EssentialsofGeneratorProtection 1/4/2016

EssentialsofGenerator
Protection
EdKhan

PROPRIETARYINFORMATION
Doble Engineering (Doble) hereby grants the recipient (you) the right to retain this
presentation and materials included within (the Presentation) for private
reference. No other rights, title, or interest, including, but not limited to, the rights
to copy, make use of, distribute, transmit, display or perform in public (or to third
parties), edit, translate, or reformat any portion of the Presentation are hereby or
otherwise granted and shall remain expressly reserved by Doble. You acknowledge
and agree that such limited license is expressly conditioned upon your acceptance
of the terms herein. You further agree that, in the event of your breach, Doble will
suffer irreparable damage and injury for which there is no adequate remedy at
law. As such, Doble, in addition to any other rights and remedies available, shall be
entitled to seek injunction by a tribunal of competent jurisdiction restricting you
from committing or continuing any breach of these terms.
2017DobleEngineeringCompany.AllRightsReserved 2

1
EssentialsofGeneratorProtection 1/4/2016

Generators KeyElementofPowerSystem

Verycriticalandexpensiveasset
Correctbehaviorkeepspowersystemtied
together
Incorrectbehaviorcanleadtodisastrous
consequenceforpowergrid
Abnormalsystemconditionsinhostutilitycan
damageagenerator needrelayprotection
package
Protectionpackagemustalsoensurethatthe
generatordoesnotcreateabnormalsystem
conditionsforhostutilities
2017DobleEngineeringCompany.AllRightsReserved 3

Generators PowerGenerationinUS

TotalPowergeneratedinUSAis4trillionkWhr (2015)

Coal =33%
Naturalgas=33%
Nuclear=20%
Hydropower=6%
Renewables=7%

2017DobleEngineeringCompany.AllRightsReserved 4

2
EssentialsofGeneratorProtection 1/4/2016

RelayProtectionofGenerators

Thereisprotectionappliedattheturbine
Thereisprotectionappliedatthegenerator
Thereisprotectionappliedatthe
interfacingswitchyard

Thiswebinarwillconsider
fewcriticalrelayprotection
appliedatagenerator
2017DobleEngineeringCompany.AllRightsReserved 5

TypicalPowerPlantLayout

Typical
Switchyard
PowerPlant
Arrangement
GSU

Excitation Auxilliary
Transformer Transformer

2017DobleEngineeringCompany.AllRightsReserved 6

3
EssentialsofGeneratorProtection 1/4/2016

RelayProtectionElements

StatorProtection
AccidentalEnergization
NegativeSequence
ReversePower
Loss ofField
GroundFault Protection
Over/UnderFrequency
TorsionalVibration
Overspeed
FieldProtection
Backup Protection
OutofStep
TrippingMethods
2017DobleEngineeringCompany.AllRightsReserved 7

RelayProtectionElements

StatorProtection
AccidentalEnergization
NegativeSequence
ReversePower
Loss ofField
GroundFault Protection
Over/UnderFrequency
TorsionalVibration
Overspeed
FieldProtection
Backup Protection
OutofStep
TrippingMethods
2017DobleEngineeringCompany.AllRightsReserved 8

4
EssentialsofGeneratorProtection 1/4/2016

StatorProtection

Phasefaultingeneratorstatorwinding
Veryharmful
R Windingdamage
Op Shaftsandcouplingscangetdamaged

GeneratorDifferential
providesanexcellent
phasefaultprotection

2017DobleEngineeringCompany.AllRightsReserved 9

StatorProtection

Willdetectfollowingfaults:
3phase
PhasePhase
R
PhasePhaseGround
Op

Maynotdetectsinglephasetogroundfault
R (dependsonhowthegeneratorisgrounded).

Detectiondependsonthemethodof
generatorneutralgrounding.
2017DobleEngineeringCompany.AllRightsReserved 10

5
EssentialsofGeneratorProtection 1/4/2016

GroundFaultProtection

Usedincommercialfacilities
480Vbreaker Generatorrated480V
HasGFtrip
Supplies480and120/220Vloads
Typicalapplication
Emergencygenerationin
datacenters,hospitals,etc.
Gen

Ifdifferentialapplieditcandetectphasetogroundfaults.
However,generatorsizesforsuchsystemsis13MVA.
Differentialusuallynotapplied.

