DETAILED FEM ANALYSIS OF SEISMIC BEHAVIORS CODIFIED METHOD CONCEPT FOR AN ECONOMICAL SOLUTION
jec ts
e PINEERING ro INC.
p l
Sam LL ENG
by J

TRANSVERSE ONLY - AS TRANSVERSE AND


SHOWN ON PLANS LONGITUDINAL ON STRAIGHT
DUCT - AS SHOWN ON PLANS ON DRAWINGS: INSTALLATION: SSA WITHIN 100 OF CONCRETE
TRANSVERSE AND LONGITUDINAL RESTRAINT LESS THAN OR EQUAL TO 600 FROM JOIST PANEL POINT, SLAB
CENTRE LINE - INSTALL AS 2 TRANSVERSE REFER TO SCHEDULE
1 1
1 600

2
STEEL JOIST

.
TYP
TOP CHORD

600
CONNECTION OF
CABLE TRAY HANGER ROD TO
1 STRUCTURE BY
(TYP.)
CONTRACTOR, DCA, REFER TO

TYP
REFER TO SCHEDULE SCHEDULE
A B

ATTACHMENT OF HANGER ROD TO STRUCTURE


STEEL JOIST

.
ATTACHMENT CONCRETE

ROD LENGTH - TOP OF CABLE TRAY TO


ROD STIFFENER ATTACHMENT
STRUT CLAMPS
(TYP.)
MAXIMUM
HANGER ROD
DETAIL C1 SPACING AS PER
OR SPECS
BEAM TOP
FLANGE

ON DRAWINGS: INSTALLATION:
RESTRAINT GREATER THAN 600 RESTRAINT GREATER THAN 600 FROM CABLE
FROM CENTRE LINE CENTRE LINE - INSTALL AS 2 TRANSVERSE TRAY

.
TYP
AND 2 LONDITUDINAL SSA OR WELD BRACKET
TO STEEL ON 3 SIDES,
1 1 REFER TO SCHEDULE
600 > 600
STEEL BEAM
2 ATTACHMENT
2

> 600
STRUT
(TYP.)

1
BRACKETS
2

DETAIL C2

NOTES:
C
1. REFER TO PLANS FOR LOCATION OF TRANSVERSE STRUTS.
NOTES:
2. IF INSTALLED ROD LENGTH IS GREATER THAN MAXIMUM ROD LENGTHS
NOTED ON PROJECT DETAILS PD04 AND PD05, THEN CONTACT HALSALL
1 TRANSVERSE RESTRAINT. REFER TO PROJECT DETAILS PD03.
ASSOCIATES FOR A MODIFIED DESIGN.
2 LONGITUDINAL RESTRAINT. STRUT REQUIRED ON BOTH SIDES OF CABLE
TRAY. LOCATE AT TRANSVERSE RESTRAINT LOCATIONS.

INTERPRETATION OF CABLE TRAY TRANSVERSE SEISMIC RESTRAINT OF


SEISMIC RESTRAINT LAYOUT CABLE TRAY
PD02 PD03
AUG 13 AUG 13
jec ts
e PINEERING ro INC.
p l
Sam LL ENG
by J

<L HANGER ROD


allow/2
ROD STIFFENER FACTORS
ANGLE STIFFENERS

L allow L25X25X3.2 L38X38X6.4 L51x51x3.2 L51x51x6.4 ANGLE


STIFFENER
9.6 400 5.2 11.7 13.2 17.7
UPPER SECTION
HANGER 12.7 550 3.3 6.8 7.6 10.0 ROD BUCKLING ROD STIFFENER
ROD CLAMP
DIAMETER 16 700 2.4 4.6 5.1 6.6

Linstall
19 835 2.0 3.5 3.9 5.0 L
LOWER SECTION allow
MAXIMUM ROD LENGTH 990 1470 2000 1950
ROD GEOMETRY

