Anda di halaman 1dari 3

MATINDOK GAS DEVELOPMENT PROJECT

(MGDP)

CHECK LIST SYSTEM RAMP UP

No Check List Ramp Up /x Remarks


Preparation
1 Mechanical Completion for All System (lube oil lubrication, PLC, For initial start up
loop test, function test, merger test, continuity test, etc) has been only
achieved.
2 PSSR has been finished. For initial start up
only
3 Pilot Main Flare is in good condition.
4 Booster Compressor System, AGRU, DHU, and DPCU are in service.
5 Auto start Hot Oil Circulation Pump hasnt been activated
6 All wellheads are ready to be operated.
Execution
1 Minimum list operating condition downstream Booster
Compressor (330-C-1001) to be monitored:
a. HP Separator (320-D-1002) pressure 320-PT-1012 is 520 psig.
b. Wellhead gas flowrate 320-FT-1007 downstream HP Separator
(320-D-1002) is minimum 26 MMSCFD.
c. Wellhead gas temperature enters AGRU 360-TIC-3001
downstream Feed Gas Propane Chiller (340-E-1008) is 77.4F.
d. Main Absorber (340-T-1001) buttom pressure is 903 psig.
e. Stripper Column (340-T-1003) bottom temperature 340-TI-
1015 is 274F.
f. Amine circulation flow rate enters Main Absorber (340-T-1001)
340-FT-1001 is 50% design
g. H2S content 340-AI-1004 A1 downstream Sweet Gas KO Drum
(340-D-1002) is 1 ppmv.
h. CO2 content 340-AI-1003 B1 downstream Sweet Gas KO Drum
(340-D-1002) is 20 ppmv.
i. Glycol Contactor (350-T-1001) pressure 350-PDT-1005 is
886.27 psig.
j. Glycol Circulation flow rate from DHU panel is 5.2 gpm(50%
design)
k. DPCU pressure 360-PT-1010 is 853 psig.
l. Hot Oil Circulation flow rate 371-FT-1002 A/B.
m. Hot Oil Temperature downstream Hot Oil Fired Heater (371-F-
1001) is 349F
n. HP Fuel Gas flow rate enters Produced Water Stripper (378-T-
1001) 378-FT-1001 upstream Produced Water Stripper (378-T-
1001) is 0.23 m3/h.
o. BSRU circulation flow rate enters H2S Absorber (340-T-1004)
340-FT-1019 is 175 m3/h (50% design) if BSRU is in circulation
phase.

Page 1 of 3
MATINDOK GAS DEVELOPMENT PROJECT
(MGDP)

CHECK LIST SYSTEM RAMP UP

2 Contact subsurface personel to increase wellhead gas flow rate to


Matindok CPP.
3 That additional wellhead gas is flare at 320-PV-1004 downstream
HP Separator (320-D-1002).
4 Increase:
a. Amine circulation flow rate by inputting new set point to 340-
FT-1003.
b. Glycol circulation flow rate by inputting new set point Glycol
Circulation Pump (350-P-1001) at DHU panel.
c. HP Fuel Gas flow rate enters Produced Water Stripper (378-T-
1001) by inputting new set point to 370-FT-1002 upstream
Produced Water Stripper (378-T-1001).

Correlation of amine, glycol, and HP Fuel Gas flow rate to wellhead


gas is based on table below:
Wellhead Gas Amine Glycol HP Fuel Gas
(MMSCFD) (m /h) (gpm) flow rate (m3/h)
3

60 109,7 10,4 0,45


55 100,6 9,5 0,41
50 91,4 8,7 0,38
45 82,3 7,8 0,34
40 73,1 6,9 0,30
35 64,0 6,1 0,26
30 54,9 5,2 0,23
25 54,9 5,2 0,23
5 Monitor parameter mentioned at no 1. If those parameters are
stable, then increase wellhead gas flow rate AGRU by inputting
desired flow rate Booster Compressor panel.
6 Monitor parameter mentioned at no1. If those parameters are
stable, then repeat procedure from no 2.

Do this action until 65 MMSCFD is read at 320-FT-1004


downstream HP Separator (320-D-1002).
Variable to be Monitored and Controlled
1 HP Separator (320-D-1002) pressure 320-PT-1002 is 520 psig.
2 Wellhead gas temperature enters AGRU 360-TIC-3001 downstream
Feed Gas Propane Chiller (340-E-1008) is 77.4F.
3 Main Absorber (340-T-1001) pressure is 903 psig.
4 Stripper Column (340-T-1003) bottom temperature 340-TI-1015 is
274F.
5 Amine circulation flow rate enters Main Absorber (340-T-1001)
340-FT-1001 is 50% design
6 H2S content 340-AI-1004 A1 downstream Sweet Gas KO Drum

Page 2 of 3
MATINDOK GAS DEVELOPMENT PROJECT
(MGDP)

CHECK LIST SYSTEM RAMP UP

(340-D-1002) is 1 ppmv.
7 CO2 content 340-AI-1003 B1 downstream Sweet Gas KO Drum
(340-D-1003) is 20 ppmv.
8 Glycol Contactor (350-T-1001) pressure 350-PG-1005 is 886.27
psig.
9 Glycol circulation flow rate from DHU panel is 10.4 gpm.
10 DPCU pressure 360-PT-1010 is 850 psig.
11 Hot Oil temperature downstream Hot Oil Fired Heater (371-F-
1001) is 350F.
12 HP Fuel Gas flow rate enters Produced Water Stripper (378-T-
1001) 378-FT-1001 upstream Produced Water Stripper (378-T-
1001) is 0.45 m3/h.

Page 3 of 3