Heating controller
Operating manual
2
Display und operating elemente
Days:
1=Monday Daytime
2=Tuesday etc.
Roomtemperature
heating mode
adoption
(with the right
Time bar rotary knob)
temperature-/
time process of the
actual day measured
temperatures of:
= Boiler
= Flow
= DHW
= Room
= Outside
Time bar:
The selected heating program is shown
b1 b2 b3
Time bloc 1 Time bloc 2 Time bloc 3
Comfort modus
Normal modus
Reduced modus
3
Notes:Display und Bedienelemente
4
1 Operation with the cover closed
Cover closed 1 2
Operating modes:
All settings are valid for both Weekly clock programme Automatic changeover from heating to
heating circuits, mixed and direct warm-water heating - reduced operation
at the same time! Clock programme exception day After running, the programme returns
automatically to the weekly clock pro-
gramme
Heating No clock programme
Heating/warm-water heating is carried
out continuously according to the set
value.
Reduced heating No clock programme
Reduced heating is carried out according
to the set value
No warm-water heating
Holiday Heating/Warm-water heating OFF
Frost/room protection function active
Heating OFF / Summer operation Heating is OFF
Warm-water heating is active according
to the weekly clock programme.
Frost/room protection function active
Manual/emergency operation Heat generator continually ON
(as per boiler thermostatt setting)
Heating circuit pump continually ON
Warm-water heating continually ON
Check boiler temperature thermostat!
Operate the mixer manually!
Request help from an expert!
A blinking symbol shows that in addition to the current operating mode,
a further function has been temporarily activated.
Warm-water heating is always active parallel to heating in the selected operating
mode and starts earlier by the set time period (factory setting, 60 mins.).
5
1.2 Set room temperature temporarily
Cover closed
Cover closed
Party function
Using the push button, heating can be
temporarily switched on during the re-
duction phase, the party symbol
blinks. If the party function is activated
during heating, the party symbol
appears.
When switching to reduced heating, the
party symbol blinks until the end of the
reduced heating period.
The duration of the party function is set The symbol of the party function
in setting 3:09. is blinking
The party function can be stopped at any
time by pushing the button again.
Operating lock
The active operating lock makes it im-
possible to change settings by mistake.
The operating lock is valid for all
functions
Press the push button for 5 seconds
until all arrows to right and left of the
display are shown.
In order to release the operating lock,
the button must be pushed again for
5 seconds until the arrows to the left
and right of the display can be seen.
6
1.4 Activation of the holiday programme
Cover closed
Cover closed
7
1.6 Activate the clock programme exception day
Cover closed 1
Cover closed 1 2
8
1.8 Manual / emergency operation
9
2 Operation with the cover open
RESET CLEAR
10
2.1 Setting the date
3 4
11
2.2 Setting the clock time
12
2.3 Check temperatures and operating mode
Checking the heating circuit Measured temperatures: The inquiry of the operating mode refers
operating mode: = Generator temperature to the current heating circuit
2. Continue to turn the left rotary knob. =Flow temperature
= Domestic hot water temperature
The current operating mode for the
= Ambient temperature
heating circuit is shown = Outside temperature
The following operating modes can be Setpoint value
shown :
0 = OFF 4 = Comfort
1 = Frost protection 5 = Pre-heating
2 = Reduced heating 7 = Manual
3 = Heating
Invalid measuring values are shown
as !
Cover open
13
2.5 Setting the weekly clock programme
5 6
The programme is only saved
(memorised) after all time periods b1,
b2, b3 have been set and confirmed
with the push-button.
The newly programmed time bars are
then shown.
2. 1.
Resetting of factory values for the Factory settings for the weekly clock programme:
weekly clock programme
Daily periods Room heating Warm-water supply
6. Using a fine point, press the CLEAR
button until the time bars on the Week day Display normal reduced On Off
display jump back to the factory Mo-Fr 06.00 22.00 05.00 22.00
settings.
Sa-Su 07.00 23.00 06.00 23.00
14
2.6 Setting the clock programme exception day
2. 1. 2. 1.
5
The programme is only saved
(memorised) after all time periods b1,
b2, b3 have been set and confirmed
with the push-button.
