Anda di halaman 1dari 4

GAS DETECTION SYSTEM CALIBRATION AND FUNCTION TEST REPORT QHSE-Form-118 A

Detection System: DETCON WIRELESS GAS DETECTION SYSTEM Performed Activity :

Client: SAUDI ARAMCO Date: 06-APR-2017 Next Calibration Due Date: 4-APR-2017 Calibration
(to be filled during calibration only)
Rig / Facility / Site #: GREY WOLF-95 Location / Well # : MNIF-242 X Function Test
CALIBRATION FUNCTION TEST
Sensor Alarm Response Time
Sensor Sensor Gas Cal Level Full Span Resultant Peak *
Manufacturer Model Range Unit Location Response Remarks
Type Serial # Applied Setting Value Value Reading Time, T50 ** Low Alarm High Alarm
DETCON CXT-DM 0-100 PPM H2S HCQ76 WELL-246 50 PPM N/A N/A N/A 51 PPM 12 SEC 22 SEC 33 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT051334 WELL-246 50 % N/A N/A N/A 49 % 12 SEC 21 SEC 30 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HLQ149 WELL-245 50 PPM N/A N/A N/A 53 PPM 14 SEC 22 SEC 32 SEC PASSED
DETCON CXT-IR 0-100 % LEL D6.05.50.A0 WELL-245 50 % N/A N/A N/A 51 % 13 SEC 23 SEC 34 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HDQ101 WELL-240 50 PPM N/A N/A N/A 52 PPM 12 SEC 22 SEC 34 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT055354 WELL-240 50 % N/A N/A N/A 48 % 11 SEC 21 SEC 32 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HHQ485 HDR-240 50 PPM N/A N/A N/A 52 PPM 11 SEC 20 SEC 30 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT038317 HDR-240 50 % N/A N/A N/A 50 % 13 SEC 24 SEC 33 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HDRO1655 HDR-245 50 PPM N/A N/A N/A 49 PPM 11 SEC 21 SEC 30 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT043019 HDR-245 50 % N/A N/A N/A 50 % 13 SEC 22 SEC 31 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HHQ88 HDR-246 50 PPM N/A N/A N/A 50 PPM 12 SEC 21 SEC 32 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT037909 HDR-246 50 % N/A N/A N/A 49 % 11 SEC 23 SEC 34 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HDQ199 MOV 50 PPM N/A N/A N/A 51 PPM 11 SEC 22 SEC 33 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT2395 MOV 50 % N/A N/A N/A 49 % 12 SEC 20 SEC 31 SEC PASSED

UPS Function Self Test


Controller Buttons / Test Auto-Switch Battery Runtime Alarm Function All Beacon All Sirens /
Display Communication (if
Function Test Touchscreen Result (power source) Test (min. 1 hour) Test Lights (Visual) Horns (Audible)
applicable)
Result PASSED PASSED PASSED (prior to PASSED PASSED PASSED Result PASSED PASSED
bump test)
Additional Remarks (if any) : ALL THE TWELVE BUZZERS INSIDE THE MINI CAMP ARE WORKING GOOD DURING FUNCTION TEST
Notes:
* Peak reading tolerances are based on ANSI/ISA standards.
H2S : 3 ppm or 10% of applied gas, whichever is greater
Acceptance Criteria for Sensor Response Performed By: IMRAN/MARBIN
LEL : 5% of range or 10% of applied gas, whichever is greater Sensor reading to get T50 value
Acceptable Peak Reading
SO2 : 0.8 ppm or 15% of applied gas, whichever is greater
Standard Reference Response Time
Applied Gas (with
Tolerance Signature:
acceptable response time)
CO : 6 ppm or 10% of applied gas, whichever is greater 25 ppm 13 ppm (less than 45 sec) 3 ppm
H2S T50 45 sec Badge Number: 15182 / 32151
** T50 refers to the time it takes for the sensor to display 50% of the 50 ppm 25 ppm (less than 45 sec) 5 ppm
applied gas. ANSI/ISA-92.00.01-2010 Performance 5 ppm 2.5 ppm (less than 30 sec) 0.8 ppm
SO2 T50 30 sec
Calibration / Test Equipment Utilized Requirements for Toxic Gas Detectors - 10 ppm 5.0 ppm (less than 30 sec) 1.5 ppm
Item Status Annex A, page 35 20 ppm 10 ppm (less than 45 sec) 6 ppm
H2S Gas Exp: NOV/2018 CO T50 45 sec 25 ppm 13 ppm (less than 45 sec) 6 ppm
Methane Gas (LEL) Exp: DEC/2020 100 ppm 50 ppm (less than 45 sec) 10 ppm Verified By: HISHAM MOSA
SO2 Gas Exp: N/A
ANSI/ISA-60079-29-1 (12.13.01) - 2013 Signature:
CO Gas Exp: N/A
Performance Requirements of Detectors LEL T50 20 sec 50 %LEL 25 % (less than 20 sec) 5 %LEL
CO2 Gas Exp: N/A for Flammable Gases - Annex A, page 39
Rawabi United Safety Services I P.O. Box 79800, Al-Khobar 31952 | Tel: 812 7758 X 212, Fax: 812 7759 | Email: operations@rawabiunited.com Rev. 02, July 2016
ANSI/ISA-60079-29-1 (12.13.01) - 2013
Performance Requirements of Detectors LEL T50 20 sec 50 %LEL 25 % (less than 20 sec) 5 %LEL
for Flammable Gases - Annex A, page 39
Regulator Flowrate: 0.5 LPM Badge Number: 162044

