Critical Power

Automatic Transfer
Switch (ATS) Withstand
and Closing Ratings (WCR)
The Purpose of Testing and Unit Ratings

GE automatic transfer switches (ATS) If a transfer switch does not have concern over coordination with
have been subjected to an extensive test adequate withstand capabilitysystem some protective devices. UL clarified
program to show that they comply with failure, fire, injury to personnel or the labeling procedure and now
and exceed UL 1008 standards as well as equipment damage may result. A clear allows for three rating categories.
the various performance specifications understanding of the interrelationship Current limiting fuse
used by most government agencies and between the protective device,
major electrical engineers throughout transfer switch and system needs Specific class (trip time) of molded
the world. The primary test to assure is necessary for a well designed case breaker
the dependability of an automatic installation. Some basic information on Umbrella or Any Breaker ratings
transfer switch is its ability to close into withstand rating terms and calculations that take into account all types of
and withstand high fault currents. The follows the enclosed rating charts. molded, insulated case and power
purpose of this publication is to provide circuit breakers; these tests are
basic information on withstand ratings performed for a duration of 3 cycles
and to document the ratings that GE Underwriters Laboratories (UL) is the on units 225 amps and greater, and for
ATS currently holds under UL 1008. independent testing body that has 1.5 cycles on 40-150 amp units (with
developed the standard UL 1008 which an optional 3 cycle duration for units
all major transfer switch manufacturers up to 150 amps; note the three cycle
NFPA 110 Standard for Emergency test to. UL lists products which have rating on 150 amp and below units is
and Standby Power Systems, Section successfully passed a battery of optional as UL has determined that
6.3.2, requires that the capacity and witnessed tests including the withstand all breakers in this size clear in less
rating of automatic transfer switches and close into fault tests described than 1.5 cycles). The Umbrella or
be adequate to withstand the thermal herein. Manufacturers that complete Any Breaker rating is therefore the
and electromagnetic effects of short these tests are then permitted to label actual UL requirement and definition
circuit currents that may arise in their products with the UL mark. of the ATS industry 3 cycle (or 1.5 as
the electrical system. It is important noted) withstand and closing rating,
to be able to compare properly the and should not to be confused with
withstand close rating (WCR) of the UL made significant changes in
April of 1989 regarding the labeling additional, non UL 1008 labeled
switch to the available short circuit withstand only tests.
(fault) current of the system until the requirements of transfer switches.
protective device clears the fault. Prior to that date there had been

ATS Products | www.gecriticalpower.com 2


Zenith Product Ratings
The GE family of transfer switches have breaker specified for the installation The ZTS/ZTG/ZTE
maintained an industry-leading role in have an equal or shorter trip time
ratings from the time of its introduction. when compared to the listed devices. Switch Families
Today all ZTS, ZTE, and ZT30 products This would limit the application of
are labeled with an umbrella (any the switch to projects within the ZTS/ZTE Automatic Transfer
molded case breaker) rating as well as scope of its specific breaker listing. Switches 40 - 4000 amps
some higher specific breaker levels giving ZTSD/ZTED Delayed Transition
the consultant a free hand with system Switches 40 - 4000 amps
design. The following pages include the In addition to this factor, many transfer
ZTSCT/ZTECT Closed Transition
UL certified ratings and specific breaker switch manufacturers perform additional Switches 100 - 4000 amps
coordination charts, withstand rating withstand tests on selected products.
ZBTS/ZBTE Transfer/Bypass
data and additional specific information. These additional tests may be either Switches 100 - 4000 amps
for a higher current value or a longer
ZBTSD/ZBTED Delayed Transfer/ Bypass
duration than their standard UL listed
Switches 100 - 4000 amps
The consulting engineer must keep ratings. The consultant must determine
ZBTSCT/ZBTECT Closed Transition
in mind that unless a transfer switch the applicability of these tests and
Transfer/Bypass Switches 100 - 4000 amps
bears an umbrella breaker approval take careful note if these levels are
ZTG Automatic Transfer
for use with any molded case breaker, normally not UL labeled ratings.
Switches 40 - 3000 amps
care must be taken to assure that the
ZTGD Delayed Transition
Switches 40 - 3000 amps
ZTGSE/ZTGDSE Standard & Delayed
Service Entrance Rated Switches 40 - 3000 amps
ZTX Automatic Transfer
Switches 40 - 400 amps
ZT30/ZBT30 ATS/ Bypass 1000-3000A
ZT30D/ZBT30D Delayed switches 1000-3000A
ZT30CT/ZBT30CT Closed transition
switch 1000-3000A

