Anda di halaman 1dari 6

ATP-EMTP Investigation for Fault Location in

Medium Voltage Networks


M. M. Saha, Senior member, IEEE, E. Rosolowski Senior member, IEEE, J. Izykowski Senior member, IEEE

Abstract-- This paper presents a new fault location (FL) difficult. Three fundamental factors contribute to this:
method for medium voltage (MV) networks operating with the
neutral solidly grounded or grounded across a small resistance.
if a current of a faulty line is not directly available to the
The FL algorithm is based on the impedance measurement FL, certain error is introduced when assuming the
principle and uses the recorded three-phase voltage and current transformer current during a fault to be a current of the
signals as well as the network impedance for the particular faulty line; moreover, it is not possible to compensate
symmetrical components pre-calculated after each change in
accurately for the pre-fault load current of the faulty line;
the network configuration and stored in the database. The phase
voltages are measured at the supplying bus-bar, while the three- MV lines may be multi-terminal and/or contain loops
phase currents are considered as delivered from the faulted what creates well known problems for oneend fault
feeder. The currents can also be taken from the supplying location as, in general, there is no indication on a single
transformer, if only one centralized-type digital fault recorder is
installed at the substation.
fault position (few alternatives appear as possible);
in the case of a MV line, there are often loads located
Keywords: medium voltage network, steady-state and fault between the fault point and the busbar; since the loads
analysis, fault location, ATP-EMTP, simulation. change and are unknown to the FL it is difficult to
compensate for them;
I. INTRODUCTION
MV lines are mainly cable feeders what creates additional

F AULT location in distribution medium voltage (MV)


networks has been a subject of interest to utility engineers
and researchers [1-3]. Information on accurate fault location
problems with adequate representation of the equivalent
scheme, when comparing with overhead lines.
The paper describes the algorithm for calculation of the
available just after the fault helps utility personnel to expedite distance to fault (Sections II, III) as well as the EMTP
service restoration and to make adequate reconfiguration of simulations and analysis of the algorithm - Section IV.
the network for reducing outage time and operating costs.
Therefore, more efficient methods for fault location, supply II. THE PROPOSED ALGORITHM
restoration and high quality customer service, which reduce The presented method overcomes the above mentioned
the overall costs, are highly required [4-5]. difficulties by utilizing the following two-step procedure for
Fault location in distribution networks (DN) creates new fault location in distribution networks (Fig.1).
problems comparing with the same task in HV and EHV f
First, the equivalent positive- ( Z 1k ) and zero-sequence
transmission lines. In HV and EHV networks each f
transmission line may be equipped with the dedicated Fault ( Z 0k ) impedance of the network is computed in pre-fault
Locator (FL). In such a case, the FL algorithm is a numerical steady-state for all k = 1,.., M nodes of the network based
procedure that converts voltage and current, given in a digital on existing topology, loads and feeder parameters. These
form, into a single number being a distance to fault. In values represent positive- and zero-sequence impedance
contrary to the transmission lines, the distribution networks as seen from the substation up to a given k node of the
are usually non-homogeneous, with branches and loads along
steady-state post-fault
the line which make the fault location difficult [1, 3]. analysis analysis
In DN networks, FLs are usually assumed to be of a feeder parameters
centralized type, i.e., they measure the quantities common for & currents voltages
topology
the whole substation (busbar voltages and transformer
currents) what makes the accurate fault location more
Estimation of the Estimation of the
fault-loop
feeder impedance impedance
M. M. Saha is with ABB Automation Technologies Vsters, Sweden,
measured
(e-mail: murari.saha@se.abb.com). impedance
E. Rosolowski is with Wroclaw University of Technology Wroclaw, Poland, Which feeder short-
(e-mail: rose@pwr.wroc.pl). Estimation of circuited?
J. Izykowski is with Wroclaw University of Technology Wroclaw, Poland, network the distance Information from
(e-mail: jan.izykowski@pwr.wroc.pl). impedance relays and/or CBs

