This manual describes the details of Diagnostic Information messages displayed in the
Diagnostic Information Window of SCS Maintenance Support Tool or System Alarm View of HIS.
The table of the contents of this manual can be used as message number index.
This manual consists of the following chapters:
Chapter 1 :
This chapter explains how to refer to the Diagnosis Information in SENG.
Chapter 2 :
This chapter explains the details about SCS Messages.
Chapter 3 :
This chapter explains the details about common messages of CENTUM VP or CS 3000 and
SENG.

Media No. IM 32S02B10-21E (CD) 3rd Edition : Dec. 2009 (YK) IM 32S02B10-21E 3rd Edition : Dec.22,2009-00
All Rights Reserved Copyright 2008, Yokogawa Electric Corporation
ii

ProSafe-RS Document Map


Safety System

Engineering
Safety Manual
Guide
IM 32S01S10-21E IM 32S01C10-21E

Software

Safety Control Station Integration with Open Interfaces


Reference CENTUM VP/CS 3000
IM 32S03B10-21E IM 32S01E10-21E IM 32S05B10-21E

Engineering Utilities and Messages


Reference Maintenance
Reference
IM 32S04B10-21E IM 32S04B20-21E IM 32S02B10-21E

ProSafe-RS
Integration with
System Test
FAST/TOOLS Workbench Users Guide
Reference
IM 32S04B30-21E IM 32S56H20-21E

Hardware Vnet/IP

Safety Control
Communication ProSafe-RS
Stations
Devices Vnet/IP
(Hardware)
IM 32S06C10-21E IM 32S06H10-21E IM 32S56H10-21E

Installation

Installation Manual

Software Help
IM 32S01C50-21E
Read Me First

IM 32S02B10-21E 2nd Edition : Dec.15,2008-00


iii

Safety Precautions
n Safety, Protection, and Modification of the Product
In order to protect system controlled by this product, the product itself and ensure safe
operation, observe the safety precautions described in this users manual. We assume no
liability for safety if users fail to observe these instructions when operating the product.
You must use this product according to the instructions described in user manuals. If not,
protective functions of this product may not work as expected.
If any protection or safety circuit is required for system controlled by the product or for the
product itself, prepare it separately.
Be sure to use the parts approved by Yokogawa Electric Corporation (hereafter simply
referred to as YOKOGAWA) when replacing parts or consumables.
Modification of the product is strictly prohibited.
The following symbols are used on the product and in this user manual to indicate that
safety precautions are required:

Indicates that user must take caution. The symbol on the equipment refers the user to the
relevant manual to avoid potentially hazardous situations that may result in injury or death.
The symbol appears next to the cautionary information in user manuals required to avoid
harm to personnel and to the equipment.

Identifies a protective grounding terminal. Before using the product, ground the terminal.

Identifies a functional grounding terminal. Before using the product, ground the terminal.

Indicates an AC supply.

Indicates a DC supply.

Indicates that main switch is ON.

Indicates that main switch is OFF.

IM 32S02B10-21E 1st Edition : May 30,2008-00


iv

n Notes on Handling User Manuals


Please hand over user manuals to your end users so that they can have them on hand for
convenient reference.
Please read the user manuals thoroughly before using the product.
The purpose of these user manuals is not to warrant that the product is well suited to any
particular purpose but rather to describe the functional details of the product.
YOKOGAWA reserves the right to make improvements in the user manuals and product at
any time, without notice or obligation.
If you have any questions, or you find mistakes or omissions in the user manuals, please
contact our sales representative or your local distributor.

n Warning and Disclaimer


The product is provided on an as is basis. YOKOGAWA shall have neither liability nor
responsibility to any person or entity with respect to any direct or indirect loss or damage arising
from using the product or any defect of the product that YOKOGAWA can not predict in advance.

n Notes on Software
YOKOGAWA makes no warranties, either expressed or implied, with respect to the
softwares merchantability or suitability for any particular purpose, except as specified in the
terms of warranty.
This software may be used on one machine only. If you need to use the software on another
machine, you must purchase another copy of the software.
It is strictly prohibited to reproduce the product except for the purpose of backup.
Store the CD-ROM (the original medium) in a safe place.
It is strictly prohibited to perform any reverse-engineering operation, such as reverse
compilation or reverse assembling on the product.
No part of the product may be transferred, converted or sublet for use by any third party,
without prior written consent from YOKOGAWA.

IM 32S02B10-21E 1st Edition : May 30,2008-00




Documentation Conventions
n Typographical Conventions
The following typographical conventions are used throughout the user manuals:

l Commonly used Conventions throughout User manuals:

Character strings in the following font and style:


Indicate that user must enter them in the relevant field or text box in the context.
Example:
FIC100.SV=50.0

Mark
Indicates a space between character strings that must be entered.
Example: Calling the tuning view with the tag name of S0001 on HIS (Human Interface Station of
the integrated CENTUM)
S0001TUN

Character string enclosed by brackets ({ }):


Indicates an option that can be omitted.
Example: Parameters for calling the tuning view on HIS.
Tag name TUN {-window size} {=Display position}

l Conventions used to show key or button operations:

Characters enclosed by brackets ([ ]):


Characters enclosed by brackets within any description on a key or button operation, indicate
either a key on the keyboard, a button name on a window, or an item displayed on a window.
Example:
Click [OK] button.

l Conventions of User Defined Folder


User-Dfined Folder Name
If the path of a folder can be defined by users, it is written within parentheses.
Example: (RS Project Folder) \SCS0101
If the RS project folder is C: \MYRSPJT, the above path becomes: C: \MYRSPJT\SCS0101

IM 32S02B10-21E 2nd Edition : Dec.15,2008-00


vi

n Symbol Marks
Throughout this user manual, you will find that several types of symbols are used to identify
different sections of text. This section describes these icons.

CAUTION
Indicates instructions that must be observed in order to prevent physical injury and death of
operator.

WARNING
Identifies instructions that must be observed in order to prevent software or hardware from
being damaged or system from becoming faulty.

IMPORTANT
Identifies important information required to understand operations or functions.

TIP
Identifies additional information.

SEE
ALSO

Identifies a source to be referred to.


Clicking a reference displayed in green can call up its source, while clicking a reference
displayed in black cannot.

n Drawing Conventions
Some drawings in the user manual may be partially emphasized, simplified, or omitted, for the
convenience of description.
Note that screen images in user manuals may be slightly different from the actual ones (for
example, display positions and case differences), and some show only example images.

n Integration with CENTUM


ProSafe-RS can be used by integrating with CENTUM VP or CENTUM CS 3000. In the Users
Manuals of ProSafe-RS, the integration with CENTUM VP or CENTUM CS 3000 is referred to as
Integration with CENTUM.
For the same features of CENTUM VP and CENTUM CS 3000 that have different feature names,
the name used in CENTUM VP will be referred to in the explanations. (For example, CENTUM
CS 3000 System Alarm Window and CENTUM VP System Alarm View have the same functions,
but only System Alarm View will be referred to when explaining this feature.) Nevertheless,
if there is any difference in functionality according to whether ProSafe-RS is integrated with
CENTUM VP or CENTUM CS 3000, the feature will be explained separately for both cases.

SEE
ALSO For information about the functions and usage of CENTUM VP components, see CENTUM VP Users
Manuals (IM) and related Technical Information (TI) and General Specifications (GS).
For information about the functions and usage of CENTUM CS 3000 components, see CENTUM CS 3000
Users Manuals (IM) and related Technical Information (TI) and General Specifications (GS).

IM 32S02B10-21E 2nd Edition : Dec.15,2008-00


vii

n About Explanation of System Behavior


In this manual, system behavior is explained assuming the use of the latest software and
hardware that Yokogawa provides at the publication of the manual. Wherever a topic needs
explanation of earlier revisions of software or hardware, a link to the required explanation is
provided so that you can read them according to your system.

n About Station Types


Safety control stations (SCS) are named as follows according to the CPU node (SSCx0S/
SSCx0D) and CPU module (SCP4x1) mounted in them.
SCSV1-S : SCS that uses SSC10S/SSC10D (SCP401 is installed)
SCSP1-S : SCS that uses SSC50S/SSC50D (SCP451 is installed)
SCSP2-S : SCS that uses SSC60S/SSC60D (SCP461 is installed)
To explain the functions of these different types of SCS, the following generic terms or
abbreviations may be used in this manual.
SCS : Generic term that denotes all types of SCS
SCSV : SCS connected on V net (this denotes SCSV1-S)
SCSP : SCS connected on Vnet/IP (this denotes SCSP1-S and SCSP2-S)
SCSV1 : Abbreviation for SCSV1-S
SCSP1 : Abbreviation for SCSP1-S
SCSP2 : Abbreviation for SCSP2-S

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


viii

Copyright and Trademark Notices


n All Rights Reserved
The copyright of the programs and online manuals contained in the DVD-ROM or CD-ROM shall
remain in Yokogawa.
You are allowed to print out the required pages of the online manuals for using the product,
however, you are not allowed to print out the entire document.
Except as stated above, no part of the online manual may be reproduced, either in electronic
or written form, registered, recorded, transferred, sold or distributed (in any manner including
without limitation, in the forms of paper documents, electronic media, films or transmission via the
network).

n Trademark Acknowledgments
CENTUM, ProSafe, Vnet/IP and STARDOM are registered trademarks of YOKOGAWA.
Microsoft, Windows, Windows Vista, Visual Basic, Visual C++ and Visual Studio are either
registered trademarks or trademarks of Microsoft Corporation in the United States and/or
other countries.
Adobe, Acrobat and Acrobat Reader are either registered trademarks or trademarks of
Adobe Systems Incorporated in the United States and/or other countries.
Ethernet is a registered trademark of XEROX Corporation.
Modicon and Modbus are registered trademarks of Schneider Electric SA.
PLC is a registered trademark of Rockwell Automation, Inc.
HART is a registered trademark of the HART Communication Foundation.
All other company and product names mentioned in this users manual are trademarks or
registered trademarks of their respective companies.
We do not use TM or mark to indicate those trademarks or registered trademarks used in
this users manual.

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


Toc-1

ProSafe-RS
Messages
IM 32S02B10-21E 3rd Edition

CONTENTS
1. Referencing Diagnostic Information Messages on the SENG............. 1-1
1.1 How to Call Diagnostic Information Window.................................................. 1-1
1.2 Diagnostic Information Window....................................................................... 1-2
1.3 Printout of Diagnostic Information Message.................................................. 1-3
2. Details of Output Messages Specific to the SCS................................... 2-1
2.1 System Alarms (Message Numbers 4101 through 4199).............................. 2-2
No. 4101 Inter-SCS safety communication error information............................ 2-2
No. 4102 Inter-SCS safety communication error recovery information............. 2-3
No. 4103 Variable lock........................................................................................ 2-4
No. 4104 Cancellation of variable lock............................................................... 2-4
No. 4105 I/O module lock................................................................................... 2-5
No. 4106 Cancellation of I/O module lock.......................................................... 2-5
No. 4107 All input module locks......................................................................... 2-5
No. 4108 Cancellation of all input module locks................................................. 2-5
No. 4109 All output module locks....................................................................... 2-6
No. 4110 Cancellation of all output module locks.............................................. 2-6
No. 4111 All module locks.................................................................................. 2-6
No. 4112 Cancellation of all module locks......................................................... 2-6
No. 4113 Number of locks exceeded................................................................. 2-7
No. 4114 Recovery from exceeded number of locks......................................... 2-7
No. 4115 Override setting................................................................................... 2-7
No. 4116 Cancellation of override...................................................................... 2-8
No. 4117 Information of change to override enabled state................................ 2-8
No. 4118 Information of change to override disabled state................................ 2-8
No. 4119 Number of overrides exceeded.......................................................... 2-9
No. 4120 Recovery from exceeded number of overrides.................................. 2-9
No. 4121 Number of enabled overrides exceeded............................................ 2-9
No. 4122 Recovery from exceeded number of enabled overrides.................. 2-10
No. 4123 Number of active PASSWD FBs exceeded...................................... 2-10
No. 4124 Recovery from exceeded number of active PASSWD FBs.............. 2-10
No. 4125 I/O module channel error occurred................................................... 2-11
No. 4126 Recovery from I/O module channel error......................................... 2-11

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


Toc-2

No. 4127 Setting PASSWD FB to ON.............................................................. 2-11


