Anda di halaman 1dari 6

HVAC BOQ

S.No.

a
b
c
d
e

a
b

# Sensitivity: L13:48:32 Construction Internal Use


3

a
b

a
b
c
d
e
f
g
h

# Sensitivity: L13:48:32 Construction Internal Use


HVAC BOQ
Description

Supply & Installation of Variable Refrigerant Flow (VRF) system, module split type multi-system ai
comprising of outdoor and indoor units, having capability to cool and heat independently for the requirement of
below mentioned capacity complete with voltage stabiliser, Refrigerant CFC-free R410A, high efficiency DC invert
high pressure chamber, more compact structure, refrigerant be compressed directly, blower fan , cooling coil, filte
standard filters, Temperature sensot with cordless remote, indoor & outdoor Mounting stand, drain pipe, fan mo
power & control cables, Control Panel & Necessary accessories. Environment : desert/tropical, high chemical conten
Temperature at ambient air Max : +48 C, Min : 28C, Refrigerant copper tubes with insulation for the above uni
distance b/w Indoor & Outdoor unit shall be 20 mtrs per unit)
Electrical Characteristics: Outdoor Unit: 380~415 V/3-ph with utilization range of 342~440 V/3-ph for 50Hz system;
Indoor Unit: shall be 220~240 V/1-ph with utilization range of 198~254 V/1-ph for 50Hz System.
Other Details are as per Annexure-1.

Indoor Unit
Location: Communication Room (1st Floor) Cooling Capacity 9600 BTU/H and Heating Capacity 10,900 BTU/H
Location: Maintenance Office (Ground Floor) Capacity 15400 BTU/H and Heating Capacity 17,100 BTU/H
Location: SS Incharge Room (Ground Floor) Capacity 15400 BTU/H and Heating Capacity 17,100 BTU/H
Location: LVAC DC Room (1st Floor) Capacity 24200 BTU/H and Heating Capacity 27,300 BTU/H
Location: Protection & Control Room (1st Floor) Capacity 19100 BTU/H and Heating Capacity 21,500 BTU/H
Outdoor Unit
Location; Roof Floor, Cooling Capacity 114,000 BTU/H and Heating Capacity 128,000 BTU/H

Five (5) of monthly routine servicing of air-conditioning units and control panel. (cost including of both air-cond
refrigerant and control panel's part accessories)

Note: The Capacity of Split Ac are based on DAIKIN equipment catalogue.The vendor is free to choose diff
equipment

Supplying, installing, testing and commissioning of direct driven heavy duty wall mounted PROPELLER FAN
coated for exhaust air . Each fan shall be complete with permanent split capacitor or shaded pole motor, mounting pla
like wire guard, bird screen and fixed louvers for weather protection, GI rain protection etc., as required. Fan selectio
and Electrical characteristics shall be as follows : Propeller fans shall be free static unless otherwise specified. The
suitable for 220~240 V/1-ph with utilization range of 198~254 V/1-ph for 50Hz System., AC supply, Necessary pow
be consider from the starter to fan motor as required. Local Starter Panel shall be considered

Location : Toilet; Capacity : 250 CFM


Location : Store room; Capacity : 150 CFM

# Sensitivity: L13:48:32 Construction Internal Use


Supplying, installing, testing and commissioning of direct driven heavy duty wall mounted flame proof PROPELLE
epoxy coated for Battery exhaust air. Each fan shall be complete with permanent split capacitor or shaded pole motor,
plate, accessories like wire guard, bird screen and fixed louvers for weather protection, GI rain protection etc., as requ
selection arrangement and Electrical characteristics shall be as follows : Propeller fans shall be free static unless other
specified. The motor shall be suitable for 220 V + 10% volts 1 phase 50 cycles, AC supply, EFF-CLASS 1 The motor
be energy efficient having efficiency at full load ranging between 82.5% to 92% in accordance with motor rating as p
Necessary power cable shall be consider from the starter to fan motor as required. Local Starter Panel shall be consid
Location : Battery Room; Capacity : 300 CFM
Location : Battery Room in 960 kWp DC Plant Control Room , Capacity : 300 CFM (5 Duty, 2 Stand by)

Efficient weather protection louvers / moisture eliminators to remove the majority of the liquid (rain, sea spray, coarse
with moisture separation efficiency shall typically be 96 % for droplet sizes of 30 m and larger at a system velocity o
Location : 232 kV GIS room : 1000 CFM
Location : 132 kV GIS room : 1000 CFM
Location : 33 kV GIS room : 100 CFM
Location : LV AC/DC room : 100 CFM
Location : Protection and Control Room : 100 CFM
Location : SS Incharge Room : 100 CFM
Location : Control Room : 100 CFM
Location : Maintenance Room : 100 CFM

Fresh Air Louver with Filter and sand trap for Solar Battery Room
Location : Battery Room in 960 kWp DC Plant Control Room , Capacity : 100 CFM

Door Grills for Rest Room,Shower and Store Room

# Sensitivity: L13:48:32 Construction Internal Use


Unit Qty Unit Price Total Price

Set 1
Set 1
Set 1
Set 1
Set 2

Set 1

LS 1

Set 1
Set 1

# Sensitivity: L13:48:32 Construction Internal Use


Set 2
Set 7

Set 3
Set 1
Set 1
Set 1
Set 2
Set 1
Set 1
Set 1

Set 4

No 3

# Sensitivity: L13:48:32 Construction Internal Use

Anda mungkin juga menyukai