EarthFaultProtection
FromOpenElectrical
Contents
1 RecommendedSettings
1.1 SolidlyEarthedSystems
1.2 ImpedanceEarthedSystems
1.3 UnearthedSystems
2 References
RecommendedSettings
SolidlyEarthedSystems
FromAlstomNetworkProtectionandAutomationGuide(2011)Section9.16[3]:"Typical[earthfaultrelay]
settingsare3040%ofnominalfullloadcurrentorminimumearthfaultcurrentforthecircuitbeingprotected."
Therefore,apickupsettingof30%40%ofInissuggested,whereInis:
Fortransformerfeeders:In=fullloadcurrentoftransformer
Forcablefeeders:In=cableratedcurrent
Formotorfeeders:In=fullloadcurrentofmotor
Fielding[5]suggestshighersensitivitytoearthfaults,withpickupsettingsof20%ofIn.Ultimately,thedecision
dependsonthetradeoffbetweenhighsensitivitytoearthfaultsandtheprobabilityofspuriousandnuisance
tripping.
ImpedanceEarthedSystems
Inanimpedanceearthedsystem,earthfaultsarelimitedtoamaximumvaluebysomeimpedance.Anearthfault
pickupsettingof10%20%ofthemaximumearthfaultcurrentisrecommended,tobeselectedinconjunction
withthefollowingminimumpickupsettingssuggestedin[4]toavoidspurioustripping:
ForCTsinresidualconnection:>12%ofthenominalCTprimarycurrent
ForcorebalanceCTs:>1Afor0.1s
UnearthedSystems
Inanunearthedsystem,corebalanceCTsarenecessarytohavethesensitivitytodetectearthfaultcurrents
(becauseearthfaultcurrentsarepurelycapacitive).TheminmumthresholdforcorebalanceCTsshouldbe>1A
for>0.1sassuggestedby[4]toavoidspurioustripping.
References
http://wiki.openelectrical.org/index.php?title=Earth_Fault_Protection 1/2
5/1/2017 EarthFaultProtectionOpenElectrical
[1]IEEEStd242,IEEERecommendedPracticeforProtectionandCoordinationIndustrialand
CommercialPowerSystems(Buffbook),2001
[2]IEEEStd142,IEEERecommendedPracticeforGroundingofIndustrialandCommercialPower
systems(Greenbook),2007
[3]AlstomGrid,NetworkProtectionandAutomationGuide,May2011
[4]Preve,C.,ProtectionofElectricalNetworks,2006,ISTELtd,London
[5]Fielding,G.,ProtectionofMVIndustrialNetworks,1997,IEEColloquium,London