APPLICATION NOTE
ST72141 BLDC MOTOR CONTROL SOFTWARE AND
FLOWCHART EXAMPLE
by Microcontroller Division Applications

INTRODUCTION
The purpose of this application note is to give the flowcharts of the software examples showing
how to drive a motor in both current and voltage modes and give examples of Open Loop or
Closed Loop speed regulation.
The software examples described in this application note are those generated by the
ST7MTC2 Kanda kit for Sensorless mode. 80% of the code is generic, the remaining 20% is
specific to the implementation of the ST72141 microcontroller (MCU) in the ST7MTC2 kit (user
interface and communication data).
Note: Please refer to Application Note 1321 for details concerning Sensor mode.
The software examples given in the file attached with this application note illustrate Current
mode and Closed Loop driving mode for a 4-pole, brushless DC (BLDC) motor.

1 DESCRIPTION OF SOURCE FILES


The source files described in this section refer to the software provided in the file attached with
this application note.
Aut_cc.asm is the main file and also contains the interrupt routines,
Sub_cc.asm contains the software subroutines,
Sub_cc.inc contains the subroutine declarations,
Cst_cc.asm and Cst_cc.inc contain the constant declarations,
ST72e141.asm and st72e141.inc are the map files.
Paramcc.txt is a complete set of motor parameters. These parameters are declared in the
ROM part of the ST72141 MCU (with an include file) and then transferred to the RAM part of
the ST72141 MCU at the beginning of the main file. This is because the value of some param-
eters can be changed while the motor is running. Most of these parameters are coded as indi-
cated in the datasheet.
Deframp.txt is the ramp table for the start-up sequence of the motor. It contains 38 consecu-
tive decreasing step times required to accelerate the motor and to detect the first Back-EMF
zero-crossing event.
Def_prep.txt is the current ramp for the pre-positioning phase of the motor. It contains 25 steps
of increasing current values required to set the rotor in a given position.

AN1083/1101 1/31

1
Table of Contents
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

1 DESCRIPTION OF SOURCE FILES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

2 PERIPHERAL INITIALIZATION AND START-UP SEQUENCE . . . . . . . . . . . . . . . . . 6

3 MAIN PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

4 THE THREE PRINCIPAL INTERRUPT ROUTINES (C, D AND Z) . . . . . . . . . . . . . . 12

4.1 FIRST PART OF C AND D INTERRUPT ROUTINES . . . . . . . . . . . . . . . . . . . . 12

4.2 BODY OF C INTERRUPT ROUTINE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

4.3 SYNCHRONOUS MODE PART OF C INTERRUPT ROUTINE . . . . . . . . . . . . . 14

4.4 FIRST PART OF Z AND R INTERRUPT ROUTINES . . . . . . . . . . . . . . . . . . . . 16

4.5 BODY OF Z INTERRUPT ROUTINE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

4.6 TRANSITION FROM SYNCHRONOUS TO AUTO-SWITCHED MODE . . . . . . 18

4.7 AUTO-SWITCHED MODE PART OF C INTERRUPT ROUTINE . . . . . . . . . . . 19

4.8 LAST PART OF C INTERRUPT ROUTINE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

5 SPECIAL FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

5.1 R INTERRUPT (MTIM TIMER RATIO CHANGE) . . . . . . . . . . . . . . . . . . . . . . . 22

5.2 SOFTWARE DEMAGNETIZATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

5.3 O AND E INTERRUPT ROUTINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

6 SUMMARY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

31

2/31

2
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

The Start/Stop order of the motor is given by pin PB0 on the microcontroller board in the
Kanda Kit. Do not forget to unplug the communication cable from the microcontroller board to
ensure the correct behaviour of pin PB0.
This software (except for the declaration of motor parameters) is for the Current mode and
Closed Loop Driving mode in the third stage of the ST7MTC2 Motor Control Evaluation Kit.
Figure 1. BLDC Control Strategy

Start Motor in Synchronous


mode

No End of Forced
Synchronous
Mode?

Yes

No Back-EMF Yes
Zero crossing?

Motor in Auto-switched
Mode

No End of
Ramp up?

Yes Yes End of No


Stabilization
Phase?
Valid Speed Loop

No Target Yes
Speed
crossing?
Allow Speed Loop

Yes No
Stop?

