 16 mm
10012078 2.0 E EV 302 001 R1/2" x 16 mm

ID NUMBER ORIFICE LETTER EY NUMBER THREADS & FITTING SIZES


SIZE (MM) CODE
10077553 0.4 M EV 302 000 R3/8" x R3/8"
10077555 0.55 N EV 302 000 R3/8" x R3/8"
10012075 0.7 A EV 302 000 R3/8" x R3/8"
10012083 0.8 G EV 302 000 R3/8" x R3/8"
10012086 1.0 B EV 302 000 R3/8" x R3/8"
10012259 1.1 H EV 302 000 R3/8" x R3/8"
10012084 1.2 F EV 302 000 R3/8" x R3/8"
10012087 1.3 C EV 302 000 R3/8" x R3/8"
MALE to FEMALE
REDS TYPE 10041326 1.4 P EV 302 000 R3/8" x R3/8"
10041325 1.5 I EV 302 000 R3/8" x R3/8"
10012088 1.7 D EV 302 000 R3/8" x R3/8"
10100230 2.5 S EV 302 000 R3/8" x R3/8"

ID NUMBER ORIFICE LETTER EY NUMBER THREADS & FITTING SIZES


SIZE (MM) CODE
10013886 0.7 A EV 302 004 R3/8" x R3/8"
10033540 0.8 G EV 302 004 R3/8" x R3/8"
10037858 0.9 K EV 302 004 R3/8" x R3/8"
10034181 1.0 B EV 302 004 R3/8" x R3/8"
10033541 1.1 H EV 302 004 R3/8" x R3/8"
FEMALE to FEMALE
10033543 1.3 C EV 302 004 R3/8" x R3/8"
10037859 1.8 L EV 302 004 R3/8" x R3/8"

ID NUMBER ORIFICE LETTER EY NUMBER THREADS & FITTING SIZES


SIZE (MM) CODE
NOZZLE
SCREW 10077811 1.2 F N.O.F. HD 44 X 12
10077806 1.5 I N.O.F. HD 44 X 12
S0017.eps

Service Manual 665


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Boom Times/Without Weights


Front Rear
Boom #1 Boom #2 Boom #3 Boom #4 Boom #5 Slewing Right &
Outrigger Outrigger Outrigger
Type Boom Up/Down 90 Up/Down Up/Down *180 Up/Down Up/Down *90 Left 90
Extension Extension Slewing In/Out
Degrees ( ) Degrees Degrees *180 Degrees Degrees Degrees
In/Out In/Out

KVM 17 58/52 30/22 (90) 37/25 *(180) N/A N/A 35 N/A N/A N/A
KVM 23 52/72 60/74 (180) 43/46 N/A N/A 23 N/A N/A N/A
KVM 23-4H 54/65 43/40 (90) 27/30 *(90) 26/34 *(90) N/A 27 9/14 N/A N/A
KVM 24-4 50/59 36/35 (90) 26/36 *(90) 24/33 *(90) N/A 29 9/14 N/A N/A
24-4 Prop. (Apitech) 53/60 48/43 (90) 27/33 *(90) 22/31 *(90) N/A 35 14/27 N/A N/A
KVM 26-4 54/65 43/40 (90) 27/36 *(90) 26/34 *(90) N/A 27 9/14 N/A N/A
26-4 Prop. (Apitech) 50/64 45/43 (90) 53/68 45/61 N/A 33 12/20 N/A N/A
KVM 26 Meter 55/70 69/77 (180) 45/60 N/A N/A 27 9/14 N/A N/A
KVM 28 65/62 62/67 (180) 40/48 N/A N/A 28 N/A N/A N/A
KVM 28X 65/58 43/42 (90) 41/51 N/A N/A 28 13/22 N/A N/A
KVM 28X (Apitech) 53/60 74/78 (180) 44/46 N/A N/A 34 13/22 N/A N/A
S 28-4 H 50/50 35/35 (90) 50/50 25/25 N/A 40 13/26 N/A N/A
KVM 31 81/79 75/85 (180) 47/51 N/A N/A 28 N/A N/A N/A
#1 Boom Telescopic
S 31 HT 70/70 33/33 (90) 43/43 23/23 N/A 43 12/23 8/12 In / Out 40/50

KVM 32 94/90 63/54 (90) 75/70 40/46 N/A 30 7/12 7/12 8/14
KVM 32XL Black &
76/73 63/54 (90) 75/70 40/46 N/A 43 13/21 8/10 N/A
White or Proportional
KVM 34X Standard 63/63 46/46 (90) 62/62 31/31 N/A 35 12/23 8/12 N/A
Outrigger System
KVM 34X Regenerative 63/63 46/46 (90) 62/62 31/31 N/A 35 12/13 6/6 N/A
Outrigger System

