2013 IEEE Asia Pacific Conference on Postgraduate Research in Microelectronics and Electronics (PrimeAsia)

Voltage quality improvement and harmonic mitigation using custom power


devices : DVR and Hybrid filters

M.Sharanya1 Dr.B.Basavaraja2 Dr M.Sasikala3


Associate professor,Department of EEE HOD & Professor, EEE Department Professor, EEE Department
Vignana Bharathi Institute of Technology GITAM University Hyderabad Campus, CVR College of Engineering
Ghatkesar, Hyderabad, India. Hyderabad, India. Ibrahimpatnam, Hyderabad, India
sharanya2702@gmail.com banakara36@gmail.com sasi_mun@rediffmail.com

Abstract - The various power quality issues are of an injection transformer and restores the quality of
great concern now a days. The quality of power power.[11]
provided to the consumers can be improved by Harmonics problem are usually resolved by the use
using custom power devices, (CPD). CPD uses of conventional passive and active filters. LC filters
power electronic controllers in distribution systems which are the conventional passive filters, can
in order to provide reliable and good quality of compensate reactive power with harmonics and has
power needed to power consumers. This paper simple structure and is of low cost.[7] Passive
gives that the use of Dynamic voltage restorer and filters has disadvantages like resonance problem,
hybrid active filters improves the quality of power large size, fixed compensation, tuning problems
by voltage profile improvement and by the etc. To overcome these problems active power
mitigation of harmonics in the supply current. The filters are used.
DVR and hybrid filters are controlled by using PI Active filters are controlled for removing the
controllers. The system is modelled by using harmonics and making the current of the
MATLAB/SIMULINK software and performance distribution system sinusoidal by producing
is observed. currents according to non-sinusoidal current of
Key words : custom power devices, CPD, DVR, loads or system. But its cost increases with the
Hybrid filters, MATLAB increase in the ratings. Hybrid filters which is the
combination of passive and active filters are used to
I INTRODUCTION mitigate the harmonics problems and to have the
The power quality problems are transients, voltage advantages of both these filters.
sag, harmonics, voltage swell, very short
interruptions, long interruptions, voltage unbalance, II DYNAMIC VOLTAGE RESTORER (DVR)
voltage fluctuations, voltage spikes and noise. The Dynamic Voltage Restorer (DVR), is
These various power quality problems can be connected in series with primary distribution circuit
mitigated by using various custom power devices. and it uses solid state or static power electronic
CPD involves various power electronic controllers devices and is also known as the Series Voltage
in the low and medium distribution systems to Booster (SVB) or the Static Series Compensator
provide reliable and good quality of power needed (SSC). The DVR restores load voltage to pre
by the consumers disturbance condition by providing three phase
Custom Power Devices are classified as Network controllable voltage, whose vector (magnitude and
reconfiguration devices and Compensation angle) adds to the source voltage [12]. DVR is the
devices. protects the sensitive loads from voltage sags and
Each of these devices has its own advantages and swells of the distribution network. And so is
disadvantages. DVR is a compensating device. It is installed between supply and sensitive load feeders
considered for the mitigation of voltage sags. in distribution system. Other than the compensation
Harmonics and Power Factor correction are the of voltage swells and sags, DVR is used for the
other features of DVR. Because of its small size compensation of line voltage harmonics, fault
and capabilities DVR can be considered current limitations and voltage transients
economically over other devise.[9] The DVR does reductions.[13] A DVR consists of an injection
the injection of voltages in series with the supply transformer, voltage source converter, energy
voltage of required magnitude and duration through storage unit and filter as shown in Fig 1.

978-1-4799-2751-7/13/$31.00 2013 IEEE

213
2013 IEEE Asia Pacific Conference on Postgraduate Research in Microelectronics and Electronics (PrimeAsia)

advantages of active filters and passive filters.[8]


Hybrid filters of different structures can be utilized
in power systems such as series active and shunt
passive filter with nonlinear loads, shunt passive
and active filter with nonlinear load, series passive
and active filter parallel with Nonlinear load, etc as
shown in Fig 2.

Figure 1 Block diagram of DVR

Voltage source converter,VSC is used to generate


part of supply voltage which is missing. Injection
transformer connects the DVR to the distribution
system and converts the voltages from the VSC to
the incoming supply voltage. Passive filter
eliminates the unwanted harmonic components
generated by the VSC The energy storage such as
battery is responsible to supply energy storage in
DC form. A DC link voltage is used by the VSC to
synthesize an AC voltage into the grid and during a
majority of voltage dips active power injection is
necessary to restore the supply voltages. [10]