No. 4128 Setting PASSWD FB to OFF............................................................ 2-12
No. 4129 GPS interface unit error.................................................................... 2-12
No. 4130 Recovery of GPS interface unit........................................................ 2-12
No. 4131 Communication module lock............................................................ 2-13
No. 4132 Cancellation of Communication module lock................................... 2-13
No. 4133 Information of a diagnosis error in the received data of SCS Link
Transmission..................................................................................... 2-13
No. 4134 Information of a diagnosis error recovery in the received data of
SCS Link Transmission..................................................................... 2-15
No. 4135 SCS Link Transmission data lock..................................................... 2-15
No. 4136 Cancellation of SCS Link Transmission data lock............................ 2-15
No. 4137 Number of Locked Stations in SCS Link Transmission Exceeded... 2-16
No. 4138 Recovery from exceeded number of locked stations in SCS Link
Transmission..................................................................................... 2-16
No. 4139 Inter-SCS Safety Communication data lock..................................... 2-16
No. 4140 Cancellation of Inter-SCS Safety Communication data lock............ 2-17
No. 4141 Number of locked stations in Inter-SCS Safety Communication
exceeded.......................................................................................... 2-17
No. 4142 Recovery from exceeded number of locked stations in Inter-SCS
Safety Communication..................................................................... 2-17
No. 4143 Start of automatic scan period extension......................................... 2-18
No. 4144 Cancellation of automatic scan period extension............................. 2-18
No. 4145 Abnormal calculation occurred......................................................... 2-18
No. 4146 Recovery from abnormal calculation................................................ 2-19
No. 4152 On-line change of scan period.......................................................... 2-19
No. 4153 Information of Inter-SCS Safety Communication data lock
time-up.............................................................................................. 2-19
No. 4154 Information of forced cancellation of Inter-SCS Safety
Communication data locks............................................................... 2-20
No. 4155 Information of SCS Link Transmission status change...................... 2-20
No. 4156 Information of SCS Link Transmission definition change................. 2-20
No. 4157 Information of SCS Link Transmission wiring change...................... 2-20
No. 4158 Information of SCS Link Transmission lock time-up......................... 2-21
No. 4159 Information of forced cancellation of SCS Link Transmission
locks.................................................................................................. 2-21
No. 4160 Invalid password for Manual Operation FB...................................... 2-21
No. 4161 Information of Output IOM Shutdown............................................... 2-22
No. 4162 Information of communication I/O definition change........................ 2-22
No. 4163 Information of communication I/O wiring change............................. 2-22
No. 4164 Information of disabling security level change.................................. 2-22
No. 4165 Information of enabling security level change.................................. 2-23

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


Toc-3

No. 4166 Information of communication module lock time-up......................... 2-23


No. 4167 Information of forced cancellation of communication module
locks.................................................................................................. 2-23
No. 4168 Information of tag name change by on-line change download......... 2-23
No. 4169 NVRAM diagnosis error.................................................................... 2-24
No. 4170 Flash memory diagnosis error.......................................................... 2-24
No. 4172 Information of resource change by on-line change download......... 2-24
No. 4173 Completion of writing to flash memory............................................. 2-25
No. 4174 Failed to write to flash memory......................................................... 2-25
No. 4175 Failed to update external communication data................................. 2-26
No. 4177 Information of SCS security level change......................................... 2-26
No. 4178 Information of security level time-up................................................. 2-26
No. 4179 Information of communication I/O module output enabled
operation........................................................................................... 2-27
No. 4180 Information of password change...................................................... 2-27
No. 4181 Information of output enabled operation........................................... 2-27
No. 4182 Information of output module start operation.................................... 2-27
No. 4183 Request to upload SOE to SENG..................................................... 2-28
No. 4184 Notification on saving SOE trip signal file in SCS............................. 2-28
No. 4185 Information of variable value change................................................ 2-29
No. 4186 Information of lock time-up................................................................ 2-29
No. 4187 Information of forced cancellation of locks........................................ 2-29
No. 4188 Start of on-line change download..................................................... 2-30
No. 4189 Completion of on-line change download.......................................... 2-30
No. 4190 On-line change download error........................................................ 2-30
No. 4191 Completion of I/O definition rewriting................................................ 2-30
No. 4192 Information of override state time-up................................................ 2-31
No. 4193 Information of forced release of all overrides.................................... 2-31
No. 4194 Information of override enabled state time-up.................................. 2-31
No. 4195 Information of communication I/O data status change..................... 2-31
No. 4196 Invalid password for PASSWD FB.................................................... 2-32
No. 4197 Information on active PASSWD FB time-up..................................... 2-32
No. 4198 Information on forced reset of PASSWD FB..................................... 2-32
No. 4199 Override communication error.......................................................... 2-33

3. Details of Output Messages in Common with CENTUM....................... 3-1


3.1 Safety Control Station Error Occurrence and Recovery Messages
(Message Numbers 0001 through 0094).......................................................... 3-1
No. 0001 Reset start of safety control station..................................................... 3-1
No. 0003 Safety control station automatic reset start......................................... 3-1
No. 0005 Power ON initial cold start of safety control station............................ 3-1

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


Toc-4

No. 0009 Transfer of control right of safety control station................................. 3-2


No. 0011 Fail information of safety control station ............................................ 3-3
No. 0013 AC power supply failure of safety control station . ............................. 3-4
No. 0015 Self-diagnosis error of clock inside CPU module............................... 3-4
No. 0017 ROM checksum error of CPU module................................................ 3-5
No. 0021 Internal task error of safety control station.......................................... 3-5
No. 0023 Mapping block fatal error.................................................................... 3-5
No. 0025 Function control word error................................................................. 3-6
No. 0027 Mapping block record information error.............................................. 3-6
No. 0033 Online downloading abnormal end..................................................... 3-6
No. 0041 Safety control station fan alarm.......................................................... 3-7
No. 0042 Recovery from safety control station fan alarm.................................. 3-7
No. 0043 Safety control station temperature alarm............................................ 3-7
No. 0044 Recovery from safety control station temperature alarm................... 3-8
No. 0045 Power supply module alarm of safety control station......................... 3-8
No. 0046 Recovery from power supply module alarm of
safety control station........................................................................... 3-8
No. 0047 Battery alarm of CPU module............................................................. 3-8
No. 0048 Recovery from battery alarm of CPU module..................................... 3-9
No. 0055 Information of same frame reception in on-line change download
communication.................................................................................... 3-9
No. 0057 Information of on-line change download error.................................... 3-9
No. 0059 Information of recovery from node power failure................................ 3-9
No. 0063 ESB bus error.................................................................................... 3-10
No. 0064 Normal recovery of ESB bus............................................................ 3-10
No. 0065 Failure of ESB Bus Interface module (SSB401) of node.................. 3-11
No. 0066 Normal recovery of ESB Bus Interface module (SSB401) of
node.................................................................................................. 3-11
No. 0067 Failure of power supply module of node........................................... 3-11
No. 0068 Normal recovery of power supply module of a node........................ 3-12
No. 0069 Error before database download to I/O module............................... 3-12
No. 0081 Failure of I/O module........................................................................ 3-13
No. 0082 Normal recovery of I/O module......................................................... 3-15
No. 0083 I/O module database error occurred................................................. 3-15
No. 0085 I/O module communication error occurred....................................... 3-15
No. 0086 Recovery from I/O module communication error............................. 3-15
No. 0087 Node error occurred.......................................................................... 3-16
No. 0088 Normal recovery of node.................................................................. 3-16
No. 0089 Subsystem communication error...................................................... 3-17
No. 0090 Subsystem communication recovered............................................. 3-18

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


Toc-5
No. 0093 CPU nodes housekeeping unit error................................................ 3-18
No. 0094 Normal recovery of CPU nodes housekeeping unit......................... 3-18
3.2 Safety Control Station Status Change Related Messages
(Message Numbers 0450 through 0480)........................................................ 3-19
No. 0450 Copy program and database on control side of
safety control station to standby side................................................ 3-19
No. 0451 Information of switching of control side of safety control station...... 3-19
No. 0452 Information of switching of standby side of safety control station..... 3-19
No. 0459 Information on I/O module service side............................................ 3-19
No. 0460 Information of I/O module out service............................................... 3-20
No. 0471 Normal completion of on-line change download.............................. 3-20
No. 0474 Information of tag list duplicate error................................................. 3-20
No. 0475 Start of database download to I/O module....................................... 3-20
No. 0476 Normal completion of database download to I/O module ............... 3-20
No. 0477 Database download error to I/O module........................................... 3-21
No. 0480 Heavy load on periodical processing................................................ 3-21
3.3 Safety Control Station Related Messages
(Message Numbers 0727 through 0787)........................................................ 3-22
No. 0727 Block mode recovery error information............................................. 3-22
No. 0743 Self-diagnostic SEN-BUS Failure..................................................... 3-22
No. 0744 Self-diagnostic SEN-BUS Recovery................................................. 3-22
No. 0749 Self-diagnosis detected an I/O Error................................................. 3-23
No. 0750 I/O Recovery from the error detected by self-diagnosis................... 3-23
No. 0751 Time self-diagnostic testing error...................................................... 3-23
No. 0753 Communication Overload................................................................. 3-23
No. 0767 Faulty one ESB bus in CPU module................................................. 3-24
No. 0768 Single ESB bus in CPU module Recovery....................................... 3-24
No. 0787 Self-diagnosis detected I/O error in CPU module............................ 3-24

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<1.1 How to Call Diagnostic Information Window> 1-1

1. Referencing Diagnostic Information


Messages on the SENG
The diagnostic information messages can be displayed on the Diagnostic Information
window called from SCS Status Overview window.

1.1 How to Call Diagnostic Information Window


You can call the Diagnostic Information window from the SCS Status Overview window.

n Calling Diagnostic Information Window


The SCS Status Overview window is shown in the figure below.
Diagnostic information
button Domain number V net status

SCS Status Overview


File View Window Tool

MYRSPJT Domain:01 V net 1 V net 2

Station SCS Status CPU Status Comment


SCS0101 Ready Ready
RS project
SCS0102 R-Fail
name

Diagnostic
information mark Station name SCS status CPU status Station Comment
010201E.ai

Figure SCS Status Overview Window and Diagnostic Information Button

To open the Diagnostic Information window, select the station and then click the Diagnostic
Information button on the toolbar of SCS Status Overview window.
When the Diagnostic Information window is opened, the diagnostic information and messages of
the selected station can be displayed.

IM 32S02B10-21E 1st Edition : May 30,2008-00


<1.2 Diagnostic Information Window> 1-2

1.2 Diagnostic Information Window


The Diagnostic Information window is shown in the figure below.
Help button Toolbar Diagnostic Information
Message

Diagnostic Information-[SCS0101 1.3]


File View Operation Help

Number Date Class Message

4125 5/30/2008 10:26:19.720 AM 1 SCS0101 IOM Channel Error NO.


4125 5/30/2008 10:26:19.720 AM 1 SCS0101 IOM Channel Error NO.
0082 5/30/2008 10:26:17.620 AM 3 SCS0101 IOM Recover F10 NODE
0476 5/30/2008 10:26:09.131 AM 4 SCS0101 IOM Download Complete.
0475 5/30/2008 10:26:04.235 AM 4 SCS0101 IOM Download Start F10.
0082 5/30/2008 10:25:55.320 AM 3 SCS0101 IOM Recover F10 NODE
0459 5/30/2008 10:25:55.320 AM 4 SCS0101 IOM In Service F10 NO.
Information 0476 5/30/2008 10:25:51.931 AM 4 SCS0101 IOM Download Complete.
0475 5/30/2008 10:25:48.388 AM 4 SCS0101 IOM Download Start F10.
Warning 0047 5/30/2008 10:25:36.851 AM 2 SCS0101 LEFT Battery Alarm
4129 5/30/2008 10:25:33.328 AM 2 SCS0101 GPS Interface Unit Error
Alarm marks
0081 5/30/2008 10:25:33.320 AM 1 SCS0101 IOM Fail FIO NODE 0.

Number Date Class Message

30/95

Status bar Number of currently


generated messages
010101E.ai

Figure Diagnostic Information Window

SEE
ALSO For more information about the diagnostic information window, see the following:
3.2, Displaying SCS Diagnostic Information in Utilities and Maintenance Reference (IM 32S04B20-21E)

n Calling Help Dialog Box


You can view the details of every message in the Help dialog box. To do this, click on a message
in the window, then click the [Help] button from the toolbar. The Help dialog box appears.

SEE
ALSO For more information about the Help dialog box, see the following:
3.2.3, Diagnostic Information Message Help Function in Utilities and Maintenance Reference
(IM32S04B20-21E)

IM 32S02B10-21E 1st Edition : May 30,2008-00


<1.3 Printout of Diagnostic Information Message> 1-3

1.3 Printout of Diagnostic Information Message


The printout of diagnostic information messages is shown in the figure below.

5/30/2008 2:02:44 PM page 1/1

Search condition SCS0101 1.3

Format Alarm mark, Message number, Date, Class, Message

Selection mark New Alarm:No mark, Acknowledged:A, Deleted:D

4129 5/30/2008 9:00:15.987 AM 2 SCS0101 GPS Interface Unit Error


0081 5/30/2008 9:00:15.980 AM 1 SCS0101 IOM Fail FIO NODE 01 SLOT 05 Code = 5103
0083 5/30/2008 9:00:15.980 AM 2 SCS0101 IOM Configuration Error FIO NODE 01 SLOT 05
0081 5/30/2008 9:00:15.980 AM 1 SCS0101 IOM Fail FIO NODE 01 SLOT 03 Code = 5103
0083 5/30/2008 9:00:15.980 AM 2 SCS0101 IOM Configuration Error FIO NODE 01 SLOT 03
0081 5/30/2008 9:00:15.980 AM 1 SCS0101 IOM Fail FIO NODE 01 SLOT 01 Code = 5103
0083 5/30/2008 9:00:15.980 AM 2 SCS0101 IOM Configuration Error FIO NODE 01 SLOT 01
0451 5/30/2008 9:00:00.465 AM 2 SCS0101 LEFT Control
0005 5/30/2008 9:00:00.465 AM 2 SCS0101 Power ON (Cold Start)
0013 5/30/2008 9:00:00.465 AM 2 SCS0101 AC Fail (Time 1/1/1970 9:00:00 AM)

010301E.ai

Figure Printout of Diagnostic Information Message

IM 32S02B10-21E 1st Edition : May 30,2008-00


<2. Details of Output Messages Specific to the SCS> 2-1

2. Details of Output Messages Specific


to the SCS
This chapter describes the details of output messages specific to the SCS. The
descriptions are made up of the items shown below for each message. The Meanings,
Cause, Action, Remark, Note and Error code can be omitted, depending on the message.