ATS Products | www.gecriticalpower.com 3


Definitions & Calculations

Purpose Available Peak Current Maximum Comparison of Terms


possible short circuit current that may
Many questions arise when comparing exist in a system without protective The following values have all been used
wcr to the system fault current rating. devices. to describe identical circuit conditions:
Too often a switch is rated by a Available Short Circuit Current rms
manufacturer in one set of wcr terms Peak Let Through Current Maximum
instantaneous current through the 120,000 amps
and the available system fault currents
described with a different set of terms. protective device during the total Peak Let Through Current ( cycle)
The purpose of this paper is to outline clearing time. 130,000 amps
the different ways switches may be Withstand Current Rating The Peak Asymmetrical Current
rated (wcr) and systems are measured. rating that defines the ability of the 156,000 amps
switch to withstand the thermal Peak Symmetrical Current
and electromagnetic effects of short
Basic Defnitions circuit currents for a set period of
140,000 amps

RMS Current The Root Mean Square time. Withstand Rating 3 Cycles rms
which is the effective value of an 128,000 amps
Withstand and Closing Rating (WCR)
alternating current. It is equal to .707 ul 1008 test for a transfer switchs What do these numbers mean? They
of the peak current for a sine wave. ability to close into and withstand a mean that a switch was tested at
This is the value referred to when fault current. These are the ratings 128,000 amps rms Sym for 3 cycles;
people say current. which will actually appear on the ul the switch also had a projected peak
Peak Current The instantaneous label of the product. symmetrical current of 140,000 amps
maximum value of currentthe peak for less than cycle and a peak
Short-Time current rating (STR) - UL asymmetrical current of 156,000 amps
current of a sine wave is 1.414 times 1008 test similar to withstand and
its rms value. for less than cycle. The switch has
closing rating but for a time period been tested in a system that has an
Symmetrical Current The alternating up to 0.5 seconds and provides for available capacity of 120,000 amps rms.
current which is symmetrical around the requirement that the switch be
the zero axis of the sine wave. capable of carrying full load current How should a manufacturer rate a
after the withstand and close-on switch? Preferably by submitting test
Asymmetrical Current The data which is reported as outlined
short-circuit events.
alternating current which is not by ul 1008 specifications. This data
symmetrical around the zero axis. note: For diagrams of typical current calls for rms symmetrical readings
wave forms, see Figure 1 and Figure 2. based on specific test parameters.
Peak Fault Current The
instantaneous maximum current Other figures may be misleading.
value that occurs after the start of a
fault in any phase.

