DNP3 Protocol
Technical Manual
For
Automatic Circuit Reclosers
And
Load Break Switches
With
CAPM-4/5 Controllers
Scope
This document describes the DNP3 Protocol and Database Implementation on
Nu-Lec Automatic Circuit Reclosers and Load Break Switches using CAPM-4/5
controllers.
Preliminary
LIMITATIONS
This document is copyright and is provided solely for the use of the recipient. It is not to
be copied in any way, nor its contents divulged to any third party, nor to be used as the
basis of a tender or specification without the express written permission of Nu-Lec
Industries Pty Ltd.
This document discloses confidential intellectual property that belongs to Nu-Lec
Industries P/L. This document does not invest any rights to Nu-Lec Industries intellectual
property in the recipient. Moreover the recipient is required not to disclose any of the
intellectual property contained in this document to any other party unless authorised in
writing by Nu-Lec Industries Pty Ltd.
N00-324 R39 i
DNP V3.00 Protocol Technical Manual
Revision Control
Contents
1 Introduction............................................................................................................... 1
2 Overview................................................................................................................... 1
2.1 Status Points ...................................................................................................... 1
2.2 Controls .............................................................................................................. 2
2.3 Data Configuration.............................................................................................. 2
2.4 Password Protection........................................................................................... 2
2.5 LBS vs ACR Point Mapping................................................................................ 2
2.6 Year 2000 Compliance Statement...................................................................... 2
3 SCADA System Design ............................................................................................ 3
4 Applicability............................................................................................................... 4
4.1 Control Cubicle Software .................................................................................... 4
4.2 DNP3 Protocol.................................................................................................... 4
4.3 Switchgear Type................................................................................................. 4
4.4 Terminology........................................................................................................ 4
5 Protocol Configuration .............................................................................................. 5
5.1 Transmission Services Configuration ................................................................. 5
5.1.1 Overview ............................................................................................................. 5
5.1.2 Transmission Services Parameters..................................................................... 5
5.1.3 Use of Application and Data Link Confirmation/Retries....................................... 7
5.2 Unsolicited Response Configuration................................................................... 8
5.2.1 Overview ............................................................................................................. 8
5.2.2 Unsolicited Response Parameters ...................................................................... 8
5.2.3 Event Buffering.................................................................................................. 12
5.3 Data Configuration............................................................................................ 12
5.3.1 Overview ........................................................................................................... 12
5.3.2 Database Parameters ....................................................................................... 13
5.3.3 Database Size Permutations............................................................................. 14
5.3.4 Default Database Data Objects......................................................................... 15
5.3.5 Analogue Deadband Parameters ...................................................................... 16
Analogue Alarm Reporting ......................................................................................... 17
5.3.7 Analogue Alarm Parameters ............................................................................. 18
6 Physical Layer ........................................................................................................ 20
6.1 Communications Ports Supported .................................................................... 20
6.2 RS-232 Communication Specifications ............................................................ 20
6.2.1 RS-232 Hardware Signals................................................................................. 20
6.2.2 RS-232 Character Definition ............................................................................. 20
6.2.3 RS-232 Configuration Parameters .................................................................... 20
6.2.4 Carrier Detect.................................................................................................... 24
1 Introduction
This document describes the Nu-Lec DNP3 implementation for Automatic Circuit
Reclosers (ACRs) and Load Break Switchs (LBS) on Control and Protection Module types
4 and 5 (CAPM).
For more information about the Recloser mode or Load Break Switch refer to relevant
technical manual for your switchgear type.
This implementation is more complex than most telemetry protocols. It is essential to read
the Overview section in order to set up the SCADA system correctly.
2 Overview
The Nu-Lec CAPM controller combines the functions of protection relay and switchgear
controller into a single intelligent electronic device (IED).
The controller provides a user friendly operator interface on a four line LCD control panel
that allows configuration and control of the switchgear.
In addition the controller generates time tagged events which are displayed on the
operator control panel. These events show the history of the switchgear operation for the
benefit of the operator and for post fault analysis.
Examples would be:
Operator Actions such as trip or close
Protection Pick up
Protection Trips
Fault Current Levels
Auto-reclose actions
These events are optimised to give the operator the most useful information.
Electricity supply utilities frequently link the controller into their SCADA systems as a
Remote Terminal Unit (RTU).
To make this simple the controller provides:
Mounting room for a radio or modem in the control cubicle.
Power supply for the radio or modem in the control cubicle.
Embedded protocol handler for the required SCADA protocol in the controller
firmware.
The DNP3 protocol allows digital and analogue data to be sent from the controller to the
SCADA system with time tags attached. This facility has enabled Nu-Lec to provide a
sophisticated SCADA system interface that not only provides the SCADA system with
status information but also allows the SCADA system to re-create the Event Log display
on the operator control panel.
N00-324 R39 1
DNP V3.00 Protocol Technical Manual
2.2 Controls
A list of the controls supported by the protocol handler is detailed in Appendices H and N.
All controls have a corresponding binary status point. The master station must use these
status points to verify that the control action has been successful. Sometimes a control will
be rejected because of an underlying controller condition preventing the action. These
conditions are detailed in the table in the appendices.
The DNP3 protocol handler can trigger two events to be recorded in the controller event
log - DNP3 Trip Req and DNP3 Close Req. This event log reporting indicates only that
the protocol handler has requested a trip or a close from the controller. It does not
necessarily mean that the action has been taken. As detailed above, the request may be
over-ridden by operational conditions.
The DNP3 protocol handler is designated as a remote user. Refer to the equipment
manual for more information.
4 Applicability
4.1 Control Cubicle So ftware
This document applies to Nu-Lec pole top reclosers and load break switches using a
CAPM Controller which displays DNP3 Manual N00-324R39+ on the controller
capability pages.
To find these pages refer to the main equipment manual.
Some features described in this manual may only be available on later releases of the
software. In this case the manual will declare which version of software applies.
5 Protocol Configuration
The DNP3 protocol handler adds several pages to the System Status menus. The
additional pages fall into the following groups,
Transmission Services Configuration (refer Section 5.1)
Unsolicited Response Configuration (refer Section 5.2)
Data Configuration (refer Section 5.3)
Communications Configuration (refer Sections 6.2 and 6.3)
Communication Statistics (refer Section 6.4)
All protocol configuration parameters can be viewed, modified and stored on a personal
computer with the WSOS utility.
Parameter Description
DL Cf Rqd Data Link Confirm Required
On some communications links it is required to have extra
communications integrity to ensure that all data link frames are
successfully received by the master station.
Parameter Description
If NEVER, the protocol handler will not request acknowledgment
messages from the master station for data link frame transmissions. It
assumes all data link frames are received by the master station and
relies solely on application layer message integrity checking.
If SOMETIMES, the protocol handler requests a data link
acknowledge response from the master station only on multi-frame
DNP3 messages.
If ALWAYS, the protocol handler will expect a data link
acknowledgment message from the master station to all data link
frame transmissions.
Range: NEVER, SOMETIMES, ALWAYS.
Factory default is SOMETIMES
DL Cf TO Data Link Confirm Timeout
When the controller DNP3 data link layer transmits a frame that
requires an acknowledge response from the master station, it starts a
timer. The timer is triggered upon transmission of the last byte of a
frame.
If an acknowledge frame is not received from the master station with-
in the data link confirm time out period, DL Cf TO, then the frame is
resent.
If the communications link has failed then the controller will continue
retransmissions until DL Max Retries failures occur after which it
informs the application layer of the failure.
Range: 50 to 65535 ms.
Factory default is 4000 ms
DL Max Data Link Maximum Retries
Retries Maximum number of times a frame is re-sent before communication
failure is identified.
Range: 0 255.
Factory default is 2
Apl Cf TO Application Layer Confirm Timeout
When the controller transmits some DNP3 messages, such as a
application layer messages that contain change of state data, a DNP3
application layer confirm message is expected from the master
station. When the last byte of one these messages is transmitted by
the controller a timer is started.
If an application layer confirm message is not received from the
master station with-in the time out period then the message is deemed
failed. Refer to section 5.2.3 for more information regarding failed
application layer message handling.
If the application layer message is too large for a single data link
frame then the protocol handler segments the application message
into multiple data link frames. The application confirm timeout period
must therefore allow for multiple data link frames.
If DL Cf Rqd is set to either SOMETIMES or ALWAYS then for correct
operation of the confirm timeouts Apl Cf TO must be set using the
Parameter Description
following formula:
Apl Cf TO >= ((DL Max Retries + 1) x DL Cf TO x 7)
The controller calculates this value and automatically overwrites a
value that is entered which is less than the calculated value.
If DL Cf Rqd is set to NEVER then the minimum Apl Cf TO is 0ms.
Range: 0 or (Apl Cf TOCalculated) to 3600000 ms.
Factory default is 84000 ms
Arm Select Arm Select Timeout
Maximum time permitted, in milliseconds, between receiving a select
command message and an operate command message from the
master station for the control action to be deemed valid.
Range: 50 to 65535 ms.
Factory default is 10,000 ms
DNP Address DNP3 Station Address
The station address of the controller on the communication link.
Changing this parameter will cause the DNP3 handler task to perform
a warm restart. This will mean a re-initialisation of all communication
parameters such as FCB, sequence numbers, restart internal
indication etc. A temporary loss of communications with the master
station may occur. Also, any queued events will be deleted.
This field is not configurable via WSOS if Nulec DNP3
communications is used.
Range: 0 to 65519
Factory default is 5
Time Dly Rq Time Synchronisation Request Delay
The DNP3 protocol allows for the master station to send time
synchronisation messages independently or at the request of the
controller or both.
Time Dly Rq is the amount of time, in minutes, after the last master
station time synchronisation message that the controller will wait
before setting the Time Synchronisation Required internal indication
bit (IIN1-4). This bit is sent to the master station in every controller
DNP3 message.
If this field is set to 0 then the internal indication bit is never set and
the master station solely determines time synchronisation operation.
Range: 0 65535 minutes
Factory default is 0 minutes
Parameter Description
Unsolicited Enable/Disable Unsolicited Responses
Note 1 If OFF, change of state events are buffered but only sent as
responses to event polls from the master. Any Enable or Disable
Unsolicited Messages commands received by the controller will
result in the controller responding with its Function Code Not
Implemented internal indication bit set.
If ON or FORCED, change of state events are buffered and are
transmitted when:-
A class count is exceeded, or
A class notification delay timer expires, or
As a response to a master station event poll.
When a class count is exceeded, or class notification delay timer
expires, then only the events for that class are transmitted. Any
other classs events remain stored in the controllers buffer.
If the master station issues an Enable or a Disable Unsolicited
Messages command to the controller after the controller has sent
its initial unsolicited Null message then the mode of the controller
will be overridden regardless of ON or FORCED setting.
Note:
1. If ON, the unsolicited reporting ability in the controller is
enabled. The controller will inform the master station of this
ability via an initial unsolicited Null message and will only
transmit unsolicited response change of state events after it
receives an Enable Unsolicited Messages command from the
master station.
Setting this field to ON will mean that the controller DNP3
implementation is compliant with the DNP3-1999+
specification.
2. If FORCED, the controller will transmit unsolicited response
change of state events immediately without waiting for the
Enable Unsolicited Messages command from the master
station.
Parameter Description
Setting this field to FORCED will cause the controller DNP3
implementation to be non-compliant with the DNP3-1999+
specification and is not recommended. This parameter setting
has been provided for compatibility with legacy master station
implementations that are in conflict with the specification.
Range: OFF, ON, FORCED.
Factory default is OFF
Master Addr DNP3 Master Station Address
Note 1 This is the DNP3 address to which the unsolicited responses are
sent.
If the controller is set up to communicate with WSOS using Nulec
DNP3 Radio communications then it is recommended that this
field should not be set to the WSOS DNP3 master address.
Range: 0 to 65519
Factory default is 3.
Unsol Retries Unsolicited Response Number of Retries
Maximum number of attempts to re-transmit an unsolicited
response without getting a confirmation from the master.
Refer to section 5.2.3 below for more information.
This limitation does not apply to an initial unsolicited Null
message. (A DNP3-2000 requirement.)
A value of 0 means that only a single transmission is made and
no re-transmits are attempted.
A value of 255 means unlimited retries ie maximum limit is
disabled.
Range: 0 to 255
Factory default is 255
Unsol Dly Unsolicited Response Retry Delay
If the controller has not received a confirmation from the master
station to an unsolicited response within Apl Cf TO period then
this parameter determines when the next unsolicited response will
be sent.
The Apl Cf TO timer and Unsol Dly timers are started at the same
time ie started immediately after the transmission of the last byte
of a controller message that expects a response from the master.
If Unsol Dly is greater than Apl Cf TO then it will wait until Unsol
Dly seconds after transmission of last message before sending a
retry.
Unsol Dly should never be set to less than Apl Cf TO.
Range: 1 to 86400 seconds
Factory default is 90s
C1 Count Unsolicited Response Class 1 Notification Max Count
The number of events which must occur in Class 1 before they
will be reported.
Parameter Description
Range: 1 to 255
Factory default is 1 event.
C2 Count Unsolicited Response Class 2 Notification Max Count
The number of events which must occur in Class 2 before they
will be reported.
Range: 1 to 255
Factory default is 3 events.
