Anda di halaman 1dari 8

Neutral-Point-Clamped Circuits of Single-Phase PV

Inverters: Generalized Principle and Implementation


Liwei Zhou1, Feng Gao1, Tingting Yang2
1 2
School of Electrical Engineering State Grid Chongqing Electric Power Company
Shandong University Chongqing, China
Jinan, China

AbstractThe common-mode leakage current should be common mode leakage current in transformerless inverter, the
carefully considered when designing a transformer-less most effective solution is to keep the common mode voltage
photovoltaic (PV) inverter since the leakage current can cause constant [3]. So far, several single-phase topologies have been
the output current distortion and increase the operational risk. proposed to maintain the common-mode voltage constant as
The unipolar SPWM of traditional H-bridge inverter can half of DC bus voltage, for example, H5, HERIC and H6
produce superior output performance but will cause a high- topologies [4-7]. However, the common-mode voltage is
frequency common-mode voltage and consequently the non- indeed variable during the freewheeling stage because of the
negligible leakage current. To attenuate the fluctuation of potential variation induced by the charging of switch junction
common-mode voltage, few neutral-point-clamped circuits have
capacitance. Thus, the leakage current still exists in the
been designed to clamp the neutral point voltage and maintain
the common mode voltage constant. This paper reviews the
common-mode circuit. Besides, few neutral-point-clamped
already published single-phase inverters with constant common circuits have been proposed to effectively clamp the common
mode voltage in theory and proposes a generalized design mode voltage to be half of dc bus voltage during whole
principle of multi-terminal neutral-point-clamped circuits, whose fundamental period [8-10]. But the general methods to design
unidirectional and bidirectional variations are fully analyzed and analyze the neutral-point-clamped circuits were lack of
respectively. Subsequently, two families of new single-phase PV presentation.
inverters with neutral-point-clamped circuits are proposed. Also,
This paper presents the general design method of clamping
the efficiency, cost and control complexity are compared between
circuits and proposes the corresponding unidirectional and
the proposed topologies and the traditional NPC inverters to
prove the superiority of the proposed topologies. The simulation
bidirectional neutral-point-clamped circuits and analyzes their
and experimental results verified the theoretical findings. operational theory. And then two families of neutral-point-
clamped single-phase PV inverters are proposed by using
Keywordsphotovoltaic inverter; neutral-point-clamped unidirectional and bidirectional clamping circuits, respectively.
circuit; common-mode voltage; transformerless inverter The comparative analysis shows the advantages of the
proposed topologies in the aspect of efficiency, device cost and
I. INTRODUCTION control complexity. The simulation and experimental results
In the grid-connected photovoltaic (PV) inversion system, have verified the performance of proposed circuits.
high efficiency, high performance and low cost are the three
II. MODELING OF COMMON MODE CIRCUIT IN SINGLE-PHASE
main targets pursuing. Traditionally, a line-frequency or high-
PV INVERTER
frequency transformer is employed in the PV inverter to isolate
the grid from the PV source to attenuate the common mode Fig. 1 shows the topology of traditional single-phase
leakage current and step up output voltage. However, the transformerless PV inverter, where four switches operate at
transformer will unavoidably reduce the operational efficiency high frequency and the corresponding common mode voltage
and increase system cost and size [1]. Therefore, the can be expressed as:
transformerless PV inverters are now attracting much more
uao + ubo
attention. The main problem of transformerless PV inverter is ucm = (1)
that it has no galvanic isolation and then the common-mode 2
leakage current can flow through the parasitic capacitance Where, uao and ubo are the pulsating voltage between the
between PV array and ground, which will threaten people midpoint of bridges and the negative DC rail, respectively. The
safety and cause other severe problems [2]. To attenuate the common-mode current icm is mainly induced by the fluctuation
of ucm as expressed in (2).
ducm
icm = CPV (2)
dt
Without the isolation transformer, the common-mode
leakage current can flow through the parasitic capacitance
existed between ground and PV array, the equivalent grid
impedance, and the output filter. As a consequence, the leakage
Fig. 1. The common-mode circuit of single-phase PV inverter. current may exceed the permissible levels defined by standards,

978-1-4673-7151-3/15/$31.00 2015 IEEE 442


p p p
S1 S3 La La La

a E E E
b
U dc U dc U dc
o o o
PV PV
PV Lb Lb
Lb
S5 S6

S2 S4
n n
n
(a) (b) (c)
Fig. 2. (a) Topology of H6 inverter and the equivalent circuits during (b) power transferring mode and (c) freewheeling mode.