2017DobleEngineeringCompany.AllRightsReserved 11

GroundFaultProtection
Utility
IndustrialPlant

Gen
Linetogroundfaultlimitedto
Loads 200400A
Differentialappliedifsizeis5MVA
orlarger
Differentialcandetectphaseto
51G IECIg>
groundfaults
Resistor Timeovercurrentgroundrelay

2017DobleEngineeringCompany.AllRightsReserved 12

6
EssentialsofGeneratorProtection 1/4/2016

GroundFaultProtection

HighResistanceGrounding

Allows510A
ofgroundfault

Thisispowerplantapplication

Largegenerators
Distribution Differentialisalwaysapplied
Resistor transformer
Phasetogroundmayormay
Groundovervoltagerelay notbedetected
2017DobleEngineeringCompany.AllRightsReserved 13

GroundFaultProtection

95%
5%

Turbine

59Groundovervoltagerelay
Providesgroundfaultprotectionto
27Thirdharmonicundervoltagerelay 95%ofthewinding.
Needathirdharmonicundervoltage
Distribution
transformer
relaytodetectfaultsin5%ofthe
windingmeasuredfromneutral
Resistor

2017Doble EngineeringCompany.AllRightsReserved 14

7
EssentialsofGeneratorProtection 1/4/2016

AccidentalEnergization

GeneratorEnergizedwhileonturninggearorwhileitiscoastingtoastop.
GeneratoractsasanInductionMotor(notdesignedforthismodeofoperation)
Highcurrentinrotor

Generatorconnectedtostrongsystem
Current34timesratedcurrent
Voltage5070%ofratedvoltage X

15

AccidentalEnergization

Reasons
Operatorerror
BreakerFlashover
ControlCircuitmalfunction
Combinationofabovereasons

2017DobleEngineeringCompany.AllRightsReserved 16

8
EssentialsofGeneratorProtection 1/4/2016

AccidentalEnergization

Theobjectiveofinadvertentenergizationprotectionistodetect
thatthegeneratorhasbeenremovedfromservice,buthas
suddenlybeenreenergized.

Wemustdetect:
[Generatorwasdeenergized] and[Generatorisnowenergized]

2017DobleEngineeringCompany.AllRightsReserved 17

AccidentalEnergization

Whengenerator isoffline,someoftheconditionsare:

Lowterminalvoltage
Fieldcircuitbreakerisopen
Nophasecurrent

2017DobleEngineeringCompany.AllRightsReserved 18

9
EssentialsofGeneratorProtection 1/4/2016

NegativeSequence

NegativeSequenceInducesDoubleFrequencyCurrents
intherotor

Causes:
OpenPhase
Faultsinvolvingnegativesequence
Unbalancedloads
Untransposed transmissionlines
2017DobleEngineeringCompany.AllRightsReserved 19

NegativeSequence

ANSILimitsforNegativeSequence
MachineType PermissibleI22t
SalientPoleGenerators(HydroMachines) 40 tinsecs=I22 /40
SynchronousCondensers 30 tinsecs=I22 /30
Roundrotor(indirectlycooled) 30
Roundrotor(directlycooled)<=800MVA 10
Roundrotor(directlycooled)>800MVA <10

Thelimitslistedareforshorttimeduty
ThisdataisavailableontheMainDataSheetfurnishedbytheManufacturer
2017DobleEngineeringCompany.AllRightsReserved 20

10
EssentialsofGeneratorProtection 1/4/2016

NegativeSequence

ContinuousCapabilityofMachines

MachineType PermissibleI22t
SalientPoleGenerators(withammortisseur winding) 10
SalientPoleGenerators(withammortisseur winding) 5
Roundrotor(indirectlycooled) 10
Roundrotor(directlycooled)<960MVA 8
Roundrotor(directlycooled)9611200MVA 6
Roundrotor(directlycooled)>1200MVA 5

2017DobleEngineeringCompany.AllRightsReserved 21

ReversePower

Synchronousgeneratoroperatesasasynchronousmotor
2017Doble EngineeringCompany.AllRightsReserved 22

11
EssentialsofGeneratorProtection 1/4/2016

ReversePower

ReversePoweroccurswhen:
Theturbinepowerisremoved
Excitationisavailable
Generatorisconnectedtothegrid
Generatorrunsasasynchronousmotor
Harmfulforgeneratorsespeciallysteamandhydrounits
SteamTurbinesOverheatinganddamagetoblades
HydroturbinesCavitationofblades
2017Doble EngineeringCompany.AllRightsReserved 23

ReversePower
TypicalValuesneededtoreversepower:

