It enables you to decentralize control tasks. Therefore, an ET 200S with IM-151-8 can exercise full and, if
necessary, independent control over a process-related functional unit.
Functions of the IM 151-8
IO controller
I-Device
I device and IO controller
Controller Specifications
User Internal memory 128 kb
Built In communication Ports PN interface (3x RJ45)
Communication Options Profibus DP
I/O Modules
24 V DC 8 Channel DI Modules 6ES7131-4BF00-0AA0
24 V DC 8 Channel Do Modules 6ES7132-4BF00-0AA0
ELECTRONIC MODULE , 4AI STANDARD I-2-WIRE, 4 - 20MA
ELECTRONIC MODULE , 2AO 2 AO I 15 MM WIDE, +/-20 MA
Programming Software
All controllers shall be programmed using STEP 7 programming software
Scada Software
Maximum transparency is essential for the operator who works in an environment where
processes are becoming more complex, and requirements for machine and plant
functionality are increasing. The HMI BASED SCADA System provides this transparency.
S.NO ITEM DESCRIPTION EQUIP QTY Type
.TAG
A. Pre Bleaching Section Chemicals
- Digital, Analog Input Outputs 1 set Siemens
- Electronic Dosing Pump Phosphoric Acid 1 Electronic
- Limit Switch for dosing Valves 4 Dome Type
- Level transmitterfor Phosphoric dosing & Caustic Dosing 2 Cap.
- Pump/Start stop Remote Selector switch 2 Selzer
- Mass Flowmeter 1 ENDRESS
B. Post Bleaching section
- Digital Analog Inputs 1 set Siemens
- Limit Switch for dosing Valves 2 Electronic
- Pump Auto start stop Hardware unit 4 trumen
- Pump/Start stop Remote Selector switch 1 Salzer
- Mass Flow meter 1 Endress
C. Degumming Section 1
- Electronic dosing pump Phosphoric Pump 1 Khrone
- Electronic Dosing Unit for Caustic dosing Pump 1 Electronic
- Level Transmitter 2 Cap.
- Mass Flowmeter for Oil flow 1 ENDRESS
D. Esterification Section ( with Volumetric Flow ) +/- 2% of f.Scale
- Mass flowmeter for oil flow 1 Endress
- Common Mass flow meter for Glycerin flow 1 Endress
consumtion
- VFD for Glycerence Dosing Pump 2 Danfoss
- Digtal 8 CHANNEL RELAY CARD a/r Phex
- Pump/Start stop Remote Selector switch a/r salzer
E. HMI Based Programmable Logic Controllerfor all Sections 1 set Siemens
- Digital Inputs
- Digital Outputs
- Analog Inputs
- Analog Outputs
Stand Alone PLC panel with HMI based Scada & Logic
For Automatic dosing of the Chemicals as per flow rate of oil.
-Logic is designed for dosing of Earth,Silica,Carbon as per
predetermined % of dosing by the authorized personnel.
The system shall comprise of centralized PLC system with I/O modules, power supply at
each rack (such as CPU rack, remote I/O drops) and communication link between the
CPUs & remote I/O drops if any.( Non redundant system)
Control philosophy: The system shall be designed to operate in two modes viz Remote
manual and Auto mode as explained below and shall cater to controlling of three different
sections of the plant.
1. Auto Mode: This mode will be initiated through HMI screens. Auto mode of shall be
separately selectable for a group of operations. Once the start button is pressed relevant
operations shall be completed as per the given sequence / timings / interlocks. In case of a
problem, the changeover to Remote Manual mode shall be bump less without affecting the
process.
3. Local Mode: It shall be possible to manually operate all the Pumps individually ..
The Actuator valves will automatically adjust the dosing cycle based on the % of dosing
selected for bleaching process.The Level of Phosphoric acid will be continuously
monitored by the PLC to avoid any interruption and will provide low level alarm to refill
the chemicals in the dosing tanks.
Esterification Section : feed oil flowrate shall be monitored with Volumetric Flowmeter
continuously and glycerene dosing will be controlled according to Oil flow rate . dosing
rate can be controlled form the SCADA SCREEN .