Stop

3/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

Figure 1 gives a general overview of the control software after receiving an order to start the
motor.
After the start order, the motor begins to run in Forced Synchronous mode. Forced Synchro-
nous mode is the first part of Synchronous (switched) mode. It is the motor start-up se-
quence. Please refer to Application Note 1276 BLDC Motor Start Routine for ST72141 Micro-
controllers for details concerning the start-up phase of the motor. During Synchronous
(switched) mode, the rotor is set to a given position (pre-positioning phase) and then de-
creasing step times are imposed in order to accelerate the motor and to detect the first Back-
EMF zero crossing event (Z event). The current is also imposed. This succession of de-
creasing step times is referred to as the motor ramp-up.
Forced Synchronous mode corresponds to the first few steps of the ramp-up before the Z
event interrupt is enabled. The number of steps in Forced Synchronous mode (with Z inter-
rupts disabled) is chosen by the software programmer.
After these few steps in Forced Synchronous mode, the Z event interrupt is enabled and the
motor is still in the ramp-up, or start-up, phase and switches to Synchronous (switched) mode.
The step time and current are still imposed. A Z event has not yet been detected.
If Z event is not detected before the end of the ramp-up, the motor is stopped.
When the first Z event is detected in Synchronous (switched) mode, the user can choose to
have 2 or more consecutive Z events detected before setting the motor in Auto-switched run-
ning mode.
Once the motor is in Auto-switched mode, it must wait for the end of the stabilization phase be-
fore entering the speed regulation loop. For example, in Closed Loop driving mode, the stabi-
lization phase consists of a few steps between the first step in Auto-switched mode and en-
tering the speed regulation loop. The number of steps in the stabilization phase is chosen by
the software programmer.
In summary, after receiving the start order, the motor starts in Forced Synchronous mode,
then enters Synchronous (switched) mode when the Z event interrupt is enabled by the soft-
ware. The motor will then enter Auto-switched mode when 2 or more consecutive Z events are
detected.

4/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

Figure 2. Start-up Sequence Summary Example


Synchronous (switched) mode Auto-switched mode
Forced Synchronous mode Synchronous (switched) mode

Pre-positioning Phase Ramp-up Phase Stabilization Speed Regulation Loop


Phase

Start
Detection of 2 or more
Order Z event interrupt enabled consecutive Z events

In this application note, the flowchart illustrates the start-up sequence of the motor and the
transition between Synchronous and Auto-switched modes. First, the three main interrupt rou-
tines are described (C, D, Z events), and then other features are described in Section 5 of this
document.
Other special cases are presented at the end of this application note.
Note: All the names of the software routines presented in this document are strictly the same as in the
code generated in the ST7MTC2 kit.

5/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

2 PERIPHERAL INITIALIZATION AND START-UP SEQUENCE


Figure 3. ST72141 Start-up Sequence Flowchart

Reset

Initialization of
Peripheral

Basic Initialization of
Motor Control Peripheral

Start

No
START Order?

Yes

Motor Control Peripheral


Initialization

Start Motor in
Synchronous mode and
Enable IT on C
for Step update

Main
Program

Before starting the motor, a basic initialization of the peripheral is performed by the software
(Figure 4). Once the peripheral is initialized, the motor waits for the start order.
When the start order is received, the Motor Control (MTC) peripheral is initialized (Figure 5)
according to the selected driving mode and motor parameters. The motor then starts in Syn-
chronous (switched) mode and the software switches to the main program (Figure 7).
In Forced Synchronous mode, only the C (commutation) event interrupt is enabled. After
switching into Synchronous (switched) mode, the Z event interrupt is also enabled. The D

6/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

(demagnetization) event interrupt can be disabled in both Forced Synchronous and Syn-
chronous (switched) modes. Otherwise, it is software demagnetization only.
Figure 4. Basic Initialization Phase of the Motor Control Peripheral

Basic
Initialization

Reset MTC Peripheral & MCOx in Hiz

MCES Pin
(Emergency Stop)?
Yes
No

MPOL Register
Select "OFF" time
and Channel Polarity

MPHST Register reset


Set PWM Frequency & MTIM Clock with
MPRSR Register

MCRA Register
Clock disable
(MOE =1 & DAC =1)
MCOx in "OFF" state

Figure 4 shows the basic initialization phase of the peripheral performed by the software be-
fore the detection loop for the motor start-up order can be enabled.
The following actions takes place during the basic initialization phase:
The Motor Control Peripheral is reset (by setting a control bit in the MCRA register).
All outputs are set to high impedance and to OFF states.
The channel polarity is selected (by the MPOL register).
The internal clock frequency (current mode) is selected as well as the MTIM internal 8-bit
timer ratio with the MPRSR register.
The clock is disabled.

7/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

Once the basic initialization is completed and the motor start order is detected, the motor con-
trol peripheral is initialized according to the selected driving mode and motor parameters.
Figure 5. Motor Control Peripheral Initialization Phase

MTC Peripheral
Initialization

Reset all Flags and Status_step variable

MPAR Register Select


Z & D edge polarity
Channel to read Z
Channel Parity

Load MCOMP with first step time


Load MDREG with Software Demagnetization time

Initialize MCRA / MCRB


and output first step word

Set IREF and start MTIM

No End of Yes
Pre-positioning
Phase?

Ramp-up

When the start order is received:


All the flags present in the RAM variables are reset, as well as the status_step variable
(RAM variable).
The pre-positioning phase is executed in order to place the rotor in a known position. Refer
to Application Note 1276 for more information.
The motor starts in Synchronous (switched) mode according to the step time in the
MCOMP register due to the acceleration ramp table.
The step time is imposed by the ramp table in the software. (The ramp table is the succession
of decreasing step times used to accelerate the motor during the start-up sequence). The first
step time is loaded in the MCOMP register (in Synchronous mode, the MCOMP register con-
tains the step time).

