AREA
EQUIP. FIRE WATER STORAGE TANK Doc No CL-1007-24135-001
TAG No. T-24135A/B Rev. 3
DESIGN CALCULATION FOR FIRE WATER STORAGE TANK Date 28-Feb-17
Owner PETROLEUM DEVLOPMENT OMAN
AREA
EQUIP. FIRE WATER STORAGE TANK Doc No CL-1007-24135-001
TAG No. T-24135A/B Rev. 3
DESIGN CALCULATION FOR FIRE WATER STORAGE TANK Date 28-Feb-17
Owner PETROLEUM DEVLOPMENT OMAN
AREA
EQUIP. FIRE WATER STORAGE TANK Doc No CL-1007-24135-001
TAG No. T-24135A/B Rev. 3
DESIGN CALCULATION FOR FIRE WATER STORAGE TANK Date 28-Feb-17
Allowable external loads on nozzles (As per appendix - P)
Nozzle size = 18 inch.
a = 228.5 mm 0.2285 m
L = 933 mm 0.933 m
H = 15000 mm 15 m
DT = 82 C
R = 15000 mm
G = 1
t = 18.00 mm
R/t = 833.33
a/R = 0.0152333
L/2a = 2.04
KL = 5.9E+09 N-mm/rad
KL = 1.2E+10 N-mm/rad
Step-2) Calculate the unrestrained shell deflection & rotation at the nozzle centerline
resulting from the hydrostatic head of the full tank
= 1.285/(Rt)0.5
= 0.00247 mm
*L = 2.31 rad
-L
W = 9.8X10-6*G*H*R2 [1- cos(L)-L/H] +*R*T
E*t
= 22.50 mm
Owner PETROLEUM DEVLOPMENT OMAN
AREA
EQUIP. FIRE WATER STORAGE TANK Doc No CL-1007-24135-001
TAG No. T-24135A/B Rev. 3
DESIGN CALCULATION FOR FIRE WATER STORAGE TANK Date 28-Feb-17
= 9.8X10-6*G*H*R2 *{(1/H)--L[cos(L)+sin(L)]}
E*t
= 9.23 x -0.000189
= -0.001748 rad
XA = 1162
XB = 705
XC = 933
XA/(Rt)0.5 = 2.24
XB/(Rt)0.5 = 1.36
XC/(Rt)0.5 = 1.80
= a/(Rt)0.5 = 0.44
1.0-0.75*XA/(Rt)0.5 = -0.68
1.0-0.75*XB/(Rt)0.5 = -0.02
1.0-0.75*XC/(Rt)0.5 = -0.35
FP = P**a2
= (9800)(1)(H-L)**a2
= 22601.10 N