Anda di halaman 1dari 24

BUSSMANN

Application note 3148


Effective September 2015
Supersedes July 2015 SERIES

Quik-Spec Coordination Panelboard (QSCP)

Contents
Description Page
Description Page
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 QSCP applications and fuse sizing
Features/benefits. . . . . . . . . . . . . . . . . . . . . . . . . . 2 Lighting circuits. . . . . . . . . . . . . . . . . . . . . . . . 17
QSCP Overview . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 Motor circuits . . . . . . . . . . . . . . . . . . . . . . . . . 18
Selective coordination made easy. . . . . . . . . . . . . 5 Transformers. . . . . . . . . . . . . . . . . . . . . . . . . . 19
Comparing fusible branch circuit panelboards . . . 6 CUBEFuse sizing for motors (115-575Vac). . . 20
QSCP Short-Circuit Current Ratings (SCCRs). . . 7-8 Protecting leads fed from Uninterruptable
Power Supplies (UPS) . . . . . . . . . . . . . . . . . . . . 21
How to achieve selective coordination. . . . . . . 9-10
Surge Protective Devices (SPDs) . . . . . . . . . . . . 22
Selective coordination using fuses . . . . . . . . . . . 11
Reference materials . . . . . . . . . . . . . . . . . . . . . . 23
Selective coordination using upstream Eaton
thermal magnetic circuit breakers. . . . . . . . . . . . 12
240, 480, 600Vac Quick Pick tables . . . . . . . . 13
240Vac Circuit breaker tables. . . . . . . . . . . . . 14
480Vac Circuit breaker tables. . . . . . . . . . . . . 15
600Vac Circuit breaker tables. . . . . . . . . . . . . 16
Application Note 3148 Quik-Spec Coordination Panelboard (QSCP)
Effective September 2015 application note

Introduction
The Bussmann series Quik-Spec Coordination Panelboard (QSCP) By utilizing the Bussmann series CUBEFuse Compact Circuit
is innovative in many ways compared to other commercially available Protector Base (CCPB) fusible disconnect, the panel is rated up
branch circuit panelboards, while providing the benefits of current- to 600Vac and is capable of providing up to a 200kA short-circuit
limiting fusible overcurrent protection. The QSCP can simplify the current rating (SCCR). At the same time, it provides many features
effort to ensure Code compliance for systems where selective that increase electrical safety.
coordination is a mandatory NEC requirement, as well as for other
electrical systems.

Issue Features Benefits


Simplified selective coordination designs for fault levels up to
Selective coordination between branch and upstream fuses or 200kA, including systems required by NEC 620.62, 700.28,
upstream Eaton circuit breakers using published tables 701.27, 708.54 and 645.27

UL Listed panel short-circuit current ratings available up to 200kA Easier to comply with electrical system protection requirements
in NEC 110.10
Easily complies with the interrupting rating requirements of
UL Listed, high, 300kA AC interrupting rating Low-Peak fuses NEC 110.9

Code No need to be constrained by series ratings


compliance Current-limiting overcurrent protection integrated with innovative,
CCPB branch circuit fused disconnect compact, UL 98, horsepower rated, load-break branch circuit
disconnect
U.B.C. & C.B.C. Seismic Qualified, I.B.C. Approved (Uniform Meets the requirements of installation in areas subject to
Building Code, California Building Code, International Building earthquakes
Code)
Helps comply with 2014 NEC 700.8 that requires a listed SPD
Surge Protective Device option to be installed in or on all emergency system switchboards and
panelboards and 517.26 for healthcare life safety branch
Helps ensure continued circuit protection at the specified
CUBEFuse/CCPB amp rating rejection system standard branch circuit amp rating
Finger-safe CUBEFuse and disconnect assembly Helps prevent exposure to live components
(with dead-front cover installed)
Safety Permanent lockout/tagout provisions on main and branch circuit Allows for isolation of individual branch circuit loads or entire
disconnects panel for safe work practices
CUBEFuse and CCPB disconnect interlocked Helps ensure circuit is de-energized before fuse removal
Service fuses without removing deadfronts or interior trim Reduced exposure to live electrical parts
UL Listed with up to 600Vac panel voltage rating Suitable for use on most AC systems, 600V or less
UL Listed 125Vdc panel voltage rating on MLO with 20kA SCCR Suitable for use on systems, 125Vdc or less and 80A or less
with CCPB 80 amps or less. branch circuits
Space requirements equivalent to other commercially available
Standard 20 inch panel width circuit breaker branch circuit panelboards
Non-fused main disconnect, fused main disconnect or main lug Provides design and overcurrent protection options
only configurations available up to 400A
Local open fuse indication Open circuits can be identified quickly and easily
Panelboard branch circuits configurable up to 100A in 1-, 2- and
CCPB branch circuit fused disconnect 3-pole devices with Class CF CUBEFuse overcurrent protection
Ease and (Class J, time-delay or fast-acting performance)
flexibility
Surface and flush mount enclosures
18, 30 and 42 branch circuit positions
NEMA 1 and 3R enclosures
Door-in-door available Installation design options
UL service entrance rated panel option
Sub-feed lug options
Sub-feed fused disconnect switch option
Spare CUBEFuses are readily available when in place, speeding
Equipped with six space spare CUBEFuse holder maintenance procedures

2 www.bussmann.com
Quik-Spec Coordination Panelboard (QSCP) Application Note 3148
application note Effective September 2015

QSCP Overview 200A and 400A main disconnect


Ease of selective Fused and non-fused versions
coordination with upstream Fused disconnects use time-delay or fast-
Bussmann fuses or Eaton acting Class J fuses
circuit breakers
Allows for isolation of all branch circuits
Panel SCCR available up to:
200kA for 600Vac or less Permanent lockout means
panels, 20kA for 125Vdc or Contact blades visible without removing
less panels. dead-front cover
600Vac or less Interlock with dead-front cover ensures
125Vdc, MLO only, CCPB switch is OFF before removing cover
80A or less.
30A, 60A and 100A CCP fused main
30A, 60A, 100A, 200A or disconnect
400A panel rating
Integrates fuse protection and disconnect
Standard 20 width
into single, finger-safe device
18, 30 and 42 branch Time-delay or fast-acting Class CF
positions available
CUBEFuse with Class J performance
Sub-feed lug options Switch interlock prevents removing fuses
Sub-feed fused disconnect while energized
option Local open fuse indication
Surge Protective Device
option CCPB fused branch disconnect
Equipped with 6 space Uses time-delay or fast-acting Class CF
spare CUBEFuse holder CUBEFuse with Class J performance
Surface or flush mount CCPB SCCR:
Door-in-door trim available 200kA/600Vac

20kA/125Vdc, 80A or less


Hp rated, branch circuit disconnect
Circuits up through 100A, 1-, 2- and
3-pole
Permanent lockout provisions
Local open fuse indication
Switch interlock prevents removing fuses
while energized
Fuse ampacity rating rejection

Main Lug Only (MLO)

QSCP with time-delay QSCP with fast-acting


CUBEFuses for branch circuit CUBEFuses for branch circuit
protection of all types of loads protection of electrical loads such
Fused main disconnect as those fed from a UPS

www.bussmann.com 3
Application Note 3148 Quik-Spec Coordination Panelboard (QSCP)
Effective September 2015 application note

Innovative time-delay or fast-acting Class CF CUBEFuse contact CCPB disconnect handle provides clear
blade design in conjunction with CCPB fused disconnect provides circuit status indication with colored and
amp rating rejection at specified levels (15, 20, 30, 40, 50, 60, 70, international symbol markings
90 and 100A - See Table 3). Blade design also interlocks with CCPB Local, neon open fuse indication
disconnect assembly to prevent fuse removal while energized (requires panelboard bus be energized,
circuit closed and minimum 90Vac)
Permanently installed
integrated lockout/ Time-delay or fast-acting Class CF
tagout provisions CUBEFuse provides Class J overcurrent
protection

