Anda di halaman 1dari 9

REFRIGERATING ENGINEER B. magnetic stop valve D.

bimetallic valve

1. A method of reducing capacity without 9. If the compressor has been running


reducing compressor speed is called: satisfactorilly for a long period of time but the
A. low-pressure bypassing oil level can rise slowly, the thing to do would
B. high- pressure bypassing be to:
C. hot-gas bypassing A. drain without sufficient oil to bring it down to
D. short-cycling the proper running level
B. shutdown the compressor and check the oil
2. The thermal expansion valve responds to the: level with the machine stopped
A. amount of superheat in the vapor leaving the C. check the dehydrator cartridge
coil D. check to see if there is too much refrigerant
B. amount of superheat in the liquid in the system
C. temperature in the evaporator coils
D. pressure in the evaporator coils 10. If the compressor had been running
satisfactorily for a long period of time but
3. The bulb for the thermal expansion valve is suddenly the compartment temperature started
located: to rise, the trouble might be:
A. in the middle of the evaporator coils A. the solenoid valve has jammed shut
B. near the evaporator coils outlet B. the expansion valve may have water frozen in
C. near the evaporator coils inlet it
D. on the bottom row of evaporator coils C. a refrigerant leak has developed
D. Any of the above
4. Thermostat is a:
A. temperature-operated switch 11. When charging a Freon system, all the
B. pressure-operated switch valves should be in their normal position except
C. superheat-operated switch in the:
D. back-pressure-operated switch A. expansion valve C. king valve (liquid)
B. purge valve D. solenoid valve
5. The elements of a thermostat switch are
usually of the: 12. Abnormal discharge temperatures would be
A. diaphragm type C. valve type caused by:
B. bimetal type D. pilot-valve type A. leaky suction valves C. faulty piston rings
B. leaky discharge valves D. any of the above
6. When heavy electrical currents are involved,
the thermostat will be operated by a: 13. A device for holding open the suction valve
A. small circuit breaker C. fusetron and drawing gas from the suction manifold and
B. pressure pipe D. relay returning it to the suction line without
compressing it is called a:
7. If the compressor runs continually, the cause A. discharge line bypass C. suction line bypass
might be the: B. cylinder unloader D. relief valve
A. high-pressure cutout switch is jammed open
B. low-pressure switch is jammed shut 14. As heat is removed from a substance it gets
C. thermal bulb is not operating properly colder. When no more heat can be removed
D. scale trap is clogged and the temperature cannot be lowered any
further, we have reached:
8. The solenoid valve can be typed as a: A. perfect zero C. absolute zero
A. thermal valve C. bellows valve B. double zero D. cold zero
15. The boiling point of water in an open 22. If the compressor-discharge temperature is
container at sea level is 212F. If the pressure in higher than the receiver temperature:
the open container is decreased, such as going A. increase the amount of cooling water to the
up to the top of a mountain, the boiling point condenser
will be: B. decrease the amount of cooling water to the
A. increased C. the same condenser
B. decreased D. none of the above C. add more refrigerant to the system
D. remove some of the refrigerant from the
16. Another name for the liquid valve is the: system
A. master valve C. Freon valve
B. king valve D. shutoff valve 23. The dehydrator is used:
A. to remove moisture from the system
17. If the temperature in the icebox is too high, B. to remove air from the system
the trouble could be: C. when adding refrigerant to the system
A. a clogged scale trap D. A and C
B. air in the system
C. automatic controls not functioning properly 24. If the discharge side of the thermal
D. insufficient cooling water to the condenser expansion valve is warmer than the inlet side,
the:
18. Oil is added to a Freon compressor by: A. expansion valve is working normally
A. pouring through oil hole in base B. expansion valve is not working normally
B. pumping in with a hand pump C. solenoid is not working normally
C. pumping in with an electric-driven pump D. scale trap is dirty
D. shutting down the machine and pouring in
through the crack-case inspection plate opening 25. The oil level in the compressor should be
checked:
19. If no gaskets are used in the piping joints of A. while the compressor is in operation
a Freon system, the joints must be is to: B. just before starting the compressor
A. finished joints C. ground joints C. after a long period of operation
B. welded joints D. soldered joints D. B and C

20. When adding oil to a Freon system one 26. The relief valve is located on the:
must be sure that: A. discharge side of condenser
A. all air is removed from the pump and fittings B. discharge side of compressor
B. there is not too high a suction pressure C. outlet of the evaporator coils
C. the discharge pressure is not too high D. receiver tank
D. the condenser is shutdown
27. The expansion valve on a Freon system
21. If the head pressure is too high: controls the:
A. the relief valve should open before the high- A. superheat of the gas leaving the compressor
pressure cutout B. back pressure in the evaporator
B. the relief valve should open and let excess C. temperature of the icebox
refrigerant go to receiver D. superheat of the gas leaving the evaporator
C. the high-pressure cutout switch should
operate before the relief valve opens 28. The scale trap is located between the:
D. close in on the suction valve A. king valve and the expansion valve
B. solenoids valve and expansion valve
C. evaporator and receiver
D. compressor and evaporator B. increased the capacity of the evaporator
C. control the refrigerant to the evaporator in
29. If the high-pressure switch on the case the automatic valve fail
compressor opens and stops the compressor, a D. bypass the compressor
possible cause could be:
A. too much cooling water going through the 36. Frost on the outside of the thermal
condenser expansion valve maybe caused by:
B. no enough refrigerant in the system A. air in the system C. moisture in the system
C. a leak in the evaporator coils B. too much superheat D. any of the above
D. no enough cooling water going through the
condenser 37. The charging valve is located between the:
A. king valve and expansion valve
30. The capacity of the refrigerating unit can be B. receiver and the condenser
regulated by: C. compressor and the receiver
A. changing the speed of the compressor D. evaporator coils and the compressor
B. changing the amount of cooling water to the
condenser 38. A high suction pressure and a cold crankcase
C. changing the amount of the refrigerant in the indicate:
system A. air in the system
D. any of the above B. leaky suction valves
C. expansion valve open too wide
31. Which of the following would not cause high D. B or C
suction pressure?
A. insufficient refrigeration 39. A high temperature in the icebox could not
B. leaky suction valves be caused by:
C. expansion valve stuck open A. insufficient refrigerant
D. suction valve not adjusted properly B. air in the system
C. expansion valve open too wide
32. A device used to keep moisture from D. too much refrigerant in system
passing through the system is called a:
A. humidifier C. dehydrator 40. When securing a Freon system for repairs:
B. aerator D. trap A. pump down to 1 or 2 pounds pressure
B. pump down to a slight vacuum
33. If a compressor runs continuously, the cause C. pump down to 10 to 15 pounds pressure
might be a: D. remove all refrigerant from system
A. defective thermal valve
B. clogged scale trap 41. The solenoid valve is located between the:
C. stuck high-pressure switch A. scale trap and the thermal expansion valve
D. Stuck low-pressure switch B. thermal expansion valve and the evaporator
C. king valve and the scale trap
34. Dairy products should be kept at a D. automatic and manual expansion valves
temperature of:
A. 10 to 20 C. 35 to 45 42. When starting s refrigerating system,
B. 20 to 30 D. 15 to 25 always:
A. vent the condenser
35. The purpose of the expansion valve bypass B. vent the evaporator
is to: C. bypass the condenser
A. increased the efficiency of the plant D. none of the above
43. Before securing a compressor to do
maintenance work on it, be sure to: 52. Too much oil in the compressor would:
A. have gas mask handy A. absorb too much refrigerant from the system
B. notify the captain B. damage the expansion valve
C. make arrangements to have perishables C. cause leakage through the shaft seals
taken care of D. deposit oil on the condenser tubes
D. A and C
53. The refrigerant with the lowest boiling point
44. 212F is equal to: is:
A. 106C B. 110C C. 100F D. 100C A. NH3 B.CO2 C. F12 D. F22

45. A good refrigerant should: 54. A ton of refrigeration is equal to the


A. have a low boiling point removal of:
B. have a higher latent heat A. 288,000 BTU per 24 hrs
C. be able to be liquefied at normal sea-water B. 28,000 BTU per 24 hrs
temperatures C. 28,800 BTU per 24 hrs
D. all of the above D. 280,000 BTU per 24 hrs

46. 140F is equivalent to: 55. Which of the following would cause a high
A. 50C B. 60C C. 40C D. 55C suction pressure?
A. expansion valve not open enough
47. 70C is equivalent to: B. expansion valve open too wide
A. 150F B. 160F C. 158F D. 155F C. king valve not open wide enough
D. dirty dehydrator
48. Low suction pressure is caused by:
A. air in the system 56. Which of the following would cause high
B. leaky compressor suction valves head pressure?
C. solenoid valve not functioning properly A. dirty dehydrator
D. expansion valve causing flooding back B. insufficient cooling water
C. air in the condenser
49. The charging connection in a refrigerating D. all of the above
system is located:
A. before the receiver 57. Which of the following would cause low
B. between the condenser and the receiver head pressure?
C. between the receiver and the king valve A. too much cooling water
D. between the king valve and the solenoid B. insufficient refrigeration gas
valve C. insufficient cooling water
D. A and B
50. If there is too much Freon in the system:
A. the compressor will short cycle 58. The principle of mechanical refrigeration is:
B. the compressor will run continuously A. the absorption of temperature under heat,
C. the safety valve will discharge pressure, compression, and expansion
D. it will mix with the oil in the crankcase B. the compression of a liquid under
temperature and expansion
51. A refrigerating unit of 1 ton capacity can C. the absorption of heat under temperature,
remove: compression, pressure, and expansion
A. 500 BTUs per min C. 200 BTUs per min D. the conversion of a liquid to a gas
B. 288 BTUs per min D. 100 BTUs per min
59. The function of the expansion valve is to: 66. The purpose of the dehydrator is to:
A. change the high-pressure liquid to a low- A. remove oil from the refrigerant
pressure liquid B. add more refrigerant to the system
B. regulate the amount of liquid refrigerant to C. remove moisture from the refrigerant
the expansion coils D. remove moisture from the crankcase oil
C. change the gas refrigerant to a liquid
D. shut off the flow of refrigerant to the 67. Which of the following would you apply if a
condenser person got Freon on his eyes?
A. soapy water C. clean water
60. The oil separator (trap) is located between B. sterile mineral oil D. sodium bicarbonate
the:
A. compressor discharge valve and the 68. The thermal expansion valve is located
condenser between the:
B. condenser and the receiver A. receiver and the king valve
C. receiver and the king valve B. king valve and the solenoid valve
D. receiver and the expansion valve C. solenoid valve and the evaporator coils
D. charging valve and the solenoid valve
61. The purpose of the oil trap is:
A. to remove oil from the charging tank 69. The thermal expansion valve:
B. to add oil to the compressor A. controls the amount of gas coming from the
C. to remove oil from the refrigerating gas dehydrator
D. none of the above B. maintains a constant superheat of gas leaving
the evaporator coils
62. The boiling point of the ammonia at C. controls the amount of gas going to the
atmospheric pressure is: receiver
A. -28 C. B. +28 C. C. +28F. D. -28 F. D. removes trapped oil from the refrigerant

63. The boiling point of CO2 at atmospheric 70. Water in the refrigerant is liable to:
pressure is: A. freeze on the expansion valve seat and cut
A. +110F. B. -110F. C.+110C. D.-110C flow of the liquid refrigerant
B. emulsify the oil in the compressor
64. The boiling point of Freon at atmospheric C. freeze in the king valve
pressure is: D. clog the oil trap
A. -22F. B. +22F. C.+22C. D. -22C.
71. The purpose of the scale trap is to:
65. The dehydrator is located between the: A. control the amount of the scale going to the
A. receiver and the king valve compressor
B. receiver and the expansion valve B. remove insoluble gases from the refrigerant
C. condenser and the king valve C. remove dirt, scale, and metal chips from the
D. condenser and receiver refrigerant
D. dissolve scale and dirt in the system
66. The purpose of the dehydrator is located
between the: 72. A double-seated valve allows the valve to
A. receiver and the king valve be:
B. receiver and the expansion valve A. packed only in the closed position
C. condenser and the king valve B. packed in wide open or closed position
D. condenser and receiver C. operated as suction or discharge valve
D. removed for replacement without shutting C. the CO2 will come out in liquid form
down D. pumped out with a suction pump

73. Sensible heat: 80. How is a Freon system purged?


A. can be measured with a thermometer A. the same as the ammonia system
B. cannot be measured with a thermometer B. the same as the CO2 system
C. changes in the receiver tank C. back to the extra supply bottle
D. increases with the cold D. with a reefer pump

74. The latent heat of fusion is the amount of 81. The solenoid valve is:
heat required to convert: A. a pressure-controlled stop valve
A. 2 lbs. of ice at 32F to 1 lb. of ice at 32F B. a Freon-controlled check valve
B. 1 lb. of ice at 32F to 1 lb. of water at 32F C. a temperature-controlled stop valve
C. 1 lb. of ice at 32F to 1 lb. of steam at 32F D. none of the above
D. 2 lbs. of ice at 32F to 1 lb. of water at 32F
82. The latent heat of fusion of ice is:
75. The latent heat vaporization of water is: A. 144 BTU B. 188 BTU C. 940 BTU D. 500 BTU
A.144 BTU B. 940 BTU C. 970 BTU D. 288 BTU
83. Latent heat:
76. The latent heat vaporization is the amount A. can be measured with a thermometer
of heat required to convert: B. can be measured with a pyrometer
A. 1 lb. of water at 212F to 1 lb. of steam at C. cannot be measured with a thermometer
212 F D. changes as the refrigerant cools
B. 1 lb. of water at 180F to 1 lb. of steam at
180 F 84. Absolute zero is:
C. 2 lbs. of water at 212F to 1 lb. of steam at A. 970 below 0 on the Fahrenheit scale
212 F B. 460 below 0 on the Fahrenheit scale
D. 1 lb. of ice at 32F to 1 lb. of steam at 212F C. 144 below 0 on the Fahrenheit scale
D. the same as 0 on the Centigrade scale
77. Too high suction pressure could be caused
by: 85. When the evaporator coils are located in
A. expansion valve open too wide the icebox, the system is unknown as a:
B. leaky suction valves A. direct system
C. expansion valve bulb not working properly B. low-pressure system
D. any of the above C. indirect system
D. high-pressure system
78. How is an ammonia system purged so that
the operator will not be overcome by the 86. The amount of CO2 of Freon in a cylinder is
fumes? measured by:
A. into the atmospheric line A. pressure C. weight
B. into a bucket of water B. volume D. psi
C. into a bucket of lube oil
D. back into the compressor 87. An excessively high head pressure could be
caused by:
79. How is a CO2 system purged? A. solenoid valve shutoff
A. when CO2 comes out, frost will form on a B. insufficient cooling water to the condenser
piece of metal held near the outlet coil
B. through the king valve
C. insufficient cooling water to the evaporator D. suction valve not open enough
coil
D. too much cooling water to the condenser 95. The high pressure side of the system is
sometimes referred to as the:
88. The solenoid valve is controlled by: A. suction side
A. the amount of liquid in the system B. cold side
B. the amount of gas In the system C. hot side
C. the temperature in the condenser D. filling side
D. the thermal switch operated by the icebox
temperature 96. A ton of refrigeration is equal to the cooling
effect of :
89. The purge valve is located: A. 2000 lbs. of ice melting in 24 hours
A. in the lowest part of the system B. 2000 lbs. of ice melting in 12 hours
B. in the highest part of the system C. 2000 lbs. of water being converted to ice
C. on the receiver discharge D. 2240 lbs. of ice melting in 24 hours
D. on the evaporator coil
97. The scale trap (liquid strainer) is located
90. The system should be purged: between the
A. while the system is operating A. compressor and oil separator
B. while starting up the system B. king (liquid ) valve and expansion valve
C. after the system has been shut down for a C. expansion valve and evaporator coils
few hours D. evaporator coil and compressor
D. once a week
98. When there is a Freon leak, the halide torch
91. The function of the compressor is to: will burn :
A. pulls the refrigerant gas through the system A. orange
B. increase the pressure of the refrigerant B. blue
C. discharge the refrigerant to the condenser C. white
D. all of the above D. green

92. The expansion valve is located between the: 99. Which of the following could be used to
A. receiver and evaporator check a leak in an ammonia system?
B. evaporator and compressor A. litmus paper
C. compressor and condenser B. halide torch
D. condenser and receiver C. sulphur stick
D. A and C
93. If frost forms on the cylinder, the cause
would be: 100. Valve and piping in an ammonia system are
A. expansion valve not open wide enough made of:
B. charging valve left open A. iron
C. expansion valve open to wide B. Brass
D. dehydrator not working properly C. copper
D. bronze
94. Which of the following would cause high
head pressure? 101. In an ammonia system, the oil gauge must
A. icebox door left open be kept:
B. Insufficient cooling water A. closed except when checking oil level
C.Too much cooling water B. open at all times
C. closed when machine is shutdown 108. A sulphur stick burning in the presence of
D. open when machine is shutdown ammonia will give off a :
A. dense yellow smoke
102. Freon is : B. dense whit smoke
A. colorless C. dense red smoke
B. odorless D. dense green smoke
C. nonpoisonous
D. All of the above 109. If the compressor were to run continuously
without lowering the temperature, the trouble
103. Which of the following gasket materials would probably be:
should be used on a Freon system? A. insufficient refrigerant in the system.
A. Metallic B. leaks
B. asbestos C. leaky discharge valve
C. rubber D. any of the above
D. A and B
110. Ammonia leaks in the condenser can be
104. A double pipe condenser has: detected by:
A. two piping systems side by side, one with A. smelling the discharge water
cooling water one with refrigerant B. applying litmus paper to the circulating water
B. a small pipe inside a larger pipe, the cooling discharge
water passing through the small pipe and the C. adding oil of peppermint to the system and
refrigerant through the large pipe. tracing the smell
C. two pipes for cooling water and one for the D. applying a soapy mixture to the condenser
refrigerant heads and looking for bubbles
D. none of the above
111. When purging an ammonia condenser into
105. air can be prevented from getting into the a bucket of water, one can tell when the air is
system by: out and ammonia starts to come through by
A. keeping all glands and stuffing boxes on the the:
high pressure side type A. smell of ammonia being liberated from the
B. keeping the dehydrator clean at all times water
C. keeping all glands and stuffing boxes on the B. color of the water turning green
low pressure side type C. color of the water turning bluish
D. running the refrigerant to an aerator D. change of the bubbling sound of air to the
crackling sounds of ammonia
106. the agent used in an indirect reefer system
is: 112. Large leaks in a Freon system cannot
A. sodium chloride always be detected with halide torch because it
B. potassium chloride changes color with the slightest amount of
C. calcium chloride Freon present. A large leak can be detected
D. A and C easier by applying
A. sheets of litmus paper to all joints and watch
107. An Ammonia leak will turn litmus paper : for the color change
A. blue B. a soapsuds solutions, mix with a little
B. red glycerine to hold the solutions together, and
C. green watch for the bubbles
D. yellow C. a thin layer of mineral oil to all joints and
watch for bubbles
D. a lighted candle at the joints and watching A. lack of refrigerant
for leaky spots blowing candle flame B. dirty traps and strainers
C. too much frost on coils
113. When the evaporator coils are located in a D. any of the above
brine solution and the brine is pumped through
the icebox, the system is known as: 120. Ammonia will corrode:
A. a direct system A. copper B. bronze C. brass D. all of the above
B. an indirect system
C. a low-pressure system 121. The dehydrating agent in Freon system is
D. a double-evaporator system usually:
A. slaked lime C. activated alumina
114. Obstruction of the expansion valve is B. sodium chloride D. calcium chloride
usually caused by:
A. congealed oil in the system 122. If any of the electrically controlled devices
B. scale in a Freon system malfunction, which of the
C. water in the system following valves will also automatically shut off?
D. all of the above A. king valve
B. expansion valve
115. Too low suction pressure could be caused C. solenoid valve
by: D. condenser cooling-water inlet valve
A. dirty scale traps
B. shortage of refrigerant gas 123. Many pressure gages on a Freon system
C. too much oil in the system have two dials or graduations on one gage. The
D. any of the above two dials represent:
A. pressure and temperature
116. If an electrically operated compressor B. liquid pressure and gas pressure
failed to start, the cause might be: C. suction and discharge pressure
A. an open switch D. cooling-water inlet and outlet temperatures
B. a blown fuse
C. burned-out holding coils in solenoid valve 124. A leaky discharge valve can usually be
D. any of the above detected by:
A. a fluctuating high-pressure gage
117. The oil separator is located between the: B. a drop in icebox temperatures
A. evaporator and the compressor C. a discharge pressure lower than normal
B. compressor and the condenser D. any of the above
C. condenser and the dehydrator
D. solenoid valve and the thermal expansion 125. The suction pressure in a Freon system
valve should be:
A. the pressure which corresponds with a
118. To help a person who had been temperature about 20F. below the
overexposed to ammonia gas, one would: temperature of the icebox
A. apply artificial respiration B. the pressure which corresponds with a
B. wrap in warm blankets temperature equal to the temperature of the
C. apply could compresses icebox
D. douse with cold water C. the pressure which corresponds with a
temperature about 20 above the temperature
119. If the compressor short-cycles on the low- of the icebox
pressure cutout, the trouble might be: D. none of the above

Anda mungkin juga menyukai