e.g. DIN VDE 0126-1-1, and will cause the safety problems (a) The clamping circuit should be bidirectional.
and distort the output current.
(b) The clamping circuit will not shoot-through DC rails.
Several single-phase inverters have the capability of
attenuating the common-mode current, such as H5, Heric, HB- (c) The clamping circuits should be connected to the
ZVR and H6 topologies. These inverters can use the auxiliary midpoint of DC link and form an additional freewheeling path.
switches and diodes to provide the additional freewheeling path Following the above principles, the clamping circuit should
to make the common-mode voltage be constant during the have at least three effective connection terminals, one of which
whole fundamental period in theory. However, because of the will connect to the midpoint of dc-link and others will connect
charging of switch junction capacitance during the to the output terminal per bridge to form a freewheeling path.
freewheeling modes, the common-mode voltage is indeed not Because the null state operation of unipolar PWM in traditional
constant. Specifically taking the topology of Fig. 2 as an H-bridge inverter will force common mode voltage be Vdc or 0,
example, which can maintain the common mode voltage not Vdc/2, the alternative freewheeling path should leave S1-S4
constant in theory, during the energy transferring modes in the OFF during the null state intervals. Fig. 3 shows the general
positive fundamental period, although the equivalent junction configuration of clamping circuit in single-phase inverter,
capacitances C2, C3 and C6 are charged, Uan and Ubn will where the clamping circuit can be inserted at three different
maintain constant as Vdc and 0, respectively. On the other hand, locations. To fully satisfy the operational principle of clamping
in the freewheeling mode, the junction capacitances C1-C4, C6 circuits, two types of neutral point clamped circuits can be
are charged and Upa, Ubn are increased, thus the potentials of a designed with unidirectional and bidirectional current flow
and b vary during the whole fundamental period. Then the capability, respectively. In particular, Fig. 4 shows the
common-mode voltage is not strictly half of DC bus voltage, unidirectional clamping circuits, which consists of two diodes
especially during the freewheeling mode. A fluctuating and one switch. It is noted that only diode Dc connects to the
common-mode voltage will cause a high level of leakage midpoint of dc-link allowing current flow in one direction. Fig.
current which is not permitted in the PV applications. Hence, it 5 shows the bidirectional clamping circuits, which consists of
is necessary to add a neutral-point-clamped circuit to make the three switches. Following the principle (a) stated above, the
common-mode voltage constant. clamping circuit should be bidirectional. Therefore, a complete
neutral point clamping circuit for a single phase PV inverter
III. GENERAL DESIGN PRINCIPLE OF NEUTRAL-POINT-CLAMPED should consist of the two unidirectional neutral clamping
CIRCUITS circuits in Fig. 4 or one of the bidirectional neutral clamping
The function of neutral-point-clamped circuits is to clamp circuits in Fig. 5.
the output voltage of two phase-legs during freewheeling mode.
Thus, the design of clamping circuits should follow the IV. IMPLEMENTATION OF NEUTRAL-POINT-CLAMPED CIRCUITS
principles below:
p p p
S1 S3 S1 S3 S1 S3
La La La
a a
a

PV E PV E PV E

b o o o
b b
Lb Lb Lb
S2 S4 S2 S4 S2 S4

n n n

(a) (b) (c)


Fig. 3. The general configuration of clamping circuits inserted at three different locations.

443
[10]. And Fig. 6(b) and (c) show that the clamping circuits can
be inserted in any phase-leg to form a freewheeling path, which
correspond to the general indication of Fig. 3(b) and (c).
Besides, two unidirectional circuits can be inserted flexibly as
shown in Fig. 6(d), (e), (f) and (g), where one unidirectional
circuit is inserted in one phase-leg and another connects the
midpoint of dc-link and output terminals of H-bridge directly.
To briefly illustrate the operational principle of proposed
single-phase inverters with unidirectional clamping circuits, the
(a) (b) topology of Fig. 6(b) is assumed as an example, which has four
Fig. 4. The unidirectional neutral clamping circuits. operation modes. Fig. 7 shows the specific current flow paths
during the energy transferring modes and the freewheeling
modes.
Mode 1: During positive half period, S1 and S4 are
modulated in high frequency, while S5 is always ON and S6
works complementarily to S1 and S4. When S1 and S4 are on,
the current flows through S1, S5, grid and S4 successively. The
common-mode voltage is
uan + ubn udc + 0 udc
(a) (b) ucm = = = (3)
Fig. 5. The bidirectional neutral clamping circuits. 2 2 2
This section presents the detailed implementation of Mode 2: When S1 and S4 are off, the current flows through
neutral-point-clamped circuits. The unidirectional and D1, S5 and grid successively. The common-mode voltage is
bidirectional clamping circuits are implemented, respectively. uan + ubn udc / 2 + udc / 2 udc
ucm = = = (4)
A. Implementation of Unidirectional Clamping Circuits 2 2 2
As indicated by Fig. 3 and 4, two unidirectional clamping Mode 3: During negative half period, S2 and S3 are
circuits should be combined together to form a bidirectional modulated in high frequency, while S6 is always ON and S5
freewheeling path. Also, the variations of circuit combination works complementarily to S2 and S3. When S2 and S3 are on,
can be inserted in the traditional H-bridge inverter as the current flows through S3, grid, S6 and S2 successively. The
generalized in Fig. 3. Fig. 6(a)-(g) shows the produced common-mode voltage is
topologies using unidirectional clamping circuits, which makes
up a family of neutral-point-clamped single-phase inverters. In uan + ubn 0 + udc udc
ucm = = = (5)
particular, Fig. 6(a) shows the topology with clamping circuits 2 2 2
inserted between dc-link and H-bridge as indicated by Fig. 3(a)

