Anda di halaman 1dari 1

SPRINKLER PIPING SCHEDULE - EXTRA HAZARD SPRINKLER PIPING SCHEDULE

ABOVE - BELOW CEILING SPRINKLER


NO. OF SPRINKLERS PIPE DIA IN MM PIPE DIA IN INCH
NO. OF SPRINKLERS PIPE DIA IN MM PIPE DIA IN INCH
1 25 mm 1"
2 25 mm 1"
2 32 mm
4 32 mm
2 - 5 40 mm
7 40 mm
6 - 8 50 mm 2"
8 - 15 50 mm 2"
9 - 15 65 mm
16 - 50 65 mm
16 - 27 80 mm 3"

28 - 55 100 mm 4"

56 - 150 150 mm 6"

SPRINKLER PIPING SCHEDULE - ORDINARY HAZARD SPRINKLER PIPING SCHEDULE


ORDINARY HAZARD - GROUP II
NO. OF SPRINKLERS PIPE DIA IN MM PIPE DIA IN INCH
NO. OF SPRINKLERS PIPE DIA IN MM PIPE DIA IN INCH
MAXIMUM DISTANCE - ORDINARY HAZARD 1 - 2 25 mm 1"
1 25 mm 1"
MAX. SPRINKLER TO SPRINKLER - 4.6m 3 32 mm
2 32 mm
MAX. SPRINKLER TO WALL - 2.3m 4 - 5 40 mm
3 40 mm
6 - 10 50 mm 2"
MAX. COVERAGE OF ONE SPRINKLER - 12.1 Sq.mt 4 - 6 50 mm 2"
MINIMUM DISTANCE OF SPRINKLER TO SPRINKLER - 1.8m 11 - 20 65 mm
6 - 10 65 mm
21 - 40 80 mm 3"
11 - 20 80 mm 3"
41 - 100 100 mm 4"
21 - 40 100 mm 4"
101 - 275 150 mm 6"
41 - 100 150 mm 6"

SPRINKLER PIPING SCHEDULE - LIGHT HAZARD SPRINKLER PIPING SCHEDULE - LIGHT HAZARD
NO. OF SPRINKLERS PIPE DIA IN MM PIPE DIA IN INCH NO. OF SPRINKLERS PIPE DIA IN MM PIPE DIA IN INCH

MAXIMUM DISTANCE - LIGHT HAZARD 1 - 2 25 mm 1" 1 - 2 25 mm 1"


3 32 mm 3 32 mm
MAX. SPRINKLER TO SPRINKLER - 4.6m
4 - 5 40 mm 4 - 5 40 mm
MAX. SPRINKLER TO WALL - 2.3m
6 - 10 50 mm 2" 6 - 10 50 mm 2"
MAX. COVERAGE OF ONE SPRINKLER - 16 Sq.mt
11 - 30 65 mm 11 - 30 65 mm
MINIMUM DISTANCE OF SPRINKLER TO SPRINKLER - 1.8m
31 - 60 80 mm 3" 31 - 60 80 mm 3"

61 - 100 90 mm 61 - 100 90 mm
SEE SECTION 8.2 100 mm 4" SEE SECTION 8.2 100 mm 4"