distance
Presented at the International Conference on Power Systems
Transients (IPST05) in Montreal, Canada on June 19-23, 2005 Fig. 1. Basic block diagram of the proposed fault location algorithm.
Paper No. IPST05 - 220
network. V pp = V A V B ,
Then after the fault the specific fault-loop parameters are
I kpp - phase-to-phase fault loop current, for example:
calculated depending on the fault type (phase-to-phase or
phase-to-ground) and the place of measurements (at the I kpp = I kA I kB .
supplying transformer or at the faulty feeder).
Phase-to-ground fault loop (a phase-to-ground fault):
The fault place is determined as a result of checking the V ph
following set of conditions for consecutive nodes of the Zk = (5)
I kph + k kN I kN
network:
Im(Z ek ) 0 , k = 1,2,..M (1) where:
where: V ph , I kph - voltage and current from a faulty phase,
Z f Z 1 f for ph - to - ph fault Z '0 Z 1'
Z ek = 1fk f (2) k kN = (6)
Z 1k + k I Z 0k Z 1N for ph - to - grnd fault 3Z '
1
I pN 3V ph Z '0 ,Z 1' - zero and positive sequence impedance per length of
kI = , Z 1N = (3)
3I p I pN 3I p I pN the faulted feeder,
I kN = I kA + I kB + I kC (7)
and: V ph - voltage at the faulty phase, Z 1 f - positive-
sequence fault-loop impedance obtained from measurements, B. Measurements at the substation level
I p , I pN - adequately: fault-loop and residual currents In this case we assume that the faulty line is identified.
obtained from measurements. Moreover, some of the described below pre-fault parameters
The final distance to fault will be chosen when the of the network are also known or can be estimated from the
condition as in (1) is fulfilled. The method of calculation of SCADA information.
the parameters ( Z 1 f , I p , I pN ) depends on the place of Let a faulty feeder (say feeder k) from the considered radial
network has the pre-fault equivalent impedance Z Lk (Fig. 3).
measurement (at the substation or at the feeder).
The remaining parallel-connected feeders are represented with
A. Measurements at the faulty feeder the equivalent branch of the impedance Z L (i.e.
As far as only one-end supplied radial networks are 1 / Z L = 1 / Z 1 + 1 / Z 2 + ... + 1 / Z m ). Both Z Lk and Z L are
considered, the positive sequence fault-loop impedance is
calculated according to well known equations depending on assumed to be the positive sequence impedance.
the type of fault (Fig.2).
Z1 pre-fault state post-fault state

ZLk ZLk
Z2
I kA
Vpre,Ipre V,I
I k = I kB

Zk I kC
I A
ZL I = I B ZL

I kA I C

I k = I kB I LA
I I L = I LB
kC
V kA I LC
Zm
V k = V kB Fig. 3. Equivalent circuits of the distribution network.
V
kC
The aim of the analysis is to determine the post-fault
Fig. 2. Diagram of the network: measurements are taken in the faulty feeder. positive sequence impedance Z k under assumption that the
equivalent impedance Z L remains unchanged during a fault.
Phase-to-phase fault loop (phase-to-phase, phase-to-
The following equation is valid for the pre-fault state (Fig. 3):
phase-to-ground or three phase fault): V pre Z L Z Lk
V pp Z pre = = (8)
Zk = (4) I pre Z L + Z Lk
I kpp
where: V pre , I pre - are phase-to-phase or phase-to-ground
where:
V pp - phase-to-phase fault loop voltage, for example: (for symmetrical condition) variables.
Two post-fault cases should be considered: network parameters the fault loop impedance can be
Phase-to-phase fault loop (phase-to-phase, phase-to- established in the similar way as for measurements from the
phase-to-ground or three phase fault). feeder [6, 7].
The positive sequence impedance seen from the substation Summarizing the above derivations we can represent
is obtained from the equation: currents I p , I pN in (3) as follows:
V pp ZLZk for measurements in the feeder:
Z= = (9)
I pp Z L + Z k I p = I ph , (14a)
where: I pN = I N = I A + I B + I C (14b)
V pp - phase-to-phase fault loop voltage, for example:
for measurements at the substation:
V pp = V A V B , V ph V 0
I p = I ph (1 k z ) (15a)
I pp - phase-to-phase fault loop current taken at the substation, Z pre

