LIFT CONTROLLER
USER MANUAL
ARKEL Elektrik Elektronik Ltd. ti. www.arkel.com.tr
CONTENTS
ARL-100
ARKEL 2011 3
ARKEL Elektrik Elektronik Ltd. ti. www.arkel.com.tr
System parameters of ARL-100 lift controllers can be modified easily by using three buttons and
two 7-segment displays located on the board. These buttons are named as follows:
When system is energized for the first time or restarted the software version of controller appears
on display for about 2 seconds.
1 6 : The software version of controller is V1.6.
Then the start up message is displayed while the controller checks the bottom limit switch signal
(817). After the bottom limit switch signal is detected, the floor text which is displayed on digital
displays will be indicated. But if there is an error in the system, the error code will be displayed.
- - : Controller checks the bottom limit switch signal (817)
Entering menu is not allowed while lift is in operation besides the car/landing calls are not accepted
while the controller is in menu mode.
E : In order to enter menu push E (Enter) button. The first menu parameter and its value
are displayed one after another.
The parameters with the numbers P0-P8 are used for system parameters in controller.
The parameters with the numbers d1-d8 are used for car and landing digital display patterns
E : In order to exit from menu push and hold E (Enter) button until the display indicates
the floor where the car stays. Also the controller leaves menu while there is no
operation in menu mode for 20 seconds.
When you exit from menu mode, then last configuration you prepared is stored into memory. The
controller uses these new parameters in operation and system is ready to function as a controller
again.
ARL-100
ARKEL 2011 4
ARKEL Elektrik Elektronik Ltd. ti. www.arkel.com.tr
2. LIST OF PARAMETERS
ARL-100
ARKEL 2011 5
ARKEL Elektrik Elektronik Ltd. ti. www.arkel.com.tr
These parameters store the digital display codes for the corresponding floors. These codes control
hall and cabin displays but not the display on ARL-100 board. Parameter d1 holds the code for the
floor 1 and parameter d8 holds the code for the floor 8.
You will search with and keys all characters, which are possible to be displayed for the
system. There is table below which shows the codes for characters.
ARL-100
ARKEL 2011 6
ARKEL Elektrik Elektronik Ltd. ti. www.arkel.com.tr
3. ERROR CODES
When an error occured, the error code with letter H in first display is indicated by flashing
displays.
Only H6 (Max. Floor to floor time is elapsed) error blocks the system.
For the other errors (excluding H1 and H3), controller waits 30 s to be removed from the system.
If the problem can not be solved at the end of this period, controller resets the error.
In order to terminate the error messages push E (Enter) button or activate the inspection switch.
H 2 -
ARL-100
ARKEL 2011 7
ARKEL Elektrik Elektronik Ltd. ti. www.arkel.com.tr
ARL-100
ARKEL 2011 8
ARKEL Elektrik Elektronik Ltd. ti. www.arkel.com.tr
5. TROUBLESHOOTING
No Inspection Movement
When inspection switch is turned on, the inspection indicator coded as 869 which is on the ARL-100 board must be
turned off. Also the inspection movement buttons must set the 500 and 501 coded indicators. The car connection should
be controlled if the indicators are not acts correctly.
Be sure that 120 (Stop), 130 (Door Closed) and 140 (Door Locked) circuits are closed when inspection UP or
inspection DOWN buttons are pressed (All signals of these circuits on the controller board have to be on).
The limit switches may stop movements. The 817 (KSR1) and 818 (KSR2) indicators can not be off at the same time.
The limit switches should be controlled if the indicators are off.
Lift Stops Before Reaching Low Speed ( For two speed systems)
If the same trouble occurs at all floors, possibly the 142 magnetic switch is failed. During traveling with low speed
142 indicator must be on. After the lift is at floor level, the 142 magnetic switch has to switch off and stop the lift.
If the trouble occurs at a specific floor, magnetic switches and the distance between magnets should be controlled.
Lift Hits Up
Top limit switch circuit 818 (KSR2) should be controlled. When the lift slows down at the top floor, 818 indicator
must be turned off. If not, the magnetic switch and the magnets should be controlled. M1 and 818 switches slow down
the car at the same position. 818 limit switch must not be late to slow down car. Because it corrects the faulty counting
of M1 switch.
The 142 magnetic switch may be failed. When the lift is at floor level, 142 indicator must be off. If not, the magnetic
switch and the magnets should be controlled.
ARL-100
ARKEL 2011 9
ARKEL Elektrik Elektronik Ltd. ti. www.arkel.com.tr
When Stop Button Is Pressed The Counter Shows The Top Floor
The common of 817 and 818 limit switches has to be 100 (+24V).
Lift Stops Operating And Starts Operating By Itself Without Any Stimulation
Motor PTC may stop lift. If motor ventilation is not enough , PTC stops lift up to desired temperature.
Power failures may cause this problem. Check for R,S,T phase line voltages.
When Calling Lift, It Stops At Each Level And Need To Call Again
If lift does this for each call, the voltages may decrease. Check 100 (24V) terminal voltage while operating. Control
the capacitors (3 x 1000uf/35V) for 24V. If line voltage increase too much or neutral signal missed the transformer
output increase also. Check for the line powers and neutral signal.
If lift does this for a specific call, that calls latch may be failed. The latch circuit should be controlled. Check
connections for this call. Car flexible cable order is important. There must be no high voltage wire near call signals.
ARL-100
ARKEL 2011 10
ARKEL Elektrik Elektronik Ltd. ti. www.arkel.com.tr
Programming buttons
198mm
220mm
20mm
20mm
115mm
ARL-100
ARKEL 2011 11
ARKEL Elektrik Elektronik Ltd. ti. www.arkel.com.tr
All persons performing installation and commissioning work on the ARL-100 Controller
must read these chapters and follow the regulations.
In a lift control system, for a full electrical conformity with EN-81 standards it is required
that controller (control boards), control panel and electrical connections must be proper.
ARKEL guaranties that controller and control panel are in conformity with the
standards. However external connections of control panel and other electrical connections
are under installers responsibility.
ARL-100
ARKEL 2011 12
ARKEL Elektrik Elektronik Ltd. ti. www.arkel.com.tr
ATTENTION!
Take care while connecting
your flexible cable
There are small points to take care while connecting your flexible cable. Arrange your cable
order according to their electrical signal level. Although the cables have enough insulation, long
parallel cables have transformer effect. The signals can joint between each neighbors. If there is
two or more flexible cables it is better to separate low an high voltage signals.
In this example ever car lamp on/off operation makes high voltage peaks on line and it can leak to
406 (car call signal). In long term this causes a fault on 406 output transistor. Also there is risk
because of Magnetic cam power lines. 818 and 804 signal may have faulty operation in long term.
ARL-100
ARKEL 2011 13
ARKEL Elektrik Elektronik Ltd. ti. www.arkel.com.tr