SteamTurbines(Conventional) 0.54%
SteamTurbines(directlycooled) 0.51%
Hydroturbines(Pondedwithpenstock) 50100%
Runoftheriverhydrounits 210%
GasTurbines(singleshaft) 4050%
GasTurbines(2shaft) 1015%
Diesel(4cycle) 15%
Diesel(2cycle) 25%

2017Doble EngineeringCompany.AllRightsReserved 24

12
EssentialsofGeneratorProtection 1/4/2016

Impedance(DistanceRelay)
X
Z=V/I RelayLocation

R R
R R

X Towards
RelayLocation generator

X
TransmissionLine
TransmissionLine
Generator ImpedanceRelay
Generator ImpedanceRelay

2017Doble EngineeringCompany.AllRightsReserved
2017DobleEngineeringCompany.AllRightsReserved 25

GeneratorCapabilityCurve

X Z=KV2/MVA

Z
MVAR(PU)

R R
MW(PU)

X
TerminalVoltageRated1perunit(PU)

2017Doble EngineeringCompany.AllRightsReserved
2017DobleEngineeringCompany.AllRightsReserved 26

13
EssentialsofGeneratorProtection 1/4/2016

GeneratorCapabilityCurveandRXdiagram

X(MVAR)
Synchronous Synchronous
Motor Generator

R R(MW)
Induction Induction
Motor Generator

2017Doble EngineeringCompany.AllRightsReserved 27

LossofField

2017Doble EngineeringCompany.AllRightsReserved 28

14
EssentialsofGeneratorProtection 1/4/2016

LossofField

Lossoffieldcausesasynchronousgeneratortooperateasan
inductiongenerator
Synchronousmachinesarenotdesignedforoperationas
inductiongenerator
Rotorsurfacetemperatureincreasesduetoslipinducededdy
current
Lossoffieldcanhavedevastatingimpactonthesystem

2017Doble EngineeringCompany.AllRightsReserved 29

LossofField

Causes:
Opencircuitinthefield
Fieldshortcircuit
Accidentaltrippingoffieldbreaker
Regulatorcontrolsystemfailure
Lossoffieldduetolossofmainexciter
Lossofacsupplytoexcitationsystem

2017Doble EngineeringCompany.AllRightsReserved 30

15
EssentialsofGeneratorProtection 1/4/2016

LossofField

Lossoffieldprotectionshouldreliablydetectthelossof
excitation
Itshoulddetectwithoutoperatingonstableswings
Itshouldbeimmunetotransients
Shouldnotoperateforshortcircuitconditions
Protectionbasedonmeasuringthefieldcurrenthavebeenused
todetectlossofexcitationbutthisisnotadequate.
2017Doble EngineeringCompany.AllRightsReserved 31

LossofField

Weneeddetectionofbothreducedexcitationandcompleteloss
ofexcitationsimpleovercurrentwillnotdothis.
Impedancerelaylookingbackintothemachineisthemost
reliabledetectionschemeforlossofexcitation

2017Doble EngineeringCompany.AllRightsReserved 32

16
EssentialsofGeneratorProtection 1/4/2016

LossofField

RelayLocation

R
X ImpedanceRelaylookinginto R
thegeneratoractsas
LossofFieldprotection

TransmissionLine
Generator ImpedanceRelay

2017Doble EngineeringCompany.AllRightsReserved 33

LossofField
Implementation

2017Doble EngineeringCompany.AllRightsReserved 34

17
EssentialsofGeneratorProtection 1/4/2016

LossofField

???
Whythisdisplacement?
Lossoffield
relaymay
operateonshort
circuit.Zmeasured
byrelayiszero

2017DobleEngineeringCompany.AllRightsReserved 35

LossofField

NodetectionifGenerator
losesfieldduringlightly
loadedcondition X
Circlemustbebigenough
Heavilyloadedgenerator
Lightlyloadedgenerator

2017DobleEngineeringCompany.AllRightsReserved 36

18
EssentialsofGeneratorProtection 1/4/2016

KeyPoints

Therearemanyprotectionfunctionsthatareneededto
provideadequateprotectiontoagenerator.
Relaysselectedtoprovidetheprotectionmustbetherighttype.
Thesettingsprovidedontherelaysmustbecorrect.
Adequatemaintenanceofrelaysisamust.

2017DobleEngineeringCompany.AllRightsReserved 37

EdKhan
ekhan@doble.com
www.doble.com

2017DobleEngineeringCompany.AllRightsReserved 38