KVM 36 with 3 SPD. 65/92 50/61 (90) 70/105 31/75 N/A 6/6 6/6 22/15

KVM 36 Prop. 73/75 48/47 (90) 55/63 39/44 N/A 45 8/10 8/10 17/25
36X Prop.(Rexroth) 80/78 49/47 (90) 59/63 47/52 N/A 49 8/10 8/10 N/A
36X Prop.(Apitech) 80/95 49/47 (90) 59/65 47/52 N/A 60 8/10 8/10 N/A
S 36 RZ 70/70 50/50 (90) 70/70 20/20 N/A 50 10/10 10/10 N/A
KVM 39 X 80/80 60/60 (90) 75/75 50/50 N/A 60 15/12 7/6 N/A
S 41 SX 80/80 60/60 (90) 80/80 50/50 N/A 60 10/10 7/8 N/A
KVM 42 75/80 68/70 (90) 76/79 51/53 N/A 70 11/19 11/19 17/30

KVM 42 with 2 SPD. 75/80 68/70 (90) 76/79 51/53 N/A 10/18 10/18 16/28

42 Prop. (Rexroth) 76/80 52/61 (90) 71/76 60/61 N/A 60 10/18 10/18 16/28
42 Prop. (Apitech) 80/90 60/60 (90) 80/83 55/64 N/A 65 10/18 10/18 16/28
S 45/47 SX 90/95 70/70 (90) 90/90 60/60 N/A 70 12/12 N/A 8/7
Front Slewing Rear Slewing
KVM 52 76/90 60/67 (90) 66/76 81/75 N/A 82 17/26
23/37 6/10
Rear Slewing
S 52 SX 105/105 90/90 (90) 65/65 40/40 20/20 85 25/25 N/A
17/17
Front Slewing Rear Slewing
KVM 55 110/110 90/90 (90) 120/120 70/70 N/A 95 17/26
23/37 6/10
Rear Slewing
S 58 SX 120/120 95/95 (90) 120/120 65/65 N/A 90 25/25 N/A
17/17
Rear Slewing
S 61 SX 130/130 105/105 (90) 135/135 70/70 N/A 100 25/25 N/A
17/17

Oil must be at 40 - 50 Celsius before testing. Times are without weights.


Times are considered within specifications at +/- 5 seconds.

666 Service Manual


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Boom Pressures & Nozzle Chart Size

Hydraulic Valve Pressure Settings (BAR)

BOOM SIZE 32XL 32XL


(proportional)
(B&W)
32M 31M 28X
(proportional)
28X
(B&W)
28M 26M (proportional)
26-4 26-4 (B&W)
24-4 23-4H 23M 17M
(proportional)

FUNCTION
DumpValve/E-Stop 320 320 250 250 320 350
Boom Regulator 290 290 290 290
Handvalve Relief 300 310 280 350 350 280 290 330 290 350 280 260 280
Downside Relief 140 140 140 140 140 140 140 140 140 140 140 140 170
OUTRIGGER 280 320 200 280 280 300 290 280 280 280 280 260 280
PRETENSION 6 (air) 5.5 5.5 15 15 5.5 5.5 15 5-7 15 5-7 5.5 5-7
Pretension Relief 30 30 30 30 30
Piston Side Relief

Boom Holding Valve Relief Settings (BAR)


FUNCTION
Sec. 1 Piston Side 320 400 400 400 320 320 320 320 270 300 300 320
Sec. 1 Rod Side 320 320 300 300 320 320 300 320 270 300 300 320
Sec. 2 Piston Side 320 320 300 300 320 320 270 320 320 270 300 300 270 320
Sec. 2 Rod Side 320 320 300 300 320 320 270 300 320 270 300 300 270 320
Sec. 3 Piston Side 320 320 300 300 320 320 270 300 320 270 300 300 270 320
Sec. 3 Rod Side 320 320 300 300 320 320 270 300 320 270 300 300 270 320
Sec. 4 Piston Side 320 320 300 320 320 320 270 300 300 320
Sec. 4 Rod Side 320 320 300 320 320 320 270 300 300 320

Boom Circuit Nozzle Sizes are in mm / "T" after size denotes a Throttle Check
FUNCTION
Sec. 1 Piston Side 1.9T 1.9T 2.0T 1.9T 1.9T 1.8T 1.1 1.9T 1.5T 1.1
Sec. 1 Rod Side 1.5 1.5 1.7 1.5 1.7 1.4 0.8 1.5 1.3 0.9
Sec. 2 Piston Side 1.7 1.7 1.7 1.1 1.7 1.4 1.0 1.0 1.3 1.1
Sec. 2 Rod Side 1.3 1.3 1.3 1.5 1.3 1.1 1.2 1.3 1.0 0.9
Sec. 3 Piston Side 1.4 1.4 1.3 0.8 1.3 1.1 1.1 1.2 1.0 0.9
Sec. 3 Rod Side 1.1 1.1 1.0 1.1 1.0 0.9 1.5 1.7 0.7 0.5
Sec. 4 Piston Side 1.1 1.1 1.2
Sec. 4 Rod Side 0.8 0.8 1.0
Tower Slewing 1.3 1.2 1.3 1.3 1.2 1.3 1.0 0.7
S0020.eps

Service Manual 667


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Boom Pressures & Nozzle Chart Size

Hydraulic Valve Pressure Settings (BAR)