8/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

The MDREG register is loaded with the Software Demagnetization time. In Synchronous
(switched) mode, all the Demagnetization (D) events are simulated by software. There are no
hardware End of Demagnetization events in Synchronous (switched) mode.
The Z event and D event edge polarities are selected using the ZVD and CPB bits.
The MCRA and MCRB registers are initialized when the driving mode (current or voltage
mode with or without sensors) is selected and all the motor parameters are downloaded in the
software.
The reference current or voltage for the ramp table is set and the internal 8-bit timer is started
by enabling the clock.
In summary, once the Pre-positioning phase is completed, the software goes through the
ramp table (ramp-up phase shown in Figure 6) using the decreasing imposed step times to ac-
celerate the motor.
Figure 6. Synchronous Starting Ramp-up

Ramp-up

Prepare next Step Configuration


and update the MISR Register
for clock radio action on C event.

Load preload Register for next C event


MPHST with phase word
MCRB with Phase comparator edge,
Demagnetization Mode and PWM orientation

Enable IT on C event

Figure 6 shows what the software does in each step during the ramp up. As the MPHST and
MCRB registers have preload registers (see Application Note 1082), in each step the data for
the next step is prepared and entered in the preload register. This data will be taken in account
and loaded in the active registers when the C event is detected.
In Forced Synchronous mode, only the C event interrupt is enabled. After a few steps in the
ramp table, the Z event interrupt will also be enabled.

9/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

3 MAIN PROGRAM
Figure 7. Main Program Flowchart

Main Program

Yes
STOP order?

Stop the MOTOR


No
No
Start Auto-Switched
Mode?

Yes One Mechanical No


Rotation Completed?

Compute?
Yes

No
Compute the New
Reference Current to
reach the Targeted Speed

Yes
Update
Update IREF
IREF?

No

Figure 7 shows what is done in the main program. The main program continuously checks for
the stop order. This is the only operation that is carried out until the motor enters the Auto-
switched mode. If the motor is in Synchronous (switched) mode, the main program will be in-
terrupted by a C event and a Z event. A D event interrupt is not enabled in Synchronous
(switched) mode.
If the motor is in Auto-switched mode, the software waits until one mechanical rotation is com-
pleted (this is the stabilization phase, where the number of steps of the stabilization phase is
decided by the software programmer). In Auto-switched mode, the main program can be inter-

10/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

rupted by all the events enabled by the software programmer. This will be described in Section
5.2 of this document.
The dotted line indicates what is done in the main program in Closed Loop speed regulation
mode. After the stabilization phase, the main program checks if there is a need to compute
and update a new reference current or voltage in order to keep the motor running at the target
speed fixed by the user.
If the motor is still in Synchronous (switched) mode, the software waits for a C event interrupt
(Figure 8) before computing the reference current or voltage.

11/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

4 THE THREE PRINCIPAL INTERRUPT ROUTINES (C, D AND Z)

4.1 FIRST PART OF C AND D INTERRUPT ROUTINES


When a C event or a D event occurs, the software reads the MISR register and stores the in-
terrupt flags in a RAM variable (step_isr) before resetting these flags in the MISR register.
Figure 8. C Event and D Event Interrupt Routines

C or D
IT

Read MISR

Memorize CI & DI bit in step _isr


Reset these flags in MISR

End_IT_CD

Yes
CI set?

No

Yes
DI set?

Is_C_IT

Reset DI in step_isr No

Reset DI flag in
MISR register

IRET

The RAM variable is then read in order to know what flags have been set. If the commutation
flag is set (CI flag), the software enters the C interrupt routine (Is_C_IT shown in Figure 9). If
this flag is not set, the software checks if the End of Demagnetization flag is set (DI flag). If the
DI flag is set, the software enters the End of Demagnetization event interrupt routine. In this in-
terrupt routine, only the flag reset operation is performed. Afterwards, the software returns to
the main program and waits for an interrupt. Figure 9 shows what is done when the commuta-
tion event interrupt flag (CI) is set.

12/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

4.2 BODY OF C INTERRUPT ROUTINE


Figure 9. Overview of the C Event Interrupt Routine

Is_C_IT

temdreg = MDREG
temcomp = MCOMP
MDREG = MCOMP-2

Reset CI and ZI in step_isr


Reset R-plus flag

Update MPHST & MCRB


preload registers

Yes No
Auto-switched
Mode?

C-action-autosw

Yes First Auto-switched


Step?

Set-ki-autosw No

Yes
Last Switched Step?

Val-autosw No

Synchronous
Mode

Regardless of the motor driving mode or sequence during a C event interrupt routine, the De-
magnetization time in the MDREG register is stored in a RAM variable. The value of the
MCOMP register is also stored. Then, to avoid a parasitic Demagnetization when the interrupt
routine is executed, a value less than the value in the MCOMP register is loaded in the
MDREG register (meaning that the internal timer has already at that time a value greater than
the value loaded in the MDREG register. This will prevent a Demagnetization interrupt from
occurring while this part of the interrupt routine is executed).
The interrupt flags are reset and the MCRB and MPHST preload registers are updated to pre-
pare the data for the next C event.