III HYBRID FILTERS


For most of the industrial applications and
transmission/distribution networks a number of Figure 2 Different structures of hybrid filters
solid state power converters such as diode bridge
rectifiers and thyristor converters are used. These
IV PROPOSED DVR MODEL
power converters are nonlinear in nature and cause
The system considered for the model is
serious problems of , non-sinusoidal supply
generation system of 13 KV, 50HZ. This system
voltage, current harmonics, poor power factor,
feeds two transmission lines which is done with a
reactive power burden and low system efficiency.
three winding transformer connected in Y//
Hence, due to these serious issues there has been an
13/115/115 kV. These transmission lines feeds two
increasing interest in the subject of power quality
distribution networks with two transformers
improvement techniques which can suppress
connected in /Y, 115/11 kV.
supply
Harmonics, improve power factor and balance the
input supply. [8] Harmonics problem are usually TABLE I DVR MODEL PARAMETERS
resolved by the use of conventional passive and
Line Resistance=0.02 Inductance=3.8e-
active filters. Conventional LC passive filters can
compensate reactive power along with harmonics impedance 4H
and has simple structure, low cost .[7] But Passive Pwm Carrier Sampling time=5e-
filters has disadvantages like resonance problem, generator frequency=1080Hz 6
large size, fixed compensation, tuning problems
Sensitive Resistance=40 Inductance=2e-3H
etc. To overcome these problems active power
filters are used. load
Active filters are controlled to make the current of
the distribution system sinusoidal and produce
currents as per the non sinusoidal current of loads
or system for removing the harmonics. But with the
increase in its ratings its cost increases .
Hybrid filters which is the combination of passive
and active filters are used to mitigate the harmonics
problems. Low cost passive filters along with the
active filter, reduces the power rating of active
converter compared to that of pure active filters.
Hybrid filter are cost effective and retains the

214
2013 IEEE Asia Pacific Conference on Postgraduate Research in Microelectronics and Electronics (PrimeAsia)

and with DVR for sag. The Fig5 shows the voltage
with respect to time without DVR. The wave form
shown is a voltage without DVR, sag is happened
to be in between 0.1 to 0.3 sec the max amplitude is
1. Due to fault occurred in the line voltage falls
down to 0.5.This could be rectified by using DVR
system. The Fig 6 shows load voltage where DVR
is connected.

Figure 3 DVR circuit model

In this model i.e Fig 3 the output from generating


unit is fed to the primary of the three winding
transformer. Two parallel feeders are drawn each of
11kv. One feeder is kept as it is and in the other Figure 5 Voltage without DVR (Sag)
feeder DVR is connected in series. The controller
used is a PI controller. The same is shown in the
Simulink model. The DVR is connected to
distribution system through a booster transformer.
Fig 4. Shows the simulink model of DVR .

Figure 6 Voltage with DVR for Sag

B Result analysis
The output voltage for both the conditions of with
DVR and without DVR for swell is shown in the
Fig 7 and Fig 8. The Fig7 represents voltage with
respect to time without DVR. The wave form
shown is a voltage without DVR, where swell is
happened to be in between 0.1 to 0.3sec and the
max amplitude is 1. Due to fault occurred in the
line, voltage rises to 1.5.This could be rectified by
using DVR system. The Fig 8 is for voltage where
DVR is connected.
Figure 4 Simulink model of DVR

A Result analysis
Result for the DVR system in which the fault is
created is given below. Fig 5 and Fig 6 shows the
output voltage for both the conditions without DVR

215
2013 IEEE Asia Pacific Conference on Postgraduate Research in Microelectronics and Electronics (PrimeAsia)

0.25 : 33.30 mH: 6.55 F (L2 : C2) 0.2 : 14.80


mH: 18.5F (L3 : C3) 0.2 : 11.24 mH: 19.40F

Figure 7 Voltage without DVR for Swell

Figure 9 Simulink circuit of passive filter

A Result analysis

Figure 8 Voltage with DVR for Swell The proposed HAPF controller simulation results
are presented to show the performance
characteristics. Load compensation is done by a
rectifier with high nonlinear characteristics. To
V PROPOSED HYBRID FILTER check the effectiveness of the proposed controller
The simulation results of the proposed hybrid its performance is analysed with PF alone and with
active power filters, HAPF controller are taken for HAPF which has both APF and PF.
sinusoidal voltage at various operating conditions
and presented to show the performance Fig.10 shows the source current, filter current and
characteristics. Load compensation is done by a load current when only passive filter is connected.
rectifier with high nonlinear characteristics. To The injected filter current at the point of common
check the effectiveness of the proposed controller coupling is of the required magnitude which makes
its performance is analysed with PF alone and with the current drawn from the source nearer to
APF and PF. sinusoidal wave.

