Name : Bearing cap.

Stage : 1; Analysis: 1

Delta = 0,00

3,39

2,50 2,50
+x

+y

3,50

Verification of spread footing bearing capacity


Vertical bearing capacity check
Shape of contact stress : rectangle
Most severe load case No. 1. (Load No. 1)

Design bearing capacity of found.soil Rd = 255,93 kPa


Extreme contact stress s = 245,95 kPa
Bearing capacity in the vertical direction is SATISFACTORY

Horizontal bearing capacity check


Most severe load case No. 1. (Load No. 1)

Horizontal bearing capacity Rdh = 601,52 kN


Extreme horizontal force H = 0,00 kN
Bearing capacity in the horizontal direction is SATISFACTORY

Bearing capacity of foundation is SATISFACTORY

[GeoStructural Analysis - Spread Footing | version 5.17.6.0 | Copyright 2013 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]
Spread footing verification
Input data
Project
Date : 30.4.2015
Settings
Standard - EN 1997 - DA1
Materials and standards
Concrete structures : EN 1992-1-1 (EC2)
Coefficients EN 1992-1-1 : standard
Settlement
Analysis method : Analysis using oedometric modulus
Restriction of influence zone : by percentage of Sigma,Or
Coeff. of restriction of influence zone : 10,0 [%]
Spread Footing
Analysis for drained conditions : EC 7-1 (EN 1997-1:2003)
Analysis of uplift : Standard
Verification methodology : according to EN 1997
Design approach : 1 - reduction of actions and soil parameters
Partial factors on actions (A)
Permanent design situation
Combination 1 Combination 2
Unfavourable Favourable Unfavourable Favourable
Permanent actions : gG = 1,35 [] 1,00 [] 1,00 [] 1,00 []

Partial factors for soil parameters (M)


Permanent design situation
Combination 1 Combination 2
Partial factor on internal friction : gf = 1,00 [] 1,25 []
Partial factor on effective cohesion : gc = 1,00 [] 1,25 []
Partial factor on undrained shear strength : gcu = 1,00 [] 1,40 []
Partial factor on unconfined strength : gv = 1,00 [] 1,40 []
Basic soil parameters
jef cef g gsu d
No. Name Pattern
[] [kPa] [kN/m3] [kN/m3] []

1 tlo 16,23 3,20 18,00 8,00

All soils are considered as cohesionless for at rest pressure analysis.

Soil parameters
tlo
Unit weight : g = 18,00 kN/m3
Angle of internal friction : jef = 16,23
Cohesion of soil : cef = 3,20 kPa
Oedometric modulus : Eoed = 12,00 MPa
Saturated unit weight : gsat = 18,00 kN/m3

Foundation
Foundation type: centric spread footing

1
[GeoStructural Analysis - Spread Footing | version 5.17.6.0 | Copyright 2013 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]
Depth from original ground surface hz = 1,80 m
Depth of footing bottom d = 1,80 m
Foundation thickness t = 0,70 m
Incl. of finished grade s1 = 0,00
Incl. of footing bottom s2 = 0,00
Unit weight of soil above foundation = 25,00 kN/m3

Geometry of structure
Foundation type: centric spread footing
Spread footing length x = 3,50 m
Spread footing width y = 2,50 m
Column width in the direction of x cx = 0,60 m
Column width in the direction of y cy = 0,40 m
Spread footing volume = 6,12 m3
Material of structure
Unit weight g = 23,56 kN/m3
Analysis of concrete structures carried out according to the standard EN 1992-1-1 (EC2).

Concrete : C 25/30
Cylinder compressive strength fck = 25,00 MPa
Tensile strength fct = 2,60 MPa
Elasticity modulus Ecm = 31000,00 MPa
Longitudinal steel : B500
Yield strength fyk = 500,00 MPa
Transverse steel: B500
Yield strength fyk = 500,00 MPa
Geological profile and assigned soils
Layer
No. Assigned soil Pattern
[m]

1 5,00 tlo

2 - tlo

Load
Load N Mx My Hx Hy
No. Name Type
new change [kN] [kNm] [kNm] [kN] [kN]
1 YES Load No. 1 Design 1575,00 0,00 112,50 0,00 0,00
Global settings
Type of analysis : analysis for drained conditions

