Anda di halaman 1dari 4

Stand-alone Operation Paralleled With The Utility

In stand-alone operation a generator is not If a generator is paralleled with the utility grid
connected with other generators or the utility. and it is considered as an infinite bus, the utility
As an isolated unit it supplies power to all grid will determine the generator frequency,
connected load. Examples are emergency speed and voltage. An example is an industrial
generators, aggregates or portable diesel generator used for cogeneration. In practice
generator sets. such an engine generator set can not change
the frequency, but it can slightly change the
generator terminal voltage.

Stand-alone Operation the governor and voltage


regulators determine frequency and voltage.

Features:

more / less fuel will raise / lower the


frequency (Hz) Paralleled With Utility Operation if considered as an
more / less excitation current will raise / infinite bus, the utility grid will determine the generator
lower the voltage (kV) frequency, speed and voltage.
the total load determines the generator
output power (MW, MVAr) Features:
engine fuel control options:
isochronous speed control, droop speed more / less fuel will raise / lower the
control generator active power (MW)
excitation current control options: constant more / less excitation current will raise /
voltage control, droop voltage control lower the generator reactive power (MVAr)
power management system could keep bus the utility determines the frequency (Hz),
frequency and voltage constant if droop speed (rpm) and voltage (kV)
control modes are active (else not the difference between the total plant load
necessary) and the generator output power will be
load flow analysis model: Slack Bus (also imported or exported (MW, MVAr)
Reference Bus, Swing Bus) engine fuel control options: droop speed
control, base load (MW) control
excitation current control options: droop
voltage control, VAR control, PF control
power management system could keep the
imported or exported power (MW, MVAR)
or power factor constant
load flow analysis model: PQ bus (also Load
Bus), PV bus (also Generator Bus)
load flow analysis model: at least one
Island Operation generator (or a fictive untility) must be slack
bus, the other generators may be PQ or PV
In island operation a generator is connected buses
with other generators, but not with the utility.
As an isolated system the generators supply all Note that cross-current compensation is
power to the connected load. Examples are sometimes used to share reactive power, while
power systems on ships, on offshore platforms maintaining the bus voltage constant. I prefer a
or in the desert. power management system or VAr Load Sharing
devices.

Mode Of Operation Changes


All modes of operation are possible after closing
or tripping breakers in the configuration in the
image below. During the power system
engineering, this should be taken into
consideration. I highly recommend to use
a power management system in this
Island Operation all generators together determine
frequency, speed and voltage. The total load (MW, MVAr)
configuration.
should be shared.

Features:

more / less fuel will raise / lower generator


active power and the bus frequency (MW,
Hz)
more / less excitation current will raise /
lower the generator reactive power and the
bus voltage (MVAr, kV)
the total plant load determines the sum of
the power of all generators (MW, MVAr)
engine fuel control options: droop speed
control
excitation current control options: droop Mode Of Operation Changes all modes are possible after
voltage control closing or tripping breakers.
power management system keeps the bus
frequency and voltage constant, while
sharing the load (MW, MVAr) proportional
or cost optimised over all engine generator
sets
Isochronous and Droop Speed Control
In the isochronous speed control mode the speed will return to the original speed setpoint after a load
has been applied or rejected. However in parallel operation this would cause instability as explained
above.

In the droop speed control mode the speed will decrease by a fixed percentage when the generator is
loaded from no-load to full load. This provides a stable working point for each load in case of parallel
operation.

Isochronous Speed Control speed and frequency Droop Speed Control speed and frequency will
return to speed setpoint after a load change. decrease when the load increases.

The droop slope is a fixed setting mostly between 3 and 5%. But the operator or power management
system can adjust the speed setpoint in order to:

return to the rated frequency in stand-alone operation


change the generator active power (MW) in parallel operation

Constant Voltage Control and Reactive Droop Compensation


In the constant voltage control mode the voltage will return to the original voltage setpoint after a load
has been applied or rejected. However in parallel operation this would cause instability as explained
above.

In the droop voltage control or reactive droop compensation mode the voltage will decrease by a fixed
percentage when the generator is loaded from no-load to full load. This provides a stable working
point for each load in case of parallel operation.
Constant Voltage Control voltage returns to the Droop Voltage Control voltage will decrease if the
voltage setpoint if reactive load changes. reactive load increases.

The droop slope is a fixed setting mostly between 2 and 4%. But the operator or power management
system could adjust the voltage setpoint in order to:

return to the rated voltage in stand-alone operation


change the generator reactive power (MVAr) in parallel operation

Anda mungkin juga menyukai