BOOM SIZE 58SX 52M


55M
45SX 42M 42M
47SX (proportional) (B&W) 39X 36X 36LW 36M 34X 31HT

FUNCTION
DumpValve/E-Stop 350 360 330 320 320 330 330 330 300 330 350
Boom Regulator 310 320 310 290 310 300 310 310 300 310
Handvalve Relief 360 350 350 330 330 350 340 330 280 350 350
Downside Relief 80 80 140 80 80 140 140
OUTRIGGER 350 150 300 280 280 280 280 160 200 280 280
PRETENSION 20 35 35 25 25 15 25 25 5.5 15 15
Pretension Relief 50 40 34 34 30 40 40 30 30
Piston Side Relief 230

Boom Holding Valve Relief Settings (BAR)


FUNCTION
Extend Piston Side 150
Extend Rod Side 240
Sec. 1 Piston Side 250 320 330 400 400 330 350 350 400 320 320
Sec. 1 Rod Side 310 350 330 300 320 320 320 320 300 180 180
Sec. 2 Piston Side 330 320 310 300 320 320 320 320 300 320 270
Sec. 2 Rod Side 320 320 310 300 320 330 320 320 300 310 290
Sec. 3 Piston Side 260 320 320 300 320 310 320 320 300 280 230
Sec. 3 Rod Side 320 350 320 300 320 330 320 320 300 320 320
Sec. 4 Piston Side 240 260 260 300 320 320 320 320 300 290 220
Sec. 4 Rod Side 320 350 300 300 320 330 320 320 300 320 300

Boom Circuit Nozzle Sizes are in mm / "T" after size denotes a Throttle Check
FUNCTION
Sec. 1 Piston Side 1.4T
Sec. 1 Rod Side 1.4T
Sec. 2 Piston Side 1.8T
Sec. 2 Rod Side 1.3
Sec. 3 Piston Side 1.3T
Sec. 3 Rod Side 1.2
Sec. 4 Piston Side 0.9T
Sec. 4 Rod Side 0.8
Tower Slewing
S0131.eps

668 Service Manual


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Rotek Bearing Clearance Instructions - SAIE - 5114


Standard: 5114
SAIE STANDARD Page: 1 of 9
Subject: Slewing Bearing & Drive Gear Inspection

When doing the boom inspections on slew bearing units, the drive spur gear and the turret slewing bear-
ing gear must be inspected for wear and/or galling, tipping, and gear lash as outlined. The drive gear must
all be inspected by axial and radial movement.

Slewing Bearing Tipping Clearance


1. Before inspecting the drive spur. Gear
and turret slewing bearing, you must
first secure the vehicle on which you
will be working, make sure that you are
on solid ground and there is plenty of Outrigger
clearance around the vehicle. Support

Warning!
Allow yourself enough room to move the
boom without causing danger to yourself
or others. Set up the outriggers for sup-
port, the same as you would for any job,
use carpenters level or the units bubble
level to set the base both longitudinally
and laterally level.

2. Remove the slewing bearing and drive


gear shroud. To do this, you must
Shroud
remove four bolts from the underside of
the shroud and two bolts holding the
two havles together.
Bolts connecting the
two shroud halves
Warning! Drive Gear
Shroud
While the shroud is removed from the
gears, there is the potential danger of
injury or dismemberment to yourself or
others. Use caution at all times and
beware of the potential hazards.

Visually inspect both the drive spur gear


and the turret slewing gear teeth for wear
and/or galling, any metal shavings or slivers Shroud Bolts
are an indication of excessive teeth wear
caused by too swall a gear lash or excessive
bearing wear.

Prepared by: Mark Berggren Approved by: Jason Mehl


Issue: 06/04/06

Service Manual 669


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Standard: 5114
SAIE STANDARD Page: 2 of 9
Subject: Slewing Bearing & Drive Gear Inspection

3. Raise the boom in a straight, vertical position.

Note: Steady the boom, there should be no


movement in the boom while tacking the
measuremens, or it will result in a false read-
ing. Extends booms as shown.

4. Once the boom is steady, locate point A on


the underside of the slewing bearing gear.
This will be the starting point from which you Boom Direction
will determine the amount of tipping clear-
ance on the slewing bearing. Mount dial indi-
cator as necessary.
Point "A"
(Leave no gap)
The location of point A must be on the
opposite side from the direction the boom
will be lowered.

5. Rock the boom back and forth to determine


its balancing point. Then tilt the boom
slightly opposite the measurement side so
that the boom will not rock. Make sure that
before you lower the boom, opposite mea- Dial Indicator
surement side, that there is no gap between
the underside of the slewing bearing and the
dial indicator which is in ful contact

Prepared by: Mark Berggren Approved by: Jason Mehl


Issue: 06/04/06

670 Service Manual


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Standard: 5114
SAIE STANDARD Page: 3 of 9
Subject: Slewing Bearing & Drive Gear Inspection

Neutral Position

5-10
Dial indicator will move fast when
Set dial indicator at zero indicator slows down to slow
movement.
Take reading approximately 5-10
then divide dial indicator reading by
2 and compare to maximum tipping
clearances listed below.

Pressure #1 out

2 to 3 Maximum

Unfold the boom as shown above


KVM 36 STD and 42 LW and HV must be positioned as shown with 3 maximum tilt by raising
the rear outriggers.
KVM 32XL, 31 EZ, 34X, 36X, 39X, 41SX, 45SX, 47SX, 52, 52 EXT & 55, do not require the 3
tilt (can be level becuase boom assembly can move over neutral position).
It is only required to measure in the one position shown.