Bolt-on style bus


connector

Table 1. CCPB specifications


Typical installed amp range Yellow label time-delay and blue label fast-acting CUBEFuse.
Fuse Max Time-delay Time-delay Fast-acting Time-delay CUBEFuse has optional open fuse indication to provide
CCPB* part amp CCPB non-indicating indicating non-indicating positive fuse status at a glance. The fast-acting (blue label) version is
number Poles range amps fuses fuses** fuses non-indicating only.
CCPB-1-15CF 1 TCF1RN, FCF1RN,
TCF3RN, TCF6, FCF3RN,
CCPB-2-15CF 2 1-15 15 TCF6RN, TCF10, FCF6RN, Table 2. CCPB horsepower ratings
TCF10RN, TCF15 FCF10RN,
CCPB-3-15CF 3
TCF15RN FCF15RN
Amp Hp rating @ Vac
CCPB-1-20CF 1
TCF17-RN, TCF17-, CCPB disconnect rating 120 240* 240** 480 600
CCPB-2-20CF 2 1-20 20 FCF20
TCF20RN TCF20 CCPB-(Poles)-15CF 15 0.5 1.5 3 5 7.5
CCPB-3-20CF 3
CCPB-(Poles)-20CF 20 0.75 2 3 7.5 10
CCPB-1-30CF 1
CCPB-(Poles)-30CF 30 1.5 3 5 15 10
TCF25RN, TCF25, FCF25RN,
CCPB-2-30CF 2 1-30 30
TCF30RN TCF30 FCF30RN CCPB-(Poles)-40CF 40 2 3 7.5 20 10
CCPB-3-30CF 3
CCPB-(Poles)-50CF 50 3 5 7.5 20 10
CCPB-1-40CF 1
CCPB-(Poles)-60CF 60 3 7.5 7.5 20 10
TCF35RN, TCF35, FCF35RN,
CCPB-2-40CF 2 1-40 40 CCPB-(Poles)-70CF 70 3 7.5 15 30 40
TCF40RN TCF40 FCF40RN
CCPB-3-40CF 3 CCPB-(Poles)-90CF 90 5 10 20 50 40
CCPB-1-50CF 1 CCPB-(Poles)-100CF 100 5 10 20 50 40
TCF45RN, TCF45, FCF45RN,
CCPB-2-50CF 2 1-50 50 * Split-phase
TCF50RN TCF50 FCF50RN
** Three-phase
CCPB-3-50CF 3 Available for a bus rating of 225A or higher.
CCPB-1-60CF 1
Table 3. CCPB maximum amp ratings and CUBEFuse rejection
CCPB-2-60CF 2 1-60 60 TCF60RN TCF60 FCF60RN
CCPB branch Maximum Accepts CUBEFuse
CCPB-3-60CF 3
disconnect circuit amps amp ratings*
CCPB-1-70CF 1
CCPB-_-15CF 15 1 to 15A
CCPB-2-70CF 2 1-70 70 TCF70RN TCF70 FCF70RN
CCPB-_-20CF 20 1 to 20A
CCPB-3-70CF 3
CCPB-_-30CF 30 1 to 30A
CCPB-1-90CF 1
CCPB-_-40CF 40 1 to 40A
TCF80RN TCF80 FCF80RN
CCPB-2-90CF 2 1-90 90 CCPB-_-50CF 50 1 to 50A
TCF90RN TCF90 FCF90RN
CCPB-3-90CF 3 CCPB-_-60CF 60 1 to 60A
CCPB-1-100CF 1 CCPB-_-70CF 70 1 to 70A
CCPB-2-100CF 2 1-100 100 TCF100RN TCF100 FCF100RN CCPB-_-90CF 90 1 to 90A
CCPB-3-100CF 3 CCPB-_-100CF 100 1 to 100A
* CCPB disconnect can accept CUBEFuses with amp ratings less than or equal to the amp * Always install an indicating time-delay CUBEFuse with date code R38 or later.
rating of the CCPB disconnect.
** Correct fit with CCPB disconnect requires indicating time-delay CUBEFuses with date code
R38 or later.
Available for a bus rating of 225A or higher.

4 www.bussmann.com
Quik-Spec Coordination Panelboard (QSCP) Application Note 3148
application note Effective September 2015

Selective coordination made easy A circuit with selectively coordinated overcurrent protective devices
allows only the nearest upstream overcurrent protective device
QSCP and upstream fuses to open under any overcurrent condition. Selective coordination
The QSCP provides the fusible solution for branch panelboard increases the reliability of a system to deliver power to the loads.
applications making it simple and cost effective to selectively Selective coordination is mandatory per the NEC for the circuit
coordinate the branch circuits with upstream Bussmann fuses paths of some vital loads on specific systems including:
or upstream Eaton circuit breakers. This innovative branch circuit
panelboard uses CUBEFuse fuses (1 to 100A) for the branch circuit Emergency systems: 700.28
protective devices. The main fusible disconnect options are Class Legally required standby systems: 701.27
J Low-Peak 200A or 400A LPJ-_SP fuses or, the 30A, 60A or 100A
Compact Circuit Protector (CCP) that also utilizes the CUBEFuse.
Critical operations power systems: 708.54
The time-delay CUBEFuse and Low-Peak LPJ-_SP fuses are easy to Critical operations data systems: 645.27
selectively coordinate with each other. CUBEfuses were tested to Elevator circuits: 620.62*
selectively coordinate with Eaton circuit breakers used in upstream
power distribution panelboards and switchboards. Simply use the For other systems, selective coordination is a desirable design
published Bussmann fuse ratio and Bussmann fuse-to-Eaton circuit consideration. It is in the best interest of the building owner or
breaker tables to determine selective coordination. For the purpose tenants to have selectively coordinated overcurrent protective
of selectively coordinating a system, there is no need to plot time- devices to avoid unnecessary blackouts.
current curves or perform a short-circuit current analysis. See page
10 to details. * For elevator fusible disconnects use Bussmann Quik-Spec Power Module
elevator disconnect switches (PS) and panelboards (PMP). See data sheets 1145
and 1146.

Figure 1. Selectively coordinated fusible system utilizing Low-Peak and time-delay CUBEFuse fuses

Fuse selective coordination is as simple as maintaining the amp rating ratios of 2:1 (or greater) between all time-delay CUBEFuse and
Low-Peak fuses in a circuit. For other fuse types or Eaton circuit breakers, see published selective coordination tables.
* Automatic Transfer Switch (ATS) can achieve high withstand close-on rating with Low-Peak Class J fuses upstream. See Automatic Transfer Switch Protection section
in the Bussmann publication Selecting Protective Devices (SPD) handbook, publication no. 3002, for details

www.bussmann.com 5
Application Note 3148 Quik-Spec Coordination Panelboard (QSCP)
Effective September 2015 application note

Comparing fusible branch circuit panelboards


The Bussmann QSCP provides benefits over existing fusible branch Safety features include the finger-safe CUBEFuse that does not
circuit panels including up to a 600Vac rating, high SCCRs up to require removing any trim components for servicing along with
200kA, high interrupting rated fuses along with a broader range a unique switch interlock on the CCPB that helps prevent fuse
of branch circuit switch amp ratings that have a unique ampacity removal while the circuit is energized. Table 4 illustrates several
rejection feature that helps prevent overfusing. design and safety feature comparisons versus traditional fusible
branch circuit panelboards.

Table 4. QSCP compared to traditional fusible branch circuit panelboards (MLO*)

Typical Class CC fuse


holder/circuit breaker
branch circuit arrangement

Quik-Spec Coordination Mersen (SCP) GE (ADS) Class H or


Panel configuration Panelboard Littelfuse (LCP) Square D (QMB) plug fuse
SCCR 50kA (std.) 200kA (high) 100kA 200kA 10kA
Voltage 600V 600V 480V 600V 250V
Type MLO MLO MLO MLO MLO
Branch fuse type CUBEFuse CUBEFuse Class CC or J** Class H, J, K, R & T Class H or plug
fuse
Size 20 W x 5 D 20 W x 5 D 28 W x 6 D 36-44 W x 10.4 D 20 W x 6 D
Cost $$ $$$ $$$$ $$$$ $
Design features
Up to 100A Up to 30A Up to 30A
Branch-circuit amp ratings Up to 1200A
(1-, 2- and 3-pole) (1-pole2) (1-pole2)
Class H - no (plug
Non-rejection fuse
15, 20, 30, 40, 50, 60, 70, 90, and Rejection by fuse fuse rejection
Branch amp rating rejection feature holders(1 to 30
100A(rejection breaks) case size only requires adapters)
amps) rejection
277/480V, 250Vac and less
Panel voltage rating Up to 600Vac3 Up to 600Vac
20/240V**120/208V systems
UL 98 CCPB (innovative UL 98 fused General use snap
Branch circuit disconnect Circuit breaker
disconnect) disconnect switch
Safety features
Branch disconnect with integrated lockout Yes No Yes, but defeatable No
means
Interlock to prevent branch fuse removal Yes No No No
while energized
Lockable main disconnect(main Yes (optional) No Yes (optional) Yes (optional)
configuration)

* Also available with fused and non-fused main disconnects up to 400A.


** Class J and 120/240V specifications Mersen only.
1. Typical panelboard voltage ratings are 208Y/120 3-P, 4W, 120/240 1-P, 3W, and 480Y/277 3-P, 4W.
2. Multi-pole configurations may be available by special order.
3. Suitable for use on most systems up to 600Vac.