Message name Name of the message.


Example: Information of security level time-up

Printing example Indicates an example of print or display.


Example: SCS0101 Security Level = 1 Elapsed the Specified Period = 08:00:00
In this document, space in messages and the leading 00 of various numbers
may be different from actual printing examples to the extent they do not impair the
understanding of messages.

Meaning Meaning of a message.


Example: The security level is set to 1 for the duration exceeding the time limit (8
hours in the above example) specified in SYS_SECURE Function Block (hereinafter
referred to as FB).

Cause Describes the cause of occurrence. The description may be omitted depending on
the message.
Example: The security level has not been reverted.

Action Describes the action to take. The description may be omitted depending on the
message.
Example: Revert the security level to 2.

Remark Describes an item(s) related to the message. The description may be omitted
depending on the message.

Note Describes cautions. The description may be omitted depending on the message.

Error code Describes details of the error code included in the message, if any. The description
may be omitted depending on the message.

IM 32S02B10-21E 1st Edition : May 30,2008-00


<2.1 System Alarms> 2-2

2.1 System Alarms (Message Numbers 4101


through 4199)
This section describes system alarm messages issued from the SCS.

No. 4101
Message name Inter-SCS safety communication error information

Printing example SCS0101 Inter-SCS Safety Communication Receive Error Variable = C0102001
Code = 5041-8000

Meaning An error is detected during inter-SCS safety communication. The erroneous binding
variable (C0102001 in the above example) is included in the message.

Cause The following causes may be considered. Check the error codes for more detail.
Stop/restart on the producing side SCS
Problem in the communication path
Change in the application of inter-SCS safety communication

Remark Inter-SCS safety communication

Error code The first four digits are an error code, and the next four digits are a cause code. The
error detail can be found from the descriptions of the both codes. The error codes
and cause codes are listed below.

The error code represents the type of error. The following table explains each error code and the
action you can take to fix the error.
Table Message No. 4101 - Error Code List
Code (hexadecimal) Description Action
An error that occurs
5040 when an application is Check the application logic.
created incorrectly.
No data received within
5041 the reception interval
timeout value. Check the producing side SCS and the communication
path.
Time diagnosis found
5042
an error.
Communication
Record the message content and report to Yokogawas
5043 protocol error (internal
service department.
error)

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-3
The cause code represents the event that caused the problem and is logical OR of the following
codes.
Table Message No. 4101 - Cause Code List
Code
Errors Description Presumed cause
(hexadecimal)
Communication stopped and Communication was cut off, or
8000 No response
data no longer arrived. the producing side stopped.
The restart on the producing side
4000 Reset detection Restart on the producing side
was detected.
The communication content and
1000 CRC mismatch Temporary communication error
CRC do not match.
The variable name is not An application was created
0200 Variable name error
Cddssxxx. incorrectly.
The domain and station numbers
An application was created
0100 Address error are different from the binding
incorrectly.
variable.
Communication was updated
0040 Transmission delay occurred later than the transmission delay Communication delay
timeout time.
An error occurred in time
Date/time error on the producing management on the producing Date/time management error on
0020
side side, so the date/time is not the producing side
reliable.
An error occurred in time
Date/time error on the management on the consuming Date/time management error on
0010
consuming side side, so the date/time is not the consuming side
reliable.
The FB ID information is different
0004 Different FB ID information Internal error
from the initial value.
0001 Data type error The data type does not match. Internal error

No. 4102
Message name Inter-SCS safety communication error recovery information

Printing example SCS0101 Inter-SCS Safety Communication Receive Recover Variable =


C0102001

Meaning An inter-SCS safety communication error for the variable (C0102001 in the above
example) recovered. (This is a recovery message of No. 4101.)

Cause The following causes may be considered.


Recovery of the producing side SCS
Recovery of the communication path
Recovery of the application of inter-SCS safety communication

Remark Inter-SCS safety communication

IM 32S02B10-21E 1st Edition : May 30,2008-00


<2.1 System Alarms> 2-4
No. 4103
Message name Variable lock

Printing example In the case of I/O variables:


SCS0101 Variable Locked Variable=VAR001 NODE 01 SLOT 02 CH 03

In the case of internal variables:


SCS0101 Variable Locked Variable=VAR001

Meaning The variable (VAR001 in the above example) was locked by operation from the
SENG. In the case of I/O variables, the channel position (node 1, slot 2 and
channel 3 in the above example) corresponding to the variable is also included in
the message.

Remark Forcing function

Note Be sure to cancel the lock of the variable that was locked.
If an IO_BOOL type or IO_REAL type variable is locked, the member variable v
or status will be indicated in the format of [Variable=VAR001.v] at the position of
the variable name in the system alarms. If the variable is not wired to the channel,
the member variable v will be always displayed. Nevertheless, in any of the above
cases, the whole IO_BOOL type or IO_REAL type variable will be locked.
When locking an array element, the whole array will be locked. Under this
circumstance, the variable name displayed in the system alarm will be attached
with the array element subscript as [Variable=VAR001[1]].

No. 4104
Message name Cancellation of variable lock

Printing example In the case of I/O variables:


SCS0101 Variable Unlocked Variable=VAR001 NODE 01 SLOT 02 CH 03

In the case of internal variables:


SCS0101 Variable Unlocked Variable=VAR001

Meaning The lock of the variable (VAR001 in the above example) was cancelled by operation
from the SENG. In the case of I/O variables, the channel position (node 1, slot 2
and channel 3 in the above example) corresponding to the variable is also included
in the message.

Remark Forcing function

Note If an IO_BOOL type or IO_REAL type variable is unlocked, the member variable
v or status will be indicated in the format of [Variable=VAR001.v] at the position of
the variable name in the system alarms. If the variable is not wired to the channel,
the member variable v will be always displayed. Nevertheless, in any of the above
cases, the whole IO_BOOL type or IO_REAL type variable will be unlocked.
Moreover, when unlocking an array element, the whole array will be unlocked.
Under this circumstance, the variable name displayed in the system alarm will be
attached with the array element subscript as [Variable=VAR001[1]].

IM 32S02B10-21E 1st Edition : May 30,2008-00


<2.1 System Alarms> 2-5
No. 4105
Message name I/O module lock

Printing example SCS0101 IOM Locked NODE 01 SLOT 02

Meaning An I/O module was locked by operation from the SENG. The I/O module position
(node 1 and slot 2 in the above example) is included in the message.

Remark Forcing function

Note Be sure to cancel the lock of the I/O module that was locked.

No. 4106
Message name Cancellation of I/O module lock

Printing example SCS0101 IOM Unlocked NODE 01 SLOT 02

Meaning The lock of an I/O module was cancelled by operation from the SENG. The I/
O module position (node 1 and slot 2 in the above example) is included in the
message.

Remark Forcing function

No. 4107
Message name All input module locks

Printing example SCS0101 All Input IOM Locked

Meaning All input modules were locked by operation from the SENG.

Remark Forcing function

Note Be sure to cancel the locks of the input modules that were locked.

No. 4108
Message name Cancellation of all input module locks

Printing example SCS0101 All Input IOM Unlocked

Meaning The locks of all input modules were cancelled by operation from the SENG.

Remark Forcing function

IM 32S02B10-21E 1st Edition : May 30,2008-00


<2.1 System Alarms> 2-6
No. 4109
Message name All output module locks

Printing example SCS0101 All Output IOM Locked

Meaning All output modules were locked by operation from the SENG.

Remark Forcing function

Note Be sure to cancel the locks of the output modules that were locked.

No. 4110
Message name Cancellation of all output module locks

Printing example SCS0101 All Output IOM Unlocked

Meaning The locks of all output modules were cancelled by operation from the SENG.

Remark Forcing function

No. 4111
Message name All module locks

Printing example SCS0101 All IOM Locked

Meaning All I/O modules were locked by operation from the SENG.

Remark Forcing function

Note Be sure to cancel the locks of the I/O modules that were locked.

No. 4112
Message name Cancellation of all module locks

Printing example SCS0101 All IOM Unlocked

Meaning The locks of all I/O modules were cancelled by operation from the SENG.

Remark Forcing function

IM 32S02B10-21E 1st Edition : May 30,2008-00


<2.1 System Alarms> 2-7
No. 4113
Message name Number of locks exceeded

Printing example SCS0101 Number of Locks Exceeds the Limit = 3

Meaning The total number of locked variables exceeded the limit count (3 in the above
example) specified in SYS_FORCE FB.

Cause This is an operation from the SENG. The number of locks is too many.

Action Cancel the variable locks.

Remark SYS_FORCE FB

Note Lock variables within the limit count.

No. 4114
Message name Recovery from exceeded number of locks

Printing example SCS0101 Number of Locks Within the Limit = 3

Meaning The total number of locked variables is reduced to within the limit count (3 in the
above example) specified in SYS_FORCE FB. (This is a recovery message of No.
4113.)

Cause This is an operation from the SENG.

Remark SYS_FORCE FB

No. 4115
Message name Override setting

Printing example SCS0101 TAG001 Overridden (Instance = OVR0001)

Meaning Override operation was performed for the override FB (OVR0001 in the above
example) that corresponds to the tag name (TAG001 in the above example) from
the HIS.

Remark OVR_B, OVR_I, OVR_R, OVR_IB, OVR_IR, GOV_B, GOV_IB FB

IM 32S02B10-21E 1st Edition : May 30,2008-00


<2.1 System Alarms> 2-8
No. 4116
Message name Cancellation of override

Printing example SCS0101 TAG001 Override Released (Instance = OVR0001)

Meaning An override was cancelled for the override FB (OVR0001 in the above example)
that corresponds to the tag name (TAG001 in the above example) from the HIS.

Remark OVR_B, OVR_I, OVR_R, OVR_IB, OVR_IR, GOV_B, GOV_IB FB

No. 4117
Message name Information of change to override enabled state

Printing example SCS0101 Override Enabled

Meaning An override was enabled.

Cause The SW input parameter of the override FB was set to TRUE.

Remark OVR_B, OVR_I, OVR_R, OVR_IB, OVR_IR, GOV_B, GOV_IB FB

Note If the SW input parameter of at least one override FB is set to TRUE, this message
is notified.

No. 4118
Message name Information of change to override disabled state

Printing example SCS0101 Override Disabled

Meaning An override was disabled.

Cause The SW input parameter of all override FBs were set to FALSE.

Remark OVR_B, OVR_I, OVR_R, OVR_IB, OVR_IR, GOV_B, GOV_IB FB

Note If the SW input parameters of all override FBs are set to FALSE, this message is
notified.

IM 32S02B10-21E 1st Edition : May 30,2008-00


<2.1 System Alarms> 2-9
No. 4119
Message name Number of overrides exceeded

Printing example SCS0101 Number of Overrides Exceeds the Limit = 3

Meaning The total number of overridden override FBs exceeded the limit count (3 in the
above example) specified in SYS_OVR FB.

Cause This is an operation from the HIS. There are too many overrides.

Action Cancel overrides.

Remark SYS_OVR FB

Note Override within the limit count.

No. 4120
Message name Recovery from exceeded number of overrides

Printing example SCS0101 Number of Overrides Within the Limit = 3

Meaning The total number of overridden override FBs is within the limit count (3 in the above
example) specified in SYS_OVR FB. (This is a recovery message of No. 4119.)

Cause This is an operation from the HIS.

Remark SYS_OVR FB

No. 4121
Message name Number of enabled overrides exceeded

Printing example SCS0101 Number of Enabled OVR FBs Exceeds the Limit = 3

Meaning The total number of override FBs in the override enabled state exceeded the limit
count (3 in the above example) specified in SYS_OVR FB.

Action Disable override FBs.

Remark SYS_OVR FB

Note Enable overrides within the limit count.

IM 32S02B10-21E 1st Edition : May 30,2008-00


<2.1 System Alarms> 2-10
No. 4122
Message name Recovery from exceeded number of enabled overrides

Printing example SCS0101 Number of Enabled OVR FBs Within the Limit = 3

Meaning The total number of override FBs in the override enabled state is within the limit
count (3 in the above example) specified in SYS_OVR FB. (This is a recovery
message of No. 4121.)

Remark SYS_OVR FB

No. 4123
Message name Number of active PASSWD FBs exceeded

Printing example SCS0101 Number of Activated PASSWD FBs Exceeds the Limit = 3

Meaning The total number of active PASSWD FBs exceeded the limit count (3 in the above
example) specified in SYS_PSWD FB.

Cause This is an operation from the HIS. There are too many active PASSWD FBs.

Action Inactivate (reset to OFF) the PASSWD FBs that have exceeded the limit count.

Remark SYS_PSWD FB

Note Make PASSWD FBs active within the limit count.

No. 4124
Message name Recovery from exceeded number of active PASSWD FBs

Printing example SCS0101 Number of Activated PASSWD FBs Within the Limit = 3

Meaning The total number of active PASSWD FBs is within the limit count (3 in the above
example) specified in SYS_PSWD FB. (This is a recovery message of No. 4123.)

Cause Active PASSWD FBs were inactivated (reset to OFF) by operation from the HIS.

Remark SYS_PSWD FB

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-11
No. 4125
Message name I/O module channel error occurred

Printing example SCS0101 IOM Channel Error NODE 01 SLOT 02 CH 03 XXXXXXXX (YYYY)

Meaning An error occurred in an I/O module channel (node 1, slot 2 and channel 3 in the
above example). XXXXXXXX indicates an error cause, and YYYY indicates an
error code.

