Anda di halaman 1dari 4

Optimal Coordination of Directional Over Current

Relays in Power System Using Genetic Algorithm

F. Kavehnia (1) H. Seifi(2) H. Keivani (1) M.R. Askari (1)


(1) Islamic Azad University, Branch of Kazeroon
(2) Tarbiat-Modarress University

ABSTRACT It will be shown that this idea will improve the speed and
coordination of protection system. In this paper, at first,
In this paper a new approach will be used for optimal the process to obtain the constraints of over current
coordination of directional over current (DOC) relays relays coordination is illustrated and then we will
based on genetic algorithm. In this approach, optimal investigate the proposed approach for solving these
operation characteristics and also optimal current constraints. Finally the proposed approach will be tested
setting and time setting of each OC relays will be on a real network and the results will be compared with
determined simultaneously. Also, a new objective other approaches.
function will be used which is different from ordinary
methods such as simplex, two phase simplex, dual 2. DOC RELAYS COORDINATION
simplex. Improvement of selectivity and speed of the CONSTRAINTS
protection system, obtaining the absolute optimal point
of the optimization problem are the specifications of As what has expressed in [8] in order to coordinate two
the proposed approach. Numerical results obtained over current relay, one as main relay (m) and the other as
with the proposed method for a real power system are back up relay (b), (it is shown in figure 1), the difference
presented. between the operation time of back up relay and the
operation time of main relay for faults F1 and F2 should
be more than CTI . F1 and F2 are short circuit at near
1. INTRODUCTION bus and far bus of main relay respectively. CTI is the
time interval for coordination of main and backup relay.
Directional over current (DOC) relays are commonly
used in power system for protecting of lines.
Optimization methods are usually used for setting and t
coordination of these relays. Increasing of the > CTI
protection system selectivity and the speed of relays in tb
clearing faults, are the main specification of > CTI tm
optimization methods. In these methods, at first, the
coordination constraints for each main and backup b m
DOC relay will be determined. [1] has discussed the
process of determining such constraints. Then, these F1 F2
constraints are solved by an optimization method in
order to achieve minimum time setting of each relay.
Some of the optimization methods that have been used Fig 1- Coordination constraint of DOC relays
for the above problem are: simplex method [2, 3, 4],
two phase simplex method [5] and dual simplex [6]. In
[7] a matrix method is used to get the relay setting. In So the constraints for coordination of DOC relays b and
[8], the above problem has been solved using genetic m will be in the form of inequalities 1 and 2:
algorithm. In this reference, current setting multiplier
(PSM) and time setting multiplier (TSM) of each OC t b ( F1 ) t m ( F1 ) > CTI (1)
relays have been considered as chromosomes of t b ( F2 ) t m ( F2 ) > CTI (2)
genetic algorithm in order to achieve optimum values
of PSM and TSM simultaneously.
All of the above approaches consider a predefined t b ( F1 ) and t m ( F1 ) are respectively the operation time
characteristic for each over current relays and then of backup and main relay for a short circuit in F1 ,
current settings and time settings are obtained. Since it t b ( F2 ) and t m ( F2 ) are respectively the operation time
is possible to apply different characteristics on over
current relays, so in this paper we will try to achieve of backup and main relay for a short circuit in F2 .
the optimum operation characteristic and also the For instance if relays b and m set on normally inverse
optimum time setting and current setting of over characteristics [11], then inequities 1 and 2 can be
current relays while solving the optimization problem. expressed as 3 and 4.
0.14 0.14 Figure 2 shows these characteristics for TSM=1.
TSM b TSM m > CTI
I b , F 1 0.02 I m, F 1 0.02
( ) 1 ( ) 1
I b , pickup I m , pickup
(3)
0.14 0.14
TSM b TSM m > CTI
I b, F 2 I m, F 2 LTI
( )0.02 1 ( )0.02 1 EI
I b , pickup I m , pickup
(4)
VI
Where I b,F1 and I m,F1 are currents of backup and
main relay for fault F1 . I b,F 2 and I m,F 2 are currents t
NI
of backup and main relay for fault F2 . I b, pickup and
RXIDG
I m, pickup are current setting of backup and main relay.
RI
TSMb and TSMm are time setting multiplier of backup
and main relay.
For optimal coordination of power system relays, at
first, it is essential to form the coordination constraints I / I pickup
of all main and backup relays. Then the parameters of
relays should be set such that for the least operation Fig 2- Different characteristics
time of DOC relays, all the constraints be satisfied. of SPCS DOC relay