6 www.bussmann.com
Quik-Spec Coordination Panelboard (QSCP) Application Note 3148
application note Effective September 2015

QSCP Short-Circuit Current Ratings (SCCR) Table 5. Panelboard short-circuit current ratings
For panelboard installations, the National Electrical Code 110.10

AC main options DC
requires that the short-circuit current rating (SCCR) of the panelboard
110-200A 225-400A
be equal to or exceed the available short-circuit current at the point
main disc. main disc. 30, 60 or
of installation.
Main no fuses* no fuses* 100A Main
The QSCP is offered in a standard SCCR option or a high SCCR Lug Only or w/ or w/ CCP-_-_CF Lug Only
option for each of the three main configurations. Refer to Table 5 SCCR (MLO)* Class J fuses Class J fuses main disc.** (MLO)*
and the clarifying figures that follow for examples. The SCCR is High 200kA 200kA 100kA 200kA 100kA
marked on the panelboard, as well as provided in the data sheet. Std. 50kA 50kA 50kA 50kA 20kA
Fuses in the QSCP will selectively coordinate with upstream * For panelboards with sub-feed main lugs, or panelboards with optional feed-through lugs,
Bussmann fuses if upstream fuse type and amp rating meet Class J, T, or R fuses are required upstream - max amps = panel amps.
or exceed the published Selectivity Ratios. The QSCP will also ** CUBEFuse disconnect.
selectively coordinate with specific Eaton upstream circuit breakers
(see pages 13-18).

Figure 2. QSCP short-circuit current ratings with upstream fuses (600Vac or less system)
Example 1 Example 2

Distribution panelboard Distribution panelboard


To ensure selective
coordination, these fuses
must be Bussmann fuses
LPJ-200SP and adhere to the LPJ-200SP
200A Class J 200A Class J
published selectivity ratios

Suitable for up to 200kA Suitable for up to 50kA


available fault current available fault current

TCF15RN
X TCF60RN TCF15RN
X TCF60RN
200kA SCCR 50kA SCCR
TCF20RN TCF50RN TCF20RN TCF50RN

TCF30RN TCF40RN TCF30RN TCF40RN

200A QSCP MLO 200A QSCP MLO


High SCCR Option Standard SCCR Option

www.bussmann.com 7
Application Note 3148 Quik-Spec Coordination Panelboard (QSCP)
Effective September 2015 application note

Figure 3. QSCP short-circuit current ratings with upstream fuses (600Vac or less system)
Example 3 Example 4

Distribution panelboard Distribution panelboard


To ensure selective
coordination with fuses
upstream from this level,
LPJ-200SP select Bussmann fuses LPJ-200SP
200A Class J 200A Class J
and adhere to the
published selectivity ratios

Suitable for up to 200kA Suitable for up to 50kA


available fault current available fault current

X 200kA SCCR
X 50kA SCCR

LPJ-200SP LPJ-200SP

TCF15RN TCF60RN TCF15RN TCF60RN

TCF20RN TCF50RN TCF20RN TCF50RN

TCF30RN TCF40RN TCF30RN TCF40RN

200A QSCP 200A QSCP


Fused Main Disconnect Fused Main Disconnect
High SCCR Option Standard SCCR Option
Note the upstream 200A fuses do not have to selectively coordinate with the 200A panelboard main fuses because if both open, no
additional parts of the electrical system would be unnecessarily shut down. See NEC 700.28 and 701.27 exceptions.

Figure 4. QSCP short-circuit current ratings with upstream fuses (600Vac or less system)
Example 5 Example 6
Distribution panelboard These upstream Distribution panelboard

overcurrent protective
devices must be
LPJ-200SP Class J, RK1 or T fuses LPJ-200SP
200A Class J rated 200A or less 200A Class J

To ensure selective
coordination with fuses
upstream from this level,
select Bussmann fuses
and adhere to the
published selectivity ratios

Suitable for up to 200kA Suitable for up to 50kA


available fault current available fault current

X 200kA SCCR X 50kA SCCR


when protected when protected
TCF15RN TCF60RN upstream by TCF15RN TCF60RN upstream by
max. 200A max. 200A
Class J, RK1 or T Class J, RK1 or T
TCF20RN TCF50RN TCF20RN TCF50RN
fuses fuses

TCF30RN TCF40RN TCF30RN TCF40RN

200A QSCP 200A QSCP


Non-fused Main Disconnect Non-fused Main Disconnect
High SCCR Option Standard SCCR Option

8 www.bussmann.com
Quik-Spec Coordination Panelboard (QSCP) Application Note 3148
application note Effective September 2015

How to achieve selective coordination


The QSCP saves the designer time and provides an easy means The system on the right illustrates selective coordination: for the
to selectively coordinate lighting and other branch circuits with full range of overcurrents possible for this system, only the nearest
upstream Bussmann fuses or Eaton circuit breakers. upstream overcurrent protective device opens. No other upstream
Selective coordination increases the reliability of an electrical system overcurrent protective devices open and interruption of power is
to provide availability of power to vital loads. minimized to the fewest loads. Similarly, the fault could also occur
on a feeder circuit and a selectively coordinated circuit would result
For selective coordination with upstream Eaton circuit breakers, go in only the nearest upstream feeder overcurrent protective device
to page 12. opening.
The two one-line diagrams in Figure 5 below demonstrate the
concept of selective coordination.
The one-line diagram on the left illustrates a lack of selective
coordination. A fault on the loadside of one overcurrent protective
device unnecessarily opens other upstream overcurrent protective The NEC definition in Article 100:
devices. The result is unnecessary power loss to loads that should
not be affected by the fault. Coordination (Selective). Localization of an overcurrent condition
to restrict outages to the circuit or equipment affected,
accomplished by the selection and installation of overcurrent
protective devices and their ratings or settings for the full
range of available overcurrents, from overload to the maximum
available fault current, and for the full range of overcurrent
protective device opening times associated with those
overcurrents.

Figure 5. Electrical system selective coordination

Without selective coordination With selective coordination

Opens
Opens

Not affected
Fault Not affected Fault

Unnecessary power loss

www.bussmann.com 9
Application Note 3148 Quik-Spec Coordination Panelboard (QSCP)
Effective September 2015 application note

Figure 6. Selectively coordinated QSCP

Normal Alternate
source source
Switchboard

KRP-C-800SP 6 KRP-C-800SP 4

LPJ-_SP LPJ-_SP LPJ-400SP 5 * LPJ-400SP 3

N E
ATS
Distribution panelboard

LPJ-_SP LPJ-_SP LPJ-200SP 2

TCF15RN TCF60RN
1
TCF20RN TCF50RN
* Fuse 5 is not required to selectively
coordinate with fuse 6 by NEC 700.28.
However, it is a good design practice for
fuse 5 to selectively coordinate with TCF30RN TCF40RN
fuse 6 because continuity of service Quik-Spec Coordination
is greatly improved. Panelboard

Selective coordination is as simple as maintaining amp rating ratios of 2:1 or greater between time-delay CUBEFuse and Low-Peak fuses in a
circuit. For other fuse types see Selectivity Ratio Guide.

Example analysis
Designers have been selectively coordinating fused systems by The analysis should be completed for both the circuit path from the
using the Bussmann Selectivity Ratio Guide (page 11). Now, the QSCP branch TCF-_RN fuses to the service fuses on the normal
QSCP permits designers to ensure selective coordination for branch path as well as the circuit path to the alternate source feeder fuses.
circuits fed from branch circuit panelboards. In Figure 6 above is a
one-line example of how simple selective coordination analysis is The as-designed amp ratios must be equal to or greater than the
with Bussmann fuses. published ratios in the Selectivity Ratio Guide for the following
(analyzed fuses in Figure 6 have been assigned numbers 1 to 6):
Check the upstream feeder fuse at location 2 with the largest TCF60RN fuse at 1 with fuses at 2 (distribution panelboard), 3 and
branch circuit fuse at location 1: 4 (alternate source), 5 and 6 (normal source)
The as-designed amp ratio of feeder LPJ-200SP to branch TCF60RN LPJ-200SP fuse at 2 with fuses 3 and 4 (alternate source), 5 and
(largest branch) is 3.3:1 and the published selectivity ratio to ensure 6 (normal source)
coordination is 2:1. (Note the time-delay TCF60RN is the non-
indicating version of the TCF CUBEFuse.) LPJ-400SP fuse at 3 with fuse 4 (alternate source).
As long as the as-designed ratio is 2:1 or greater, then selective LPJ-400SP fuse at 5 with fuse 6 (normal source)*
coordination is achieved. Since 3.3:1 is greater than 2:1, the LPJ-
200SP fuse is selectively coordinated with the TCF60RN fuse for The published ratios in the Selectivity Ratio Guide for all the fuse
any overcurrent up to 200kA. combinations above are 2:1. In all cases, the as-designed ratios,
in the above example are 2:1 or greater. Therefore, fuse selective
The other TCF-_RN fuses in the panelboard have an amp rating coordination is ensured for the circuit paths from the fuses in the
lower than 60A, so they, too, will selectively coordinate with the QSCP to the normal source, as well as to the alternate source.
LPJ-200SP fuse.