TABLE NOTES:
1. DETERMINE INSTALLED ROD LENGTH (Linstall). SUPPORTING
2. IF Linstall > L allow THEN A ROD STIFFENER IS REQUIRED. STRUCTURE
IF Linstall < L allow THEN A ROD SITFFENER IS NOT REQUIRED.
3. IF "ROD BUCKLING" GOVERNS THE ROD DESIGN, THEN:
<L
A. CALCULATE THE RATIO BETWEEN Linstall AND L allow (R) AND ROUND THE NUMBER UP TO THE NEAREST FIRST allow/2
DECIMAL PLACE.
EXAMPLE: IF THE INSTALL LENGTH IS 920 AND THE MAXIMUM ALLOWED LENGTH IS 410 THEN THE RATIO,
R = 920/410 = 2.24 --> 2.3 (ROUNDED UP)
B. BASED ON THE KNOWN HANGER ROD DIAMETER, SELECT AN ANGLE STIFFENER FROM THE UPPER SECTION
WHOSE FACTOR IS GREATER THAN R.
EXAMPLE: IF 9.6 DIAMETER HANGER ROD WITH Linstall /L allow = 2.3 IS USED, THEN SELECT
L25x25x3.2 WITH R=5.2. IT
/UN
C. ENSURE THAT Linstall IS LESS THAN THE MAXIMUM STIFFENER LENGTH IN THE LOWER SECTION. IF Linstall CT
EXCEEDS THIS VALUE, THEN CHOOSE A LARGER STIFFENER. DU
EXAMPLE: IF A HANGER ROD IS 1200 LONG (990 MAXIMUM ROD LENGTH FOR L25x25x9.6 STIFFENER),
SELECT L38x38x6.4 STIFFENER.
5. IF "ROD GEOMETRY" GOVERNS THE ROD DESIGN, THEN: NUT AT TOP AND
A. SELECT THE STIFFENER SIZE BASED ON THE LOWER SECTION OF THE TABLE. BOTTOM OF SLEEVE
THREADED ROD CONNECTION
EXAMPLE: IF A HANGER ROD IS 1200 LONG, SELECT L38x38x6.4 STIFFENER. BY CONTRACTOR. PROVIDE
6. A MINIMUM OF TWO CLAMPS MUST ANCHOR THE STIFFENER TO THE HANGER ROD. THE SPACING BETWEEN CLAMPS 100 MAX
TOP & SHOP DRAWINGS.
MUST NOT EXCEED L allow.
7. IF ROD LENGTH EXCEEDS 2000mm, REFER TO PD05 FOR ALTERNATE STIFFENER. BOTTOM
8. ANGLE STIFFENERS TO BE GRADE 300W MINIMUM. 6.4 CAP PLATE AT TOP AND
BOTTOM WELDED TO SLEEVE
HSS 51x51 SLEEVE
(350 MPa MIN)

HANGER ROD STIFFENER TABLE HANGER ROD STIFFENER DETAIL


(3500mm MAXIMUM LENGTH)
j e c ts
e P roRING INC.
a m pl ENGINEE
S by JLL

ELECTRICAL UNIT SCHEDULE - SUSPENDED DISTRIBUTED SYSTEMS

HANGER RODS STRUTS

UNIT SIZE TRANSVERSE LONGITUDINAL REMARKS PD NO.


HANGER STRUT ANCHOR
ROD SIZE
ANCHOR TYPE MAX SPACING T/C FORCE IN MAX SPACING T/C FORCE IN TYPE
(m) STRUT (kN) (m) STRUT (kN)

