Diagnostics
s
April, 2015
Concrete Testing
High Voltage/
High Current Lab
General Offices and Labs
(Forensics)
current
time/sec
Presence of moisture or
thermal aging : Increase
of the frequency
dependent capacitance
and dielectric loss of
cellulose paper
VAX 30/40
Amplifier
13
life cycle management solutions Kinectrics - Proprietary and Confidential
Copyright 2013 Kinectrics Inc. All rights reserved. Page 13
DS Case Study 1 115kV Aged SCOF
Cables (40+ years)
Assessment
(based on
minimum tan
criteria):
Estimated
average moisture
content below 1%
Capacitance of B
(white) phase of
A, C due to cable
cut
Good Condition
Capacitance
Cable Minimum PF (F) Condition
Stirton HL4 HV-A Phase 0.00333 0.725 Good
Stirton HL4 HV-B Phase 0.00332 0.415 Good
Stirton HL4 HV-C Phase 0.00336 0.723 Good
14
life cycle management solutions Kinectrics - Proprietary and Confidential
Copyright 2013 Kinectrics Inc. All rights reserved. Page 14
DS Case Study 2 115kV Aged SCOF
Cables (40+ years)
Assessment (based
on minimum tan
criteria):
A Phase:
Estimated average
moisture content
between 2.5 3.5%
Considerably
Moist/Aged
B, C Phase:
Estimated average
moisture content
Capacitance between 1 2.5%
Cable Minimum PF (F) Condition
A8G- A phase 0.00513 0.974 Considerably aged Moderately Aged
A8G- B phase 0.00384 0.976 Moderately aged
A8G- C phase 0.0039 0.976 Moderately aged
15
life cycle management solutions Kinectrics - Proprietary and Confidential
Copyright 2013 Kinectrics Inc. All rights reserved. Page 15
DS Case Study 3 161kV SCOF
Cables in Power Plant (35+ years old)
Circuit 4
A-phase
B-Phase
C-Phase
70
60
TanD E-3
50
40
30
20
10
0
0 5 10 15 20 25 30 35
Test Voltage kV
18
life cycle management solutions Kinectrics - Proprietary and Confidential
Copyright 2013 Kinectrics Inc. All rights reserved. Page 18