10 www.bussmann.com
Quik-Spec Coordination Panelboard (QSCP) Application Note 3148
application note Effective September 2015

Selective coordination using fuses


Adhering to published fuse selectivity ratios makes it easy to design There is no need to plot time-current curves or do a short-circuit
and install a selectively coordinated fusible system. In the Selectivity current analysis to determine selective coordination (if the available
Ratio Guide below, the top horizontal axis shows loadside fuses and short-circuit current is less than 200kA or the interrupting rating of
the left vertical axis shows lineside fuses covering selectivity ratios the fuses, whichever is less).
for all levels of overcurrents up to the fuse interrupting ratings or To assure selective coordination, just make sure the fuses and amp
200kA, whichever is lower. rating ratios for the mains, feeders and branch circuits meet or
These ratios are valid for all overcurrents and opening times. The exceed the applicable selectivity ratios in Table 6.
designer just needs to specify the proper amp rating. If the ratios are not satisfied, then the designer should investigate
another fuse type or design change.

Table 6. Selectivity ratio guide (upstream/lineside to downstream/loadside)1


Circuit Downstream / loadside fuse
Amp rating 601- 601- 601-
1-100A 0-600A 0-600A 0-1200A 0-600A 0-60A 0-30A
range 6000A 4000A 6000A
Fuse Time- Time- Fast- Fast- Fast- Fast- Time-
Time-delay Dual-element, time-delay
type delay delay acting acting acting acting delay
Trade name Low-Peak Limitron CUBEFuse Low-Peak Low-Peak Fusetron Limitron Limitron Limitron Limitron SC
(CC)
(fuse class) (L) (L) (CF2) (J) (RK1) (RK5) (L) (RK1) (T) (J) (G)
Bussmann LP-CC
LPN-RK_SP FRN-R KTN-R JJN
fuse KRP-C_SP KLU TCF LPJ-SP KTU JKS SC FNQ-R
LPS-RK_SP FRS-R KTS-R JJS
symbol KTK-R
Time- Low-Peak
601 to 6000A KRP-C_SP 2:1 2.5:1 2:1 2:1 2:1 2:1
delay (L)
Time- Limitron
601 to 4000A KLU 2:1 2:1 2:1 2:1 2:1 4:1 2:1 2:1 2:1 2:1 2:1 2:1
delay (L)
Dual- Low-Peak LPN-RK_SP
0 to 600A 2:1 2:1 2:1 8:1 3:1 3:1 3:1 4:1 2:1
element (RK1) LPS-RK_SP
Dual- Low-Peak
0 to 600A LPJ-SP 2:1 2:1 2:1 8:1 3:1 3:1 3:1 4:1 2:1
element (J)
Upstream / lineside fuse

Dual- CUBEFuse
0 to 100A TCF 2:1 2:1 2:1 8:1 3:1 3:1 3:1 4:1 2:1
element (CF2)
Dual- Fusetron FRN-R
0 to 600A 1.5:1 1.5:1 1.5:1 2:1 1.5:1 1.5:1 1.5:1 1.5:1 2:1
element (RK5) FRS-R
Fast- Limitron
601 to 6000A KTU 2:1 2.5:1 3:1 3:1 3:1 6:1 2:1 2:1 2:1 2:1 2:1 2:1
acting (L)
Fast- Limitron KTN-R
0 to 600A 3:1 3:1 3:1 8:1 3:1 3:1 3:1 4:1
acting (RK1) KTS-R
Fast- Limitron JJN
0 to 1200A 3:1 3:1 3:1 8:1 3:1 3:1 3:1 4:1
acting (T) JJS
Fast- Limitron
0 to 600A JKS 3:1 3:1 3:1 8:1 3:1 3:1 3:1 4:1
acting (J)
Time- SC
0 to 60A SC 3:1 3:1 3:1 4:1 2:1 2:1 2:1 2:1
delay (G)

General notes: Ratios given in this table apply to only Bussmann fuses. When fuses are within the same case size, consult Bussmann.
1. Where applicable, ratios are valid for indicating and non-indicating versions of the same fuse. At some values of fault current, specified ratios may be lowered to
permit closer fuse sizing. Consult Bussmann.
2. Time-delay Class CF TCF or TCF_RN CUBEFuses are 1 to 100A Class J performance; dimensions and construction are a unique, finger-safe design.

www.bussmann.com 11
Application Note 3148 Quik-Spec Coordination Panelboard (QSCP)
Effective September 2015 application note

Selective coordination using upstream Eaton circuit breakers Notes on the QSCP
The tables on pages 13 to 18 show the upstream/lineside Eaton The QSCP is a highly configurable fusible panelboard that can be
thermal magnetic circuit breakers that have been tested to installed on systems up to 600Vac, three-phase.
selectively coordinate with downstream/loadside time-delay or fast- As covered earlier in this guide and summarized in the table below
acting CUBEFuses up through the interrupting rating of the lineside the QSCP can be ordered with high 200kA or standard 50kA
circuit breaker. assembly SCCRs:
Coordination tables are presented for 240Vac, 480Vac and 600Vac Panel ratings of 30, 60, 100, 200 and 400 amps
systems covering the tested breaker frame, family and the minimum
and maximum amp ratings. The available Eaton Pow-R-Line panels Three main options
for which those circuit breakers can be applied are also presented. MLO
Test results are also summarized in quick-pick tables that Non-fused switch
are limited to system voltage, circuit breaker frame, family and
maximum and minimum amp rating. Fused switch

Using the coordination tables 1-, 2- or 3-pole branch circuit disconnects


NOTE: For purposes of this guide, only the MLO, non-fused main
To use the MCCB/CUBEFuse Selective Coordination Combination
switch and 30, 60 and 100 amp main switch options are covered by
tables, available fault current to which selective coordination
the upstream circuit breaker coordination tables.
must be achieved and system voltage must be known. With this
information, perform the following: The 30, 60 and 100 amp main fused switch options use the
Bussmann Compact Circuit Protector (CCP).
Use the system voltage to determine the applicable table
The branch circuit disconnect switches are the Bussmann Compact
Locate the desired downstream CUBEFuse ampacity in the lower
Circuit Protector Base (CCPB).
left hand column and read across the row for those values greater
than the available fault current. Both the CCP and CCPB are ampacity rejecting and will hold
any time-delay or fast-acting CUBEFuse up to their amp rating.
Each column where the value exceeds the available fault current
CUBEFuses with an amp rating greater than the switch cannot be
presents a possible upstream circuit breaker solution that will
installed.
selectively coordinate to the maximum available fault current
available. When determining which 30, 60 or 100A fused main switch to
select, size the switch to the lowest rating possible with the
From the top section of the table, where the table kA exceeds the
desired CUBEFuse ampacity. E.g., in a 240V system, if you want to
available fault current, locate the desired upstream Eaton circuit
selectively coordinate the GHB 100, the largets CUBEFuse that can
breaker frame and family with a minimum amp setting less than
be applied is 50 amps. This 50 amp CUBEFuse must be installed in
or equal to that which will protect the feeder circuit conductor
a CCP greater than 30A. This would be the 60 or 100A CCP.
The circuit breaker and the fuse will selectively coordinate for all
When working with MLO or non-fused main disconnect switch
values of overloads and short-circuits up to the values shown (kA).
versions of the QSCP, this same consideration for ampacity rejection
Using the quick-pick tables is applied to the CCPB branch disconnect switches.

Thequick-pick tables (tables 7, 8 and 9) present the same


information as the coordination tables, only they omit the Pow-R-
Line panel and QSCP information. They simply present solutions for
the same system voltages and circuit breakers/amp ratings along
with the permissible CUBEFuse ampacity. If you want to quickly
determine if an upstream circuit breaker and the ampacity of a
downstream CUBEFuse will selectively coordinate, start with these
tables.

