1
Introduction
Technical Information:
Hollow Core Floors are manufactured using a long line
casting technique with automatic casting equipment 100 mm thick
which places high strength, low water/cement
ratio concrete under a high degree of vibration and 1200 mm Nominal width
compaction.
150 mm thick
200 mm thick
250 mm thick
The section profile incorporates hollow cores to reduce 1200 mm Nominal width
self-weight without significant reduction in section
stiffness. Reinforcement is by high tensile prestressing
strand or wire which has an ultimate strength of 300 mm thick
more then 3 times that of conventional high tensile 350 mm thick
reinforcement. The structural performance resulting 400 mm thick
450 mm thick
from the combination of those featured produces a
slab which is highly efficient and economic for any
load/span situation.
1200 mm Nominal width
We confirm that the tests as detailed in your document title Fixings Testing on Bison Hollow
Core Slabs, were carried out in our laboratory. The tests were carried out on the soffit of a
standard 150 mm deep slab, and the results are a true record of the tests. Therefore, we can
recommend that the fixings described are suitable for use with hollow core slabs, up to the
safe working loads stated.
Yours Faithfully
For Bison Manufacturing Ltd
Dr Kamel BENSALEM
Chief Structural Engineer
2
2
Chemical Fixings
1 FIS V Resin
2 FIS S Static nozzle
3 FIS H N anchor sleeve with net
Suitability
Steel Constructions
Machines
Gratings
Gates
Handrails
Technical Data Brackets
Pipelines
1) 2) Sanitary items
Cable trays
1) FIS H N
Type Art.-No. drill min. drill hole Min. Min. Mortar anchor per fits Qty. per box
depth anchorage depth anchorage depth sleeve filling quantity 360 ml-cartridge
do t hv hv
[mm] [mm] [mm] [mm] pcs.
FIS H 16 x 85 N 50470 16 95 90 85 15 11 8/M8 20
FIS H 18 x 85 N 50472 18 95 90 85 17 10 10/M10 20
FIS H 20 x 85 N 50474 20 95 90 85 19 9 12/M12 20
3
Steel Anchors
Description Description
The fischer Hollow Ceiling Slab anchor FHY has been developed The FDA-R is a drop in anchor with a rim so that the anchor
specially for fastenings in hollow core slabs of prestressed remains flush with the surface of the substrate at all times. As
concrete. It is designed for use with standard bolts or threaded the anchor retains its position item that has been attached to
rods with metric threads from M6 to M10. The FHY is installed the substrate can be removed and refitted several times with
flush with the concrete surface. When the bolt or the nut is no effect. The drill hole can be a slightly deeper depth without
tightened a tapered element is pulled into the sleeve, which effecting the anchors performance. This anchor is suitable for
presses this outwards. In this way, the FHY presses against the use with all types of screws and studs with a metric thread.
sides of the hole, creating a friction fit. If the anchor encounters
a cavity during installation, the expansion of the sleeve forms a
Y shape. The holding power is now the result of a combination
of expansion pressure and formfit. The FHY offers considerable Building Materials Suitability
scope in the location of attachment points. Unlike other Concrete B15 and dense Ideal for fastening bolts and
competing products, it does not have to be located at the centre natural stone plus hollow threaded rods in combination
of the cavity axis, which is often very difficult to define. Instead, core slabs. with general plumbing
it can be located down to a minimum distance of 50 mm from materials.
the pre-stressing steel. Air-conditioning
Heating & ventilation
Pipes
Building Materials Certification Sanitary items
Hollow ceiling slabs of Cable trays
prestressed concrete,
concrete B55.
from M8
Suitability Installation
All types of anchoring:
Cross beams
Pipes and ventilation Approved for:
ducts Pre-stressed hollow-core
Suspended ceilings concrete slabs C45/55 (only
Safety engineering Note: The correct setting tool must be used on installation,
zinc-plated version) otherwise anchor may not be set correctly.
Cable trays.
Technical Data
Type Art.-No. approval drill- min. drill effect. anchorage anchor thread min. bolt max. bolt qty.
hole depth depth length penetration penetration per box
DIBt do t hef l M e2 e1
[mm] [mm] [mm] [mm] [mm] [mm] pcs.
FHY M 6 30138 10 50 30 37 M6 37 45 50
FHY M 8 30146 12 60 35 43 M8 43 55 25
FHY M10 30148 16 65 40 52 M 10 52 60 20
FHY M 6 A4 30139 10 50 30 37 M6 37 45 50
FHY M 8 A4 30147 12 60 35 43 M8 43 55 25
FHY M10 A4 30151 16 65 40 52 M 10 52 60 20
1 3 5
Description Description
fischer concrete screws have a specially hardened thread. The frame fixing screw, type FFS provides stress free standoff
The lower turns of the thread also have a serrated edge. The installations without the use of additional plugs. The continuous
diameter of the hole and the thread of the screw are adapted so thread ensures that the fixture cannot be pulled up against the
that the serrated thread of the screw cuts into the concrete. The building material. Distortion of the profile will therefore not
thread turns creating a fine undercut, ensuring that the load is take place, either during or after installation (for instance when
safely supported by a perfect form fit. The teeth allow the thread applying insulating foam). The distance is also maintained
to cut into the concrete, thereby reducing the amount of energy when loads are subsequently applied. The long screw length
required to insert the screw into its position. make exact positioning easy.
