Anda di halaman 1dari 3

6/6/2017 FunctionexpansionsforET200SPinterfaceandI/OmodulesID:101096918IndustrySupportSiemens

Entrytype:Productnote,EntryID:101096918,Entrydate:09/09/2014 (0)
Rate

FunctionexpansionsforET200SPinterfaceandI/Omodules
Entry Associatedproduct(s)


New firmw areversionsorfunctionexpansionsarenow availablefordifferentinterfaceandI/Omodules.

ET200SPinterfacem odules

Properties IM1556PNHigh IM1556DPHighFeature


Feature (6ES71556BU000CN0)
6ES71556AU000CN0 BundleMLFB:6ES71556BA00
0CN0
New firm w areversion V3.0.0 V3.0.0
Compatibility Fullycom patible Fullycom patible
from V1.0.0 from V1.0.0
Maybeupdated Yes,from V1.0.0 Yes,from V1.0.0
Configuration GSDML GSD
(configurationandparameterization)via or or
HSPforSTEP7V5.5 HSPforSTEP7V5.5SP4
SP3 or
or TIAPV13SP1
TIAPV13update4
Configuringofshareddevice,MSI,MSO from EACHV13 No
update4
StationexpansionviaETconnection Yes Yes
(BaseUnitBUSendandBusAdapterBASend)
SingularNAPS2systemredundancy Yes No
DarkBaseUnitscannow alsobepluggedinto Yes Yes
Slot1
BaseUnittypeB1(ACmodules)
BaseUnittypeD0(AIenergymeter)

New functionsfortheIM1556PNHighFeature(PROFINET)

ConnectionofET200AL
SingularsystemredundancyNAP:S2
DarkBaseUnitsarenow alsopermissibleinSlot1ofthestation(forexample,fortheAIenergymeter)

LinkstotheIM1556PNHF

Firmw aredow nload:85624387

Manual:73184046

GSDML:57138621

ConnectionofET200AL

Fromfirmw areV3.0.0,anIM1556canbeexpandedviatheBaseUnitBUSendandtheBusAdapterBASend
w ithupto16modulesofthenew IP67I/OlineET200AL.Formoredetailedinformation:SeeSalesreleaseET
200AL,entryID:92345524

Module ArticleNo.
BaseUnitBUSend 6ES71936BN000NE0
BusadapterBASend 6ES71936AS000AA0

Singularsystem redundancy:NAP:S2

Fromfirmw areversionV3.0,theET200SPinterfacemoduleIM1556PNHFcanbeconnectedviaNAPS2system
redundancytoanS7400Hsystem(fromfirmw areversionV6.0.4).Thefollow ingstationsetuprulesapplyhere:
https://support.industry.siemens.com/cs/document/101096918/functionexpansionsforet200spinterfaceandiomodules?dti=0&lc=enAR 1/3
6/6/2017 FunctionexpansionsforET200SPinterfaceandI/OmodulesID:101096918IndustrySupportSiemens
1.Themaximumdatalengthperstationw ithactiveS2redundancyis990byteseachforinputdataandoutput
data.Thelengthiscomposedof:

I/Odata,includinguserdataqualifiersthatmayhavebeenconfigured

NumberofI/Omodulesw ithexclusivelyinputoroutputdata(inbytes)

2xnumberofI/Omodulesw ithinputandoutputdata(inbytes)

2.ThecombinationofS2redundancyw iththeConfigurationcontrollerfunction(optionhandling)isnotsupported
w ithfirmw areV3.0.

3.PossibleI/Omodulesw ithactiveS2Systemredundanz
Withfirmw areversionV3.0,allI/Omodulescanbeusedw iththeexceptionofPROFIsafemodulesandthestation
expansionw ithETconnectionforconnectingtheET200AL

New functionsfortheIM1556DPHighFeature(PROFIBUS)

ConnectionofET200AL

DarkBaseUnitsarenow alsopermissibleinSlot1ofthestation(forexample,fortheAIenergymeter)

LinkstotheIM1556DPHF

Firmw aredow nload:85026994

Manual:73098660

GSD:73016883

I/Om odules

Thefollow ingnew functionsareintroducedw iththenew firmw areversionV1.1.0:

Supportforvaluestatus(QI,qualityinformation)
Supportforupdatew ithsignedfirmw are

Analogmodulesandtherelaymodulecanbeupgradedw iththenew functionsviaafirmw areupdatefromfirmw are


V1.0.0.Thethreedigitalmodules(DI8x24VDCST,DQ4x24VDC/2ASTandDQ8x24VDC/0.5AST)canbeupgraded
fromfirmw areV1.0.1.