Rawabi United Safety Services I P.O. Box 79800, Al-Khobar 31952 | Tel: 812 7758 X 212, Fax: 812 7759 | Email: operations@rawabiunited.com Rev. 02, July 2016
GAS DETECTION SYSTEM CALIBRATION AND FUNCTION TEST REPORT QHSE-Form-118 A

Detection System: DETCON WIRELESS GAS DETECTION SYSTEM Performed Activity :

Client: SAUDI ARAMCO Date: 14-APR-2017 Next Calibration Due Date: 4-APR-2017 Calibration
(to be filled during calibration only)
Rig / Facility / Site #: GREY WOLF-95 Location / Well # : MNIF-242 X Function Test
CALIBRATION FUNCTION TEST
Sensor Alarm Response Time
Sensor Sensor Gas Cal Level Full Span Resultant Peak *
Manufacturer Model Range Unit Location Response Remarks
Type Serial # Applied Setting Value Value Reading Time, T50 ** Low Alarm High Alarm
DETCON CXT-DM 0-100 PPM H2S HCQ76 WELL-246 50 PPM N/A N/A N/A 49 PPM 13 SEC 23 SEC 36 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT051334 WELL-246 50 % N/A N/A N/A 51 % 14 SEC 22 SEC 33 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HLQ149 WELL-245 50 PPM N/A N/A N/A 50 PPM 12 SEC 24 SEC 35 SEC PASSED
DETCON CXT-IR 0-100 % LEL D6.05.50.A0 WELL-245 50 % N/A N/A N/A 48 % 11SEC 21 SEC 32 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HDQ101 WELL-240 50 PPM N/A N/A N/A 53 PPM 14 SEC 24 SEC 35 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT055354 WELL-240 50 % N/A N/A N/A 49 % 12 SEC 20 SEC 31 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HHQ485 HDR-240 50 PPM N/A N/A N/A 51 PPM 14 SEC 23 SEC 34 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT038317 HDR-240 50 % N/A N/A N/A 50 % 12 SEC 22 SEC 34 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HDRO1655 HDR-245 50 PPM N/A N/A N/A 48 PPM 12 SEC 22 SEC 32 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT043019 HDR-245 50 % N/A N/A N/A 52 % 14 SEC 24 SEC 34 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HHQ88 HDR-246 50 PPM N/A N/A N/A 51 PPM 13 SEC 22 SEC 33 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT037909 HDR-246 50 % N/A N/A N/A 47 % 11 SEC 21SEC 31 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HDQ199 MOV 50 PPM N/A N/A N/A 49 PPM 13 SEC 22 SEC 32 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT2395 MOV 50 % N/A N/A N/A 51 % 13 SEC 24 SEC 34 SEC PASSED

UPS Function Self Test


Controller Buttons / Test Auto-Switch Battery Runtime Alarm Function All Beacon All Sirens /
Display Communication (if
Function Test Touchscreen Result (power source) Test (min. 1 hour) Test Lights (Visual) Horns (Audible)
applicable)
Result PASSED PASSED PASSED (prior to PASSED PASSED PASSED Result PASSED PASSED
bump test)
Additional Remarks (if any) : ALL THE TWELVE BUZZERS INSIDE THE MINI CAMP ARE WORKING GOOD DURING FUNCTION TEST
Notes:
* Peak reading tolerances are based on ANSI/ISA standards.
H2S : 3 ppm or 10% of applied gas, whichever is greater
Acceptance Criteria for Sensor Response Performed By: IMRAN/MARBIN
LEL : 5% of range or 10% of applied gas, whichever is greater Sensor reading to get T50 value
Acceptable Peak Reading
SO2 : 0.8 ppm or 15% of applied gas, whichever is greater
Standard Reference Response Time
Applied Gas (with
Tolerance Signature:
acceptable response time)
CO : 6 ppm or 10% of applied gas, whichever is greater 25 ppm 13 ppm (less than 45 sec) 3 ppm
H2S T50 45 sec Badge Number: 15182 / 32151
** T50 refers to the time it takes for the sensor to display 50% of the 50 ppm 25 ppm (less than 45 sec) 5 ppm
applied gas. ANSI/ISA-92.00.01-2010 Performance 5 ppm 2.5 ppm (less than 30 sec) 0.8 ppm
SO2 T50 30 sec
Calibration / Test Equipment Utilized Requirements for Toxic Gas Detectors - 10 ppm 5.0 ppm (less than 30 sec) 1.5 ppm
Item Status Annex A, page 35 20 ppm 10 ppm (less than 45 sec) 6 ppm
H2S Gas Exp: NOV/2018 CO T50 45 sec 25 ppm 13 ppm (less than 45 sec) 6 ppm
Methane Gas (LEL) Exp: DEC/2020 100 ppm 50 ppm (less than 45 sec) 10 ppm Verified By: MOHAMMED SHAHIN
SO2 Gas Exp: N/A
ANSI/ISA-60079-29-1 (12.13.01) - 2013 Signature:
CO Gas Exp: N/A
Performance Requirements of Detectors LEL T50 20 sec 50 %LEL 25 % (less than 20 sec) 5 %LEL
CO2 Gas Exp: N/A for Flammable Gases - Annex A, page 39
Rawabi United Safety Services I P.O. Box 79800, Al-Khobar 31952 | Tel: 812 7758 X 212, Fax: 812 7759 | Email: operations@rawabiunited.com Rev. 02, July 2016
ANSI/ISA-60079-29-1 (12.13.01) - 2013
Performance Requirements of Detectors LEL T50 20 sec 50 %LEL 25 % (less than 20 sec) 5 %LEL
for Flammable Gases - Annex A, page 39
Regulator Flowrate: 0.5 LPM Badge Number: 8055122