20 August 2015
Stefan Naude RCDD
The SIEMON Company
Agenda
ISO/IEC 14763-1
Information technology Implementation and
operation of customer premises cabling Part 1:
Administration
ISO/IEC 14763-3
Information technology Implementation and
operation of customer cabling Part 3: Testing of
Optical Fibre
ISO/IEC 14763-2
Information technology Implementation and
operation of customer cabling Part 4: Testing of
balanced copper cabling in the horizontal subsystem
Data Centre Standards
ANSI/TIA 568-C.2
ANSI/TIA 568-C.0 ANSI/TIA 568-C.1
Balanced Twisted-Pair
Generic Telecommunications Cabling Commercial Building
Telecommunications Cabling &
for Customer Premises Telecommunications Cabling
Components
o Server Virtualization
o New Applications
o IoT (Estimated 50 Billion object by 2020)
o TV/Video on demand
o Wireless Devices
o Big Brother society
o Cloud Computing
The Need for Speed
40G MTP
TX RX
10G
TX RX
10G
TX
10G
RX o OM3 to 100m
TX
10G
RX o OM4 to 150m
o Spare 4 fibre's
can be used to
create another
RX TX
RX
10G
TX
port
10G
RX TX
10G
RX TX
10G
Fibre in the Data Centre
100G MTP
TX RX
25G
TX RX
25G
TX RX
25G
TX RX
25G o OM3 to 70m
o OM4 to 100m
o Approved by IEEE
RX TX
March 2015
25G
RX TX
25G
RX TX
25G
RX TX
25G
Fibre in the Data Centre
Fibre in the Data Centre
Link Budgets
Fiber
Distance Max Channel
Application Attenuation
(Meters) Loss/Connector Loss
(3.0dB/km)
10 GbE OM3
300 2.6 dB/NA 0.9 dB
@850 nm
40/100 GbE
100 1.9 dB/1.5 dB 0.3 dB
OM3 @ 850 nm
10 GbE OM4
400 2.9 dB/NA 1.2 dB
@850 nm
40/100 GbE
150 1.5 dB/1.0 dB 0.4 dB
OM4 @ 850 nm
Fibre in the Data Centre
Link Budgets
Fibre loss @
1. Length Attenuation physical fibre
2. LC to LC interface (Front of cassette)
3. MTP to MTP interface( Back of cassette)
**Consider Low Loss products**
Fibre in the Data Centre
High Density
o Space in a DC comes at premium
o Environments with high volume of fibre
o SAN switches
o LAN Switches
o Cross Connects in a centralized patching zone
o 144 Cores in 1U is high density
o Consider the panels and management
Agenda
Cable Management
Other Design Considerations
Correct Cable Management
Other Design Considerations
Correct Cable Management
Agenda