for example: I pp = I A I B , (1 k zk 0 )V 0
I pN = I N (15b)
Combining (8) and (9) yields: jX C 0
Z Z pre where:
Zk = (10) X C0 C
Z pre Z (1 k zk ) k zk 0 = = 0k
X C 0 k CC 0
where:
C 0k - zero-sequence capacitance of the faulty feeder,
Z pre S Lk
k zk = = (11) CC 0 - zero-sequence capacitance of all MV network,
Z Lk S
k zk as in (11),
S Lk - power in the faulty line in the pre-fault conditions,
V pre
S - power in all the lines in the pre-fault conditions. Z pre = - pre-fault positive-sequence impedance at the
I pre
Combining (8) and (11) one also obtains
ZL supplying transformer,
k zk = (12) index ph stands for the faulty phase.
Z L + Z Lk
Moreover, the positive sequence fault loop impedance Z 1 f
The coefficient k zk for each line is estimated on the basis
seen from the substation can be obtained from division of
of the pre-fault steady-state conditions. In a substation with a
adequate voltage drop by difference of currents:
large number of feeders these coefficients are close to zero
V pp
and change only a little, e.g. for two identical lines: k zk = 0.5 Z1f = (16)
I pp
(if only line reactance is taking into account) while for twenty
lines: k zk = 0.05 . One should observe that, in general, k zk is where: V pp - phase-phase voltage, I pp - phase-phase current,
a complex number. e.g. for A-B fault: V pp = V A V B , I pp = I A I B .
From equation (10) one can calculate the fault loop f f
Having the network impedance Z 1k and Z 0k for steady-
impedance using the measurements from the substation.
Dividing numerator and denominator of (10) by Z pre and state condition, and fault loop parameters: Z 1 f , k I , Z 1N

substituting (9) for Z , equation (10) can be rewritten in a given from measurements according to (2, 3) with respect to
(4-6) it is possible o utilize the criterion (1) for distance to
more convenient form:
V fault calculation.
pp
Zk = (13)
V pp
I pp (1 k zk ) III. DISTANCE TO FAULT ESTIMATION
Z pre
Distance to fault can be determined on the basis of criterion
Phase-to-ground fault loop (phase-to-ground fault). (1). In the searching algorithm two impedances: first one
In the case of a phase-to-ground fault, the positive calculated for steady state while the second - obtained from
sequence fault loop impedance is calculated according to the measurements should be compared against matching the
second equation in (2). One can observe that as only a single criterion. Two different algorithms are used depending of the
phase-to-ground fault is considered (say, in feeder k) the zero fault loop type: phase-to-phase or phase-to-ground fault loops.
sequence current measured in the substation contains the
faulty feeder current I kN and the zero-sequence current flows A. Phase-to-phase fault
In this case the measured impedance in (2) is represented
through capacitances of the healthy feeders I CL . Knowing
by the positive-sequence impedance Z 1 f which is compared
voltage and current measurements at the substation and
where l k is a length of the section.
f
with the impedance Z 1k for successive k = 1,.., M network
nodes. Let us consider the phase-to-phase fault at node k of The algorithm for the distance x calculation is derived as
f
the network as in Fig. 4. It is assumed that the impedance Z 1k follows:
(positive-sequence network impedance as seen from the 1. The fault-loop impedance Z 1 f measured at the
substation under assumption that the fault with no resistance substation meets the following relation (Fig. 5a):
occurs at the node k) is known from steady-state calculations
Z 1 f = (1 m) Z 1fk1 +
(
m Z 1fk1 + Z f Z 1fk2 ) (19)
and Z 1 f is obtained from measurements according to (6).
m Z 1fk1 + Z f + Z 1fk2
For further analysis the fault loop seen from the substation
is represented with the equivalent scheme as in Fig. 6. The 2. After rearranging (19) the value for residuum impedance
following condition is fulfilled for this scheme: can be obtained as:

Z 1fk = (1 m ) Z 1fk1 +
m Z 1fk1 Z 1fk2 (Z f1
1k )(
Z 1 f m Z 1fk1 + Z 1fk2 m Z 1fk1 ) ( ) 2

m Z 1fk1 + Z 1fk2
(17) Z f =
(
m Z 1fk1 Z 1fk2 Z 1fk1 Z 1 f ) (20)

The separate impedance in (7) can be easily determined from 3. The impedance Z f represents the scheme seen from
f
the known impedance Z 1k by choosing the parameter m the node k up to the fault place (Fig. 5b) what can be
( 0 < m 1 ). determined as:
f
Representation of the impedance Z 1k in a form as in Fig. 5
Z 1k x Z L +
(
R f (1 x ) Z L + Z 1u( k +1) )
gives possibility to include the fault resistance into considered R f + (1 x ) Z L + Z 1u( k +1)
(21)
fault loop what is depicted in Fig. 5a. The residual impedance
Z f represents the equivalent impedance involved in the fault
Z f =
Z 1k + x Z L +
(
R f (1 x ) Z L + Z 1u( k +1) )
R f + (1 x ) Z L + Z 1u( k +1)
loop due to the fault resistance R f , if the fault occurs at node
4. Right-hand sides of (20) and (21) should be equal what
k or behind them. The equivalent scheme for representing the
leads to determination of the unknown fault resistance:
impedance Z f is shown in Fig. 5b. Here:
R f = x 2 A xB + C (22)
Z 1k - equivalent shunt impedance at node k,
Z L - impedance of the cable section between nodes k, k+1, A=
(
Z L2 Z1k Z f ) (
Z L M + 2Z f Z 1k )
where: , B= ,
M M
Z 1u( k +1) - equivalent impedance of the network seen from
C=
u
(
Z f Z 1k Z L + Z1(k +1) )
the node k+1 up to the end of the feeder. ,
M
)( )
u
The impedance Z 1( k +1) should be also calculated for
M = Z 1k ( u
Z f Z L + Z1(k +1) Z f Z 1k .
steady-state conditions for all network nodes and stored in the
5. Distance to fault x can be obtained from (22) under
database.
condition that the fault resistance takes real value:
The distance to fault d f , m is determined as a sum of a
distance d [m] from substation up to node k (Fig. 5b) and a (1 m ) Z 1k
f1
m Z 1k
f1 a)
k
distance xl k , m inside a given section:
d f = d + xl k (18)

Z1 f Z 1k
f2
Z f
3 4 5

1 Ipp 2 6 ZL5

Vpp ZL2 k xZ L (1 x) Z L k+1 b)


n-1 n
k

Z f Z 1k Rf Z 1u( k +1)
k+1 k+2
d x 1-x
ZL(k+1)