C3 Count Unsolicited Response Class 3 Notification Max Count
The number of events which must occur in Class 3 before they
will be reported.
Range: 1 to 255
Factory default is 5 events.
C1 Delay Unsolicited Response Class 1 Notification Delay
The maximum time an event in this class will wait to be reported.
Range: 1 to 86400 seconds
Factory default is 1s.
C2 Delay Unsolicited Response Class 2 Notification Delay
The maximum time an event in this class will wait to be reported.
Range: 1 to 86400 seconds
Factory default is 5s
C3 Delay Unsolicited Response Class 3 Notification Delay
The maximum time an event in this class will wait to be reported.
Range: 1 to 86400 seconds
Factory default is 10s
C1 Timeout Unsolicited Response Class 1 Notification Time
The number of seconds remaining before an unsolicited response
class 1 transmission. (Display only)
C2 Timeout Unsolicited Response Class 2 Notification Time
The number of seconds remaining before an unsolicited response
class 2 transmission. (Display only)
C3 Timeout Unsolicited Response Class 3 Notification Time
The number of seconds remaining before an unsolicited response
class 3 transmission. (Display only)
C1 Buffered Unsolicited Response Class 1 Buffered Events
The number of queued events in the unsolicited response class 1
buffer. (Display only)
C2 Buffered Unsolicited Response Class 2 Buffered Events
The number of queued events in the unsolicited response class 2
buffer. (Display only)
C3 Buffered Unsolicited Response Class 3 Buffered Events
The number of queued events in the unsolicited response class 3
buffer. (Display only)
Note
1. Changing this parameter will cause the DNP3 handler task to perform a warm restart.
This will mean a re-initialisation of all communication parameters such as FCB,
sequence numbers, restart internal indication etc. A temporary loss of communications
with the master station may occur. Also, any queued events will be deleted.
Point class assignment. The classes shown in the appendices are factory defaults.
The class of each point can be assigned using the WSOS utility on a PC or via a
DNP3 Assign Class commands from the master station.
Parameter Description
Analogue Alarms Analogue Alarming Operation
This field determines if analogue threshold alarming is enabled
or disabled.
If ON, the operation of binary alarm points are enabled. All
alarms are independent of the protocol handler analogue
configuration. eg The event class of the analogues does not
effect alarm operation. Similarly alarming is not effected by
whether the analogues are in the configured Analogue Pnts set.
If OFF, alarms are disabled. All binary alarm points are cleared.
Refer to section 5.3.6 for more information.
Range: OFF, ON
Factory default is OFF
Analogue Pnts Analogue Point Set
This field determines which, if any, of the analogue point
mapping sets are included in the controllers DNP3 Points list. A
summary of all the available mapping permutations is given in
section 5.3.3.
Changing this parameter will cause the DNP3 handler task to
perform a warm restart. This will mean a re-initialisation of all
communication parameters such as FCB, sequence numbers,
restart internal indication etc. A temporary loss of
communications with the master station may occur. Also, any
Parameter Description
queued events will be deleted.
Range: OFF, SMALL, FULL
Factory default is SMALL.
Binary Time Binary Time Tag Usage
Determines whether or not a time tag is included with DNP3
binary change of state events transmitted to a master station by
the controller.
Range: ON, OFF
Factory default is ON.
Analogue Time Analogue Time Tag Usage
Determines whether or not a time tag is included with DNP3
analogue change of state events transmitted to a master station
by the controller.
Range: ON, OFF
Factory default is OFF
Analogue Size Default Analogue Data Object Size
Determines the size of the controller DNP3 default analogue
objects. This size is transmitted by the CAPM for all static and
event data responses where the master does not explicitly ask
for data size.
Range: 16, 32 bits (signed)
Factory default is 16 bit
Analogue Flag Analogue Flag Reporting
Determines whether or not a byte containing the analogues
status data is included with its value in a controller response to a
static data scan.
If ON, the controller will always send a flag of either 0x01 (point
online) or 0x21 (point online and overrange). It is recommended
that this field should only be set ON if the use of the analogue
flag bits is a master station requirement.
Range: ON, OFF
Factory default is OFF
Binary Outputs Binary Output Status Reporting
Determines whether or not the Binary Output status data is
included in a controller response to an integrity poll.
If ON, the controller will always include the Binary Output status
data to the end of an integrity poll response.
Range: ON, OFF
Factory default is OFF
database used by the controllers DNP3 protocol handler and thus determine the size of
an integrity poll response.
ACR
Analogue Binary Point Table(s) Analogue Point Table(s)
Points
OFF Appendix D No analogues
SMALL Appendix D Appendix E
FULL Appendix D Appendix F
LBS
Analogue Binary Point Table(s) Analogue Point Table(s)
Points
OFF Appendix J No analogues
SMALL Appendix J Appendix K
FULL Appendix J Appendix L
The rest of the default data objects used by the controller are:
Binary input status (Object 01 variation 01),
Binary counter status (Object 20 variation 05),
Frozen counter status (Object 21 variation 09), and
Binary output status (Object 10 variation 02).
These object types are not configurable.
Parameter Description
Phase Current Phase Current Default Deadband
The A, B and C phase current analogue inputs will have their
deadband set to this value.
Range: 1 to 999A
Factory default is 10A.
Phase Voltage Phase Voltage Default Deadband
The A, B, and C phase voltage analogue inputs will have their
deadband set to this value. All phase-phase as well as phase-
earth/ground voltages are effected.
Range: 1 to 38000V
Factory default is 100V.
Earth/Gnd Earth/Ground Current Default Deadband
Current The earth/ground current analogue input will have its deadband
set to this value.
Range: 1 to 999A
Factory default is 5A.
System Power System Power Default Deadband
All power analogue inputs will have their deadband set to this
value i.e. KVA, KVAR, and KW.
Range: 1 54000 units
Factory default is 250 units.
A/V/kW
H1
HIGH THRESHOLD HI ALARM ON
H2
LOW + 90% (HIGHLOW) HI ALARM OFF
Time
The protocol handler has four configurable alarm analogue types: phase voltage, phase
current, earth current and system power. Each analogue type has a configurable high
alarm threshold value as well as a configurable low alarm threshold value.
Each of these analogue types also has a pair of binary alarm points in the protocol handler
database. If an analogue value passes the alarm threshold (eg H1 or L1 above) the binary
alarm becomes active. A binary alarm change of state event is put into the DNP3 event
buffers for reporting to the master station.
If, after a HI Alarm, all analogues of the same type are below the high alarm reset
threshold (eg H2 above), then the HI binary alarm is turned off and a binary alarm change
of state is put into the DNP3 event buffers for reporting to the master station.
If, after a LOW Alarm, the analogues of the same type are above the low alarm reset
threshold (eg L2 above), and all other, then the LOW binary alarm is turned off and a
binary alarm change of state is put into the DNP3 event buffers for reporting to the master
station.
Alarming is enabled/disabled via configuration of the protocol handlers Analogue Alarms
field.
Parameter Description
Phase Current Phase Current High Alarm
The A, B and C phase current analogue inputs will have their
high alarm threshold set to this value.
Range: 1 to 999A
Factory default is 999A.
Phase Voltage Phase Voltage High Alarm
The A, B, and C phase voltage analogue inputs will have their
high alarm threshold set to this value.
The type of voltage monitored, phase-phase or phase-
earth/ground, is determined by the configuration of the controller.
Refer to the equipment manual for more information.
Range: 1 to 38000V
Factory default is 38000V.
Earth/Gnd Earth/Ground Current High Alarm
Current The earth/ground current analogue input will have its high alarm
threshold set to this value.
Range: 1 to 999A
Factory default is 999A.
System Power System Power High Alarm
All power analogue inputs will have their high alarm threshold
set to this value i.e. KVA, KVAR, and KW.
Range: 1 54000 units
Note: If a high alarm threshold is set lower than, or equal to, its corresponding low alarm
threshold then the protocol handler will automatically reset the high threshold back to its
previous value.
Parameter Description
Phase Current Phase Current Low Alarm
The A, B and C phase current analogue inputs will have their low
alarm threshold set to this value.
Range: 0 to 998A
Factory default is 0A.
Phase Voltage Phase Voltage Low Alarm
The A, B, and C phase voltage analogue inputs will have their
low alarm threshold set to this value.
The type of voltage monitored, phase-phase or phase-
earth/ground, is determined by the configuration of the controller.
Refer to the equipment manual for more information.
Range: 0 to 37999V
Factory default is 0V.
Earth/Gnd Earth/Ground Current Low Alarm
Current The earth/ground current analogue input will have its low alarm
threshold set to this value.
Range: 0 to 998A
Factory default is 0A.
System Power System Power Low Alarm
All power analogue inputs will have their low alarm threshold set
to this value i.e. KVA, KVAR, and KW.
Range: 0 53999 units
Factory default is 0 units.
Note: If a low alarm threshold is set higher than, or equal to, its corresponding high alarm
threshold then the protocol handler will automatically reset the low threshold back to its
previous value.
6 Physical Layer
6.1 Communications P orts Supported
The controller can communicate to the Master station via one of the following ports.
RS-232 Port P8 (refer to section 6.2)
V23 FSK Port P10 (refer to section 6.3)
6.2 RS-232 Communic ation Specifications
The RS-232 communications on P8 can be configured to in one of three modes:
P8 RS-232 for direct or PSTN/radio modem communications
P8 PAKNET for communications to a PAD on a X.25 network (no service signals)
P8 PAKNET SS for communications to a PAD on a X.25 network using service
signals
The controller uses RTS/CTS hardware handshaking. If not supported by the master then
a loop back is required at the controller end of the communications link.
For P8 RS-232 the DTR is set upon protocol handler start up kept permanently asserted.
For P8 PAKNET and P8 PAKNET SS the DTR line is toggled as described below.
Also, the controller does not support any XON/XOFF software handshaking.
None of these fields are configurable via WSOS if Nulec DNP3 communications is used.
Parameter Description
Port Selection
This field selects the communications medium the DNP3 protocol
uses for transmission.
OFF When OFF is selected, the protocol handler is disabled.
P10 V23 FSK When P10 V23 FSK is selected, the protocol uses the built in
V23 modem on P10. Also, the DNP Communications 1 and 2
pages are automatically updated to reflect relevant FSK data.
Refer to section 6.3 for the P10 configuration details.
Range: OFF, P8 RS-232, P8 PAKNET, P8 PAKNET SS,
P10 FSK V23
Factory default is P8 RS 232
Parameter Description
Protocol Status
Indication of the current status of the communications. (Display
only)
RUNNING RUNNING means that the protocol handler has connected to the
communication port (P8 or P10) and is running.
INACTIVE INACTIVE means that the protocol handler has been disabled via
the OFF state above or has been unable to connect to a
communication port. This is usually caused by another
application already having exclusive access to the port.
Range: INACTIVE, RUNNING
Pre-Tx Pre-Transmission Period
The time delay between asserting RTS to when the message
starts.
Note: CTS must be asserted for transmission to occur else
message is held until it is asserted.
Range: 0 to 1000 ms.
Factory default is 250 ms
Post-Tx Post-Transmission Period
The time after the last character is sent before RTS is negated.
Range: 0 to 1000 ms.
Factory default is 10 ms
Baud Communications Baud Rate
Range: 300, 1200, 2400, 4800, 9600 or 192001 baud.
Factory default is 9600 Baud
PSTN Dial Up Number
Dialup Number The PSTN number that the protocol handler will call when it
needs to send an Unsolicited response. This field supports a
maximum of 18 digits.
Dialling
DISABLED If this field is set to Dialling DISABLED then the protocol will not
try to dial the modem.
Factory is Dialling DISABLED with default number field blank
Pre-amble Preamble Usage
Determines whether the protocol transmits some preamble
characters prior to the start of a protocol message. The message
itself is not otherwise modified. Some modems require these
characters to assist with message reception and synchronisation
at the master station. Start of frame filtering at the master station
ensures identification of the protocol message.
ENABLED ENABLED means that the preamble characters are transmitted
prior to a protocol message.
DISABLED
DISABLED means that protocol message are transmitted without
any preamble characters.
1
19200 baud is only available with CAPM5 controllers.
Parameter Description
Range: ENABLED, DISABLED
Factory default is DISABLED
First Char Preamble First Character
This is the first character to be transmitted as a preamble. The
character is specified by entering its ASCII code in hexadecimal
format.
Range: is 0 to FF hexadecimal.
Factory default is 0x55
Repeat First Number of Preamble First Characters
This is the number of times the first character will be repeated as
part of the preamble.
Eg if all preamble settings are at default values then the
preamble sent is 0x55, 0x55, 0x55, 0xFF
Range: 0 to 20.
Factory default is 3
Last Char Last Preamble Character
This is the last char that will be sent as part of the preamble. The
character is specified by entering its ASCII code in hexadecimal
format.
Range: is 0 to FF hexadecimal.
Factory default is 0xFF
DCD Usage
DCD Ignore If the modem does not support a Data Carrier Detect (DCD)
signal this parameter should be set to DCD Ignore.
Even if the modem does support a DCD signal this parameter is
usually set to DCD Ignore. This is because most point-point
systems using conventional modems run as full duplex so that
the DCD is always asserted during normal operation.
When set to this mode, the protocol uses any received data to
build an incoming packet irrespective of DCD input signal. Also
the protocol will transmit irrespective of the DCD input signal.
