ABSTRACT It will be shown that this idea will improve the speed and
coordination of protection system. In this paper, at first,
In this paper a new approach will be used for optimal the process to obtain the constraints of over current
coordination of directional over current (DOC) relays relays coordination is illustrated and then we will
based on genetic algorithm. In this approach, optimal investigate the proposed approach for solving these
operation characteristics and also optimal current constraints. Finally the proposed approach will be tested
setting and time setting of each OC relays will be on a real network and the results will be compared with
determined simultaneously. Also, a new objective other approaches.
function will be used which is different from ordinary
methods such as simplex, two phase simplex, dual 2. DOC RELAYS COORDINATION
simplex. Improvement of selectivity and speed of the CONSTRAINTS
protection system, obtaining the absolute optimal point
of the optimization problem are the specifications of As what has expressed in [8] in order to coordinate two
the proposed approach. Numerical results obtained over current relay, one as main relay (m) and the other as
with the proposed method for a real power system are back up relay (b), (it is shown in figure 1), the difference
presented. between the operation time of back up relay and the
operation time of main relay for faults F1 and F2 should
be more than CTI . F1 and F2 are short circuit at near
1. INTRODUCTION bus and far bus of main relay respectively. CTI is the
time interval for coordination of main and backup relay.
Directional over current (DOC) relays are commonly
used in power system for protecting of lines.
Optimization methods are usually used for setting and t
coordination of these relays. Increasing of the > CTI
protection system selectivity and the speed of relays in tb
clearing faults, are the main specification of > CTI tm
optimization methods. In these methods, at first, the
coordination constraints for each main and backup b m
DOC relay will be determined. [1] has discussed the
process of determining such constraints. Then, these F1 F2
constraints are solved by an optimization method in
order to achieve minimum time setting of each relay.
Some of the optimization methods that have been used Fig 1- Coordination constraint of DOC relays
for the above problem are: simplex method [2, 3, 4],
two phase simplex method [5] and dual simplex [6]. In
[7] a matrix method is used to get the relay setting. In So the constraints for coordination of DOC relays b and
[8], the above problem has been solved using genetic m will be in the form of inequalities 1 and 2:
algorithm. In this reference, current setting multiplier
(PSM) and time setting multiplier (TSM) of each OC t b ( F1 ) t m ( F1 ) > CTI (1)
relays have been considered as chromosomes of t b ( F2 ) t m ( F2 ) > CTI (2)
genetic algorithm in order to achieve optimum values
of PSM and TSM simultaneously.
All of the above approaches consider a predefined t b ( F1 ) and t m ( F1 ) are respectively the operation time
characteristic for each over current relays and then of backup and main relay for a short circuit in F1 ,
current settings and time settings are obtained. Since it t b ( F2 ) and t m ( F2 ) are respectively the operation time
is possible to apply different characteristics on over
current relays, so in this paper we will try to achieve of backup and main relay for a short circuit in F2 .
the optimum operation characteristic and also the For instance if relays b and m set on normally inverse
optimum time setting and current setting of over characteristics [11], then inequities 1 and 2 can be
current relays while solving the optimization problem. expressed as 3 and 4.
0.14 0.14 Figure 2 shows these characteristics for TSM=1.
TSM b TSM m > CTI
I b , F 1 0.02 I m, F 1 0.02
( ) 1 ( ) 1
I b , pickup I m , pickup
(3)
0.14 0.14
TSM b TSM m > CTI
I b, F 2 I m, F 2 LTI
( )0.02 1 ( )0.02 1 EI
I b , pickup I m , pickup
(4)
VI
Where I b,F1 and I m,F1 are currents of backup and
main relay for fault F1 . I b,F 2 and I m,F 2 are currents t
NI
of backup and main relay for fault F2 . I b, pickup and
RXIDG
I m, pickup are current setting of backup and main relay.
RI
TSMb and TSMm are time setting multiplier of backup
and main relay.
For optimal coordination of power system relays, at
first, it is essential to form the coordination constraints I / I pickup
of all main and backup relays. Then the parameters of
relays should be set such that for the least operation Fig 2- Different characteristics
time of DOC relays, all the constraints be satisfied. of SPCS DOC relay