Figure 2 shows that for some short circuit currents, a


3. PROPOSED APPROACH FOR OPTIMAL special characteristic can provide a less operation time.
COORDINATION OF DOC RELAYS In this paper we try to achieve the most suitable
operation characteristic, current setting and time setting
As what expressed in the previous section, we should
of over current relays simultaneously by using genetic
determine three parameters in order to set and
algorithm.
coordinate directional over current relays:
b) Current setting multiplier (PSM) is the other
a) Operation characteristic of relays should be
parameter that should be set on DOC relays. This
determined. To achieve inequalities 3 and 4, we
parameter that is determined according to I pickup , should
assumed that the operation characteristic of main and
backup relay is normally inverse. Since we can apply be set such that the relay do not operate for the
several characteristic on an over current relay, so in maximum load current but operate for the minimum
this paper we try to achieve the optimal operation short circuit current.
characteristic of relays which improve the selectivity
and speed of protection system. c) Time setting multiplier (TSM) is the other parameter
For example for SPCS 2D26 relay, which is produced for OC relays coordination. This parameter should be set
by A.B.B. Company we can apply six characteristics as such that for the minimum TSM value, sufficient time
expressed in table 1. interval between main and backup relay is provided.
In this paper, all of the three parameters have been
Table 1- Characteristics of SPCS DOC relay determined using genetic algorithm. Genetic algorithm
0.14 uses random number (gene) for each of variables. A
Normally t= * TSM
: (
I
) 0.02 1 chromosome is a set of random numbers produced for all
Inverse I pickup of variables. Therefore each chromosome is a solution of
13.5 problem. In genetic algorithm, a set of chromosomes is
Very t= * TSM
: (
I
)1 1
provided and then they will be graded using an objective
Inverse I pickup function. Then a number of them will be selected, which
80 are called the first generation. After producing the first
Extremely t= * TSM generation, we can use operators such as transposition
: I
Inverse ( )2 1
I pickup and mutation to produce the next generation and finally
finding an optimal solution.
120
Long Time t= * TSM In this paper, each chromosome contains characteristic,
: I
Inverse ( )1 1 PSM and TSM of over current relays as figure 3.
I pickup
1 | Charac1| ... | Characn | PSM 1 | ... | PSM n | TSM 1 | ... | TSM n |
t= * TSM
RI-type : I pickup 1
0.339 0.236( )
I Fig 3- Genetic algorithm chromosome
I
RXIDG-type : t = 5.8 1.35 * Ln( )1
TSM * I pickup
Where: Table 2 illustrates optimal PSM, TSM and characteristics
Charac i : Characteristic of i' th DOC relay of each directional over current relays of the case
PSMi : network.
Current setting multiplier of the i' th
DOC relay
Table 2- Optimal PSM, TSM and characteristics
TSMi : Time setting multiplier of the i' th of case network relays
DOC relay Relay
PSM TSM Charac.
Num.
The objective function use for grading of 1 25 0.84 N.I
chromosomes is defined as 5: 2 25 0.34 V.I
ObjectiveFunction = 3 25 0.96 V.I
N
(5) 4 75 0.08 N.I
Min{ K1 * MC + K 2 * CTINM + K 3 * Sum(tOC )}
n =1 5 75 0.83 V.I
6 75 0.06 N.I
Where: 7 75 0.60 RXIDG
MC is the number of times that the backup relay 8 25 0.74 V.I
operate earlier than main relay, CTINM is the number 9 25 0.27 V.I
of times that time interval of main relay and backup 10 25 0.73 V.I
relay is less than CTI and Sum(t oc ) is the sum of 11 25 0.69 V.I
operation time of over current relays. K1 , K 2 and 12 75 0.05 N.I
13 125 0.18 V.I
K 3 are arbitrary coefficients. 14 75 0.05 N.I
Simultaneous optimization of operation speed and 15 125 0.05 N.I
selectivity of protection system is the benefit of this 16 25 0.64 V.I
objective function. So we can be sure that relays will 17 25 0.91 V.I
operate fast and coordinated to clear faults. 18 25 0.80 V.I
19 25 0.86 V.I
20 25 0.97 V.I
4. RESULTS OF PROPOSED APPROACH ON A 21 25 0.64 V.I
CASE STUDY 22 25 0.59 R.I
23 25 0.93 V.I
The proposed approach has been tested on a network 24 25 0.08 N.I
shown in figure 4. This network contains 26 busbars, 5 25 25 0.80 V.I
generators, 43 lines, 7 transformers and 52 directional 26 50 0.66 V.I
over current relays. 27 50 0.41 R.I
28 25 0.90 V.I
29 25 0.33 V.I
30 100 0.67 V.I
31 125 0.55 V.I
32 75 0.15 N.I
33 75 0.40 V.I
