Anda di halaman 1dari 6

#(s17H# CIUDAD : OCUMARE AO : 2017

ALTERNATIVA : 1 FECHA : 06-JUL-17


PAG: 1
HORA : 08:29

CIRCUITO NO. 2 El Playon S/E INDEPENDENCIA 34.5KV


TENSION FASE A FASE 13.80 KV
FACTOR DE POTENCIA 0.90 %
% DE TENSION EN BARRA 105. %

DEMANDA 2260. KVA 2032. KW


989. KVAR

TRAM / KVA CONEC C A R G A S LONGIT C O N D U C T O R IMPEDANCIA


CARGA/TRAMO PCT DE CAIDA % KVLL PERD./SECC. CORRIENTE
CARGA S PRESENT KW KVAR KM TIPO % CARGA RESIS REACT KW
KVAR TRAM. ACUM. KW KVAR AMPS

1.........3 FASE ......... 0.000 4/0 ARV 23.70 0.000 0.000 2032.
989. 0.00 0.00 105.00 0.0 0.0 90.1
1 0.00 0. 0.
2.........3 FASE ......... 0.002 4/0 ARV 23.70 0.001 0.001 2032.
989. 0.00 0.00 105.00 0.0 0.0 90.1
2 0.00 0. 0.
3.........3 FASE ......... 0.000 4/0 ARV 23.70 0.000 0.000 2032.
989. 0.00 0.00 105.00 0.0 0.0 90.1
3 0.00 0. 0.
4.........3 FASE ......... 0.059 4/0 ARV 23.70 0.017 0.025 2032.
989. 0.03 0.03 104.97 0.4 0.6 90.1
4 0.00 0. 0.
5.........3 FASE ......... 0.059 4/0 ARV 23.70 0.017 0.025 2032.
988. 0.03 0.06 104.94 0.4 0.6 90.1
5 65.00 140. 68.
6.........3 FASE ......... 0.097 4/0 ARV 22.06 0.028 0.041 1891.
920. 0.04 0.11 104.89 0.6 0.9 83.8
6 0.00 0. 0.
7.........3 FASE ......... 0.250 4/0 ARV 22.06 0.071 0.105 1891.
919. 0.12 0.22 104.78 1.5 2.2 83.8
7 0.00 0. 0.
8.........3 FASE ......... 0.059 4/0 ARV 22.06 0.017 0.025 1889.
917. 0.03 0.25 104.75 0.4 0.5 83.8
8 0.00 0. 0.
9.........3 FASE ......... 0.000 4/0 ARV 22.06 0.000 0.000 1889.
916. 0.00 0.25 104.75 0.0 0.0 83.8
9 125.00 270. 131.
10.........3 FASE ......... 0.029 4/0 ARV 18.92 0.008 0.012 1619.
785. 0.01 0.26 104.74 0.1 0.2 71.9
10 150.00 324. 157.
11.........3 FASE ......... 0.036 4/0 ARV 15.14 0.010 0.015 1295.
629. 0.01 0.27 104.73 0.1 0.2 57.5
11 0.00 0. 0.
12.........3 FASE ......... 0.054 4/0 ARV 15.14 0.015 0.023 1295.
628. 0.02 0.29 104.71 0.2 0.2 57.5
12 0.00 0. 0.
13.........3 FASE ......... 0.070 4/0 ARV 15.14 0.020 0.030 1295.
628. 0.02 0.31 104.69 0.2 0.3 57.5
13 0.00 0. 0.
14.........3 FASE ......... 0.067 4/0 ARV 15.14 0.019 0.028 1295.
628. 0.02 0.33 104.67 0.2 0.3 57.5
14 75.00 162. 78.
15.........3 FASE ......... 0.103 4/0 ARV 13.25 0.029 0.044 1133.
549. 0.03 0.36 104.64 0.2 0.3 50.3
15 75.00 162. 78.
16.........3 FASE ......... 0.041 4/0 ARV 11.35 0.012 0.017 971.
471. 0.01 0.37 104.63 0.1 0.1 43.1
16 50.00 108. 52.
17.........3 FASE ......... 0.072 4/0 ARV 10.09 0.021 0.031 863.
418. 0.02 0.39 104.61 0.1 0.1 38.4
17 0.00 0. 0.
21.........3 FASE ......... 0.041 4/0 ARV 2.84 0.012 0.018 243.
118. 0.00 0.39 104.61 0.0 0.0 10.8
21 112.50 243. 118.
22.........3 FASE ......... 0.000 4/0 ARV 0.00 0.000 0.000 0.
0. 0.00 0.39 104.61 0.0 0.0 0.0
22 0.00 0. 0.