If the modem supports a Data Carrier Detect (DCD) signal this
DCD Dont
parameter can be set to DCD Dont Ignore. When set to this
Ignore
mode, the protocol will only read data and build an incoming
protocol packet when DCD is asserted. In addition, the protocol
will not transmit when DCD is asserted. This is necessary for
multi-dropped systems or ones shared with voice users or some
radio-modems.
Range: DCD Ignore, DCD Dont Ignore
Factory default is DCD Ignore
CA Delay Collision Avoidance Delay
On a multidrop communications link this parameter can be used
to provide priority access.
If the controller prepares to transmit and finds the link busy (DCD
Parameter Description
asserted), it waits until it is no longer busy, then waits a back off
time as follows:
Back off time = CA Delay + ([random delay with range 0.0 to 1.0] x CA Delay)
After the back off time the device tries again. If still unsuccessful
then the controller will continue in an indefinite loop until
successful.
If radio modems are used then Tx Delay must be configured to a
value slightly larger than the master stations post-transmission
time. This is necessary to ensure that the incoming messages
tail does not trigger back off operation.
If the DCD usage is configured to DCD Ignore then the back off
time is disabled.
Range: 0 to 180000 milliseconds
Factory default is 1000 ms
Tx Delay Transmission Delay
Additional time in milliseconds between receiving a request and
sending the response.
This field is used when the master station requires time to
disable its transmitter. If collision avoidance delay, CA Delay, is
configured then this field should be set to a value slightly greater
than the master stations post-transmission period.
Range: 0 to 65535 ms.
Factory default is 0 ms
7. RTS is negated
6.2.6 DTR
DTR is asserted by the protocol handler at power-up or upon P8 selection.
Parameter Description
DTR Low Time
DTR Low Time The time that DTR is held low in order to clear a call
Range: 10 to 5000 ms
Factory default is 500 ms
NUA Address PAKNET NUA Address
PAKNET NUA Address for dialing. Supports both short and long
address schemes.
Range: 0 to 99999999999999
Factory default is 0
Tx on line Tx on line Time
The time the call is maintained after the last character is
transmitted. The call is cleared by lowering DTR for a period of
time specified by the DTR Low Time parameter. Calls are only
cleared by the controller if it initiated the call.
Range: 0 to 120 seconds.
Factory default is 5 seconds
Parameter Description
Minimum Retry Time
Min Retry The initial time between retries if a call-out sequence to the master
station fails.
Range: 5 to 86400 seconds
Factory default is 60 seconds
Max Retry Maximum Retry Time
The maximum time allowed between retries if call-out sequences
to the master station continue to fail.
Range: 5 to 86400 seconds
Factory default is 3600 seconds
Multiplier Retry Multiplier
The factor by which the current retry interval is multiplied to obtain
the new retry interval. For example if the multiplier is set to 2 and
the retry interval is initially set to 60 then the second retry will
occur after 120 seconds, the third after 240 seconds etc until the
Max Retry Interval is reached.
Range: 1 to 10
Factory default is 2
Timeout Retry Timeout
The number of seconds remaining before the retry timer expires.
Note: P8 PAKNET assumes immediate low level connection, so
this low-level timeout is unlikely to be used. Higher level DNP
timeouts come into play if there is not a valid P8 PAKNET
connection (eg.DL Cf To).
The delay between retry countdowns is due to multiples of 5sec
waits and DTR low times.
Range: 0 to 86400 seconds
(Display only).
Parameter Description
Port Selection
This field selects the communications medium the DNP3
protocol handler uses for transmission.
Parameter Description
P8 PAKNET When P8 PAKNET is selected, the protocol handler uses the P8
serial port to communicate through an X.25 network via a
PAKNET Pad without using the Service Signals. Refer to
section 6.2 for the P8 configuration details.
When P10 V23 FSK is selected, the protocol uses the built in
P10 V23 FSK
V23 modem on P10. Also, the DNP Communications 1 and 2
pages are automatically updated to reflect relevant FSK data as
detailed below.
Range: OFF, P8 RS-232, P8 PAKNET, P8 PAKNET SS,
P10 V23 FSK
Factory default is P8 RS-232
Protocol Status
Indication of the current status of the communications. (Display
only)
RUNNING RUNNING means that the protocol handler has connected to
the communication port (P8 or P10) and is running.
INACTIVE INACTIVE means that the protocol handler has been disabled
via the OFF state above or has been unable to connect to a
communication port. This is usually caused by another
application already having exclusive access to the port.
Range: INACTIVE, RUNNING
Pre-Tx Pre-Transmission Period
The time delay between keying PTT to when the data is
transmitted.
During this period the carrier is transmitted on the Tx line.
Range: 0 to 1000 ms.
Factory default is 250 ms
Post-Tx Post-Transmission Period
The time after the last character is sent before PTT is negated.
During this period the carrier is transmitted on the Tx line.
Range: 0 to 1000 ms.
Factory default is 35 ms
Busy Sense Polarity of Busy Signal
This field determines the polarity of the input signal from the
radio (P10 pin 6) that the controller uses as BUSY.
LOW LOW means that a low input signal will assert BUSY.
HIGH HIGH means that a high input signal will assert BUSY.
Range: LOW, HIGH
Parameter Description
Factory default is Busy Sense LOW.
Transmission Mode
This field can be used to test the radio transmitter.
Tx NORMAL Tx NORMAL means that the protocol handler controls the radio
for normal DNP3 transmissions.
Tx TEST Tx TEST means that the protocol handler will send continuous
text strings of TX TEST. This string is transmitted as an
asynchronous message with 8 bit, no parity, 1 stop bit, 1 start bit
format.
Range: Tx NORMAL, Tx TEST
Factory default is Tx NORMAL.
BUSY Signal Status
The status of the BUSY signal into the controller (Display only)
Rx IDLE, Rx IDLE indicates that the signal is in the not BUSY state.
Rx BUSY Rx BUSY Asserted indicates that the signal is in the BUSY
state. This usually means that the radio squelch has opened.
Range: Rx IDLE, Rx BUSY
Pre-amble Preamble Usage
ENABLED When ENABLED the protocol handler inserts a string of
characters in front of a message packet. The message frame is
otherwise not affected. Start of frame filtering at the master
station will ensure identification of the message. This parameter
is sometimes required for modems to aid with their keying.
DISABLED When DISABLED the protocol handler does not insert any
preamble characters.
Range: ENABLED, DISABLED
Factory default is DISABLED
First Char Preamble First Character
This is the first character to be transmitted as a preamble. The
character is specified by entering its ASCII code in hexadecimal
format.
Range: is 0 to FF hexadecimal.
Factory default is 0x55
Repeat First Number of Preamble First Characters
This is the number of times the first character will be repeated
as part of the preamble.
Eg if all preamble settings are at default values then the
preamble sent is 0x55, 0x55, 0x55, 0xFF
Range: 0 to 20.
Factory default is 3
Last Char Last Character of Preamble
This is the last char that will be sent as part of the preamble.
The character is specified by entering its ASCII code in
Parameter Description
hexadecimal format.
Range: is 0 to FF hexadecimal.
Factory default is 0xFF
DCD Usage
DCD Ignore The DCD Ignore mode is used when there is no busy signal
available. eg A twisted pair link. To operate in this mode the
Busy Sense needs to be set to HIGH so that the receiver is
busy at all times. When set to this mode, the protocol uses any
received data to build a DNP3 packet. The protocol is able to
DCD Dont Ignore transmit at any time.
The DCD Dont Ignore mode is the normal operating mode for
radio systems that have a busy signal available. When set to
this mode, the protocol will only read data and build a DNP3
packet when busy is asserted. Also, the protocol will not
transmit when busy is asserted. This reduces clashes with voice
users.
Factory default is DCD Dont Ignore
CA Delay Collision Avoidance Delay
On a multidrop communications link this parameter can be used
to provide priority access.
If the controller prepares to transmit and finds the link busy
(DCD asserted), it waits until it is no longer busy, then waits a
back off time as follows:
Back off time = CA Delay + ([random delay with range 0.0 to 1.0] x CA Delay)
After the back off time the device tries again. If still unsuccessful
then the controller will continue in an indefinite loop until
successful.
If radio modems are used then Tx Delay must be configured to a
value slightly larger than the master stations post-transmission
time. This is necessary to ensure that the incoming messages
tail does not trigger back off operation.
If the DCD usage is configured to DCD Ignore then the back off
time is disabled.
Range: 0 to 180000 milliseconds
Factory default is 1000 ms
Tx Delay Transmission Delay
Additional time in milliseconds between receiving a request and
sending the response.
This field is used when the master station requires time to
disable its transmitter. If collision avoidance delay, CA Delay, is
configured then this field should be set to a value slightly greater
than the master stations post-transmission period.
Range: 0 to 65535 ms.
Parameter Description
Factory default is 0 ms
Statistic Description
Tx Count Transmission Message Count
The number of DNP3 datalink messages transmitted from this
recloser into the DNP3 link.
Range: 0 to 32768
Rx Count Receive Message Count
The number of DNP3 datalink messages received by this
recloser from the DNP3 link.
Range: 0 to 32768
All of the above counters are zeroed when: the controller is reset; a DNP3 cold or warm
restart message is received; or a configuration parameter is changed that triggers a DNP3
handler warm restart; or the reset all button is selected in Windows SOS.
Any field can be cleared via the operator control panel by selecting it and pressing either
the left or right keys.
All communication statistic parameters are not password protected.
The controller implementation complies with the DNP3 Subset Definitions document.
Additional implementation information is given in this section.
The DNP3 device profile defines the mapping of all data points used, in the standard
format recommended by the DNP3 users group.
Conforms to DNP3 level 2 subset definition requirements with many additional level 3 features built
in.
These extra features include the parsing of read requests (FC 1) for the following objects and/or
qualifiers:
Binary Input (Object 1 Variations 0 Qualifiers 00, 01,07,08,17,28)
Binary Input (Object 1 Variation 1 Qualifiers 00, 01, 06,07,08,17,28)
Binary Output (Object 10 Variation 0 Qualifiers 00, 01, 07, 08, 17, 28)
Binary Output (Object 10 Variation 2, Qualifiers 00, 01, 06, 07, 08, 17, 28)
Binary Counter (Object 20 Variation 6 Qualifiers 00, 01, 06, 07, 08, 17, 28)
Frozen Counter (Object 21 Variation 10 Qualifiers 00, 01, 06, 07, 08, 17, 28)
Analogue Input (Object 30 Variation 0, Qualifiers 00, 01, 07, 08, 17, 28)
Analogue Input (Object 30 Variations 1, 2, 3, 4 Qualifiers 00, 01, 06,07,08,17,28)
Analogue Change Event (Object 32 Variations 1, 2, 3, 4 Qualifiers 06, 07, 08)
Analogue Input Deadband (Object 34 Variations 1, 2, Qualifiers 00, 01, 06,07,08,17,28)
Analogue Output Status (Object 40 Variation 1, 2 Qualifiers 00, 01,07,08,17,28)
Analogue Output Block (Object 41 Variation 1, 2 Qualifiers 00, 01, 07, 08, 17, 28)
Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):
Transmitted: 292 Transmitted: 2048
Received: 292 Received: 249
Maximum Data Link Retries: Maximum Application Layer Retries:
Configurable 0..255 None
Requires Data Link Layer Confirmation:
Configurable, 3 settings Never, Always, Sometimes (on multi frame fragments only)
Sometimes (only when reporting event data or when sending multifragment responses)
20,,21
60 2 Class 1 Data 1 06, 07, 08 N/A N/A
20,,21, 22
60 3 Class 2 Data 1 06, 07, 08 N/A N/A
20, 21, 22
60 4 Class 3 Data 1 06, 07, 08 N/A N/A
20, 21, 22
80 1 Internal Indications 2 00 index = 7 N/A N/A
112 Virtual Terminal Output Block 2 00, 01, 06, N/A N/A
Note 5 08, 17, 28
113 Virtual Terminal Event Data 1 06, 07, 08 129 17, 28
No Object 13 14 23 N/A N/A N/A
Note
1. All shaded areas are the additional level 3 or above function, objects, variations and/or qualifiers supported
by controller.
2. Bold italics response function codes represent controller default objects. These are the object variations that
the controller will issue as in its response to an event (class 1, 2, 3) poll, an integrity (class 1, 2, 3, 0) poll, in
a response to a variation 0 read request, or in an unsolicited response message. Where more than one
data object variation is highlighted then default object can be configured. Selection of default objects is
explained in section 5.3.
3. All Request and Response options marked N/A are Not Applicable.
4. For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent
with qualifiers 17 or 28, respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06,
07, or 08, will be responded with qualifiers 00 or 01. (For change-event objects, qualifiers 17 or 28 are
always responded.)
5. The Virtual Terminal Objects (112 and 113) are used to transport SOS data between WSOS and the
controller. No other data is supported.
6. A write with an analogue input deadband value of zero will be rejected. The response will have the
parameter in qualifier, range or data field not valid or out of range internal indicator bit (IIN2-2) set.
Note
1. When a cold or warm restart command is received by the controller it will restart the DNP3 protocol handler
only. The CAPM itself does not restart.