CT 1 100x300 9.5 DIA DCA 12.7 12.2 2.0 24.4 4.0 DCA 9.5 ROD BUCKLING GOVERNS HANGER ROD DESIGN PD02-03

CT 2 100x300 9.5 DIA SSA 12.7 12.2 3.5 24.4 6.5 SSA 9.5 ROD BUCKLING GOVERNS HANGER ROD DESIGN PD02-03

NOTE:
1. UNITS ARE mm AND kN UNLESS NOTED OTHERWISE.
2. REFER TO ANCHOR SCHEDULE ON DRAWING B350-60220-006-01-DD-E FOR ANCHOR TYPES.
3. PROPOSED STRUT AND CONNECTIONS MUST BE CAPABLE OF SUPPORTING TENSION AND COMPRESSION FORCE (T/C)
INDICATED IN SCHEDULE.
4. STRUT MATERIAL TO BE 12 GA MINIMUM. MAXIMUM SLENDERNESS RATIO KL/R = 200. CONTRACTOR TO CONFIRM ALL
STRUT LENGTHS ON SITE.
5. STRUTS TO BE AT A MAXIMUM OF 45 DEGREES FROM HORIZONTAL.
6. FOR SPACING OF HANGER RODS, REFER TO SPECIFICATIONS AND MANUFACTURER'S INSTRUCTIONS.
7. CONTRACTOR TO SUMBIT SHOP DRAWINGS INDICATING PROPOSED STRUT AND STRUT CONNECTIONS FOR EACH
UNIT.
8. CONTRACTOR TO SUBMIT SHOP DRAWINGS FOR THREADED HANGER ROD CONNECTION TO SUPPORTING STRUCTURE.
REQUIRED CAPACITY IS 8.5kN AT LOCATIONS OF SEISMIC BRACING AND 4.5kN AT GRAVITY HANGERS.
9. MINIMUM GRADE OF HANGER ROD IS A36.
ON DRAWINGS: INSTALLATION:
TRANSVERSE AND LONGITUDINAL 1
TRANSVERSE AND
TRANSVERSE ONLY - AS 600
LONGITUDINAL ON STRAIGHT
SHOWN ON PLANS
PIPE - AS SHOWN ON PLANS
A

600
D
1
1 1
PIPE PIPE

DETAIL A
PIPE 2 PIPE

HANGER ROD
(WITH STIFFENER B
A B IF REQUIRED) LONGITUDINAL
RESTRAINT AS E
PER F1

PIPE TRAPEZE

ELEVATION

2
LONGITUDINAL
RESTRAINT

C F

LONGITUDINAL
RESTRAINT 2
PLAN F1 ACCEPTED STRUT CONFIGURATION FOR
TRANSVERSE SEISMIC RESTRAINT OF TRAPEZED PIPES
NOTES:
1 TRANSVERSE REFER TO PROJECT DETAIL PD07, PD09, & PD10.

2 LONGITUDINAL REFER TO PROJECT DETAIL PD08.

j ec ts
e PINEERING ro INC.
p l
S am ENG LL
by J

INTERPRETATION OF SEISMIC
RESTRAINT LAYOUT FOR PIPING
PD06
AUG 13
ts
SSA WITHIN 100 OF CONCRETE
JOIST PANEL POINT, SLAB
j ec
ro INC.
REFER TO SCHEDULE

p le PINEERING
S am ENGLL
STEEL JOIST CONNECTION OF
by J

X
TOP CHORD

MA
HANGER ROD TO
STRUCTURE,
REFER TO
SCHEDULE
DCA, REFER TO
ROD SCHEDULE

MA
STIFFENER

X
STEEL JOIST CONCRETE
CLAMPS
ATTACHMENT ATTACHMENT

MAXIMUM
STRUT HANGER ROD
(TYP.) SPACING AS
PER SPECS STRUT
BEAM TOP (TYP.)
FLANGE
CLEVIS
HANGER

X
MA

SSA OR WELD
BRACKET TO STEEL
ON 3 SIDES, REFER
TO SCHEDULE
STEEL BEAM SUPPORTING
ATTACHMENT BRACKETS STRUCTURE
PIPE DIAMETER 100
VARIES
RISER CLAMP AND NUTS
STANDARD AS SUPPLIED BY
MECHANICAL TRADE.

NOTES:
NUT AT TOP AND
1. REFER TO PLANS FOR LOCATIONS OF LONGITUDINAL SEISMIC RESTRAINTS. BOTTOM OF SLEEVE
THREADED ROD CONNECTION
100 MAX BY CONTRACTOR. PROVIDE
TOP & SHOP DRAWINGS.
BOTTOM
6.4 CAP PLATE AT TOP AND
BOTTOM WELDED TO SLEEVE
HSS 51x51 SLEEVE
(350MPa MIN.)

