Anda di halaman 1dari 4

ALGOMA STEEL INC.

REVISION:
DOCUMENT NO.: 452 PIPING STANDARDS & SPECIFICATIONS AUGUST 17, 1999
SECTION 16 STEAM 150 P.S.I. STEAM LINES @ 365F

1. VALVES

1.1.

STYLE DESCRIPTION SIZE NUMBER


150# buttweld, cast steel body, 13% Cr. solid or flexible wedge
Gate Valve disc, HF seats, O.S. & Y rising stem, bolted bonnet, Grafoil 3" 12" GT-153
packing, ASME B16.34, ASME B16.5 & CSA Z245.15-96
800# screwed forged steel body, 13% Cr. solid wedge disc, HF
Gate Valve seats, O.S. & Y rising stem, welded bonnet, Grafoil packing, " - 2" GT-800
Conventional or full port, ASME B1.20.1, ASME B16.11
800# socket weld forged steel body, 13% Cr. solid wedge disc, HF
Gate Valve seats, O.S. & Y rising stem, welded bonnet, Grafoil packing, " - 2" GT-801
Conventional or full port, ASME B16.11
150# buttweld, cast steel body, 13% Cr. disc, HF seat, O.S. & Y
Globe
rising stem, bolted bonnet, Grafoil packing, ASME B16.34, 3" 12" GL-152
Valve
ASME 16.5
800# screwed forged steel body, 13% Cr. disc, HF seat, O.S. & Y
Globe
rising stem, welded bonnet, Grafoil packing, Conventional or full " - 2" GL-800
Valve
port, ASME B1.20.1, ASME B16.11
Globe 800# socket weld forged steel body, 13% Cr. disc, HF seat, O.S. &
" - 2" GL-801
Valve Y rising stem, welded bonnet, Grafoil packing, ASME B16.11
150# buttweld, cast steel body, swing check, 13% Cr. disc, hard
Check
faced seat, flanged cover, ASME B16.34, ASME 16.5 & CSA 3" 12" CH-151
Valve
Z245.15-96
Check 800# screwed forged steel body, swing check, 13% Cr. disc, hard
" - 2" CH-800
Valve faced seat, flanged cover, ASME B1.20.1, ASME 16.11
Check 800# socket weld forged steel body, swing check, 13% Cr. disc,
" - 2" CH-801
Valve hard faced seat, flanged cover, ASME B1.20.1, ASME 16.11
Check 800# screwed forged steel body, lift check, 13% Cr. disc, hard
" - 2" CH-802
Valve faced seat, flanged cover, ASME B1.20.1, ASME 16.11
Check 800# socket weld forged steel body, lift check, 13% Cr. disc, hard
" - 2" CH-803
Valve faced seat, flanged cover, ASME B1.20.1, ASME 16.11
1000# socket weld 3-piece 316 S.S. body, Full-port, firetite, 316
Ball Valve S.S. ball & stem, Teflon seat & Grafoil seals, C.G.A. approved & " - 2" BA-1001
tagged, Safety Lock ready, ASME B16.34, API-607.
2000# screwed 316 S.S. body, Full-port, firetite, 316 S.S. ball &
Ball Valve stem, Teflon seat & Grafoil seals, C.G.A. approved & tagged, " - 2" BA-2001
Safety Lock ready, ASME B16.34, API-607.

NOTE: FOR ACCEPTABLE VALVE MAUFACTURERS SEE SECTION


45. FLANGED VALVES ARE BY EXCEPTION ONLY.

C:\Piping Standards\Section 16.doc

Last printed February 17, 2005


Page 1 of 4
ALGOMA STEEL INC. REVISION:
DOCUMENT NO.: 452 PIPING STANDARDS & SPECIFICATIONS AUGUST 17, 1999
SECTION 16 STEAM 150 P.S.I. STEAM LINES @ 365F

2. PIPE

2.1.

DESCRIPTION SIZE
Sch. 80 ASTM A-53-Gr-B seamless. CSA Z245.1-98 Up to 2"
Sch. 40 ASTM A-53-Gr-B seamless. CSA Z245.1-98 3" 10"
ASTM A-53 Gr. B. Seamless designed to suit pressure & temperature.
12" and up
CSA Z245.1-98

3. FITTINGS, GASKETS, TRAPS, ETC.

3.1.

STYLE DESCRIPTION SIZE


3000# forged cast steel, screwed or socket
Fittings Up to 2"
weld, CSA Z245.11-96
Cast steel, buttweld, same wall thickness as
Fittings 3" and up
pipe , CSA Z245.11-96
Gaskets Garlock - Graphonic 1/16" thick
Packing Garlock #1300 / 9000 EVSP 1/16" thick
Packing Anchor #1200 Enviro Graph
Alloy steel ASTM A-193, Grade B-7 stud
Bolts bolts c/w two hot-forged heavy hex nuts,
ASTM A-194 Grade 2H.
Trap Yarway 721-B
Trap Bestobell DM-12
Cast Steel screwed or socket weld Y-type,
Strainers 600# - 850F Grinnell or equal. Strainers
must be installed upstream of all PRV's.
Expansion Loops & As specified on drawing.
Anchors
Weld-o-lets, sock-o-lets, or full size tees.
Shut-off valves must be installed as close to
Branches
take-off as possible, unless noted otherwise
on drawing.