13/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

Once the targeted number of consecutive Z events (set by the software programmer) is de-
tected in Synchronous (switched) mode, the fact that the motor is in its last step in Synchro-
nous (switched) mode is memorized (Figure 12).
When the next C event is detected, the software will memorize that the motor is in the first step
in Auto-switched mode.
Then the C event interrupt routine is sub-divided to handle the several cases when the inter-
rupt occurs:
The motor is still in synchronous (switched) mode
The motor is on the last step in synchronous (switched) mode
The motor is in the first step in Auto-switched mode
The motor is already in Auto-switched mode
Lets take each case independently.
In the first case, the motor is in Synchronous (switched) mode when a C event is detected.
When this occurs, the software enters the C event interrupt routine and goes to the Synchro-
nous (switched) mode routine (Figure 10).
In the second case, the motor is in its last step in Synchronous (switched) mode (position
memorized during the previous Z interrupt routine) when the C event interrupt is detected.
When this occurs, the software goes to the val_autosw routine (Figure 13). In this routine, the
software memorizes that the motor is in its first step in Auto-switched mode.
In the third case, the motor is in its first step in Auto-switched mode when the C event interrupt
is detected. When this occurs, the software goes to the Set_ki_autosw routine (Figure 14).
In the last case, the motor is in Auto-switched mode when the C event interrupt is detected.
When this occurs, the software goes to the C_action_autosw routine (Figure 14).

4.3 SYNCHRONOUS MODE PART OF C INTERRUPT ROUTINE


In the event that the motor is still in Synchronous (switched) mode when the C event interrupt
occurs, the software goes to the Synchronous mode routine (Figure 10).
When a commutation (C) event occurs, the motor is in Synchronous (switched) mode, so the
software must enter the synchronous routine in the C event interrupt routine.
The MDREG, MCOMP and MISR registers are updated for this step. The data for the next C
event is prepared and memorized in RAM variables. The data will be loaded in the preload
register one step before it is used.
The software checks if the motor is at the end of the ramp table. If this is the case, the motor
must be stopped because it is not yet in Auto-switched mode. Normally, the motor enters
Auto-switched mode after only a few steps.

14/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

Figure 10. Commutation Interrupt in Synchronous (switched) Mode

Synchronous
Mode

MDREG = mem-mdreg
MCOMP = mem-mcomp
MISR = mem-misr

Prepare Data for next C event


mem-phst, mem-mcrb

Yes No
End of Ramp-up?

STOP Yes
End of Forced
Synchronous
mode?

Z IT enabled
No

Load memory of register


mem-comp with step time
mem-ratio with clock
mem-mdreg with soft demagn time

No
Z event?

Yes
No
Consecutive Z?

Yes

Clear Z counter Increment Z counter

IRET

If the motor is not at the end of the ramp table, the software checks if it is at the end of Forced
Synchronous mode. If this is the case, the Z event interrupt is enabled.
All the register values are memorized by the software which also checks if a Z event has oc-
curred in the previous step. When a Z event is detected, a counter is incremented until the
number of consecutive Z events reaches the target number set by the software programmer.
When this number is reached, the motor switches to Auto-switched mode and the software re-
turns to the main program (Figure 7) and waits for the next interrupt.

15/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

In the event that the motor is in Synchronous (switched) mode and the Z event interrupt has
been enabled, the next interrupt in the main program could be a Z event and the software will
go through the Z event interrupt routine (Figure 11).
Note that we are assuming for the moment that we are in Synchronous (switched) mode,
therefore only the C and Z event interrupts have been enabled by software.

4.4 FIRST PART OF Z AND R INTERRUPT ROUTINES


Figure 11 shows the beginning of the R (Ratio) and Z (Back- EMF zero crossing) interrupt rou-
tines. These routines read the interrupt flags, store them in a RAM variable and then reset the
flags. If the R event (ratio) flag has been set, the software enters the R event interrupt routine
depending on whether it is an R- or an R+ event. This is explained in Section 5 at the end of
this application note (Figure 17 and Figure 18). If the Z event flag (ZI) has been set in the
MISR register, the software goes through the Z event interrupt routine (BEMF_Z) (Figure 12).
Otherwise, the software returns to the main program and waits for the next interrupt.
Figure 11. R (Ratio) and Z (Back-EMF) Interrupt Routine

R or Z IT

Read MISR

Memorize RPI, RMI & ZI bits in step _isr


Reset these flags in MISR

Yes No
RIM set?

Valid RPI & RMI in step_isr


IT_mng

No
RMI set?

Yes No
RPI set?

Z_55
Yes No
ZI set?
Timer_ovf
Yes

BEMF_Z
IRET

16/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

4.5 BODY OF Z INTERRUPT ROUTINE


In Auto-switched mode, no actions are performed in the Z event interrupt routine. An interrupt
is generated and the software just returns to the main program (Figure 7). If the motor is still
in Synchronous (switched) mode, the zero crossing times (current and previous) are memo-
rized in two RAM variables and the counter of consecutive Z events is incremented. If the
number of consecutive zero-crossing events is equal to the target number fixed by the soft-
ware programmer, the software memorizes that the motor is in its last step in Synchronous
(switched) mode.
Figure 12. Z Event Interrupt Routine

BEMF_Z

Restore Ratio update

Yes
Auto-switched mode?