Cause See the table below.

Action Check to see if the connected devices and connecting cables are normal.
Table Message No. 4125 - Error Causes
Error cause Code Description Remark
TRNS + 5121 Upper limit error of the transmitter occurred.
TRNS - 5122 Lower limit error of the transmitter occurred.
IOP + 5123 Upper limit error of the IOP occurred.
IOP - 5124 Lower limit error of the IOP occurred.
Input value is outside of the range of input
5125
Ovr Range values (-25 % to 125 %). This indicates a
5126
failure of the I/O module.
Disconnection of DI/DO is included in
Ch Fail 5127 A channel error was detected.
this error cause.

No. 4126
Message name Recovery from I/O module channel error

Printing example SCS0101 IOM Channel Recover NODE 01 SLOT 02 CH 03

Meaning An error occurred in an I/O module channel (node 1, slot 2 and channel 3 in the
above example) recovered. (This is a recovery message of No. 4125.)

No. 4127
Message name Setting PASSWD FB to ON

Printing example SCS0101 TAG001 PASSWD FB Set to ON (Instance = PASSWD001)

Meaning PASSWD FB (PASSWD001 in the above example) that corresponds to the tag
name (TAG001 in the above example) was set to ON (active) by operation from
the HIS.

IM 32S02B10-21E 1st Edition : May 30,2008-00


<2.1 System Alarms> 2-12
No. 4128
Message name Setting PASSWD FB to OFF

Printing example SCS0101 TAG001 PASSWD FB Set to OFF (Instance = PASSWD001)

Meaning PASSWD FB (PASSWD001 in the above example) that corresponds to the tag
name (TAG001 in the above example) was inactivated (reset to OFF) by operation
from the HIS.

No. 4129
Message name GPS interface unit error

Printing example SCS0101 GPS Interface Unit Error (RIGHT CPU)

Meaning A CPU module (right side in the above example) detected a GPS unit error or time
synchronization error.

Cause The following causes may be considered.


Problem in the cable connecting the GPS unit and the GPS interface unit.
Failure of the GPS interface unit

Action Check to see if a cable connecting the GPS unit and the GPS interface unit is
disconnected or cut. Also, check to see if a terminator is connected to the ends of
the cable. If everything is in place, replace the GPS interface unit.

Note If this message is displayed while the time synchronization method is V net time
synchronization, the CPU module may be faulty.

No. 4130
Message name Recovery of GPS interface unit

Printing example SCS0101 GPS Interface Unit Recover (RIGHT CPU)

Meaning Time synchronization of the GPS unit detected by CPU module (right side in the
above example) is recovered. (This is a recovery message of No. 4129.)

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-13
No. 4131
Message name Communication module lock

Printing example 1 SCS0101 Communication Module All Inputs/Outputs Locked NODE 01 SLOT 02

Printing example 2 SCS0101 Communication Module All Inputs Locked NODE 01 SLOT 02

Printing example 3 SCS0101 Communication Module All Outputs Locked NODE 01 SLOT 02

Meaning The communication module was locked by operation from the SENG. The message
varies depending on the locked range (inputs and outputs, inputs only or outputs
only). The location of the communication module is also included in the messages
(such as node 1, slot 2).

Remark Forcing function, subsystem communication

Note Be sure to cancel the lock of the communication module that was locked.

No. 4132
Message name Cancellation of Communication module lock

Printing example 1 SCS0101 Communication Module All Inputs/Outputs Unlocked NODE 01 SLOT 02

Printing example 2 SCS0101 Communication Module All Inputs Unlocked NODE 01 SLOT 02

Printing example 3 SCS0101 Communication Module All Outputs Unlocked NODE 01 SLOT 02

Meaning The lock of the communication module was cancelled by operation from the SENG.
The message varies depending on the locked range (inputs and outputs, inputs
only or outputs only). The location of the communication module is also included in
the messages (such as node 1, slot 2).

Remark Forcing function, subsystem communication

No. 4133
Message name Information of a diagnosis error in the received data of SCS Link Transmission.

Printing example SCS0101 SCS Link Transmission Receive Error Stn(SCS)=05 Code = 5041-
8000

Meaning A diagnosis error has been found in the received data of SCS Link Transmission.
The source station number (such as 05) and the station type (SCS in the above
example) that sent the Link Transmission are indicated in the message text. The
station type indicated in the message is the station type defined on the SCS Link
Transmission builder.

Cause The following causes may be considered. Check the error codes for more detail.
Stop or restart the sender station
Problem in the communication path
The definition of the SCS Link Transmission builder may contain errors.

Remark SCS Link Transmission


IM 32S02B10-21E 1st Edition : May 30,2008-00
<2.1 System Alarms> 2-14

Error code The first four digits are an error code, and the next four digits are a cause code. The
error detail can be found from the descriptions of the both codes. The error codes
and cause codes are listed below.

The error code represents the type of error. The following table explains each error
code and the action you can take to fix the error.
Table Message No. 4133 - Error Code List
Code (hexadecimal) Description Action
No data received within
5041 the reception interval
timeout value. Check the sender SCS and its communication path.
Time diagnosis found
5042
an error.
Communication
Record the message content and report to Yokogawas
5043 protocol error (internal
service department.
error)

The cause code represents the event that caused the problem and is logical OR
of the following codes.
Table Message No. 4133 - Cause Code List
Code
Errors Description Presumed Cause
(hexadecimal)
Communication error, or the
Communication stopped and
8000 No response sender station stopped or unable
data no longer arrived.
to send outputs.
Temporary communication error,
The communication content and or SCS Link Transmission builder
1000 CRC mismatch
CRC do not match. definition may contain [Type]
error.
The application may contain
errors, or the setting in the
0100 Address error Illegal station number
database is inconsistent with the
setting of dipswitches.
Communication was updated
0040 Transmission delay occurred later than the transmission delay Communication delay
timeout time.
Time diagnosis error occurred in
Time diagnosis error of the Time diagnosis error of the
0020 the sender, so that this date/time
sender sender
may not be correct.
Time diagnosis error occurred in
Time diagnosis error of the Time diagnosis error of the
0010 the receiver, so that this date/
receiver receiver
time may not be correct.
The detected scan cycle is an
0008 Illegal scan cycle Internal error
illegal value 0.

IM 32S02B10-21E 1st Edition : May 30,2008-00


<2.1 System Alarms> 2-15
No. 4134
Message name Information of a diagnosis error recovery in the received data of SCS Link
Transmission.

Printing example SCS0101 SCS Link Transmission Receive Recover Stn(SCS)=05

Meaning The diagnosed reception error of SCS link transmission has been recovered. The
source station number (such as 05) and the station type (SCS in the above example)
are indicated in the message text. The station type indicated in the message is the
same station type defined on the SCS Link Transmission builder.
(This is a recovery message of No. 4133.)

Cause The following causes may be considered.


Recovery of the sender station
Recovery of the communication path
The errors in the SCS Link Transmission definition have been removed.

Remark SCS Link Transmission

No. 4135
Message name SCS Link Transmission data lock

Printing example SCS0101 SCS Link Transmission Data Locked Stn(SCS)=02

Meaning The reception/transmission data for SCS Link Transmission (in the above example,
data received from station 2) were locked. The (SCS) in the message text indicates
the station type defined on the SCS Link Transmission builder.

Remark Forcing function, SCS Link Transmission

Note Be sure to cancel the lock of the station that was locked.

No. 4136
Message name Cancellation of SCS Link Transmission data lock

Printing example SCS0101 SCS Link Transmission Data Unlocked Stn(SCS)=02

Meaning The lock of reception/transmission data for SCS Link Transmission (in the above
example, data received from station 2) was cancelled. The (SCS) in the message
text indicates the station type defined on the SCS Link Transmission builder.

Remark Forcing function, SCS Link Transmission

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-16
No. 4137
Message name Number of Locked Stations in SCS Link Transmission Exceeded

Printing example SCS0101 Number of Locks about SCS Link Transmission Exceeds the Limit = 3

Meaning The number of locked stations exceeded the limit (3 in the above example), which
is defined in SYS_FORCE_ LT FB as the number of stations allowed for forcing.

Cause Operation from the SENG to lock too many stations.

Action Cancel SCS Link Transmission locks for some SCS.

Remark Forcing function, SCS Link Transmission, SYS_FORCE_LT FB

Note You should not lock stations beyond the limit.

No. 4138
Message name Recovery from exceeded number of locked stations in SCS Link Transmission

Printing example SCS0101 Number of Locks about SCS Link Transmission Within the Limit = 3

Meaning The number of locked stations fell within the limit (3 in the above example), which
is defined in SYS_FORCE_ LT FB as the number of stations allowed for forcing.
(This is the recovery message of No.4137.)

Cause Operation from the SENG.

Remark Forcing function, SCS Link Transmission, SYS_FORCE_LT FB

No. 4139
Message name Inter-SCS Safety Communication data lock

Printing example SCS0101 Inter-SCS Safety Communication Data Locked Dom=01 Stn=02

Meaning The Inter-SCS Safety Communication data received from a producer SCS (in the
above example, station 2 in domain 1) were locked.
The message for a lock of the local station (data produced by the station are locked)
is also output in the same format, showing its own domain number and station
number.

Remark Forcing function, Inter-SCS Safety Communication

Note Be sure to cancel the lock of the station that was locked.

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-17
No. 4140
Message name Cancellation of Inter-SCS Safety Communication data lock

Printing example SCS0101 Inter-SCS Safety Communication Data Unlocked Dom=01 Stn=02

Meaning The lock of Inter-SCS Safety Communication data received from a producer SCS
(in the above example, station 2 in domain 1) was cancelled.
The message of cancellation for the lock of local station (data produced by the
station are locked) is also output in the same format, showing its own domain
number and station number.

Remark Forcing function, Inter-SCS Safety Communication

No. 4141
Message name Number of locked stations in Inter-SCS Safety Communication exceeded

Printing example SCS0101 Number of Locks about Inter-SCS Safety Communication Exceeds the
Limit = 3

Meaning The number of locked stations exceeded the limit (3 in the above example), which
is defined in SYS_FORCE_ BD FB as the number of stations allowed for forcing.

Cause Operation from the SENG to lock too many stations

Action Cancel Inter-SCS Safety Communication locks for some SCS.

Remark Forcing function, Inter-SCS Safety Communication

Note You should not lock stations beyond the limit.

No. 4142
Message name Recovery from exceeded number of locked stations in Inter-SCS Safety
Communication

Printing example SCS0101 Number of Locks about Inter-SCS Safety Communication Within the
Limit = 3

Meaning The number of locked stations fell within the limit (3 in the above example), which
is defined in SYS_FORCE_ BD FB as the number of stations allowed for forcing.
(This is the recovery message of No.4141.)

Cause Operation from the SENG

Remark SYS_FORCE_BD FB

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-18
No. 4143
Message name Start of automatic scan period extension

Printing example SCS0101 Scan Period Extended from the Original Scan Period 100ms to 200ms

Meaning Automatic extension of the scan period of the application logic execution started. (In
the above example, the original scan period of 100 ms was extended to 200 ms.)

Cause The application caused heavy load on the SCS.

Remark SYS_SCANEXT FB, automatic scan period extension

No. 4144
Message name Cancellation of automatic scan period extension

Printing example SCS0101 Scan Period Recovered to the Original Scan Period 100ms

Meaning Automatic extension of the scan period of the application logic execution is
cancelled. (In the above example, the scan period recovered to its original period
of 100 ms.)

Cause The load on the SCS caused by the application was reduced.

Remark SYS_SCANEXT FB, automatic scan period extension

No. 4145
Message name Abnormal calculation occurred

Printing example SCS0101 Calculation Error (Div by Zero) Program=PG01


SCS0101 Calculation Error (FPU Overflow) Program=PG01
SCS0101 Calculation Error (Cast Overflow) Program=PG01
or
SCS0101 Calculation Error (Div by Zero) Program=PG01 FU/FB=UFB01
SCS0101 Calculation Error (Access to the Outside of Array) Program=PG01 FU/
FB=UFB01
SCS0101 Calculation Error (FPU Overflow) Program=PG01 FU/FB=UFB01
SCS0101 Calculation Error (Cast Overflow) Program=PG01 FU/FB=UFB01

Meaning Abnormal calculation occurred in the application logic. The text in parentheses
means the following:
Div by Zero: Division by zero
Access to the Outside of Array: Access to the outside of an array
FPU Overflow: Overflow in the floating-point calculation
Cast Overflow: Overflow in casting
At Program=, the name of the program (POU name) where the abnormal
calculation occurred is indicated. If the abnormal calculation occurred in a user-
defined FU/FB, the POU name of that FU/FB is indicated at FU/FB=.

Cause Error in the application

Remark SYS_CERR FB

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-19
No. 4146
Message name Recovery from abnormal calculation

Printing example SCS0101 Calculation Recover (Div by Zero) Program=PG01


SCS0101 Calculation Recover (FPU Overflow) Program=PG01
SCS0101 Calculation Recover (Cast Overflow) Program=PG01
or
SCS0101 Calculation Recover (Div by Zero) Program=PG01 FU/FB=UFB01
SCS0101 Calculation Recover (Access to the Outside of Array) Program=PG01
FU/FB=UFB01
SCS0101 Calculation Recover (FPU Overflow) Program=PG01 FU/FB=UFB01
SCS0101 Calculation Recover (Cast Overflow) Program=PG01 FU/FB=UFB01

Meaning Indicates a recovery from the abnormal calculation occurred in the application logic.
The text in parentheses means the following:
Div by Zero: Division by zero
Access to the Outside of Array: Access to the outside of an array
FPU Overflow: Overflow in the floating-point calculation
Cast Overflow: Overflow in casting
At Program=, the name of the program (POU name) where the abnormal
calculation occurred is indicated. If the abnormal calculation occurred in a user-
defined FU/FB, the POU name of that FU/FB is indicated at FU/FB=.