NOTE: SEE ITEM 6 (STEAM TRAP SELECTION REFERENCE SHEET)


FOR STEAM TRAP SELECTION REFERENCES & ADDITIONAL
INFORMATION.

C:\Piping Standards\Section 16.doc

Last printed February 17, 2005


Page 2 of 4
ALGOMA STEEL INC. REVISION:
DOCUMENT NO.: 452 PIPING STANDARDS & SPECIFICATIONS AUGUST 17, 1999
SECTION 16 STEAM 150 P.S.I. STEAM LINES @ 365F

NOTE: ALL VALVES, TRAPS, PIPING, & PIPE FITTINGS IN THIS


SECTION MUST BE MARKED WITH THEIR CRN (CANADIAN
REGISTRATION NUMBER) WHEN DELIVERED TO A.S.I.
DOCUMENTATION MUST ALSO BE FORWRDED TO A.S.I.
PURCHASING DEPARTMENT & THE Q/C INSPECTOR &
CHIEF OPERATING ENGINEER OR A.S.I. UTILITIES
DEPARTMENT.

4. PRESSURE TEST REQUIREMENTS

WORKING LENGTH OF PIPE


PIPE DIAMETER TEST PRESSURE TEST DURATION
PRESSURE OR TUBING
(INCHES) (P.S.I.G.) (HOURS)
(P.S.I.G.) (FEET)
1.5x Maximum
Over 33 All Sizes All Lengths 24
Operating Pressure

5. ADDITIONAL INFORMATION

5.1. Steam main lines to be properly sloped and provided with drip legs and
trap connections at low points. 300' maximum spacing.

5.2. Welds must be Department of Labour Standard and bear stamp of welder.

5.3. All steam lines having a pressure above 15 p.s.i.g are to be approved by a
certified Professional Engineer Licensed in the Province of Ontario, and
also subject to the approval of the TSSA (Technical Standards & Safety
Authority) which is an independent, non-government, organization
responsible for regulating boilers, pressure vessels, pressure piping and
fittings manufactured and used in Ontario under the "Boilers and Pressure
Vessels Act".

5.4. For insulation requirements for steam mains see Section 10 (INSULATION
PIPE COVERING & INSULATION)

5.5. Socket weld fittings preferred for 2" diameter & under, however, screwed
fittings can be used where frequently serviced equipment is installed, (i.e.
steam traps, strainers, gauges, etc.) provided the valve directly upstream of
these items is a socket weld valve (last isolation valve).

C:\Piping Standards\Section 16.doc

Last printed February 17, 2005


Page 3 of 4
ALGOMA STEEL INC. REVISION:
DOCUMENT NO.: 452 PIPING STANDARDS & SPECIFICATIONS AUGUST 17, 1999
SECTION 16 STEAM 150 P.S.I. STEAM LINES @ 365F

6. STEAM TRAP SELECTION REFERENCE SHEET

DRIP LEG APPLICATIONS YARWAY BESTOBELL NOTES


MODEL MODEL
150# Applications 721 B DM 12
400# Applications 721 HP DM 40
600# Applications HP - 60 DM - 64
150# Process Applications
Small sized unit heaters 0-86,000 BTU All sub-cooled traps should have
that are graded to condensate return 761-5 or PB 5 M - 22 ample dirt pocket, 14" x 1" or larger
system before trap leg of unit heater.
Small sized unit heaters 0-86,000 BTU
741 AL M 22
with an overhead condensate return
Medium sized unit heaters and Heat
exchangers 86,000-100,000 BTU that are 721 HC DM 12
graded to condensate return system
Medium sized unit heaters and Heat
exchangers 86,000-100,000 BTU with an 741 AL DM 12
overhead condensate return
Large unit heaters and Heat exchangers
100,000-750,000 BTU graded to 741 BL M 16
condensate return
Large unit heaters and Heat exchangers
100,000-750,000 BTU with overhead 741 CL M 16
condensate return
X-large unit heaters and heat exchanger
units 750,000-1,000,000 BTU graded to 151 GM 16
condensate return
X-large unit heaters and heat exchanger
units 750,000-1,000,000 BTU with 151 - HC GM - 16
overhead condensate return
YARWAY BESTOBELL NOTES
Tracing Applications
MODEL MODEL
Black pipe tracing systems 761 40 M 22 Install blowdown valve
Stainless Steel pipe or stainless steel and
PB 40 TM 22 Blowdown valve not required
copper tubing
The above applications are for a quick reference only. If in doubt please contact Terry Walsh ext. 3694 for inspection prior to
installation. For example: low pressure (15# or 30#) multi-trap or elevated condensate return form grade applications into a common
return header where back pressure may short circuit the system. Additional specialty traps are available for extreme service but in
the best interest of Algoma Steel Inc. standardization to the above units will be adequate.

C:\Piping Standards\Section 16.doc

Last printed February 17, 2005


Page 4 of 4