Project: P1526 - 115-22kV NHHP SWY

Sag Calculation / Installation Table


All sag-data are given for one sub-conductor
Designed by: USM
Date: 2017/04/18

General Data
Calculation type: Optimized Sag
Horizontal span length: 1620.00 mm
Height difference of anchor points: -540.00 mm
Specified sag: 81.00 mm (Maximum Sag at 810.00mm)
Maximum horizontal tensile force: 85.42 N (at 5C (Wind))

Conductor data
Description: Conductor AAC 400
Number: 2
Diameter: 25.65 mm
Area (Aluminium): 389.14 mm
Area (Steel): 0.00 mm
Mass per unit length: 1075.00 kg/km
Young's modulus E: 62078.00 N/mm
Coefficient of thermal expansion: 23.00 10^-6/K

Additional loads
Temperature Load Wind pressure Wind drag factor
5.00 C Wind 700.00 N/m 1.00

Conductor with individual loads


Temperature Load H-Tensile force Left-Anchor V-Reaction Right-Anchor V-Reaction Sag @ 0 m Sag @ 0.81 m Sag @ 1.62 m
4.00 C 43 N -6 N 24 N 0.00 m -0.19 m -0.54 m
5.00 C 43 N -6 N 24 N 0.00 m -0.19 m -0.54 m
5.00 C Wind 85 N -11 N 47 N 0.00 m -0.19 m -0.54 m
10.00 C 43 N -5 N 24 N 0.00 m -0.18 m -0.54 m
15.00 C 42 N -5 N 23 N 0.00 m -0.18 m -0.54 m
20.00 C 42 N -5 N 23 N 0.00 m -0.18 m -0.54 m
25.00 C 42 N -5 N 23 N 0.00 m -0.18 m -0.54 m
30.00 C 41 N -5 N 23 N 0.00 m -0.18 m -0.54 m
35.00 C 41 N -5 N 23 N 0.00 m -0.18 m -0.54 m
40.00 C 41 N -5 N 23 N 0.00 m -0.18 m -0.54 m
45.00 C 40 N -5 N 23 N 0.00 m -0.18 m -0.54 m
50.00 C 40 N -4 N 23 N 0.00 m -0.18 m -0.54 m
55.00 C 40 N -4 N 22 N 0.00 m -0.18 m -0.54 m
60.00 C 39 N -4 N 22 N 0.00 m -0.18 m -0.54 m
65.00 C 39 N -4 N 22 N 0.00 m -0.18 m -0.54 m
70.00 C 39 N -4 N 22 N 0.00 m -0.18 m -0.54 m

Customer: Project Code Word: Nam Ninboun Hydro Project Number:


Originator: USM Date: 18/04/2017 (Print Date: 07/03/2017) Document Number: Nam Ninboun Hydro
Conductor without individual loads (Conductor installation table)
Temperature H-Tensile force Cond. Elev. @ 0 m Cond. Elev. @ 0.81 m Cond. Elev. @ 1.62 m Left mark Right mark
4.00 C 43 N 0.00 m -0.19 m -0.54 m 0.08 m 0.08 m
5.00 C 43 N 0.00 m -0.19 m -0.54 m 0.08 m 0.08 m
10.00 C 43 N 0.00 m -0.18 m -0.54 m 0.09 m 0.09 m
15.00 C 42 N 0.00 m -0.18 m -0.54 m 0.09 m 0.09 m
20.00 C 42 N 0.00 m -0.18 m -0.54 m 0.09 m 0.09 m
25.00 C 42 N 0.00 m -0.18 m -0.54 m 0.09 m 0.09 m
30.00 C 41 N 0.00 m -0.18 m -0.54 m 0.09 m 0.09 m
35.00 C 41 N 0.00 m -0.18 m -0.54 m 0.09 m 0.09 m
40.00 C 41 N 0.00 m -0.18 m -0.54 m 0.09 m 0.09 m
45.00 C 40 N 0.00 m -0.18 m -0.54 m 0.09 m 0.09 m
50.00 C 40 N 0.00 m -0.18 m -0.54 m 0.09 m 0.09 m
55.00 C 40 N 0.00 m -0.18 m -0.54 m 0.09 m 0.09 m
60.00 C 39 N 0.00 m -0.18 m -0.54 m 0.09 m 0.09 m
65.00 C 39 N 0.00 m -0.18 m -0.54 m 0.09 m 0.09 m
70.00 C 39 N 0.00 m -0.18 m -0.54 m 0.09 m 0.09 m

Customer: Project Code Word: Nam Ninboun Hydro Project Number:


Originator: USM Date: 18/04/2017 (Print Date: 07/03/2017) Document Number: Nam Ninboun Hydro
Mechanical Effects of Short-Circuit Current acc. IEC 60865-1

Input data
Three-phase a.c system/single-phase a.c. system:
System frequency f:
Initial symmetrical short-circuit current I''k:
Factor for the calculation of the peak short-circuit current :
Duration of first short-circuit current flow T_k1:
Center-line distance between supports I:
Length of both insulator chains 2*l_i:
Center-line distance between main conductos a:
Effective distance between sub-conductors a_s:
Number of sets of spacers k:
Description:
Number of sub-conductors n:
Diameter of a flexible conductor d_s:
Cross-section of sub-conductor (Aluminium) A_s:
Cross-section of sub-conductor (Steel) A_s:
Mass per unit length of main conductor m'_s:
Young's module E:
Static tensile force in the main conductor F_st at 40C:
Static tensile force in the main conductor F_st at 70C:
Resulting spring constant of both supports S:

Short-circuit tensile forces and displacement of conductors


Maximum short-circuit tensile force in main conductor F_t,d at 40C
Maximum drop force in Main conductor F_f,d at 70C
Maximum pinch-force in main conductor F_pi,d at 40C
Rating of connectors:
Rating of supports and insulators:
Maximum horizontal displacement b_h at 90.00:
Minimum air clearance between two main conductors a_min:
Maximum dynamic sag ed:

Intermediate results
Cord length of main conductor in the span l_c:
Relation l_c/l:
Mass per unit length including individual loads:
Electromagnetic force per unit length:
Parameter r:
Angular direction of the force _1:
Dynamic sag ed:
Equivalent static conductor sag at midspan b_c:
Period of conductor oscillation T:
Resulting period of conductor oscillation T_res:
Used duration of the first short-circuit current flow T_k1:
Relation T_k1/T_res:
Static stress of conductor:
Actual Young's modulus E_s:

Stiffness norm N:
Stress factor :
Swing-out-Angle _k:
Factor :
Maximum swing-out angle _m:
Factor :
Factor :

Short-circuit tensile force in main conductor F_t,d:


Drop force in main conductor F_f,d:
Elastic expansion _ela:
Material constant c_th:
Thermal expansion _th:
Dilatation factor C_D:
Form factor C_F:
Maximum horizontal displacement b_h:
Minimum air clearance between two main conductors a_min:
Center-line distance between 2 spacers l_s:

Sub-conductors don't clash effectively


Pinch-force in main conductor F_pi,d:
Relation a_s/d_s:
Factor :
Factor :
Factor :
Short-circuit current force between sub-conductors F_:
Strain factor _st:
Strain factor _pi
Parameter j:

Sub-conductors clash together:


Factor :
Factor :
Factor _e:
Current acc. IEC 60865-1

Three-phases short-circuit current


50.00 Hz
31.50 kA
1.80
1.00 s
1620.00 mm
0.00 mm
450.00 mm
50.00 mm
1
Conductor AAC 400
2
25.65 mm
389.14 mm
0.00 mm
1075.00 kg/km
62078.00 N/mm
81.10 N
77.18 N
980.00 N/mm

3216.49 N
3224.52 N
2928.91 N
4824.74 N
3224.52 N
115.74 mm
218.52 mm
115.74 mm

40 C 70 C
1620.00 mm 1620.00 mm
1.00 1.00
1.08 kg/m 1.08 kg/m
330.75 N/m 330.75 N/m
15.69 15.69
86.35 86.35
111.77 mm 115.74 mm
85.29 mm 89.61 mm
0.52 s 0.54 s
0.15 s 0.16 s
0.21 s 0.21 s
1.36 1.36
0.10 N/mm 0.10 N/mm
18765.65 N/mm 18758.79 N/mm

698.35 10^-9/N 698.38 10^-9/N


130.51 151.38
172.71 172.71
-14.69 -14.69
180.00 180.00
44.16 44.16
0.88 0.89

3216.49 N 3105.97 N
3146.04 N 3224.52 N
2.19 10^-3 2.12 10^-3
0.27 10^-18 0.27 10^-18
0.02 10^-3 0.02 10^-3
1.14 1.12
1.15 1.15
111.77 mm 115.74 mm
226.46 mm 218.52 mm
810.00 mm 810.00 mm

2928.91 N 2924.46 N
1.95 1.95
0.26 0.26
0.74 0.74
0.65 0.65
925.02 N 925.02 N
0.09 0.09
17.83 17.83
4.04 4.05

Yes Yes
2.58 2.58
0.95 0.95
1.28 1.28