No

BEMF_mem = BEMF_n

BEMF_n = MZREG

Increment nbemf

No
nbemf = target?

Yes

Z event is centered on last step in


Synchronous mode
MCOMP = MZREG *2

Memorize last step in Synchronous mode

No
Closed loop mode?

Yes
Initialize all closed loop parameter

IRET
VR02141K

17/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

The Z event time is centered on the current step, meaning that the value entered in the
MCOMP register (step time in Synchronous mode) is twice the value in the MZREG register.
If the motor is in Closed Loop mode (speed regulation), the Closed Loop parameters are ini-
tialized at this point in the program.
The software then returns to the main program (Figure 7) and waits for the next interrupt which
will be a C event. As shown in Figure 9, if the software has memorized that the motor is in its
last step in Synchronous (switched) mode, the program will enter the Val_autosw routine
when the next C event is detected (Figure 13).

4.6 TRANSITION FROM SYNCHRONOUS TO AUTO-SWITCHED MODE


Figure 13. Val_autosw Routine

Val-autosw

MDREG = mem-mdreg
MCOMP = $FF

Set SWA bit in MCRA

Memorize first auto-switched step

Restore demagnetization selection


for first auto-switched step

Enable IT on C, D, Z, E and R

Prepare Data for next C event

IRET

In this case, the motor is at the last step of the Synchronous (switched) mode and the software
has entered the corresponding C event interrupt routine (see Figure 9). Auto-switched mode
is enabled and the maximum value is loaded in the MCOMP register to prevent parasitic C
events from occurring during the enabling routine.
The SWA bit in the MCRA register is set to enable Auto-switched mode. When this step is
completed, the internal 8-bit timer MTIM will be reset on a Z event.
The software memorizes that the motor is in its first step in Auto-switched mode.
The demagnetization selection for the first auto-switched step is restored and all the interrupts
are enabled as the motor enters Auto-switched mode.

18/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

The E event and R event interrupts are described in Section 5 of this document (see Figure
17, Figure 18 and Figure 22).
The data for the next commutation event is prepared and memorized so that it may be loaded
in the preload registers.
Once this data is stored in the preload registers, the software returns to the main program and
waits for the next interrupt which will be a D event. But as shown in Figure 8, when a D event
is detected, the interrupt routine only stores the DI bit and clears the MISCR flags before re-
turning to the main program and waiting for the next interrupt.
The next interrupt will be a Z event, but as the motor is now in Auto-switched mode (first step
in this mode), this interrupt routine does not perform any actions either (as shown in Figure
12). The software will again return to the main program and wait for the next interrupt which
will be a C event. Now, the software has memorized that the motor is in its first step in Auto-
switched mode, so as shown in Figure 9, the program will enter the Set_ki_autosw routine
(Figure 14).

4.7 AUTO-SWITCHED MODE PART OF C INTERRUPT ROUTINE


Figure 14. Commutation Event Routine (first step in Auto-switched mode)

Set-ki-autosw

Enable Auto-switched mode


Reset memory of change of ratio

MWGHT= selected Delay

C-action-autosw

Read current ratio of TIMER


bemf_n+1 = MZREG

Yes Hardware
Demagnetization?

No
Save MCOMP for next Software Demagnetization

End-C_action SDM-autosw

19/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

In this case, Auto-switched mode is enabled and the MWGHT register is loaded with the delay
coefficient. This means that the MCOMP register contains the value of the real delay (time in
each step between the zero crossing event and the next commutation event).
Note: For more information concerning the real delay value, refer to Application Note 1082.
The Z event time is memorized and then depending on the step configuration (falling or rising
edge of the end of Demagnetization event), there will be a software or a hardware Demagnet-
ization. Software Demagnetization is a special case that is described in more detail in Section
5.2 of this document (Figure 19 and Figure 20). If there is a hardware Demagnetization, the
software enters the End_C_action routine where the data for the next commutation event is
prepared. The software then goes to the C_action_end routine (Figure 15).
Note: For more information concerning the step configuration, refer to Application Note 1130.

4.8 LAST PART OF C INTERRUPT ROUTINE


Figure 15. C_action_end Routine

C_action_end

Yes No
Closed Loop?

End of stabilization after Yes


entering Auto-switched mode?
(Step_cpt = $80)

No

Step_cpt = Step_cpt - 1

No
Step_cpt = 0?

Yes

Step_cpt = $80 End_IT_CD

Crossing

In this case, the execution of the routine depends on whether the motor is running in Open
Loop or Closed Loop mode. If the motor is running in Closed Loop (speed regulation), the soft-

20/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

ware checks if the stabilization phase is completed (fixed number of steps in Auto-switched
mode before entering the speed regulation loop).
If the stabilization phase is not finished, the value of the counter for the number of steps in
Auto-switched mode is incremented and the software goes to the End_IT_CD routine (Figure
8) before returning to the main program.
If the stabilization phase is completed, the software goes to the crossing routine (Figure 16) to
check if the target speed of the motor has been crossed.
If the motor is running in Open Loop mode, the software just exits the C interrupt routine.
Note that the number of steps for the stabilization phase is fixed by the software programmer
in a RAM variable. Step_cpt acts like a flag and $80 is an arbitrary value set by the software
programmer.
Figure 16. Crossing Routine

Crossing

No
Target speed crossing?
(Crossing = $80)

Yes

Yes
Speed Update?