HANGER ROD STIFFENER DETAIL


PIPE SEISMIC RESTRAINT OF
(3500mm MAXIMUM LENGTH)
LONGITUDINAL RESTRAINT - CLEVIS HANGER
PD08
AUG 13
j ec ts <L
allow/2
HANGER ROD

e P EERING INro C.
l
mp NGIN
Saby JLL E STIFFENER

ROD STIFFENER FACTORS ROD STIFFENER


CLAMP
ANGLE STIFFENERS

Linstall
L
allow
L allow L25X25X3.2 L38X38X6.4 L51x51x3.2 L51x51x6.4

9.6 400 5.2 11.7 13.2 17.7


UPPER SECTION
HANGER 12.7 550 3.3 6.8 7.6 10.0 ROD BUCKLING
ROD
DIAMETER 16 700 2.4 4.6 5.1 6.6

19 835 2.0 3.5 3.9 5.0


LOWER SECTION
MAXIMUM ROD LENGTH 990 1470 2000 1950 <L
ROD GEOMETRY allow/2

TABLE NOTES:
1. DETERMINE INSTALLED ROD LENGTH (Linstall).
2. IF Linstall > L allow THEN A ROD STIFFENER IS REQUIRED.
IF Linstall < L allow THEN A ROD SITFFENER IS NOT REQUIRED.
3. IF "ROD BUCKLING" GOVERNS THE ROD DESIGN, THEN:

A. CALCULATE THE RATIO BETWEEN Linstall AND L allow (R) AND ROUND THE NUMBER UP TO THE NEAREST FIRST
DECIMAL PLACE.
EXAMPLE: IF THE INSTALL LENGTH IS 920 AND THE MAXIMUM ALLOWED LENGTH IS 410 THEN THE RATIO,
R = 920/410 = 2.24 --> 2.3 (ROUNDED UP)
B. BASED ON THE KNOWN HANGER ROD DIAMETER, SELECT AN ANGLE STIFFENER FROM THE UPPER SECTION
WHOSE FACTOR IS GREATER THAN R.
EXAMPLE: IF 9.6 DIAMETER HANGER ROD WITH Linstall /L allow = 2.3 IS USED, THEN SELECT A B C
L25x25x3.2 WITH R=5.2.
C. ENSURE THAT Linstall IS LESS THAN THE MAXIMUM STIFFENER LENGTH IN THE LOWER SECTION. IF Linstall
EXCEEDS THIS VALUE, THEN CHOOSE A LARGER STIFFENER.
EXAMPLE: IF A HANGER ROD IS 1200 LONG (990 MAXIMUM ROD LENGTH FOR L25x25x9.6 STIFFENER),
SELECT L38x38x6.4 STIFFENER.
5. IF "ROD GEOMETRY" GOVERNS THE ROD DESIGN, THEN:
A. SELECT THE STIFFENER SIZE BASED ON THE LOWER SECTION OF THE TABLE.
EXAMPLE: IF A HANGER ROD IS 1200 LONG, SELECT L38x38x6.4 STIFFENER.
6. A MINIMUM OF TWO CLAMPS MUST ANCHOR THE STIFFENER TO THE HANGER ROD. THE SPACING BETWEEN CLAMPS
MUST NOT EXCEED L allow.
7. IF ROD LENGTH EXCEEDS 2000mm, REFER TO PD12 FOR ADDITIONAL STIFFENER OPTIONS.
8. ANGLE STIFFENERS TO BE GRADE 300W MIN.

HANGER ROD STIFFENER TABLE FOR PIPE


AT LOCATIONS OF SEISMIC RESTRAINT D F
E

ACCEPTED STRUT CONFIGURATION FOR


TRANSVERSE SEISMIC RESTRAINT OF DUCTWORK
SSA WITHIN 100 OF CONCRETE
JOIST PANEL POINT, SLAB
REFER TO SCHEDULE

CONNECTION OF
STEEL JOIST HANGER ROD TO

X
TOP CHORD STRUCTURE,

MA
REFER TO
SCHEDULE

ROD LENGTH - TOP OF DUCT TO ATTACHMENT


DCA, REFER TO
ROD

MA
SCHEDULE
ts
STIFFENER

OF HANGER ROD TO STRUCTURE

X
STEEL JOIST
CLAMPS
j ec
ro INC.
ATTACHMENT CONCRETE

STRUT
ATTACHMENT

p le PINEERING
am ENG
MAXIMUM
(TYP.) HANGER ROD
SPACING AS PER S by J
LL
SPECS

BEAM TOP
FLANGE
ANGLE OR
UNISTRUT
X
MA

SSA OR WELD BRACKET


TO STEEL ON 3 SIDES, CT
DU SUPPORTING
REFER TO SCHEDULE STRUCTURE
STEEL BEAM
ATTACHMENT

STRUT
(TYP.)