ATS Products | www.gecriticalpower.com 4


Test Documents then used to open the fault current in Where time beyond the first cycle is
place of a protective devicethis may given suitable decisions can be made
As fault currents can occur at any level, leave the transfer switch with both to use circuit breakers or fuses.
a transfer switch must be capable normal and emergency open which
of withstanding any fault current up Misleading reporting is eliminated.
then requires manual resetting of the
to its maximum rating. This rating is breakers within the transfer switch
based on the rating of the protective
device in front of the unit and must
enclosure. The circuit breakers may Blow-On Effects on
require factory inspection after high
be considered on that basis. current interruption in accordance with Short Circuit Current in
GEtests show results based on various common circuit breaker procedures. Contacts
current values and time durations, and Some switch designers analyze blow-on
include additional high current tests with and blow-off effects and force vectors
fuses. By considering this range of values, WCR ratings, as opposed to IC ratings
(due to electromagnetic repulsion) to
it is possible to predict performance with appear to offer a better choice to
claim increased WCR capability of their
different fuse characteristics or specific the system designer as he attempts
product. Such calculations are very rough
circuit breaker current-time curves with to coordinate the protection of the
approximations because of inherent
a given available short circuit current. entire system. Knowing the maximum
errors in estimating domain size and
amount and duration of fault current
number, current pinch effect and the
a switch will withstand gives the
problem of complex geometry of actual
Interrupting Ratings designer the information necessary for
contact structures when compared to
complete coordinated system design.
Some manufacturers of circuit breaker idealized models. The only proof of a
type automatic transfer switches list successful design are tests, uniformly
interrupting current (IC) ratings in
lieu of WCR. These switches will then
Advantage of RMS performed and consistently reported all
to the same criterion such as UL 1008.
open on faults instead of withstanding Symmetrical Ratings
the fault until the external protective Date is consistently reported based
device clears. As the transfer switch is on UL test procedures.

ATS Products | www.gecriticalpower.com 5


Coordinated Breaker Model Types

UL ANY MAXIMUM CURRENT


GE ZENITH MAX MAX
SHORT-TIME BREAKER MAXIMUM COORDINATED BREAKER LIMITING
MODEL AMP BREAKER BREAKER TYPE FUSE
RATING RATING (A) VOLTAGE BREAKER MFR FUSE
FAMILY AMPERAGE SIZE
(STR) (WCR) NOTE 1 RATING (A) RATING (A)
ZTX 40 - 10,000 480V 30,000 Eaton 100A FCL 200,000NOTE 2 400A
(40-225A) 80 (Class J)
250A JGS, JGH, JGC, JGU,
100 JGX, JBD, JD, HJD,
ZTG 150 JDC, LCL, LCLA
(OT) (40-225A) 200
225 400A LDC, CLDC, KDB, KD,
ZTS HKD, KDC, LD, CLD,
(OT) (40-150A) HLD, CHLD

ITE/ 125A CED6, HED4, HED6


ZTE Siemens
(OT) (40-150A) 250A CFD6, FD6A, FXD6,
HFD6, HFXD6, HHFD6,
HHFXD6

400A CJD6

General 150A SEL, SEP, THLC1


Electric
225A THLC2

250A SFH, SFL, SFP

400A SGH, SGL, SGP, FGN,


FGH, FGL, FGP

Schneider 150A HG, HJ, HL, HR

250A JJ, JL, JR

400A LG, LJ, LL, LR

600V 22,000 Eaton 250A JGS, JGH, JGC, JGU,


JGX, JDB, JD, HJD,
JDC, LCL, LCLA

400A LDC, CLDC, KDB, KD,


HKD, KDC, LD, CLD,
HLD, CHLD

ITE/ 125A CED6, HED4, HED6


Siemens
250A CFD6, FD6, FXD6,
HFD6, HFXD6, HHFD6,
HHFXD6

General 150A SEL, SEP, THLC1


Electric
225A THLC2

250A SFH, SFL, SFP

400A SGH, SGL, SGP, FGN,


FGH, FGL, FGP

Schneider 150A HG, HJ, HL, HR

250A JJ, JL, JR

400A LG, LJ, LL, LR

ATS Products | www.gecriticalpower.com 6


Coordinated Breaker Model Types (cont.)