INICIANDO RAMA EN 17
18.........3 FASE ......... 0.097 4/0 ARV 7.25 0.028 0.041 620.
301. 0.01 0.40 104.60 0.1 0.1 27.6
18 25.00 54. 26.
#(s17H# CIUDAD : OCUMARE AO : 2017
ALTERNATIVA : 1 FECHA : 06-JUL-17
PAG: 2
HORA : 08:29

CIRCUITO NO. 2 El Playon S/E INDEPENDENCIA 34.5KV


TENSION FASE A FASE 13.80 KV
FACTOR DE POTENCIA 0.90 %
% DE TENSION EN BARRA 105. %

DEMANDA 2260. KVA 2032. KW


989. KVAR

TRAM / KVA CONEC C A R G A S LONGIT C O N D U C T O R IMPEDANCIA


CARGA/TRAMO PCT DE CAIDA % KVLL PERD./SECC. CORRIENTE
CARGA S PRESENT KW KVAR KM TIPO % CARGA RESIS REACT KW
KVAR TRAM. ACUM. KW KVAR AMPS

19.........3 FASE ......... 0.059 4/0 ARV 6.62 0.017 0.025 566.
274. 0.01 0.41 104.59 0.0 0.0 25.2
19 75.00 162. 78.
20.........3 FASE ......... 0.048 4/0 ARV 4.73 0.014 0.021 405.
196. 0.00 0.41 104.59 0.0 0.0 18.0
20 0.00 0. 0.
23.........3 FASE ......... 0.074 4/0 ARV 4.73 0.021 0.031 405.
196. 0.01 0.42 104.58 0.0 0.0 18.0
23 0.00 0. 0.
26.........3 FASE ......... 0.012 4/0 ARV 0.00 0.004 0.005 0.
0. 0.00 0.42 104.58 0.0 0.0 0.0
26 0.00 0. 0.
29.........3 FASE ......... 0.006 4/0 ARV 0.00 0.002 0.003 0.
0. 0.00 0.42 104.58 0.0 0.0 0.0
29 0.00 0. 0.
30.........3 FASE ......... 0.129 4/0 ARV 0.00 0.037 0.055 0.
0. 0.00 0.42 104.58 0.0 0.0 0.0
30 0.00 0. 0.

INICIANDO RAMA EN 23
24.........3 FASE ......... 0.063 4/0 ARV 4.73 0.018 0.027 404.
196. 0.01 0.43 104.57 0.0 0.0 18.0
24 112.50 243. 118.
25.........3 FASE ......... 0.034 4/0 ARV 1.89 0.010 0.014 162.
78. 0.00 0.43 104.57 0.0 0.0 7.2
25 0.00 0. 0.
27.........3 FASE ......... 0.067 4/0 ARV 1.89 0.019 0.029 162.
78. 0.00 0.43 104.57 0.0 0.0 7.2
27 75.00 162. 78.
28.........3 FASE ......... 0.020 4/0 ARV 0.00 0.006 0.009 0.
0. 0.00 0.43 104.57 0.0 0.0 0.0
28 0.00 0. 0.

PERDIDAS TOTALES EN
EL CIRCUITO 4.6 6.8
#(s17H# CIUDAD : OCUMARE AO : 2017
ALTERNATIVA : 1 FECHA : 06-JUL-17
PAG: 2
HORA : 08:29

S U M A R I O P O R C I R C U I T O

C I R C U I T O MAXIMA CAIDA DE TENSION MAXIMA


CARGA EN CONDUCTOR PERDIDA EN KW DEMANDA

TRAMO PORCENTAJE TRAMO


PORCENTAJE (KW) (KVA)

2 El Playon S/E INDEPENDENCIA 34.5KV 28 0.43 4


23.69 4.57 2260.08

DEMANDA TOTAL CALCULADA


2260.08 #(s10H