Calculation of Size of Earth Conductor

Formula Used For Calculation I 1


= k
S t

Value of earth fault current of negligible impedance which can flow


I 12.06 kA
through the protective device, in ampres
S Cross sectional area in Square millimeters ? Sq.mm
k Constant depends on material of earth strip 80 As per IS:3043 (Page-30)
t Operating time of the disconnecting device in seconds 1 Sec.

S = I x t
As per IS: 3043(Page-29)
k

= 12 x 1 x 1000

80

12 x 1.000 x 1000
= = 150.75 Sq.mm
80

Minimum cross section of Earthing Conductor (Calculated) = 150.75 Sq.mm

Size of selected Earthing Conductor = 50 X 6

Cross sectional area of considered Earthing conductor = 300 Sq.mm

Thus, selected size of Earthing Conductor meets the requirements

3 of 1
Calculation of Size of Earth Conductor

Formula Used For Calculation I 1


= k
S t

Value of earth fault current of negligible impedance which can flow


I 12.06 kA
through the protective device, in ampres
S Cross sectional area in Square millimeters ? Sq.mm
k Constant depends on material of earth strip 80 As per IS:3043 (Page-30)
t Operating time of the disconnecting device in seconds 1 Sec.

S = I x t
As per IS: 3043(Page-29)
k

= 12 x 1 x 1000

80

12 x 1.000 x 1000
= = 150.75 Sq.mm
80

Minimum cross section of Earthing Conductor (Calculated) = 150.75 Sq.mm

Size of selected Earthing Conductor = 50 X 6

Cross sectional area of considered Earthing conductor = 300 Sq.mm

Thus, selected size of Earthing Conductor meets the requirements

3 of 2
Calculation of Size of Earth Conductor

Formula Used For Calculation I 1


= k
S t

Value of earth fault current of negligible impedance which can flow


I 12.06 kA
through the protective device, in ampres
S Cross sectional area in Square millimeters ? Sq.mm
k Constant depends on material of earth strip 80 As per IS:3043 (Page-30)
t Operating time of the disconnecting device in seconds 1 Sec.

S = I x t
As per IS: 3043(Page-29)
k

= 12 x 1 x 1000

80

12 x 1.000 x 1000
= = 150.75 Sq.mm
80

Minimum cross section of Earthing Conductor (Calculated) = 150.75 Sq.mm

Size of selected Earthing Conductor = 50 X 6

Cross sectional area of considered Earthing conductor = 300 Sq.mm

Thus, selected size of Earthing Conductor meets the requirements

3 of 3

Anda mungkin juga menyukai