Fig.4. Scheme of the network for phase-to-phase fault at node k. Fig. 5. Equivalent scheme of the fault loop: a - from the substation up to
the fault point, b - beyond the fault point.
Im( R f ) = x 2 Ai xBi + Ci = 0 (23) 2 Z 1L + Z 0 L 2 Z 1k + Z 0k u 2 Z ue1 + Z ue0
Z eL = , Z ek = , Ze =
where: Ai = Im(A) , Bi = Im(B ) , Ci = Im(C ) 3 3 3
After rearranging one obtains: Index e relates to the equivalent impedance of the scheme
B + p Bi p in Fig. 6b.
x1 = i , x2 = (24) The distance to fault is also calculated according to (18).
2 Ai 2 Ai
2
where: p = Bi 4 Ai Ci . IV. SIMULATION RESULTS
First root of (24) takes unrealistic value so, finally, a The considered 10 kV substation is supplied from 150 kV
distance to fault is determined as x = x 2 . system. The cable network is operated in a radial way.
Measurements of current are available at the supplying
B. Phase-to-ground fault transformer or at the feeders. Cable shield is considered as
For phase-to-ground faults the criterion for distance to fault grounded only at the load points.
estimation, defined by (1) with respect to the second equation For a distance to fault calculation the each feeder should be
in (2) is equivalent to the following condition (for simplicity represented by the detail scheme with adequate line and load
the equality is considered): models. In the cable networks grounding system has different
Z 1fk = Z 1N k I Z 0f k (25) structure than feeders have (open cables may have connected
grounding circuits), what should be also represented in the
where: k I and Z 1N are defined by (3).
model. This requires representing all feeders connected in a
The parameters k I and Z 1N in (25) can be calculated from given substation in the general simulation model. However,
f f
measurements whereas Z lk and Z 0k are actual positive- and for proper post-fault transient analysis some simplifications
zero-sequence impedance of the assumed fault loop and are can be introduced: - supplying system is described by steady-
available from steady-state conditions. state parameters; - analyzed feeder is represented in detail; -
Equivalent scheme of the fault loop circuit, which satisfies all other feeders are represented by equivalent schemes with
the condition (25) is similar to the phase-to-phase one reproducing only the grounding system connections.
(Fig. 6). Instead of Z 1 f now the impedance combination Example of the analyzed network is presented in Fig. 7.
Cable sections are represented by appropriate -schemes,
Z 1N k I Z 0f k is used. Bearing this in mind, the algorithm for a while loads and equivalent circuits are reflected by R L or
distance x [p.u.] to the fault at section k, k+1 can be derived by R L C scheme. EMTP/ATP model [8] of the analyzed
repeating points 1-5 from the previous section. Final relation network has been extensively used for investigation of the
is represented by (22), where: proposed fault location algorithm. The MV network consists

A=
2
Z eL (
Z ek Z f ) (
Z eL M + 2Z f Z ek ) of 16 feeders which, except of the particular analyzed feeder,
, B= , are represented by their equivalent schemes. Let us consider
M M

C=
(u
Z f Z ek Z L + Z e(k +1) ) 1 uB a)
,
M
( )( ) 0.5
voltage, V*104

u
M = Z ek Z f Z eL + Z e(k +1) Z f Z ek ,

-0.5
equivalent a equivalent b
4 uA uC
-1 0 0.02 0.04 0.06 0.08 0.1
1 2 3 5 6 7 8 1.5 b)
iA
1.0
9 16 iB
current, kA

10 0.5
11 12 13 14 15 17 18 19 20
0
-0.5
equivalent c equivalent d iC
-1.0
equivalent e
-1.5 0 0.02 0.04 0.06 0.08 0.1
Fig. 7. Equivalent scheme of the analyzed network; dotted lines are for time, s
grounding system connection. Fig. 8. Phase voltages (a) and currents (b) during A-G fault at node 17
an example of A-G (phase A to ground) fault at node 17 in the The developed algorithm utilizes the current measurements
analyzed feeder (actual distance to fault - 8138 m., Fig. 7) delivered from the faulty feeder or from the substation. In the
with assuming the fault resistance R f = 0.1 . Phase voltages latter case the estimation error depends on accuracy of pre-
and currents observed at the substation during A-G and 3- fault condition determination in the MV substation. The
phase faults are presented in Figs. 8 and 9, respectively. distance to fault estimation error depends on the accuracy of
measurements as well as cable parameters. Successful tests on
0.8 a) fault data from EMTP/ATP detailed model suggest that the
method can be viable.
0.6