Prepared by: Mark Berggren Approved by: Jason Mehl


Issue: 06/04/06

Service Manual 671


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Standard: 5114
SAIE STANDARD Page: 4 of 9
Subject: Slewing Bearing & Drive Gear Inspection

For Overhead Roll n Fold - Tipping Clearances


1. Rock the boom back and forth to determine its balancing point.

2. Then using a protractor, position the #1 boom over top dead center toward the cab at 10

3. Zero out dial indicator at point A

4. The position the #1 boom over top dead center toward the hopper at 10 at this position the reading on
dial indicator is divided by 2 and compare to maximum tipping clearance chart below.

Neutral Position
10 10

Table 1: Maximum Tipping Clearances Above Initial Clearance


KVM 32XL .059 +.010 = .069 S 41 SX .025 +.010 = .035
KVM 34X .059 +.010 = .069 KVM 42LW .025 +.010 = .035

KVM 36X .074 +.010 = .084 KVM 42HW .025 +.010 = .035

KVM 36 .019 +.010 = .029 S 45/47 SX .074 +.010 = .084


KVM 39X .074 +.010 = .084 KVM 52, 52 EXT .078 +.010 = .088
KVM 31EZ .059 +.010 = .069 KVM 55 .078 +.010 = .088

S 58/61SX .078 +.010 = .088

Prepared by: Mark Berggren Approved by: Jason Mehl


Issue: 06/04/06

672 Service Manual


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Standard: 5114
SAIE STANDARD Page: 5 of 9
Subject: Slewing Bearing & Drive Gear Inspection

Gear Lash / Axial Movement Inspection


1. Determine the maximum and minimum clearance between the drive spur gear teeth and the turret
slewing bearing teeth. the minimum clearance, should be found in the tooth grooves marked in color
or stamped H.

Note: If the markings are not visible, rotate the boom 360 in small increments and measure the clear-
ance (gap) until the minimum and maximum clearances have been located. Mark the minimum clear-
ance gear points on the slewing bearing teeth with an H stamp.

2. Raise the boom in the verticle position (neutral)


as shown.

3. Once the boom is steady, use a pry bar and


rotate the drive gear just enough so that the
side of the drive gear tooth is in solid contact
with the side of the accompanying gear tooth.
this will leave the total clearance (gap) on the
opposite side of the drive gear tooth.

Total Gap

Prepared by: Mark Berggren Approved by: Jason Mehl


Issue: 06/04/06

Service Manual 673


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Standard: 5114
SAIE STANDARD Page: 6 of 9
Subject: Slewing Bearing & Drive Gear Inspection

4. Check at thigh point using feeler


gauge, measure the gap between the
gear teeth. This is the gear lash clear-
ance.

GEAR LASH CLEARANCE

MINIMUM GEAR LASH IS 0.008"


MINIMUM GEAR LASH IS 0.040"

5. Using a pry bar and dial indicator,


the axial movement shall be mea-
sured by prying up the spur gear.
Maximum axial movement is
0.040.

Prepared by: Mark Berggren Approved by: Jason Mehl


Issue: 06/04/06

674 Service Manual


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Standard: 5114
SAIE STANDARD Page: 7 of 9
Subject: Slewing Bearing & Drive Gear Inspection

6. Once inspection is complete, and the Shroud


gear lash is satisfactory, replace the
slewing bearing and drive gear shroud.

Warning! Bolts connecting the


two shroud halves
Drive Gear
To prevent any danger to yourself or oth- Shroud
ers and to protect the gears from damage
from any foreigh objects or debris,
replace the protective shrouding for both
the slewing gear and drive gear.

Shroud Bolts

Prepared by: Mark Berggren Approved by: Jason Mehl


Issue: 06/04/06

Service Manual 675


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Standard: 5114
SAIE STANDARD Page: 8 of 9
Subject: Slewing Bearing & Drive Gear Inspection

Gear Lash Adjustment


1. To adjust the gear lash, you must first support the drive gear
from above. Screw two 10mm eye bolts Schwing part
#10014781 (997-126-001-013) into the top of the drive gear,
and support it with chain and hoist. remove all the outer bolts
from the underside, holding the gear housing to the tower
weldment.

Note: Check hydraulic supply tubes or hoses for adequate


movement.
Remove bolts after chain
and hoist are in place

2. The drive gear housing was


designed eccentrically, so
depending on the direction
of rotation, and the eccen-
tric position when installed,
the gear lash will either
increase or decrease. deter-
mine the proper rotation
direction before continuing.
Decrease Increase Increase Decrease

Right of Center Left of Center

3. Lower the drive gear enough to rotate it at least one bolt hole
position, which will amount to approximately .017 gear lash
depending on the location of eccentricity and amount of tol-
erance desired.

Note: Once the drive gear has been rotated, the supply tubes Lower hoist
on the 42M will not fit becuase of their alignment features.
Replace the three tubes with three hydraulic hoses, Schwing
part#10050169 (944-070-308-100). The 36M may not need
any replacement hoses, unless the tower weldment interfers
with the tubing while rotating the gear housing. In this case,
use one hydraulic hose, Schwing part #10050168 (994-070-
308-080).