Settings of the stage of construction


Design situation : permanent

Verification No. 1
Load case verification
Self w. ex ey s Rd Utilization
Name Is satisfied
in favor [m] [m] [kPa] [kPa] [%]
Load No. 1 Yes -0,06 0,00 230,84 256,00 90,17 Yes
Load No. 1 No -0,05 0,00 245,95 255,93 96,10 Yes

2
[GeoStructural Analysis - Spread Footing | version 5.17.6.0 | Copyright 2013 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]
Analysis of bearing capacity - partial results
jd = 16,230
cd = 3,200 kPa
g1prum = 18,000 kN/m3
g2prum = 18,000 kN/m3
bef = 2,500 m
Nd = 4,432
Nc = 11,789
Nb = 1,998
sd = 1,206
sc = 1,266
sb = 0,779
dd = 1,000
dc = 1,000
db = 1,000
id = 1,000
ic = 1,000
ib = 1,000
bd = 1,000
bc = 1,000
bb = 1,000
gd = 1,000
gc = 1,000
gb = 1,000
Rd = 255,933 kPa
Analysis carried out with automatic selection of the most unfavourable load cases.

Computed weight of spread footing G = 194,84 kN


Computed weight of overburden Z = 315,93 kN
Vertical bearing capacity check
Shape of contact stress : rectangle
Most severe load case No. 1. (Load No. 1)

Parameters of slip surface below foundation:


Depth of slip surface zsp = 2,62 m
Length of slip surface lsp = 6,51 m

Design bearing capacity of found.soil Rd = 255,93 kPa


Extreme contact stress s = 245,95 kPa
Bearing capacity in the vertical direction is SATISFACTORY

Horizontal bearing capacity check

Most severe load case No. 1. (Load No. 1)

Earth resistance: at rest


Design magnitude of earth resistance Spd = 32,91 kN
Friction angle foundation-footing bottom y = 16,23
Cohesion foundation-footing bottom a = 3,20 kPa
Horizontal bearing capacity Rdh = 601,52 kN
Extreme horizontal force H = 0,00 kN

3
[GeoStructural Analysis - Spread Footing | version 5.17.6.0 | Copyright 2013 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]
Bearing capacity in the horizontal direction is SATISFACTORY

Bearing capacity of foundation is SATISFACTORY

Dimensioning No. 1
Analysis carried out with automatic selection of the most unfavourable load cases.

Verification of longitudinal reinforcement of foundation in the direction of x


Bar diameter = 14,0 mm
Number of bars = 16
Reinforcement cover = 40,0 mm
Cross-section width = 2,50 m
Cross-section depth = 0,70 m
Reinforcement ratio r = 0,15 % > 0,14 % = rmin
Position of neutral axis x = 0,03 m < 0,40 m = xmax
Ultimate moment MRd = 685,52 kNm > 655,66 kNm = MEd
Cross-section is SATISFACTORY.

Verification of longitudinal reinforcement of foundation in the direction of y


Bar diameter = 16,0 mm
Number of bars = 4
Reinforcement cover = 40,0 mm
Cross-section width = 3,50 m
Cross-section depth = 0,70 m
Reinforcement ratio r = 0,04 % < 0,14 % = rmin
Cross-section is NOT SATISFACTORY; increase reinforcement ratio.

Spread footing for punching shear failure check


Column normal force = 1575,00 kN

Maximum resistance at the column perimetr


Force transmitted into found. soil = 43,20 kN
Force transmitted by shear strength of SRC = 1531,80 kN
Considered column perimeter u0 = 2,00 m
Shear resistance at the column perimeter vEd,max = 1,44 MPa
Resistance at the column perimetr vRd,max = 3,60 MPa
Critical section without shear reinforcement
Force transmitted into found. soil = 611,68 kN
Force transmitted by shear strength of SRC = 963,32 kN
Distance of section from the column = 0,49 m
Section perimeter ucr = 6,04 m
Shear stress at section vEd = 0,58 MPa
Shear resistance of section without shear reinforcement vRd,c = 0,90 MPa
vEd < vRd,c => Reinforcement is not required

Spread footing for punching shear is SATISFACTORY

4
[GeoStructural Analysis - Spread Footing | version 5.17.6.0 | Copyright 2013 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]