34 75 0.33 V.I
35 75 0.92 V.I
36 75 0.45 R.I
37 75 0.09 N.I
38 75 0.33 V.I
39 75 0.13 V.I
40 50 0.39 V.I
41 50 0.28 V.I
42 50 0.05 N.I
43 50 0.10 N.I
44 125 0.30 V.I
45 75 0.07 N.I
Figure 4- Case study 46 75 0.05 N.I
The software program can get all of the six 47 75 0.18 V.I
characteristics, expressed in table 1. But, we ignore 48 75 0.60 V.I
using extremely inverse (E.I.) characteristic since E.I. 49 75 0.44 RXIDG
is often used in the industrial networks to coordinate 50 50 0.09 V.I
relays with fuses. CTI value has considered 0.3 51 75 0.09 N.I
seconds. 52 50 0.5 V.I
Table 3 compares total operation time and the Transaction on Power Delivery, Vol. 16, No.3, July
percentage of coordination constraints which are 2001, PP. 1276-1284
satisfied in three cases:
Case 1: Dual simplex method with the assumption of 3. A.Urdenata, H.Restrepo, S.Marques and J.Sanches,
normally inverse characteristic for all relays. Coordination of Directional Overcurrent Relay Timing
Case 2: Genetic Algorithm method with the Using Linear Programming, IEEE Transaction on
assumption of normally inverse characteristic for all of Power Delivery, Vol. 11, Jan.1996, PP. 122-129
DOC relays.
Case 3: Genetic algorithm method, which determines 4. A.J.Urdenata, R.Nadira and L.Prez, Optimal
optimal operation characteristic of DOC relays Coordination of Directional Overcurrent Relays in
(proposed method). Interconnected Power System, IEEE Transaction on
Power Delivery, Vol. 3, July 1988, PP. 903 911
Table 3. Comparison of results for the case
network 5. A.S.Braga, J.T.Saraiva, Coordination of Directional
Overcurrent Relays in Meshed Networks Using Simplex
Case 1 Case 2 Case 3 Method, IEEE conf. MELECON 96, Vol. 3, No. 3,
1996, PP. 1458-
Total
operation
56.92 47.80 31.43 6. B.Chattopadhyay, M.S.Sachdev, T.S.Sidhu, An On
time of relays
line Relay Coordination Algorithm for Adaptive
(Sec)
Protection Using Linear Programming Technique, IEEE
satisfied Transaction on Power Delivery, Vol. 11, Jan. 1996, PP.
constraints 86.2 90.8 96.3 165-173
(%)
7. H.A.Abyaneh and R.Keyhani, Optimal Coordination
Table 3 illustrates the advantages of proposed of Overcurrent Relays in Power System by Dual Simplex
approach. Using Genetic algorithm and determination Method in Proc. 1995 AUPEC Conf, Perth, Australia,
of optimal Characteristic, PSM and TSM of relays Vol. 3, 1995, PP. 440445
simultaneously, results in:
a) More constraints are satisfied which means 8. H.A.Abyaneh, M.Al-Dabbagh, H.Karegar, A New
increasing of relays coordination and selectivity of Optimal Approach for Coordination of Overcurrent
protection system. Relays in Interconnected Power Systems, IEEE
b) Considerable decrease in the operation time of Transaction on Power Delivery, Vol. 18, No. 2, April
relays, which means faster operation of protection 2003, PP. 430435
system.
9. C.W.So, K.K.Li, K.T.Lai, K.Y.Fung, Application of
Genetic Algorithm to Overcurrent Relay Grading
5. CONCLUSION Coordination, IEE Conf. Developments in Power
System, March 1997, PP. 6669
In this paper, a new method is proposed in order to
optimize coordination of directional over current relays 10. H.K.Karegar, H.A.Abyaneh, M.Al-Dabbagh, A
base on genetic algorithm. This method can determine Flexible Approach for Overcurrent Relay Characteristics
optimal operation characteristic, current setting Simulation", Electric Power System Research, 2003, PP.
multiplier (PSM) and time setting multiplier (TSM) of 233-239
DOC relays simultaneously. Increase of coordination
and the operation speed of relays, finding the absolute 11. A.R.Van, C.Warrington, Protective Relays, Their
optimal point, not being trapped in a local optimal Theory and Practice", John Wiley and Sons, NY, 1962
point, the ability to be apply on large networks, the
ability to consider both linear and non-linear
characteristics of relays are some of advantages of the AUTHOR'S ADDRESS
proposed method. The first author can be contacted at:
Department of Electrical Engineering
Islamic Azad University, Branch of Kazeroon
6. REFERENCES Kazeroon
Iran
1. L.Perez, A.J.Urdaneta, Optimal Computation of Email: FarzadKavehnia@yahoo.com
Directional Overcurrent Relays Considering Definite
Time Backup Relaying ", IEEE Transaction on Power
Delivery, Vol. 4, No.4, October 1999, PP. 385-388

2. L.Perez, A.J.Urdaneta, Optimal Computation of


Distance Relays Second Zone Timing in a Mixed
Protection Scheme with Directional Relays", IEEE

Anda mungkin juga menyukai