It is recommended by the DNP3 User Group that master stations do not ask for a data link acknowledgement
nor an application confirm on restart commands (refer to Cold/Warm Restart Sequence, Technical Bulletin
9701-003)
The controller reports a time object of 500ms for both restart types. The master station should not initiate any
message sequences for this period. However, if the controller has unsolicited messages configured ON then it
will automatically establish communications on restart. This may be within the 500ms period.
DNP3 Qualifiers
Qualifier Use in a Request Use in a Response
(Hex)
00, 01 A range of static points, or a single point with a Static Objects
point number.
Object headers use either 8 bit (Q=00) or 16 bit
(Q=01) start and stop range indices.
06 All points. Not valid
Object headers and data sizes are determined by
controller configured parameters.
07, 08 A limited quantity of events or a single point with A single point with no number (eg Time and Date)
no number (eg Time and Date).
Object headers have either 8 bit quantity fields
(Q=07) or 16 bit quantity fields (Q=08).
17, 28 Controls (usually one or more unrelated points) Event objects (usually one or more unrelated
Object headers have either 8 bit quantity field with points)
8 bit indices (Q=17) or 16 bit quantity field with 16
bit indices (Q=28)
Response
Controller Control Response Description
Status Value
0 Control request accepted
1 Control request denied. Select/Operate timed out. The time out parameter is configurable.
2 Control request denied. Operate without select message OR operate/select application
sequence number mis-match.
3 Control request denied. Formatting error
4 Control request denied. Control operation not supported
Examples:
Trip control sent to a point that supports only Pulse or Latch operations. The supported
operations are indicated on a per point basis in the table in Appendix H or Appendix N.
The binary output (or analogue output) point number is out of range.
The analogue output value is out of range.
5 Control request denied. Already Active
6 Control request denied. Control rejected by controller because of an underlying condition
preventing the action. These conditions are indicated on a per point basis in the table in
Appendix H or Appendix N.
All binary output points have a matching binary input status point. The master station must always use the
corresponding binary status for the control to verify the success of the action.
Note:
1) It is Nulec policy that all technical bulletin rules that are required for the controller to be DNP33 level 2
compliant are implemented.
2) The following data types are not used by the controller:-
File transfer objects
String objects
Analogue input floating point and analogue output floating point objects
Variable arrays objects
8 bit unsigned integer objects
Cleared = 0
Comment
Accuracy
W Series
DNP3 ID
Set = 1
Name
Class
Time
and
0 Abnormal Y 1 For any of the None of the specified This flag shows that the
Operator following conditions:- conditions are true operator has the ACR in an
conditions Trip or Close abnormal state such as work
Isolated, tag applied. This means that it
will operate differently to its
ACR
normal mode of operation.
Mechanically
locked open (if 500ms
applicable)
Work Tag
Applied
1 ACR Tripped Y 1 ACR Tripped ACR not Tripped These are repeats of the
(open) mechanism travel switches.
2 ACR Closed Y 1 ACR Closed ACR not Closed When the ACR is disconnected
from the control cubicle they are
both cleared.
500ms
3 Controller Y 2 LOCAL control LOCAL Control The controller is either in
Mode Disabled Enabled LOCAL or Remote Controller
Remote control Remote Control Mode. This affects the closing
Enabled Disabled command the permission to
set/remove work tag.
500ms
4 Maintenance Y 1 For any of the No maintenance The controller has detected one
Required following conditions:- required or more conditions which
Battery not require maintenance.
normal This point cannot become Set
Capacitor charge until at least five minutes after
failure controller start.
Low power mode 500ms
Low SF6 gas
pressure (if
applicable)
ACR data not
valid (includes
connection to an
N00-324 R39 44
DNP V3.00 Protocol Technical Manual (ACR)
Cleared = 0
Comment
Accuracy
W Series
DNP3 ID
Set = 1
Name
Class
Time
and
invalid switch
type)
Any vacuum
interrupter
contact life is
less than 20%
Mechanical
failure
5 Work Tag Y 2 Work Tag Applied Work Tag Removed The controller can have a work
tag. This affects the closing
command
500ms
6 Prot A Active Y 2 Protection Group A is Protection Group A is not
active active
7 Prot B Active Y 2 Protection Group B is Protection Group B is not
active active
8 Prot C Active Y 2 Protection Group C is Protection Group C is not Only one protection group is
active active active at any one time.
9 Prot D Active Y 2 Protection Group D is Protection Group D is not
active active
10 Prot E Active Y 2 Protection Group E is Protection Group E is not 500ms
active active
11 Prot F Active Y 2 Protection Group F is Protection Group F is not
active active
12 Prot G Active Y 2 Protection Group G is Protection Group G is
active not active
13 Prot H Active Y 2 Protection Group H is Protection Group H is not
active active
14 Prot I Active Y 2 Protection Group I is Protection Group I is not
active active
15 Prot J Active Y 2 Protection Group J is Protection Group J is not
active active
16 Earth / Ground N 2 Earth / Ground Earth / Ground 500ms
Protection Protection ON Protection OFF
Enabled
17 SEF/SGF N 2 SEF/SGF protection SEF/SGF protection 500ms
Protection ON OFF
Enabled
18 Auto Reclose Y 2 Auto Reclose ON Auto Reclose OFF 500ms
19 Cold Load Idle Y 2 Cold Load is Idle or is Cold load is NOT Idle. 500ms
turned off. This means that the
This means that the threshold multiplier is
threshold multiplier is being raised by the cold
not being affected by load pickup function in
the cold load order to pick up cold
function. load.
20 High Current Y 2 High Current Lockout High Current Lockout 500ms
Lockout Protection ON Protection OFF
21 Loss of Phase N 2 Loss of Phase Loss of Phase Protection 500ms
Protection Protection ON OFF
Cleared = 0
Comment
Accuracy
W Series
DNP3 ID
Set = 1
Name
Class
Time
and
22 Sequence Y 2 Sequence Control Sequence Control OFF 500ms
Control ON
23 Live Load Y 2 Live Load blocking Live Load blocking OFF 500ms
blocking ON
24 Protection Y 2 Protection Enabled Protection turned OFF 500ms
enable
25 Switchgear Y 3 Set for Load Break Clear For Recloser
Family Switch 500ms
26 Power Flow Y 2 Source X, Load I Source I, Load X The power flow direction
Direction (source/load designation) is
determined by the user. Refer
to the Power Flow Direction
binary output for more
information
500ms
Protection Trip Operation Flags
This group of points indicates what happened in the last protection sequence. For example the recloser may have
tripped, closed, tripped again and locked out. Or it may have tripped, closed and stayed closed because the fault
was cleared.
In both cases the flags below are set to show the causes of the trips and whether the lockout state has been
reached or not.
A set of flags is available for each trip in a protection sequence.
In addition analogue data is available which shows the fault currents which occurred during the sequence and the
number of trips which took place (refer Appendix F)
Note that a sequence starts when there is a protection trip or a sequence advance.
Most of these flags are cleared either by protocol command or when the switchgear is tripped/closed by the
operator or when a new protection sequence starts.
This data is volatile i.e. it is zeroed on controller software reset.
General Protection Flags
27 Sequence in Y 1 Start of sequence This shows that a protection
Progress That is a protection sequence has started and not
trip or sequence yet completed.
advance has End of sequence. Either Note that operator trip does not
occurred. lockout or reclaim. cause a sequence in progress.
Event time is the time of the trip
or sequence advance.
10ms
Cleared = 0
Comment
Accuracy
W Series
DNP3 ID
Set = 1
Name
Class
Time
and
28 Protection Y 1 End of sequence, All fault flags are cleared This shows that the protection
Data Valid either lockout or by one of the following sequence is over and the other
reclaim actions :- flags are set.
Reset Fault Flags This could be used to drive an
and Currents operator alarm at the SCADA
protocol control system to alert him to the fact
command that a protection sequence has
Any Operator Close occurred. Note that operator trip
action alone does not cause a
Controller software protection data valid
reset (data is Event time is the time of lockout
volatile) or reclaim.
At the time of the
next trip the flags 10ms
29 Single Shot Y 1 Single Shot are refreshed atOne flag only provided because
Protection Protection was active this time old flags
a single shot trip forces lockout.
at the time of the trip. are cleared and the
Event time is the time of the
cause of the mostpickup.
recent protection 10ms
operation set.
30 Loss Of Phase Y 1 Trip was caused by One flag only provided because
Trip Loss of Phase Protection turned LOP protection forces lockout.
Protection ON
Event time is the time of the trip.
10ms
31 Loss Of Phase Y 1 Phase A was lost at Set if A Phase is lost at time of
- Phase A time of Loss of Phase Loss of Phase trip
trip 10ms
32 Loss Of Phase N 1 Phase B was lost at Set if B Phase is lost at time of
- Phase B time of Loss of Phase Loss of Phase trip
trip 10ms
33 Loss Of Phase N 1 Phase C was lost at Set if C Phase is lost at time of
-Phase C time of Loss of Phase Loss of Phase trip
trip 10ms
34 High Current Y 1 All fault flags are cleared One flag only because High
Lockout by one of the following Current Lockout forces lockout
actions :- Time stamp as for flags above.
Reset Fault Flags Event time is the time of the
and Currents lockout event.
The high current
lockout function protocol control 10ms
forced the controller command
to lockout during the Any Operator Close
last protection action
sequence Controller software
reset (data is
volatile)
Start of a new
sequence
35 Lockout Y 1 The controller is in Cleared by any close This flag shows that the
lockout action controller is in lockout.
Therefore no auto-reclosing will
take place.
Cleared = 0
Comment
Accuracy
W Series
DNP3 ID
Set = 1
Name
Class
Time
and
If the ACR is closed this flag will
be clear. Therefore when this
flag is clear and the ACR is
closed it indicates that the
protection sequence cleared the
fault. Event time is the time of
the trip
10ms
36 Operator Trip Y 1 The most recent trip Cleared by any close One flag only because operator
was caused by a action trip forces lockout.
local or remote
Event time is the time of the trip
operator (eg IOEX,
Protocol, or panel) 10ms
Protection Trip 1
37 Phase Over Y 0 Trip was caused by All fault flags are cleared
Current Trip Phase Overcurrent by one of the following
Protection actions :-
Reset Fault Flags 10ms
and Currents
protocol control
command
38 Earth / Ground N 0 Trip was caused by
Over Current Earth / Ground Any Operator Close
10ms
Trip Overcurrent action
Protection
39 SEF/SGF N 0 Trip was caused by
controller software
Over Current Sensitive Earth /
reset (data is 10ms
Trip Ground Fault
volatile)
Protection
40 Sequence Y 0 Sequence advance Start of a new
10ms
Advance occurred. sequence
Protection Trip 2
41 Phase Over Y 0 Trip was caused by All fault flags are cleared
Current Trip Phase Overcurrent by one of the following
Protection actions :-
Reset Fault Flags 10ms
and Currents
protocol control
command
42 Earth / Ground N 0 Trip was caused by
Over Current Earth / Ground Any Operator Close
10ms
Trip Overcurrent action
Protection
43 SEF/SGF N 0 Trip was caused by
controller software
Over Current Sensitive Earth /
reset (data is 10ms
Trip Ground Fault
volatile)
Protection
44 Sequence Y 0 Sequence advance Start of a new
10ms
Advance occurred. sequence
Protection Trip 3
Cleared = 0
Comment
Accuracy
W Series
DNP3 ID
Set = 1
Name
Class
Time
and
45 Phase Over Y 0 All fault flags are cleared
Current Trip by one of the following
Trip was caused by actions :-
Phase Overcurrent Reset Fault Flags 10ms
Protection and Currents
protocol control
command
46 Earth / Ground N 0 Trip was caused by
Over Current Earth / Ground Any Operator Close
10ms
Trip Overcurrent action
Protection
47 SEF/SGF N 0 Trip was caused by
controller software
Over Current Sensitive Earth /
reset (data is 10ms
Trip Ground Fault
volatile)
Protection
48 Sequence Y 0 Sequence advance Start of a new
10ms
Advance occurred. sequence
Protection Trip 4
49 Phase Over Y 0 All fault flags are cleared
Current Trip by one of the following
Trip was caused by actions :-
Phase Overcurrent Reset Fault Flags 10ms
Protection and Currents
protocol control
command
50 Earth / Ground N 0 Trip was caused by
Over Current Earth / Ground Any Operator Close
10ms
Trip Overcurrent action
Protection
51 SEF/SGF N 0 Trip was caused by
controller software
Over Current Sensitive Earth /
reset (data is 10ms
Trip Ground Fault
volatile)
Protection
52 Reserved N 0 Start of a new
Always 0
sequence
Accumulated Protection Trip Operation Flags
Multiple Flags can be set in this section because they accumulate all the trips in the sequence
53 Phase Over Y 1 One or more trips All fault flags are cleared
Current Trip were caused by by one of the following
Phase Overcurrent actions :-
.
Protection Reset Fault Flags
10ms
and Currents
protocol control
command
54 Earth / Ground N 1 One or more trips
Over Current were caused by
Any Operator Close
Trip Earth / Ground 10ms
action
Overcurrent
Protection
Cleared = 0
Comment
Accuracy
W Series
DNP3 ID
Set = 1
Name
Class
Time
and
55 SEF/SGF N 1 One or more trips
Over Current were caused by controller software
Trip Sensitive Earth / reset (data is 10ms
Ground Fault volatile)
Protection
56 Sequence Y 1 One or more
Start of a new
Advance sequence advances 10ms
sequence
occurred.
