Anda di halaman 1dari 1

CURRENT IN AMPERES

100K
100

10K
1K

1M
0.5 1 10
1000
BAS 50/51 (N) MAIN SWGR - Phase
PECO RELAY - Phase
CBL-0002
CBL-0001

100

Device: SUB A-B (N) FUSE


ECL155, 15.5kV E-Rated
125A
Settings Phase
125.0 Amps

Device: BAS 50/51 (N) MAIN SWGR


Device: PECO RELAY 10
BE1-50/51B, Series 200 (ABB)
751A
Settings Phase
Settings Phase
Pickup 5 (600A)
51P1P, (0.5-16 x CTR) 5 (600A)
I, Inverse 0.7
U3, Very Inverse 3.0

TIME IN SECONDS
INST 27 (3240A)
50P1P, (0.5-100 x CTR) 35.03 (4203.6A)
F, Fixed Time 1.5
50P1D, (0.001 - 5s) 3.28

UTIL-0001
Name CBL-0002
Size 4/0 AWG/kcmil 1

13200.0 V
Qty/Ph 1
SEL SC 3P 3558.0 Amps
751A SC SLG 2890.0 Amps

PECO RELAY

Name CBL-0001
CBL-0001
1 - #4/0 AWG/kcmil, 760 ft Size 4/0 AWG/kcmil
BAS 50/51 (N) MAIN SWGR Qty/Ph 1
BASLER
BE1-50/51B, Series 200 (ABB)

MAIN CB.
CUTLER-HAMMER
VCP-W

MAIN OUTDOOR SWGEAR


0.10
13200V

SUB A-B (N) SW.

SUB A-B (N) FUSE


BUSSM1
ECL155, 15.5kV E-Rated
125AS

CBL-0002
1 - #4/0 AWG/kcmil, 760 ft

SUB A-B (N) SW

SUB A-B (N) /RE BUS

13200V
0.01

Eaton Electrical Services and Systems Plot name: TCC-0X1 PECO UTIL RELAY TO SUB A-B(N) PHAS
March 30, 2017 Ref. Voltage: 13200V
Current Scale: x 1

3-6