0.4 VI. REFERENCES


[1] M.S. Sachdev, R. Das and T.S. Sidhu, "Determining locations of fault in
0.2
voltage, V*104

distribution systems", Sixth International Conference on Developments


in Power System Protection, IEE Conf. Publ.434, 1997, pp. 188-191.
0 [2] R. Das, D. Novosel, "Review of fault location techniques for
transmission and subtransmission lines". Georgia Tech, April 2000.
-0.2 [3] A.A. Girgis, M. Fallon, D.L. Lubkeman, "A fault location technique for
rural distribution feeders". IEEE Trans. Industry Application, vol. 29,
-0.4 no. 6, Nowember/December1993, pp. 1170-1175.
[4] M.S. Sachdev, T.S. Sidhu, R. Das, "A fault location technique for radial
-0.6 subtransmission lines with tapped loads". CIGRE Colloquium, SC34,
Florence, October 11-15, 1999, paper 203.
-0.8 [5] R.K. Aggarwal, Y. Aslan and A.T. Johns, "An interactive approach to
4.0 b) fault location on overhead distribution lines with load taps", Sixth
International Conference on Developments in Power System Protection,
3.0 IEE Conf. Publ. 434, 1997, pp. 184-187.
[6] M.M. Saha and F. Provoost, "Fault Location in Medium Voltage
2.0 Networks", CIRED, Nice, France, 1-4 June 1999.
[7] M. M. Saha, E. Rosolowski and J. Izykowski, A new fault location
1.0 algorithm for distribution networks, in Proc. 2004 IEE Eighth
current, kA

International Conference on Developments in Power System Protection,


0 Amsterdam, pp. 168171.
[8] H. Dommel, ElectroMagnetic Transient Program, BPA, Portland,
-1.0 Oregon, 1986.

-2.0
VII. BIOGRAPHIES
-3.0
Murari Mohan Saha (M76, SM87) was born in 1947
-4.0 in Bangladesh. He received B.Sc.E.E. from Bangladesh
0 0.02 0.04 0.06 0.08 0.1
time, s University of Engineering and Technology, Dhaka in
1968 and completed M.Sc.E.E. in 1970. In 1972 he
Fig. 9. Phase voltages (a) and currents (b) during 3-phase fault at node 17 completed M.S.E.E. and in 1975 he was awarded with
Ph.D. from the Technical University of Warsaw, Poland.
Results of distance to fault estimation for 3-phase and Currently he is a Senior Research and Development
phase-to-ground fault are gathered in Table 1. It can be seen Engineer at ABB Automation Technologies, Vsters,
Sweden. His areas of interest are power system
that the algorithm gives quite good results.
simulation, and digital protective relays
TABLE I
RESULTS OF DISTANCE TO FAULT ESTIMATION Eugeniusz Rosolowski (M97, SM00) was born in
Type of fault Fault resistance, Obtained result, m Error, m Poland in 1947. He received M.Sc. degree in Electrical
Eng. from the Wroclaw University of Technology
3-phase 0.1 8145 +7
(WUT) in 1972 and Ph.D. from Kiev Politechnical
2.0 8135 -3 Institute in 1978. In 1993 he received D.Sc. from the
A-G 0.1 8131 -7 WUT. Presently he is a Professor in the Institute of
2.0 8081 -57 Electrical Engineering and Director of this Institute. His
research interests are in power system analysis and
microprocessor applications in power systems.

V. CONCLUSIONS Jan Izykowski (M1997, SM04) was born in Poland in


1949. He received his M.Sc., Ph.D. and D.Sc. degrees
The presented fault location algorithm for distribution
from the Faculty of Electrical Engineering of Wroclaw
networks is based on voltage and current phasor estimation. University of Technology (WUT) in 1973, 1976 and in
The algorithm was investigated and proved on the basis of 2001, respectively. Presently he is an Associate
voltage and current data obtained from versatile EMTP/ATP Professor in Institute of Electrical Engineering of the
WUT. His research interests are in power system
simulations. simulation, protection and control, and fault location.

Anda mungkin juga menyukai