T6818DP04

Digital Thermostat
Data Sheet

Features

Cabinet compact design with primary


white appearance, suitable for office,
hotel and residential building

One type cover 2-pipe and 4-pipe appli-


cation

Digital LCD with Kelly backlight

Independent installation on 86 size box

Application Easy to install and set-up

Adjustment of display room temperature


T6818DP04 digital thermostats are designed
for application of 3-speed fan and valves in 2-
pipe and 4-pipe fan coil system. Including: Temperature unit either C or F

2-pipe cool only/heat only/Heat/Cool Manual Keypad lock in Installer Set-Up


changeover
4-pipe heat/cool Manual /Auto changover End user configuration could be kept
Ventilation mode when power lost
Manual/Auto 3-speed fan control

Operation voltage Manual/


Item Backlight 2pipe/4pipe Ventilation Automation Fan
VAC

T6818DP04 Kelly 2/
/4pipe 220V Y Y

1
Mechanical De- In automatic mode, fan speed depends on the
difference between room temperature and set-
point. When room temperature reaches
setpoint, valve will be closed and meanwhile,
fan will be closed either.

Fan speed is high or off

Difference between RT and SP

COOL
4F
Fan speed is medium or off
2F
Fan speed is low or off
Setpoint
Fan speed is low or off
-2F
Fan speed is medium or off
LCD Display
-4F

HEAT
Fan speed is high or off

Temperature display
The displayed temperature can be set to dis-
play room temperature or setpoint.
The setting can be made during ISU process.

Backlight
Pressing any key will activate the backlight.
Backlight will turn off after 8 seconds. When in
ISU mode or Installer test mode, the
backlight will turn off after 60 seconds
without operation.
Function
Valve control Ventilation
Thermostat acquires the room temperature via
its integrated sensor and maintains the set- Pressing Modeenter ventilationFan speed
point by delivering on/off output. can be selected to automatic or manual
3-speed control mode.
Fan Operation
Fan can be selected as manual or automatic Keypad lock
3-speed operation. In Manual mode, the fan is The default status of Keypad Lock is all keys
switched to the selected speed via control available and it can be changed in ISU mode.
output Gh, Gm, Gl. Keypad lock has the following settings:
All keys are available (Default)
System button is locked out
Fan and System button are locked out
All buttons are locked

2
L L
Technical specification
N N
Gh
Power supply 220VAC Gm Fan
Fan
10%,50Hz Gl
W/Y Cool valve
Control algorithm PIon/off output
Y
Accuracy +/-1C at21C
Fig.2.2 Typical wiring for 2 pipes
Load rating Fan 4(2)AValve 2(1)A cooling only
Relay life 100000 times L L
Setpoint range 10-32C N N
Installation 8686mm box Gh
Protection class IP20 Gm Fan
Fan
Environmental Gl
Operation temp. -18C~49C W/Y valve
Shipping temp. -35C ~65C Y
Relative humidity 5~95%
Recomm.Wire Dia Min 0.75mm2 Fig.2.3 Typical wiring for 2 pipes
1 stage Heat or 1 stage Cool MCO

L L
N
Terminal Designations N
Gh
Gm Fan
Fan
Terminal Description Gl
W/Y Heat valve
L Line Voltage Power
Y Cool valve
N Neutral Voltage Power
Fig.2.4 Typical wiring for 4 pipes
1 stage Heat /1 stage Cool MCO/ACO
Gh High speed fan Operating modes
`

Gm Medium speed fan


Gl Low speed fan 1. Power On/Off

W/Y Heating open/cooling open Press the POWER button to switch thermo-
Y cooling open stat to the On/Off mode.

2. Fan switch
Wiring diagrams(*
(*VC4013)
(*
Press the FAN button to select Fan mode
Low , Med , High or Auto.
L L
N N 3. System Mode Setting
Gh
Gm Faf`
Fan
Press the MODE button to choose Heat ,
Gl
Cool or Vent mode.
W/Y Heat valve
4. Temperature Setting
Y
In Heat/Cool mode press the UP or DOWN
Fig.2.1 Typical wiring for 2 pipes
heat only button to select the desired temperature set-
3
ting.
Installation & Commission- Troubleshooting Tips

If Then

Heating system does Set the mode to Heat by pressing the Mode button.
not turn on. Check if the heat temperature setting is above the room temperature.
Wait five minutes, for the heating system to respond.

Cooling system does Set the Mode button to cool by pressing the Mode button.
not turn on. Check if the cool temperature setting is below the room temperature.
Wait five minutes, for the cooling system to respond

The Mode button Check whether the keypad is locked or not.


doesnt work. Check whether the thermostat is off.

Check whether the keypad is locked or not.


The Up or Down
Check whether the system is working in Ventilation mode.
button doesnt work.
Check whether the thermostat is off.

Dimension

4
Installation and Commission

ISU Setup
Press and hold MODE and UP buttons for 3 seconds to enter (or exit) Installer
Setup (ISU) mode.
In ISU mode press MODE button to change item number and press UP/DOWN but-
ton to change the value.

No. Description Possible Options


No. Description Possible Options

0 Heat only

1 Cool only

-2 C( 4 F)

1 System type 2 Two pipes 1H1C manual


4 Four pipes Manual Changover
-1.5 C( 3 F)

5 Four pipes Auto Changover (Default)



-1 C( 2 F)

Temperature
0 F

-0.5 C( 1 F)
2
scale Display
1 C (Default) 6 Temperature 0 C (0 F) (Default)
adjustment
0 Auto only 0.5 C(1 F)

Fan Control
3 1 Constant only 1 C(2 F)
Type

2 Both (Default) 1.5 C(3 F)

1 2 C(4 F)

2 0 Display Room Temperature(Default)


Temperature
7
Display mode
3 1 Display Setpoint

Heating Range
4 (Default) 8 10-32 C Default 32 C (50-90 F Default 90 F)
Stops

Cooling Range
5 9 10-32 C Default 10 C (50-90 F Default 50 F)
Stops

6 0 All keys available (Default)


CPH value For
4
Heat
7 1 MODE button is locked out

Keypad
8 10 2 FAN and MODE buttons are locked out
Lockout

9 3 All buttons are locked out except POWER button

10 4 All buttons are locked out

11 0 OFF (Default)
Power recovery
11
status
12 1 Previous status

1 1 C (2 F)

2 12 Deadband 1.5 C (3 F) (Default)


for ACO 2 C (4 F)
2.5 C (5 F)
3 (Default) 3 C (6 F)
CPH value For
5
Cool
4

35FTower A, City Certer 100 Zun Yi Road


Shanghai , 200051, China
Tel+
+86 021-52574568-6549
Fax+
+86 021-62372825
5