CONSTRUCTION OF 2X20 MVA 33/11 KV INDOOR NEW

Project
MUKHAILIF-2 PRIMARY SUBSTATION SUB STATION

Date 29-08-2016
Client MAJAN ELECTRICITY CO. (SAOC)
Report ref TLC-051-TR 8
11KV CIRCUIT
Contractor CIVIL CONTRACTING CO. LLC Device
BREAKER

TEST REPORT FOR 11KV SWHITCH GEAR CIRCUIT BREAKER


Feeder: OUT GOING FEEDER 2 (PANEL No.4)

1.A) NAME PLATE DETAILS:


MAKE :JYOTI TYPE :VK-10J25F
SERIAL NUMBER :A-26161 FREQUENCY : 50 HZ
Ur : 12 KV Ins.Level P.F.28 KV
Ir : 1250 A Isc : 25 KA , 3S
Ic : 25 KA YEAR : 2014

2. INSULATION RESISTANCE TEST with 5 KV Megger :


CB Position IR Value
RE YE BE
Closed
70G 64.6G 67.6G
R-Y Y-B B-R
Closed
160G 152G 166G
R-R Y-Y B-B
Open
187G 184G 191G

3. CIRCUIT BREAKER TIMING TEST:

a) Attached CB Operation Analyser Test Report.


SEQUENCE C O C-O
CB POSITION Close(ms) Trip(ms) Close(ms) Trip(ms)
R-Phase 36.6 38.1 37.0 36.4
Y-Phase 38.0 36.7 38.6 35.2
B-Phase 36.6 37.8 37.1 36.3

4.CONTACT RESISTANCE MEASUREMENT OF BREAKERS:

FEEDER NAME PANEL NO. PHASE-


R Y B
OUT GOING FEEDER - 2 4 33 34 33

TESTED BY WITNESSED/APPROVED BY
CIVIL CONTRACTING CO. LLC MAJAN ELCTRICITY CO. (SAOC)
Sign Sign

Name T. Satti Reddy,PE007/2016 Name Talal Hamed Al Suqatari


Date 29-08-2016 Date 29-08-2016
Page 1 of 2
CONSTRUCTION OF 2X20 MVA 33/11 KV INDOOR NEW
Project
MUKHAILIF-2 PRIMARY SUBSTATION SUB STATION

Date 29-08-2016
Client MAJAN ELECTRICITY CO. (SAOC)
Report ref TLC-051-TR 8
11KV CIRCUIT
Contractor CIVIL CONTRACTING CO. LLC Device
BREAKER

5.FUNCTIONAL CHECK

SNO Description Remark


1 Check the Doors are open/close properly Checked OK
2 Check Lock and key working/availability Checked OK
3 Breaker manual spring charging operation Checked OK
4 Spring Charge indication Checked OK
5 Breaker motor spring charging operation Checked OK
Check CB opened/CB closed position indicator
6 Checked OK
available/working
7 Check Earth switch open position indication Checked OK
8 Check Earth switch closed position indication Checked OK
9 Check Panel lighting and door limit switch fixed/working Checked OK
10 Check Panel heater fixed/working Checked OK

6. TESTING EQUIPMENT DETAILS:

Serial
Equipment Name Make Model Calibration Valid Up to
Number
Insulation Tester Kyoritsu 3125 W0361152 24/3/2016
CB Timing Kit Megger EGIL 1302602 18/07/2016
MOM MEGGER MOM PB976V (V1) 06/08/2016

8.REMARKS/OBSERVATION: All the test results found satisfactory.

TESTED BY WITNESSED/APPROVED BY
CIVIL CONTRACTING CO. LLC MAJAN ELCTRICITY CO. (SAOC)
Sign Sign

Name T. Satti Reddy,PE007/2016 Name Talal Hamed Al Suqatari


Date 29-08-2016 Date 29-08-2016