Prepared by: Mark Berggren Approved by: Jason Mehl


Issue: 06/04/06

676 Service Manual


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

Standard: 5114
SAIE STANDARD Page: 9 of 9
Subject: Slewing Bearing & Drive Gear Inspection

4. Once the drive gear has been rotated, re-


install 4 of the gear housing bolts in 90
increments and re-connect the hydraulic
supply tubes and hoses. return to Gear
Lash inspection. If the clearance is
within the .012 to eye bolt and chain
hoist, and continue with step 5. How-
ever, if the gear lash still requires further
adjustment, repeat adjustment until it is
within the allowed clarance.

5. Once the inspection is complete, and the


gear lash is satisfactory, replace the slew
Maximum Gear Lash is 0.040 90
bearing and drive gear shroud. Minimum is 0.008 90 90
90

Warning!
Shroud
To prevent any danger to yourself or oth-
ers and to protect the gears from damage
from any foreign objects or debris, Bolts connecting the
replace the protective shrouding for both two shroud halves
Drive Gear
the slewing gear and drive gear. Shroud

Shroud Bolts

Prepared by: Mark Berggren Approved by: Jason Mehl


Issue: 06/04/06

Service Manual 677


HOME PRINT
SERVICE TRAINING
Formulas, Conversions & Specifications

678 Service Manual


HOME PRINT
SERVICE TRAINING
Special Tools

Special Tools Hydraulic Oil Filter Cart


Prevent premature failure with this filter cart from
Schwing America. This filter cart moves easily around
Hydraulic Trouble Shooting Kits your shop on pneumatic tires and operates on 120-volt
These kits contain a 0-600 Bar pressure gauge, a 0-40 power. Dule elements (included) filter synthetic and oil
Bar pressure gauge, plus all the necessary fittings, based fluids at up to 8 GPM
locking plugs, manitrol valves, and hoses to plumb the
gauges into any hydraulic circuit on the unit. These
kits include the heavy duty foam lied carrying case

S0038.eps S0179.eps

Trouble Shooting Kit for All BPA and BPL Models


except BPA 750 H.P. Portable Filtration Cart
Part # .......................................................30308553 Part #........................................................30380898
Replacement Filter Element
Part #........................................................30380857

Service Manual 679


HOME PRINT
SERVICE TRAINING
Special Tools

Flow Meters and Accesories Accessories:


AC/DC Power Supply
Flow Meter Y223 Model HT200 Part # .......................................................30314788
Blow-Out Disc
Schwing Part#..........................................30314789
Adapter Flange (SAE to BSP)
Schwing Part#..........................................30303384
Calibrator
Schwing Part#..........................................30328467
Schwing America offers the flow meter with or without
the calibrator. Please contact our Spare Parts
Department for current pricing.

S0039.eps

Flow Meter (only)


Part #........................................................30314787

Specifications:
Maximum Flow (G.P.M.).........................................200
Flow Ranges-High Scale:
U.S.G.P.M .......................................................... 25-200
t/min. ................................................................ 100-750
Flow Ranges-Low Scale:
U.S.G.P.M .............................................................. 5-40
t/min ................................................................... 20-150

Maximum Operating Pressure ........345 Bar (5000 psi)


Temperature Scale Range ... 100-250 F (40-120 C)
Port Sizes ................................. 11/2" SAE (split flange)
Weight ................................................. 30 lbs. (13.6kg)

Dimensions:
Length ............................................ 15 7/8" (403.47mm)
Width.............................................. 13 1/4" (336.55mm)
Height............................................... 6 3/4" (171.45mm)

680 Service Manual


HOME PRINT
SERVICE TRAINING
Special Tools

Material Cylinder Alignment machine requires, measure the O.D. of your differential
rod and the I.D. of the material cylinders installed. To
Tool order one of those tools, find the proper tool from the
Schwing America offers a tool which aligns the following chart, and contact our Spare Parts
material cylinders after rotation or replacement has Department.
been completed. To determine whick tool your

Rod Diameter

Material Cylinder Diameter

Ordering Chart
Rod Cylinder Item
Diameter Diameter Number Pumpkit Model Number

50 mm 150 mm 30379547 450, 500, BP 750-15


50 mm 180 mm 30339165 WP 750-18, WP 1000-18, BP 1000-18
55 mm 150 mm 30379532 250-15
55 mm 180 mm 30379533 350-18, 500-18, 650-18
63 mm 150 mm 30379534 650-15
63 mm 180 mm 30379535 580-18, 600-18, 650-18, 601-18, 900-18, 901D-18
63 mm 200 mm 30379536 800-20, 801-20, 901-20
80 mm 150 mm 30379541 3000-15, 3001-15, 5000-15
80 mm 150 mm 30379544 5000-15
80 mm 180 mm 30379548 900-18, 2000-18, 3000-18, 3001-18, 4000-18, 5000-18,
80 mm 200 mm 30379542 900-20, 1200-20, 1201-20, 2000-20, 3000-20, 3001-20, 4000-20,
5000-20, 8000-20, 2020
80 mm 230 mm 30379543 1200-23, 1201-23,2000-23, 4000-23, 5000-23, 8000-23, 2023
85 mm 180 mm 30379538 4000-18
90 mm 180 mm 30379549 8000-18HPR, 4000-18
85 mm 200 mm 30379540 1001-20
90 mm 200 mm 30379550 4000-20
85 mm 230 mm 30379539 1001-23, 4000-23
85 mm 250 mm 30364756 2525 S0044.eps

