Anda di halaman 1dari 2

1. A transmission line has a reactance of 1 Pu is operating at Vs = Vr = 1 Pu.

The
generator is connected at source end which is delivering 0.5 Pu of active power. Find
the load angle?
a) 35
b) 30
c) 45
d) 60

2. In a transmission line terminated by characteristic impedance, Zo


(A) There is no reflection of the incident wave.
(B) The reflection is maximum due to termination.
(C) The reflection and refraction of incident wave are equal.
(D) The incident current is zero for any input.
Ans: A
3. What happens in a long transmission lines under no load?
a. The receiving end voltage is less than the sending end voltage.
b. The sending end voltage is less then receiving end voltage.
c. The sending end voltage is equal to receiving end voltage.
d. None of these.
Ans: b
4. A = D = 0.9 0 , B = 200 90 , and C = 0.95 *10-3 90 . At no load
condition a shunt inductive reactor is connected at the receiving end of the line to
limit the receiving end voltage to be equal to the sending end voltage. What is the
ohmic value of the reactor?
a) Infinity.
b) 2000
c) 105.26
d) 1052.6
ANSWER: b. 2000
5. The ABCD parameter of a 3 phase transmission line is given as follows
A = D = 0.8 1 , B = 170 85 , and C = 0.002 90.4 the sending end
voltage is 400 kV. What is the receiving end voltage under no load condition?
a. 400 kV
b. 500 kV
c. 320 kV
d. 417 kV
ANSWER: b. 500 kV