End of Protection Flags
57 Close Isolate Y 2 Close Isolate Switch Close Isolate Switch Shows the state of the Trip &
OFF/ISOLATE(i.e. ON/ENABLE (i.e. Close Close isolate switches on the
Close is disabled) is enabled) control panel
58 Trip Isolate Y 1 Trip Isolate Switch Trip Isolate Switch 10ms
OFF (i.e. Trip is ON(i.e. Trip is enabled)
disabled)
59 Locked Y 1 ACR Locked Open ACR not locked open Shows that the ACR is
mechanically and electrically
locked in the open position. Not
supported on the N-Series
where it will always be zero.
10ms
60 ACR Memory Y 2 ACR Memory Data ACR Memory Data Valid Shows that the controller has
Data Invalid not valid retrieved the data from the ACR
memory. When invalid the
switchgear attributes and the
gas pressure are zeroed,
500ms
61 Auxiliary Y 2 Auxiliary supply has Auxiliary supply is 500ms
Supply failed normal
Fail
62 Switchgear Y 2 Switch disconnected Switch connected from
Shows the connection state of
Connection from control cubicle. control cubicle. the cable between the
switchgear and the controller.
When connected to the ACR
Trip, Close and Locked
indications are valid.
When disconnected from the
ACR data will be forced invalid
500ms
63 SF6 Gas N 2 Gas pressure Low or Gas Pressure Normal, or Only set when switchgear is
Pressure Low Invalid Not Known, or Not a connected and ACR memory
or Invalid switchgear which has data is valid and switchgear
SF6. type has SF6.
500ms
64 Battery Supply Y 2 Battery supply not Battery supply normal 500ms
normal.
This includes :-
Battery Off
Battery Overvolt
Battery Low Volts
Cleared = 0
Comment
Accuracy
W Series
DNP3 ID
Set = 1
Name
Class
Time
and
65 Contacts Life Y 2 When any vacuum When all vacuum 500ms
Low interrupter contact life interrupters have contact
is less than 20%. life >= 20%
66 Reserved N 2
67 Capacitor Y 2 Capacitor Charge Capacitor Charge OK The Trip/Close Capacitors have
Charge Failed failed to charge
Failure 500ms
68 Mechanism Y 2 Mechanism Failure Mechanism OK The switchgear has failed to
Failure Trip or Close electrically
500ms
69 Phase Ai Live Y 1 Phase is live Phase is dead Shows if the phase bushings
70 Phase Bi Live N 1 are above or below the live line
71 Phase Ci Live N 1 threshold.
72 Phase Ax Live Y 1
Note 3
73 Phase Bx Live N 1
Note 3
74 Phase Cx Live N 1 10ms
Note 3
75 Source Y 1 Shows that any of the All of the source side are Note that these points are
Voltage Status three phases of the Terminals dead different to the Load/Source
76 Load Voltage Y 1 designated Source Live/Dead events in the
side or Load side are All of the load side are controller event record
Status
live. Terminal dead
Note 3 10ms
77 Load Current Y 1 Current of 2.5A or Current of less than 2.5A
On more is flowing in at is flowing in all three 10ms
least one phase phases
78 Loop Auto On Y 2 Loop Automation is Loop Automation is Off Note 1
On 500ms
79 Loop Auto Y 2 Loop Auto Restore is Loop Auto Restore is Off Note 1
Restore On On 500ms
80 Loop Auto Y 2 The Tie recloser is The Tie Recloser will Note 1, 2
Tie Restore configured to restore only restore supply to its 500ms
On supply in both Load side or the
directions Recloser type is not set
to Tie
81 Loop Auto Y 2 Recloser type is set Recloser type is not set Note 1
Type Feeder to Feeder to Feeder 500ms
82 Loop Auto Y 2 Recloser type is set Recloser type is not set Note 1
Type Midpoint to Midpoint to Midpoint 500ms
83 Loop Auto Y 2 Recloser type is set Recloser type is not set Note 1
Type Tie to Tie to Tie 500ms
84 Reserved N Reserved Reserved
Cleared = 0
Comment
Accuracy
W Series
DNP3 ID
Set = 1
Name
Class
Time
and
87 Loop Auto Y 2 Set when Loop Normal state, cleared on Note 1
Close Request Automation issues a next internal scan after 10ms
Close Request. set
88 Dummy Circuit Y 2 DCB Closed DCB Not Closed The dummy circuit breaker is
Breaker an internal point useful for
Closed SCADA system testing. The
value of the DCB is non-volatile.
500ms
89 Automatic N 2 APGS is ON APGS is OFF 500ms
Protection
Group
Selection
90 Supply Y 2 Supply Outage Supply Outage 500ms
Outage Measurement ON Measurement OFF
Measurement
91 Door Open N 2 Cubicle Door Open Cubicle Door Closed This point only valid if hardware
option installed.
10ms
92 Phase Current Y 2 Phase Current Alarm Phase Current Alarm 500ms
HI Alarm ON OFF
93 Phase Current Y 2 Phase Current Alarm Phase Current Alarm 500ms
LOW Alarm ON OFF
94 Phase Voltage Y 2 Phase Voltage Alarm Phase Voltage Alarm 500ms
HI Alarm ON OFF
95 Phase Voltage Y 2 Phase Voltage Alarm Phase Voltage Alarm 500ms
LOW Alarm ON OFF
96 Earth Current N 2 Earth Current HI Earth Current HI Alarm 500ms
HI Alarm Alarm ON OFF
97 Earth Current N 2 Earth Current LOW Earth Current LOW 500ms
LOW Alarm Alarm ON Alarm OFF
98 System Power Y 2 System Power HI System Power HI Alarm 500ms
HI Alarm Alarm ON OFF
99 System Power Y 2 System Power LOW System Power LOW 500ms
LOW Alarm Alarm ON Alarm OFF
100 Auxiliary Y 2 Auxiliary Supply has Auxiliary Supply has 500ms
Supply Fail failed for more than been restored for more
(Delayed) 120 seconds than 20 seconds
101 Most Recent Y 1 Set if the most recent All fault flags are cleared 10ms
Trip Phase A trip was caused by a by one of the following
Overcurrent A Phase Overcurrent actions :-
Protection Trip Reset Fault Flags
and Currents
protocol control
command
102 Most Recent Y 1 Set if the most recent Any Operator Close 10ms
Trip Phase B trip was caused by a action
Overcurrent B Phase Overcurrent
Protection Trip
Cleared = 0
Comment
Accuracy
W Series
DNP3 ID
Set = 1
Name
Class
Time
and
103 Most Recent Y 1 Set if the most recent Protection turned 10ms
Trip Phase C trip was caused by a ON
Overcurrent C Phase Overcurrent
Protection Trip
104 Instantaneous Y 1 The peak current for At the time of next 10ms
Most Recent the most recent trip trip - the flags are
Trip was greater than the refreshed
instantaneous setting
105 Under Y 1 Under frequency Under frequency Note 4. 500ms
Frequency protection ON protection OFF
106 Over Y 1 Over frequency Over frequency Note 4. 500ms
Frequency protection ON protection OFF
107 Normal Y 1 Enable Normal Enable Normal Note 4. 500ms
Frequency Frequency Close Frequency Close
Close protection ON protection OFF
108 Source Dead Y 1 Source Dead Source Dead Protection Note 5 500ms
Protection Protection ON OFF
109 Source Dead Y 1 Set if a lockout Cleared by: Note 5 10ms
Lockout caused by the Dead protocol command
Lockout feature
any operator close
occurred.
or operator trip. This
includes remote
control commands.
Start of a new
sequence.
110 Work Tag Trip Y 1 Work Tag Protection All fault flags are cleared One flag only provided because
was active at the time by one of the following a work tag trip forces lockout.
of the trip. actions :- Event time is the time of the
Reset Fault Flags pickup.
and Currents 10ms
protocol control
command
Any Operator Close
action
controller software
reset (data is
volatile)
Start of a new
sequence
111 IOEX Input 1 Y 1 Input state for IOEX Input asserted Input not asserted
input 1
112 IOEX Input 2 Y 1 Input state for IOEX Input asserted Input not asserted
input 2
113 IOEX Input 3 Y 1 Input state for IOEX Input asserted Input not asserted
input 3
114 IOEX Input 4 Y 1 Input state for IOEX Input asserted Input not asserted
input 4
115 IOEX Input 5 Y 1 Input state for IOEX Input asserted Input not asserted
input 5
Cleared = 0
Comment
Accuracy
W Series
DNP3 ID
Set = 1
Name
Class
Time
and
116 IOEX Input 6 Y 1 Input state for IOEX Input asserted Input not asserted
input 6
117 IOEX Input 7 Y 1 Input state for IOEX Input asserted Input not asserted
input 7
118 IOEX Input 8 Y 1 Input state for IOEX Input asserted Input not asserted
input 8
119 IOEX Input 9 Y 1 Input state for IOEX Input asserted Input not asserted
input 9
120 IOEX Input 10 Y 1 Input state for IOEX Input asserted Input not asserted
input 10
121 IOEX Input 11 Y 1 Input state for IOEX Input asserted Input not asserted
input 11
122 IOEX Input 12 Y 1 Input state for IOEX Input asserted Input not asserted
input 12
123 Most recent Y 1 Set if the most recent Cleared by one of the One flag only provided because
trip Under trip was caused by following: there is no auto reclose after a
Frequency an Under Frequency protocol command frequency trip.
condition 10ms
any operator close
124 Most recent Y 1 Set if the most recent or operator trip. This
trip Over trip was caused by includes remote
Frequency an Over Frequency control commands.
condition Start of a new
sequence.
125 Operator Y 1 Set if the most recent Cleared by: 10ms
Close close caused by local ! 'Reset Flags and
or remote panel close Currents' protocol
request. command
126 IOEX Close Y 1 Set if the most recent ! Controller Software 10ms
close caused by an Reset (data is
IOEX close input. volatile)
127 Protocol Close Y 1 Set if the most recent 10ms
! At the time of the
close caused by a
next Close
protocol close
request.
128 Automation Y 1 Set if the most recent 10ms
Close close caused by a
Distributed
Automation close
request (ie Loop
Automation or Auto
Changeover).
129 Normal Y 1 Set if the most recent 10ms
Frequency close caused by
Close Normal Frequency
close request
Cleared = 0
Comment
Accuracy
W Series
DNP3 ID
Set = 1
Name
Class
Time
and
130 External Close Y 1 Set if any of the 10ms
following caused the
most recent close
CCEM external
button on N-
Series
Mechanical
action. The
switchgear
detected as
closed without a
close request
Electrical action
(only available
on the Advanced
controller)
131 ACO N 2 ACO Autorestore ON ACO Autorestore OFF Whether to automatically
Autorestore change back to master supply if
it returns live.
500ms
132 Auto N 2 Auto-changeover is Auto-changeover is Turn ACO on/off
Changeover enabled disabled 500ms
Enable
133 Auto N 2 Break before Make. Make before Break.
Changeover 500ms
Mode
134 ACO Rank N 2 ACO Master ACO Slave 500ms
135 Live Load Y 1 Live Load Blocking Live Load Blocking 10ms
Blocking Active Inactive
136-160 Reserved
Note:
1. These point are only valid when the Loop Automation option is enabled for the current configuration and
are otherwise always reported as OFF (0).
2. The power flow direction (source/load designation) is determined by the user. Refer to the Power Flow
Direction binary input for status and binary output for control.
3. Not available on standard U-series ACR without external CVTs, value will always be 0.
4. Not available on CAPM4 controllers
5. Only available in Version 26 onwards.
Dead Band
W Series
DNP3 ID
Default
Name
Class
Units
Max
Min
Dead Band
W Series
DNP3 ID
Default
Name
Class
Units
Max
Min
10 Earth / Ground Fault N 0 16000 1A 1A 1
Current - Written on a G-
Max event. This includes
SEF/SGF Fault currents.
11 During a protection Y 1 4 1 1 1
sequence the value
increments indicating the
current trip or sequence
advance.
After a protection sequence
the final trip or sequence
advance that occurred.
12 Protection Group that was Y 0 9 1 1 1
in service at the start of the
sequence
0 = Group A
1 = Group B
9 = Group J
Voltage Measurements
Voltage measurements are provided for all terminals with voltage measurements. This varies depending upon
the model of ACR.
All x side voltages are not available in standard U-series ACR without external CVTs. Value always zero.
The source/load designation of the voltages is determined by the user. Refer to the Power Flow Direction
binary input for status and binary output for control.
13 Ai Phase-(Earth / Ground) Y 0 30000 1V 100 V. 2
Voltage
14 Bi Phase-(Earth / Ground) N 0 30000 1V 100 V. 2
Voltage
15 Ci Phase-(Earth / Ground) N 0 30000 1V 100 V. 2
Voltage
16 Ax Phase-(Earth / Ground) Y 0 30000 1V 100 V. 2
Volts Note 3
17 Bx Phase-(Earth / Ground) N 0 30000 1V 100 V. 2
Volts Note 3
18 Cx Phase-(Earth / Ground) N 0 30000 1V 100 V. 2
Volts Note 3
19 to 69 Reserved
Note
1. The deadband for all analogue points can be configured, refer section 5.3.5 for more information.
2. These points may exceed the 16 bit limit and can be obtained using 32 bit analogue input objects.
3. Not available on standard U-series ACR without external CVTs, value will always be 0.
Dead Band
W Series
DNP3 ID
Default
Class
Units
Max
Min
Name
Dead Band
W Series
DNP3 ID
Default
Class
Units
Max
Min
Name
9 C Fault Current Written N 0 16000 1A 1A 1
on a C-Max event.