QSCP Panelboard Mains and Branch Disconnect Switches

Main options

Non-fused Fused main switch Fused branches


Panelboard switch Fused Branch disconnect Branch amp rating
amp ratings MLO amps switch amps Amp range / fuses switches (fuse amp range)
225-400A Bussmann series time-delay LPJ-_SP
400 400 400A switch UL Class J Fuses
110-200A Bussmann series time-delay LPJ-_SP
200 200 200A switch UL Class J Fuses 15 (15A), 20 (20A),
30 (30A), 40 (40A),
1-100A Bussmann series time-delay (TCF) or
100 Yes 100 100A CCP 1-, 2-, 3-pole CCPB 50 (50A), 60 (60A),
fast-acting (FCF) CUBEFuse UL Class CF Fuses 70 (70A), 90 (90A),
1-60A Bussmann series time-delay (TCF) or fast- 100 (100A)
60 60 60A CCP acting (FCF) CUBEFuse UL Class CF Fuses
1-30A Bussmann series time-delay (TCF) or fast-
30 30 30A CCP acting (FCF) CUBEFuse UL Class CF Fuses

12 www.bussmann.com
Quik-Spec Coordination Panelboard (QSCP) Application Note 3148
application note Effective September 2015

Table 7. 240Vac Eaton thermal magnetic circuit breaker quick pick selective coordination with CUBEFuse amp ratings*
Eaton lineside circuit breakers Loadside CUBEFuse (time-delay or fast-acting)
Max circuit
Breaker frame Breaker family Min. amp rating Max amp rating fault current (kA) TCF or FCF amp ratings**
G Frame GHB 100 100 65 15, 20, 25, 30, 35, 40, 50
E Frame EGB 125 125 25 15, 20, 25, 30, 35, 40, 50, 60
EHD 100 100 18 15, 20, 25, 30, 35, 40, 50
FD 100 100 65 15, 20, 25, 30, 35, 40, 50
F Frame
FD 150 150 65 15, 20, 25, 30, 35, 40, 50, 60, 70
FD 225 225 65 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
JD 70 70 65 15, 20, 25, 30
J Frame
JD 150 150 65 15, 20, 25, 30, 35, 40, 50, 60, 70
KD 200 400 65 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
K Frame
HKD 400 400 100 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100

* For circuit breakers with an adjustable instantaneous trip, selective coordination is based upon instantaneous trip set at maximum.
** TCF (time-delay) and FCF (fast-acting) 600Vac fuses can be used on any 600Vac or less system. The CUBEFuses have an interrupting rating of 300kA at 600Vac or less.

Table 8. 480Vac Eaton thermal magnetic circuit breaker quick pick selective coordination with CUBEFuse amp ratings*

Eaton lineside circuit breakers Loadside CUBEFuse (time-delay or fast-acting)


Max circuit
Breaker frame Breaker family Min. amp rating Max amp rating fault current (kA) TCF or FCF amp ratings**
G Frame GHB 100 100 14 15, 20, 25, 30, 35, 40, 50
E Frame EGB 125 125 18 15, 20, 25, 30, 35, 40, 50, 60
EHD 100 100 14 15, 20, 25, 30, 35, 40, 50
FD 100 100 35 15, 20, 25, 30, 35, 40, 50
F Frame
FD 150 150 35 15, 20, 25, 30, 35, 40, 50, 60, 70
FD 225 225 35 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
JD 70 70 35 15, 20, 25, 30
J Frame
JD 150 150 35 15, 20, 25, 30, 35, 40, 50, 60, 70
KD 200 400 35 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
K Frame
HKD 400 400 65 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100

* For circuit breakers with an adjustable instantaneous trip, selective coordination is based upon instantaneous trip set at maximum.
** TCF (time-delay) and FCF (fast-acting) 600Vac fuses can be used on any 600Vac or less system. The CUBEFuses have an interrupting rating of 300kA at 600Vac or less.
480/277Vac

Table 9. 600Vac Eaton thermal magnetic circuit breaker quick pick selective coordination with CUBEFuse amp ratings*

Eaton lineside circuit breakers Loadside CUBEFuse (time-delay or fast-acting)


Max circuit
Breaker frame Breaker family Min. amp rating Max amp rating fault current (kA) TCF or FCF amp ratings**
FD 100 100 18 15, 20, 25, 30, 35, 40, 50
F Frame FD 150 150 18 15, 20, 25, 30, 35, 40, 50, 60, 70
FD 225 225 18 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
JD 70 70 18 15, 20, 25, 30
J Frame
JD 150 150 18 15, 20, 25, 30, 35, 40, 50, 60, 70
KD 200 400 25 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
K Frame
HKD 400 400 35 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
LD 300 600 25 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100
L Frame
HLD 300 600 35 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 90, 100

* For circuit breakers with an adjustable instantaneous trip, selective coordination is based upon instantaneous trip set at maximum.
** TCF (time-delay) and FCF (fast-acting) 600Vac fuses can be used on any 600Vac or less system. The CUBEFuses have an interrupting rating of 300kA at 600Vac or less.

www.bussmann.com 13
Application Note 3148 Quik-Spec Coordination Panelboard (QSCP)
Effective September 2015 application note

Table 10. MCCB/CUBEFuse Selective Coordination Combinations* all values in kAIR rms at 240Vac

Breaker Frame G Frame E Frame F Frame


Circuit Breaker Family GHB EGB EHD FD FD FD
Upstream Breaker Trip Unit Type T/M T/M T/M T/M T/M T/M
Minimum Amp Rating 100A 125A 100A 100A 150A 225A
Maximum Amp Rating 100A 125A 100A 100A 150A 225A
Pow-R-Line: Main 2a 3E 1a, 2a, 3a 1a, 2a, 3a 1a, 2a, 3a 1a, 2a, 3a
3a, 4, 3a, 4, 3a, 4, 3a, 4,
Downstream Fuse Pow-R-Line: Branch 2a, 3a, 4 3E Swbd Swbd Swbd Swbd
Pow-R-Line: Sub-Feed 1a, 2a 1a, 2a 1a, 2a 1a, 2a
CUBEFuse (TCF/FCF)**
Lineside circuit breakers selectively coordinate with
Fusible Panel downstream CUBEFuses up to the
Fuse amps circuit breaker interrupting ratings listed below
Main Branch Sub-Feed****
15 QSCP 65 25 18 65 65 65
20 QSCP QSCP 65 25 18 65 65 65
with 30A
25 switch*** QSCP 65 25 18 65 65 65
30 QSCP 65 25 18 65 65 65
35 QSCP 65 25 18 65 65 65
40 QSCP QSCP 65 25 18 65 65 65
with 60A
50 switch*** QSCP 65 25 18 65 65 65
60 QSCP 25 65 65
70 QSCP 65 65
80 QSCP QSCP 65
with 100A
90 switch*** QSCP 65
100 QSCP 65

Table 11. MCCB Selective Coordination Combinations* all values in kAIR rms at 240Vac

Breaker Frame J Frame K Frame


Circuit Breaker Family JD JD KD KD HKD
Upstream Breaker Trip Unit Type T/M T/M T/M T/M T/M
Minimum Amp Rating 70A 150A 200A 400A 400A
Maximum Amp Rating 70A 150A 200A 400A 400A
1a, 2a, 1a, 2a,
Pow-R-Line: Main 3a, 3E, 4, 3a, 3E, 4,
Swbd Swbd
Downstream Fuse
Pow-R-Line: Branch 4, Swbd 4, Swbd 4, Swbd 4, Swbd 4, Swbd
Pow-R-Line: Sub-Feed
CUBEFuse (TCF/FCF)**
Lineside circuit breakers selectively coordinate with
Fusible Panelboard downstream CUBEFuses up to the
Fuse amps circuit breaker interrupting ratings listed below
Main Branch Sub-Feed****
15 QSCP 65 65 65 65 100
20 QSCP QSCP 65 65 65 65 100
with 30A
25 switch*** QSCP 65 65 65 65 100
30 QSCP 65 65 65 65 100
35 QSCP 65 65 65 100
40 QSCP QSCP 65 65 65 100
with 60A
50 switch*** QSCP 65 65 65 100
60 QSCP 65 65 65 100
70 QSCP 65 65 65 100
80 QSCP QSCP 65 65 100
with 100A
90 switch*** QSCP 65 65 100
100 QSCP 65 65 100

* For circuit breakers with an adjustable instantaneous trip, selective coordination is based upon instantaneous trip set at maximum.