UL ANY MAXIMUM CURRENT


GE ZENITH MAX MAX
SHORT-TIME BREAKER MAXIMUM COORDINATED BREAKER LIMITING
MODEL AMP BREAKER BREAKER TYPE FUSE
RATING RATING (A) VOLTAGE BREAKER MFR FUSE
FAMILY AMPERAGE SIZE
(STR) (WCR) NOTE 1 RATING (A) RATING (A)
ZTG 260 - - 480V 35000 Eaton 250A JGS, JGH, JGC, JGU, - -
(OT) (260A) JGX, JDB, JD, HJD,
JDC, LCL, LCLA

400A LDC, CLDC, LD, CLD,


HLD, CHLD, KDB, KD,
HKD, KDC

ITE/ 125A CED6, HED4, HHED6


Siemens
250A CFD6, FD6, FXD6,
HFD6, HFXD6, HHFD6,
HHFXD6

General 150A SEL, SEP, THLC1


Electric
225A THLC2

250A SFH, SFL, SFP

350A SGH

400A SGH, SGL, SGP, FGN,


FGH, FGL, FGP

Schneider 150A HG, HJ, HL, HR

250A JJ, JL, JR

400A LG, LJ, LL, LR

ATS Products | www.gecriticalpower.com 7


Coordinated Breaker Model Types (cont.)

UL ANY MAXIMUM CURRENT


GE ZENITH MAX MAX
SHORT-TIME BREAKER MAXIMUM COORDINATED BREAKER LIMITING
MODEL AMP BREAKER BREAKER TYPE FUSE
RATING RATING (A) VOLTAGE BREAKER MFR FUSE
FAMILY AMPERAGE SIZE
(STR) (WCR) NOTE 1 RATING (A) RATING (A)
ZTX 40 - 35,000 480V 50,000 Eaton 250A HJD, JDC, JGC, JGH, 200,000 600A
(300-400A) 80 JGU, JGX (Class J)
100
ZTG 150 400A CHLD4, CLD, HLD4, 100,000
(OT) (400A) CLDC, LDC, KDC, HKD,
200 CHMDL4, CMDL4 (Class RK5,
225 RK1)
ZTG 260 600A CHLD6, HDL6,
(DT) (40-400A) CHMDL6, CMDL6,
300
CLDC, CLD6, LDC6,
400
ZTS CLDC6
(OT) (225-
400A) 800A CHMDL8, HMDL8,
MDL8, CMDL8
ZTS
ITE/ 250A CFD6, HFD6, HFXD6,
(DT, CT)
Siemens HHFD6, HHFXD6
(40-400A)
400A CJD6
ZBTS
(OT, DT) 600A CLD6, HHLD6,
(100-400A) HHLXD6, HLD6,
HLXD6
ZTE
(OT) 800A CMD6, MD6, HMD6,
(225-400A) HMXD6, MXD6

General 250A SFL, SFP


ZTE Electric
(DT, CT) 400A SGL, SGP
(40-400A)
600A SGL, SGP, FGL, FGP
ZBTE
(OT, DT) Schneider 150A HJ, HL, HR
(100-400A)
250A JJ, JL, JR

600A LJ, LL, LR

800A MJ

600V 42000 Eaton 250A JGU, JGX 200,000NOTE 3


(Class J)
400A CLDC4, KDC, LDC4

600A CLDC6, LDC6, NB


Tri-Pac

800A NB Tri-Pac

ITE/ 250A CFD6


Siemens
400A CJD6, SCLD6

600A CLD6, HHLD6,


HHLXD6, SCLD6

800A CMD6,
HMD6,
HMXD6,
SCMD6,
SHMD6

General 150A THLC1


Electric
400A FGL4, FGP4, THLC4,
TLB4

600A SGL, SGP, FGL6, FGP6

800A SKL8, SKP8

Schneider 150A HJ, HL, HR

250A JJ, JL, JR

600A LJ, LL, LR

800A MJ

ATS Products | www.gecriticalpower.com 8


Coordinated Breaker Model Types (cont.)