No

No
End of Average of
Step time?

Yes

Reset Average memory

End_IT_CD

In this routine, the software checks if the motor has already crossed the target speed. If the
motor has not crossed the target speed, the software exits the C interrupt routine. (This routine
is only available in Closed Loop mode.)
If the motor has crossed the target speed, the software checks if the speed has to be updated
or if the step time average has to be computed by the speed regulation subroutine. After-
wards, the software returns to the main program.

21/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

As the motor is now in Auto-switched mode, the same path is always followed by the software:
Main program: software waits for an interrupt
C event interrupt is detected: the software enters the C_action_autosw (Figure 14) routine
then returns to the main program
D event interrupt is detected: nothing is done in the software
Z event interrupt is detected: nothing is done in the software on a Z event in Auto-switched
mode
However, C, D and Z events are not the only events that can provoke an interrupt. In Auto-
switched mode, R (ratio) events, E (emergency stop) events and O (delay multiplication over-
flow) events are all able to generate interrupts. These cases and others such as software De-
magnetization and setting the carry bit after a computation are all managed by the software.
They are described in the last part of this document.

5 SPECIAL FEATURES

5.1 R INTERRUPT (MTIM TIMER RATIO CHANGE)


There are two types of R event interrupts; R+ event and R- event. The type of interrupt de-
pends on the value of the MTIM timer counter when the event is detected.
Note: For more information concerning R event interrupts, refer to Application Note 1082.
If a Z event is detected while the MTIM timer counter is between 55h and FFh, the event is
processed normally.
If the timer reaches FFh before the Z or D event is detected, an R+ event (timer overflow) oc-
curs. In this case, the clock needs to be slowed down, so the ratio is increased.
If a Z event is detected before the timer has reached the value 55h, an R- event (timer under-
flow) occurs. In this case, the clock needs to be accelerated, so the ratio is decreased.
Figure 17 and Figure 18 show what is done by the software when R+ or an R- event occurs.
As shown in Figure 11, when an R event is detected, the software checks the interrupt flags to
determine if it is an R+ or an R- event.
If RMI flag is set, it is an R- event and the software goes to the Z_55 routine (Figure 17).
If RPI flag is set, it is an R+ event and the software goes to the Timer_ovf routine (Figure 18).

22/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

Figure 17. Z_55: Internal 8-bit Timer Underflow

Z_55

SLL of mem_mcomp
for computation of Software Demagnetization

Yes Carry set?

No
mem_mcomp = $FF

IT_mng

Figure 17 shows what takes place in the event of a timer underflow (an R- event). For all prac-
tical purposes, the timer ratio is automatically decreased by the microcontroller. Therefore, all
the values are multiplied by two for the current step in order to avoid computation errors.
This means that the previous Zn and Z times are multiplied by 2, as well as the Demagnetiza-
tion time value in the MDREG register.
If the carry is set during the computation, the maximum value is stored in the MCOMP register.
Then the software returns to the IT_mng routine (Figure 11), checks again for interrupt flags
and returns to the main program and waits for another interrupt.
Figure 18 shows what is done when a timer overflow occurs (an R+ event). For all practical
purposes, the timer ratio is automatically increased by the microcontroller. Therefore, all the
values are divided by two for the current step in order to avoid computation errors.
This means that the previous Zn and Z times are divided by 2, as well as the Demagnetization
time value in the MDREG register.
The timer is reset to its middle value, i.e. 7Fh.
After division, if the value in the MCOMP register is equal to zero, the software stores a min-
imum value of 1 in the register.
Then the software checks again for the R+ event flag and returns to the IT_mng routine
(Figure 11).

23/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

Figure 18. Timer_ovf: Internal 8-bit Timer Overflow

Timer_ovf

SRL of mem_mcomp
for computation of Software Demagnetization

Yes
mem_mcomp = 0?

mem_mcomp = 1
No

Yes
Flag R_plus = 0?

No

R_plus = R_plus - 1

No
Flag R_plus = 0?

Yes
MDREG = mem_mdreg

IT_mng VR02140Q

5.2 SOFTWARE DEMAGNETIZATION


In the software included with this application note, if Auto-switched mode is enabled, every
second step will use software demagnetization. Note that this is a software example and that
the fact that every second step uses software demagnetization can be changed.
Therefore, each step is checked by software for hardware or software demagnetization (set
using the HDM or SDM bits in the MCRB register). This is shown in Figure 14.
Figure 19 and Figure 20 show what is done by the software in the event of software demag-
netization.
Figure 19 shows the first part of the software demagnetization. In the event that a software de-
magnetization takes place in the current step (step n), a hardware demagnetization must have
taken place in the previous step (step n-1). Therefore, Dn-1 was a hardware demagnetization.