BRACKETS

#10 SELF-TAPPING SHEET


METAL SCREWS AT 300 c/c MAX.

NUT AT TOP AND


NOTES: BOTTOM OF SLEEVE
THREADED ROD CONNECTION
1. REFER TO PLANS FOR LOCATIONS OF TRANSVERSE RESTRAINTS. 100 MAX BY CONTRACTOR. PROVIDE
TOP & SHOP DRAWINGS.
2. IF INSTALLED ROD LENGTH IS GREATER THAN MAXIMUM ROD LENGTH BOTTOM
NOTED ON PROJECT DETAIL PD08 OR PD09, THEN CONTACT HALSALL 6.4 CAP PLATE AT TOP AND
ASSOCIATES FOR A MODIFIED DESIGN. BOTTOM WELDED TO SLEEVE
HSS 51x51 SLEEVE
(350MPa MIN.)

HANGER ROD STIFFENER DETAIL


(3500mm MAXIMUM LENGTH)

TRANSVERSE SEISMIC RESTRAINT OF DUCTWORK


SSA WITHIN 100 OF CONCRETE
j ec ts
JOIST PANEL POINT, SLAB

e PINEERING ro INC.
REFER TO SCHEDULE
p l
S am ENG LL
by J
STEEL JOIST

X
TOP CHORD CONNECTION OF

MA
HANGER ROD TO
STRUCTURE,
REFER TO
SCHEDULE DCA, REFER TO

MA
SCHEDULE

X
STEEL JOIST ROD
ATTACHMENT STIFFENER CONCRETE
CLAMPS ATTACHMENT
STRUT
(TYP.)
MAXIMUM
HANGER ROD
SPACING AS PER
SPECS

BEAM TOP
FLANGE
STRUT
(TYP.)
X
MA

SSA OR WELD BRACKET


SUPPORTING
TO STEEL ON 3 SIDES,
STRUCTURE
REFER TO SCHEDULE

STEEL BEAM
ATTACHMENT

BRACKETS

NUT AT TOP AND


BOTTOM OF SLEEVE
THREADED ROD CONNECTION
100 MAX BY CONTRACTOR. PROVIDE
TOP & SHOP DRAWINGS.
BOTTOM
NOTES:
6.4 CAP PLATE AT TOP AND
1. WHERE LONGITUDINAL RESTRAINTS ARE REQUIRED, PROVIDE ONE STRUT ON EACH BOTTOM WELDED TO SLEEVE
HSS 51x51 SLEEVE
SIDE OF THE DUCT OR PROVIDE ONE STRUT AT THE CENTRELINE OF THE DUCT. (350MPa MIN.)
2. REFER TO PLANS FOR LOCATIONS OF LONGITUDINAL SEISMIC RESTRAINTS.

HANGER ROD STIFFENER DETAIL


(3500mm MAXIMUM LENGTH)
LONGITUDINAL SEISMIC RESTRAINT OF DUCTWORK
ts
<L HANGER ROD
allow/2
j e c
ROD STIFFENER FACTORS
e P roRING INC.
ANGLE STIFFENERS
a m pl ENGINEE
L allow L25X25X3.2 L38X38X6.4 L51x51x3.2 L51x51x6.4 STIFFENER
S by JLL
ANGLE
9.6 400 5.2 11.7 13.2 17.7
UPPER SECTION
HANGER 12.7 550 3.3 6.8 7.6 10.0 ROD BUCKLING ROD STIFFENER
ROD CLAMP
DIAMETER 16 700 2.4 4.6 5.1 6.6

Linstall
19 835 2.0 3.5 3.9 5.0 L
LOWER SECTION allow
MAXIMUM ROD LENGTH 990 1470 2000 1950
ROD GEOMETRY