UL ANY MAXIMUM CURRENT


GE ZENITH MAX MAX
SHORT-TIME BREAKER MAXIMUM COORDINATED BREAKER LIMITING
MODEL AMP BREAKER BREAKER TYPE FUSE
RATING RATING (A) VOLTAGE BREAKER MFR FUSE
FAMILY AMPERAGE SIZE
(STR) (WCR) NOTE 1 RATING (A) RATING (A)
ZTG 600 - 35,000 480V 50,000 Eaton 250A HJD, JDC, JGC, JGH, - -
(OT, DT) JGU, JGX

400A CHLD4, CLD, HLD4,


CLDC, LDC, KDC, HKD,
CHMDL4, CMDL4

600A CHLD6, HDL6,


CHMDL6, CMDL6,
CLDC6, LDC6, CLDC6

800A CHMDL8, HMDL8,


MDL8, CMDL8

ITE/ 250A CFD6, HFD6, HFXD6,


Siemens HHFD6, HHFXD6

400A CJD6

600A CLD6, HHLD6,


HHLXD6, HLD6,
HLXD6

800A CMD6, MD6, HMD6,


HMXD6, MXD6

General 250A SFL, SFP


Electric
400A SGL, SGP

600A SGL, SGP, FGL, FGP

Schneider 150A HJ, HL, HR

250A JJ, JL, JR

600A LJ, LL, LR

800A MJ

600V 42,000 Eaton 250A JGU, JGX

400A CLDC4, KDC, LDC4

600A CLDC6, LDC6, NB


Tri-Pac

800A NB Tri-Pac

ITE/ 250A CFD6


Siemens
400A CJD6, SCLD6

600A CLD6, HHLD6,


HHLXD6, SCLD6

800A CMD6,
HMD6,
HMXD6,
SCMD6,
SHMD6

General 150A THLC1


Electric
400A FGL4, FGP4, THLC4,
TLB4

600A SGL, SGP, FGL6, FGP6

800A SKL8, SKP8

Schneider 150A HJ, HL, HR

250A JJ, JL, JR

600A LJ, LL, LR

800A MJ

ATS Products | www.gecriticalpower.com 9


Coordinated Breaker Model Types (cont.)

UL ANY MAXIMUM CURRENT


GE ZENITH MAX MAX
SHORT-TIME BREAKER MAXIMUM COORDINATED BREAKER LIMITING
MODEL AMP BREAKER BREAKER TYPE FUSE
RATING RATING (A) VOLTAGE BREAKER MFR FUSE
FAMILY AMPERAGE SIZE
(STR) (WCR) NOTE 1 RATING (A) RATING (A)
ZTS 600 - 50,000 480V 65,000 Eaton 600A HLD, CHLD, LDC, 200,000 750A
(OT, DT, CT) CLDC (Class L, J,
RK5, RK1)
800A HMDL, HMDLB,
ZBTS CHMDL, NB Tri Pac
(OT, DT)
ITE/ 600A CLD6, SHLD6, SCLD6,
ZBTS Siemens HLD6, HLDX6, HHLD6,
(CT) HHLXD6
(100-600A)
800A CMD6, HMXD6,
HMD6, SCMD6,
ZTE SHMD6, SCND6,
(OT, DT, CT) SHND6

ZBTE 1200A HND6, HNXD6, CND6


(OT, DT) 1600A HRD6, HRXD6

ZBTE General 600A SGH, SGL, SGP


(CT) Electric
(100-600A) 1200A SKL, SKP, SKT, SKS

Schneider 600A LJ, LL, LR

1200A PJ

1600A MASTERPACT
NW

42,000 600V 50,000 Eaton 600A LDC, CLDC 150,000NOTE4 750A


(Class L, J,
800A NB Tri-Pac, DSL206 RK5, RK1)
Schneider 600A LI, LXI

800A NC, NE, NX

1200A PK

ITE/ 600A CLD6, HHLD6,


Siemens HHLXD6, SCLD6,
SHLD6

800A CMD6, HMD6, SCMD6,


SCND6, SHMD6,
SHND6

1200A CND6, SCND6

General 600A TB6, SGL6, SGP6


Electric
800A TB8, THP, THC, SKP8

1200A SKP

ATS Products | www.gecriticalpower.com 10


Coordinated Breaker Model Types (cont.)

