COMMISSIONING TEST Page 1/3

REPORT FOR NON


DIRECTIONAL O/C & E/F RELAY

SUBSTATION NAME: 66 KV
TESTING OF CONTROL & RELAY PANEL
Panel Details:
Client : Honda Motorcycle & Scooter India Ltd
Designation : Non Directional Over current and Earth fault Relay.
RELAY TYPE : V57F-4AAA2BBA
Serial Number : EB164610010
Panel Name : INCOMER FEEDER-2
Aux. Volts : 110V DC
Nominal Current :1A

Settings:
CT Primary Current 1200 A
CT-Secondary Current 1A

1. MEASUREMENT:
Inject current in the relay as per the table below. Observe the reading on the relay display, in
primary values.
Phase Current Primary Current Displayed on Relay (Amp)
Injected (A) IL1 IL2 IL3 IN
L1-E 1 1198.00 0 0 1198.00
L2-E 1 0 1199.00 0 1199.00
L3-E 1 0 0 1198.00 1198.00
L1L2L3 1 1200.00 1200.00 1200.00 0

REMARKS: Measurement Check O.K

2. OVER CURRENT

TESTED BY M/S SREX WITNESSED BY M/S HONDA

Name UMAKANT Mr. JIMIT DESAI


Signature
COMMISSIONING TEST Page 2/3
REPORT FOR NON
DIRECTIONAL O/C & E/F RELAY

IDMT CHARACTERISTCS : SETTING CURRENT, I = 0.8 A, SETTING TIME, TMS = 0.05 s


INJECTED CALCULATEDTIME TRIPPING TIME IN
PHASES
CURRENT IN Amps IN sec sec
2 Times 1.6 0.500 .503
R-PHASE
10 Times 5 0.15 .152
2 Times 1.6 0.500 .502
Y-PHASE
10 Times 5 0.15 .153
2 Times 1.6 0.500 .503
B-PHASE
10 Times 5 0.15 .153
HIGH SET: SETTING CURRENT, IE = 2.5 A, SETTING TIME, T = .030 s
INJECTED CURRENT IN
Tripping time in sec
Phase Amps
R 2.5 0.032
Y 6 0.032
B 6 0.033

REMARKS: Over current Protection checked OK.

3. EARTH FAULT :

IDMT CHARACTERISTICS(51N): SETTING CURRENT,I = 0.1 A, SETTING TIME, TMS = 0.05

INJECTED CALCULATEDTIME TRIPPING TIME IN


PHASES
CURRENT IN Amps IN sec sec
2 Times 0.2 0.500 0.521
R-PHASE
5 Times 1 0.15 0.152
2 Times 0.2 0.500 0.522
Y-PHASE
5 Times 1 0.15 0.153
2 Times 0.2 0.500 0.521
B-PHASE
5 Times 1 0.15 0.153

HIGH SET(50N): SETTING CURRENT, IE = 1 A, SETTING TIME, T = 0.04 s


INJECTED CURRENT IN
Tripping time in sec
Phase Amps

TESTED BY M/S SREX WITNESSED BY M/S HONDA

Name UMAKANT Mr. JIMIT DESAI


Signature
COMMISSIONING TEST Page 3/3
REPORT FOR NON
DIRECTIONAL O/C & E/F RELAY

R 1 0.041
Y 1 0.042
B 1 0.042

REMARKS: Earth Fault Protection checked OK.

TESTED BY M/S SREX WITNESSED BY M/S HONDA

Name UMAKANT Mr. JIMIT DESAI


Signature