I/Omodule ArticleNo. New Firm w arecanbe EntryID EntryID


firm w are upgraded Firm w are Manual
OFST8x24VDC 6ES71316BF00 V1.1.0 FromV1.0.1,FS3 98710077 59753552
0BA0
DQ4x24VDC/2AST 6ES71326BD20 V1.1.0 FromV1.0.1,FS3 98710194 59753576
0BA0
DQ8x24VDC/0.5AST 6ES71326BF00 V1.1.0 FromV1.0.1,FS3 98710722 59753588
0BA0
RQ4x24VUC230VUC/5A 6ES71326HD00 V1.1.0 FromV1.0.0 98710725 66912566
ST 0BB0
AI4xI2/4w ireST 6ES71346GD00 V1.1.0 FromV1.0.0 98710667 59768161
0BA1
AI4xU/I2w ireST 6ES71346HD00 V1.1.0 FromV1.0.0 98710721 59753624
0BA1
AQ4xU/IST 6ES71356HD00 V1.1.0 FromV1.0.0 98710697 59753612
0BA1

Functionexpansionfortheanaloginputm oduleAIEnergyMeter400VACST

Withthenew firmw areversionV2.0.0,theanaloginputmoduleAIEnergyMeter400VACisexpandedw ithtw o


new functions.ExistingEnergyMetermodulescanbeupgradedfromV1.0.0.

Parameterizablelow ermeasuringlimitofthecurrentvalues(zeropointsuppression):From20to250mA,
defaultvalue:50mA
Ifthesuppliedcurrentislessthantheparameterizedlow ercurrentlimit,thecurrentmeasuredvalueandall
https://support.industry.siemens.com/cs/document/101096918/functionexpansionsforet200spinterfaceandiomodules?dti=0&lc=enAR 2/3
dependentvariablesw illbesuppressedorsetto"0".
6/6/2017 FunctionexpansionsforET200SPinterfaceandI/OmodulesID:101096918IndustrySupportSiemens
Alluserdatavariantsalsoreceivequalifierinformationinthesecondbyte

Introductionofanadditionaluserdatavariant:BasicquantitiesofthreephasemeasurementL1,L2,L3(see
tablebelow )

Byte Assignment
0 Userdatavariant=245(F5H)
1 Qualityinformation=ObQQI3U3I2U2I1U1
2...5 Totalactivepow erL1L2L3
6...9 TotalactiveenergyL1L2L3export
10...13 TotalactiveenergyL1L2L3import
14...17 CurrentL1
18...21 CurrentL2
22...25 CurrentL3
26...27 VoltageUL1N
28...29 VoltageUL2N
30...31 VoltageUL3N

LinkstotheAIEnergyMeter400VACST

Firmw aredow nload:98709668

Manual:73098696

Additionalinform ation

ET200SPManualCollection

UnderentryID84133942 ,allET200SPmanualsw ithcurrentproductinformationandsomeselectedfunction


manualscanbedow nloadedcombinedinaPDFfile.

Thisfilecontains:

ET200SPSystemManual

Productinformation(importantinformationinadditiontothemanuals)

Functionmanualsonthetopics

Diagnostics

Communication

Analogvalueprocessing

Counting,measuringandpositiondetection

Highprecisioninput/outputw ithtimebasedIO

Interferenceproofdesignofthecontrollers

Cycletimesandresponsetimes

ET200SPCPU

S71510SP1PN

S71512SP1PN

PROFINETandPROFIBUSinterfacemodules

I/Omodules

FailsafeI/Omodules

BaseUnits

https://support.industry.siemens.com/cs/document/101096918/functionexpansionsforet200spinterfaceandiomodules?dti=0&lc=enAR 3/3