Cause The error in the application was corrected.

Remark SYS_CERR FB

No. 4152
Message name On-line change of scan period

Printing example SCS0101 Scan Period Changed to 200ms

Meaning The scan period of the application logic was changed by on-line change
download.

Cause Operation from the SENG

Remark On-line change download

No. 4153
Message names Information of Inter-SCS Safety Communication data lock time-up

Printing example SCS0101 Inter-SCS Safety Communication Data Lock Elapsed the Specified
Period = 08:00:00

Meaning Inter-SCS Safety Communication lock exceeded the time limit (8 hours in the above
example) specified in SYS_FORCE_BD FB.

Action Check whether all Inter-SCS Safety Communication locks have been cancelled
and cancel unnecessary locks.

Remark Forcing function, Inter-SCS Safety Communication, SYS_FORCE_BD FB

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-20
No. 4154
Message name Information of forced cancellation of Inter-SCS Safety Communication data locks

Printing example SCS0101 All Inter-SCS Safety Communication Data Unlocked.

Meaning Locks of all the Inter-SCS Safety Communication data (reception/transmission) in


the station were forcibly cancelled.

Cause Locks of all the Inter-SCS Safety Communication data were cancelled by using the
SYS_FORCE_BD FB.

Remark Forcing function, Inter-SCS Safety Communication, SYS_FORCE_BD FB

No. 4155
Message name Information of SCS Link Transmission status change.

Printing example SCS0101 SCS Link Transmission Data Status Set to TRUE Old=FALSE
Stn(SCS)=03

Meaning The data status of SCS Link Transmission (such as from station 03) has been
changed (For an example, changed from FALSE to TRUE). The (SCS) in the
message text indicates the station type defined on the SCS Link Transmission
builder.

Remark Forcing function

No. 4156
Message name Information of SCS Link Transmission definition change

Printing example SCS0101 SCS Link Transmission Definition Changed

Meaning SCS Link Transmission definitions were changed by on-line change download.

Cause On-line change download was executed from the SENG.

No. 4157
Message name Information of SCS Link Transmission wiring change

Printing example SCS0101 SCS Link Transmission Wiring Changed

Meaning SCS Link Transmission wirings were changed by on-line change download.

Cause On-line change download was executed from the SENG.

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-21
No. 4158
Message name Information of SCS Link Transmission lock time-up

Printing example SCS0101 SCS Link Transmission Data Lock Elapsed the Specified Period =
08:00:00

Meaning SCS Link Transmission lock continued exceeding the time limit (8 hours in the above
example) specified in SYS_FORCE_LT FB.

Action Check whether all SCS Link Transmission locks have been cancelled, and cancel
unnecessary locks.

Remark Forcing function, SCS Link Transmission, SYS_FORCE_LT FB

No. 4159
Message name Information of forced cancellation of SCS Link Transmission locks

Printing example SCS0101 All SCS Link Transmission Data Unlocked

Meaning Locks of all the locked SCS Link Transmission were forcibly cancelled.

Cause Locks of all SCS Link Transmission were cancelled by operation using SYS_
FORCE_LT FB.

Remark Forcing function, SCS Link Transmission, SYS_FORCE_LT FB

No. 4160
Message name Invalid password for Manual Operation FB

Printing example SCS0101 TAG001 Specified Invalid Password

Meaning The password string specified for Manual Operation FB (MOB_21, MOB_11, MOA)
from the HIS is invalid.

Cause The password entered from the HIS and the password set in Manual Operation
FB did not match.

Action Enter the correct password for Manual Operation FB again.

Remark Manual Operation FB (MOB_21, MOB_11, MOA)

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-22
No. 4161
Message name Information of Output IOM Shutdown

Printing example 1 SCS0101 All Output IOM Shutdown

Printing example 2 SCS0101 Output IOM Shutdown NODE 01 SLOT 02

Meaning An output IOM shutdown task is performed by a Shutdown FB (SYS_ALLSD or


SYS_IOSD). If the shutdown task is performed by SYS_IOSD, the output module
location for shutting down (node 1 and slot 2 in the above example) is also included
in the message.

Remark SYS_ALLSD, SYS_IOSD

No. 4162
Message name Information of communication I/O definition change

Printing example SCS0101 Communication Definition Changed

Meaning The communication I/O definitions of the communication module were changed by
on-line change download.

Cause On-line change download was executed from the SENG.

No. 4163
Message name Information of communication I/O wiring change

Printing example SCS0101 Communication I/O Wiring Changed

Meaning The communication I/O wirings were changed by on-line change download.

Cause On-line change download was executed from the SENG.

No. 4164
Message name Information of disabling security level change

Printing example SCS0101 Security Levels Change Disabled

Meaning The security level change of the SCS by a password-authenticated operation


performed from SENG is disabled.

Remark SYS_SEC_CTL FB

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-23
No. 4165
Message name Information of enabling security level change

Printing example SCS0101 Security Levels Change Enabled

Meaning The security level change of the SCS by a password-authenticated operation


performed from SENG is enabled.

Remark SYS_SEC_CTL FB

No. 4166
Message name Information of communication module lock time-up

Printing example SCS0101 Communication Module Lock Elapsed the Specified Period = 08:00:00

Meaning The communication module lock continued exceeding the time limit (8 hours in the
above example) specified in SYS_FORCE_SC FB.

Action Check whether all communication module locks have been cancelled, and cancel
unnecessary locks.

Remark Forcing function, subsystem communication, SYS_FORCE_SC FB

No. 4167
Message name Information of forced cancellation of communication module locks

Printing example SCS0101 All Communication Modules Unlocked

Meaning Locks of all communication modules were forcibly cancelled.

Cause Locks of all communication modules were cancelled by operation using SYS_
FORCE_SC FB.

Remark Forcing function, subsystem communication, SYS_FORCE_SC FB

No. 4168
Message name Information of tag name change by on-line change download

Printing example SCS0101 Online Change Download Tag Name = TAG001 Changed

Meaning The tag name (TAG001 in the above example) of PASSWD FB or override FB was
changed by on-line change download.

Cause On-line change download was executed from the SENG.

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-24
No. 4169
Message name NVRAM diagnosis error

Printing example SCS0101 RIGHT NVRAM Diagnosis Error

Meaning An error was detected during diagnosis of NVRAM (nonvolatile memory) in a CPU
module (right side in the above example).

Cause NVRAM may be faulty.

Action Replace the applicable CPU module.

No. 4170
Message name Flash memory diagnosis error

Printing example SCS0101 RIGHT Flash Memory Diagnosis Error

Meaning An error was detected during self-diagnosis of flash memory in a CPU module (right
side in the above example).

Cause Part of data stored in flash memory was destroyed, or flash memory may be
faulty.

Action If the SCS is in a single CPU module configuration, the SCS will not be able to start
when this CPU restarts next time. It is necessary to change the CPU module right
away.
If the SCS is configured with redundant CPU modules, the control will switch to the
other module after detecting this error, and the module where the error occurs is
restarted as a standby module.
If the error is caused by damage to the data in the flash memory, data in the control
side will be copied to the standby module where the error occurs, and that module
will then recover from abnormal to normal status.
If the error is caused by the physical damage of the flash memory, this system
alarm will occur even after the damaged CPU is switched to standby. Under this
circumstance, it is necessary to change the damaged CPU module.

No. 4172
Message name Information of resource change by on-line change download

Printing example SCS0101 Online Change Download Resource Changed (Total POU=10)

Meaning The resource was changed by on-line change download.The resource defines total
number of POU (10 in the above example).

Cause On-line change download was executed from the SENG.

Action Check and confirm that the total number of POU indicated in this message is equal
to the total number of POU indicated by Database Validity Check Tool.

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-25
No. 4173
Message name Completion of writing to flash memory

Printing example SCS0101 Writing XXXXXX to Flash Memory Succeeded

Meaning Writing to flash memory in a CPU module was normally completed.


XXXXXX: Indicates the data written.
Security Password
System Database
Integration Database
Variable Database
Difference Data

Cause When on-line change download from SENG to SCS was executed or the password
was changed, data was normally written to flash memory.

No. 4174
Message name Failed to write to flash memory

Printing example SCS0101 Writing XXXXX to Flash Memory Error

Meaning Write data error was detected during check at flash memory write in a CPU
module.
XXXXXX: Indicates the data attempted to be written.
Security Password
System Database
Integration Database
Variable Database
Difference Data

Cause Flash memory may be faulty.

Action If the SCS is in a single CPU module configuration, the CPU module continues the
operation even if this error occurs. However, the SCS will not start properly when
this CPU module restarts next time. It is necessary to change the CPU module as
soon as possible.
On a dual-redundant CPU module configuration SCS, if this writing error to flush
memory occurs on one of the CPU modules, the CPU module will be failed and
operation is continued with the other CPU module. It is necessary to change the
failed CPU module right away.
If writing to the flash memories in both CPU modules fails, the SCS will not be able
to start when the CPU restarts. Under this circumstance, it is necessary to change
both CPU modules right away.

Remark Flash memory diagnosis

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-26
No. 4175
Message name Failed to update external communication data

Printing example SCS0101 External Data Refresh Failed

Meaning The SCS has failed to update external communication data. This data is referenced
in communications with CENTUM stations and Modbus, so when this error occurs,
data will not be updated in those stations.

Cause The CPU processing time allocated for the external communication function
processing was not sufficient. As a result, processing to update the external
communication data is not performed.

Action Reduce the communication load on the SCS. If this error occurs regularly, review
the balance between the application logic amount and the scan period.

No. 4177
Message name Information of SCS security level change

Printing example SCS0101 Security Level Changed to 1

Meaning The security level of the SCS was changed (1 in the above example).

Cause The security level of the SCS was changed. The security level can be changed from
the SENG or SYS_SECURE FB.

Note Be sure to revert the security level to 2.

No. 4178
Message name Information of security level time-up

Printing example SCS0101 Security Level = 1 Elapsed the Specified Period = 08:00:00

Meaning The security level is set to 1 for the duration exceeding the time limit (8 hours in
the above example) specified in SYS_SECURE FB.

Cause The security level has not been reverted.

Action Revert the security level to 2.

Remark SYS_SECURE FB

Note When the security level is 0, the message is not informed.

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-27
No. 4179
Message name Information of communication I/O module output enabled operation

Printing example SCS0101 Communication Modules Output Enabled

Meaning The communication modules are enabled for output.

Remark I/O Channel Status dialog box, SYS_STAT_SC FB

Note This is irrelevant for enabling the output of the safety I/O modules.
If you have done the Output enabled operation for the safety output modules,
confirm the message 4181.

No. 4180
Message name Information of password change

Printing example SCS0101 Security Level = 1 Password was Changed

Meaning The password for the SCS security level (1 in the above example) was changed.

Cause The password was changed from the SENG.

Note The message of No. 4173 is also informed after this alarm.

No. 4181
Message name Information of output enabled operation

Printing example SCS0101 Output Enabled

Meaning The output enabled operation for the SCS was performed from the SENG.

Remark I/O Channels Status dialog box, SYS_STAT_FB

Note When all the safety modules output channels go into output-enabled state, the
SCSs operating mode changes to Running.

No. 4182
Message name Information of output module start operation

Printing example SCS0101 IOM Started NODE 01 SLOT 02

Meaning An output module (node 1 and slot 2 in the above example) was started from the
SENG.

Remark SCS State Management window

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-28
No. 4183
Message name Request to upload SOE to SENG

Printing example SCS0101 SOE Save Request

Meaning This notification prompts to upload the event information collected on the SCS to
SENG.

Cause This message is informed every time 12,000 events have been occurred on the
SCS.

Action Start SOE Viewer on SENG and upload events from SCS.

Remark SOER function

Note This system alarm is informed even if SOE Viewer is started periodically. Events
can be uploaded from the SCS by starting SOE Viewer and displaying the latest
event.

No. 4184
Message name Notification on saving SOE trip signal file in SCS

Printing example SCS0101 SOE Trip Signal File No.= 01 Saved

Meaning The SOE trip signal file (No. 01 in the above example) was saved in SCS.

Action Start SOE Viewer on SENG and upload the events in the file.

Remark SOER function

Note When uploading the events is complete, the trip signal files need to be reset. Up to
two trip signal files can be held in the SCS.
The trip signal files can be reset by starting the Message Cache Tool and initializing
the trip information.

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-29
No. 4185
Message name Information of variable value change

Printing example 1 SCS0101 Variable Set to 10.0 Old = 5.0 Variable = VAR001

Printing example 2 SCS0101 Variable Set to TRUE Old = FALSE Variable = VAR001 NODE 01 SLOT
02

Printing example 3 SCS0101 Variable Set to TRUE Old = FALSE Variable = VAR001 NODE 01 SLOT
02 CH 03

Printing example 4 SCS0101 Variable Set to TRUE Old=FALSE Variable=VAR001 Stn=02 No=025

Meaning The value of the variable (VAR001 in the above example) was changed from the
SENG. For a communication I/O, a variable corresponds to the communication
module location (as shown in example 2, node 1, slot 2) is also included in the
message. For an I/O variable, a variable corresponds to the variable location (as
shown in example 3, node 1, slot 2, channel 3) is also included in the message.
The VAR001 in the above printing example 4 is the instance name of the function
block that accesses the data of SCS Link Transmission. The related station number
and bit number are also printed.

