Anda di halaman 1dari 1

Sudden tripping of one or more Control the furnace pressure by adjusting I.D.

mills or choking of mills/raw coal fan vanes. Simultaneously try to start stand by
feeder pipe mill. Remove the chocking of affected mill/raw coal
feed pipe.

Partial flame failure Take the oil gun into service to establish flame at
that locations/corner.

Accidental closing of secondary See the proper functioning of secondary air path
air path damper.

2.11.3.Drum Level Low


Mai-operation of Feed Auto Control Take feed control valve on hand and increase
or Feed Regulator or Scoop auto. feeding rate. Take scoop tube control on hand and
increase scoop tube position. Check that feed
water flow through each pump does not exceed }ts
capacity. Check feed water control valve and scoop
tube control linkages.
Tripping of one of working feed Start reserve feed pump on tripping of running
pump (standby pump does not start) feed pump, if auto starting fails.
Sudden reduction of load Try to increase the load if not possible reduced
firing irate accordingly to control drum pressure.
Sudden increase in firing e.g. Reduce firing rate by suitably adjusting the feeding
starting of mills having rate of running mills.
sufficient coal left before previous
stopping.
Tube rupture/puncture Check water flow and compare with previous
feeding rate and steam flow. High feed flow
indicates tube failure. Inspect water wall and econ-
omiser or any tube leakage. If tube leakage is
observed stop the boiler as soon as possible.
Inadvertent opening of low point Check drum drains and low point drain for tight
drain valves or Emergency drum closing.
drain valve.

Note :
If drum level goes below gauge glass and low drum level trip protection fails, trip boiler at once.
2.11.4.High Drum Level

Mal-operation of feed water control Take feed control valve on manual and reduce the
feeding rate.
Sudden increase in load resulting Try to decrease the load as far as possible.
in drum pressure drop.

70

Anda mungkin juga menyukai