The parameters used for the simulation study are as


given below : Sinusoidal source voltage(Vs) 220V
peak , 50 Hz. Source Impedance(Rs : Ls) 0.15 : 0.1
mH. Smoothing Impedance(Rsm : Lsm) 0.1 : 0.5 mH
Load Impedance (RL : LL) dc-side of the uncontrolled
rectifier 7.5 : 25 mH. Active filter parameters :
Filter Impedance (RC : LC) 0.15 ohm : 2.5 mH .DC-
link capacitor values (Vdcref : Cdc) 250V: 1600 F.
Three tuned passive filter parameters : (R1: L1: C1)

216
2013 IEEE Asia Pacific Conference on Postgraduate Research in Microelectronics and Electronics (PrimeAsia)

B Result analysis

Fig.12 shows the source current, filter current and


load current when both active and passive filter are
connected. The injected filter current at the point of
common coupling is of the required magnitude
which makes the current drawn from the source
nearer to sinusoidal wave. The filter is controlled
by using the PI controller.

Figure 10 Source current, Filter current and Laod current with


only passive filter

The circuit model of Hybrid filter with both passive


and active filter is shown in fig 11

Figure 12 Source current, Filter current and load current with


Hybrid filter

CONCLUSION
This paper shows that by using a dynamic voltage
restorer and hybrid filter the power quality in the
distribution network can be improved. Voltage sag
and swell are mitigated using dynamic voltage
restorer. The design and comprehensive results for
voltage sag and swell of DVR is presented. The
simulation results shows that the performance of
DVR is satisfactory in mitigating sag/swell.
Simulation results also show that the DVR has fast
response and it very quickly compensates these
disturbances and provide excellent voltage
regulation. To reduce the harmonics passive filter,
Figure 11 Simulink model of Hybrid filter active filter, hybrid filter etc. are developed. The
simulation results are shown for passive filter alone
and with HAPF which is the combination of both
passive and active filters. The simulation results

217
2013 IEEE Asia Pacific Conference on Postgraduate Research in Microelectronics and Electronics (PrimeAsia)

show that the shunt HAPF is much superior in active filter. The single phase HAPF is
performance compared to only passive or only
implemented in simulation as combination of
shunt passive filter and shunt active filter. These
are controlled by using the PI controllers.
single phase rectifier, ACEEE International jounal
on Electrical and power engineering, Feb 2012.
[8] K. Triveni Krishna, Aswani Kumar Eedara,
Hybrid series active power filters for by using PI
References : andfuzzy controller, International journal for
[1] Yen-Ching Wang, Tzung-Lin Lee, A control engineering and science research, Vol 2 Issue 11,
strategy of hybrid active filter to compensate Nov 2012.
unbalanced load in three phase three wire power [9] Himadri Ghosh, Pradip Kumar Saha, Goutam
system, 3rd IEEE international symposium on Kumar Panda, Design and Simulation of a Novel
power electronics and distributed generation Self Supported Dynamic Voltage Restorer (DVR)
systems, 2012. for Power Quality Improvement, International
[2] P. Salmern and S. P. Litrn, Improvement of Journal of Scientific & Engineering Research,
electrical power quality using series active and Volume 3, Issue 6,june2012.
shunt passive filters, IEEE transactions on power [10] Dominik viglas, anton belan, zaneta eleschova,
delivery, Vol 25 No 2, Apr-10. peter janiga, Implementation of Dynamic voltage
[3] Ionel vechiu, Gelu gurguiatu, Emil rosu, restorer for mitigation of voltage sags in the
Advanced active power conditioners to improve distribution system, Advances in Computer
power quality in microgrids, IEEE IPEC, 2010 Science.
[4] Alexander Varschavsky, Juan Dixon, [11] Anita Pakharia, Manoj Gupta, Dynamic
Cascaded nine level inverter for hybrid series voltagerestorer for voltagesag and swell: A
active power filters using industrial controller, literature review, International Journal of
IEEE transactions on industrial electronics, VOL. Advances in Engineering & Technology, Vol 4
57, NO. 8, aug 2010. Issue 1, july2012.
[5] R. D. Patidar, S. P. Singh, A single phase [12] Mahmoud A. El-Gammal, Amr Y. Abou-
hybrid filter to improve power quality, XXXII Ghazala, and Tarek I. El-Shennawy, Dynamic
National systems conference, 2008. Voltage Restorer (DVR) for Voltage Sag
[6] melchor gmez, miguel ngel cmara, emilio Mitigation, International Journal on Electrical
jimnez, eduardo martnez-cmara, Engineering and Informatics, Vol 3, No 1, march
Custom power equipment to facilitate the 2011.
penetration of embedded generation in distribution [13] Md. Riyasat Azim, Md. Ashraful Hoque, A
networks. FuzzyLogic based DynamicVoltageRestorer for
[7] Thirumoorthi P and Yadaiah N, Mitigation of Voltage Sag and Swell Mitigation for Industrial
harmonic current through hybrid power filter in InductionMotor Loads, International Journal of
Computer Applications, Vol 30 No.8, Sep-11