p p
S1
p S3
S1 S3
S3 S1
La
a S5 La S5
La
U dc E a
PV a E
S5 S6 PV PV b E
o o
b
b o S6
Lb S6 Lb
Lb S2
S2 S4
S4
S4
n
S2
n n

(a) (b) (c)


p p
p p
S1 S3 S1 S3
S1 S3 S1 S3
La
La ' La a
a a La
'F 'F ' S5 '
S6 ' U dc E
U dc 'F S5 E U dc E S6 a
PV PV PV b PV U dc 'F
' 'F S6 S5 S6
'F S5 Lb E
' o o o
'F b b ' '
Lb Lb 'F b o
S2 S4 S2 S4 Lb
S2 S4 S2 S4
n n
n n

(d) (e) (f) (g)


Fig. 6. A family of single-phase inverters with unidirectional clamping circuits.

444
p
S1

S3
S5 La
a E
PV
o
b
S6
Lb

S4

S2
n

(a)

p
S1

S3
Fig. 8. Modulation illustration.
S5 La
Mode 4: When S2 and S3 are off, the current flows through
a
PV E S6, D2 and grid successively. The common-mode voltage is
o
b
Lb uan + ubn udc / 2 + udc / 2 udc
S6 ucm = = = (6)
2 2 2
S4
When the potential of points a and b falls to lower than that
n
S2 of the midpoint of DC link, the common-mode current flows
through D3, thus it will balance the potential of freewheeling
(b) path. On the other hand, when the potential of points a and b
rises to higher than that of the midpoint of DC link, the
p
S1
common-mode current will flow through D4 and balance the
potential of two bridges. Thus, the common-mode voltage can
S3
keep constant during the whole fundamental period.
S5 La
The corresponding modulation strategy is shown in Fig. 8,
where S1-S6 are the gating signals of proposed inverters in Fig.
a
E 6(b).
PV
o
b B. Implementation of Bidirectional Clamping Circuits
S6
Lb
As indicated by Fig. 3 and Fig. 5, three switches combined
S4 together with the common emitters or common collectors can
form a bidirectional freewheeling path. Also, the clamping
S2 circuit can be inserted in the traditional H-bridge inverter as
n
generalized in Fig. 3. Fig. 9 shows the produced topologies
(c) using bidirectional clamping circuits, which makes up a family
of neutral-point-clamped single-phase inverters. In particular,
p Fig. 9(a) and (d) show the topologies with clamping circuits
S1
inserted between dc-link and H-bridge as indicated by Fig. 3(a)
S3 [9]. And Fig. 9(b), (c), (e) and (f) show that the clamping
circuits can be inserted in any phase-leg to form a freewheeling
S5 La path, which correspond to the general indication of Fig. 3(b)
a
and (c).
PV E
b
o In order to briefly illustrate the operational principle of
S6
Lb proposed single-phase inverters with bidirectional clamping
circuits, the topology of Fig. 9(b) is assumed as an example,
S4 which has four operation modes. Fig.10 shows the specific
current flow paths during the energy transferring modes and
S2
n the freewheeling modes. When the potential of points a and b
falls to lower than that of the midpoint of DC link in the
(d)
Fig. 7. Four operating modes of the proposed topology in Fig. 6(b).