** TCF (time-delay) and FCF (fast-acting) 600Vac fuses can be used on any 600Vac or less system. The CUBEFuses have an interrupting rating of 300kA at 600Vac or less.
*** The mains consist of main CCP switch and fuses. A CCP switch of a specific amp rating can accept any CUBEFuse of that same amp rating or less.
**** Sub-feed switch with LPJ-(amp)SP fuses are an option for the QSCP panels. However, at time of publication selective coordination testing results are not available for LPJ fuses to upstream
Eaton circuit breakers.
14 www.bussmann.com
Quik-Spec Coordination Panelboard (QSCP) Application Note 3148
application note Effective September 2015

Table 12. MCCB/CUBEFuse Selective Coordination Combinations* all values in kAIR rms at 480Vac

Frame Family G Frame E Frame F Frame


Circuit Breaker Family GHB EGB EHD FD FD FD
Upstream Breaker Trip Unit Type T/M T/M T/M T/M T/M T/M
Minimum Amp Rating 100A 125A 100A 100A 150A 225A
Maximum Amp Rating 100A 125A 100A 100A 150A 225A
Pow-R-Line: Main 2a 3E 2a, 3a 2a, 3a 2a, 3a 2a, 3a
2a, 3a, 3a, 4, 3a, 4, 3a, 4, 3a, 4,
Downstream Fuse Pow-R-Line: Branch 4 3E Swbd Swbd Swbd Swbd
Pow-R-Line: Sub-Feed 2a 2a 2a 2a
CUBEFuse (TCF/FCF)**
Lineside circuit breakers selectively coordinate with
Fusible Panelboard downstream CUBEFuses up to the
Fuse amps circuit breaker interrupting ratings listed below
Main Branch Sub-Feed****
15 QSCP 14 18 14 35 35 35
20 QSCP QSCP 14 18 14 35 35 35
with 30A
25 switch*** QSCP 14 18 14 35 35 35
30 QSCP 14 18 14 35 35 35
35 QSCP 14 18 14 35 35 35
40 QSCP QSCP 14 18 14 35 35 35
with 60A
50 switch*** QSCP 14 18 14 35 35 35
60 QSCP 18 35 35
70 QSCP 35 35
80 QSCP QSCP 35
with 100A
90 switch*** QSCP 35
100 QSCP 35
Table 13. MCCB Selective Coordination Combinations* all values in kAIR rms at 480Vac

Frame Family J Frame K Frame


Circuit Breaker Family JD JD KD KD HKD
Upstream Breaker Trip Unit Type T/M T/M T/M T/M T/M
Minimum Amp Rating 70A 150A 200A 400A 400A
Maximum Amp Rating 70A 150A 200A 400A 400A
2a, 3a, 3E, 2a, 3a, 3E,
Pow-R-Line: Main
4, Swbd 4, Swbd
Downstream Fuse Pow-R-Line: Branch 4, Swbd 4, Swbd 4, Swbd 4, Swbd 4, Swbd
Pow-R-Line: Sub-Feed
CUBEFuse (TCF/FCF)**
Lineside circuit breakers selectively coordinate with
Fusible Panelboard downstream CUBEFuses up to the
Fuse amps circuit breaker interrupting ratings listed below
Main Branch Sub-Feed****
15 QSCP 35 35 35 35 65
20 QSCP QSCP 35 35 35 35 65
with 30A
25 switch*** QSCP 35 35 35 35 65
30 QSCP 35 35 35 35 65
35 QSCP 35 35 35 65
40 QSCP QSCP 35 35 35 65
with 60A
50 switch*** QSCP 35 35 35 65
60 QSCP 35 35 35 65
70 QSCP 35 35 35 65
80 QSCP QSCP 35 35 65
with 100A
90 switch*** QSCP 35 35 65
100 QSCP 35 35 65

* For circuit breakers with an adjustable instantaneous trip, selective coordination is based upon instantaneous trip set at maximum.

** TCF (time-delay) and FCF (fast-acting) 600Vac fuses can be used on any 600Vac or less system. The CUBEFuses have an interrupting rating of 300kA at 600Vac or less.
*** The mains consist of main CCP switch and fuses. A CCP switch of a specific amp rating can accept any CUBEFuse of that same amp rating or less.
**** Sub-feed switch with LPJ-(amp)SP fuses are an option for the QSCP panels. However, at time of publication selective coordination testing results are not available for LPJ fuses to upstream
Eaton circuit breakers.
480/277Vac
www.bussmann.com 15
Application Note 3148 Quik-Spec Coordination Panelboard (QSCP)
Effective September 2015 application note

Table 14. MCCB/CUBEFuse Selective Coordination Combinations* all values in kAIR rms at 600Vac

Frame Family F Frame


Circuit Breaker Family FD FD FD
Upstream Breaker Trip Unit Type T/M T/M T/M
Minimum Amp Rating 100A 150A 225A
Maximum Amp Rating 100A 150A 225A
Pow-R-Line: Main 3a 3a 3a
Downstream Fuse Pow-R-Line: Branch 3a, 4, Swbd 3a, 4, Swbd 3a, 4, Swbd
Pow-R-Line: Sub-Feed
CUBEFuse (TCF/FCF)**
Lineside circuit breakers selectively coordinate with
Fusible Panelboard downstream CUBEFuses up to the
Fuse amps circuit breaker interrupting ratings listed below
Main Branch Sub-Feed****
15 QSCP 18 18 18
20 QSCP QSCP 18 18 18
with 30A
25 switch*** QSCP 18 18 18
30 QSCP 18 18 18
35 QSCP 18 18 18
40 QSCP QSCP 18 18 18
with 60A
50 switch*** QSCP 18 18 18
60 QSCP 18 18
70 QSCP 18 18
80 QSCP QSCP 18
with 100A
90 switch*** QSCP 18
100 QSCP 18

Table 15. MCCB Selective Coordination Combinations* all values in kAIR rms at 600Vac

Frame Family J Frame K Frame


Circuit Breaker Family JD JD KD KD HKD
Upstream Breaker Trip Unit Type T/M T/M T/M T/M T/M
Minimum Amp Rating 70A 150A 200A 400A 400A
Maximum Amp Rating 70A 150A 200A 400A 400A
Pow-R-Line: Main 3a, 3E, 4, 3a, 3E, 4,
Swbd Swbd
Downstream Fuse Pow-R-Line: Branch 4, Swbd 4, Swbd 4, Swbd 4, Swbd 4, Swbd
Pow-R-Line: Sub-Feed
CUBEFuse (TCF/FCF)**
Lineside circuit breakers selectively coordinate with
Fusible Panelboard downstream CUBEFuses up to the
Fuse amps circuit breaker interrupting ratings listed below
Main Branch Sub-Feed****
15 QSCP 18 18 25 25 35
20 QSCP QSCP 18 18 25 25 35
with 30A
25 switch*** QSCP 18 18 25 25 35
30 QSCP 18 18 25 25 35
35 QSCP 18 25 25 35
40 QSCP QSCP 18 25 25 35
with 60A
50 switch*** QSCP 18 25 25 35
60 QSCP 18 25 25 35
70 QSCP 18 25 25 35
80 QSCP QSCP 25 25 35
with 100A
90 switch*** QSCP 25 25 35
100 QSCP 25 25 35
* For circuit breakers with an adjustable instantaneous trip, selective coordination is based upon instantaneous trip set at maximum.

** TCF (time-delay) and FCF (fast-acting) 600Vac fuses can be used on any 600Vac or less system. The CUBEFuses have an interrupting rating of 300kA at 600Vac or less.
*** The mains consist of main CCP switch and fuses. A CCP switch of a specific amp rating can accept any CUBEFuse of that same amp rating or less.
**** Sub-feed switch with LPJ-(amp)SP fuses are an option for the QSCP panels. However, at time of publication selective coordination testing results are not available for LPJ fuses to upstream
Eaton circuit breakers.

16 www.bussmann.com
Quik-Spec Coordination Panelboard (QSCP) Application Note 3148
application note Effective September 2015

Application and fuse sizing guidelines Individual lighting ballast protection recommendation
CUBEFuse sizing guide Bussmann provides in-line fuses/holders for the specific purpose
of isolating individual luminaires when an internal fault occurs.
The time-delay CUBEFuses permit closer fuse sizing than non-time See example in Figure 8. If a ballast fails, the low amp rated
delay fuses for loads with inrush currents such as transformers or in-line fuse quickly opens without opening the branch circuit
across the line AC motors. The CUBEFuse has excellent current- overcurrent protective device or the service ground fault protection,
limiting characteristics (UL Class J) which results in superior short- and therefore isolates just the one faulted luminaire. The other
circuit protection for circuit components and outstanding arc flash luminaires on the lighting branch circuit remain in operation. The
hazard mitigation when the arcing current is within the current- GLR/HLR or GLQ/HLQ fuse/holder combination are typically used
limiting range of the fuse. In addition, these fuses are rated 600Vac for this application. See data sheet nos. 2032 and 2033. Fuse amp
and have a 300kA interrupting rating. rating should be per luminaire manufacturers recommendation.
Branch circuits, lighting and appliance loads (no motors) Figure 8. Fusing individual luminaires
For lighting branch circuits, a common application for QSCP branch
circuits, the CUBEFuse and conductors are sized at the rated circuit Distribution panelboard
ampacity. The branch circuit conductor (per NEC 210.19(A)(1)) and Luminaires
fuse (per NEC 210.20(A)) must be sized for the non-continuous load
plus 125% of the continuous load. Most lighting branch circuits are LPJ-200SP
continuous loads, so a branch circuit with a 16A lighting load (16A x 200A Class J