Note 10
10 Earth / Ground Fault N 0 16000 1A 1A 1
Current - Written on a G-
Max event. This includes
SEF/SGF Fault currents.
11 During a protection Y 1 4 1 1 1
sequence the value
increments indicating the
current trip or sequence
advance.
After a protection sequence
the final trip or sequence
advance that occurred.
12 Protection Group that was Y 0 9 1 1 1
in service at the start of the
sequence
0 = Group A
1 = Group B
9 = Group J
Voltage Measurements
Voltage measurements are provided for all terminals with voltage measurements. This varies
depending upon the model of ACR.
All x side voltages are not available in standard U-series ACR without external CVTs. Value always
zero.
The source/load designation of the voltages is determined by the user. Refer to the Power Flow
Direction binary input for status and binary output for control.
All voltages have a common deadband which can be configured (refer section 5.3.5).
13 Ai Phase-(Earth / Ground) Y 0 30000 1V 100 V. 2
Voltage
14 Bi Phase-(Earth / Ground) N 0 30000 1V 100 V. 2
Voltage
15 Ci Phase-(Earth / Ground) N 0 30000 1V 100 V. 2
Voltage
16 Ax Phase-(Earth / Ground) Y 0 30000 1V 100 V. 2
Volts
Note 10
17 Bx Phase-(Earth / Ground) N 0 30000 1V 100 V. 2
Volts
Note 10
18 Cx Phase-(Earth / Ground) N 0 30000 1V 100 V. 2
Volts
Note 10
19 A-Bi Phase-Phase Voltage N 0 38000 1V 100 V. 2
Note 2
20 B-Ci Phase-Phase Voltage N 0 38000 1V 100 V. 2
Note 2
21 C-Ai Phase-Phase Voltage N 0 38000 1V 100 V. 2
Note 2
22 A-Bx Phase-Phase Volts N 0 38000 1V 100 V. 2
Note 2, 10
Dead Band
W Series
DNP3 ID
Default
Class
Units
Max
Min
Name
23 B-Cx Phase-Phase Volts N 0 38000 1V 100 V. 2
Note 2, 10
24 C-Ax Phase-Phase Volts N 0 38000 1V 100 V. 2
Note 2, 10
System Status
25 System Power (kW) Y -1.9GW 1.9GW 1 kW 250kW. 1
This can be a signed
quantity that indicates
direction of power flow, or
an unsigned quantity that is
always positive regardless
of the direction of the power
flow. This is determined by
the controller configuration
Note 2
26 System Power Factor Y 0.0 1.0 0.1 0.1 1
Note 6
27 Gas Pressure, kPag. N -100 300 1 kPaG 5kPaG 2
Note 3, 9
28 Gas Pressure, psi N -14 44 1 psi 1psi 2
Note 3, 9
29 Code Version Y 0 99,999,999 1 1 0
Note 2, 4
30 Configuration Number Y 0 99,999 1 1 0
Note 2, 5
31 CAPM Serial Number Y 0 2147483647 1 1 0
32 ACR Serial Number Y 0 2147483647 1 1 2
Note 2
33 I Contact Life Y 0.0 100.0 0.1 % 0.1 % 2
Note 7
34 II Contact Life N 0.0 100.0 0.1 % 0.1 % 2
Note 7
35 III Contact Life N 0.0 100.0 0.1 % 0.1 % 2
Note 7
36 Protection setting selection Y 0 9 1 1 1
0 = Group A
1 = Group B
9 = Group J
37 Transmitted frame count Y 0 32768 1 1 0
38 Received frame count Y 0 32768 1 1 0
39 Received message length Y 0 999 1 1 0
error
40 Received message CRC Y 0 999 1 1 0
error
Dead Band
W Series
DNP3 ID
Default
Class
Units
Max
Min
Name
Protection Sequence Data
These analogue points record data about the protection sequence including maximum fault
currents. These are derived from the max current events that are seen in the Operator Control
Panel event record and record the current for each phase and for earth/ground.
For any one protection trip or sequence advance more than one fault current can be set. For
example a Phase/Phase fault might set an A-Phase current and a B-Phase current.
Other data recorded includes the number of trips in the protection sequence and the Protection
Group that was active at the time of the protection operation.
Data is cleared to zero by the following actions:-
Reset Fault Current remote control command defined below
Any Operator Close or Trip action
Start of a new sequence.
This data is volatile, ie they are zeroed on controller software reset.
Protection Trip 1
41 A Fault Current Written Y 0 16000 1A 1A 1
on an A-Max event.
42 B Fault Current Written N 0 16000 1A 1A 1
on a B-Max event.
43 C Fault Current Written N 0 16000 1A 1A 1
on a C-Max event.
44 Earth / Ground Fault N 0 16000 1A 1A 1
Current - Written on a G-
Max event. This includes
SEF/SGF Fault currents.
Protection Trip 2
Dead Band
W Series
DNP3 ID
Default
Class
Units
Max
Min
Name
Protection Trip 4
60 Auto-Changeover Status N 0 15 1 1 1
0 Auto-Changeover OFF
1 Auto-Changeover ON
2 ACO load MASTER
3 ACO load SLAVE
4 ACO No SLAVE comms
5 ACO abort - status 1
6 ACO abort - status 2
7 ACO abort - status 3
8 ACO abort - status 4
9 ACO abort - status 5
10 ACO abort - status 6
11 ACO abort - status 7
12 ACO abort - status 8
13 ACO abort - status 9
14 ACO abort - status 10
15 ACO abort - status 11
61 to Reserved
69
Note
1. The deadband for all analogue points can be configured, refer section 5.3.5 for more information.
2. These points may exceed the 16 bit limit and can be obtained using 32 bit analogue input objects.
Name
Units
Max
Min
Note:
1. This accumulates the total kWH flowing through the ACR.
If the controller is set for Power Flow Unidirectional then the cumulative total increases irrespective of
the direction of power flow to show the total power that has passed through the device.
If the controller is set for Bi-Directional power flow then the cumulative total can increase or decrease
reflecting the nett power flow.
2. Resetting any Outage counter via a protocol counter reset command will result in the resetting of all
outage counters.
3. The power flow direction (source/load designation) is determined by the user. Refer to Power Flow
Direction Binary Input for status and Binary Output for control.
Set = 1
Name
Control Type
Cleared = 0
W Series
DNP3 ID
Set = 1
Name
Rejected if:
SEF/SGF is not
available
2 Auto Reclose Y Auto Reclose ON Auto Reclose OFF L, P
3 ACR Control Y Close Trip TC,
Rejected if: Rejected if: L, P
Close coil is Trip coil is isolated
isolated SF6 gas pressure
controller is in is low (if applicable)
LOCAL control AND low gas
mode lockout is ON
SF6 gas pressure Switchgear data
is low (if applicable) invalid
AND low gas
lockout is ON
Work Tag is
applied
Switchgear data
invalid
Mechanically
interlocked (if
applicable)
Live load blocking
ON AND any load
side terminal live
Trip and/or Close
capacitors are
charging or failed
4 Work Tag Y Applies Work Tag. Removes Work Tag. L, P
Rejected if: Rejected if:
controller is in controller is in
LOCAL Mode LOCAL Mode.
5 Cold Load Idle/Max Y Set cold load time to its Set cold load time to L, P
maximum value. This zero. This means that
means that the cold the threshold multiplier
load threshold current will not be affected by
will be set to its the cold load function.
maximum value Rejected if:
Rejected if: Cold load support
Cold load support is OFF
is OFF
6 High Current Lockout Y Enable High Current Disable High Current L, P
Lockout Lockout
7 Loss of Phase Protection N Enable Loss of Phase Disable Loss of Phase L, P
Rejected if: Protection Protection
LOP and Loop Auto
linked.
Single Phase switchgear.
8 Sequence Control Y Enable Sequence Disable Sequence L, P
Control Control
9 Live Load Blocking Y Live Load blocking ON Live Load blocking OFF L, P
Control Type
Cleared = 0
W Series
DNP3 ID
Set = 1
Name
10 ` Reset Fault Y Resets all Object 30 No Action L, P
Flags and Currents Fault Currents to zero
Note 1 and clears all Object 01
protection trip flags
11 Protection Control Y Enable Protection Turn ALL Protection L, P
OFF
Rejected if:
protection OFF is
not allowed
12 Power Flow Direction Note 4 Y Source X, Load I Source I, Load X L, P
13 Protection Group A Note 1, 3 Y Group A ON Note 5 No Action L, P
14 Protection Group B Note 1, 3 Y Group B ON Note 5 No Action L, P
15 Protection Group C Note 1, 3 Y Group C ON Note 5 No Action L, P
16 Protection Group D Note 1, 3 Y Group D ON Note 5 No Action L, P
17 Protection Group E Note 1, 3 Y Group E ON Note 5 No Action L, P
18 Protection Group F Note 1, 3 Y Group F ON Note 5 No Action L, P
19 Protection Group G Note 1, 3 Y Group G ON Note 5 No Action L, P
20 Protection Group H Note 1, 3 Y Group H ON Note 5 No Action L, P
21 Protection Group I Note 1, 3 Y Group I ON Note 5 No Action L, P
22 Protection Group J Note 1, 3 Y Group J ON Note 5 No Action L, P
23 Loop Automation Control Y Loop Automation ON Loop Automation OFF L, P
Note 2 Rejected if: Rejected if:
Loop automation Loop automation
capability not capability not
available available
Work tag applied
Trip coil isolated
Close coil isolated
Mechanism fail
Switchgear data
invalid
Battery not normal
SF6 Gas Pressure
is low (if applicable)
AND Low Gas
Lockout is ON
Tripped AND
(Midpoint OR
Feeder)
U Series AND no
external CVTs
AND (TIE OR Auto
Restore ON)
24 Dummy Circuit Breaker Y DCB Close DCB Trip TC,
L, P
Control Type
Cleared = 0
W Series
DNP3 ID
Set = 1
Name
25 Automatic Protection Group Y APGS ON APGS OFF L, P
Selection Rejected if:
APGS ON is Not
Allowed
Loop Automation
ON
26 Supply Outage Measurement Y Supply Outage Supply Outage L, P
Control Measurement ON Measurement OFF
27 Supply Outage Measurement Y Resets all Supply No Action L, P
Reset Outage counters
values.
28 Under Frequency Protection Y Enable under frequency Disable under L, P
protection frequency protection
Rejected if: Rejected if:
CAPM4 CAPM4
29 Over Frequency Protection Y Enable over frequency Disable over frequency L, P
protection protection
Rejected if: Rejected if:
CAPM4 CAPM4
30 Normal Frequency Close Y Enable normal Disable normal L, P
Protection frequency close frequency close
protection protection
Rejected if: Rejected if:
CAPM4 CAPM4
31 Source Dead Protection Y Enable Disable L, P
32 Protocol IOEX control 1 Y Sets IOEX output that is Clears the IOEX output TC,
33 Protocol IOEX control 2 Y mapped to this point. that is mapped to this L, P
For RTU emulation. point. For RTU
34 Protocol IOEX control 3 Y
emulation.
35 Protocol IOEX control 4 Y
36 Protocol IOEX control 5 Y
37 Protocol IOEX control 6 Y
38 Protocol IOEX control 7 Y
39 Protocol IOEX control 8 Y
40 ACO Auto Restore Y ACO Auto Restore ON. ACO Auto Restore L, P
Rejected if: OFF. Rejected if:
Switch is LBS Switch is LBS
ACO feature is not ACO feature is not
available available
41 ACO Enable Y ACO ON. Rejected if: ACO OFF. Rejected if: L, P
Switch is LBS Switch is LBS
ACO feature is not ACO feature is not
available available
Note:
1. The response for binary output status for these points will always be 0.
2. This point is only valid when the Loop Automation option is enabled for the current configuration
otherwise No Action is taken.
3. Only one protection group can be active at any one time. Activating any of these protection groups will
automatically reset the previously active setting.
4. Changing the Source/Load direction affects the following aspects of the operation of the controller:
Whether the source or load corresponds to I side or X side on the voltage measurements
Which side is the source or load for the Live Load Blocking
Which side is the source or load for the Directional Blocking
Which direction is positive power flow for the System Power Analogue Input
Power Flow Direction Binary Input status
5. The number of protection groups available in the controller is configurable. If a control is not available
because the protection set is not supported then it is rejected.
Name
Units
Max
Min
Note:
1. The number of protection groups available in the controller is configurable. If the analogue output block
value is not available because the protection set is not supported then it is rejected.
Cleared = 0
Resolution
Comment
DNP3 ID
Set = 1
Name
Class
Time
and
0 Abnormal Operator 1 For any of the following None of the specified This flag shows that the
conditions conditions:- conditions are true operator has the LBS in
Trip or Close an abnormal state such
Isolated, as work tag applied.
This means that it will
LBS Mechanically
operate differently to its
locked open (if
normal mode of
applicable)
operation.