UL ANY MAXIMUM CURRENT


GE ZENITH MAX MAX
SHORT-TIME BREAKER MAXIMUM COORDINATED BREAKER LIMITING
MODEL AMP BREAKER BREAKER TYPE FUSE
RATING RATING (A) VOLTAGE BREAKER MFR FUSE
FAMILY AMPERAGE SIZE
(STR) (WCR) NOTE 1 RATING (A) RATING (A)
ZTG 800 - 50,000 480V 65,000 Eaton 600A HLD, CHLD, LDC, 200,000 1,200A
(OT, DT) CLDC (Class L)
800A HMDL, HMDLB,
ZTS CHMDL, NB Tri Pac
(OT, DT, CT)
ITE/ 600A CLD6, SHLD6, SCLD6,
ZTE Siemens HLD6, HLDX6, HHLD6,
(OT, DT, CT) HHLXD6

800A CMD6, HMXD6,


HMD6, SCMD6,
SHMD6, SCND6,
SHND6

1200A HND6, HNXD6, CND6

1600A HRD6, HRXD6

General 600A SGH, SGL, SGP


Electric
1200A SKL, SKP, SKT, SKS

Schneider 600A LJ, LL, LR

1200A PJ

1600A MASTERPACT NW

42,000 600V 50,000 Eaton 600A LDC, CLDC - -

800A NB Tri-Pac, DSL206

Schneider 600A LI, LXI

800A NC, NE, NX

1200A PK

ITE/ 600A CLD6, HHLD6,


Siemens HHLXD6, SCLD6,
SHLD6

800A CMD6, HMD6, SCMD6,


SCND6, SHMD6,
SHND6

1200A CND6, SCND6

General 600A TB6, SGL6, SGP6


Electric
800A TB8, THP, THC, SKP8

1200A SKP

ATS Products | www.gecriticalpower.com 11


Coordinated Breaker Model Types (cont.)

UL ANY MAXIMUM CURRENT


GE ZENITH MAX MAX
SHORT-TIME BREAKER MAXIMUM COORDINATED BREAKER LIMITING
MODEL AMP BREAKER BREAKER TYPE FUSE
RATING RATING (A) VOLTAGE BREAKER MFR FUSE
FAMILY AMPERAGE SIZE
(STR) (WCR) NOTE 1 RATING (A) RATING (A)
ZBTS 800 - 50,000 480V 85,000 Eaton 1600A PB, HND 200,000 3,000A
(OT, DT, CT) (Class L)
ITE/ 800A CMD6
Siemens
ZBTE 1200A CND6
(OT, DT, CT)
1600A CPD6-HPD6

General 1200A SKL, SKP, SKS


Electric

42,000 600V 65,000 Eaton 800A NB Tri Pac - -

1600A RDC, CRDC, PC, PCC,


PB Tri Pac

Schneider 1200A NC, NE, NX

1600A PCF, PEF, PHF, PXF

ITE/ 800A CMD6, SCMD6


Siemens
1200A CND6, SCND6

1600A CPD6, HPD6, HRD6

General 800A THP, THC, TB8, SKP8


Electric
1200A SKP

1600A THP, THC, TRP

MG 1600A MP16H1, MP16H2,


MC16H1

ATS Products | www.gecriticalpower.com 12


Coordinated Breaker Model Types (cont.)

UL ANY MAXIMUM CURRENT


GE ZENITH MAX MAX
SHORT-TIME BREAKER MAXIMUM COORDINATED BREAKER LIMITING
MODEL AMP BREAKER BREAKER TYPE FUSE
RATING RATING (A) VOLTAGE BREAKER MFR FUSE
FAMILY AMPERAGE SIZE
(STR) (WCR) NOTE 1 RATING (A) RATING (A)
ZTG 1000 - 50,000 480V 85,000 Eaton 1600A PB, HND 200,000 3,000A
(OT, DT) 1200 (Class L)
ITE/ 800A CMD6
Siemens
ZTS 1200A CND6
(OT, DT, CT)
1600A CPD6-HPD6
ZBTS General 1200A SKL, SKP, SKS
(OT, DT, CT) Electric