125% = 20A) would require a 20A branch circuit rating with 12 AWG
Faulted ballast
75C copper conductor and 20A CUBEFuse. (This is before any X

NEC adjustment or correction factors that may apply.) See example Supplementary
in Figure 7. protection
(GLR-3 fuses)
Figure 7. CCPB disconnect/CUBEFuse sized for lighting TCF20RN TCF20RN
branch circuit
TCF20RN TCF20RN
Distribution panelboard
Luminaires TCF20RN TCF20RN
This fuse opens and isolates one individual luminaire

LPJ-200SP
200A Class J 200A QSCP MLO

Ballasts

TCF20RN TCF20RN 16A continuous load

TCF20RN TCF20RN

TCF20RN TCF20RN
12AWG 75C Cu conductor

200A QSCP MLO 20A branch circuit


TCF20RN CUBEFuse with CCPB-20 disconnect

GLR fuse and HLR in-line fuse holder.

www.bussmann.com 17
Application Note 3148 Quik-Spec Coordination Panelboard (QSCP)
Effective September 2015 application note

Branch circuits: Individual motor circuits Applying Quik-Spec Coordination Panelboards


The CUBEFuse provides excellent motor branch circuit short-circuit The panelboard Short-Circuit Current Rating (SCCR) must be greater
and ground-fault protection per NEC 430.52 for an individual than the available short-circuit current. See the section QSCP: Short-
motor on a branch circuit. Based on the motor full load amps from Circuit Current Rating (SCCR) in this publication for more details on
NEC Tables 430.248 to 430.250, there are three different sizing this subject.
alternatives to consider. See the CUBEFuse motor sizing table at the Each panelboard must be individually protected within the
end of this section. An example is in Figure 9. panelboard (fused main disconnect) or on the supply side by a set
Optimal branch circuit protection - 150% or the next larger of fuses or circuit breaker having an amp rating not greater than the
CUBEFuse amp rating if 150% does not correspond to a fuse panelboard (NEC 408.36). See Figure 10.
amp rating. This provides the greatest degree of short-circuit and
Figure 10. QSCP overcurrent protection
ground-fault protection for motor branch circuits (NEC 430.52), but
typically is not the maximum sizing allowed. If a motor has a long
Distribution panelboard Distribution panelboard
starting time, high starting current profile or is cycled frequently, it
may be necessary to use one of the next two sizing guidelines. In
some cases for the CUBEFuse Motor Sizing Table at the end of this
section, the fuse size is slightly less than 150%. This can provide LPJ-200SP LPJ-200SP
slightly better protection and in some cases, be less cost. 200A Class J 200A Class J

Maximum branch circuit protection size, general applications (code


max) - 175% or the next larger (NEC 240.6) standard fuse amp Panelboard protected Panelboard protected
rating if 175% does not correspond to a standard fuse amp rating by main fuses by upstream fuses
(NEC 430.52(C)(1) Exc. 1).
Maximum branch circuit protection size, heavy start - Where sizing
TCF15RN
at 175% is not sufficient for the starting current of the motor, size at TCF60RN

225% or the next smaller CUBEFuse amp rating if 225% does not LPJ-200SP TCF20RN TCF50RN
correspond to a CUBEFuse fuse amp rating (NEC 430.52(C)(1) Exc.
2). TCF15RN TCF60RN TCF30RN TCF40RN
For any of the alternatives above, motor running overload protection
(NEC 430.32) needs to be provided by other means such as an TCF20RN TCF50RN
overload relay. If the motor controller manufacturers overload relay 200A QSCP MLO
tables state a maximum branch circuit protective device of a lower TCF30RN TCF40RN
rating, that lower rating must be used in lieu of the sizes determined
above. Finally, the Compact Circuit Protector Base (CCPB)
200A QSCP
disconnect must have a horsepower rating equal to or greater than
Fused Main Disconnect
the motor horsepower rating.
Bussmann recommends using indicating time-delay CUBEFuses on
motor branch circuits for easy, positive viewing of fuse status.
Figure 9. CUBEFuse/CCPB disconnect sized for optimal
motor branch circuit protection

Distribution panelboard

LPJ-200SP
200A Class J

CCPB-30 disconnect with


TCF25RN CUBEFuse
TCF20RN TCF20RN
12AWG 75C Cu conductor
TCF20RN TCF25RN

Motor starter with overload


TCF20RN TCF20RN protection based on motor
nameplate FLA per
NEC 430.32

200A QSCP MLO


10Hp motor
three-phase, 460V
NEC Table 430.250
14A for determining branch circuit
protective device

18 www.bussmann.com
Quik-Spec Coordination Panelboard (QSCP) Application Note 3148
application note Effective September 2015

If the panelboard is supplied through a transformer, the fuses for 2. The overcurrent protective device on the primary of the
the protection of the panelboard must be located on the transformer transformer does not exceed the ampacity of the secondary
secondary per NEC 408.36(B). See Figure 11. An exception conductor (or amp rating of the panelboard), multiplied by the
is where a panelboard supplied by a single-phase, two-wire or secondary to primary voltage ratio. Selecting the next higher
three-phase, three-wire, delta-delta transformer is permitted to be standard size overcurrent protective device is NOT allowed.
protected by a set of fuses or a circuit breaker on the primary where
the protection complies with NEC 240.21(C)(1) which requires:
1. The transformer is protected in accordance with 450.3. The
maximum fuse permitted for 600V or less, transformer primary
only protection per NEC 450.3(B) is 125% of transformer
primary rated current or the next standard amp rating in NEC
240.6 if 125% of this current does not correspond to a standard
fuse amp rating.

Figure 11. QSCP supplied through a transformer


Distribution panelboard Distribution panelboard

LPJ-XXXSP
J- LPJ-(amp)SP
XXXA Class J Class J

Transformer
single-phase, two wire
or
three-phase, three wire
Delta-Delta

Panelboard protected
by main fuses
In this case, fuses on the
transformer primary are
TCF15RN TCF60RN considered to protect the
MLO panelboard.
However, the fuse amp
LPJ-200SP TCF20RN TCF50RN rating must adhere to NEC
requirements and the fuse
TCF15RN TCF60RN type must adhere to the
TCF30RN TCF40RN
panelboard SCCR
requirements
TCF20RN TCF50RN
200A QSCP MLO
TCF30RN TCF40RN

200A QSCP
Fused Main Disconnect

www.bussmann.com 19
Application Note 3148 Quik-Spec Coordination Panelboard (QSCP)
Effective September 2015 application note

Table 16. Sizing time-delay CUBEFuse for motors

Motor1 Time-delay CUBEFuse (A) Motor1 Time-delay CUBEFuse (A)


Motor FLA Optimal Code Heavy Motor FLA Optimal Code Heavy
Voltage size (Hp) (Amps) protection max start Voltage size (Hp) (Amps) protection max start
0.167 4.4 10 10 10 0.5 2.2 6 6 6
0.25 5.8 10 15 15 0.75 3.2 6 6 6
0.333 7.2 15 15 15 1 4.2 10 10 10
0.5 9.8 15 20 20 1.5 6 10 15 15
115Vac, 0.75 13.8 25 25 30 2 6.8 15 15 15
1-Phase 230Vac,
1 16 25 30 35 3 9.6 15 20 20
3-Phase
1.5 20 30 35 45 5 15.2 25 30 30
2 24 40 45 50 7.5 22 35 40 45
3 34 50 60 70 10 28 45 50 60
5 56 90 100 N/A 15 42 70 80 90
0.167 2.2 6 6 6 20 54 90 100 N/A
0.25 2.9 6 6 6 0.5 1.1 3 3 3
0.333 3.6 6 10 10 0.75 1.6 3 3 3
0.5 4.9 10 10 10 1 2.1 6 6 6
0.75 6.9 15 15 15 1.5 3 6 6 6
230Vac, 1 8 15 15 17.5 2 3.4 6 6 6
1-Phase 1.5 10 15 20 20 3 4.8 10 10 10
2 12 20 25 25 5 7.6 15 15 15
460Vac,
3 17 25 30 35 7.5 11 17.5 20 20
3-Phase
5 28 45 50 60 10 14 25 25 30
7.5 40 60 70 90 15 21 35 40 45
10 50 80 90 N/A 20 27 40 50 60
0.5 2.5 6 6 6 25 34 60 60 70
0.75 3.7 6 10 10 30 40 60 70 90
1 4.8 10 10 10 40 52 80 100 N/A
1.5 6.9 15 15 15 50 65 100 N/A N/A
2 7.8 15 15 17.5 0.5 0.9 3 3 3
200Vac, 0.75 1.3 3 3 3
3 11 17.5 20 20
3-Phase
5 17.5 30 35 35 1 1.7 3 3 3
7.5 25.3 40 45 50 1.5 2.4 6 6 6
10 32.2 50 60 70 2 2.7 6 6 6
15 48.3 80 90 100 3 3.9 6 10 10
20 62.1 100 N/A N/A 5 6.1 10 15 15
0.5 2.4 6 6 6 575Vac, 7.5 9 15 20 20
0.75 3.5 6 10 10 3-Phase 10 11 17.5 20 20
1 4.6 10 10 10 15 17 30 30 35
1.5 6.6 10 15 15 20 22 35 40 45
2 7.5 15 15 15 25 27 45 50 60
208Vac, 30 32 50 60 70
3 10.6 17.5 20 20
3-Phase
5 16.7 25 30 35 40 41 70 80 90
7.5 24.2 40 45 50 50 52 80 100 N/A
10 30.8 50 60 60 60 62 100 N/A N/A
15 46.2 70 90 100 Note: Use code max column for low to moderate reverse/jog/plug applications.
Heavy start permitted only if code max does not allow motor start-up.
20 59.4 90 N/A N/A
1. Based on motor FLA from NEC Tables 430.248 and 430.250.

