Client: SAUDI ARAMCO Date: 06-APR-2017 Next Calibration Due Date: 4-APR-2017 Calibration
(to be filled during calibration only)
Rig / Facility / Site #: GREY WOLF-95 Location / Well # : MNIF-242 X Function Test
CALIBRATION FUNCTION TEST
Sensor Alarm Response Time
Sensor Sensor Gas Cal Level Full Span Resultant Peak *
Manufacturer Model Range Unit Location Response Remarks
Type Serial # Applied Setting Value Value Reading Time, T50 ** Low Alarm High Alarm
DETCON CXT-DM 0-100 PPM H2S HCQ76 WELL-246 50 PPM N/A N/A N/A 51 PPM 12 SEC 22 SEC 33 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT051334 WELL-246 50 % N/A N/A N/A 49 % 12 SEC 21 SEC 30 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HLQ149 WELL-245 50 PPM N/A N/A N/A 53 PPM 14 SEC 22 SEC 32 SEC PASSED
DETCON CXT-IR 0-100 % LEL D6.05.50.A0 WELL-245 50 % N/A N/A N/A 51 % 13 SEC 23 SEC 34 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HDQ101 WELL-240 50 PPM N/A N/A N/A 52 PPM 12 SEC 22 SEC 34 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT055354 WELL-240 50 % N/A N/A N/A 48 % 11 SEC 21 SEC 32 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HHQ485 HDR-240 50 PPM N/A N/A N/A 52 PPM 11 SEC 20 SEC 30 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT038317 HDR-240 50 % N/A N/A N/A 50 % 13 SEC 24 SEC 33 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HDRO1655 HDR-245 50 PPM N/A N/A N/A 49 PPM 11 SEC 21 SEC 30 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT043019 HDR-245 50 % N/A N/A N/A 50 % 13 SEC 22 SEC 31 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HHQ88 HDR-246 50 PPM N/A N/A N/A 50 PPM 12 SEC 21 SEC 32 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT037909 HDR-246 50 % N/A N/A N/A 49 % 11 SEC 23 SEC 34 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HDQ199 MOV 50 PPM N/A N/A N/A 51 PPM 11 SEC 22 SEC 33 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT2395 MOV 50 % N/A N/A N/A 49 % 12 SEC 20 SEC 31 SEC PASSED
Rawabi United Safety Services I P.O. Box 79800, Al-Khobar 31952 | Tel: 812 7758 X 212, Fax: 812 7759 | Email: operations@rawabiunited.com Rev. 02, July 2016
GAS DETECTION SYSTEM CALIBRATION AND FUNCTION TEST REPORT QHSE-Form-118 A
Client: SAUDI ARAMCO Date: 14-APR-2017 Next Calibration Due Date: 4-APR-2017 Calibration
(to be filled during calibration only)
Rig / Facility / Site #: GREY WOLF-95 Location / Well # : MNIF-242 X Function Test
CALIBRATION FUNCTION TEST
Sensor Alarm Response Time
Sensor Sensor Gas Cal Level Full Span Resultant Peak *
Manufacturer Model Range Unit Location Response Remarks
Type Serial # Applied Setting Value Value Reading Time, T50 ** Low Alarm High Alarm
DETCON CXT-DM 0-100 PPM H2S HCQ76 WELL-246 50 PPM N/A N/A N/A 49 PPM 13 SEC 23 SEC 36 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT051334 WELL-246 50 % N/A N/A N/A 51 % 14 SEC 22 SEC 33 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HLQ149 WELL-245 50 PPM N/A N/A N/A 50 PPM 12 SEC 24 SEC 35 SEC PASSED
DETCON CXT-IR 0-100 % LEL D6.05.50.A0 WELL-245 50 % N/A N/A N/A 48 % 11SEC 21 SEC 32 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HDQ101 WELL-240 50 PPM N/A N/A N/A 53 PPM 14 SEC 24 SEC 35 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT055354 WELL-240 50 % N/A N/A N/A 49 % 12 SEC 20 SEC 31 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HHQ485 HDR-240 50 PPM N/A N/A N/A 51 PPM 14 SEC 23 SEC 34 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT038317 HDR-240 50 % N/A N/A N/A 50 % 12 SEC 22 SEC 34 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HDRO1655 HDR-245 50 PPM N/A N/A N/A 48 PPM 12 SEC 22 SEC 32 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT043019 HDR-245 50 % N/A N/A N/A 52 % 14 SEC 24 SEC 34 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HHQ88 HDR-246 50 PPM N/A N/A N/A 51 PPM 13 SEC 22 SEC 33 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT037909 HDR-246 50 % N/A N/A N/A 47 % 11 SEC 21SEC 31 SEC PASSED
DETCON CXT-DM 0-100 PPM H2S HDQ199 MOV 50 PPM N/A N/A N/A 49 PPM 13 SEC 22 SEC 32 SEC PASSED
DETCON CXT-IR 0-100 % LEL OPT2395 MOV 50 % N/A N/A N/A 51 % 13 SEC 24 SEC 34 SEC PASSED
Rawabi United Safety Services I P.O. Box 79800, Al-Khobar 31952 | Tel: 812 7758 X 212, Fax: 812 7759 | Email: operations@rawabiunited.com Rev. 02, July 2016