445
p p p
S1 S3 S1 S3 S1 S3
La La
La a a
S6 S6
a E
b
E
PV E PV PV o
b
S5 Lb
b o
S5 o S5 Lb
S2 S4 Lb S2 S4 S2
S6 S 4

n n n

(a) (b) (c)


p p p
S1 S3 S1 S3 S1 S3
S6
S6 La La
a
S5 La
a
E S5
PV PV E PV
a
b S6 E
o o o
Lb b b
S2 S4 S2 S4 Lb S2 S4 Lb
S5
n n n

(d) (e) (f)


Fig. 9. A family of single-phase inverters with bidirectional clamping circuits.
freewheeling modes, the common-mode current flows through which is less than the topologies in Fig 11. Finally, in the
S7, thus it will balance the potential of freewheeling path. On aspect of control complexity, the NPC circuits in Fig. 6 and Fig.
the other hand, when the potential of points a and b rises to 9 are simpler compared to Fig. 11(b).
higher than that of the midpoint of DC link, the common-mode
current will flow through S7 and balance the potential of two VI. SIMULATION AND EXPERIMENTAL RESULTS
bridges either. Thus, the common-mode voltage can keep The simulation and experimental results are shown in this
constant during the whole fundamental period. section. The proposed inverters in Fig. 6(b) and Fig. 9(b) were
The corresponding modulation strategy is also shown in Fig. simulated in Matlab/Simulink. The DC voltage is 200V, and
8, where S1-S7 are the gating signals of proposed inverters in the grid voltage is 110V/50Hz. The switching frequency is
Fig. 9(b). 10kHz. The output inductors are both 2mH. The stray
capacitance between PV array and ground is 470nF. The grid
V. COMPARISON WITH OTHER NPC TOPOLOGIES current is controlled by a conventional PR controller. Fig. 12
shows the comparison of the common-mode characteristics of
To make a specific analysis of the two families of novel traditional H6 inverter and proposed inverters with the
NPC inverters, a comparison between the proposed topologies unidirectional neutral clamping circuits and the bidirectional
and the traditional NPC inverters is shown in this section. neutral clamping circuits. The proposed topologies can achieve
Fig. 11 shows the traditional NPC single phase inverters a more constant common-mode voltage and low leakage
[11-12], which also have the function of clamping the common current. Fig. 13 and Fig. 14 show the switching sequences of
mode voltage to half of the DC link voltage during the two inverters proposed in Fig. 6(b) and Fig. 9(b).
freewheeling period. From the point of cost and losses, the In order to further validate the proposed topologies and the
comparative analysis is given in Table I. Firstly, in the aspect modulation strategies, the 1kW experimental prototypes were
of device cost, the topologies in Fig. 9 with the bidirectional built with the same parameters as the simulation model. The
circuits only need 7 switches, which save 1 switch compared to experimental results are shown in Fig. 15 and 16. It is noted
that in Fig. 11(b) and 2 diodes compared to that in Fig 11(a), that the common mode voltage of proposed circuits have less
respectively. So, the novel inverters have lower cost. Secondly, variation as shown in Fig. 16.
in the aspect of efficiency, the novel NPC topologies have the
VII. CONCLUSION
This paper generalizes the neutral-point-clamped circuits
TABLE I. THE COMPARISON OF THE NPC TOPOLOGIES with unidirectional and bidirectional current flow capability.
power freewheeling Then this paper implements the specific circuits in single-phase
topologies switches diodes
modes modes photovoltaic inverters, where two families of single-phase
Fig 6 6 4 2(3)switches 1switch+1diode inverters are fully analyzed. Doing so, the common mode
Fig 9 7 0 2(3)switches 2switches
Fig 11(a) 6 2 4switches 2switches voltage of single-phase inverter can be effectively maintained
Fig 11(b) 8 0 4(2)switches 4switches constant as half of dc-link voltage. Besides, a hybrid switching
advantages in the conduction loss. In the power delivering modulation strategy can be assumed to command these new
modes, the current flows through only 2 or 3 devices in inverters. The simulation and experimental results verified the
proposed topologies and 2 devices in the freewheeling modes, performance of proposed inverters.

