h.high hlow
Mean roof height h h 27 ft
2
Least horizontal dimension Lmin min Lroof_side Lroof_end Lmin 50 ft
V
2
qh 0.00256 Kz Kzt Kd psf qh 28.2 psf
mph
Enclosure Classification ENC "PARTIALLY ENCLOSED" Sec. 26.10
Internal Pressure Coefficient GCpi 0.18 (+ & -) Table 26.11-1
Wind Pressures - Components and Cladding Reference
External Pressure Coefficients - Components and Cladding
End dimension a max 3 ft 0.04 Lmin min 0.10 Lmin 0.4 h a 5.00 ft
2 2
A2_end 198 ft A2_end 198 ft
GCp_2_end_POS 0.20
GCp_2_end_NEG 1.10
2
A2_side 235 ft 2
A2_side 235 ft
GCp_2_side_POS 0.20
GCp_2_side_NEG 1.10
2 2
A3 25 ft A3 25 ft
GCp_3_POS 0.30
GCp_3_NEG 2.0
2 2 Consider the
A4 1071 ft A4 1071 ft smallest area
GCp_4_POS 0.70 of each end.
GCp_4_NEG 0.80
2 2
A5 135 ft A5 135 ft
GCp_5_POS 0.80
GCp_5_NEG 1.0
Wind Pressures - Components and Cladding - continued Reference
In the following calculations, the subscript POS or NEG refers to whether the external Sec. 30.4.2
pressure, GCp, is positive or negative, respectively. Since GCpi can be positive or negative,
only the condition which increases the magnitude of the external pressure is considered.
For overhang regions, GCpi does not apply.
Roof Areas
Along End
pc2_end_POS qh GCp_2_end_POS GCpi pc2_end_POS 11 psf
pc2_end_NEG qh GCp_2_end_NEG GCpi pc2_end_NEG 36 psf
Along Side
pc2_side_POS qh GCp_2_side_POS GCpi
pc2_side_POS 11 psf
pc2_side_NEG qh GCp_2_side_NEG GCpi
pc2_side_NEG 36 psf
Corner Regions
pc5_POS qh GCp_5_POS 0.9 GCpi pc5_POS 25 psf
pc5_NEG qh GCp_5_NEG 0.9 GCpi pc5_NEG 30 psf