24/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

The values in the MDREG (n-1) register for the hardware demagnetization and the
MCOMP(n-1) register for the computed delay have been memorized.
The value in the MDREG (n-1) register represents the time between the previous Z event (Z n-
2) and the End of Demagnetization event at step n-1 (Dn-1).
The real hardware demagnetization time is the time between the commutation event (n-1) and
the End of Demagnetization event (n-1). So, the first thing done by the software is to compute
the value of the real hardware demagnetization (HDM) event from the previous step:
HDM (n-1) = MDREG(n-1)-MCOMP(n-1)
Then the software checks if this value is greater than 0. If not, a minimum value of 1 is set.
Then, to compute the software demagnetization time for the current step (step n), the hard-
ware Demagnetization time is multiplied by a correction factor (chosen arbitrarily by the soft-
ware programmer) to ensure that the software Demagnetization time for the current step will
be greater than the hardware demagnetization time from the previous step (for safety pur-
poses to prevent the End of Demagnetization event from occurring too soon):
SDM (software Demagnetization value) = HDM*1.25
Then the software checks if this value is greater than 255. If yes, this value is forced to 255.
The software then checks if the value of the software Demagnetization time is greater than the
time needed to process the interrupt routine (IT_time). If not, this interrupt processing time is
set as a minimum value.
This is done because if the value in the internal 8-bit timer is greater than the value of the soft-
ware Demagnetization when the routine is completed, the End of Demagnetization event will
never occur since the value of the software Demagnetization would have been already
reached by the internal timer before the end of the routine.
Then, the value of the delay between the Zn-1 event and the next commutation event Cn is
added in order to obtain the time between the Zn-1 event and the software End of Demagnet-
ization event.
If the carry has been set by these computations, the software goes to the carry-set routine
(Figure 21). Otherwise, the software Demagnetization routine continues (Figure 20).

25/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

Figure 19. Software Demagnetization (First Part)

SDM-autosw

HDM = MDREG(n-1) - MCOMP (n-1)

No HDM > 0?

Dn-1 Dn HDM =1
Yes

SDM =HDM * 1.25


Cn-1
MCOMP(n-1) Cn
Yes SDM > 255?
HDM
SDM =255
No

MDREG(n-1) No
SDM > IT_time
Zn-2 Zn-1 Zn Update?
SDM =IT_time
Yes
IT_time_low
MDREG(n-1)-MCOMP(n-1)=HDM
SDM =SDM + MCOMP (n)

Yes
Carry?

No
Carry_set

The software adds another correction factor to the software Demagnetization time corre-
sponding to the time needed to load the register. If the carry has been set, the program goes
to the carry_set routine. Otherwise, the actual value for the software End of Demagnetization
event is memorized and the software checks if this value is greater than the current value of
the MTIM timer.
If the value set for the software End of Demagnetization event is greater than the current value
of the MTIM timer, a value greater than that of the MTIM timer is set for the software Demag-
netization time.

26/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

Figure 20. Software Demagnetization (Second Part)

SDM =SDM + (timer_table)

Yes
Carry?

Carry_set No

mem_mdreg = SDM

Yes No
MTIM > SDM?
SDM = MTIM + (timer_table)

No
Carry?

Yes mem_mdreg = SDM

Carry_set
Read MISR

Yes
Is R+?

Reset RPI in MISR No


Write MDREG
SRL MCOMP

End-C_action
Is_C_IT

If the value set for the software End of Demagnetization event is less than the current value of
the MTIM timer, the software checks if the flag for an R+ event is set.
If the flag for an R+ event is set, the flag is reset and the software returns to the beginning of
the C interrupt routine. Otherwise, the value is written in MDREG register, then the software
goes to the End_C_action routine to prepare the data for the next C event and then returns to
the main program.
If the carry has been set during the computation for the software End of Demagnetization
event, the software enters the carry_set routine as shown in Figure 21.

27/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

Figure 21. Carry Set Routine Flowchart

Carry_set

No
Ratio = $0F?

Increment flag R_plus


SRL A Yes
A = A + $7F

Yes
Carry?

No

mem_mdreg = A

Read MTIM mem_mdreg = $FA

Yes Write MDREG


MTIM > $7F?

MDREG = $70
No

MDREG = MTIM - 2

End-C_action

If the carry has been set, the software End of Demagnetization event will occur after the time
the MTIM timer would have reached the value FFh. This will cause an overflow of the MTIM
timer (an R+ event). Therefore, the software checks if the ratio of the MTIM timer is set to the
maximum value.
If the ratio of the MTIM timer is set to the maximum value, an arbitrary value is memorized for
the software End of Demagnetization event and is written in the MDREG register.
If the ratio of the MTIM timer is not set to the maximum value, the R_plus flag is incremented,
meaning that the overflow will occur during the software Demagnetization. To prevent this
from occurring, the clock must be slowed down, i.e. the ratio must be incremented. The value
of the ratio is updated to the new future ratio by dividing by 2 the value for the software De-
magnetization. Then, when the ratio changes, the MTIM timer is reset to its middle value
(7Fh), which is added to the software Demagnetization value. This new value is then memo-
rized in the mem_mdreg variable and the MTIM timer value is read. To ensure that an End of
Demagnetization event will not take place before the ratio change (when the R+ event will

28/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

occur), a value lower than the MTIM value is written in the MDREG register. The next interrupt
will be an R+ event. At that time, the MDREG register is written.