Service Manual 681


HOME PRINT
SERVICE TRAINING
Special Tools

Piston Installation Tools for completely installed. Attempting to install the piston
without this tool can cause damage to the piston rings.
Differential Cylinders
Because the differential cylinders are designed with a To obtain any of these tools, find the proper sized tool
counter bore, it is extremely difficult to install the for your application from the chart below, and contact
differential piston while compressing the piston rings our Spare Parts Department to place your order.
at the same time. These piston intalling tools have a
taper at the mouth of tool to help compress the piston
rings and keep them compressed untill the piston is

Ordering Chart
Piston Item
Diameter Number Description

70 mm 10061734 PISTON INSTALLING TOOL 70MM


80 mm 10061732 PISTON INSTALLING TOOL 80MM
90 mm 10061733 PISTON INSTALLING TOOL 90MM
120 mm 10061737 PISTON INSTALLING TOOL 120MM
125 mm 10061736 PISTON INSTALLING TOOL 125MM
130 mm 10061735 PISTON INSTALLING TOOL 130MM
150 mm 10103894 PISTON INSTALLING TOOL 150MM

S0045.eps

682 Service Manual


HOME PRINT
SERVICE TRAINING
Special Tools

Gland Packing Installation Tools pushed into the mouth of the guide bushing and then
pushed completely into position by using the packing
for Differential Cylinders tool as a slide-hammer.
Important! Reference SAIE 5221 regarding proper To do this, first * lightly lubricate the inside radius of
shimming, in "Rock Valve" section in this Service the packing tool to avoid scratching the rod surface.
Manual. Then gently slide the packing tool along the rod
The gland packing tools are designed to aid in surface, drawing away from the seal and then back to
installing the gland packing seal kit (chevrons) into the the seal; again and again tapping it a little further in
guide bushing of the diff cylinder. The packing tool with each slide until the packing section is completely
has a "V" groove machined into one end to fit the shape home.
of the individual seals of the packing set. The guide NOTE: do not attempt to insert all seal sections at the
tool is beveled on one end forcing the hard edge of the same time. Rather, remove both tools from the rod and
seal section to compress thus providing easy check the seal section you just installed to be sure it did
installation into the bushing. not catch on the mouth of the guide bushing and roll
To properly use these tools together, first * lightly inside-out. If seal appears correctly installed, repeat
lubricate the inside radius of the guide tool and also the this exact procedure with the remaining seal sections,
rod surface. Then insert the guide tool onto the rod * but do not reapply any more lubricant.
with beveled edge facing outward. Now take one * To avoid trapping air or lubricant between the
section of the packing set and slide it onto the piston packing sections, we recommend using a silicone spray
rod all the way to the beveled edge of the guide tool. lubricant, if oil is used, be careful not to over-lubricate
Slide the packing tool onto the rod, with "V" groove any surfaces or seal sections.
inward mating the "V" groove with the curvature of the
seal section. Using a rubber mallet, softly strike the flat
end of the packing tool to start the seal section into the To obtain any of these tools, find the proper sized tool
guide tool. for your application from the following chart, and
contact our Spare Parts Department to place your order.
With this seal section inside the guide tool, check to
be sure the guide tool is resting flush with the guide
bushing of the diff cylinder. Now the section can be

PACKING TOOL GUIDE TOOL


S0046.eps
Ordering Chart
Bushing Diameter of Rod Diameter of Item Number Item Number
Differential Cylinder Differential Cylinder Guide Tool Packing Tool
90 mm 50 mm 30378922 30378926
125 mm 80 mm 30378923 30378927
120 mm 80 mm 30378924 30378927
150 mm 90 mm 30378925 30378929
120 mm 85 mm 30356740 30356741

Service Manual 683


HOME PRINT
SERVICE TRAINING
Special Tools

Seal Replacement Tools Bushing Installation Tool


Piston Seal Guide Tool Rock Shaft Bushing Installation Tool
This tool is designed to aid in installing the piston seal This 4 piece tool aids in removal and installation of the
onto the piston rod of the Rock Valve Shifting brass bushings that are pressed into the rock valve
Cylinder. The tool allows the piston seal to stretch housing and housing cover. This tool works for both
uniformly to the diameter size of the piston and then be the short rock and long rock models. This tool prevents
easily slid into the groove of the piston rod. damage to the bushings by eliminating any need to
pound the bushings into place. With the rock housing
cover bolted into place, a bushing is placed between
one of the tools plates and the rock housing. The
tools other plate is placed onto the tools threaded rod
between the opposite end of the rock housing and the
tools threaded nut. The threaded nut is then slowly
wrenched onto the rod, drawing the brass bushing into
its place in the rock housing.

S0054.eps

Piston Seal Guide Tool


Schwing Part#..........................................30313746
Schwing Part# (150mm)..........................30356740

Piston Seal Form Tool


This tool, much like the piston installation tool for
differential cylinders, has a taper at the mouth to
compress (form) the piston seal and keep it formed
until the piston is completely installed into the rock
shifting cylinder barrel. The tool prevents the piston
seal from damage due to rolling.

