JUNE 2017
PAGE
TITLE PAGE i
APPROVAL PAGE
BIOGRAPHICAL SKETCH
ACKNOWLEDGEMENT
TABLE OF CONTENTS ii
LIST OF TABLES vi
LIST OF FIGURES vii
LIST OF APPENDICES viii
LIST OF APPENDIX TABLES ix
LIST OF APPENDIX FIGURES x
EXECUTIVE SUMMARY xi
1. INTRODUCTION 1
1.1 Background of the Field Practice 1
1.2 Significance of the Field Practice 2
1.3 Objectives of the Field Practice 3
1.4 Scope and Limitations of the Field Practice 3
1.5 Time and Place of the Field Practice 4
2. THEORETICAL BACKGROUND 5
2.1 Arc-Flash 5
2.2 Arc-Flash Hazard Analysis 7
PAGE
2
Definition of the System Modes of Operation 30
PAGE
7. REFERENCES 61
APPENDICES 64
APPENDIX TABLES 65
APPENDIX FIGURES 88
3
4
LIST OF TABLES
TABLE PAGE
5
LIST OF FIGURES
FIGURE PAGE
FIGURE PAGE
6
LIST OF APPENDIX TABLES
APPENDIX
TABLE PAGE
APPENDIX
TABLE PAGE
7
LIST OF APPENDIX FIGURES
APPENDIX
FIGURE PAGE
8
EXECUTIVE SUMMARY
In this study, arc flash hazard analysis was performed on a 10-MVA substation
with a relay protection designed by Sunertech Corporation. This was done to determine
the maximum incident energy of the system buses and identify the required personal
protective equipment (PPE). The method used was based on IEEE Standard 1584-2002:
Guide for Performing Arc Flash Hazard Calculations. To determine the available bolted
fault current on the buses and protective devices, short-circuit analysis was performed
using ETAP 12.6.0 considering 10 modes of operation which were based on the number
of feeders in operation. The obtained bolted fault currents were used as input for the
IEEE 1584-2002 spreadsheet calculator to compute for the maximum incident energy and
flash protection boundary of the system buses. The calculations on the spreadsheet
calculator resulted to a maximum incident energy of 7.7 cal/cm 2 for the 69 kV bus and
2.0 cal/cm2 for the 13.8 kV bus, both during Study Case A: Normal Operation, with
the computed incident energies, the Hazard/Risk Category of the buses were identified as
Category 1 for the 69 kV bus and Category 0 for the 13.8 kV bus. The required PPE for
each bus depending on the level of hazard/risk was determined based on the Hazard/Risk
category defined by NFPA 70E Standard for Electrical Safety in the Workplace.