446
p
S1 S3
La
a
S6
E
PV b

S5 Lb
S2 S4

n
(a)
(a)
p
S1 S3
La
a
S6
E
PV b

6 S5 Lb
S2 S4

n
(b)
(b) Fig. 11. Traditional neutral point clamped topologies

p
S1 S3 REFERENCES
La [1] O. Lopez, F. D. Freijedo, A. G. Yepes, P. Fernandez-Comesana, J.
a Malvar, R. Teodorescu, and J. Doval-Gandoy, Eliminating ground
current in a transformerless photovoltaic application, IEEE Trans.
S6
Energy Convers.,vol. 25, no. 1, pp. 140147, Mar. 2010.
E
[2] T. Kerekes, R. Teodorescu, and M. Liserre. Common mode voltage in
PV b case of transformerless PV inverters connected to the grid, IEEE
International Symposium on Industrial Electronics, 2008, pp. 2390-
S5 Lb 2395.
S2 S4 [3] T. Kerekes, M. Liserre, R. Teodorescu, C. Klumpner and M. Sumner,
Evaluation of Three-Phase Transformerless Photovoltaic Inverter
n Topologies, IEEE Trans. on Power Electron., vol. 24, no. 9, pp. 2202-
2211, Sept. 2009.
(c) [4] M. Victor, G. Kaufungen, and B. Alheim, et al., Method of converting
a direct current voltage of a source of direct current voltage, more
p specifically of a photovoltaic source of direct current voltage, into an
S1 S3 alternating current voltage, U.S Patent 7411 802 B2, 2008.
La
[5] T. Kerekes, R. Teodorescu, P. Rodriguez, G. Vazquez, E. Aldabas, A
a new high-efficiency single-phase transformerless PV inverter topology,
S6 IEEE Trans. Ind. Electron., vol. 58, no. 1, pp. 184-191, Jan. 2011.
E [6] S. Heribert, S. Christoph, and K. Jurgen, Inverter for transforming a
PV DC voltage into an AC current of an AC voltage, Europe Patent 1 369
b
985 (A2), December 2003.
S5
[7] W. S. Yu, J.-S. Lai, H. Qian, C. Hutchens, J. H. Zhang, G. Lisi, A.
Lb Djabbari, G. Smith, and T. Hegarty, High-efficiency inverter with H6-
S2 S4 type configuration for photovoltaic non-isolated AC module
applications, in Proc. IEEE Appl. Power Electron. Conf. Expo., 2010,
n pp. 10561061.
[8] Xiao, H.F., Xie, S.J., Yang, C., Huang, R.H.: An optimized
(d) transformerless photovoltaic grid-connected inverter, IEEE Trans. Ind.
Fig. 10. Four operation modes of the proposed inverter in Fig. Electron., 2011, 58, (5), pp. 18871895
9(b). [9] S. J. Hu, W. F. Cui, X. N. He, A High-Efficiency Single-Phase Inverter
for Transformerless Photovoltaic Grid-Connection, in Proc. IEEE
ECCE 2014, pp.4232-4236.

447
[10] H. Xiao, K. Lan, and L. Zhang, A Quasi-Unipolar SPWM Full-Bridge single-phase photovoltaic systems[J]. Power Electronics, IEEE
Transformerless PV Grid-Connected Inverter with Constant Common- Transactions on, 2007, 22(2): 693-697.
Mode Voltage, IEEE Trans. Power Electron., vol. 30, no. 6, pp. 3122- [12] Zhang L, Sun K, Feng L, et al. A family of neutral point clamped full-
3132, Jun. 2015. bridge topologies for transformerless photovoltaic grid-tied inverters[J].
[11] Gonzlez R, Lpez J, Sanchis P, et al. Transformerless inverter for Power Electronics, IEEE Transactions on, 2013, 28(2): 730-739.

5 5 5
$

$
0 0 0
-5 -5 -5
0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04

200 200 200


9

9
100 100 100
0 0 0
0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04

200 200 200


9

9
100 100 100
0 0 0
0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04
150 120 120
9

9
100 100 100

50 80 80
0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04
0.01 0.01 0.01
$

$
0 0 0

-0.01 -0.01 -0.01


0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06

(a) (b) (c)


Fig. 12. Comparison of (a) the traditional H6 inverter (b) the proposed inverter in Fig. 6 and (c) the proposed inverter in Fig. 9.

1 1
0.5
0.5
0
0
1
1 0.5
0
0.5

1
0
0.5
1 0

0.5 1

0 0.5
0
1
1
0.5
0.5
0 0
0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06

Fig. 13. The switching sequences of the proposed inverter in Fig. 6(b) Fig. 14. The switching sequences of the proposed inverter in Fig. 9(b).

(a) (b)
Fig. 15. (a) The gating signals of proposed inverter in Fig. 6; (b) the detailed switching sequences.

448
(a)

LO
LFP

8DQ
8FP

8EQ

(b)

(c)
Fig. 16. Experimental waveforms of (a) the traditional H6 inverter, (b) the
proposed inverter in Fig. 6(b) and (c) the proposed inverter in Fig. 9(b).

449

Anda mungkin juga menyukai