ZTE 42,000 600V 65,000 Eaton 800A NB Tri Pac - -


(OT, DT, CT)
1600A RDC, CRDC, PC, PCC,
PB Tri Pac
ZBTE
(OT, DT, CT) Schneider 1200A NC, NE, NX

1600A PCF, PEF, PHF, PXF

ITE/ 800A CMD6, SCMD6


Siemens
1200A CND6, SCND6

1600A CPD6, HPD6, HRD6

General 800A THP, THC, TB8, SKP8


Electric
1200A SKP

1600A THP, THC, TRP

MG 1600A MP16H1, MP16H2,


MC16H1

ATS Products | www.gecriticalpower.com 13


Coordinated Breaker Model Types (cont.)

UL ANY MAXIMUM CURRENT


GE ZENITH MAX MAX
SHORT-TIME BREAKER MAXIMUM COORDINATED BREAKER LIMITING
MODEL AMP BREAKER BREAKER TYPE FUSE
RATING RATING (A) VOLTAGE BREAKER MFR FUSE
FAMILY AMPERAGE SIZE
(STR) (WCR) NOTE 1 RATING (A) RATING (A)
ZTG 1600 - 100,000 480V 100,000 Any - Any Breaker 200,000 2,500A
(OT, DT) 2000 Breaker (Class L)
2600
ZTS 85,000 600V 85,000 Any - Any Breaker - -
3000 Breaker
(OT, DT, CT)

ZBTS
(OT, DT, CT)

ZTE
(OT, DT, CT)

ZBTE
(OT, DT, CT)

ZBTS 1600 - 65.000NOTE 5 600V 65000 Any - Any Breaker - -


(OT, DT, CT) 2000 Breaker
2600
ZBTE 3000
(OT, DT, CT)

ATS Products | www.gecriticalpower.com 14


Coordinated Breaker Model Types (cont.)

UL ANY MAXIMUM CURRENT


GE ZENITH MAX MAX
SHORT-TIME BREAKER MAXIMUM COORDINATED BREAKER LIMITING
MODEL AMP BREAKER BREAKER TYPE FUSE
RATING RATING (A) VOLTAGE BREAKER MFR FUSE
FAMILY AMPERAGE SIZE
(STR) (WCR) NOTE 1 RATING (A) RATING (A)
ZTS 4000 - 100,000 480V 100,000 Any - Any Breaker 200,000 6,000A
(OT, DT, CT) Breaker (Class L)

ZBTS 85,000 600V 85,000 Any - Any Breaker 200,000 6,000A


(OT, DT, CT) Breaker (Class L)

ZTE
(OT, DT, CT)

ZBTE
(OT, DT, CT)

ZT30 1000 85,000 100,000 600V 100,000 Any - Any Breaker 200,000 4,000A
(OT, DT, CT) 1200 (30 cycle) Breaker (Class L)
1600
ATS & BYPASS 2000 100,000
3000 (3 cycle)

Note 1: The Any Breaker rating is not applicable to ZTX and ZTG products.
Note 2: Fuse Rating does not apply to 200 & 225A @ 600V ATS product
Note 3: Fuse Rating does not apply to 100-400A @ 600V Bypass product
Note 4: Fuse Rating does not apply to 600A @ 600V Bypass product
Note 5: For 1600-3000A Horizontal Bypass product @ 600v

UL References:
E23911 : ZTX, ZTG, ZTS, ZTE, ZT3
E67544 : ZBTS, ZBTE, ZBT3

LEGEND

OT: Open Transition

DT: Delayed Transition

CT: Closed Transition

ATS Products | www.gecriticalpower.com 15


GE
Critical Power
601 Shiloh Road
Plano, TX 75074
+1 877 546 3242
www.gecriticalpower.com

*Registered trademark of the General Electric Company.


The GE brand, logo, and lumination are trademarks of the General Electric Company. 2015 General Electric Company.
Information provided is subject to change without notice. All values are design or typical values when measured under
laboratory conditions.