20 www.bussmann.com
Quik-Spec Coordination Panelboard (QSCP) Application Note 3148
application note Effective September 2015

The QSCP and fast-acting CUBEFuse for protecting the Figure 12. Holdup time with fast-acting CUBEFuse
loadside of Uninterruptable Power Supplies (UPS)
Normal
Several industries, such as the petrochemical or pharmaceutical Source
industries, have a need to maintain power to critical, sensitive
loads making power system reliability an important design criteria. UPS
These loads can include alarm and protection systems, sensors 30kVA
and monitors, distributed control systems (DCS) circuits and PWM (Pulse Width Modulated)
120V 1
Alternate
programmable logic controllers (PLC). These loads typically are fed Short-Circuit Approximately Source
via an Uninterruptable Power Supply (UPS) system which presents 1.5 x FLC for Cycle
300-400A S.C.
unique design considerations with regard to overcurrent protection. Static
Transfer
These considerations include process load holdup times, UPS Switch
dropout, transfer switch operation and selective coordination.
Holdup time
Holdup times for DCS, PLC and critical instrumentation loads are LPJ-200SP Holdup Times 0 VRMS
Duration Average
typically 30ms or less. These loads are also typically low ampacity FCF6RN
circuits of 5 amps or less. See Figure 12. FCF Clearing Time
PLC 0-40ms 16ms
FCF10RN
Set. - Cycle
However, given the low fault current from the UPS and/or small (4-8ms)
DCS 17-40ms 28ms
FCF15RN
conductor size for these loads, the operation time of the overcurrent Critical 0-30ms 15ms
Instrumentation
protective device under fault conditions can exceed the holdup time QSCP Panelboard
of the critical loads.
Specifying overcurrent protective devices with fast fault clearing
time characteristics and sizing them according to manufacturers Figure 13. Selective coordination with fast-acting CUBEFuse
specifications is essential. The objective is to have the overcurrent Normal
protective device reliably clear fault conditions in times less than Source
the holdup time of the critical loads. In most cases, FCF fast-acting
CUBEFuses (blue label) can be sized small enough to ensure fault
UPS
operation times within the holdup time of the critical devices. Fast- 30kVA
acting CUBEFuses are available in the small amp ratings (1, 3, 6, 10 PWM (Pulse Width Modulated)
120V 1
Alternate
and 15 amps) that can provide this necessary protection. Short-Circuit Approximately Source
1.5 x FLC for Cycle
UPS Dropout and selective coordination 300-400A S.C.
Static
UPS dropout or damage occurs when a fault on one branch circuit Transfer
UPS Drops out Switch
powering critical loads is not cleared quickly enough so it induces Transfer switch operates
voltage drop on the UPS output. See Figure 13. If the duration is
long enough, the induced voltage dropout can result in damage to FCF Fuse is selectively
the UPS or cause some UPS systems to shut themselves down, LPJ-200SP
coordinated with 200A
upstream LPJ fuse
depending on the UPS type. When static transfer switches are FCF6RN
used, the dropout of the UPS results in higher fault currents on PLC
FCF Clearing Time FCF10RN
these critical branch circuits. If the branch circuit overcurrent Set. - Cycle DCS
protective devices do not selectively coordinate with panel feeder (4-8ms) FCF15RN
device, loss of all critical UPS loads can result. Figure 13 shows a Critical
Instrumentation
fuse panel that utilizes fuses which only require a minimum of 2:1 QSCP Panelboard
ampacity ratio to selectively coordinate.

www.bussmann.com 21
Application Note 3148 Quik-Spec Coordination Panelboard (QSCP)
Effective September 2015 application note

QSCP and Surge Protective Devices


2014 NEC 700.8 requires a listed SPD to be installed in or on all
emergency system switchboards and panelboards.
All configurations of the QSCP intended for installation on an AC
circuit can be ordered with an optional Surge Protective Device to Available with
comply with this requirement. optional remote local visual
signal Form C status
The factory installed SPDs feature local, visual easyID status
contact indication
indication and can be specified with a remote Form C contact
relay for integration into a monitoring system. The relay is rated
at 250Vac/0.5A and 250Vdc/0.1A, 125Vdc/0.2A, 75Vdc/0.5A to
accommodate many signaling needs.
Although a Type 1 SPD may be retrofitted and added externally
to meet the NEC 2014 700.8 or other surge suppression needs,
it is recommended to factory order the SPD to assure correct High SCCR DIN-Rail Type 2 component assembly SPDs are factory
specification for the system voltage and type as well as proper installed when the QSCP is ordered with a surge protective device.
installation.
If an SPD is required after the QSCP is installed (for surface mount
QSCPs only), Bussmann recommends installing the external-mount
Type 1 SurgePOD HEAVY DUTY (50kA surge current capacity
[Imax]), or the Type 1 or Type 2 BSPD (from 120kA up to 400kA surge
current capacity [Imax]) SPDs.
Installation of the externally-mounted SPD is facilitated by using a
CCPB branch disconnect to make the connections to the QSCPs
internal busways. See suggested ampacities in Table A for the SPD
family product being installed.
Care should be taken to order the correct SurgePOD HEAVY DUTY
catalog number or specify the correct BSPD (from the catalog
number system) to match the electrical system type and voltage.
Table A - Circuit breaker and fused switch sizing guide SurgePOD HEAVY DUTY is a Type 1 listed SPD with a 50kA surge
current capacity. Field installed device, does not ship with QSCP.
Suggested minimum Must be ordered separately.
SPD family CCPB ampacity
SurgePOD HEAVY DUTY (SPH) 60A
BSPD 100A

BSPD includes listed Type 1 or Type 2 SPDs (depending on the


configuration ordered) with surge current capacities from 120kA to
400kA and are configurable for Wye (120/208, 277/480, 600) and
Delta (240, 480, 600) systems. Field installed device, does not ship
with QSCP. Must be ordered separately.

22 www.bussmann.com
Quik-Spec Coordination Panelboard (QSCP) Application Note 3148
application note Effective September 2015

Reference materials
QSCP data sheet No. 1160
QSCP installation leaflet No. 3A1071
CCPB data sheet No. 1161
CCP data sheet No. 1157
Time-delay Class CF CUBEFuse data sheet No. 9000
Fast-acting Class CF CUBEFuse data sheet No. 2147
Time-delay Class J LPJ fuses, data sheet No. 1007
Fast-acting Class J JKS fuses, data sheet No. 1027
Selecting Protective Devices handbook No. 3002
Eaton molded case circuit breakers catalog No. CA08100005E
Eaton molded case circuit breakers and enclosures application data No. CA08104001E, sheet 27042
Eaton panelboards overview, No. CA08104001E, sheet 22002
North American UL Type 1, 2 and 3 Surge Protective Device application note No. 3193
SurgePOD HEAVY DUTY data sheet No. 2163
BSPD Surge Protective Devices data sheet No. 10209

www.bussmann.com 23
Application Note 3148 Quik-Spec Coordination Panelboard (QSCP)
Effective September 2015 application note

Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com

Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries

2015 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. 3148 BU-SB14696 All other trademarks are property
September 2015 of their respective owners.

Anda mungkin juga menyukai