5.3 O AND E INTERRUPT ROUTINES


Figure 22. Multiplier Overflow and Emergency Stop Interrupt Routine

O or E
IT

Read MISR

Memorize OI & EI bit in step _isr


Reset these flags in MISR

Yes
OI set?

No

Yes
EI set?

No
Reset OI in step_isr Reset Reference
Current

Permanent Waiting
Loop with Blinking LED

IRET

If a multiplication overflow is detected when computing the delay between the zero crossing
event and the next commutation, nothing is really done by the software. The interrupt flag is
reset and the software returns to the main program.
For the emergency stop interrupt, the reference current is reset and the software enters a per-
manent loop that waits for the end of the emergency stop signal.

29/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

6 SUMMARY
Figure 23. Software Overview
Case: 2 consecutive Z events are required to enable Auto-switched mode.

Z counter =1
Z Event Interrupt At next interrupt C,
is enabled go back to main program. First step in Auto-switched mode. Wait for C6.
Restore
C1 C2 C3 C4 C5 Z3 right Z4 Z5 Z6
WEIGHT

Z1 MZREG Z2 Ds D

C6 C7

MCOMP MCOMP MCOMP


with the with the
Forced Synchronous mode 1st Z interrupt is detected. default Ki right delay
Z Interrupt is not allowed nbemf is not equal to target number.
Return to the main program.
If it is at first a soft demagnetization,
we compute the value with previous
Go back to the main 2nd Z interrupt is detected. MCOMP (first time with the default
program, waiting for Z event counter = target number. delay coefficient)
the next interrupt. Last step in Switched mode.
We change MCOMP to MCOMP=MZREG*2
Go back main program and wait for next C interrupt (C5).

Synchronous mode Auto-switched mode

Figure 23 shows how the software behaves in the start-up sequence, when the motor is
passing from Synchronous mode (switched mode) to Auto-switched mode. This figure illus-
trates the case where the software programmer wants 2 consecutive Z events before enabling
Auto-switched mode and 3 steps in Forced Synchronous mode.
At C1, the motor is in Forced Synchronous mode. In this phase, the Z event interrupt is disa-
bled. At the end of Forced Synchronous mode (set by software), the Z event interrupt is ena-
bled (C3). The software then returns to the main program and counts the number of consecu-
tive Z events detected.
When the second consecutive Z event is detected (Z2), the target number of consecutive Z
events (set by software) is reached. Z2 is centered on the current step and the software mem-
orizes that this is the last step in Synchronous mode.
At the following step, the motor enters Auto-switched mode and the software memorizes that
it is the first step in this mode and the MTIM timer is now reset on the Z event and the D event
interrupt is enabled.
Note that during all steps in Synchronous mode, the D event interrupt is not enabled and all
End of Demagnetization events are software D events.

30/31
ST72141 BLDC MOTOR CONTROL SOFTWARE AND FLOWCHART EXAMPLE

"THE PRESENT NOTE WHICH IS FOR GUIDANCE ONLY AIMS AT PROVIDING CUSTOMERS WITH INFORMATION
REGARDING THEIR PRODUCTS IN ORDER FOR THEM TO SAVE TIME. AS A RESULT, STMICROELECTRONICS
SHALL NOT BE HELD LIABLE FOR ANY DIRECT, INDIRECT OR CONSEQUENTIAL DAMAGES WITH RESPECT TO
ANY CLAIMS ARISING FROM THE CONTENT OF SUCH A NOTE AND/OR THE USE MADE BY CUSTOMERS OF
THE INFORMATION CONTAINED HEREIN IN CONNEXION WITH THEIR PRODUCTS."

Information furnished is believed to be accurate and reliable. However, STMicroelectronics assumes no responsibility for the consequences
of use of such information nor for any infringement of patents or other rights of third parties which may result from its use. No license is granted
by implication or otherwise under any patent or patent rights of STMicroelectronics. Specifications mentioned in this publication are subject
to change without notice. This publication supersedes and replaces all information previously supplied. STMicroelectronics products are not
authorized for use as critical components in life support devices or systems without the express written approval of STMicroelectronics.
The ST logo is a registered trademark of STMicroelectronics
2001 STMicroelectronics - All Rights Reserved.
Purchase of I2C Components by STMicroelectronics conveys a license under the Philips I2C Patent. Rights to use these components in an
I2C system is granted provided that the system conforms to the I2C Standard Specification as defined by Philips.
STMicroelectronics Group of Companies
Australia - Brazil - Canada - China - Finland - France - Germany - Hong Kong - India - Israel - Italy - Japan
Malaysia - Malta - Morocco - Singapore - Spain - Sweden - Switzerland - United Kingdom - U.S.A.

http://www.st.com

31/31

Anda mungkin juga menyukai