Remark Forcing function

No. 4186
Message name Information of lock time-up

Printing example SCS0101 Lock Elapsed the Specified Period = 08:00:00

Meaning Lock continued exceeding the time limit (8 hours in the above example) specified
in SYS_FORCE FB.

Action Check whether all locks have been cancelled, and cancel unnecessary locks.

Remark Forcing function, SYS_FORCE FB

No. 4187
Message name Information of forced cancellation of locks

Printing example SCS0101 All Variables Unlocked

Meaning Locks of all variables were forcibly cancelled.

Cause Locks of all variables were cancelled by operation using SYS_FORCE FB.

Remark Forcing function, SYS_FORCE FB

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-30
No. 4188
Message name Start of on-line change download

Printing example SCS0101 Online Change Download (System Database) Start

Meaning On-line change download to the system database was started.

Remark Download function

No. 4189
Message name Completion of on-line change download

Printing example SCS0101 Online Change Download (System Database) Complete

Meaning On-line change download to the system database was normally completed.

Remark Download function

No. 4190
Message name On-line change download error

Printing example SCS0101 Online Change Download (System Database) Error = 5340-0001

Meaning On-line change download to the system database ended with an error.

Cause/Action Causes and actions vary depending on the error code.


Table Message No. 4190 - Error Causes and Actions
Error code Cause Action
Set the security level to 1 and then execute on-line
5340-**** The security level stays 2.
change download again.
Record the message content and report to
Others Internal error
Yokogawas service department.

No. 4191
Message name Completion of I/O definition rewriting

Printing example SCS0101 IOM Definition Changed NODE 01 SLOT 02

Meaning I/O definition was changed by on-line change download to the system database.
The I/O module position is included in the message (node 1, slot 2 in the above
example).

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-31
No. 4192
Message name Information of override state time-up

Printing example SCS0101 Override Elapsed the Specified Period = 08:00:00

Meaning Override continued exceeding the time limit (8 hours in the above example) specified
in SYS_OVR FB.

Action Check whether overrides were released, and release unnecessary overrides.

Remark SYS_OVR FB

No. 4193
Message name Information of forced release of all overrides

Printing example SCS0101 All Overrides Released

Meaning The overrides for all variables were forcibly released.

Cause The overrides for all variables were forcibly released by operation using SYS_OVR
FB.

Remark SYS_OVR FB

No. 4194
Message name Information of override enabled state time-up

Printing example SCS0101 Enabled OVR FB Elapsed the Specified Period = 08:00:00

Meaning The override enabled state continued exceeding the time limit (8 hours in the above
example) specified in SYS_OVR FB.

Action Check override FB in the override enabled state, and release unnecessary override
enabled state.

Remark SYS_OVR FB

No. 4195
Message name Information of communication I/O data status change

Printing example SCS0101 Communication Data Status Set to TRUE Old = FALSE NODE 01 SLOT
02 Definition 001

Meaning The data status of the communication I/O (such as node 1, slot 2, definition 1 in the
above example) was changed (such as from FALSE to TRUE) from the SENG.

Remark Forcing function

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-32
No. 4196
Message name Invalid password for PASSWD FB

Printing example SCS0101 TAG001 PASSWD FB Specified Invalid Password

Meaning The password string specified for PASSWD FB from the HIS is invalid.

Cause The password entered from the HIS and the password set in PASSWD FB did not
match.

Action Specify the correct password for PASSWD FB and enter it again.

Remark PASSWD FB

No. 4197
Message name Information on active PASSWD FB time-up

Printing example SCS0101 Activated PASSWD FB Elapsed the Specified Period = 10:00:00

Meaning PASSWD FB has been active exceeding the time limit (10 hours in the above
example) specified in SYS_PSWD.

Action Deactivate PASSWD FB that is not required to be active.

Remark SYS_PSWD FB

No. 4198
Message name Information on forced reset of PASSWD FB

Printing example SCS0101 All PASSWD FB Reset to OFF

Meaning The outputs of all active PASSWD FBs were forcibly set to OFF.

Cause The outputs of all active PASSWD FBs were forcibly inactivated (reset to OFF) by
operation using SYS_PSWD FB.

Remark SYS_PSWD FB

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<2.1 System Alarms> 2-33
No. 4199
Message name Override communication error

Printing example SCS0101 TAG001 Override Communication Error (Instance = OVR001)

Meaning Despite an attempt to operate override on the FB OVR001 (in the above example)
with the tag name TAG001 (in the above example) from HIS, communication error
has occurred.

Cause A temporary communication error occurred, and the SCS detected the problem of
the communication data.

Action Execute override operation again.

Remark SYS_OVR FB

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages> 3-1

3. Details of Output Messages in


Common with CENTUM
This chapter describes the details of output messages in common with CENTUM.

3.1 Safety Control Station Error Occurrence


and Recovery Messages (Message
Numbers 0001 through 0094)
This section describes messages having the same message numbers as those of the
CENTUM control station.

No. 0001
Message name Reset start of safety control station

Printing example SCS0101 RIGHT Manual Reset Start

Meaning A CPU module (right side in the above example) of the safety control station (station
name = SCS0101) was reset and started.

Cause Start operation from the SENG or from the front switch of the CPU module

No. 0003
Message name Safety control station automatic reset start

Printing example SCS0101 RIGHT Automatic Reset Start

Meaning An error in the displayed CPU module (right side in the example) of the safety
control station (station name=SCS0101) caused the safety control station to be
automatically reset and started.

Cause CPU module is faulty.

No. 0005
Message name Power ON initial cold start of safety control station

Printing example SCS0101 Power ON (Cold Start)

Meaning The safety control station (station name = SCS0101) performed the initial cold start
processing after it was powered ON.

Cause Recovery from power failure

Note The safety control station always performs the initial cold start processing after
recovery from power failure.

IM 32S02B10-21E 2nd Edition : Dec.15,2008-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages> 3-2
No. 0009
Message name Transfer of control right of safety control station

Printing example SCS0101 Control Transfer

Meaning A transfer of control right occurred in the redundant safety control station (station
name = SCS0101).

Cause The CPU module on one side was stopped.


An error occurred in the CPU module on one side.

Action The CPU module on the standby side takes over control. Replace the CPU module
that was stopped.

IM 32S02B10-21E 1st Edition : May 30,2008-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages> 3-3
No. 0011
Message name Fail information of safety control station

Printing example SCS0101 RIGHT Fail (xxxxxxxx Code= yyyy yyyy yyyy yyyy)

Meaning A CPU module (right side in the above example) of the safety control station (station
name = SCS0101) failed.

Cause The causes are indicated by causes (xxxxxxxx) and a code. For more information,
see the table below.

Action If the safety control station operates normally after restarting automatically, continue
operation. If the safety control station stops after restarting automatically, replace
the CPU module.
Table Message No. 0011 - Cause List
Causes Code (hex 16 digits) Auto (*1)
Item Description
xxxxxxxx yyyy yyyy yyyy yyyy restart
SW STOP Stop by operation of the front switch of the CPU module
V STOP Stop instruction via control bus
DC STOP Stop due to power failure
NSR3 (*2)
INTSTS (*2) An error occurred during CPU module error check.
CPU CPU DOWN NSR3, INTSTS, ERRSTS1 and ERRSTS2 are detailed Yes
module ERRSTS1 (*2) error codes.
stop ERRSTS2 (*2)
SELFSTOP Stop after software detected an error
UNKNOWN Stop due to unknown cause
(*3)
RESTART Restart after software detected an error Yes

*1: Auto restart: (No)


*2: If this error message is displayed, report the display contents of causes (xxxxxxxx) and code to Yokogawas service department.
*3: Refer to the following Table Error Codes and Solutions.

IM 32S02B10-21E 1st Edition : May 30,2008-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages> 3-4
Table Error Codes and Solutions
Code
Error Solution
(HEX; 16 Digits)
Check to see if the application logic contains zero
Zero division occurred when running
0000 5090 yyyy yyyy division or not, and correct the application logic if it
the application logic.
contains.
The application logic is trying to access Check the application and find out which logic
0000 5091 yyyy yyyy an array datum beyond the scope of program is accessing the out-of-range array data
the array. and correct the error.
A database inconsistency has been
detected, possibly caused by
0000 50a9 yyyy yyyy Run offline downloading.
restarting the SCS without releasing the
break point.
The firmware (Revision F4) in the
For a system that contains Optical ESB Bus
4000 3BF1 0255 8082 CPU module is too old to support the
Repeater modules, the firmware of CPU with the
(*1) system with Optical ESB Bus Repeater
proper revision number should be used.
modules.
The CPU model and station model are Match the CPU model and station model with each
0000 5010 yyyy yyyy
inconsistent. other.
The calculation in a running application Check the application and find out what caused the
FFFF 000B 0000 000F
overflowed. calculation overflow and then modify it.
If this error message is displayed, report the display
Other Other contents of causes (xxxxxxxx) and the code to
Yokogawas service department.
*1: This code is not generated in SCSP2.

No. 0013
Message name AC power supply failure of safety control station

Printing example SCS0101 AC Fail (Time 05.02.01 18:45)

Meaning AC power of the safety control station (station name = SCS0101) failed and was then
recovered. The date and time indicated are when the power failed. This message
is dispatched after the power is recovered.

Cause The voltage of AC power supply dropped, or a power failure occurred.

Note The SCS has been initialized and then started.

No. 0015
Message name Self-diagnosis error of clock inside CPU module

Printing example SCS0101 RTC Diagnose Error Code=0001

Meaning An error was detected during self-diagnosis of the clock inside the safety control
station (station name = SCS0101).
Code=0001: Check pattern mismatch
Code=0002: Inappropriate date/time value
Code=0003: Date/time not updated

Action Replace the CPU module.

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages> 3-5
No. 0017
Message name ROM checksum error of CPU module

Printing example SCS0101 RIGHT ROM Sum Check Error

Meaning A ROM checksum error was detected in the indicated CPU module (right side in the
above example) of the safety control station (station name = SCS0101).

Action Replace the CPU module.

No. 0021
Message name Internal task error of safety control station

Printing example SCS0101 Internal Error TASK=TSK1 Code=100 Error=1000 - E0F0

Meaning An error state was detected during the execution of a task (TSK1 in the above
example) in the safety control station (station name = SCS0101). TASK, Code
and Error indicate detailed error information.

Cause This is a software problem.

Action Report the message content to Yokogawas service department.

No. 0023
Message name Mapping block fatal error

Printing example SCS0101 Block TAG001 Return Error 8E04 and stop

Meaning An execution disabled error was detected during the execution of a mapping
block (TAG001 in the above example) in the safety control station (station name =
SCS0101).

Cause There is a problem in the integration DB. Error indicates detailed error
information.

Action Report the message content to Yokogawas service department.

IM 32S02B10-21E 1st Edition : May 30,2008-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages> 3-6
No. 0025
Message name Function control word error

Printing example SCS0101 No Block Control Word for Block Type=1804

Meaning The internal program that corresponds to the block type code of the safety control
station (station name = SCS0101) does not exist. Type indicates detailed internal
information.

Cause This is an internal error at task initialization.

Action Report the message content to Yokogawas service department.

No. 0027
Message name Mapping block record information error

Printing example SCS0101 TAG001 Block Bad Record No = 3

Meaning There is a bad record in the mapping block (TAG001 in the above example) of the
safety control station. No indicates the bad record number in the database.

Cause The mapping block and the record block number do not match.

Action Report the block type and record number where an error occurred to Yokogawas
service department.

Note Do not perform on-line change download after this alarm occurred.

No. 0033
Message name Online downloading abnormal end

Printing example SCS0101 Online Download Error Code=9402 - 0000

Meaning On-line change download of the safety control station (station name = SCS0101)
ended with an error. Error Code indicates detailed internal information.

Cause/Action See the table below.


Table Message No. 0033 - Error Code List
Code Error Contents Cause Action
9402
On-line change
9403 The SCS was reset and started
downloading Execute off-line download.
9404 during on-line change download.
abnormal end
9405
Report the display content of the code to
Others Internal error Internal error
Yokogawas service department.

IM 32S02B10-21E 1st Edition : May 30,2008-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages> 3-7
No. 0041
Message name Safety control station fan alarm

Printing example SCS0101 Fan (SCU N1) Alarm

Meaning A cooling fan of the safety control station (station name = SCS0101) is abnormal.
One of the following items is displayed in the parentheses in the above example.
SCU N1: Left side fan
SCU N2: Right side fan

Cause The cooling fan stopped or its revolution is abnormal.

Action Replace the failed fan unit.

Remark HKU function

No. 0042
Message name Recovery from safety control station fan alarm

Printing example SCS0101 Fan(SCU N1) Recover

Meaning The cooling fan of the safety control station (station name = SCS0101) recovered.
The content in the parentheses in the above example is the same as message No.
0041. (This is a recovery message of No. 0041.)

Remark HKU function

No. 0043
Message name Safety control station temperature alarm

Printing example SCS0101 Temperature(RIGHT BATTERY) Alarm

Meaning This is a temperature rise alarm of the safety control station (station name =
SCS0101). One of the following items is displayed in the parentheses in the above
example.
RIGHT BATTERY: Battery of the right side CPU module
LEFT BATTERY: Battery of the left side CPU module
AIR IN: Air inlet
AIR OUT: Air outlet

Cause The CPU module temperature exceeded the specified value.