Work Tag Applied
500ms
1 LBS Tripped (open) 1 LBS Tripped LBS not Tripped These are repeats of the
mechanism travel
switches. When the LBS
is disconnected from the
2 LBS Closed 1 LBS Closed LBS not Closed control cubicle they are
both cleared.
10ms
3 Controller Mode 2 LOCAL control Disabled LOCAL Control The controller is either in
Remote control Enabled LOCAL or Remote
Enabled Remote Control Controller Mode. This
Disabled affects the closing
command the
permission to
set/remove work tag.
500ms
4 Maintenance 1 For any of the following No maintenance The controller has
Required conditions:- required detected one or more
Battery NOT normal conditions which require
maintenance.
Capacitor charge
failure This point cannot
become Set until at least
Low power mode
five minutes after
Low SF6 gas controller start.
pressure LBS data 500ms
not valid (includes
connection to an
Cleared = 0
Resolution
Comment
DNP3 ID
Set = 1
Name
Class
Time
and
invalid switch type)
Any contact life is
less than 20%
Mechanical failure
5 Work Tag 2 Work Tag Applied Work Tag Removed The controller can have
a work tag. This affects
the closing command
500ms
6 Detection A Active 2 Detection Group A is Detection Group A is not These flags indicate
active active the active protection
7 Detection B Active 2 Detection Group B is Detection Group B is not group. If neither A nor
active active B is active (eg.
Because C is active)
then flags will be clear
and the analogue value
point must be used to
determine the active
group.
500ms
8 Detection C Active 2 Detection Group C is Detection Group C is not Only one detection
active active group is active at any
one time.
9 Detection D Active 2 Detection Group D is Detection Group D is not
active active
10 Detection E Active 2 Detection Group E is Detection Group E is not 500ms
active active
11 Detection F Active 2 Detection Group F is Detection Group F is not
active active
12 Detection G Active 2 Detection Group G is Detection Group G is not
active active
13 Detection H Active 2 Detection Group H is Detection Group H is not
active active
14 Detection I Active 2 Detection Group I is Detection Group I is not
active active
15 Detection J Active 2 Detection Group J is Detection Group J is not
active active
16 Power Flow 2 Source X, Load I Source I, Load X The power flow direction
Direction (source/load
designation) is
determined by the user.
Refer to the Power Flow
Direction binary output
for more information
500ms
17 Close Isolate 2 Close Isolate Switch Close Isolate Switch Shows the state of the
OFF/ISOLATE(i.e. Close ON/ENABLE (i.e. Close Trip & Close isolate
is disabled) is enabled) switches on the control
18 Trip Isolate 1 Trip Isolate Switch OFF Trip Isolate Switch panel
(i.e. Trip is disabled) ON(i.e. Trip is enabled) 10ms
Cleared = 0
Resolution
Comment
DNP3 ID
Set = 1
Name
Class
Time
and
19 Locked 1 LBS Locked Open LBS not locked open Shows that the LBS is
mechanically and
electrically locked in the
open position..
10ms
20 LBS Memory Data 2 LBS Memory Data not LBS Memory Data Valid Shows that the controller
Invalid valid has retrieved the data
from the LBS memory.
When invalid the
switchgear attributes and
the gas pressure are
zeroed,
500ms
21 Auxiliary Supply 2 Auxiliary supply has Auxiliary supply is 500ms
Fail failed normal
22 Switchgear 2 Switchgear Switchgear is connected Shows the connection
Connection disconnected from to control cubicle. state of the cable
control cubicle. between the switchgear
and the controller. When
connected to the LBS
Trip, Close and Locked
indications are valid.
When disconnected from
the LBS data will be
forced invalid
500ms
23 SF6 Gas Pressure 2 Gas pressure Low or Gas Pressure Normal, Only set when
Low or Invalid Invalid or Not Known, or Not a switchgear is connected
switchgear which has and LBS memory data is
SF6. valid and switchgear
type has SF6.
500ms
24 Battery Supply 2 Battery supply not Battery supply normal 500ms
normal.
This includes :-
Battery Off
Battery Overvolt
Battery Low Volts
25 Switchgear Family 3 Set for Load Break Clear For Recloser
Switch 500ms
26 Contacts Life Low 2 When any contact life is When all contacts have 500ms
less than 20%. contact life >= 20%
27 Capacitor Charge 2 Capacitor Charge Failed Capacitor Charge OK The Trip/Close
Failure Capacitors have failed to
charge. (where relevant)
500ms
28 Mechanism Failure 2 Mechanism Failure Mechanism OK The switchgear has
failed to Trip or Close
electrically
500ms
Cleared = 0
Resolution
Comment
DNP3 ID
Set = 1
Name
Class
Time
and
29 Phase Ai Live 1 Phase is live Phase is dead Shows if the phase
30 Phase Bi Live 1 bushings are above or
below the live line
31 Phase Ci Live 1 threshold.
32 Phase Ax Live 1
33 Phase Bx Live 1 10ms
34 Phase Cx Live 1
35 Source Voltage 1 Shows that any of the All of the source side are Note that these points
Status three phases of the Terminals dead are different to the
designated Source side Load/Source Live/Dead
36 Load Voltage 1 or Load side are live. All of the load side are events in the controller
Status Terminal dead event record
10ms
37 Load Current On 1 Current of 2.5A or more Current of less than 2.5A
is flowing in at least one is flowing in all three 10ms
phase phases
38 Dummy LBS 2 Dummy LBS Closed Dummy LBS not closed. This point represents an
Closed internal dummy LBS.
This is an internal point
useful for SCADA
system testing. The
value of the dummy LBS
is non-volatile.
500ms
39 Supply Outage 2 Supply Outage Supply Outage 500ms
Measurement Measurement ON Measurement OFF
40 Reserved 1 2 Reserved Reserved
41 Phase Current HI 2 Phase Current Alarm Phase Current Alarm 500ms
Alarm ON OFF
42 Phase Current 2 Phase Current Alarm Phase Current Alarm 500ms
LOW Alarm ON OFF
43 Phase Voltage HI 2 Phase Voltage Alarm Phase Voltage Alarm 500ms
Alarm ON OFF
44 Phase Voltage 2 Phase Voltage Alarm Phase Voltage Alarm 500ms
LOW Alarm ON OFF
45 Earth Current HI 2 Earth Current HI Alarm Earth Current HI Alarm 500ms
Alarm ON OFF
46 Earth Current LOW 2 Earth Current LOW Earth Current LOW 500ms
Alarm Alarm ON Alarm OFF
47 System Power HI 2 System Power HI Alarm System Power HI Alarm 500ms
Alarm ON OFF
48 System Power 2 System Power LOW System Power LOW 500ms
LOW Alarm Alarm ON Alarm OFF
49 Auxiliary Supply 2 Auxiliary Supply has Auxiliary Supply has 500ms
Fail (Delayed) failed for more than 120 been restored for more
seconds than 20 seconds
Cleared = 0
Resolution
Comment
DNP3 ID
Set = 1
Name
Class
Time
and
Operator/Detection Flags
These flags show the status of the operator controls and some of the detection flags.
They are equivalent to the indications available on the Operator Control Panel of the controller.
50 Phase Detection 2 Phase Detection ON Phase Detection OFF 500ms
Enabled
51 Earth/Ground 2 Earth/Ground Detection Earth/Ground Detection 500ms
Detection Enabled ON OFF
52 SEF/SGF 2 SEF/SGF Detection ON SEF/SGF Detection 500ms
Detection Enabled OFF
53 Sectionaliser Auto 2 Sectionaliser Auto ON Sectionaliser OFF (Load 500ms
Break Switch)
54 Cold Load Auto 2 Cold Load auto-mode is Cold Load pickup is
armed. OFF.
This means the Cold This means that the cold
Load function is enabled load function is 500ms
and may, or may not, be completely disabled.
affecting the threshold See Cold Load Idle
multiplier. (below)
55 Cold Load Idle 2 Cold Load is Idle or is Cold load is NOT Idle.
turned off. This means that the
This means that the threshold multiplier is 500ms
threshold multiplier is not being raised by the cold
being affected by the load pickup function.
cold load function.
56 Live Load Blocking 2 Live Load Blocking ON Live Load Blocking OFF 500ms
57 Automatic 2 Automatic Detection Automatic Detection 500ms
Detection Group Group Selection is ON Group Selection is OFF
Selection
(Code Version 025-
01 and later)
Detection Flags
This group of points indicates what happened in the most recent fault detection. Unlike the ACR, these flags dont
attempt to reconstruct a fault sequence. The flags are not cumulative, they are cleared as each new fault is
detected. For example, if there is an earth fault followed by a phase fault, the earth fault flag will be cleared when
the phase fault flag is set.
In addition analogue data is available which shows the fault currents.
Most of these flags are cleared either by protocol command or when the switchgear is tripped/closed by the
operator or when a new fault is detected.
This data is volatile, i.e. it is zeroed on controller software reset.
If there is more than one protocol running simultaneously in the controller this data is replicated between the
protocols so that each master station can clear its data independently from the others.
58 Sequence in 2 Start of sequence That End of sequence. This shows that a
Progress is a detection trip or Detection sequence has
sequence advance has started and not yet
occurred. completed.
Note that operator trip
does not cause a
sequence in progress
10ms
Cleared = 0
Resolution
Comment
DNP3 ID
Set = 1
Name
Class
Time
and
59 A Phase 2 A Phase Overcurrent Cleared by These flags show which
Overcurrent Fault Fault Operator trip elements were picked up
since last clear action
60 B Phase 2 B Phase Overcurrent Any close
Overcurrent Fault Fault 10ms
Reset Flags
61 C Phase 2 C Phase Overcurrent Protocol Command
Overcurrent Fault Fault
62 Earth/Ground 2 Earth/Ground
Overcurrent Fault Overcurrent Fault
63 SEF/SGF 2 SEF/SGF Overcurrent
Overcurrent Fault Fault
64 Supply Interrupt 1 Supply Interrupt Set if a supply interrupt
occurred after the most
recent fault.
10ms
65 Sectionaliser Trip 1 Sectionaliser Trip Set if switch trips to
sectionalise
66 1 Input state for IOEX Input asserted Input not asserted
IOEX Input 1
input 1
67 1 Input state for IOEX Input asserted Input not asserted
IOEX Input 2
input 2
68 1 Input state for IOEX Input asserted Input not asserted
IOEX Input 3
input 3
69 1 Input state for IOEX Input asserted Input not asserted
IOEX Input 4
input 4
70 1 Input state for IOEX Input asserted Input not asserted
IOEX Input 5
input 5
71 1 Input state for IOEX Input asserted Input not asserted
IOEX Input 6
input 6
72 1 Input state for IOEX Input asserted Input not asserted
IOEX Input 7
input 7
73 1 Input state for IOEX Input asserted Input not asserted
IOEX Input 8
input 8
74 1 Input state for IOEX Input asserted Input not asserted
IOEX Input 9
input 9
75 1 Input state for IOEX Input asserted Input not asserted
IOEX Input 10
input 10
76 1 Input state for IOEX Input asserted Input not asserted
IOEX Input 11
input 11
Cleared = 0
Resolution
Comment
DNP3 ID
Set = 1
Name
Class
Time
and
78 1 Set if the most recent Cleared by: 10ms
close caused by local or ! 'Reset Flags and
Operator Close
remote panel close Currents' protocol
request. command
79 1 Set if the most recent ! Controller 10ms
IOEX Close close caused by an Software Reset
IOEX close input. (data is volatile)
80 1 Set if the most recent ! At the time of the 10ms
Protocol Close close caused by a next Close
protocol close request.
81 1 Set if any of the following 10ms
caused the most recent
close
Mechanical action.
The switchgear
detected as closed
without a close
External Close request
CCEM external
button on N-Series
Electrical action
(only available on
the Advanced
controller)
82 Live Load Blocking 1 Set if the most recent Cleared by: 10ms
close was blocked due ! 'Reset Flags and
to a Live Load condition Currents' protocol
command
! Controller Software
Reset (data is
volatile)
! At the time of the
next Close
83
Reserved
93
Note:
1. Only available on CAPM-5 controller
All analogue points have 500ms resolution time tags. Refer to Appendix A for more
information on timing.
All analogues in the small analogue data set can fit in a signed 16-bit DNP3 data object
except where noted.
The phase designation A, B, C is determined by the user, refer to the equipment manual
for more information.
Phase and terminal terminology is explained in section 4.4.
DNP3 Implementation
Static: Configurable Object 30 Variation 1, 2, 3, or 4 (refer to section 5.3)
Event: Configurable Object 32 Variation 1, 2, 3, or 4 (refer to section 5.3)
Deadband: Configurable Object 34 Variation 1, 2 (refer to section 5.3)
Request Function Code: 01 Read
Dead Band
DNP3 ID
Default
Name
Class
Units
Max
Min
Dead Band
DNP3 ID
Default
Name
Class
Units
Max
Min
Fault Detection Data
These analogue points record data about the fault detection including maximum fault currents.
These are derived from the max current events, which are seen in the Operator Control Panel event
record and record the current for each phase and for earth/ground.
For any one fault more than one fault current can be set. For example a Phase/Phase fault might set
an A-Phase current and a B-Phase current.
Other data recorded includes the supply interrupt count and the Detection Group which was active at
the time of the fault detection.