S0056.eps

S0055.eps
Tool, Installation, 95 mm Rock Shaft Bushing
Piston Seal Form Tool Schwing Part#..........................................10013417
Schwing Part#..........................................30313745
Schwing Part# (150mm)..........................30356741

684 Service Manual


HOME PRINT
SERVICE TRAINING
Special Tools

Accumulator Charging Kit Technition Support Kit

100

50 1
50
150
100 0 20
0 00
50 25
0 00
30
00
0 35 20
00 0

25
0
S0163.eps

S0164.eps

O-Ring O-Ring O-Ring O-Ring


13 X 2 25.12 X 1.78 37.69 X 3.53 21 X 26
10061730 10000442 10166320 10004056

O-Ring - 48 X 55
O-Ring O-Ring O-Ring 10004053
12 X 5 22 X 2.5 34 X 2.5
10000205 10061728 10077601 O-Ring - 56.74 X 3.53
Accumulator Charging Kit 10118767

O-Ring Flat Ring O-Ring O-Ring


Schwing Part# .........................................30355436 10.77 X 2.62 19.5 X 24 X 1 32.93 X 3.53 52 X 4
10000175 10002827 10000497 10000721

O-Ring O-Ring O-Ring O-Ring

Adjustment Meters for Analog 9.19 X 2.62


10000155
18.72 X 2.62
10000361
32.92 X 3.53
10068689
47.2 X 3.53
10015089

Proportional Cards O-Ring


9X2
10016731
O-Ring
17 X 2.5
10061729
O-Ring
32 X 2.5
10000489
O-Ring
44 X 3
10000677

O-Ring O-Ring O-Ring O-Ring


Analog Adjustment Meter 8.73 X 1.78
10000151
15.54 X 2.62
10067850
27 X 2.5
10077249
38 X 4
10000652

Drawer 1
Toggle Switch ON/OFF/ON Toggle Switch ON/ON Corrosion Inhibitor Press Out Tool - Harting
1TL 1-8 2TL 1-3 30346014 10083751
30315771 30341455

Crimp Pin - 0.5 MM


10022656
Toggle Switch ON/ON Toggle Switch ON/OFF/ON
1TL 1-3 2TL 1-7
30315770 30333041 Crimp Pin - 1.5 MM
10013423

Toggle Switch ON/OFF/ON Toggle Switch ON/OFF/ON Crimp Pin - 0.5 MM


1TL 1-1 1TL 1-7 10013422
30314009 30324217
Press Out Tool - Burndy
10028823

Toggle Switch OFF/ON Toggle Switch ON/ON Crimp Bushing - 0.5 MM


1TL 1-2 4TL 1-3 10013421
30333040 30324215

Fuse, 80 AMP E-stop Contact Crimp Bushing - 1.5 MM


30348131 303038211 10013420

S0052.eps Drawer 2
Adjusting Device Technition Support Cabinet
Schwing Part# .........................................30321192 Schwing Part#..........................................30366963

Service Manual 685


HOME PRINT
SERVICE TRAINING
Special Tools

Electrical Tools and connectors. The kit includes an ejection tool for
removing and inserting the contacts into the
Accessories connectors. The kit also includes a crimping pliers
Schwing America Inc. is offering an Electrical Service with interchangeable jaw inserts that adapt to both
Kit for the repair of electrical connections in cables and styles of connector contacts. All the following pieces
connectors. This kit enables a wide range of repairs to of this kit are contained in a painted metal box with a
Schwing electrical equipment. The kit includes crimp plastic divider tray and may be ordered separately or as
style pin and bushing contacts for the BURNDY brand a complete kit.
electrical connectors as well as the HARTING brand

Part Description Item Number


Service-Kit (complete) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10083745