The newly programmed time bars are
then shown.
Reloading of factory values for the Factory settings for the clock programme exception day:
clock programme exception day
5. Using a fine point, press the CLEAR
Room heating Warm-water supply
button until the time bars on the dis- normal comfort reduced On Off
play jump back to the factory set-
08.00-17.00 17.00-23.00 23.00-08.00 07.00 23.00
tings.
15
2.7 Setting the room temperature
16
2.8 Setting the automatic holiday programme
17
3 Settings in the service level
Open the cover 1 2
WARNING:
Unintentional use of the CLEAR but-
ton deletes plant-specific settings
which can lead to malfunctioning of
the system.
Open the cover
18
3.2 Setting level 3 - Room temperature control
mixed heating circuit
75 3: 03
1.2
3:0 65
2
0.8
55
Flow temperature
45
0.4
25
35
C
25 3:01
0
re
atu
per
15
tem 15
C
om
Ro point
Outside temperature set
5
-20 -15 -10 -5 0 5 10 15 20 25 C
19
3.2 Setting level 3 - Room temperature control
mixed heating circuit
Setpoint
3
Set value
9
-4 -3 -2 -1 0 +1 +2 +3 +4
Room temperature deviation (K)
Example:
Increase room temperature = 2 K; set value = 6
Decrease of the flow temperature = 12 K
20
3.3 Setting level 3 - Room temperature control
direct heating circuit
75 3: 03
1.2
3:0 65
2
0.8
55
Flow temperature
45
0.4
25
35
C
25 3:01
0
re
atu
per
15
tem 15
C
oom int
R po
Outside temperature set
5
-20 -15 -10 -5 0 5 10 15 20 25 C
21
3.3 Setting level 3 - Room temperature control
direct heating circuit
3:08 Heating limit as per flow temperature set value -1010 -10 K
Summer operation becomes active when the difference between the calculated flow temperature and the room temperature
is lower then the set value.
The pump is reduced by the value given at setting 7:03.
If the difference increases to 2 K above the switch-off value, heating is started again.
-10 = OFF
2 = function active (recommended for control strategies and ).
22
4 Settings in the coded service level
supply
5:04 = Legionella protection temp.
5:05 = Day selection legionella
protection
5:07 = Warm-water supply parallel or
with priority over heating
6:00 = Minimum heat generation
temperature
6:04 = Maximum heat generation
temperature
6:05 = Switching difference heat
generator.
7:00 = Proportional mixer range
7:03 = Follow-up time circulation pump
7:13 = Running time mixing valve
23
4.1 Setting level 3 - Room temperature control
24
4.3 Setting level 6 - Heat generator (Boiler)
25
5 Constant values
The functions and values described in the following can be neither selected or set. It is however necessary to know them, as
they have an influence on the functioning of the controller.
26
6 General points
1 warm-water supply
1 heat generator with a one-stage
burner Manual/
emergency mode
OpenTherm
Operation is carried out only via the BUS
SR 5811
6.3 Hydraulic
Application alternatives:
1. Without heat generator
Do not attach the boiler sensor
2. Without warm-water supply
Do not attach the warm-water sensor
3. Direct heating circuit (without mixer)
Do not attach the flow sensor
Set the setting 3:01 lower by 5 K.
Pump
Boiler sensor
Burner
DHW sensor
27
7 Dimensions and installation
Determination of position
The VS 5511 plus control unit should be
placed as close as possible to the heat B
generator/heating circuit so that only a
short cable is required.
127.5
145
control unit is fastened to the wall using
three screws.
1. Drill the top, middle hole and screw in
12 11 10 9 8 7 6 5 4 3 2 1 7 6 5 4 3 2 1 L N N N
the screw.
2. Hang in the unit without the clamp
cover and mark the lower two screw
holes. B
3. Remove the unit and drill the two
lower holes. 180.5
4. Replace the unit again and fasten the 200
lower screws.
The controller can now be connected
to the electricity supply. Terminal cover 44.3
Controller housing
Installation notes
The electrical installation and protec- Attachment hook controller housing 2
tion must be carried out and must
confirm to local regulations. B = Screw anchorage at the wall
The VS 5511 plus must have a conti-
nual electricity supply in order to
ensure functioning at all times.
