PROJECT NO.

ELECTRICAL MAXIMUM DEMAND

Existing Conditions

Transformer 300 kVA


435 Amps per Phase
240 Maximum Demand Existing
195 Spare Capacity remaining

Addition Load Description Amps per Phase

Office 14
Car Park 12
Accommodation 120

Total 146
Safety Factor 110%

New Maximum Demand 160


Office

Calculation - Maximum Demand assessed by AS 3000 - Table C3

Type Average VA/m2 Area m VA

Light and Power 50 Length 20


Air Conditioning 25 Width 5
Spare 15

100 m2 100 10000 VA


14.4927536 Amps per Phase

Car Park

Calculation - Maximum Demand assessed by AS 3000 - Table C3

Type Average VA/m2 Area m VA

Basement Car Park 15 Length 20


Spare 5 Width 20

20 m2 400 8000 VA
11.5942029 Amps per Phase
Calculation - Maximum Demand assessed by AS 3000 - Table C1 - Single and Multiple Domestic Electrical Installations

Total No. of Units 12 No. of Units Red, White, Blue Check

4 4 4 12

Load Group Equivalent Total


Total Installed Red White Blue Red White Blue
(Per AS 3000 - Table Item Quantity Unit Calculation AS NZS 3000 Amps Power Factor Equivalent No of Phases
(W) (A) (A) (A) (A) (A) (A)
C2, Column 2) (at unity pf) Amps

A Indoor Lighting 12 Residence 6Amps 18.0 0.8 22.5 3 7.5 7.5 7.5 7.5 7.5 7.5 22.5

A Outdoor Lighting 12 Residence NA; not deemed to exceed total of 1000W

10Amps plus 5Amps per living


B(i) Socket-outlets 12 Residence 70.0 0.8 87.5 3 29.2 29.2 29.2 29.2 29.2 29.2 87.5
unit

B(ii) Socket-outlets 12 Residence NA; unless the installation includes one or more 15A socket outlets other than those provided for by groups C, D, E, F, G, and L

B(iii) Socket-outlets 12 Residence NA; unless the installation includes one or more 20A socket outlets other than those provided for by groups C, D, E, F, G, and L

Ranges, cooking appliances,


laundry equipment or socket-
C 12 Residence 15 Amps 15.0 15.0 15.0 15.0 15.0 15.0 45.0
outlets rated at more than 10A
for the connection thereof

Fixed space heating or


airconditioning equipment, 75% connected load;
D saunas or socket-outlets rated 12 Residence Allowance of 5kW electrical a/c 60000 65.2 0.8 81.5 3 27.2 27.2 27.2 27.2 27.2 27.2 81.5
at more than 10Amps for the load per unit
connection thereof

E Instantaneous water heaters 12 Residence No allowance included, gas 0.0 0.0 0.0 0.0

F Storage water heaters 12 Residence No allowance included 0.0 0.0 0.0 0.0

G Spa and swimming pool heaters 12 Residence No allowance included 0.0 0.0 0.0 0.0

Loading not associated with individual units - connected to each phase (communal lighting, laundry loadings, lifts, motors, etc)

H Communal lighting 12 Residence Allowance 1000W 1000 4.3 0.8 5.4 3 1.8 1.8 1.8 1.8 1.8 1.8 5.4

Socket outlets not included in


I 12 Residence NA
groups J and M below

Appliances rated at more than


J 10A and socket-outlets for the 12 Residence No allowance included 0.0 0.0 0.0 0.0
connection thereof-

125%; Allowance of 25Amps


K Lifts 12 Residence 31.3 0.8 39.1 3 39.1 39.1 39.1 39.1 39.1 39.1 39.1
3Ph per Lift

L Motors 12 Residence NA

Appliances, including socket-


M outlets other than those set out 12 Residence NA
in groups A to L above -

Red White Blue Red White Blue


Avg
(A) (A) (A) (A) (A) (A)

LOAD 120 120 120 120 120 120 120

SPARE 30% 156 156 156 156 156 156 156