Type Art.-No. approval drill- drill hole dia. screw dia. drill hole anchorage thread width across qty.
in object depth depth nut per box
DIBt do df ds h0 hef M sw
ETA [mm] [mm] [mm] [mm] pcs.
FBS 6 M8/5 66949 6 8 7.6 60 55 M8 SW 10 100
FBS 6 M8/M10I 66950 6 8 7.6 60 55 M8 SW 10 100
5
General Fixings
SX Plug M Anchor
Hollow Core Slab Fixing Systems
Description Description
This plug has been developed to expand 4-ways. It form A conical expansion fixing of glassfibre reinforced nylon and
locks in solid the substrates which guarantees maximum brass taper for universal installation with machine screws and
load bearing capabilities. The area of application ranges from threaded bolts. Designed for a high degree of expansion, the
solid materials through to perforated materials. The screw fixing is not sensitive to inaccuracies in drilled holes or material
tolerance range allows the safe use of different screw types tolerances. The fixing is also ideal for fastenings in thin concrete,
and diameters, especially for chipboard screws and the fischer artificial stone and other pressure-resistant flat material.
ASL universal spacer screws.
Type Art.-No. drill min. drill hole plug length chipboard qty. per box
depth = min. anchoring depth screw
do t l = hef ds x ls
[mm] [mm] [mm] [ mm] pcs.
SX 4 x 20 70004 4 25 20 2-3 200
SX 5 x 25 70005 5 35 25 3-4 100
SX 6 x 30 70006 6 40 30 4-5 100
SX 6 x 50 * 24827 6 60 50 4-5 100
SX 6 x 50 R 78185 6 60 50 4-5 100
SX 8 x 40 70008 8 50 40 4,5 - 6 100
SX 8 x 65 24828 8 75 65 4,5 - 6 50
SX 10 x 50 70010 10 70 50 6-8 50
SX 10 x 80 24829 10 95 80 6-8 25
SX 12 x 60 70012 12 80 60 8 - 10 25
SX 14 x 70 70014 14 90 70 10 - 12 20
SX 16 x 80 70016 16 100 80 12 (1/2) 10
* without collar
6
General Fixings
Testing
The table below shows the ultimate and maximum safe working loads of all the anchors tested into the section product of BISON
hollow core slabs or Tarmac Topfloor 150 spirall units. The tested slabs have a concrete web thickness of 25 mm and a minimum
compressive strength of 55N/mm2. These results are tabulated below starting with the highest performing anchor at the top.
Technical data
Type drill- average ultimate safe working characteristic
load load axial spacing
[mm] kN kN
FIS V 360 S injection resin with net 18 25.80 6.45 240/400
FHY M10 metal expansion unit 16 16.10 4.02 200
FDA-R M10 rimmed drop-in anchor 12 16.92 3.38 200
FBS 8 self tapping screw 8 7.83 1.57 100
KD 8 metal gravity toggle 20 12.00 3.00 200
M Anchor M10 20 10.60 1.51 200
FFS self tapping screws 6 9.96 2.50 75
SX10 nylon plug 10 6.78 0.96 200
FHY M6 metal expansion unit 10 2.96 0.74 200
Conclusion
It is in our opinion that the fixing types tested in conjunction with hollow core slabs e.g. Bison are highly suitable for typical applications
e.g. various M + E services, timber battens, insulation, suspended ceilings etc. As the tests were conducted into the thinnest of the
manufactured slabs (150 mm overall depth), it is our opinion that the fixings would be suitable for all slab sections varying from 150
- 450 mm deep with web thicknesses greater than 25 mm.
The test results for all of the fixing tested offers good variation in ultimate loads. This allows the Engineer/Architect/End user to have
a broad range of anchors to choose from depending on both function or load performance.
Axial spacings vary from anchor to anchor due to the expansion or form-locking characteristics. In our opinion it would be suitable
to have axial spacing >200 mm for all the anchors tested except the FIS V 360 S and FFS screw. The axial spacing for the FIS V
360 S as written above are conservative, for more detailed, comprehensive and possibly smaller spacing further testing should be
carried out.
Note: The FIS V 360 S resin with FIS H N net achieved a very large concrete cone failure during testing. This cone is larger than
the characteristic cone failure expected in standard reinforced concrete due to the compressive stress patterns that the pre-stressing
induces. For further information on the testing, please contact our Technical Team.
7
Precast Hollow Core Slabs 2012 / 01
We cannot be held responsible for any errors within this document and
we reserve the right to make technical and range modifications without
notice.
No liability is accepted for printing errors and omissions.