Action After checking the operation of the cooling fans, report to Yokogawas service
department as necessary.

Remark HKU function

IM 32S02B10-21E 1st Edition : May 30,2008-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages> 3-8
No. 0044
Message name Recovery from safety control station temperature alarm

Printing example SCS0101 Temperature(RIGHT BATTERY) Recover

Meaning The temperature of the safety control station (station name = SCS0101) recovered
normally. The content in the parentheses in the above example is the same as
message No. 0043. (This is a recovery message of No. 0043.)

Remark HKU function

No. 0045
Message name Power supply module alarm of safety control station

Printing example SCS0101 RIGHT PSU Alarm

Meaning The power supply module of a CPU node (right side in the above example) of the
safety control station (station name = SCS0101) is abnormal.

Cause Power supply module failure

Action Replace the applicable power supply module.

No. 0046
Message name Recovery from power supply module alarm of safety control station

Printing example SCS0101 RIGHT PSU Recover

Meaning The power supply module of a CPU node (right side in the above example) of the
safety control station (station name = SCS0101) recovered normally. (This is a
recovery message of No. 0045.)

No. 0047
Message name Battery alarm of CPU module

Printing example SCS0101 RIGHT Battery Alarm

Meaning A battery of the CPU module (right side in the above example) of the safety control
station (station name = SCS0101) is abnormal.

Cause The battery switch is OFF, or the battery is faulty.

Action Make sure that the switch of the applicable battery is ON. If the above message
occurs even if the battery switch is ON, replace the battery.

Remark HKU function

IM 32S02B10-21E 1st Edition : May 30,2008-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages> 3-9
No. 0048
Message name Recovery from battery alarm of CPU module

Printing example SCS0101 RIGHT Battery Recover

Meaning A battery of the CPU module (right side in the above example) of the safety control
station (station name = SCS0101) recovered normally. (This is a recovery message
of No. 0047.)

Remark HKU function

No. 0055
Message name Information of same frame reception in on-line change download communication

Printing example SCS0101 Received Same Online Download Frame Code=1 Frame=3

Meaning The same communication frame was received twice during the execution of on-line
change download. Code and Frame indicate detailed internal information.

Action Execute on-line change download again.

No. 0057
Message name Information of on-line change download error

Printing example SCS0101 Online Download Error Call Code=9601 - 0000 Data=91,0,0,0

Meaning An error occurred during the execution of on-line change download of the safety
control station (station name = SCS0101). Code and Data indicate detailed
internal information.

Cause This error occurs if error data cannot be saved on the safety control station side.

Action It is necessary to determine an action to take based on the Code and Data
information. Report the display contents of Code and Data to Yokogawas service
department.

Note Do not execute on-line change download after this alarm occurred.

No. 0059
Message name Information of recovery from node power failure

Printing example SCS0101 FIO NODE Power On FIO NODE 02

Meaning An I/O node (2 in the above example) of the safety control station (station name =
SCS0101) recovered from power failure.

IM 32S02B10-21E 1st Edition : May 30,2008-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages> 3-10
No. 0063
Message name ESB bus error

Printing example SCS0101 FIO-BUS Fail FIO BUS No.1

Meaning An error occurred on one side (No. 1 in the above example) of the ESB buses of
the safety control station (station name = SCS0101).

Cause This is an ESB bus error on one side.

Action SSB401, SEC402/SEC401 or ESB bus failure may be considered as an error


cause. Take appropriate action in the following:
Check to see if the ESB bus cables are connected correctly. Check for incorrect
connection or bad connection of the cables, or check the terminators of the
bus.
Check to see if one SSB401 is causing a bus error of the entire buses
according to the following procedure. Pull out the ESB bus connector of each
SSB401 that connects to the corresponding bus, one by one, from the node.
Wait for two to three seconds, and if Recover is not printed, insert the
ESB bus connector again, and pull the bus connector of the next node.
If Recover is printed, the bus connector of the SSB401 that was pull out at
that time is faulty, so replace the SSB401.
If no recovery was made even after the bus connectors of all nodes were
pulled out, the SEC402/SEC401 may be faulty. In such a case, replace the
SEC402/SEC401.
If no recovery was still made, press the START/STOP button on the CPU
modules front panel on the control side twice, and switch the control right of
the CPU module. Replace the CPU module after restarting.

If no recovery was still made after the above actions, it may be an ESB bus cable
failure (such as a bus connector). Replace the applicable bus.

Note This message will be notified if all the I/O nodes, excluding the CPU node, become
abnormal.
However, if a system contains Optical ESB Bus Repeater module, when all the
I/O nodes directly connected to/from SEC402/SEC401 (i.e., the I/O nodes not
connected via Optical ESB Bus Repeater module), become abnormal, but the
I/O nodes connected via the Optical ESB Bus Repeater module are normal, this
message will not be notified

No. 0064
Message name Normal recovery of ESB bus

Printing example SCS0101 FIO-BUS Recover FIO BUS No.1

Meaning The ESB bus indicated in the message recovered normally. (This is a recovery
message of No. 0063.)

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages> 3-11
No. 0065
Message name Failure of ESB Bus Interface module (SSB401) of node

Printing example SCS0101 SBS Fail FIO NODE 02 SBS RIGHT

Meaning An error occurred in an ESB Bus Interface module (right side in the above example)
of an I/O node (2 in the above example) of the safety control station (station name
= SCS0101).

Cause One of the following causes may be considered.


ESB Bus Interface module becomes abnormal.
Connection route to the ESB Bus Interface module becomes abnormal.
For the I/O nodes that are connected via Optical ESB Bus Repeater module,
the Optical ESB Bus Repeater module related hardware such as module or
Fiber-optic cable may have problem.

Action If an I/O node routed through the Optical ESB Bus Repeater related devices
becomes abnormal, the erroneous device can be identified according to the content
of the messages or the LED status so as to replace the damaged device. If all the
I/O nodes routed through the Optical ESB Bus Repeater related devices become
abnormal, the error may have occurred in the Optical ESB Bus Repeater module
related hardware such as module or Fiber-optic cable. Moreover, if the Optical ESB
Bus Repeater modules are mounted in the SNT10D, the error may be caused by
the failure of a power supply module of SNT10D unit.

No. 0066
Message name Normal recovery of ESB Bus Interface module (SSB401) of node

Printing example SCS0101 SBS Recover FIO NODE 02 SBS RIGHT

Meaning An ESB Bus Interface module (right side in the above example) of an I/O node
(2 in the above example) of the safety control station (station name = SCS0101)
recovered normally. (This is a recovery message of No. 0065.)

No. 0067
Message name Failure of power supply module of node

Printing example SCS0101 PSU Fail FIO NODE 02 PSU RIGHT

Meaning An error occurred in a power supply module (right side in the above example) of
an I/O node (2 in the above example) of the safety control station (station name =
SCS0101).

Cause Failure of a power supply module of an I/O node

Action Replace the power supply module of the applicable node.

Note When the message shows node 1, it indicates that an error occurred in a PSU for
the CPU node.

IM 32S02B10-21E 1st Edition : May 30,2008-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages> 3-12
No. 0068
Message name Normal recovery of power supply module of a node

Printing example SCS0101 PSU Recover FIO NODE 02 PSU RIGHT

Meaning The power supply module of the I/O node indicated in the message (2 in the above
example) recovered normally. (This is a recovery message of No. 0067.)

No. 0069
Message name Error before database download to I/O module

Printing example SCS0101 IOM Download Error=A701

Meaning Database download to the I/O module (IOM) can not be started.

Cause/Action The cause and action vary depending on the content of the error.
A701
This message occurs when attempting to download to an IOM while another
IOM download is still running. Only one IOM download can be performed
at one time, so please wait for the other IOM download to complete before
running an IOM download operation again.
A72C
Automatic IOM download to a standby side I/O module is running. This error
occurs if IOM download to the same I/O module is manually executed from
the SENG or online change download is executed to make changes in I/O
parameter settings while automatic IOM download is running.
5135
This message occurs when attempting to download to an IOM even though it
is running normally.
Others
Report the error display content to Yokogawas service department.

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages> 3-13
No. 0081
Message name Failure of I/O module

Printing example SCS0101 IOM Fail FIO NODE 01 SLOT 01 Code=5101

Meaning An error occurred in the I/O module mounted in slot 1 of node 1 (CPU node) of the
safety control station (station name = SCS0101).

Cause For more information about error codes, see the table below.

Action Replace the applicable I/O module.

Table Error Details of Message No. 0081 - Errors of Analog Input Modules and Contact I/O Modules
Error code Description of error
The communication between CPU and I/O modules encounters a no-response error. This error is
5101
caused either by the I/O module abnormality or by the communication route abnormality.
The type of the I/O module defined on the SENG and the type of the I/O module mounted does
5102
not match. Check type of the I/O module.
The setting information defined on the SENG and the I/O module setting information do not
5103
match. Execute IOM download.
5104 A hardware error of the I/O module was detected. Check detailed error causes in the IOM report.
A setting error of the I/O module. Check detailed error causes in the IOM report (field side
5105
connector disconnection, field power supply/wiring problem, etc.)
5106 The I/O module recovered from an error state. Check detailed error causes in the IOM report.
The error that actuated the output shutoff switch occurred. Check detailed error causes in the IOM
5107
report. When this error occurred, start the I/O module after recovering from the error.
5111, 5112, A communication data check error was detected between the CPU and the I/O module. A failure
5113 of the I/O module or a problem of the communication path up to the I/O module may be the cause.
5114, 5115 An error was detected in the redundant control part of the I/O module. Replace the I/O module.
5116, 5117 An I/O module error was detected. Replace the I/O module.
5118 An SCS internal error (SCS database error) was detected.

Table Error Details of Message No.0081 - ALR111/ALR121 Modbus Slave


Error Code Cause/Action
The communication between CPU and I/O modules encounters a no-response error. This
C580 error may be caused by the I/O module abnormality, communication route abnormality or an
abnormality other than C581 to C583 depicted.
The communication program is not downloaded to the communication module. Run IOM
C581
download.
The communication program in the communication module is not the program for Modbus slave
C582
communication. Run IOM download.
The physically installed communication module shows a different model name from the
C583
communication module defined in SENG. Check the model of the communication module.

IM 32S02B10-21E 1st Edition : May 30,2008-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages> 3-14
Table Error Details of Message No.0081 - ALR111/ALR121 Subsystem Communication

Error Code Cause/Action

No response from the communication module due to communication module abnormality.


A33D
Change the communication module.
A33E Error occurred in the communication route between CPU and node.
The communication program is not downloaded to the communication module. Run IOM
C581
download.
The communication program in the communication module is not the program for the
C582
communication defined in SENG. Run IOM download.
The physically installed communication module shows a different model name from the
C583
communication module defined in SENG. Check the model of the communication module.
C585 Error is found by self-diagnosis. Change the communication module.
C598 The communication module is reset due to on-line change download or the IOM downloading.
C599 Downloading to database. This error code will be displayed only in IOM report.
C59A Downloading communication program. This error code will be displayed only in IOM report.
C5C1 Error found after resetting the communication module. Change the communication module.
Failed to download the communication program. Waiting time for shifting to the downloading
C5C6
mode of the communication program exceeded the time limit. Start IOM download again.
Failed to download the communication program. Processing time for downloading the
C5C7
communication program exceeded the time limit. Start IOM download again.
C5E2 Communication module encountered an error and stopped. Change the communication module.

IM 32S02B10-21E 1st Edition : May 30,2008-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages> 3-15
No. 0082
Message name Normal recovery of I/O module

Printing example SCS0101 IOM Recover FIO NODE 01 SLOT 01

Meaning The I/O module mounted in slot 1 of node 1 in the safety control station (station name
= SCS0101) recovered normally. (This is a recovery message of No. 0081.)

No. 0083
Message name I/O module database error occurred

Printing example SCS0101 IOM Configuration Error FIO NODE 01 SLOT 01

Meaning An error occurred in the database on the I/O module mounted in slot 1 of node 1 in
the safety control station (station name = SCS0101).

Cause The database on the I/O module and the database on the SCS do not match. The
following causes may be considered.
IOM download has not been executed.
IOM failure

Action If this error occurred after replacing a module or at startup, the database might not
have been downloaded to the I/O module. Execute IOM download.
If this error occurred during I/O module operation, the I/O module may be faulty.
Replace the I/O module.

No. 0085
Message name I/O module communication error occurred

Printing example SCS0101 IOM Communication Error FIO NODE 01 SLOT 01 RIGHT

Meaning An error occurred in one of the SB buses (right side in the above example). An error
occurred when accessing the I/O module mounted in slot 1 of node 1 in the safety
control station (station name = SCS0101).

Cause If this error occurred on all input modules within the same node, an I/O module may
be faulty, or the backboard bus of the node may be faulty. Or, an ESB bus or an
SSB401 may be faulty, or they may not be connected properly.

Action Report to Yokogawas service department.

No. 0086
Message name Recovery from I/O module communication error

Printing example SCS0101 IOM Communication Recover FIO NODE 01 SLOT 01 RIGHT

Meaning A communication error with the I/O module mounted in slot 1 of node 1 in the safety
control station (station name = SCS0101) recovered. (This is a recovery message
of No. 0085.)