145
Peripheral switches must be limited
to emergency or main switches
which are usually continually
switched on.
Before start-up, it should be checked
that all components are connected
correctly to the electricity supply.
If strong inductive forces exist in the
44.8
vicinity of the controller (protectors,
magnet valves etc.), interference
suppression using RC links directly
to the coil connectors of the interfe-
ring components may be necessary.
Recommended RC-links: 0.047 PF,
100 : . for 250 VAC (e.g. Bosch,
RIFA, etc...).
7.2 Dimensions
VS 5511 plus
28
7.3 Installation SR 5811
Determination of position
If the SR 5811 is used to record the room
Front view Side view
temperature, the following positioning open
106
actors should be taken into considerati-
on:
In the reference room on an inside
wall with normally heated next room.
No other controllers, e.g. thermostat
valves, must be active in this room.
Approx. 150 cm above floor level.
98
96
Ensure free air circulation (not in
niches or cupboards etc.)
Not directly next to a heat source or
exposed to direct sunlight.
Cable connection of the SR 5811
90.4
ved the operating unit. Never touch
Wiring room
the wires, printed back or connec-
tions of the operating unit.
91.3
4.2
56
R95
coiling and twisting of cables). 1 4
Cam
7.4 Dimensions
SR 5811
29
7.5 Start-up
The mains current connec- Mains current connection functional units (230 VAC):
tions to the right no. 1-7/LN are live
with 230 Volt. These clips may only be Alternative 1 Alternative 2
touched if they are not connected to
the electricity supply, otherwise there
Switching contact
Switching contact
Switching contact
Switching contact
is a danger of fatal electric shock.
Open
Close
Mixer
Pump
Boiler
Boiler
DHW
DHW
7.6 Electrical installa-
tion diagram 3.15 A
temperature! N
Controller test
In order to test the controller and the
T T T T T T T T
Flowtemp.
switched on:
sensor
sensor
Boiler
Boiler sensor
1 4
T
1 4
T
30
8 Help in solving problems
If no basic display or an error message
are shown after switching on, the expla-
nations in the following table may be of
help.
Problem Possible cause Remedy
No display Controller not switched on Check the fuses, switch the controller on.
External switch is set to manual/emergency Change the switch for manual/emergency
operation operation.
SR 5811 deactivate Push the RESET button
If necessary, carry out a plausibility test
with a second controller.
Error display Communication to VS 5511plus is Check connecting cable. Has the controller
interrupted been installed properly?
31
9 Technical data
32
9.3 Sensor resistance values
b1, b2, b3 Time periods which can be set for the clock programme.
h Hours
Actual value Temperature measured
K Kelvin, difference in temperature
min Minutes
Net Mains electrical supply 230V VAC
OpenTherm 2-cable data bus for heating technology
Set point value Temperature set by the operator or calculated by the controller, which controls the actual
value set by the heating controller.
33
Notes:
34
10 Index
A Set weekly clock programme 14
Automatic holiday programme setting 17 Settings in the coded service level 23
Settings in the service level 18
C Start-up 30
Check heating circuit operating mode 13
Check temperatures and operating mode 13 T
CLEAR 10 Technical data 32
CLEAR function (factory setting charge) 18
Clock programme activate exception day 8 W
Clock programme set exception day 15 Warm water heating 22
Control strategy 19 What does the VS 5500 eco control ? 27
Correction of faults 31 What makes up the VS 5500 ? 27
E
Explanation of terms and abbreviations 23
F
Frost protection function 26
H
Heating curve 19, 21
Heating limit 8
Hydraulic 27
I
Installation SR 5811 29
Installation VS 5511 eco 28
L
left rotary knob 10
M
Manual/emergency operation 9
P
Party function/operating lock 6
R
RESET 10
right rotary knob 10
Room temperature setting 16
Room temperature adjust temporarily 6
Room temperature influence switch off temporarily 13
Room temperature adjustment direct heating circuit 21
Room temperature adjustment mixed heating circuit 19
S
Select operating mode 5
Sensor resistance values 33
Set clock time 12
Set date11
35
Manufacture or distribution: