Table#1
Number of
Current Setting
Conductors External Setting of
Range Remark
thru CT CT Ratio CT Ratio
(Amps)
windows
OFF
0.560A 1 - Wide Range
(Mode:--)
0.253.0A 2 - 2t
0.11.2A 5 - 5t
112A 1 10:5 10
1.518A 1 15:5 15
2.024A 1 20:5 20
2.530A 1 25:5 25
3.036A 1 30:5 30
4.048A 1 40:5 40
560A 1 50:5 50
672A 1 60:5 60
7.590A 1 75:5 75
10120A 1 100:5 100
Function and Indication of Alert 12144A 1 120:5 120
15180A 1 150:5 150
20240A 1 200:5 200
25300A 1 250:5 250
30360A 1 300:5 300
40480A 1 400:5 400
50600A 1 500:5 500
60720A 1 600:5 600
75900A 1 750:5 750
80960A 1 800:5 800
Specification Time-Current Characteristics
Model EOCR-3DE
0.5~60A,Wide Range
Current
(11~960A with external CT, refer table#1)
Delay Time(D-Time) 1~200 sec(Definite time)/OFF
0.5 / 1~30 sec
Over-current delay
Setting (Definite Time, refer table#2),
Time(O-Time)
1~30 class(Inverse Time, refer table#3)
Under-current delay 0.5 / 1~30 sec
Time(U-Time) (Definite Time, refer table#2)
Alert 50~100%, OFF(Disable)
Depressing Reset button or control voltage
Reset Manual
interruption
- 0.5~10A : Definite/ Inverse selectable
Operation Over-current - More or equal than 11A :definite
Characteristic (If inverse required, use with external CT)
Under-current Definite
Current I < 1A : 0.05A, I 1A : 5%
Tolerance
Time t 3s : 0.2s, t > 3s : 5%
Ambient Storage -30~80C
Temperature Operation -20~60C
Ambient Humidity 30~85% RH without Condensation
220VAC : 15%, 50/60Hz
Control Voltage 110VAC : 15%, 50/60Hz
24VAC/DC
2-SPST 3A/250VAC(1a-1b), Resistive Table#2. <Definite time characteristics of OC>
Contacts
1-SPST 3A/250VAC(AL), Resistive
Output Contacts
Normally Energized in FS:ON,
Condition
9798 Closed.
Between Casing &
Insulation Over 10M(DC 500V Megger)
Circuits
Between Casing &
2 60Hz 1min.
Circuits
Dielectric Strength Between Contacts 1 60Hz 1min.
Between Circuits 2 60Hz 1min.
Mounting 35mm Din Rail or Panel
Power
Less than 3W
Consumption
Electrostatic Level 3: Air Discharge :
IEC61000-4-2
Discharge 8, Contact Discharge: 6
Radiated
Level 3: 10V/m,
Electromagnetic IEC61000-4-3
150MHz & 450MHz Portable transceiver
Field Disturbance
EFT / Burst IEC61000-4-4 Level 3: 2, 1min
Surge IEC61000-4-5 Level 3: 1.250, 2(0, 90, 180, 270)
1MHz Burst
IEC61000-4-12 Level 3: 2.5kV, 1MHz
disturbance
Conducted
EN55011 Class B
Emission
Trip Display
Function LED Display Description Remark Table#3. <Inverse time characteristics of OC>
L1 Amp
Tripped by over current on 0.5~10A / combined with external CT
Over current L2
L3 sec L1 phase
L1 Amp Tripped by under current on how to setup
Under current L2
L3 sec L2 phase
1) Current :
L1 Amp
Phase Loss L2 Tripped by L2 phase loss Definite Time Set the rated motor current
L3 sec
in OC mode. For protection of connected
L1 Amp machinery with motor, it is recommended to
Phase Reversal L2 Tripped by Phase reversal set the 110~115% of running current after
L3 sec Possible to
check each motor current is stabilized.
Tripped by unbalance current more phase current Inverse Time 100% of rated motor current
than setting % difference in terms of by search
L1 Amp max. phase current on or 110~125% actual motor current is
Unbalance L2 button
L3 sec L1 phase recommended.
[(Max - Min) / Max]100[%] > 2) D-Time : Set the expected run-up time of
setting % motor in dt mode.
L1 Amp 3) O-Time :
Locked Rotor L2 Tripped by Locked Rotor
L3 sec Definite Time Set the desired trip delay time
L1 Amp in ot mode.
Tripped by stall, mechanical shock,
Stall L2 Inverse Time Set the trip delay time
L3 sec on L3 phase
according to Time-Current characteristics.
Display Setting
Function Setting Range FND Display Description
0.5~10A : 0.1A steps.
10~60A : 1A steps.
Not possible to set a current value over 10A if inverse characteristics
1 Over-current 0.5A~60A is selected.
Required to set a preset protected value(<6A) at first based on CT
secondary output before setting a CT ratio if needed to adopt external
CT instead of wide range[CT:OFF(--)].
1~100sec : 1 sec steps.
2 Starting Delay Time 1~200sec / OFF(dt--)
100~200sec : 10 sec steps.
Within 0.5sec / 1~30sec
Over-current 0.5sec / 1~30sec : 1sec steps.
3 (definite time)
Trip Delay Time Operated after Starting Delay Time
1~30 class(Inverse)
Not possible to set over over-current set-value(oc).
0.5A~less than oc setting
4 Under-current 0.5, 1~10A : 0.1A steps.
value /OFF(uc--)
10A ~ : 1A steps.
Under-current 0.5sec / 1~30sec : 1sec steps.
5 Within 0.5sec / 1~30sec
Trip Delay Time Operated after Starting Delay Time
Definite
2~10 times of oc setting Tripped within 0.5 sec, After elapse of dt.
6 Locked Rotor
OFF(Lc--) The decreased proportional % of Lc is determined by follow
formular, [Max. value of Lc=100/oc setting value]
Definite
Tripped after elapse of preset time(St)
1.5~5times of oc setting
7 Stall More than 11A: Set automatically by proper decreased %.
OFF(Sc--)
The decreased proportional % of Sc is determined by follow
formular, [Max. value of Sc=100/oc setting value]
Operating Time of
8 Within 0.5sec / 1~10sec In case of Sc:OFF, St mode becomes OFF automatically
Stall
Phase current
9 5~50% / OFF(Ub--) [ ( Max curr. Min curr. ) / Max ] x 100[%] > Ub setting %
Unbalance
10 Fail Safe ON(FSon), OFF(FS--) Impossible to set during operation.
State of output
A(Ampere relay):energized whenever CT senses current
F(Flickering):A and current value flashes frequently
15 Type of alert output A / F/ H / U
H(Holding):ON-OFF
U(Undercurent Mode):the AL output(0708) is
transferred into uc output.
OFF(ct--) : wide range(0.5~60A).
5t : Displayed the current more than 0.04A.
OFF-5t,2t,
2t : Displayed the current more than 0.1A
10-15-20-25-30-40-50-60-75-
16 CT Ratio Required to set a current value under 6A based on CT secondary
100-120-150-200-250-300-400-
output if need to adopt external CT instead of wide range
500-600-750-800
[CT:OFF(--)] Refer detail in oc mode.
Not possible to adjust during the operation
Stored the trip causes, regardless power is off.
Memorized the last 3 trip
17 Trip Cause Memory The stored information is displayed from last trip causes and able to
causes
check each phase current when tripped.
Not permitted to test this
18 Test function during the operation to (3sec) (o-time)
prevent the unnecessary trip. Not possible to test during the operation.
Dimension
Ordering Information
Model name 1 2 3 Accessory
E O C R 3 D E H 1 D M 7 3CT-H1-100
1 2 3
Current range Relay Output Power supply Frequency
EOCR3DEWRDM7 Wide range WR b-a type D 220VAC M 50/60Hz 7
EOCR3DEWRDF7 110VAC F
EOCR3DEH1DM7 100:5 H1 220VAC M
EOCR3DEH1DF7 110VAC F
EOCR3DEHHDM7 150:5 HH 220VAC M
EOCR3DEHHDF7 110VAC F
EOCR3DEH2DM7 200:5 H2 220VAC M
EOCR3DEH2DF7 110VAC F
EOCR3DEH3DM7 300:5 H3 220VAC M
EOCR3DEH3DF7 110VAC F
EOCR3DEH4DM7 400:5 H4 220VAC M
EOCR3DEH4DF7 110VAC F
3CT - H1,HH,.H4
SRCT - S1,SH,.S4
Accessory
3CT Ratio SRCT Ratio
3CT-H1-100 H1 100:5 SR-3CT-100 100:5
3CT- HH-150 HH 150:5 SR-3CT-150 150:5
3CT- H2-200 3CT - H2 - 200:5 SR-3CT-200 SR - 3CT - 200:5
3CT- H3-300 H3 300:5 SR-3CT-300 300:5
3CT- H4-400 H4 400:5 SR-3CT-400 400:5