IM 32S02B10-21E 1st Edition : May 30,2008-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages> 3-16
No. 0087
Message name Node error occurred

Printing example SCS0101 NODE Fail FIO NODE 02

Meaning An error occurred in node 2 of the safety control station (station name =
SCS0101).

Cause One of the following causes may be considered.


A power failure occurred in the node, or both of the two ESB buses are
abnormal.
Both SSB401 are abnormal.
For the I/O nodes that connected via Optical ESB Bus Repeater module, the
Optical ESB Bus Repeater module related hardware such as module or Fiber-
optic cable may have problem.

Action Report to Yokogawas service department.

No. 0088
Message name Normal recovery of node

Printing example SCS0101 NODE Recover FIO NODE 02

Meaning The node indicated in the message recovered normally. (This is a recovery message
of No. 0087.)

IM 32S02B10-21E 1st Edition : May 30,2008-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages> 3-17
No. 0089
Message name Subsystem communication error

Printing example SCS0101 SS-COM Error FIO NODE 01 SLOT 01 PORT 01 STN001 Code=
A3B0

Meaning A communication error occurred between the indicated communication module


and the subsystem.

Cause/Action The error details can be found in the instruction manuals of the connected
subsystem. See the manuals for error details.
The error codes that irrelevant to the connected subsystems are shown below:

Remark Subsystem communication


Table Error Details of Message No.0089 - Errors that irrelevant to subsystems
Code Error Cause/Action
A391 Driver Busy Occurs when sending or receiving.
This message occurs when carrier detection fails due to the
A392 Communication Line Busy CD line is energized within the transmission enable monitoring
time.
This message occurs when clear to send fails due to the CS
line is not energized within the transmission enable monitoring
A393 Communication Line Not Ready
time, or when data ready fails due to the DR line is not
energized within the transmission enable monitoring time. (*1)
A394 Data size is too large for sending.
A395 The port for sending is not declared.
A397 Underrun
Interval of characters became This message occurs when the interval of characters exceeds
A398
timeout the specified time.
A399 Reception buffer overflow
A39A Reception parity error
A39B Reception overrun
A39C Reception frame error
Number of characters beyond
A39D
range
A39F Other errors
A3B0 to For more information, see the instruction manuals of
Reserved for subsystems
A3FF subsystems.
*1: The transmission-watching timer monitors the waiting time of the transmission line become ready for transmission.
When RS is sent, and the waiting time for transmission exceeds the specified time period, the transmission becomes error.
The transmission waiting time is normally set to 1000ms.
The conditions for transmission are as follows:
CD line off (When CD check is enabled)
CS (CTS) line on
EDR line on (When DR check is enabled)

IM 32S02B10-21E 1st Edition : May 30,2008-00


<3.1 Safety Control Station Error Occurrence and Recovery Messages> 3-18
No. 0090
Message name Subsystem communication recovered

Printing example SCS0101 SS-COM Recover FIO NODE 01 SLOT 01 PORT 01 STN001

Meaning The communication between the indicated communication module and the
subsystem recovered from the error.

Remark Subsystem communication

No. 0093
Message name CPU nodes housekeeping unit error

Printing example SCS0101 RIGHT HKU Error Code=0001

Meaning The CPU nodes housekeeping unit of the safety control station (station name =
SCS0101) is faulty. Code indicates detailed internal information.

Action Report to Yokogawas service department.

Remark HKU function

No. 0094
Message name Normal recovery of CPU nodes housekeeping unit

Printing example SCS0101 RIGHT HKU Recover Code=0001

Meaning The CPU nodes housekeeping unit of the safety control station (station name =
SCS0101) recovered normally. (This is a recovery message of No. 0093.)

Remark HKU function

IM 32S02B10-21E 1st Edition : May 30,2008-00


<3.2 Safety Control Station Status Change Related Messages> 3-19

3.2 Safety Control Station Status Change


Related Messages (Message Numbers 0450
through 0480)
This section describes messages related to status change from the safety control station.

No. 0450
Message name Copy program and database on control side of safety control station to standby
side

Printing example SCS0101 Copy

Meaning The copying of the program and database on the control side of the safety control
station to the standby side has been started.

Cause This message is displayed when the CPU module on the standby side of the safety
control station (station name = SCS0101) was started.

No. 0451
Message name Information of switching of control side of safety control station

Printing example SCS0101 RIGHT Control

Meaning The CPU module on the right or left side (right side in the above example) of the
safety control station (station name = SCS0101) has been set to the control side.

No. 0452
Message name Information of switching of standby side of safety control station

Printing example SCS0101 LEFT Stand - By

Meaning The CPU module on the right or left side (left side in the above example) of the safety
control station (station name = SCS0101) has been set to the standby side.

No. 0459
Message name Information on I/O module service side

Printing example SCS0101 IOM In Service FIO NODE 01 SLOT 01

Meaning One side (slot 1 of node 1 in the above example) of a redundant I/O module has
gained control right.

IM 32S02B10-21E 1st Edition : May 30,2008-00


<3.2 Safety Control Station Status Change Related Messages> 3-20
No. 0460
Message name Information of I/O module out service

Printing example SCS0101 IOM Out Service FIO NODE 01 SLOT 01

Meaning An I/O module (slot 1 of node 1 in the above example) has been set to standby or
stopped.

No. 0471
Message name Normal completion of on-line change download

Printing example SCS0101 Online Download (Integration Database) Complete

Meaning On-line change download to the safety control station has normally been
completed.

No. 0474
Message name Information of tag list duplicate error

Printing example SCS0101 Tag Duplication Error Tag = TAG001

Meaning A duplicate tag list name exists in the same safety control station.

Action Report to Yokogawas service department.

No. 0475
Message name Start of database download to I/O module

Printing example SCS0101 IOM Download Start FIO NODE 01 SLOT 01


In the case of automatic IOM download:
SCS0101 Automatic IOM Download Start FIO NODE 01 SLOT 02

Meaning Database download to the I/O module indicated in the message has been
started.

No. 0476
Message name Normal completion of database download to I/O module

Printing example SCS0101 IOM Download Complete FIO NODE 01 SLOT 01


In the case of automatic IOM download:
SCS0101 Automatic IOM Download Complete FIO NODE 01 SLOT 02

Meaning Database download to the I/O module indicated in the message has normally been
completed.

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


<3.2 Safety Control Station Status Change Related Messages> 3-21
No. 0477
Message name Database download error to I/O module

Printing example SCS0101 IOM Download Error FIO NODE 01 SLOT 01 Error=xxxx
In the case of automatic IOM download:
SCS0101 Automatic IOM Download Error FIO NODE 01 SLOT 02 Error=xxxx

Meaning An error occurred during database download to the I/O module indicated in the
message. xxxx indicates an error code.

Cause/Action The following lists error codes. If an error occurs, remove the cause, and execute
IOM download again.
If an error other than the following occurred, replace the I/O module and execute
IOM download again. If other error occurred again, report details to Yokogawas
service department.
IOM error codes other than ALR111 and ALR121
A701: This I/O module is currently executing download.
3B1B: The I/O module is faulty.
CFxx: An error was replied from the I/O module.
CF10: The type of the I/O module is not correct.
Error codes of ALR111 and ALR121
A33D: Communication cannot be performed with the ALR1x1.
A33E: The communication path between the CPU module and the ALR1x1
is abnormal (node failure, etc.)

No. 0480
Message name Heavy load on periodical processing

Printing example SCS0101 Too Heavy Load

Meaning The processing time of External Communication Function of the safety control
station has exceeded the four times the scan period that is specified for External
Communication Function.

Cause The load on the safety control station is too heavy.

Action Correct the application and reduce the load on the safety control station.

IM 32S02B10-21E 1st Edition : May 30,2008-00


<3.3 Safety Control Station Related Messages> 3-22

3.3 Safety Control Station Related Messages


(Message Numbers 0727 through 0787)
This section describes messages that have common message numbers with the
messages of the CENTUM control station.

No. 0727
Message name Block mode recovery error information

Printing example SCS0101 Block Mode Change Error Block=TAG001 Code=9601-0000


TAG001: Tag name
9601-0000: Error code

Meaning Block mode recovery failed at the end of downloading.

Action Report the error code to Yokogawas Service department.

No. 0743
Message name Self-diagnostic SEN-BUS Failure

Printing example SCS0101 SEN-BUS Alarm SEN-BUS No.1

Meaning The SEN-BUS in question has failed.

Cause There is a failure in the SEN-BUS in the CPU node or the CPU module mounted.

Action Replace the CPU node or the CPU module mounted.

No. 0744
Message name Self-diagnostic SEN-BUS Recovery

Printing example SCS0101 SEN-BUS Recover SEN-BUS No.1

Meaning The SEN-BUS in question has returned to normal. (This is a recovery message of
No. 0743.)

IM 32S02B10-21E 2nd Edition : Dec.15,2008-00


<3.3 Safety Control Station Related Messages> 3-23
No. 0749
Message name Self-diagnosis detected an I/O Error

Printing example SCS0101 FIO Self Diag Error FIO CODE = 00005119 DET = 00000000

Meaning I/O error was detected during self-diagnosis.

Cause/Action The action varies depending on the Code and DET. Contact Yokogawa service
department with the contents of CODE and DET.
The following describes the contents of CODE and DET.
CODE = 00005119
An error was detected in the redundant control unit. Switching is not performed
even if an error occurred on the control side. Replace the I/O module.
DET = nnss0000 (Mounting position of the error generating module, nn: Node
number, ss: Slot No.)

No. 0750
Message name I/O Recovery from the error detected by self-diagnosis

Printing example SCS0101 FIO Self Diag Recover FIO CODE = 00000000 DET = 00000000

Meaning Recovery from I/O error detected by self-diagnosis. (This is a recovery message
of No. 0749.)

No. 0751
Message name Time self-diagnostic testing error

Printing example SCS0101 RIGHT Time Self Diag Error Code=00030021

Meaning A clock error is detected by self-diagnosis while the CPU of either redundant or
non-redundant is running.

Cause VEHICLE clock, RTC or GPS clock trouble

Action Replace the CPU module.

No. 0753
Message name Communication Overload

Printing example SCS0101 Communication Overload

Meaning Communication load to safety control station exceeded the limit.

Cause There were many communication demands from the operation and monitoring
function window or application programs to the safety control station.

Action If the windows for the indicated safety control station are displayed on the HIS, the
windows need to be closed. Modifying the application programs may also reduce
the communication load to the safety control station.

IM 32S02B10-21E 1st Edition : May 30,2008-00


<3.3 Safety Control Station Related Messages> 3-24
No. 0767
Message name Faulty one ESB bus in CPU module

Printing example SCS0101 FIO-BUS Fail FIO RIGHT BUS No.1

Meaning A communication error (bus1 in the above example) occurred in standby side CPU
module (right side in the above example) of the safety control station (station name =
SCS0101). (Communication with all nodes on the bus1 side became abnormal.)

Cause The CPU module or the backboard of the CPU node may be faulty.

Action Replace the CPU module or the CPU node.

No. 0768
Message name Single ESB bus in CPU module Recovery

Printing example SCS0101 FIO-BUS Recover FIO RIGHT BUS No.1

Meaning A communication error (bus1 in the above example) in standby side CPU module
(right side in the above example) of the safety control station (station name =
SCS0101) recovered. (This is a recovery message of No. 0767.)

No. 0787
Message name Self-diagnosis detected I/O error in CPU module

Printing example SCS0101 I/O Diagnosis Error IO RIGHT CODE=02518000 00000000

Meaning A self-diagnosis error occurred in a CPU module (right side in the above example)
of the safety control station (station name = SCS0101).
Table Message No. 0787 - Error Code Detail
Code (hexadecimal, 16
digits)
Error code Error detail Factor
(Upper 8 (Lower 8
digits) digits)
0251 8000 0000 0000 A CPU module error was detected. Replace the CPU module.
This code indicates that the revision of the
If a system contains Optical ESB Bus
0000 0270 firmware (F4) in the CPU module is obsolete
0255 8082 Repeater module, the proper revision of
(*1) for the system configured with Optical ESB Bus
CPU should be used.
Repeater modules.
*1: This code is not generated in SCSP2.

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00


Rev-1

Revision Information
Title : Messages
Manual No. : IM 32S02B10-21E

Dec. 2009/3rd Edition/R2.03 or later*


* : Denotes the release number of the software corresponding to the contents of this users manual. The
revised contents are valid until the next edition is issued.
System alarm messages related to the following features were added:
Inter-SCS Safety Communication data lock (4139, 4140, 4141, 4142, 4153, 4154)
Automatic scan period extension and its on-line change (4143, 4144, 4152)
Abnormal calculation (4145, 4146)
Messages revised: 0011, 0069, 0475, 0476, 0477, 0787

Dec. 2008/2nd Edition/R2.02 or later


Overall CS 3000 was changed to CENTUM, which refers to both CENTUM VP and CS 3000.

May 2008/1st Edition/R2.01 or later


Newly published

n For Questions and More Information


Online Query: A query form is available on the following URL for online query.
http://www.yokogawa.com/iss/
If you want more information about Yokogawa products, you can visit
Yokogawas homepage at the following web site.
Homepage: http://www.yokogawa.com/
n Written by Process Automation Product Marketing Dept.
Industrial Automation Systems Business Div.
Yokogawa Electric Corporation
n Published by Yokogawa Electric Corporation
2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750, JAPAN

IM 32S02B10-21E 3rd Edition : Dec.22,2009-00

Anda mungkin juga menyukai