Fault Detection Data is cleared to zero by the following actions :-
Reset Fault Current remote control command defined below
Any Operator Close or Trip action
New fault detected
This data is volatile, that is they are zeroed on controller software reset.
If there is more than one protocol running simultaneously in the controller this data is replicated
between the protocols so that each master station can clear its data independently from the others.
Active Detection Group
13 The number of the Detection 0 9 1 1 1
Group active during the
sequence.
Supply Interrupt Count
14 The number of Supply 1 10 1 1
Interrupts Counted.
Most Recent A-Phase Fault
15 Written on a Max Current event 0 16000 Amps 1A 1
for A Phase
Most Recent B-Phase Fault
16 Written on a Max Current event 0 16000 Amps 1A 1
for B Phase
Most Recent C-Phase Fault
17 Written on a Max Current event 0 16000 Amps 1A 1
for C Phase
Most Recent Earth/Ground
Fault Current - Written on an E-
18 0 16000 Amps 1A 1
Max event. This includes
SEF/SGF Fault currents.
19
-
Reserved
29
Note
1. The deadband for all analogue points can be configured, refer section 5.3.5 for more information.
2. These points may exceed the 16 bit limit and can be obtained using 32 bit analogue input
objects.
This is the complete set of analogue status points available from the controller.
All analogue points have 500ms resolution time tags. Refer to Appendix A for more
information on timing.
All analogues in the full analogue data set can fit in a signed 16-bit DNP3 data object
except where noted.
The phase designation A, B, C is determined by the user, refer to the equipment manual
for more information.
Phase and terminal terminology is explained in section 4.4.
DNP3 Implementation
Static: Configurable Object 30 Variation 1, 2, 3, or 4 (refer to section 5.3)
Event: Configurable Object 32 Variation 1, 2, 3, or 4 (refer to section 5.3)
Deadband: Configurable Object 34 Variation 1, 2 (refer to section 5.3)
Request Function Code: 01 Read
Dead Band
DNP3-ID
Default
Name
Class
Units
Max
Min
Dead Band
DNP3-ID
Default
Name
Class
Units
Max
Min
12 Cx Phase-(Earth / Ground) 0 30000 1V 100 V 2
Voltage
Fault Detection Data
These analogue points record data about the fault detection including maximum fault currents.
These are derived from the max current events, which are seen in the Operator Control Panel event
record and record the current for each phase and for earth/ground.
For any one fault more than one fault current can be set. For example a Phase/Phase fault might set
an A-Phase current and a B-Phase current.
Other data recorded includes the supply interrupt count and the Detection Group which was active at
the time of the fault detection.
Fault Detection Data is cleared to zero by the following actions :-
Reset Fault Current remote control command defined below
Any Operator Close or Trip action
New fault detected
This data is volatile, that is they are zeroed on controller software reset.
If there is more that one protocol running simultaneously in the controller this data is replicated
between the protocols so that each master station can clear its data independently from the others.
13 Active Detection Group 0 9 1 1 1
The number of the Detection
Group which was active during
the sequence.
14 Supply Interrupt Count 1 10 1 1
The number of Supply
Interrupts Counted.
15 Most Recent A-Phase Fault 0 16000 Amps 1A 1
Written on a Max Current event
for A Phase
16 Most Recent B-Phase Fault 0 16000 Amps 1A 1
Written on a Max Current event
for B Phase
17 Most Recent C-Phase Fault 0 16000 Amps 1A 1
Written on a Max Current event
for C Phase
18 Most Recent Earth/Ground 0 16000 Amps 1A 1
Fault Current Written on an
E-Max event. This includes
SEF/SGF Fault currents.
Voltage Measurements (Phase/Phase)
19 A-Bi Phase-Phase Voltage 0 38000 1V 100 V 2
Note 2
20 B-Ci Phase-Phase Voltage 0 38000 1V 100 V 2
Note 2
21 C-Ai Phase-Phase Voltage 0 38000 1V 100 V 2
Note 2
22 A-Bx Phase-Phase Voltage 0 38000 1V 100 V 2
Note 2
23 B-Cx Phase-Phase Voltage 0 38000 1V 100 V 2
Note 2
Dead Band
DNP3-ID
Default
Name
Class
Units
Max
Min
24 C-Ax Phase-Phase Voltage 0 38000 1V 100 V 2
Note 2
System Status
25 System Power (kW) - 1.9GW 1 kW 250kW. 1
This can be a signed quantity 1.9
that indicates direction of power GW
flow, or an unsigned quantity
that is always positive
regardless of the direction of
the power flow. This is
determined by the controller
configuration
Note 2
26 System Power Factor 0.0 1.0 0.1 0.1 1
Note 6
27 Gas Pressure, kPag. - 300 1 kPaG 5kPaG 2
Note 3 100
28 Gas Pressure, psi Note 3 -14 44 1 psi 1psi 2
29 Code Version Note 2, 4 0 99,999,999 1 1 0
30 Configuration Number Note 2, 5 0 99,999 1 1 0
31 CAPM Serial Number 0 2147483647 1 1 0
32 LBS Serial Number Note 2 0 2147483647 1 1 2
33 I/U Contact Life Note 7 0.0 100.0 0.1 % 0.1 % 2
34 II/V Contact Life Note 7 0.0 100.0 0.1 % 0.1 % 2
35 III/W Contact Life Note 7 0.0 100.0 0.1 % 0.1 % 2
36 Transmitted frame count 0 32768 1 1 0
37 Received frame count 0 32768 1 1 0
38 Received message length error 0 999 1 1 0
39 Received message CRC error 0 999 1 1 0
Detection State
40 Cold Load 0 480 1 Min 1 Min 2
Value is zero when Cold Load
is Idle or OFF. When Cold Load
is not idle this shows the
operational cold load time, i.e.
the current time being used to
calculate the operational cold
load threshold multiplier.
41 Detection Group currently 0 9 1 1 2
selected
0 = Detection Group A
1 = Detection Group B
n = Other Detection Group
Miscellaneous
42 Maximum Average Current of 0 16000 1A 10A 1
all phases for the previous day
ending at 24:00
Dead Band
DNP3-ID
Default
Name
Class
Units
Max
Min
43
- Reserved
53
Note
1. The deadband for all analogue points can be configured, refer section 5.3.5 for more information.
2. These points may exceed the 16 bit limit and can be obtained using 32 bit analogue input objects.
3. If LBS Memory Data Invalid binary status is set then value is 0
4. The code version is an eight digit number that has the form XXX-XXX.XX with the dash and point
formatting removed.
5. The configuration number is a five digit number that has the form XXXXX. It identifies the
configuration loaded into the controller database.
6. Power factor has a built in scale factor of 10 i.e. range 0.0 to 1.0 with resolution 0.1 is transmitted
as 0 to 10 with resolution 1.
7. Contact life has a built in scale factor of 10 i.e. range of 0.0% to 100.0% with resolution 0.1% is
transmitted as 0 to 1000 with resolution 1.
8. This point is only valid when the Loop Automation option is enabled for the current configuration
and is otherwise always reported as zero.
DNP3 Implementation
Binary Counters
Static Object: Object 20 Variation 05 32 Bit Binary Counter without Flag
Request Function Codes: 01 Read, 07 Immediate Freeze,
08 Immediate Freeze, No Ack, 09 Freeze and Clear
10 Freeze and Clear, No Ack
Frozen Counters
Static Object: Object 21 Variation 9 32 Bit Frozen Counter without Flag
Request Function Code: 01 Read
Name
Units
Max
Min
Note:
1. This accumulates the total kWH flowing through the LBS.
If the controller is set for Power Flow Unidirectional then the cumulative total increases irrespective of
the direction of power flow to show the total power that has passed through the device.
If the controller is set for Bi-Directional power flow then the cumulative total can increase or decrease
reflecting the nett power flow.
2. Resetting any Outage counter via a protocol counter reset command will result in the resetting of all
outage counters.
3. The power flow direction (source/load designation) is determined by the user. Refer to Power Flow
Direction Binary Input for status and Binary Output for control.
Set = 1
Name
Control Type
Cleared = 0
DNP3 ID
Set = 1
Name
ON
Work Tag is
applied
Switchgear data
invalid
Mechanically
interlocked
Live load blocking
ON AND any load
side terminal live
Trip and/or Close
capacitors are
charging or failed
1 Work Tag Applies Work Tag. Removed the Work L, P
Rejected if: Tag.
controller is in Rejected if:
LOCAL Mode controller is in
LOCAL Mode.
2 Cold Load Idle/Max Set cold load time to its Set cold load time to L, P
maximum value. This zero. This means that
means that the cold the threshold multiplier
load threshold current will not be affected by
will be set to its the cold load function.
maximum value Rejected if:
Rejected if: Cold load support is
Cold load support OFF
is OFF
3 Live Load Blocking Live Load blocking ON Live Load blocking OFF L, P
4 Reset Fault Resets all Object 30 No Action L, P
Flags and Currents Fault Currents to zero
Note 1 and clears all Object 01
Detection trip flags
5 Power Flow Direction Note 4 Source X, Load I Source I, Load X L, P
6 Detection Group A Note 1, 3 Group A ON Note 5 No Action L, P
7 Detection Group B Note 1, 3 Group B ON Note 5 No Action L, P
8 Detection Group C Note 1, 3 Group C ON Note 5 No Action L, P
9 Detection Group D Note 1, 3 Group D ON Note 5 No Action L, P
10 Detection Group E Note 1, 3 Group E ON Note 5 No Action L, P
11 Detection Group F Note 1, 3 Group F ON Note 5 No Action L, P
12 Detection Group G Note 1, 3 Group G ON Note 5 No Action L, P
13 Detection Group H Note 1, 3 Group H ON Note 5 No Action L, P
14 Detection Group I Note 1, 3 Group I ON Note 5 No Action L, P
15 Detection Group J Note 1, 3 Group J ON Note 5 No Action L, P
16 Dummy Circuit Breaker DCB Close DCB Trip TC,
L, P
17 Automatic Detection Group APGS ON APGS OFF L, P
Selection Rejected if APGS ON
is Not Allowed
Control Type
Cleared = 0
DNP3 ID
Set = 1
Name
18 Supply Outage Measurement Supply Outage Supply Outage L, P
Control Measurement ON Measurement OFF
19 Supply Outage Measurement Resets all Supply No Action L, P
Reset Outage counters
values.
20 Sectionaliser Auto Turn Sectionalising ON Turn Sectionalising L, P
OFF.
21 Protocol IOEX control 1 Sets IOEX output that Clears the IOEX output TC,
22 Protocol IOEX control 2 is mapped to this point. that is mapped to this L, P
For RTU emulation. point. For RTU
23 Protocol IOEX control 3 emulation.
24 Protocol IOEX control 4
25 Protocol IOEX control 5
26 Protocol IOEX control 6
27 Protocol IOEX control 7
28 Protocol IOEX control 8
29 ACO Autorestore ACO Autorestore ON ACO Autorestore OFF L, P
30 Autochangeover Enable Auto-changeover is Auto-changeover is L, P
operating disabled
31 Auto Changeover Make before break. Break before make. L, P
Mode
Note:
1. The response for binary output status for these points will always be 0.
2. This point is only valid when the Loop Automation option is enabled for the current configuration
otherwise No Action is taken.
3. Only one Detection group can be active at any one time. Activating any of these Detection groups will
automatically reset the previously active setting.
4. Changing the Source/Load direction affects the following aspects of the operation of the controller:
Whether the source or load corresponds to I side or X side on the voltage measurements
Which side is the source or load for the Live Load Blocking
Which side is the source or load for the Directional Blocking
Which direction is positive power flow for the System Power Analogue Input
Power Flow Direction Binary Input status
5. The number of protection groups available in the controller is configurable. If a control is not available
because the protection set is not supported then it is rejected.
DNP3 Implementation
Analogue Output Status
Static Object: Object 40 Variation 02 16 Bit Analogue Status
Request Function Code: 01 Read
Analogue Output Block
Control Object: Object 41 Variation 02 16 Bit Analogue Output Block
Request Function Codes: 03 Select, 04 Operate, 05 Direct Operate,
06 Direct Operate, No Ack
Name
Units
Max
Min
Note:
1. The number of protection groups available in the controller is configurable. If the analogue output block
value is not available because the protection set is not supported then it is rejected.
7. Steps 6 and 7 are repeated until all data requests are complete.
8. The call is cleared by the Master Station.
1. DTR is asserted.
2. The master station establishes the X.25 connection.
3. The CAPM strips off the leading NUA and COM characters.
4. Initialise / Data Request or Control / Poll sequence is transmitted by the master
station.
5. CAPM transmits the requested data.
6. Steps 4 and 5 are repeated until poll / control is completed.
7. The call is cleared by the master station.
3. At the prompt character, the CAPM will transmit the master stations NUA followed
by the <CR> character.
4. The PAD returns the connected NUA followed by COM when the connection has
been established. (See below for a description of the failure sequence).
5. When the master station sees a connection established from a RTU, it sends an
INITIALISE with a Broadcast address.
6. The CAPM transmits the INITIALISE reply with its RTU address to Master.
7. The master station sends data requests and a POLL
8. The CAPM replies with the requested data.
9. Steps 6 and 7 are repeated until all data requests are complete.
10. The call is cleared by the master station.