Item # Qty Part Description Item Number


1 1 Crimping tool w/exchangeable inserts . . . . . . . . . . . . . . . . . . . . 10083746
2 1 Insert for "Burndy" contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10083747
3 1 Insert for "Harting" contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10083748
4 1 Insert for insulated pin and socket connections . . . . . . . . . . . . . 10083749
5 1 Insert for un-insulated pin and socket connections. . . . . . . . . . . 10083750
6 1 Ejection tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10083751
7 25 Contact (crimp style pin), 0.32-0.52 qmm. . . . . . . . . . . . . . . . . . 10030557
8 25 Contact (crimp style bushing), 0.32-0.52 qmm . . . . . . . . . . . . . . 10030558
9 5 Contact (crimp style pin), 0.52-1.5 qmm. . . . . . . . . . . . . . . . . . . 10027381
10 5 Contact (crimp style bushing), 0.5-1.52 qmm . . . . . . . . . . . . . . . 10027382
11 25 Contact (crimp style pin), 0.5 qmm . . . . . . . . . . . . . . . . . . . . . . . 10013422
12 25 Contact (crimp style bushing), 0.5 qmm . . . . . . . . . . . . . . . . . . . 10013421
13 5 Contact (crimp style pin), 1.5 qmm . . . . . . . . . . . . . . . . . . . . . . . 10013423
14 5 Contact (crimp style bushing), 1.5 qmm . . . . . . . . . . . . . . . . . . . 10013420
15 2 Connector guide pin, M3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10013424
16 2 Connector guide bushing), M3 . . . . . . . . . . . . . . . . . . . . . . . . . . 10013425
17 10 Blade terminal, female (RED), 6.3 x 1.0 qmm . . . . . . . . . . . . . . 10007591
18 10 Blade terminal, female (BLUE), 6.3 x 2.5 qmm . . . . . . . . . . . . . 10007297
19 10 Blade terminal, female (RED), 2.8 x 0.5 qmm . . . . . . . . . . . . . . 1000772
20 10 Butt connector (RED), 0.5-1.0 qmm . . . . . . . . . . . . . . . . . . . . . . 10013447
21 10 Butt connector (BLUE), 1.0-2.5 qmm. . . . . . . . . . . . . . . . . . . . . 10012176
22 10 Ring terminal (RED) M4, 0.5-1.0 qmm . . . . . . . . . . . . . . . . . . . . 10007299
23 10 Ring terminal (RED) M6, 0.5-1.0 qmm . . . . . . . . . . . . . . . . . . . . 10022491
24 10 Ring terminal (BLUE) M4, 1.0-2.5 qmm . . . . . . . . . . . . . . . . . . . 10007301
25 10 Ring terminal (BLUE) M6, 1.0-2.5 qmm . . . . . . . . . . . . . . . . . . . 10007295
26 100 Conductor end sleeve (WHITE), 0.75 qmm . . . . . . . . . . . . . . . . 10012648
27 100 Conductor end sleeve (YELLOW), 1.0 qmm . . . . . . . . . . . . . . . 10012917
28 100 Conductor end sleeve (RED), 1.5 qmm . . . . . . . . . . . . . . . . . . . 10012649
29 100 Conductor end sleeve (BLUE), 2.5 qmm . . . . . . . . . . . . . . . . . . 10012650
30 10 Blade terminal, female, 6.3 x 1 . . . . . . . . . . . . . . . . . . . . . . . . . . 10014953
31 10 Blade terminal, male, 6.3 x 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . 10009698
32 10 Blade terminal, male, 6.3 x 2.5 . . . . . . . . . . . . . . . . . . . . . . . . . . 10009701
33 10 Blade terminal, male, 2.8 x 0.5 . . . . . . . . . . . . . . . . . . . . . . . . . . Not on File
34 1 Steel box with higged cover and divider tray. . . . . . . . . . . . . . . . 10083752

686 Service Manual


HOME PRINT
SERVICE TRAINING
Special Tools

Spanner Socket Tools for Boom life of the boom pin nuts by preventing the need to
hammer the nuts on and off with a drift. To order these
Pins tools, find the sizes for your machine from the chart
The spanner socket tools are designed to remove and below, and contact the Schwing America Spare Parts
install the round, notched nuts which thread onto Department with the corresponding part number:
certain boom pins. These handy sockets prolong the

Ordering Chart
Boom Item
Pin Nut Number Tool Description

66 mm/2.596" 30331885 FOUR LUG NUT SOCKET (3/4" Drive)


99 mm/3.879" 30331886 FOUR LUG NUT SOCKET (3/4" Drive)
69 mm/2.702" 30331887 SIX LUG NUT SOCKET (3/4" Drive)
95 mm/3.745" 30334225 SIX LUG NUT SOCKET (3/4" Drive)
110 mm/4.350" 30331884 SIX LUG NUT SOCKET (3/4" Drive)
135 mm/5.334" 30331883 SIX LUG NUT SOCKET (3/4" Drive)

S0059.eps

Service Manual 687


HOME PRINT
SERVICE TRAINING
Special Tools

Truck Engine Tools Micellaneous Tools


Pro-Link 9000 Whip Hose and Fittings
The Pro-Link 9000 is a microprocessor-based test
instrument designed to tap into the vehicles on-board 1 or 2
computer. Its programmed to communicate with the
engine and/or transmission and ABS(Anti-lock Brake
System) and provide readouts you can use for
diagnostics. You have instant access to any of the 3
vehicles operating data as long as the Pro-Link 9000 is
5
connected to the vehicle.
4
The Pro-Link 9000 can be used on V-MacII/E-tech,
Detroit Diesel, Navistar and Cummins engines, as well
as CEEMAT and Allison transmissions.

POS. DESCRIPTION PART #


1 GAUGE (0-40 Bar) 10012414
2 GAUGE (0-400 Bar) 10004662
3 GAUGE CONNECTOR 10018990
4 WHIP HOSE 10018991
5 GAUGE PORT 10020459
S0053.eps

Rock Valve Cover Alignment


+

9 _
8 6 +
7 5 3
4 2
1
O

S0062.eps

Schwing Part# (Small Rock valve)..........30309007


Schwing Part# (Standard Rock Valve).....30304515
For ordering information contact:

Kent-Moore
Heavy Duty Division
29784 Little Mack
Roseville, MI 48066-2298
1-800-328-6657

MPSI
Micro Processor System, Inc.
6405 Nineteen Mile Road
Sterling Heights, MI 48314
1-810-731-6410

688 Service Manual

Anda mungkin juga menyukai