TABLE NOTES:
1. DETERMINE INSTALLED ROD LENGTH (Linstall).
2. IF Linstall > L allow THEN A ROD STIFFENER IS REQUIRED.
IF Linstall < L allow THEN A ROD SITFFENER IS NOT REQUIRED.
3. IF "ROD BUCKLING" GOVERNS THE ROD DESIGN, THEN:
<L
A. CALCULATE THE RATIO BETWEEN Linstall AND L allow (R) AND ROUND THE NUMBER UP TO THE NEAREST FIRST allow/2
DECIMAL PLACE.
EXAMPLE: IF THE INSTALL LENGTH IS 920 AND THE MAXIMUM ALLOWED LENGTH IS 410 THEN THE RATIO,
R = 920/410 = 2.24 --> 2.3 (ROUNDED UP)
B. BASED ON THE KNOWN HANGER ROD DIAMETER, SELECT AN ANGLE STIFFENER FROM THE UPPER SECTION
WHOSE FACTOR IS GREATER THAN R.
EXAMPLE: IF 9.6 DIAMETER HANGER ROD WITH Linstall /L allow = 2.3 IS USED, THEN SELECT
L25x25x3.2 WITH R=5.2. T
C
C. ENSURE THAT Linstall IS LESS THAN THE MAXIMUM STIFFENER LENGTH IN THE LOWER SECTION. IF Linstall DU
EXCEEDS THIS VALUE, THEN CHOOSE A LARGER STIFFENER.
EXAMPLE: IF A HANGER ROD IS 1200 LONG (990 MAXIMUM ROD LENGTH FOR L25x25x9.6 STIFFENER),
SELECT L38x38x6.4 STIFFENER.
5. IF "ROD GEOMETRY" GOVERNS THE ROD DESIGN, THEN:
A. SELECT THE STIFFENER SIZE BASED ON THE LOWER SECTION OF THE TABLE.
EXAMPLE: IF A HANGER ROD IS 1200 LONG, SELECT L38x38x6.4 STIFFENER.
6. A MINIMUM OF TWO CLAMPS MUST ANCHOR THE STIFFENER TO THE HANGER ROD. THE SPACING BETWEEN CLAMPS
MUST NOT EXCEED L allow.
7. IF ROD LENGTH EXCEEDS 2000mm, REFER TO PD09 FOR ADDITIONAL HANGER OPTIONS.
8. ANGLE STIFFENER GRADE IS 300W MIN.

HANGER ROD STIFFENER TABLE


j ec ts
ro INC.
e PINEERING
p l
Sam LL ENG
by J
j ec ts
ro INC.
e PINEERING
p l
S am ENGLL
by J
FACILITY-SUPPLIED SUPPLEMENTAL AIR DUCT
(SEE SHEET 5.0 FOR ADDITIONAL INFORMATION).
COMPRESSED AIR PIPE CL ELECTRICAL FLOOR TRENCH
(REFER TO DETAILS 1 & (REFER TO DETAILS "3" & "6"
5 ON SHEET S3). ON SHEET S3).

2
S2 USE HILTI HSL-3 M10
DRILL HOLE SIZE 15 mm
1 HOLE DEPTH 100 mm
S3

GANTRY PIT (SEE


SHEET NOTES FOR
ADDITIONAL
INFORMATION).
ISOCENTER

1
S2 1
S2

ANCHOR BOLT @
GANTRY SUB-BASE
(SEE SHEET NOTES
FOR ADDITIONAL
INFORMATION).
PATIENT TABLE
FLOOR JUNCTION
BOX (REFER TO MOISTURE SENSOR
ec ts
roj C .
DETAIL 4 ON (SEE SHEET NOTES FOR
SHEET S3). ADDITIONAL INFORMATION).
le P EERING IN
mp NGIN
Saby JLL E

ANCHOR BOLT
@ PATIENT
TABLE
SUB-BASE
SHEET S2 LEGEND
(SEE SHEET
NOTES FOR = 6" [15.2] AREA AROUND
ADDITIONAL ANCHOR BOLT LOCATION TO
INFORMATION). BE KEPT CLEAR OF ALL
CONDUITS, DRAIN LINES AND
REBAR TO A MINIMUM DEPTH
OF 10" [25.4]. (12 ANCHOR
LOCATIONS TOTAL.)

= EQUIPMENT ISO CENTER

= CONCRETE WALL

3 SUB-BASE PLAN 2 DIMENSION FORMAT: MILLIMETERS [10.0]


S2
S2 SCALE: 1/2" = 1'-0" ALTERNATIVE UNITS: FEET (1') & INCHES (1")